Download as pdf or txt
Download as pdf or txt
You are on page 1of 65

GUIDE TO CAPACITY SELECTION

AND INSTALLATION PLANNING

Installation Planning

February 2010
Pub. No. 98CAB-61000
Installation Planning

Installation is the most expensive in the power facilities, determines the performance of
engine-driven unit and gain or loss with its operation and maintenance, and can affect the
environment. Global perspective and careful planning is therefore required for installation.
Ventilation and noise are closely connected to the structure of engine room or package.
They are the significant factor in the performance of engine-driven unit and auxiliary
equipment and operator environment, and have a great influence on the installation
planning. For details, see Chapter 2 and 3.
CONTENT

Chapter 1
Planning
3. Ventilation air volume .....................31
1. Engine room .....................................1 3.1 Combustion air ...........................................31
1.1 Function ........................................................1 3.2 Cooling air ..................................................33
1.2 Arrangement .................................................1 3.3 Supply air quantity ......................................35
1.3 Maintenance .................................................3 3.4 Discharge air quantity.................................35
1.4 Ventilation .....................................................4
4. Ventilation resistance .....................36
1.5 Mounting system...........................................5
4.1 Supply air duct............................................36
1.6 Cooling system .............................................6
4.2 Discharge air duct.......................................42
1.7 Air intake system...........................................8
4.3 Ventilation resistance .................................46
1.8 Exhaust system.............................................9
1.9 Fuel system.................................................10
1.10 Lubrication system ......................................12
Chapter 3
1.11 Venting system ...........................................12
Noise
1.12 Starting system ...........................................13
1.13 Generator system .......................................14 1. Sound property ...............................48
1.14 Operation room ...........................................17 1.1 Sound evaluation........................................48
1.2 Distance decay ...........................................49
2. Outdoor installation.........................17 1.3 Transmission loss.......................................50
2.1 Package ......................................................17
1.4 Reflection....................................................51
2.2 Installation on the ground............................19
1.5 Refraction ...................................................52
2.3 Installation on rooftop..................................21
1.6 Diffraction ...................................................52
2.4 Auxiliary equipment.....................................22
1.7 Interference ................................................53
3. Carry in ...........................................22 1.8 Wind direction.............................................53
3.1 Carry-in route ..............................................22 2. Noise ..............................................54
3.2 Carrying in during construction ...................24 2.1 Environmental standard..............................54
3.3 Lifting and moving.......................................24
2.2 Noise source...............................................55
4. Layout Drawing (Top) .....................25 2.3 Transmission route .....................................55
5. Layout Drawing (Side) ....................26 2.4 Measurement and evaluation .....................56
3. Noise reduction...............................57
Chapter 2 3.1 Frequency analysis.....................................57
Ventilation 3.2 Vibration isolation .......................................58
3.3 Sound absorption .......................................58
1. Plan ................................................27 3.4 Sound insulation .........................................58
1.1 Ventilation opening .....................................27 3.5 Silencer.......................................................59
1.2 Air-supply/Air-discharge opening and fan ...28
2. Requirement ...................................30
2.1 Combustion.................................................31
2.2 Cooling........................................................31

Content - 1
Chapter 1 Planning

Engine room and package must meet the 1.1 Function


requirements for the maintenance and Engine room must not only meet the
operation of engine-driven unit. requirements specific to the equipment
Meanwhile, in installing them, such as generator set, pump-driven unit,
the environmental impact of noise, and cogeneration facilities, but also have
vibration, and exhaust gas emission must all the basic functions.
be kept to a minimum. Engine room must have engine-driven unit
In conclusion, the contradictory issue of and auxiliary equipment required for its
quiet and ventilation must be overcome. operation and meet the operation
Careful study is therefore required for requirements to offer the expected
installation planning. performance. Meanwhile, it must keep the
influence of noise, vibration, exhaust gas,
1. Engine room and combustion blow-by to a minimum to
In this chapter, engine room means the protect the environment around the
room in the building for engine-driven unit installation location. The engine room floor
and auxiliary equipment or the building in must be water-tight to prevent leaked oil,
the common use. And, package means fuel, or coolant from penetrating ground.
the engine-driven unit equipped with For fire, fire alarm apparatus, fire
enclosure that is called bonnet or cubicle. extinguishing equipment, and fire
Package is like the small-sized engine extinguishers [1] must be arranged
room, so almost all the requirements that according to the Fire Defense Law.
are described in this section are applied to The packaged engine-driven unit must
package. have the function like engine room in
Rooftop engine room may transmit limited size and control ambient noise.
vibration in the building structure. In this In planning the packages, therefore, noise
case, consult with the expert to study the and ventilation is the leading challenge.
building strength, make the response The engine-driven unit designer must
analysis, and plan to use the special design its enclosure that meets the above
vibration isolator in advance. requirements. In all of these packages, the
The standard engine room that can be correct heat balance of engine is the first
applied to all the installation places cannot and foremost priority.
be designed. Then, the layout of the 1.2 Arrangement
typical engine room that meets the basic
The arrangement of engine-driven unit,
installation requirements is shown in
auxiliary equipment, piping, operation
Fig. 1-5 and Fig. 1-6. Note that,
room, cable lines in the engine room has a
hereinafter, the numbers in angle bracket
great impact on its installation and
(e.g. [1]) denotes the equipment by the
performance.
arrow from the encircled numbers in
Fig. 1-5 and Fig. 1-6.

1
Chapter 1 Planning

1.2.1 Service entrance given to the arrangement plan of auxiliary


Service entrances [2] must be arranged so equipment and piping.
that engine-driven unit and auxiliary 1.2.3 Control panel
equipment can be carried in the engine
Control panels [9] should be arranged in
room from passageway easily. In door
the engine room for the daily check and
sizing (height and width), some cases such
emergency procedure of engine-driven
as carrying them without disassembly and
unit. However, this requirement varies
using carriages or rollers must be
depending on the operation.
assumed.
When the panels are placed in the
And, incoming or outgoing of heavy
operation room [10], soundproof glass
machinery for major overhaul of engine-
windows [11] must be arranged there to
driven unit and auxiliary equipment must
see the engine room. And, the emergency
be also considered. Otherwise, the engine
stop devices [12] must be arranged in the
room walls must be broken or the
engine-driven unit or near it for emergency.
segmentalized carry-in and on-site
The temperature around the control panels
assembly must be adopted. In this case,
should be -5 to 40°C and the relative
the unit is once disassembled after the final
humidity should be 45 to 80% for
test in the factory, shipped, and then is
condensation prevention. For this
assembled in the engine room, which
purpose, the operation room must use its
involves much cost and man-hour for
ventilation or air conditioning system to
mounting.
keep the panel conditions through the year.
1.2.2 Auxiliary equipment
1.2.4 Ventilation opening
Auxiliary equipment required for the
Ventilation air inlets [13] must be arranged
operation of the engine-driven unit contain
in the engine room so that dust, rain, snow,
remote mounted radiators [3], heat
or exhaust gas cannot enter the engine
exchangers [4], cooling tower, fuel day tank
room from outside.
[5], oil tank [6], exhaust silencers [7],
In general, low-temperature air is sucked in
exhaust gas boilers [8], and water heater.
near the ground. However, note that intake
The auxiliary equipment should be
air may be heated by the ground warmed
arranged near the engine-driven unit.
with direct sunlight, depending on
Otherwise, pressure loss, back pressure,
installation place. And also, considerably
or static head will be increased. Then,
heavy particles such as dust, raindrops,
circulating pumps with more capacity and
accumulated snow, fallen leaves, and
large silencers which involve extra
seeds may be sucked in near the ground.
installation cost will be required. On the
Ventilation air outlets [14] must be
other hand, enough space to carry the
arranged so that discharge air cannot
large components of engine, generator,
cause environmental harmful effects and
and auxiliary equipment easily for major
foreign objects cannot invade.
overhaul is required in the engine room.
Therefore, sufficient consideration must be

2
Chapter 1 Planning

Noise in the engine room may be 1.3.2 Stool


transmitted outside from ventilation air Stools with footstep [17] must be installed
inlet/outlet solely through ducts [15, 16], in one side at in-line engine or in both sides
affecting the ambient environment. Noise at V-type engine, for daily check and
transmitted through ventilation opening maintenance of tall engine.
must be within the noise control standards The stool must be able to be moved or be
at the boundary with the adjacent land. disassembled easily to ensure the place to
Daytime and nighttime noise levels may be put engine and driven equipment in major
limited in each district such as residence, overhaul.
industry, and commerce, according to the
1.3.3 Overhead lifting device
local ordinance. For the ordinances, refer
to the local government in the installation Usually "I" or "H" beams [18] and movable
site for noise regulation. overhead lifting devices [19] must be
In general, in the package enclosure, installed in ceiling to move and lift heavy
acoustic materials should be applied to the load in equipment maintenance.
panel to attenuate noise from engine, Sufficient vertical clearance must be made
radiator fan, etc, and silenced air inlet/ between overhead lifting device in ceiling
outlet should be arranged for noise control. and engine to pull out piston, connecting
In the engine room for standby generator rod, or cylinder liner from cylinder block
set, ventilation openings must meet the (See the maintenance manual of specific
Fire Defense Law in Japan. And, their model).
holes must be small enough to prevent 1.3.4 Service elevator
round rod with diameter of 10 mm from Service elevator must be installed between
passing through. So, usually, the the aboveground floor and the engine room
ventilation openings are covered with in the underground which has no dry pit,
appropriate wire mesh. machine hatch, or slope.
1.3 Maintenance And, service elevator and passage for
carriage must be arranged to carry the
1.3.1 Space precision parts of an engine in factory for
The space for putting dismounted engine maintenance.
or generator is required in the side of
1.3.5 Power source
engine-driven unit. The distance for pulling
Power supply for tools, and if possible,
out camshaft is required between the front
compressed air supply must be arranged in
of engine and wall. The workspace for
the engine room. Piping branching from
pulling out rotor shaft and replacing rear
the outlet of air tanks [20] or air
bearing, intake air filter, etc. is required in
compressors [21, 22] for engine start-up
the rear of generator.
should be also studied.
Exchange of engine filters for fuel, oil, and
intake air cleaner requires sufficient
workplace in the surrounding.

3
Chapter 1 Planning

And, piping for water supply must be And, vacuum in the engine room created
arranged to fill the cooling system with by air discharging can be used to suck in
coolant in test runs after mounting of required quantity of supply air.
engine-driven unit or after overhaul. However, to maintain the radiator heat
In general, hose can be used for water dissipation capability, the intake air inlet
supply to radiator. However, piping that can keep vacuum in the engine room
exclusively for water supply to expansion to 100 Pa (10 mm H2O) or lower and the
tank is useful. radiator duct and discharge air outlet that
can keep resistance to 50 Pa (5 mm H2O)
1.4 Ventilation or lower must be designed carefully.
Ventilation influences engine intake air, the The pressure in the engine room acts on its
performance of cooling system, driven door. For example, applying 100 Pa
equipment, and auxiliary equipment, and pressure can create about 100 N force on
human activities.
a door 1 m wide and 2 m high. Pressure
Ventilation must be designed so that the difference between room inside and
engine-driven unit can meet the installation outside may prevent the door from opening
requirement (See Chapter 2, "Ventilation"). and closing or open and close the door
The heat balance test of the engine-driven automatically. So, the door design should
unit must be performed with the doors and be taken into consideration in designing
windows of the engine room closed the ventilation system.
according to the design by the time when it
Supply air quantity for ventilation can be
is put into operation.
reduced to adjust room temperature at the
1.4.1 Ventilation air volume cold season. In this case, however, the air
Ventilation air volume is the total amount of for radiator cooling and engine combustion
combustion air in an engine and cooling air must not be reduced. As long as heat
in the engine-driven unit and auxiliary balance is kept in the engine, the radiator
equipment, etc. The supply air cooling air can be reduced, depending on
temperature must meet the environmental the supply air temperature.
conditions of the engine room. Electric drive ventilation fans [23] are used
When the engine room temperature cannot to adjust the temperature in the engine
be kept in summer by ventilation alone, air- room. In this case, it is more economic to
conditioner may be required. In this case, control the operations of two or more fans
cooling media such as Freon and depending on room temperature than to
Ammonia must not be sucked in to the install one large fan.
engine. Otherwise, they will form hydrogen On any temperature condition, intake air
chloride, hydrogen fluoride, and nitrogen quantity required for engine combustion,
oxide in the combustion chamber. radiator heat dissipation, and cooling of
The radiator in the engine-driven unit can engine-driven unit and auxiliary equipment
be used to discharge air from fan to must be maintained.
outdoors thorough the radiator duct.

4
Chapter 1 Planning

1.4.2 Ventilation method MHI does not recommend the movable


When the cooling air temperature of louver using discharge pressure of the
generator exceeds the standard maximum radiator fan, because it is not very
temperature of 40°C, the generator power trustworthy. If it is not opened, engine will
output will be restricted. Therefore, fresh be overheated.
air must be supplied from outdoors to the
1.5 Mounting system
cooling air inlet of the generator.
In general, air supply openings [24] should 1.5.1 Subbase and foundation
be arranged in the lower position at the The subbase must have enough
rear of generator. Also, air-discharge compressive strength to support the weight
openings [25] should be arranged in the of the foundation [26] and engine-driven
higher position at the front of engine. unit in operation, concretely, at least 10
Positive pressure or slight vacuum is ton/m2 (soil bearing capacity). Otherwise,
desirable in the engine room to increase soft ground may sink under their load.
the air cleaner life. In cold regions where the ground may
MHI recommends arranging the blower fan freeze in winter, the ground must be
in the air supply side in using the electric- excavated more deeply than the frost line,
driven ventilation fan. for constructing the subbase.
In general, engine mounted radiator is The foundation must have enough mass to
used for the cooling system in the package dampen vibration transmitted from the
generator set. In this package, outside air engine-driven unit. The foundation mass
enters the generator rear, passes through can be calculated based on the wet weight
the radiator, and then is discharged. of the unit. The foundation must have
The ventilation opening size is often space of 200 to 300 mm around the
restricted to control ambient noise, which mounting surface of the common bed.
limits the amount of outside air supplied to
1.5.2 Mounting
the package. So, the intake air is usually
In general, vibration isolators [27] should
heated about 10°C until it reaches the
be arranged to the engine-driven unit in the
radiator.
underground or basement to prevent the
Movable louvers can be attached to the
transmission of harmful vibration and
ventilation air inlet or outlet for temperature
decrease the foundation mass.
adjustment in engine room or package.
Base plates [28] must be put on the
However, the movable louvers may not
foundation to make the mounting surface
operate due to their freeze or corrosion,
flat and distribute the load of vibration
depending on the installation environment.
isolators on the foundation.
Their mechanism should use motive
energy such as electricity, air pressure, In the engine-driven unit in the lower
and oil pressure. And, their opening and vibration isolation system, shims, etc.
closing should be controlled with radiator must be used to adjust the height of the
coolant temperature or engine room vibration isolators in operation to share all
temperature. the load of vibration isolators.

5
Chapter 1 Planning

For the MHI engine-driven unit, the For the remote mounted engine-driven
maximum difference in the height of the unit, alignment between engine and driven
vibration isolators must be 2 mm for the equipment may be changed during
spring type or 1 mm for the rubber type. shipping and mounting.
Therefore, proper flatness must be Therefore, check the alignment and adjust
specified in the mortar grouting drawing centering as required before test runs.
applied to the mounting surface, in When the engine that was stored for long
planning the foundation. time is mounted, take necessary steps
In Japan, the quake-resistance standard before starting the engine. For the engine
for the electrical power facility is stored over three months, the measures for
established according to the Building Code long-term storage such as anti-corrosion
and Fire Defense Law. Anchor bolts and and opening sealing are taken according to
other mounting fixtures for generator set the operation manual. Therefore, before
and driven equipment must have enough starting the engine, it must be inspected
strength to support the reference and lubricated and materials for storage
earthquake intensity (G). must be removed.
The generator set with the vibration
isolation system must have the restraint 1.6 Cooling system
mechanism to restrict its vertical and 1.6.1 Installation condition
horizontal movement according to the Equipment that requires daily observation
quake-resistance standards. Otherwise, and check and periodic maintenance and
the generator set may resonate with the exchange must be arranged in the position
seismic wave to amplify earthquake lower than human eye level.
vibration. The equipment may contains heat
Relative displacement is created among exchanger, circulating pumps for hot water
the unit connections, piping, and cabling [29], pressure gauges, flow meters and
supported by the building structure, heat meters for the cogeneration facilities.
because the natural frequency and When heat transfer equipment is arranged
response to earthquake are different above engine, static head is applied to
between the buildings and units. jacket water pump by coolant. In this case,
Therefore, the joints, piping, and cabling the static head is the maximum coolant
must be checked for damage in the range level in the equipment from the pump shaft
limited by the restraint mechanism of the center.
generator set.
For the MHI engines, the static head must
Sufficient clearance must be provided not exceed 10 m to prevent coolant
between the anchor bolts and the bolt leakage from the pump seal. Otherwise, a
holes in the feet of the high-temperature decompression tank must be arranged in
auxiliary equipment in operation such as the midstream of the circuit and coolant
exhaust gas boiler and silencer so that the must be fed from the tank to the heat
thermally-expanded feet can slide. transfer equipment with circulating pump.

6
Chapter 1 Planning

When the heat transfer equipment is The total volume of tank should be at least
installed outdoors, strong wind will roll back 15% of the total coolant amount held in
discharge air from the outlet to reduce fan engine, heat transfer equipment, and
performance, thereby decreasing heat piping. Expansion volume must be at least
dissipation. 5% of the total coolant amount in the
When strong wind hits remote mounted system.
radiator or cooling tower, the hot air or high For remote mounted radiator, top tank with
humidity air discharged from the outlet can enough volume to cover the expansion
return through the inlet opening volume of coolant in the entire system
(recirculation). This recirculation consisting of radiator and piping must be
phenomenon will decrease heat dissipation mounted. Otherwise, an expansion tank
capability. Discharged air recirculation must be installed higher than the highest
tends to occur particularly in the multiple coolant level in the radiator.
remote mounted radiators arranged close In this case, the volume required for the
to each other. In this case, the preventive expansion tank varies depending on the
measures such as partitioning should be installation location or the structure of the
taken. remote mounted radiator. In fact, the
The cooling fan of heat transfer equipment expansion tank must have enough volume
generates noise. Therefore, noise to cover shortage in volume of the top tank
attenuation must be applied, depending on in the radiator. Or, the expansion tank
the installation location and ambient must have volume corresponding to 15%
environment. of the total coolant volume. Pressure cap
In cogeneration facilities, cooling water attached to the top tank must be removed
quality used in the process water and the radiator must be sealed fully.
(secondary circuit) must be researched in 1.6.3 Piping
advance. The components of tap water
It is likely that piping is arranged in higher
vary depending on the region, because
position for well-organized floor. However,
various materials are dissolved in its
piping in the lower position makes system
source (river or lake). Typical hard water,
checking and maintenance easy.
particularly well water, may form scale in
The engine coolant piping and secondary
water heater or heat exchanger, so it
hot water system should be arranged near
cannot be used unconditionally. In this
floor in accordance with heat exchanger.
case, water quality may have to be
Using piping trench [31] makes the floor
adjusted with continuous blow-down or
flat and walking ease and ensures the
chemicals feeder.
space for maintenance.
1.6.2 Expansion tank The inside of pipes must be cleaned up
Expansion tanks [30] must be installed in before an engine-driven unit is put into
the highest position in the cooling system. operation. Flexible joints [32] must be
attached to the connection with an engine
to isolate vibration.

7
Chapter 1 Planning

Gate valves [33] such as butterfly valve For the MHI engine-driven unit, the
must be arranged in the piping such as permissible ambient temperature is 40°C
engine inlet/outlet and the connection with and the permissible temperature of intake
heat exchanger, circulating pump, three- air is 50°C. However, when the
way valve, and expansion tank to minimize temperature of intake air exceeds 40°C,
coolant drained in equipment overhaul or available power may be limited in
assembly/disassembly. accordance with the specification sheet,
Drain valves must be arranged in depending on the temperature and
appropriate positions so that coolant can installation altitude above sea level.
be drained through hose or piping. And, For the engine that is installed in the
drainage trench [34] or drip pan should be position higher than 1,500 m above sea-
installed to collect coolant leaked from the level, available power is lower regardless
connection. Environmental pollutants such of intake air temperature.
as coolant and water mixed with fuel or oil Vacuum of intake air in an engine is
in drainage trench must be collected on the unavoidable due to the airflow resistance
site and dealt with properly as industry of air cleaner. However, the air intake
waste. system installed outside the engine must
be designed so that the resistance can be
1.6.4 Air venting
as low as possible.
When vent hole is provided in the engine
When an engine is not able to suck in
jacket water and intercooler system, vent
sufficient air quantity at ordinary
line must be connected to an expansion
temperature from engine mounted or
tank.
remote mounted air cleaners [37] in the
Coolant lines for jacket water and
engine room, an intake air inlet can be
intercooler must be straight (without ups
extended to outdoors. In this case, the
and downs) to prevent air trap. Otherwise,
intake air inlet must meet the following
vent lines [35, 36] with continuous upward
requirements.
slope of at least 50 mm per meter must be
ŒBe located in the most low-temperature
installed from air-trapped position to the
position in the surrounding and be able
expansion tank.
to suck in clean air.
1.7 Air intake system ŒNot suck in engine exhaust gas and
Air density decrease due to rise in combustion blow-by or gas discharged
temperature decreases oxygen included in from other burning appliances.
intake air of unit volume to lower engine ŒPrevent intake of rain or snow and be
combustion efficiency. Then, exhaust equipped with louvers or wire mesh.
temperature rises and black smoke and Air intake duct or air intake piping must be
harmful components of exhaust gas designed so that service life of air cleaner
increase due to inefficient combustion, element can be maximized.
which increases fuel consumption and
reduces engine output.

8
Chapter 1 Planning

When the engine equipped with new air Otherwise, simultaneous start and stop of
cleaner operates in the rated output, the all engines must be ensured or fully sealed
initial vacuum must be within 2.9 kPa (300 duct valve that is accompanied by high
mm H2O). Otherwise, the standard air installation cost is required.
cleaner must be exchanged with the larger Exhaust piping should be arranged in as
one. Intake air flex connectors [38] must high position as possible, because it is
be used to the connections between high-temperature and maintenance may
extended air pipe and air cleaner or not be required.
between the engine and the air intake pipe Insulating (heat-retention) material must be
of remote mounted air cleaner to absorb applied to its surface to protect humans
fluctuation created at engine-driven unit in against burn injury.
its starts and stops and vibration in Insulating pipes reduces heat released
running. from the pipes to the engine room, thereby
The inside of pipes must be cleaned up saving ventilation air volume required for
before an engine-driven unit is put into maintaining the room temperature. In the
operation. case of cogeneration facilities, the
maximum amount of heat can be
1.8 Exhaust system
recovered from exhaust gas.
For the MHI engines, the exhaust system
Expansion joints [39] must be attached to
must keep the initial resistance to 5.4 kPa
the engine exhaust outlet to isolate engine
(550 mm H2O) or lower. And, the
vibration and compensate for thermal
resistance in use must be kept 5.9 kPa
expansion. And, fixed pipe hangers [40]
(600 mm H2O) or lower even if back
should be located in the pipes just above
pressure rises for any reason.
the expansion joints to prevent the pipes
Excessive back pressure created at the from expanding thermally to the engine
external exhaust system obstructs side.
discharge of combustion gas and air intake
In supporting the piping top, the expansion
to lower engine combustion efficiency.
joints must be stretched enough to
Then, increase in exhaust temperature and
compensate for thermal growth in
fuel consumption may reduce the engine
assembling them. By doing this, when the
output.
pipes are extended downwards due to
1.8.1 Piping engine running temperature, the expansion
Each engine must have its own exhaust joints will be shrunk to their free length.
system to prevent exhaust gas from engine In any supporting method, the piping must
or boiler in operation from invading idle be restricted firmly. Otherwise, thermal
engine. growth will influence the exhaust outlet in
MHI does not recommend sharing one an engine.
exhaust system for two or more Enough expansion joints to compensate for
engines. horizontal thermal expansion must be
arranged in appropriate positions.

9
Chapter 1 Planning

And, slidable pipe hangers [41] must be Particularly, noise frequency component is
used to support the pipes between the important. Note that low-frequency wave is
joints so that the pipes can be extended likely to be diffracted and transmitted
toward the joints. remotely.
Through-holes of exhaust pipes in wall Some residents may be sensitive to even
must be insulated with sleeves [42], etc. to noise level under regulation value at night
protect the wall against heat and thermal because background noise level is low
expansion of pipes. then. Therefore, when the engine-driven
The equipment, piping, and joints must be unit operates at night in the residence
air-tight to prevent exhaust gas leakage in area, the noise from the outlet must be
the engine room. minimized.
In determining the direction and structure
1.8.2 Exhaust outlet
of the outlet, note that rain invasion into
Depending on the engine conditions,
silencer causes its corrosion.
exhaust gas including smoke and
The horizontal tail pipe may be difficult to
unburned matters may be produced at start
adopt, because it increases exhaust noise
and when load is applied. Therefore,
and concentration of emission on the
exhaust outlets [43] must be arranged in
ground, depending on the surrounding
the place from which no foreign odor or
environment.
black smoke harms surrounding
For the vertical tail pipe, rain caps [44], etc.
residences or facilities, with wind taken into
must be attached to the outlet.
consideration.
Sediment including oil or water in pipes 1.8.3 Drain
may be dispersed from the outlet to the Condensed water must be removed from
surrounding at engine start. So, the flow the drainage hole in the lowest position at
velocity of exhaust gas must be minimized, silencer. The device such as drain traps
and the outlet must be arranged in the [45] must be attached to drainage pipe to
place from which no sediment is dispersed prevent discharge of exhaust gas.
to the surrounding facilities such as parking
area. 1.9 Fuel system
Tray for collecting mist including oil or Main fuel tanks [46] are usually installed
water may have to be placed under the outdoors. So, when the tank is far away
outlet with the fence around it. from an engine-driven unit or there is the
The height, direction, and shape of the large static head in fuel circuit to the tank, a
outlet are related to diffusion of exhaust fuel day tank must be placed in the engine
gas. Therefore, in designing the outlet, the room.
regulations of Air Pollution Control Act, the The fill line to supply fuel from the main fuel
components of exhaust gas in an engine, tank and the overflow line to return extra
etc. must be taken into consideration. fuel to the main fuel tank are connected to
The outlet must meet the noise the fuel day tank.
requirements, like ventilation opening.

10
Chapter 1 Planning

In the portion that contacts with fuel such Therefore, the tank pressure must be kept
as fuel tank and fuel piping, zinc plating, constant by taking in or discharging air.
zinc alloy, or materials including zinc must The vent pipe outlet must be arranged at 4
not be used. Otherwise, impure meters or higher from the ground and away
substances formed with chemical reaction 1 meter or more from openings such as
of fuel and zinc may block fuel filter. window. Otherwise, air discharged from
In the inside of the main fuel tank and fuel the tank may take fire, because it includes
day tank, periodic maintenance such as evaporated flammable element.
cleaning, sediment removal and repair for Pipe end must be bent at least by 45° to
corrosion, etc. must be performed through prevent rain invasion and be covered with
their access hole. And also, the tanks 40 or more meshes to prevent invasion of
must be drained at appropriate period from spark.
drainage port attached at their bottom, to For the MHI engines, the maximum and
prevent excessive sediment and water negative heads between injection pump
from being accumulated there. and day tank fuel level are specified.
1.9.1 Installation standard In planning and arranging fuel day tank,
fuel level must be taken into consideration.
In Japan, fuel is designated to as hazard
Otherwise, engine oil dilution or engine
material under the Fire Defense Law, and
start failure may occur.
its handling and storage procedure and
In general, injection pump is cooled by
quantity are regulated by the law.
supplied fuel, and fuel absorbs heat and is
The volume and installation location of
injected for combustion. And, extra fuel
tank and the preventive measures of oil
transferred for cooling absorbs heat and is
leakage such as oil spill dam [47] and
returned to fuel tank, where the fuel is
drainage corner [48] must comply with
cooled.
the law.
Fuel day tank must be mounted on the low-
The law is the lowest standard.
temperature place convenient for heat
The prevention measures should be taken,
release. The temperature of fuel (supplied
depending on each installation and
from tank) at the inlet of injection pump
operation. Otherwise, leaked fuel may flow
must not exceed 80°C for general in-line
to river or invade into soil or underground
fuel injection pump and 70°C for high-
water vein, which may develop into
pressured unit injector from a pump
environmental pollution and thereby cause
durability standpoint. Otherwise, a remote-
a major social problem. The problem is
mounted fuel cooler is required.
accompanied by much cost to restore to
original state. 1.9.2 Piping
Vent pipe [49] leading to outdoor air must Each engine must have separate fuel lines
be installed on the fuel day tank in to return extra fuel from fuel injection pump
according with Fire Defense Law. to fuel tank.
When fuel level changes due to fuel supply The fuel lines for supply and return must be
or consumption in engine running, the free connected to an engine with flexible joints.
volume of the fuel day tank also varies.

11
Chapter 1 Planning

The fuel lines must be arranged away from temperature around piping taken into
hot part of engine and exhaust piping to consideration.
prevent fuel leaked in pipe or joint from Oil flows to the engine side with height
igniting. difference between a tank and oil pan.
All the fuel lines are checked for pressure Resistance created at the piping must be
resistance by fire department. Therefore, estimated based on the minimum
holes for air injection and pressure gage temperature in engine room and the
taps should be prepared in appropriate viscosity of used engine oil.
positions. When the tank oil filler is positioned so
The inside of pipes must be cleaned up high, a feed pump and piping should be
before an engine-driven unit is put into installed in a low place to supply oil to the
operation. tank. Generally, for the oil level regulator
which controls the oil level of the engine oil
1.9.3 Fuel water separator
pan, the inlet-pressure limit must be
As a general rule, fuel water separators
confirmed.
[50] must be installed to protect the parts in
The inside of pipes must be cleaned up
the engine fuel injection system.
before an engine-driven unit is put into
Fuel water separator must be arranged
operation.
between fuel transfer pump of engine and
fuel day tank. And, in its arrangement, the 1.11 Venting system
effect of water and impurities in fuel on the Combustion blow-by accumulated in an
engine and piping system must be engine crankcase must be vented to
minimized. prevent high pressure in the crankcase.
Internal pressure in the crankcase caused
1.10 Lubrication system
by back pressure accompanying venting
For generator set operating continuously
must not exceed ±294 Pa (30 mm H2O).
for long time or stand-by use and
Piping should be designed so that pressure
emergency use generator set with
loss outside an engine can be within
extended operating hour, a remote
150 Pa (15 mm H2O).
mounted lubrication system must be
When multiple engines are installed, each
installed so that oil can be supplied to them
engine must have its own vent line.
automatically.
Otherwise, combustion blow-by released
For the oil tank installation, the laws of
from one running engine may enter
hazardous material must be observed, like
another idle engine to damage its inside.
fuel day tank.
Blow-by must not be released directly to an
Oil lines for the tank must be arranged to
engine room and package. Otherwise, an
prevent leaked oil from igniting or firing.
air cleaner element will be clogged early,
And, the vent pipe [51] which has the same
and equipment performance and human
specification as fuel tank must be installed.
health will be impaired.
Tank setting height and pipe size must be
decided with the supply line length and the

12
Chapter 1 Planning

And, combustion blow-by must not be 1.12 Starting system


released to ventilation discharge air duct The MHI engine-driven unit provides two
and chimney. Otherwise, oil content will be types of starting system: electric starting
accumulated to cause fire hazard. system and air starting system.
Combustion blow-by includes oily smoke Battery charge takes long time in
and is combustible. Therefore, basically, comparison with filling starter air tank with
the outlet of combustion blow-by should be air.
located away from hot portion and naked In determining the starting system for an
flame that may cause ignition. engine-driven unit that starts or stops
Blow-by outlets [52] must be structured to frequently, such system characteristics
prevent rain invasion. must be taken into consideration.
Blow-by outlets must be decided with
1.12.1 Electric starting system
equipment arrangement taken into
The electric starting system, which is the
consideration. Otherwise, discharged oily
combination of an electric starting motor
smoke and dripping oily liquid will
using battery and electric control devices,
contaminate surrounding auxiliary
is at least expensive and easy to use.
equipment, causing its failure at worst.
Therefore, all the small/middle sized
Oily smoke separates oil when cooled.
models of the MHI engine are equipped
Therefore, vent lines in engine room must
with an electric starting motor.
have upward slope from an engine or
In principle, the batteries for starting
downward slope to outdoors of at least
engine-driven unit must be arranged near
40 mm per 1 meter to return the separated
the starter to minimize cabling resistance.
oily liquid to the engine or discharge it to
However, places subjected to high
outdoors.
temperature due to engine radiation and
Particularly, the blow-by for gas engine
impaired ventilation should be avoided,
containing much water will change into
because the temperature of battery
gelled liquid to block pipes, when cooled.
electrolyte must be within 30°C and
So, the vent lines for gas engine may need
electrolyte deteriorates severely in 45°C or
to be insulated or kept hot, depending on
higher.
the installation environment.
The circuit resistance between the starter
Drip collectors [53] are located in the
and batteries should be as small as
engine breather outlets or piping outlets in
possible to minimize voltage drop.
order to separate liquid. Oil and oily water
MHI recommends that the total circuit
accumulated there must be collected and
resistance, which consists of conductor
disposed properly. The inside of piping
resistance of battery cables and contact
must be cleaned up before an engine-
resistance at battery switch and cable
driven unit is put into operation.
connecting terminals, be kept to about
0.002 ohm to keep the voltage drop of the
circuit to 1.5 volt or lower.

13
Chapter 1 Planning

1.12.2 Air starting system Drainage devices should be arranged also


Air starting system is applied to the in lower end of pipes. Otherwise, rust on
engine-driven unit to which electric starting valve seat may cause air leakage, which
system is unfavorable (large-sized engine, may lead to failure, e.g., shortened
operation in explosion-proof region, etc.). compressor operation interval.
In the air starting system, the relay of Ideally, sufficiently strong SUS should be
control panel and the valve that operates used for piping.
with air pressure or electricity in the pipe The inside of piping must be cleaned up
line of compressed air are combined to before an engine-driven unit is put into
control its start and stop. operation.
When no compressed air source is able to 1.12.3 Starting aid
be provided or meets the start
When low temperature in the engine room
requirements, compressor and air tank are
or package disturbs engine start, the
required. In general, compressor is driven
measures to aid the start should be taken.
by AC motor with commercial power.
Particularly for standby generator set,
However, depending on the operation
starting aid is required in the seasons
requirements, the engine-driven unit may
except summer of high ambient
have to be started without commercial
temperature.
power (black start). For this operation,
compressor driven by small-sized engine 1.13 Generator system
can be applied.
1.13.1 Control panel
In Japan, The High Pressure Gas Control
Law is applied, depending on used The generator set requires numbers of
pressure. In this case, certified air tanks, panels for operation as described below.
pipes, or equipment may be required. ŒCommon Control Panel that controls the
Therefore, in planning the air starting parallel operation of generator sets and
system, check the related laws of the interconnection with commercial power.
countries or regions where the engine- ŒControl Panels of engine-driven unit.
driven unit is installed. ŒAuxiliary Panel that controls auxiliary
Drainage devices must be attached to the equipment operation.
starter air tank and compressed-air piping ŒDC Power Supply Board that has battery
to discharge condensed water for control power.
accumulated there. Otherwise, The installation location and ventilation
accumulated condensed water corrode must be taken into consideration to prevent
piping and parts in the starting system, the deterioration of electronic parts in the
which may result in failure in engine start panels due to high humidity or
due to air-valve sticking. temperature.

14
Chapter 1 Planning

Condensation is likely to occur in the panel against short circuit. Therefore, in this
in high-humidity engine room. The room case, cabling requires the best of care for
temperature may rise in the engine-driven its route and work.
unit operation, depending on the location, Cabling from the generator output
and the panel temperature lowers after terminals requires flexibility and must be
engine stops, when condensation may supported carefully.
occur. In general, generator set is equipped with
Then, insulation failure may occur at the vibration isolation system. Cabling is
printed circuits of electronic parts, thereby subjected to continual vibration during
causing abnormality in the unit control. engine running and load due to fluctuation
Therefore, the control panels should be in starts and stops. Therefore, cabling
arranged in the operation room whose requires enough flexibility to prevent
temperature is controlled properly, if any. breaking. And, the cabling must be
After cabling work in panel, clearance supported properly to prevent its shield
between wiring opening and cables must from wearing and its core wire from
be fully sealed. Otherwise, if snake, fatiguing.
mouse, or insect invades from there, short Actual load cannot be applied before the
circuit may occur particularly in high- facilities are put into operation. Therefore,
voltage generating system. And, the panel the generator output circuit in basement
door and other openings must be closed as engine room must be ready to be extended
soon as even possible in checking or repair to the ground so that load bank can be
to prevent animals from invading. used in the confirmation test.
For the package-type generator set, There are two cabling method: trench [54]
sucked exhaust smoke and dust are type and rack type. One or combination of
deposited in its built-in control panel and them is used, depending on the installation
circuit breaker, which may disturb heat requirements of engine room. The trench
release to damage equipment and lower type has advantage of smooth floor in the
insulation due to moisture to cause short whole engine room because cabling is laid
circuit. through trenches in a floor. However, the
Anyway, daily checking, periodic cabling should be floated from the bottom
maintenance and cleaning, and insulation of trench. Otherwise, if much oil or water is
resistance measurement must be leaked, the cabling may be sunk.
performed to prevent electric accidents. The rack-type cabling is easy to protect,
because the cabling is laid on shelves
1.13.2 Cabling
supported in overhead clearance with
Cabling from generator output terminals to
columns on a floor, rods suspended from a
circuit breakers must be installed in a safe
ceiling, etc. However, the shelves must be
manner with human and ambient
arranged so that an engine driven unit,
environment taken into consideration.
auxiliary equipment, etc. can be easy to
When breakers are far away from
maintain.
generator, the cabling from output
terminals to breakers cannot be protected

15
Chapter 1 Planning

Once in a long while, control panel may temperature of 40°C, the maximum
malfunction by induced current with parallel generator power output will be restricted.
cabling. So, the engine-driven unit and all Therefore, ventilation must be designed so
the electric devices must be grounded that the supply air temperature near the
properly. cooling air inlet can be as low as possible.
And, control wires in trenches and on racks Air including saline content and corrosive
must be separated from high-voltage gas may deteriorate winding insulation,
cables and power supply cables or thereby causing generator failure. In this
shielded with a separator, and the shelves case, treatments such as special coating
must be grounded appropriately. and insulation enhancement must be
Not only hot areas but also pipes for fuel applied to windings in the manufacturing
and oil must not contact with wires, and the process of generator.
wires must not be tied. Otherwise, melting For the generator sets which are installed
damage and shield wear will cause earth in humid climate or have long stand-by
fault, which may lead to fire. period because they are for disaster
prevention or emergency, space heater
1.13.3 Lighting protection
should be mounted. This heater is the
For the package-type engine-driven unit
built-in electrical heater to prevent
installed outdoors or engine room,
condensation of water vapor by warming
conductor rods must be arranged in
air around winding. The generator set in
appropriate positions to protect the unit
idle state must be controlled so that current
against lightning for its secure operation.
can be always applied to the space heater.
And, the control systems of the engine-
When the factories that manufacture metal
driven unit must be grounded properly.
casting, quarry, and cement, are in the
In the region where lightening occurs
adjacent area, solid foreign objects such as
frequently, consult with the experts to take
powder of crashed stones, cast iron,
the surge measures.
cement or sand, or wood chips may invade
However, in Japan, if commercial power
into an engine room. Abrasive dust wears
fails due to lightening, the generator set
insulation materials of generator.
operating with interconnection opens its
And, deposited powder dust disturbs heat
circuit breaker and stops, when power
release, and, when it absorbs moisture,
feeding to load stops, too. Therefore, in
hydrolyzes insulation materials to lower
order to continue power supply over the
winding insulation. At worst, the generator
long term, the requirement of the black
may burn out because of short circuit.
start that starts the generator set even in
Filter must be installed on the air supply
commercial power failure must be imposed
opening of an engine room or package or
on the generator set. And, the facilities for
the inlet of cooling air in generator to
black start must be installed.
collect foreign objects and clean air.
1.13.4 Generator And, note that the generator equipped with
When the cooling air temperature of filter has its power limit and requires
generator exceeds the standard maximum periodic filter cleaning and exchange.

16
Chapter 1 Planning

1.14 Operation room And, in snow-covered area, the


In partitioning the engine room into countermeasures against snow must also
operation room to station operators there, be taken.
the relevant laws and regulations must be
2.1 Package
observed to maintain the residence
environment, with the impact of noise, In the package-type engine-driven unit,
temperature, or vibration on health taken engine, driven equipment, and auxiliary
into consideration. equipment such as radiator, heat
exchanger, and fuel and oil tank are
Some operation rooms have the control
mounted on the common bed or in
panel, devices, equipment, etc. with built-in
enclosure.
electronic parts. In this case, the ambient
The package is like the small-sized engine
environment must be controlled at a
room, and its function and performance
temperature of -5 to 40°C and at a humidity
specification must meet the installation
of 45 to 85% for condensation prevention
conditions.
throughout the year.
All the doors in operation room must have 2.1.1 Noise
lockable structure and "NO VISITORS" and In general, noise level around package is
"DO NOT OPEN" must be displayed for measured at 1 m from it and 1.2 m from the
prevention of electric shock. ground. Noise level at cooling air inlet/
The clearance in the door or the opening of outlet must be taken into consideration,
ventilation fan in the operation room must because noise inside package is mainly
have its size or structure so that animals transmitted outside from the opening.
cannot invade there. Otherwise, small Acoustic materials should be applied inside
animals or insects may invade into control enclosure to attenuate noise inside the
panel from open door and contact with package. Note that, in Japan, for standby
high-voltage exposed area, thereby generator set, fire-resistant acoustic
causing short circuit. materials must be applied according to the
Fire Defense Law.
2. Outdoor installation In installation site such as hospital area
Only the package-type engine-driven unit that requires quiet surrounding, the double
equipped with enclosure can be installed walled enclosure in which the package is
outdoors as is. covered with additional enclosure may be
However, its specification and installation adopted for noise control.
procedure must be studied carefully. Silencer performance is indicated by
The impact of vibration, noise, and exhaust measuring noise level at 1 m and 45° from
gas must be controlled and oil leakage exhaust outlet.
must be prevented for environmental When exhaust gas is released directly from
maintenance around the installation silencer to atmosphere, gas flow velocity at
location, like engine room. tail-pipe should be 50 m/s or lower and the
pipe edge should be cut at 30 to 45° to gas
flow direction to reduce exhaust noise.

17
Chapter 1 Planning

Depending on structure or thickness of 2.1.3 Oil holding


silencer, noise caused by internal exhaust The package bottom should be sealed
gas flow may be transmitted outside. tightly. If oil or fuel leaks from joint or
Therefore, heat insulating material should piping, the package will hold it. Therefore,
be applied to the silencer surface not only prompt measures against oil spill such as
for heat insulation but also for sound measuring oil level using float switch, etc.
absorption. and issuing warning can be taken.
In mounting on package roof or outside, However, leaked oil, depending on leakage
noise transmitted through the silencer body portion or airflow velocity in the package,
may affect the surrounding. For the may be sucked by radiator fan, pass
package with built-in silencer, ventilation air through radiator, and be blown from air-
volume must be increased to avoid rise in discharge opening, etc. Therefore, the
temperature due to heat release. enclosure structure must be planned
2.1.2 Vibration carefully.
Drainage hole and valve for oily water must
In general, for the package-type engine-
be located outside the package and valve
driven unit, the upper vibration isolation
outlet must be closed with plug. And, a tag
system is adopted. In this system,
of "Normally closed" should be put on the
vibration isolators are located between the
valve so that oil can be discharged as
top surface of the common bed and the
necessary.
mounting feet of engine/driven equipment.
Vibration level at the bottom surface of 2.1.4 Waterproof
package in this system may cause no Highly water-tight package is required for
problem in installation on the ground. protecting electric equipment such as
However, in installation on rooftop, generator and control panel. The design of
vibration transmitted to the building enclosure with waterproof structure is
structure may cause some problems. important. Rain or snow, depending on
For reducing vibration more, depending on airflow velocity, may invade from air inlet
the installation requirement, double opening due to its limited size and fall to
vibration isolation system, in which equipment in drops. Vacuum in package
additional vibration isolators are arranged facilitates water invasion from the
under package, can be applied. surrounding.
In some vibration isolators arranged under However, it is very hard to realize complete
the package, pneumatic pressure, as well waterproofing in package. Therefore, drip-
as rubber or spring, is used to achieve high proof electric equipment should be
insulation performance. adopted.

18
Chapter 1 Planning

2.2 Installation on the ground


Fig. 1-1 shows the typical installation on
the ground.

Neighbor residence
Direct noise
Exhaust
Discharge air

Transmitted noise

Soundproof wall Oil spill dam

Distance decay Transmission loss


Boundary with adjacent area

Fig. 1-1 Installation on the ground

2.2.1 Noise Even if the boundary with the adjacent


When residence is far away from the area is close to the installation site, the
package installation site, noise will decay package should not be surrounded by
with distance. Otherwise, soundproof wall soundproof wall.
must be arranged around the package. When soundproof wall is higher than the air
Soundproof wall made of concrete or block inlet/outlet or exhaust outlet, hot air or
can use its high transmission loss to exhaust gas is likely to be accumulated in
reduce noise against the neighbor the soundproof wall. Depending on
residence that is as high as the package. package structure or wind direction, the hot
Ideally, soundproof wall should hide the air or exhaust gas may be sucked from the
entire package from to the neighbor air inlet. This circulation phenomenon
residences perfectly. However, noise may raises the temperature inside package,
be transmitted directly to the neighbor thereby causing engine overheat.
residences, depending on their height.
When the openings of cooling air or
exhaust gas are in the high position of the
package, the package with the
performance and structure that meets the
installation conditions must be chosen, with
the noise level from the openings taken
into consideration.

19
Chapter 1 Planning

2.2.2 Oil spill prevention When fuel, oil, or rain including oil leaked
Oil spill dams must be arranged around the from floor or oil spill dam spills outside the
package and its auxiliary equipment. site through oil-water separation pit, notify
Otherwise, fuel or oil leaked from package the local government or government office.
or remote mounted fuel or oil tank will Drainage corner must be arranged inside
spread outside the installation site. the oil spill dam, and floor should be sloped
Floor and oil spill dams must be water- to the drainage corner to impound
tightened. Otherwise, water including fuel rainwater there. Shutoff valve must be
or oil may invade into the ground or attached to the drain outlet of the drainage
surrounding field or river, thereby causing corner, and the drainage pipe from the
water or soil pollution. outlet must be connected to oil-water
Rain in oil spill dams must be discharged to separation pit tightly.
drainage ditch through oil-water separation The shutoff valve must be closed at all
pit. The oil-water separation pit uses the times. In case of rain, conform that no oil
difference in weight to separate oil from or fuel is leaked before opening the valve.
water. This is the last measure to prevent When much oil is leaked in rain, it must be
leaked rain including fuel or oil from collected promptly. Otherwise, oil will spill
spreading peripherally. When the oil-water outside separation pit. Rain including oil
separation pit cannot stop leaked oil, oil collected from oil-water separation pit must
may spill to river, lake or sea through public be processed properly.
drainage ditch, which may develop into
significant environmental problem.
Therefore, the pit must be maintained
properly.

20
Chapter 1 Planning

2.3 Installation on rooftop


Fig. 1-2 shows the typical installation on
rooftop.

Exhaust
Discharge air

Neighbor residence

Fig. 1-2 Installation on rooftop

This method has some disadvantages. the installation on the ground. Otherwise,
Strong ceiling in the building and larger no soundproof wall may be required or its
crane truck for carrying are required. height can be decreased, depending on
And, fuel must be transferred from the the distance between the package and
main fuel tank on the ground to the high building edge or the height of oil spill dam.
position. When the building edge, oil spill dam, or
Meanwhile, the noise measures can be soundproof wall hides the entire package
taken easily, depending on the height of from the neighbor residence, no noise is
the building relative to neighbor transmitted directly to the residences.
residences.
2.3.2 Vibration isolation
2.3.1 Noise Vibration may be transmitted to the
The noise measures vary depending on building structure, thereby causing
the height of the neighbor residences problems. Consult with the expert in
relative to the package. When the advance to analyze the building strength
neighbor residence is higher than the and response or apply special vibration
package, soundproof wall is effective, like systems.

21
Chapter 1 Planning

2.3.3 Oil spill prevention 2.4.3 Freeze


Fundamentally, take the measures like the When an engine does not run for 24
installation on the ground. consecutive hours or for definite period, the
temperature of the external cooling system
2.4 Auxiliary equipment will decrease during engine stop.
2.4.1 Waterproof In small size pipes with small cooling water
In principle, water-tight or drip-proof volume (heat) and bypass pipes whose
auxiliary equipment must be used. Note temperature rarely rises, water
that, for the electric equipment such as temperature decreases abruptly with heat
control panel, the outdoor structural criteria release. Unless antifreeze is applied to
are established. For panel sealed tightly, water in subfreezing conditions, the pipes
ventilation fan must be attached to control may freeze. In this case, frozen water may
humidity and temperature. expand to crack or break portions weaker
Waterproof insulation processing must be than the pipes such as joint and gauge.
applied to remote mounted silencer to Therefore, lines that are likely to freeze
protect it against corrosion and heat shock must be kept warm (insulated). And, in
due to abrupt temperature decrease. extremely low-temperature installation
environment, heater must be arranged in
Fuel or oil tanks outside the package must
piping, etc.
have waterproof structure. Otherwise,
water that invaded into fuel tank or For cooling tower around which air
condensed water vapor may be supplied temperature is below zero, heater must be
with fuel to an engine, to corrode the inside installed to prevent cooling water from
of injection pumps and nozzles. freezing during engine stop.
Particularly, springs will be broken in short
time, and faulty injection spray pattern may 3. Carry in
cause much black smoke.
3.1 Carry-in route
2.4.2 Noise
When an engine-driven unit is installed
Noise level of auxiliary equipment such as indoors, particularly in the basement
heat transfer equipment having fan or engine room, the carry-in route of the
pumps may cause problems, depending on engine-driven unit and auxiliary equipment
the regulation values in the installation must be studied in advance. The route for
location. laying crane truck alongside, dry pit
When noise of auxiliary equipment is lower neighbor to parking area, route for vehicle
than noise around the package over 10 dB, that carries in slope from the ground, and
it may not affect the noise level of the entire machine hatch should be arranged.
facilities. Otherwise, the noise may be When the equipment is carried in the
combined with the package to reach ground or rooftop, the required crane
double (3 dB) or more. performance depends on the distance from
the parking area and the equipment
weight.

22
Chapter 1 Planning

Ground

Underground
engine room
Dry pit

Fig. 1-3 Dry Pit

As shown in Fig. 1-3, dry pit is the groove When the public road traffic is regulated for
to take down engine-driven unit and carrying, notify the nearest police station in
auxiliary equipment using crane truck advance and assign the person to traffic
directly from the ground to the control.
underground. As shown in Fig. 1-4, slope is the route for
The lifting capacity of crane truck depends vehicle that carries from the ground to the
on the distance between the crane truck basement engine room. In Japan, its
and dry pit, which should be as short as incline must be 1/4 (14°) or lower, based on
possible. the climbing power of vehicle in the safety
standard of the Road Trucking Vehicle
Law.

Ground

Underground Slope
engine room

Fig. 1-4 Slope Route

When carriage or roller is used to descend appropriate positions of route or building


slope, anchors to hang chain hoist or wire for safety.
rope on hook must be arranged in the

23
Chapter 1 Planning

Machine hatch is the hole for carrying from Rust prevention treatment must be applied
upper floor to the engine room in lower to engine, according to the long storage
floor. In general, it should be closed with procedure of the operation/maintenance
door or cover after carrying. manual. And, for freeze prevention,
In machine hatch, engine-driven unit and sufficient antifreeze must be mixed with
auxiliary equipment are carried to upper cooling water or cooling system must be
floor and taken down to lower floor. To do drained.
so, beams and lifting eyes strong enough When a stand-alone engine is stored, the
to support their weight must be arranged in rack for carrying the specific engine must
the upper floor. be used. Otherwise, the oil pan gasket
may be damaged due to the engine weight,
3.2 Carrying in during construction which may cause oil leak.
Mounting of an engine-driven unit or
auxiliary equipment in the engine room 3.3 Lifting and moving
under construction for easy carrying must In principle, coolant and lubricating oil must
meet the requirements below, according to be discharged from an engine-driven unit
the outdoor storage procedure. before factory shipment for reduction of
The engine-driven unit must be protected weight to carry and safety.
against wind, snow, rain, or dust in The dry weight of equipment must be
construction, from mounting to the confirmed in the specification sheet for
completion of the engine room. safety in lifting or moving.
Ideally, the equipment should be covered In lifting or moving an engine-driven unit,
with waterproof sheets. the qualified person must use a crane
When it is hard, all the openings such as truck.
the pipe connection for coolant, fuel, oil, air Lifting eyes or holes of common bed and
intake, exhaust, air vent in engine, air inlet/ enough strong slings must be used to lift
outlet and cabling opening at generator, unit for safety.
must be closed fully. In lifting or moving equipment, keep
Electric equipment such as generator and balance with the gravity center labeled on
control panels must be water-tight fully, the common bed taken into consideration.
and, in packing it, sufficient drying agents The lifting eyes or holes attached to engine
must be applied for condensation or generator have strength enough to bear
prevention. only engine or generator, respectively.
Space heater built into generator, when its They must not be used to lift an engine
power supply is assured in construction generator set. Otherwise, drop accident
site, can be used to prevent condensation. may occur.
However, then, the generator must not be See the specification sheet or refer to a
sealed. dealer or manufacturer in advance to
confirm the weight of equipment such as
control panel, silencer, heat exchanger,
expansion tank, furl tank, or oil tank.

24
10
[Fig.1-5 Layout Drawing (Top)]

1 Fire extinguishers
47 2 Service entrances
6 5 50 3 Remote mounted radiators
4 Heat exchangers
22 5 Fuel day tank
20 21 6 Oil tank
9 11
7 Exhaust silencers
8 Exhaust gas boilers
9 Control panels
10 Operation room
48 11 Glass windows
12 Emergency stop devices
13 Ventilation air inlets
33 14 Ventilation air outlets
15 Supply air ducts
49 31 24 16 Discharge air ducts
51
17 Stools
18 Beams
19 Overhead lifting devices
20 Starter air tanks
21 Electric drive air compressor
22 Diesel powered air compressor
38 23 Electric drive ventilation fans
24 Air supply openings
1 25 Air-discharge openings
26 Foundations
37 27 Vibration isolators
29 28 Base plates
42 4
29 Circulating pumps for hot water
17
30 Expansion tanks
31 Pipng trench
32 Flexible joints
52
33 Gate valves
34 Drainage trench
35 Vent lines for jacket water
53 36 Vent lines for intercooler
37 Remote mounted air cleaners
38 Intake air flex connectors
39 Expansion joints
40 Fixed pipe hangers
41 Slidable pipe hangers
42 Sleeves
43 Exhaust outlets
44 Rain caps
45 Drain traps
46 Main fuel tank
47 Oil spill dam
2 48 Drainage corner
49 Vent pipe for fuel day tank
50 Fuel water separators
51 Vent pipe for engine oil tank
52 Blow-by outlets
53 Drip collectors
54 Cable trench

25
[Fig.1-6 Layout Drawing (Side)]

43 44

30

15

16

18

13
25
14 40
41
19
36 39
23
8
35 32
12

54
45

28
34 26 27

46

26
Chapter 2 Ventilation

Good ventilation is essential to the ŒConsideration for prevailing wind direction


functions of the air intake/cooling system such as sea breeze/land breeze and wind
for engine-driven unit. Sufficient clean blowing through buildings:
ambient-temperature air supply improves Depending on wind direction, air
engine combustion efficiency. And, discharged from heat transfer equipment
supplied air flow and temperature or exhaust with burning appliances may
determine the performance of the air- reach the inlet.
cooled heat transfer equipment. ŒRain invasion prevention:
In general, the opening of the air inlet
should be placed downwards to prevent
1. Plan
rain invasion, and appropriate rain gutter
In ventilation design, the whole installation
should be attached around the inlet.
such as noise measure in engine room and
Air velocity should be 6 m/s or lower in the
arrangement of engine-driven unit and
inlet to prevent invasion of rain drop.
auxiliary equipment must be taken into
ŒSnow invasion prevention:
consideration.
Powder snow may be sucked in extreme
Silencer may be attached to ventilation
cold because it is feathery. And, it is hard
openings, depending on the local
to prevent snow invasion with the
environmental standards.
structure of the air inlet. However, air inlet
1.1 Ventilation opening large enough to keep the flow velocity
within 3 m/s is effective in preventing
1.1.1 Ventilation air inlet snow invasion.
Ventilation air inlet must meet the following ŒLouver or mesh:
requirements. The structure of air inlet should prevent
ŒLow-temperature place: suction of large foreign matters such as
Air inlet must be arranged so that the sere leaves and invasion of wild bird.
most low-temperature air can be sucked ŒPrevention of water invasion into engine
in. Avoid suction of hot air heated by room:
daylight or discharged from remote When rain or snow invasion cannot be
mounted radiator or cooling tower. prevented in the inlet, baffle plate should
ŒClean air: be attached in air supply duct. Baffle
Air inlet must not be arranged near plate changes airflow direction suddenly.
exhaust outlet including other engines or Therefore, snow or rain that bumped into
boiler. Otherwise, black smoke will clog the baffle plate and dropped is
air cleaner element early. And, the inlet accumulated in the duct and then is
must not be arranged near blow-by outlet. drained.
Or, snow or rain falls to the duct at low air
velocity. Note that baffle increases
pressure loss and a large duct is required
to decrease air velocity.

27
Chapter 2 Ventilation

1.1.2 Ventilation air outlet Arrangement of blow type at air inlet and
In arrangement of ventilation air outlet, suction type at air outlet should be
make sure that discharged hot air does not considered to maintain atmospheric
have harmful effects on ambient pressure in the engine room. When an
environment or equipment. electric drive fan is used, fan with proper
And, the ventilation air outlet must meet capacity must be chosen. Therefore,
the same requirements as ventilation air confirm the pressure-airflow performance
inlet to prevent invasion of rain, snow, diagram based on ventilation resistance in
foreign matters, or wild bird. the engine room or refer to the fan dealer
or manufacturer.
1.2 Air-supply/Air-discharge opening
1.2.1 Air supply opening
and fan
Supply air for ventilation must be sucked in
Engine room should be designed to ensure
from the rear of a generator (cooling air
that positive pressure or as low vacuum
inlet) to the engine room. Normal
possible is kept. Otherwise, ambient
temperature air that is sucked in from air
vacuum, together with the air flow
supply opening to the engine room must be
resistance of an air cleaner, will shorten the
supplied directly to the cooling air inlet in
service life of the air cleaner element that
the generator to keep the temperature of
depends on the engine intake resistance.
cooling air in the generator within the
The blower type fan is desirable in the air
standard maximum temperature of 40°C
supply side. However, in this case, fan
(See Fig. 2-1).
type and performance must be taken into
consideration.

Air-discharge
opening

Air supply
opening

Engine Generator

Fig. 2-1 Basic arrangement of air-supply/air-discharge opening

If the supply air is sucked from opposite by hot air discharged from generator fan to
side, the air will be heated when passing get hot before reaching the air inlet in the
though near the engine and be disturbed generator.

28
Chapter 2 Ventilation

The air supply opening must be arranged 1.2.2 Air-discharge opening


in as low position as possible in the engine In principle, air-discharge opening must be
room. The supply air must flow in low arranged in as high position as possible in
position at the engine room to cool engine- the engine room. Discharging air that has
driven unit and auxiliary equipment the same flow direction as hot air rising to
mounted on the floor sufficiently. ceiling improves ventilation efficiency
When air absorbs heat from heat source in together with supply air that flows from
the engine room, the air temperature underside. Ideally, air-discharge opening
increases and its density decreases, and should be placed right above the engine
then the air rises. Therefore, when air is that is the most high-temperature except
supplied from high position, the air will for nude exhaust piping and silencer in the
bump into and be mixed with hot airflow, engine room. However, overhead lifting
thereby reducing ventilation efficiency devices and beams must be arranged in
considerably. ceiling for the maintenance of engine-
When two or more engine driven units are driven unit.
arranged in parallel, all the units must be As a second best, the air-discharge
provided with the same ventilation opening should be arranged in higher
condition by air supply. In this case, heat is position near the front of engine.
concentrated particularly between engines. When a fan is arranged in the inlet or outlet
So, the air supply opening must be of discharge air duct, fan motor must has
arranged with airflow taken into enough performance of insulation and heat
consideration. Depending on flow resistance for hot discharge air warmed in
direction, air velocity at air supply opening the engine room.
should be within 10 m/s to maintain When a fan is arranged at the air-
operator environment. discharge opening in the engine room,
When an electric drive fan is arranged at resistance of discharge air duct is applied
the ventilation air inlet in supply air duct, to the outlet side and resistance of supply
total ventilation resistance will be applied to air duct is applied to the inlet side.
the outlet side of fan. When the blower When a fan is arranged at the ventilation
type fan is arranged at air supply opening, air outlet in discharge air duct, total
positive pressure that is equal to pressure ventilation resistance is applied to the inlet
loss of discharge air duct is created at the side. When suction type fan is arranged in
engine room. the discharge air duct, vacuum that is
equal to pressure loss of supply air duct is
created at the engine room.

29
Chapter 2 Ventilation

1.2.3 Radiator Outdoor air that is pulled by fan and is


Only blower fan can be used in the radiator sucked from air inlet flows horizontally in
mounted on engine generator set (See the engine room and is discharged outside
Fig. 2-2). the engine room through radiator core.

Ventilation
fan

Radiator
duct

Dis charge
air outlet
Intake
Engine Generator air inlet

Fig. 2-2 Engine-driven unit with radiator

When the engine-driven unit equipped with 2. Requirement


radiator and blower fan is installed in the Ventilation air volume depends on the
engine room, vacuum is unavoidable there. following requirements.
However, the vacuum must be limited to ŒAir amount required for combustion and
keep heat dissipation capacity of radiator, cooling in engine and other equipment:
and the air inlet with sufficient size will be ŒPermissible room temperature and supply
required. air temperature defined in planning the
Vacuum applied to the engine room by engine room and packaged engine-driven
pressure loss at air inlet and duct must be equipment:
100 Pa (10 mm H2O) or lower. And, total Cooling medium such as Freon and
pressure loss at radiator duct and ammonia used in air conditioner must be
discharge air outlet must not exceed 50 Pa managed with care. If it is leaked and
(5 mm H2O). mixed with intake air in an engine, acid will
Separate electric drive ventilation fan be formed in a combustion chamber to
should be installed to secure the minimum damage the engine (corrosion, etc.).
ventilation in the engine room even while In installing air conditioner for cooling and/
generator set is in idle status. or heating the engine room, consult with
the technical expert.

30
Chapter 2 Ventilation

2.1 Combustion However, 40°C or lower is desirable for


For the MHI engine-driven unit, the human activity in the room.
permissible ambient temperature is 40°C Radiator is the heat exchanger for engine
and the permissible temperature of intake coolant and air. High-temperature cooling
air is 50°C. However, when the air reduces heat dissipation capacity.
temperature of intake air exceeds 40°C, Therefore, insufficient quantity or too high
available power may be limited in temperature of supply air will cause coolant
accordance with the specification sheet, overheat, which may lead to engine
depending on the temperature and shutdown.
installation altitude above sea level.
In the installation place where quantity of 3. Ventilation air volume
supply air is insufficient, the temperature of For the engine-driven unit with radiator,
intake air in engine may be high even in basically, hot air from radiator is
low outdoor air temperature. discharged outdoors through duct.
While air temperature rises, air density When pressure loss in engine room or
decreases, and the amount of oxygen package is proper, radiator fan can suck air
contained in the engine intake air enough to control room temperature and
decreases, too. Then, combustible fuel burn engine fuel. However, confirm the
decreases, which leads to power required air amounts.
reduction. For details of the radiator cooling system
Governor increases fuel injection quantity and radiator duct, see "Cooling System".
in order to increase engine output, which
causes incomplete combustion of excess 3.1 Combustion air
fuel. Then, exhaust temperature rises, Amount of air required to burn fuel
black smoke is created, and consumed fuel completely depends on the chemical
increases. equation of combustible component
contained in the fuel and oxygen.
2.2 Cooling
As low-temperature air as possible must be 3.1.1 Diesel engine
supplied to engine room or package, As shown in Table 2-1, for diesel engine,
except when heating is required. air of about 11.3 m3N (14.8 kg) is required
In general, the permissible temperature in to burn diesel fuel of 1 kg.
engine room is 50°C.

Table 2-1 Typical diesel engine composition


Element C: Carbon H: Hydrogen S: Sulfur
Weight ratio 0.855 0.140 0.005

31
Chapter 2 Ventilation

Theoretical air amount required to burn fuel


Fc Ta + 273.2
is obtained by the following formula. A = A0 • E • λ
1000 273.2
A0 = 8.88C + 26.47H + 3.33S Where:
= 8.88 x 0.855 + 26.47 x 0.140 + 3.33 x 0.005 A: Actual air quantity (m3/h)
= 11.315 (m3N/kg) E: Engine output (kWe)
Fc: Specific fuel consumption (g/kWh)
Where:
Ta: Intake air temperature (˚C)
A0: Theoretical air amount (m3N/kg)
λ: Air excess ratio
C: Weight of Carbon (kg)
Example:
H: Weight of Hydrogen (kg) Rated output: 2,500 kWe
S: Weight of Sulfur (kg) Fuel consumption: 200 g/kWh
In actual diesel engines, combustion is not Air excess ratio: 2.2
in ideal state. Theoretical air amount: 11.32 m3N/kg
Extra air to burn fuel completely is Intake air temperature: 30°C
required. The ratio of the extra air to the
200 30 + 273.2
theoretical air amount is called air excess A = 11.32 × 2500 × 䇭䇭䇭㩷㩷×䇭䇭䇭䇭䇭䇭䇭㩷㩷× 2.2
1000 273.2
ratio. 3
= 13819.3 (m /h)
In general, the air excess ratio in 3.1.2 Gas engine
turbocharged engines depends on engine
For 13A City gas, which is the typical fuel
output, and is about 2 at the rated output.
for gas engine, air of about 11 m3N (about
The amount of air required for combustion
14 kg) per 1 m3N is required.
in diesel engine is obtained by the following
Table 2-2 shows gas composition and
formula.
theoretical air amount.

Table 2-2 Composition of typical 13A city gas


Molecular Theoretical air Composition Combustion
Component
formula amount (m3N/m3N) ratio air (m3/Nm3/N)
Methane CH4 9.524 0.896 8.534
Ethane C2H6 16.667 0.056 0.933
Propane C3H8 23.810 0.034 0.810
Butane C4H10 30.952 0.014 0.433
13A gas 10.710

For combustion system of gas engine,


Ta + 273.2
standard burn with theoretical air-fuel ratio A = A0 • E • Fc λ
273.2
or lean burn with excess air for fuel is Where:
adopted. Actual amount of intake air A: Actual air quantity (m3/h)
depends on air-fuel ratio and temperature A0: Theoretical air amount
of intake air as follows. (m3N/m3N)

32
Chapter 2 Ventilation

temperature, because it receives heat


E: Engine output (kWe)
rejected from engine.
Fc: Specific fuel consumption
When the radiator mounted on an engine-
(m3N/kWh)
driven unit is used to dissipate heat
λ: Air-fuel ratio
transferred to coolant, enough airflow
Ta: Intake air temperature (˚C)
volume to absorb heat rejected from
In order to evaluate the quantity of
engine is required. Therefore, refer to the
combustion air in gas engine precisely, the
MHI dealer about the radiator airflow
amount of oxygen required to burn each
volume.
component contained in fuel gas must be
estimated, which is accompanied by 3.2.2 Radiation and conduction heat
complex chemical calculation. Therefore, Usually, heat insulation should be applied
refer to the MHI dealer with the to high-temperature piping for coolant and
composition table of actually used gas. exhaust and hot equipment such as
When burning boiler or water heater is silencer in order to protect humans against
mounted in the engine room, the amount of burn injury in checking or maintenance and
air required for burning in it is must be also reduce heat released from surface to save
evaluated. Then, refer to the equipment ventilation air volume.
dealer or manufacturer. In general, about 3% of the total heat input
is estimated to be released from the piping
3.2 Cooling air
for the exhaust and cooling system outside
In general, supposing that heat input into engine. And, about 5% of the total heat
engine, that is, low heat value of fuel is input is rejected from engine surface to the
100%, motive energy extracted from surrounding air with radiation and
crankshaft is 35 to 45%, and the remaining conduction.
55 to 65% input energy is rejected as heat.
Therefore, supposing that all equipment is
Most of rejected heat is dissipated mounted in the engine room, heat with
outdoors or collected though the exhaust radiation and conduction can be estimated
and cooling system. Some heat as follows.
transferred from the systems outside
engine to the surrounding air and heat 3+5
Qe = Fc • H E
dissipated from engine with radiation or 100
conduction must be eliminated with Where:
ventilation. Qe: Engine heat rejection (MJ/h)
Fc: Specific fuel consumption
3.2.1 Coolant heat dissipation
Diesel (kg/kWh)
Amount of heat rejected to jacket water Gas (m3N/kWh)
coolant is, in general, 20 to 30% of total H: Low heat value of fuel
heat input at engine rated output. Coolant
Disel (MJ/kg)
must be cooled through heat transfer
Gas (MJ/m3N)
equipment to be maintained at a constant
E: Engine output (kWe)

33
Chapter 2 Ventilation

Supposing that the low heat value of used 3.2.4 Other auxiliary equipment
fuel is 42.71 MJ/kg, radiation and Equipment such as control panel, air
conduction heat in electrical power facility compressor, and circulating pump and
for diesel engine whose rated output is lightning can be heat source. Heat
2,500 kWe is derived from the following dissipated by them may need to be taken
formula. into consideration.

3+5 3.2.5 Amount of cooling air


Qe = 0.2 x 42.71 x x 2500
100 The temperature in the engine room rises
= 1708.4 (MJ/h) with dissipated heat. The temperature
For precise heat rejected to the engine must be controlled with ventilation air
coolant and exhaust and the surrounding supply. The amount of supply air required
air, refer to the MHI dealer. to control the temperature, depending on
the difference between the permissible
3.2.3 Generator heat dissipation
room temperature and cooling air
Generator cannot convert all power given temperature, is given by the following
by engine into electric output because of formula.
ineffective energy such as cooling fan
power, bearing friction loss, rotor windage 1000Q
loss, winding resistance loss, and exciter Ac =
γ • Cp• Δt
loss.
Where:
Ineffective energy of generator dissipated
Ac: Cooling air quantity (m3/h)
as heat is derived from the following
Q: Heat release (MJ/h)
formula.
γ : Air Density (kg/m3)
100 Cp: Isobaric specific heat (kJ/kg°C)
Qg = G x - 1 x 3.6
η
Δt: Temperature difference in room
Where: and outdoors (°C)
Qg: Generator heat dissipation (MJ/h) The amount of heat dissipated in the
G: Generator output (kW) engine room is the sum of radiated and
η: Generator efficiency (%) conducted heat and heat dissipated from
Supposing that the power generation driven and auxiliary equipment.
efficiency of generator whose rated output The amount of heat dissipated by electrical
is 2,500 kW is 96%, dissipated heat is as power facility for diesel engine whose rated
follows. output is 2,500 kWe is derived from the
following formula.

Qg = 2500 x 100 - 1 x 3.6


96

= 375.0 (MJ/h)

34
Chapter 2 Ventilation

Q = Qe + Qg Ae + Ac
Ai =
= 1708.4 + 375.0 60
= 2083.4 (MJ/h) Where:
Where: Ai: Supply air quantity (m3/min)
Qe = 1708.4 (MJ/h) Ae: Combustion air quantity (m3/h)
Qg = 375.0 (MJ/h) Ac: Cooling air quantity (m3/h)
Supposing that the temperature at The quantity of supply air required in the
ventilation air inlet is 30°C, the amount of engine room that has an electrical power
cooling air required to keep the facility for diesel engine whose rated output
temperature rise in the engine room within is 2,500 kWe is as follows.
10°C is estimated by the following steps.
13819.3 + 177766.0
Air Density at temperature T: Ai =
60
353.2
γ= = 3193.1 (m3/min)
T + 273.2
Where:
Cooling air at 30°C: Ae = 13819.3 (m3/h)
353.2 Ac = 177766.0 (m3/h)
γ= = 1.165 (kg/m3)
30 + 273.2
Supposing that isobaric specific heat of air 3.4 Discharge air quantity
is 1.006 kJ/kg°C, the amount of cooling air The engine intake air enters the exhaust
is as follows. system through combustion chamber and
is discharged from the other outlet.
1000 x 2083.4 Therefore, the quantity of combustion air
Ac =
1.165 x 1.006 x 10 need not be included in the quantity of
ventilation discharge air even if it is
= 177766.0 (m3/h)
included in the quantity of ventilation
supply air.
3.3 Supply air quantity
The quantity of ventilation discharge air
The quantity of supply air required for
should be determined by only the quantity
ventilation in the engine room or package
of cooling air.
is the sum of the amount of combustion air
The quantity of discharge air is, depending
in engine and the amount of cooling air for
on temperature rise, as follows.
heat dissipation. However, when air
cleaner sucks in air directly from outdoors Aφ = Ac • Δt + 273.2
through duct, the quantity of combustion air 60 273.2
need not be included in the quantity of Where:
ventilation supply air. Aφ: Discharge air quantity (m3/min)

35
Chapter 2 Ventilation

Therefore, the quantity of discharge air in 4. Ventilation resistance


the engine room that has an electrical As shown in Fig. 1-5 and Fig. 1-6, in the
power facility for diesel engine whose rated case below, the diesel engine generator
output is 2,500 kWe is as follows. set whose rated output is 2,500 kWe is
installed in the engine room. In this
17776.0 × 10 + 273.2
Aφ= section, pressure loss created at air supply
60 273.2
and discharge ducts by ventilation is
= 3071.2 (m3/min) estimated in the case.
Where:
Δt = 10 (°C) 4.1 Supply air duct
As shown in Fig. 2-3, suppose that a
supply air duct is installed with a generator
set in the engine room.

0.3 m

2.5 m

7.0 m
Ventilation
Supply air
air inlet
outlet (with mesh)
(with louvers)

0.7 m
1.2 m Guide vanes
(3 places)

1.2 m

Fig. 2-3 Case: Supply air duct

36
Chapter 2 Ventilation

Thin steel and SUS plate can be used to For the rectangle whose aspect ratio is up
make duct easily. to 2, the appropriate equivalent diameter is
Large duct is prone to vibrate because its estimated by the following simple formula.
plane is wide and can be low-frequency
noise source in resonance with noise in the de = 2.2 x a • b
a+b
engine room or airflow. In this case, duct 1.2 x 1.2
= 2.2 x
must be strengthened properly. Belts such 1.2 + 1.2
as section steel, etc. may be wrapped to = 1.32 (m)
reinforce the duct. Or, partitioning the Air pressure loss is evaluated by the
section and applying acoustic materials following typical formula.
inside are effective for noise reduction,
L • υ2 γ
because attenuation of duct noise is Δp = λ
2de
proportional to number of bend and area of 1
acoustic material. λ㩷=
1.74㩷 - 2log 2ε 2

As shown in Fig. 2-3, in four partitions, 1000de


pressure loss created at one partition must Q
υ =
be estimated with quartered quantity of 60A
supply air in duct. 353.2
γ=
T + 273.2
4.1.1 Straight duct
Where:
Duct with rectangle section must be
Δp: Air flow resistance (Pa)
converted into pipe with circular section so
that they can be equal in resistance per λ: Resistance factor
unit length in equal flow. L: Equivalent length (m)
The size of this pipe, which is called de: Equivalent diameter (m)
equivalent diameter, is given by the ε : Roughness (mm)
following formula. υ: Velocity (m/s)
Q: Air quantity (m3/min)
5
(a • b) A: Section area (m2)
Equivalent diameter de = 1.3 8 (a + b)2 γ: Air Density (kg/m3)
a 0.625
(a • b) T: Air temperature (°C)
= 1.3 x
(a + b)0.25
b
For surface roughness of 0.4 mm and
rectangle whose aspect ratio is up to 2, the
The equivalent diameter of the duct in this pressure loss is estimated by the following
case is as follows. simple formula.
1.2 m
(1.2 x 1.2)0.625 L • Q2 • γ
de = 1.3 x Δp =
(1.2 + 1.2)0.25 314000de5.25
1.2 m
= 1.31 (m)

37
Chapter 2 Ventilation

For simplicity, Fig. 2-4 shows the typical Note that this cannot be applied to
air pressure loss per 10-m straight duct concrete duct because its roughness is
whose roughness is 0.4 mm. 3 mm.

10000

5000 5000
4000 4500 15 m/s
4000 13 m/s
3000
11 m/s
3500 9 m/s
2000
3000 7 m/s
1500
2500 5 m/s
1000
2000
1800
500 1600
400 1400
300 1200

200 1000
150 900
Flow rate (m3/min)

800
100 700

600

50 500
40
30 400

20
300
15
200
10
0.1 0.15 0.2 0.3 0.4 0.5 1 1.5 2 3 4 5 10 15 20 30 40 50 100
Pressure loss (Pa) per 10 m at 20 °C

Fig. 2-4 Pressure loss at straight duct

The vertical axis indicates flow rate per The right upward sloping line (pipe size
minute (m3), and the horizontal axis line) shows rectangle pipe with equivalent
indicates pressure loss (Pa) per 10-m duct diameter of 200 to 5000 mm.
at 20°C.

38
Chapter 2 Ventilation

The reading in the horizontal axis in the


intersection of flow line and pipe size line is 353.2
Density at 20°C =
20 + 273.2
pressure loss per 10-m duct.
= 1.205 (kg/m3)
The line that intersects with pipe size lines
353.2 1
shows the condition of flow velocity of 5 to F= x
T + 273.2 1.205
15 m/s for regular tetragon duct.
Therefore, the temperature correction
MHI recommends air velocity of 6 to 9 m/s factor (F) for pressure loss of air at 30°C is
and up to 11 m/s for low-speed ventilation as follows.
duct.
In this case, supply air of 798.3 m3/min (1/4 353.2 1
F= x = 0.967
of 3,193.1 m3/min) flows to rectangle duct 30 + 273.2 1.205
with equivalent diameter of 1.31 m. Then, So, the pressure loss at temperature (T) is
as shown in Fig. 2-4, pressure loss per the reading value in the graph multiplied by
10 m is about 6 Pa. F, that is, 6 x 0.967 = 5.8 (Pa).
The graph in Fig. 2-4 shows pressure loss Table 2-3 shows air density in realistic
at 20°C, and airflow resistance is temperature range.
proportional to air density. Therefore,
pressure loss at different air temperature
(T) must be obtained by multiplying a read
value of the graph by temperature
correction factor (F), as follows.

Table 2-3 Relation between temperature and density


Temperature - 10 - 5 0 5 10 15 20 25 30 35 40 45 50
Ȗ 1.342 1.317 1.293 1.270 1.247 1.226 1.205 1.185 1.165 1.146 1.128 1.110 1.093

The approximate pressure loss when 30°C 4.1.2 Ventilation air inlet
air flows in 10-m duct at a flow rate of The local resistance created at duct whose
798.3 m3/min is as follows. cross section changed suddenly is
2
obtained by the following formula.
10 x 798.3 x 1.165
ΔP = = 5.73 (Pa)
314000 x 1.315.25 υ2 γ
Local resistance ΔP = ζ
2
Where:
ζ: Local resistance factor
When wire mesh is attached to ventilation
opening, the pressure loss with local
resistance depends on the aperture ratio at
the inlet and the supply air velocity.

39
Chapter 2 Ventilation

Fig. 2-5 shows the estimated pressure loss


at 20°C.

15

10
0.9
0.8
0.7
Velocity (m/s)

5 0.6
0.5
4
0.4
3
n=0.3
2
1.5

1
1 2 3 4 5 10 20 30 40 50 100 200 300 500 1000
Pressure loss (Pa) at 20ºC

Fig. 2-5 Pressure loss at inlet with wire mesh

The vertical axis indicates air velocity In the above graph, the reading in the
(m/s), and the horizontal axis indicates horizontal axis of the intersection of the line
pressure loss (Pa) at 20°C. of n = 0.9 and the line of air velocity of 10.2
The right upward slanted line shows the is about 40 Pa, which shows pressure loss
pressure loss in inlet with wire mesh whose at 20°C. Therefore, the corrected pressure
aperture ratio is 0.3 to 0.9. Aperture ratio loss for the supply air temperature is
is the ratio of mesh's free area (which air 40 x 0.967 = 38.7 (Pa).
can pass through) to the entire inlet area. For air discharge with radiator fan of
In this case, the pressure loss in the engine-driven unit, much outdoor air flows
aperture ratio (n) of 0.9 is estimated. in. Therefore, note that area wider than
Mesh with aperture ratio of 0.9 radiator front is required, depending on the
corresponds to any of the following. aperture ratio of ventilation air inlet
ŒCenter distance between steel wires is equipped with mesh or louver.
10 mm and wire diameter is 1 mm. 4.1.3 Supply air outlet
ŒCenter distance between steel wires is When supply air blows to the engine room
20 mm and wire diameter is 2 mm. through supply air duct, local resistance is
Mesh’s free area: A = 1.2 x 1.2 x 0.9 created because its route is expanded
abruptly.
= 1.30 (m2)
In this case, the air supply opening is
Air velocity at mesh υ = 798.3 equipped with lightly-inclined louvers with
60 x 1.30 flat section. Therefore, higher resistance
= 10.2 (m/s) will be applied.

40
Chapter 2 Ventilation

Fig. 2-6 shows the estimated pressure loss Supposing that the aperture ratio (n) is 0.9
created at air supply opening equipped and velocity is 10.2 m/s, pressure loss at
with louvers. the outlet is about 94 Pa. Therefore, the
corrected pressure loss at the temperature
of supply air is 94 x 0.967 = 90.9 (Pa).

15

10
Velocity (m/s)

5

0.9 0.8 0.7 0.6 n=0.5
3

2
1.5

1
1 2 3 4 5 10 20 30 40 50 100 200 300 500 1000
Pressure loss (Pa) at 20ºC

Fig. 2-6 Pressure loss at outlet with louvers

For louvers whose zigzag shape or 4.1.4 Bend


mountain shape bends airflow, higher local Fig. 2-7 shows the estimated local
resistance will be created. Therefore, in resistance created at 90° bend
the design of inlet or outlet with louvers, (square elbow).
ventilation resistance must be taken into
consideration.

15
W
10
H
Velocity (m/s)

A
5 B

3
2
1.5
1
1 2 3 4 5 10 20 30 40 50 100 200 300 500
Pressure loss (Pa) at 20°C

Fig. 2-7 Pressure loss at 90° bend

Local resistance created at bend depends (H/W), where W is bend direction, H is


on the ratio of duct height to duct width direction perpendicular to bend direction.

41
Chapter 2 Ventilation

"A" line is applied for H/W of 1.0 or lower, And, equipping bend with one guide vane
and "B" line is applied for H/W of 1.0 to 2.0. is presumed to lower local resistance to
55% and equipping bend with two guide
Ratio of width and height: H/W = 1.2 vanes is presumed to lower to 22%. In this
1.2
case of one guide vane, the pressure loss
= 1.0
Duct area: A = 1.2 x 1.2 is 61 x 0.55 = 33.6 (Pa).
= 1.44 (m2) For supply air duct with three 90° bends,
798.3 the total pressure loss is 33.6 x 3 = 100.8
Air velocity at duct: υ =
60 x 1.44 (Pa).
= 9.2 (m/s) 4.1.5 Pressure loss
According to Fig. 2-7, the pressure loss in
Table 2-4 lists the pressure loss at supply
the air velocity of 9.2 m/s is about 63 Pa.
air duct.
The value corrected with the supply air
temperature is 63 x 0.967 = 61 (Pa).

Table 2-4 Pressure loss at supply air duct


Pressure loss at straight portion Local resistance (Pa) Total
Ventilation Supply air pressure loss
Length (m) (Pa/10m) (Pa) Bend (Pa)
air inlet outlet
10.5 5.8 6.1 38.7 90.9 100.8 236.5

4.2 Discharge air duct quartered (air quantity displacement:


In this section, as shown in Fig. 2-8, the 3,071.2/4 = 767.8 m3/min) like supply air
pressure loss in discharge air duct duct is studied.

Guide vanes
(2 places)
2.0 m
2.2 m

Ventilation 1.5 m Air-discharge


air outlet opening
(with mesh) (with mesh)

Fig. 2-8 Case: Discharge air duct

42
Chapter 2 Ventilation

4.2.1 Air-discharge opening


Air velocity at mesh: υ = 767.8
When wire mesh whose aperture ratio is
60 x 1.30
0.9 is attached to air-discharge opening,
= 9.8 (m/s)
the flow velocity is as follows.

Mesh’s free area: A = 1.2 x 1.2 x 0.9 According to Fig. 2-9, the local resistance
= 1.30 (m2) is about 36 Pa at 20°C.

15

10
0.9
0.8
0.7
Velocity (m/s)

5 0.6
0.5
4
0.4
3
n=0.3
2
1.5

1
1 2 3 4 5 10 20 30 40 50 100 200 300 500 1000
Pressure loss (Pa) at 20ºC

Fig. 2-9 Pressure loss at inlet with mesh

The temperature correction factor for Therefore, the local resistance created at
discharge air at 40°C is, with air density in air-discharge opening is 36 x 0.936 = 33.7
Table 2-3, is as follows. (Pa).

F = 1.128 = 0.936 4.2.2 45° bend


1.205
Fig. 2-10 shows the estimated local
resistance created at 45° bend.

15
W
10
H
Velocity (m/s)

A
5 B
4
3

2
1.5

1
0. 0. 0. 0. 0. 1 2 3 4 5 10 20 30 40 50 100
Pressure loss (Pa) at 20ºC

Fig. 2-10 Pressure loss at 45° bend

43
Chapter 2 Ventilation

The local resistance created at bend


depends on the ratio of duct width and Air velocity: υ = 767.8
60 x 1.2 x 1.2
height (H/W).
= 8.9 (m/s)
"A" line is applied for H/W of 1.0 or lower,
and "B" line is applied for H/W of 1.0 to 2.0. The pressure loss in the flow velocity of 8.9
m/s is about 16 Pa, according to "A "line.
When the cross section of discharge duct
The value corrected with the discharge air
is partitioned like supply air duct, the flow
temperature is 16 x 0.936 = 15.0 (Pa).
velocity is as follows.
4.2.3 90° bend
Fig. 2-11 shows the local resistance
created at 90° bend.

15
W
10
H
A
y (m/s)

5 B
4
3
Velocit

2
1.5

1
1 2 3 4 5 10 20 30 40 50 100
Pressure loss (Pa) at 20°C

Fig. 2-11 Pressure loss at 90° bend

"A "line is applied for H/W of 1.0 or lower, Equipping bend with one guide vane is
and "B" line is applied for 1.0 to 2.0. presumed to lower local resistance to 55%,
The pressure loss in the flow velocity of 8.9 and the value is estimated to be
m/s is about 60 Pa. The value corrected 56.2 x 0.55 = 30.9 (Pa).
with the discharge air temperature is For duct with two 90° bends, the local
60 x 0.936 = 56.2 (Pa). resistance is 30.9 x 2 = 61.8 (Pa).

44
Chapter 2 Ventilation

4.2.4 Straight portion the pressure loss per 10 m is about 5.4 Pa,
As shown in Fig. 2-12, for discharge air and the value corrected with temperature is
flow of 767.8 (m3/min) at rectangle duct 5.4 x 0.936 = 5.1 (Pa).
with equivalent diameter of 1.31 m,

10000

5000 5000
4000 4500 15 m/s
4000 13 m/s
3000
11 m/s
3500 9 m/s
2000
3000 7 m/s
1500
2500 5 m/s
1000
2000
1800
500 1600
400 1400
Flow rate (m3/min)

300
1200

200 1000
150 900
800
100 700

600

50 500
40
30 400

20
300
15
200
10
0.1 0.15 0.2 0. 3 0. 4 0.5 1 1.5 2 3 4 5 10 15 20 30 40 50 100
Pressure loss (Pa) 10 m at 20ºC

Fig. 2-12 Pressure loss at straight duct

The approximate pressure loss when 40°C


air flows in 10-m duct at a velocity of 767.8 10 x 767.82 x 1.128
ΔP = = 5.13 (Pa)
m3/min is as follows. 314000 x 1.315.25

45
Chapter 2 Ventilation

4.2.5 Ventilation air outlet about 67 Pa, and the value corrected with
Fig. 2-13 shows the estimated pressure discharge air temperature of 40°C is
loss at ventilation air outlet with wire mesh. 67 x 0.936 = 62.7 (Pa).
For aperture ratio (n) of 0.9 and flow
velocity of 9.8 m/s, the pressure loss is

15

10

0.9
5
Velocity (m/s)

0.7
4 0.8 0.5
0.6
3
0.4 n=0.3
2
1.5

1
1 2 3 4 5 10 20 30 40 50 100 200 300 500 1000
Pressure loss (Pa) at 20ºC

Fig. 2-13 Pressure loss at outlet with wire mesh

4.2.6 Pressure loss


Table 2-5 lists the pressure loss at
discharge air duct.

Table 2-5 Pressure loss at discharge air duct


Pressure loss at straight portion Local resistance (Pa) Total
Air- Ventilation pressure
Length (m) (Pa/10m) (Pa) discharge Bend
air outlet loss (Pa)
opening
5.7 5.1 2.9 33.7 76.8 62.7 176.1

4.3 Ventilation resistance 4.3.2 Fan


In general, when engine-driven radiator fan
4.3.1 Resistance
is not used, electric drive fan is used for air
Ventilation resistance in the engine room is
supply and/or discharge in the engine
the total pressure loss at supply air duct
room. In choosing the fan, use the
and discharge air duct.
pressure-airflow performance diagram or
In the above case, the pressure loss at
refer to the fan dealer or manufacturer.
supply air duct is 236.5 Pa (24.1 mm H2O),
When no fan has enough ventilation
the pressure loss at discharge air duct is
capacity for estimated resistance,
176.1 Pa (18.0 mm H2O), and the total
ventilation resistance must be reduced.
pressure loss is estimated to be 412.6 Pa
(42.1 mm H2O).

46
Chapter 2 Ventilation

Pressure loss at the straight portion of duct Vacuum in the engine room, together with
is low in comparison with local resistance the air flow resistance of an air cleaner,
at changed section. Therefore, to reduce shortens the service life of the air cleaner
ventilation resistance, the duct structure element that depends on the air intake
must be improved to lower local resistance. resistance.
For example, guide vanes should be added Pressure in the engine room is applied to
to 90° bend, or 90° bend should be its door and influences the door opening
changed to 90° elbow (Elbow with bend and closing. In case of vacuum, the door is
radius of 1 m can reduce the resistance easy to pull inside the engine room and
about 40% from the bend in this case). hard to push outside, and vice versa. In
case of positive pressure, the door is hard
4.3.3 Pressure
to pull inside the engine room and easy to
When the blower type fans are arranged at
push outside. Anyway, excessive pressure
air supply opening, positive pressure of
is not desirable.
176.1 Pa that is equal to pressure loss in
When fans are arranged in both supply air
discharge air duct is created at the engine
duct and discharge air duct like the above
room.
case, pressure in the engine room
When the suction type fans are arranged at
depends on the fan capacity and the
air-discharge opening, vacuum of 236.5 Pa
pressure loss at the ducts. Therefore, if
that is equal to pressure loss in supply air
the ventilation resistance is as estimated in
duct is created.
the above case, and the same number and
Positive pressure or as low vacuum as
type of fans are used for air supply and
possible is desirable in the engine room, in
discharge, slight vacuum is expected to be
consideration of air intake resistance in
created at the engine room.
engine.

47
Chapter 3 Noise

Sound is a kind of wave that transmits via 1.1.2 Sound level


matter. The loudness and pitch of sound in Human can perceive sound pressure of 20
air is perceived through the vibration of the ȝPa to 20 Pa. Then, sound pressure is
eardrum by human. converted logarithmically into the three-
Noise is all sound that repels human. Even digit numbers expressed with the unit
music that entertains one person may be called decibel (dB). Sound pressure level,
only noise for the other person. Noise that which is expressed with the logarithm of
is generated in the installation site of ratio of evaluated sound pressure to
engine-driven unit may develop into a big reference (20 ȝPa), is obtained by the
problem. formula below.
Sound pressure in the audible range
1. Sound property corresponds to 0 to 120 dB.
Noise obeys the laws of natural science, P
like usual sound. So, this section SPL = 20 log10
P0
describes the basic property of sound Where:
shortly.
SPL: Sound pressure level (dB)
1.1 Sound evaluation P0: Reference sound pressure
Apart from ultrasonic sound used for of 2 x 10-5 (Pa)
distance measurement or underwater P: Evaluated sound pressure (Pa)
search, all sound perceived by human is Minimum SPL
evaluated on basis of acoustic sense. -5
= 20 log10 2 x 10-5 = 0 (dB)
1.1.1 Property 2 x 10
Sound wave that transmits in air is wave Maximum SPL
accompanied by pressure variation (sound = 20 log10 20
= 120 (dB)
pressure). Human ear can perceive sound 2 x 10-5
of about 20 to 20,000 Hz. Sound property 1.1.3 Weighting
is as follows.
Auditory sensitivity of human ear depends
ŒFrequency: Wave number per one on not only sound pressure but also
second. Frequency determines sound frequency, unlike microphone. Low-
pitch. frequency sound seems soft and high-
ŒLevel: Indicates wave amplitude. High frequency sound seems loud. Therefore,
level means high amplitude. as shown in Table 3-1, the weighted
ŒTone quality: Determines sound difference decibel values are used to evaluate sound
depending on waveform. related to human, and A-scale or dB (A) is
used as unit.

Table 3-1 Weighted value


Frequency (Hz) 31.5 63 125 250 500 1000 2000 4000 8000
Weighted value (dB) -39.4 -26.2 -16.1 -8.6 -3.2 0 +1.2 +1.0 -1.1

48
Chapter 3 Noise

Sound before weighting collected with 1.1.6 Strength of sound source


microphone is the flat and linear decibel Sound power level that shows the strength
value. of sound source is evaluated by the
1.1.4 Decibel synthesis formula below. Sound pressure changes,
depending on the distance from sound
The pressure level of synthetic sound
source, attenuation due to transmission,
consisting of two or more sounds is
refraction, diffraction, or interference,
evaluated by the following formula.
reflection, or wind direction. However,
P = 10 log10 10P1/10 + 10P2/10 + · · · + 10Pn/10 original sound does not change.

Where: I
PWL = 10 log10
P: Synthetic sound pressure level (dB) I0
Pn: Individual sound pressure level (dB) Where:
For two 60 dB sound sources, the sound PWL: Sound power level (dB)
pressure level is as follows. I0 : Strength of reference sound
x 10-12 (watt)
P = 10 log10 106 + 106 = 63 (dB) I: Strength of sound source (watt)
The above shows that double acoustic
intensity corresponds to difference of 3 dB. 1.2 Distance decay
As shown in Fig. 3-1, sound wave emitted
1.1.5 Decibel subtraction from sound source diffuses in a spherical
The known sound pressure can be shape, decreasing its energy density.
eliminated from the pressure of the Therefore, the farther away sound wave
synthetic sound consisting of two or more goes, the lower sound pressure level goes.
sounds by the following formula. The relation between distance and sound
pressure level is derived from the formula
P' = 10 log10 10P/10 – 10P1/10 – · · · – 10Pn/10 below. In general, the reference sound
Where: pressure level is measured at a distance of
P': Sound pressure level 1 m from sound source.
after subtraction (dB) L0
S = S0 + 20 log10
When 90 dB sound is subtracted from 93 L
dB synthetic sound, 90 dB sound remains. Where:
This shows that 1/2 of acoustic intensity S: Sound pressure level at
corresponds to difference of 3 dB. measurement point (dB)
S0: Sound pressure level at
P' = 10 log10 109.3 – 109 = 90 (dB) reference point (dB)
L0: Distance from sound source
to reference point
L: Distance from sound source to
measurement point

49
Chapter 3 Noise

Sound pressure level


at measurement point
Sound pressure level
Sound
at reference point
source

L0 Measurement
distance

Fig. 3-1 Distance decay of sound

However, the above value is the theoretical distance decay of noise is 70 to 80% of the
value based on the assumption that sound theoretical value. Fig. 3-2 shows the
source is a point. When sound source is theoretical and actual values.
large engine room or package, the

100
90
80
Sound pressure (dB)

70
Actual
60
Theoretic
50
40
30
20
10
0
1 2 3 4 5 10 20 30 40 50 100 200 300 500 1000
Distance from sound source (m)

Fig. 3-2 Distance from sound source and sound pressure level

1.3 Transmission loss As shown in Table 3-2, in sound insulation


When sound wave goes through matter, it with steel plate such as duct in engine
absorbs energy and sound pressure room and enclosure panel, some
lowers. Transmission loss is proportional frequencies do not obey the mass law
to matter mass per unit area and the because of the coincidence effect.
logarithm of sound frequency, according to
Table 3-2 Limiting frequency
the mass law, as follows.
Plate thickness (mm) Frequency (Hz)
TL = 18 log10 M + 18 log10f – 44 2.3 5,338
Where: 3.2 3,837
TL: Transmission loss (dB) 4.0 3,069
5.0 2,455
M: Weight per unit area (kg/m2)
6.0 2,046
f: Sound frequency (Hz) 8.0 1,535

50
Chapter 3 Noise

In the design of sound insulation structure, As shown in Fig. 3-3, supposing that
note that the transmission loss is lower matter around sound source reflects sound
than the value based on the mass law near fully, the theoretical pressure level of sound
this limiting frequency. that was reflected from the multiple faces
and focused on specific direction is as
1.4 Reflection follows.
Soft matter absorbs energy with vibration,
so it does not reflect much sound. S = S 0 + 10log10 Q
Meanwhile, more rigid matter reflects more Where:
sound. Therefore, when rigid matter such S: Sound pressure level at
as building and wall exists around engine measurement point (dB)
room or packaged engine-driven unit, S 0 : Sound pressure level at
sound pressure applied to the measuring reference point (dB)
point is higher in comparison with flatland Q: Directivity factor
case.

+ 3dB
Sound
Q=2
source

+ 6dB

Q=4

+ 9dB

Q=8

Fig. 3-3 Sound pressure rising due to reflection

51
Chapter 3 Noise

1.5 Refraction In the daytime, sound refracts upwards


Sound transmits via air at a speed of because air temperature is high near the
331 m/s at 0ºC. High temperature and low ground and is low in the sky. Meanwhile,
air density increases sound speed. as shown in Fig. 3-4, in the nighttime,
sound refracts downwards and transmits
far.

Sound
source

Fig. 3-4 Sound refraction in nighttime

1.6 Diffraction low-pitched sound sneaks around to the


As shown in Fig. 3-5, sound diffuses back of soundproof wall, which is called
outsides from gap or long-wavelength diffraction.

Sound
source

Sound
source

Fig. 3-5 Sound wave diffraction

Wave length of high-pitched sound is short Then, the places which sound is unlikely to
relatively. For example, wave length of 2 be transmitted to like a shadow of light will
kHz sound that transmits at a speed of 331 be created behind an obstacle.
m/s at 0°C is only 167 mm.

52
Chapter 3 Noise

Meanwhile, wavelength of 20 Hz sound is


16.6 m, and wavelength of 200 Hz sound is
about 1.7 m. Low-pitched sound may
sneak around to the back of soundproof
wall, thereby generating noise in wide area Sound Sound
that cannot be seen from sound source. source source

1.7 Interference
As shown in Fig. 3-6, two waves overlap
and intensify or weaken each other, which
Fig. 3-6 Sound wave interference
is called interference. When two waves
transmit, they strength each other in one 1.8 Wind direction
position and weaken each other in the
Wind speed influences the ground speed
other position.
of sound. The direction of strong wind in
This phenomenon is used for noise high position may influence sound
reduction (active silencer) in soundproof pressure measurement.
wall in express highway, in which top of
As shown in Fig. 3-7, refraction that occurs
noise wave and bottom of speaker sound
due to difference in wind speed between
overlap to synthesize low-amplitude wave.
the ground and sky creates shadow region
toward the wind of 2 to 3 m/s. In the
shadow region, sound pressure level is low
considerably. Meanwhile, in the lee of
sound source, sound pressure level may
be higher.

Wind

Sound
source Shadow region

Fig. 3-7 Shadow region

53
Chapter 3 Noise

2. Noise The environmental standards for noise to


Noise is defined as all sound that repels observe in order to maintain life
human. Noise harms acoustic sense and circumstance and protect human health
spiritual health. Therefore, in Japan, the are, according to the Basic Environmental
environmental standards for noise are Law, as follows.
established. First Environmental Standard:
Article 1. The environmental standard shall
2.1 Environmental standard be defined in each region type and time in
Some of the Basic Environment Law about accordance with Table 3-3. Region to
noise is excerpted as below (Decibel value which each region type is applied shall be
shows the value in A-scale). specified by the prefectural governor.

Table 3-3 Environmental standard value


Standard value
Region type
Daytime Nighttime
AA 50 dB or lower 40 dB or lower
A and B 55 dB or lower 45 dB or lower
C 60 dB or lower 50 dB or lower

Note: 3. A is applied to region exclusively for


1. Daytime is from 6 a.m. to 10 p.m., residence.
and nighttime is from 10 p.m. 4. B is applied to region mainly for
to 6 a. m. residence.
2. AA is applied to region that requires 5. C is applied to region for commerce
silence, e.g., region where rest and industry with residences.
home, social welfare facilities, etc. However, for the region that faces road, the
are established. standard values shall be defined in
accordance with Table 3-4 (not Table 3-3).

Table 3-4 Standard value in region that faces road


Standard value
Regional division
Daytime Nighttime
Region that faces road with 2 or more lanes 60 dB or lower 55 dB or lower
in A region
Region that faces road with 2 or more lanes
in B region or road with lanes in C region 65 dB or lower 60 dB or lower

54
Chapter 3 Noise

Remark: 2.2.2 Exhaust sound


Lane is zonal roadway that has enough Original exhaust sound may produce the
width for one column of car to run safely highest noise. In general, the sound is
and easily. In this case, for area near attenuated by silencer and then is
arterial road, the standard values shall be discharged outdoors. Therefore, exhaust
defined in accordance with Table 3-5 as an outlet is sound source.
exception. The data of exhaust noise measured at the
distance of 1 m and in 45° direction from
Table 3-5 Standard value in region that engine exhaust outlet is required for the
faces arterial road silencer design. MHI, upon request, can
Standard value provide the noise data.
Daytime Nighttime 2.2.3 Intake sound
70 dB or lower 65 dB or lower Sound created at engine turbocharger is
absorbed by air cleaner or air silencer and
2.2 Noise source rarely becomes noise source.
All objects that emit sound can be noise
source. However, in this chapter, the target 2.3 Transmission route
is only engine-driven unit. Sound wave produced by object vibration
The openings of exhaust outlet, extended transmits through air density, that is, as
intake air inlet, ventilation air inlet and pressure wave. When sound wave collides
outlet at engine room or package emit with an object in its way, the sound wave
noise to the surrounding. And, the outdoor produces vibration and then transmits in
cooling tower, remote radiator, air the other form via solid. Therefore,
conditioner, pump, etc. directly affects the structure vibrated with main noise may
ambient noise level. emit wave in the surrounding wide area,
thereby diffusing noise.
2.2.1 Machine sound
Engine running at low speed produces
Machine sound is produced by structure
high-level low-frequency sound, which may
vibration. Engine, driven equipment,
be the secondary large noise source in
auxiliary equipment such as water or oil
resonance with the surrounding structure
pump and pressure-regulating valve,
with low natural frequency.
foundation floor, or facilities such as piping,
High-frequency sound is prone to go
support, and ventilation duct may be noise
straight ahead and apply high sound
source.
pressure to the place from which sound
The fan for radiator or generator pushes air
source can be seen directly. And, low-
by its blades intermittently, thereby
frequency sound transmits in wide area
producing pulse sound or wind noise.
with diffraction. Therefore, ambient noise
MHI, upon request, can provide the data of
level depends on the frequency
machine noise measured at a distance of
components of sound source and
1 m from engine.
transmission route.

55
Chapter 3 Noise

2.4 Measurement and evaluation 2.4.2 Environmental condition


The installation personnel must measure Noise level in the measurement points
and evaluate noise properly and notify the depends on distance from sound source,
authorities concerned of it. attenuation due to transmission, refraction,
diffraction or interference, reflection, or
2.4.1 Method
wind direction.
In Japan, the measurement and evaluation
Sound is absorbed by soil and is almost
of noise are defined, according to the Basic
reflected by asphalt, which causes the
Environment Law, as follows.
difference of 2 to 2.5 dB (A) in the
ŒNoise is evaluated based on equivalent
measurement. High-temperature and
sound level.
high-humidity air absorb and attenuates
In principle, noise is evaluated in each
sound. For example, the difference
time division over full time based on
between winter (temperature: -10°C,
equivalent sound level.
humidity: 30%) and summer (temperature:
ŒNoise is evaluated in the time when
20°C, humidity: 70%) is 1.2 dB (A) at a
average noise level is measured
distance of 100 m and 0.4 dB (A) at an
throughout the year.
altitude of 30 m.
ŒIn noise measurement, the noise meter
The difference in temperature or wind
that meets the requirements of the
speed between the ground and sky causes
measurement law is used.
sound refraction. Therefore, noise level
In this case, A-scale property is used in
may depend on wind direction in the
frequency weighting circuit.
measurement points.
ŒIn principle, noise is measured in
The conditions of sound measurement
accordance with the Japan Industrial
such as date, weather, temperature,
Standards.
humidity, and wind speed must be
Consult with the authorities concerned in
recorded to submit them to the authorities.
advance to determine the region type of
the installation site of engine-driven unit 2.4.3 Correction of background noise
stipulated by the Basic Environment Law Background noise is emitted from car, etc.
and the number and time of noise As described in Section 1.1.4, "Decibel
measurement. synthesis", background noise increases
In measurement of noise from engine room noise level in the measurement points.
or package, engine-driven unit and Therefore, in evaluating the measured
auxiliary equipment must be operated with noise level, background noise must be
the rated output, and the equipment measured for correction.
controlled by temperature or pressure must
be operated, too. Otherwise, noise at the
boundary with adjacent land may exceed
the environmental standard.

56
Chapter 3 Noise

Basically, stop engine-driven equipment


p/10 pb/10
and all auxiliary equipment after noise P0 = 10 log10 10 – 10p
measurement and measure background Where:
noise. And, then eliminate the contribution
P0: Noise level [db(A)]
of the background noise with decibel
subtraction described above to evaluate P: Measured value [db(A)]
the actual noise level. Pb: Background noise level [db(A)]
The corrected noise level must not exceed For reference, Table 3-6 lists the
the standard value in the region type differences in sound pressure between
applied in accordance with the Basic noise and background noise and the
Environment Law, as follows. contribution of background noise to the
measurement. For example, when noise
pressure is 50 dB and background noise
pressure is 42 dB, the difference in sound
pressure is 8 dB and the contribution to the
measurement is 0.6 dB.

Table 3-6 Composition of different sound pressure (dB)


Difference in 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
sound pressure
Contribution 3.0 2.5 2.1 1.8 1.5 1.2 1.0 0.8 0.6 0.5 0.4 0.3 0.3 0.2 0.2 0.1

3. Noise reduction The technology to reduce noise belongs to


The installation personnel must control the realm of construction and acoustic
noise emitted from engine room to meet engineering. Therefore, in some cases,
the environmental standards of noise at the consult with the experts.
boundary with adjacent land. The designer
of engine-driven equipment must design
3.1 Frequency analysis
enclosure structure so that package noise For sound reduction or measure, the target
can be reduced. sound frequency (octave) must be
Good ventilation and low-level ambient analyzed. Octave means double
noise are the contradictory requirements frequency. Octave band ranges from
for the design of engine room or package. maximum to minimum frequency centering
However, maintaining the heat balance for on the central frequency. Octave of 1/1 or
engine is the top priority in any installation 1/3 is used for noise analysis.
environment. Table 3-7 lists the central frequencies of
1/1 octave band in the audible range.

Table 3-7 Central frequency of 1/1 octave band


Frequency (Hz) 31.5 63 125 250 500 1k 2k 4k 8k 16k

57
Chapter 3 Noise

3.2 Vibration isolation However, note that, for standby generator


Noise produced because of vibration from set to which the Fire Defense Law is
engine-driven unit is unavoidable. applied, nonflammable materials must be
Meanwhile, secondary noise produced by used.
vibration via foundation or piping must be When glass wool is applied to wall in
prevented. engine room, ceiling, ventilation duct,
Vibration that occurred in building structure enclosure panel, etc., its surface must be
or piping will be transmitted far in wide covered with flexible cloth to prevent glass
area, thereby may cause low-frequency fiber from dispersing. Inhaled glass fiber
noise problem. does not harm human, unlike asbestos.
The surrounding floor and foundation of However, glass fiber staying on the skin
engine-driven unit must be isolated from causes itching.
each other or vibration isolators must be Sound absorbing materials are effective in
arranged to reduce vibration. Flexible the range of high-pitched engine noise.
joints must be arranged to the connection Meanwhile, in low-pitched sound area, the
of an engine and the piping for exhaust and materials are low in efficiency of sound
cooling system. And, the piping support absorption, and frequency of attenuated
must have vibration isolation structure, sound depends mainly on the material
depending on the installation condition. density. Therefore, check the catalogue of
sound absorption material or refer to the
3.3 Sound absorption selling office.
Supposing that sound source is enclosed
by rigid structure, sound is reflected inside 3.4 Sound insulation
repeatedly without attenuating, thereby Noise is emitted mainly from ventilation
increasing its energy density. opening of engine room or package.
Actually, engine-driven unit or auxiliary For high frequency range, basically,
equipment which is sound source cannot acoustic wall should be arranged so that
be sealed closely. Sound pressure in sound source cannot be seen outdoors to
engine room or package will be leaked prevent direct sound emission outdoors.
from the opening such as ventilation air At least louvers should be arranged so that
inlet and outlet to outside. Therefore, noise engine-driven unit or auxiliary equipment
must be attenuated to the greatest extent cannot be seen from the ventilation
possible in the engine room or package to opening at all. However, it may be not very
reduce sound pressure applied outside. effective for sound insulation, depending
Low-density flexible materials can be used on the requirements of ambient noise.
for sound absorption because they vibrate Louvers cannot insulate engine noise fully
with sound wave, thereby converting because low-frequency sound is prone to
energy into heat. In general, urethane diffract and transmit outside from gap.
foam or glass wool can be used.

58
Chapter 3 Noise

In general, transmission loss is high in 3.5 Silencer


composite material which contains various
3.5.1 Ventilation silencer
laminated materials, in comparison with
single material such as sound absorption In general, the ventilation opening of low-
material and steel plate. This is the key noise type of package or engine room in
point in the acoustic wall design. the region which has tough noise
There is no problem in the engine room in standards must have noise absorption
building made of efficiently thick concrete. structure.
Meanwhile, in case of enclosure, noise Inner acoustic materials or sound
may transmit, depending on the thickness insulating board may not reduce noise
of its outer plate. sufficiently. In this case, various silencers
As described above, attenuation of sound using sound property such as duct with
pressure in wall is proportional to its acoustic materials applied inside, cell-type
weight. Thick materials achieve high or split-type duct, elbow-type silencer, and
performance of sound absorption. sound absorbing chamber can be
However, performance of sound absorption designed and assembled.
is low in certain frequency, which is called Silencer design requires the knowledge of
coincidence effect. acoustic engineering. Therefore, adopt
In case of enclosure, its outer plate commercially available products, or
vibrates with sound pressure of engine and request the design of the experts. In this
pulsating of air flow discharged from case, the octave analysis data of engine
radiator or ventilation, which may cause noise measured at a distance of 1m must
ambient noise like flat speaker. This is the be provided to them.
key point in the panel structure design. 3.5.2 Exhaust silencer
Tail pipe and chimney is the final outlet of
exhaust noise. Therefore, silencer must be
used to reduce exhaust sound to the level
that meets the standard of ambient noise at
boundary with adjacent land.
In silencer order, the octave analysis data
of exhaust noise measured at a distance of
1 m and in the direction of 45° from the
engine exhaust outlet must be provided to
the manufacturer.

59
February 2010 GUIDE TO CAPACITY SELECTION AND INSTALLATION PLANNING Installation Planning Pub. No.98CAB-61000
⴫⚕
Printed in Japan
Pub. No. 98CAB-61000

You might also like