10-MPK708A Trouble list

In case of failure occurring or working under irregular conditions during the time
of elevator’s running, the commissioning personne can conduct the failure predication

by the means of the failure logging of main controller、inverter. MPK708Acan store

50 pieces of failure logging.

No.of Whether the floor


Connect Method of renew
fault display the failure
yes,computer Security circuit turn
E1 Security circuit opened
register the failure. to gight
yes,computer
Door Lock error Or over time Door Lock closed
register the failure.
E2
Door Lock open , elevator yes,computer
Door Lock closed
stop register the failure.
Cannot detect the door zone No ,register the Only register,not
E3
signal or crawl time over(10s). failure treat with
Can’t Find the Deceleration
Point ( run time yes,computer Level floor renew
E4
over“Floor protect”menu register the failure. after door opened
time limit)
yes,computer Up Limited Switch
E5 Up Limited Switch Opened
register the failure. renew.
yes,computer Down Limited
E6 DownLimited Switch Opened
register the failure. Switch renew.
No ,register the
E7 Deceleration Switch Error Slow leveling floor
failure
yes,computer
E8 Contact Not Release Release the point
register the failure.
Taco Direction Error or yes,computer Level floor renew
E9
impulse error. register the failure. after door opened
yes,computer
E10 Brake Error Check or power off
register the failure.
yes,computer
E11 Run Time Error Check or power off
register the failure.
yes,computer Connect the monitor
E12 Inverter Error
register the failure. and control point
yes,computer Check or door lock
E13 Door Contact not Release
register the failure. close
E14 Take count of impulse error No , register the After leveldown run
failure to lower base station
No.of Whether the floor
Connect Method of renew
fault display the failure
revise
The number of impulse and No ,register the
E15 Do not treat with
inductor is not same failure
In the condition of E22the signal
E16 / /
of terminal station wrong.
The lock of car door closed
E17 over 2s , which of landing door / /
is no response.
Start up over 5Scan notcheck yes,computer Check or power
E18
the input point oftransducer. register the failure. off
The input point of transducer yes,computer Input point turn
E19
closed register the failure. right.
Switch opened the elevator is No ,register the
E20 /
not at terminal station failure
Elevator stop yes,computer
E21 Switch resleased
,switchofbrakeis closed. register the failure.
No ,register the Elevator turn to
Elevator is at terminal station,
E22 failure, turn to down down terminal
speed change switch closed
terminal station station
Button locked and the time
E23 / /
over 30s
The door lock closed over 3S,
and the switch of close door
final limit is not open, the
computer will register the failure Start up inspection
E24, the outer calling and inner or the door lock open
yes,computer
E24 selection displayt E24 at the over 2S,or the final
register the failure.
same time, the door will open in limit of close door
the opposite direction .If there is open.
not 2# door operator, the input
point of close door final limit
should not be connected.
There is pre-open door
Detect the input
function, if the PM708 yes,computer
E25 point of door zone or
enlargement board cannot detect register the failure.
start up inspection.
the input point of door zone.
Detect the PM708
There is pre-open door enlargement board or
function, if the PM708 yes,computer start up inspection or
E26
enlargement board can not be register the failure. cancel the test
detected function of
enlargement board
E27 There is pre-open door yes,computer Start up inspection
No.of Whether the floor
Connect Method of renew
fault display the failure
function, if the PM708
enlargement board cannot detect
register the failure.
the input of safety touching
point, the lift stop.
There is pre-open door
function, if the PM708
enlargement board can not
/
E28 detect the input of speed test, the
door will not open when the lift
arrive the appointed stop and the
open door button can not work.