A17018 Structural Drawings

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

DRAWING LIST

Sheet
Number Sheet Name

S0 COVER SHEET
S1-01 FOUNDATION PLAN
S1-02 ROOF PLAN
S2-01 FOUNDATION SECTIONS
S2-02 ROOF SECTIONS
S3-01 GENERAL NOTES AND TYPICAL DETAILS
S3-02 TYPICAL DETAILS
S3-03 TYPICAL DETAILS
S3-04 TYPICAL DETAILS
S3-05 TYPICAL DETAILS

NOTE: EXISTING CONDITIONS AS SHOWN ON THE


STRUCTURAL DRAWINGS ARE BASED UPON INFORMATION
AVAILABLE AT THE TIME THAT DRAWINGS WERE
PREPARED AND ARE TO BE VERIFIED BY THE CONTRACTOR
ON SITE.

CLEARVIEW MEADOWS ELEMENTARY SCHOOL


ANY VARIATIONS ARE TO BE REPORTED AND INSTRUCTIONS
RECEIVED BEFORE PROCEEDING.

ADDITION stephenson
ENGINEERING
2550 Victoria Park Ave. Suite 602
THIS COVER SHEET IS A DIAGRAMATIC 3D VIEW AND DOES NOT FORM PART OF THE DOCUMENTS Toronto ON M2J 5A9 Tel: (416) 635 9970
www.stephenson-eng.com info@stephenson-eng.com
10 8 7 CONCRETE MIX SCHEDULE
STRENGTH AT SLUMP AT AIR MAXIMUM EXPOSURE
5 28 DAYS (Mpa) DELIVERY (mm) ENTRAINMENT W/C RATIO CLASSIFICATION

Sim 3 150 FROST SLAB FOOTINGS & INTERIOR 25 80 ± 20 ---- TO SUIT N

REVISION
2 S2-01 -SEE SECTION FOUNDATION WALLS
S2-01 AND ARCH

200

ISSUED FOR PERMIT AND TENDER


INTERIOR FRAMED SLABS 25 80 ± 20 ---- TO SUIT N
B.O.F. EL. 215.50 200 200 B.O.F. EL. 215.50

370
WALLS AND COLUMNS

370

ISSUED FOR COORDINATION


80% WORKING DRAWINGS
T T (1) TO SUIT
GROUT FOR 15 MIN. CONFORMING TO
MASONRY FILL / CSA A179 ---- ---- ----

370
(FINE GROUT)
BOND BEAMS SUPERPLASTICIZER
MAY BE USED
SEE SLAB-ON-GRADE TYPICAL
DETAIL T-C09 FOR TYPICAL
EXTERIOR CONCRETE

No. DATE
18_08_10
18_05_22
18_04_30
B.O.F. EL. 215.50
CONSTRUCTION JOINTS AND
SLABS, SIDEWALKS, 32 80 ± 20 5-8% 0.45 C-2
SAWCUT CONTROL JOINTS CURBS AND GUTTERS

B.O.F. EL. 215.50

B.O.F. EL. 215.50


B.O.F. EL. 215.50 (TYPICAL)

3
2
1
(2) BEFORE ADDITION OF
INTERIOR SUPERPLASTICIZER THE CONTRACTOR SHALL CHECK ALL DIMENSIONS
SLAB THICKENING UNDER BLOCK WITH THE LATEST ISSUE OF
SLAB-ON-GRADE SUPERPLASTICIZED 25 50 ± 20 ---- 0.50 N
PARTITIONS ABOVE. SEE ARCH. DWGS AFTER ADDITION OF ARCHITECTURAL, MECHANICAL AND ELECTRICAL
FOR LOCATION AND EXTENT. SEE ALSO SUPERPLASTICIZER DRAWINGS. REPORT ANY DISCREPANCIES TO THE
TYPICAL DETAIL DRAWINGS. (TYP.) ARCHITECT BEFORE PROCEEDING WITH WORK.
150 ± 20

LEAN MIX 5 150 MIX ---- NO SUIT N DRAWINGS ARE NOT TO BE SCALED. CONTRACTOR MUST
CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS ON
S S THE PROJECT; AND MUST REPORT ANY DISCREPANCIES
TO THE CONSULTANTS BEFORE PROCEEDING WITH THE
Sim EXPOSED EXTERIOR
2 WORK. THE USE OF THIS DRAWING OR PART THEREOF IS
WALLS, FOUNDATION 25 80 ± 20 4-7% 0.55 F-2 FORBIDDEN WITHOUT THE WRITTEN APPROVAL OF THE
S2-01 WALLS AND COLUMNS CONSULTANTS.

FROST SLABS 35 80 ± 20 5-8% C-1


0.40

B.O.F. EL. 215.50


Sim 1) FINE GROUT TO CONSIST OF (BY VOLUME)
4 1. PART PORTLAND CEMENT (MASONRY CEMENT IS NOT ACCEPTABLE)
S2-01 NEW
2. 1/2 TO 3 PARTS FINE AGGREGATE (SEND) AND NO COARSE AGGREGATE.
B.O.F. EL. 215.50 ADDITION
2) SYNTHETIC FIBRES ADDED AT BATCHING PLANT. REFER TO SPECIFICATION.
NOTE. IF CONCRETE IS TO BE "PUMPED" INCLUDE DETAILS IN MIX DESIGN SUBMISSION.
R R
190

DESIGN CRITERIA NOTES


1. GENERAL
1.1. THE PROJECT HAS BEEN DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF THE 2012 OBC
SDF (O. REG. 332/12 AS AMENDED) INCLUDING CLAUSES 4.1.6.1(1), 4.1.6.4(3), 4.1.7 AND 4.1.8.

SDF
150 FROST SLAB 1.2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR WHO IS SUPPLYING AND INSTALLING EQUIPMENT, THAT ALL ELEMENTS OF
STRUCTURES LISTED IN TABLE 4.1.8.18 OF THE OBC 2012 ARE DESIGNED IN ACCORDANCE WITH CLAUSE 4.1.8.18.
B.O.F. EL. 215.50

-SEE SECTION

200
1.3. BUILDING IMPORTANCE CATEGORY (SNOW, WIND, AND EARTHQUAKE) IS HIGH
200 AND ARCH 1.4. STIFF ELEMENTS NOT PART OF SFRS SHALL BE SEPARATED FROM THE STRUCTURE AS PER OBC CLAUSE 4.1.8.3 (6a). EXISTING

B.O.F. EL. 215.10


SCHOOL
B.O.F. EL. 215.50

EXAMPLES INCLUDE, BUT NOT LIMITED TO MASONRY PARTITIONS, BRICK VENEER, PRECAST CLADDING ETC. IT IS THE
B.O.F. EL. 215.10

RESPONSIBILITY OF THE SUBCONTRACTOR TO PROVIDE SHOP DRAWINGS, STAMPED, SIGNED AND DATED BY A
PROFESSIONAL ENGINEER DEMONSTRATING COMPLIANCE. PROVIDE MINIMUM 15mm SEPARATION UNLESS NOTED

B.O.F. EL. 215.10

200
OTHERWISE.

4
Sim 370 1.5. MISCELLANEOUS METAL, PRECAST AND STAIR FABRICATORS SHALL:
1.5.1. PROVIDE SHOP DRAWINGS TO THE ARCHITECT PRIOR TO FABRICATION; STAMPED, SIGNED AND DATED BY A
KEY PLAN
S2-01 PROFESSIONAL ENGINEER.
Qx Qx 1.5.2. DESIGN ALL GUARDS TO MEET LATERAL LOADS DESCRIBED IN OBC 4.1.5.14.
190
B.O.F. EL. 215.10
1.5.3. DESIGN ALL HANDRAILS TO MEET LOADS DESCRIBED IN OBC 3.4.6.5(12).
1.5.4. DESIGN ALL STAIRS TO SUPPORT A MINIMUM LIVE LOAD OF 4.8kPa.

Q Q 2. LATERAL LOADS ON STRUCTURE


150 FROST SLAB 2.1. WIND
q(1/50) = 0.39kPa
-SEE SECTION Ce = (h/10)^1/5 NOT LESS THAN 0.9.

200
200 AND ARCH Cg = 2.0
Cp = AS PER FIGURE I-15 OF USER'S GUIDE - NBC 2010 STRUCTURAL COMMENTARIES

B.O.F. EL. 215.10


(PART 4 OF DIVISION B).
2.2. SNOW
TOP OF Ss = 2.7 kPa Sr = 0.4 kPa

200
370 SLAB-0N-GRADE 2.3. EARTHQUAKE
Sa(0.2) = 0.130 PGA = 0.040 Fa = 1.3
EL. 217.53m GEODETIC Sa(0.5) = 0.097 SITE CLASS =D Fv = 1.4
190 190 Sa(1.0) = 0.060 Rd = 1.5 Ie = 1.3
2 U.N.O. Sa(2.0) = 0.020 Ro = 1.5 IeFaSa(0.2) = 0.220
S2-01
stephenson
SFRS CONSISTS OFCONVENTIONAL MASONRY SHEAR WALLS.
4 METHOD OF ANALYSIS : STATIC
S2-01 3. FOUNDATION WALLS ENGINEERING
6
3.1. WALLS RETAINING EARTH ARE DESIGNED TO SAFELY WITHSTAND HORIZONTAL EARTH PRESSURE
S2-01 (P=K (Wt.h+q) 2550 Victoria Park Ave. Suite 602
K = 0.4 Toronto ON M2J 5A9 Tel: (416) 635 9970
Px Px Wt = 22kN/m^3 www.stephenson-eng.com info@stephenson-eng.com
q = 12kPa
h = DEPTH IN METRES
OFES SI ON A L
PR
B.O.F. EL. 215.10

3.2. THE WALLS HAVE BEEN DESIGNED ASSUMING FREE DRAINING BACKFILL OR THE USE OF A DRAINAGE CORE TO PREVENT THE

ED

EN
BUILD-UP OF HYDROSTATIC PRESSURE. 18_08_10

NS

GIN
5

LI CE

EER
S2-01 150 FROST SLAB H.A. McCALLUM
B.O.F. EL. 215.50

-SEE SECTION
AND ARCH SITE PREPARATION NOTES FOR SLAB-ON-GRADE
200

O
PR
P P

RI
VI TA

O
B.O.F. EL. 215.50

NC
200 E OF ON
B.O.F. EL. 215.10

(WITHIN BUILDING ENVELOPE)


B.O.F. EL. 215.10

FOUNDATION PLAN 1. THE AREA WITHIN THE BUILDING SHALL BE STRIPPED OF THE UPPER LAYER SOIL, FILL, ORGANICALLY
200 200

CONTAMINATED MATERIAL AND RUBBLE AND TO A MINIMUM OF 400mm (16") BELOW THE UNDERSIDE OF THE SLAB ON GRADE. OFES SI ON A L
1 : 100 2. THE EXPOSED SUB-GRADE SHALL BE EXAMINED AND APPROVED BY THE SOIL CONSULTANT.
PR
190

ED

EN
B.O.F. EL. 215.50
190

B.O.F. EL. 215.10


200

18_08_10

NS

GI N
3. THE ENTIRE AREA SHALL BE PROOF ROLLED WITH A HEAVY COMPACTOR TO A MINIMUM OF100% STANDARD PROCTOR MAX. DRY
OO OO 1. ALL FOOTINGS SHALL BE FOUNDED ON SAND CAPABLE OF SUSTAINING 150 kPa.(SLS)

LI CE
Sim

EE R
DENSITY AND TO THE APPROVAL OF THE SOIL CONSULTANT.
2 200 2. REFER TO SOILS REPORT NO. G5260 DATED DECEMBER 2017. PREPARED BY McCLYMONT R RAK ENGINEERS, INC. J. C. GASDIA
4. ANY LOOSE OR SOFT SPOTS ENCOUNTERED SHALL BE SUB-EXCAVATED AND BACKFILLED WITH COMPACTED APPROVED MATERIAL.
S2-01 150 FROST SLAB 3. SOIL AT THE UNDERSIDE OF THE FOOTINGS IS TO BE INSPECTED AND APPROVED BY A REPRESENTATIVE OF A SOILS CONSULTANT 100169574
B.O.F. EL. 215.10

200 370 5. FILL REQUIRED TO RAISE THE GRADES SHALL BE COMPRISED OF APPROVED GRANULAR 'B' TYPE 1 CONFORMING TO OPSS 1010
BEFORE PLACING CONCRETE.
B.O.F. EL. 215.50

150 FROST SLAB -SEE SECTION


B.O.F. EL. 215.10

370 PLACED IN SUCCESSIVE LOOSE 200mm(8") LAYERS EACH COMPACTED TO AT LEAST 100% OF ITS STANDARD PROCTOR MAXIMUM DRY

O
PR
B.O.F. EL. 215.50

4. UNDERSIDE OF WALL FOOTINGS TO BE AT ELEVATIONS AS NOTED.

RI
VI TA

O
-SEE SECTION AND ARCH DENSITY. NC
E OF ON
5. SLAB - ON - GRADE TO BE 100 mm THICK REINFORCED SYNTHETIC FIBRES. (SEE SPECIFICATION) 6. THE LAYER IMMEDIATELY BELOW THE SLAB-ON-GRADE SHALL BE 200mm (8") OF 19mm CLEAR STONE COMPACTED TO MIN. 100%
AND ARCH Sim 6. TOP OF SLAB - ON - GRADE TO BE AT FINISHED FLOOR DATUM ELEVATION, 217.53 m EXCEPT AS CROSSED AND NOTED. TOS = TOP OF SLAB. STANDARD PROCTOR MAX. DRY DENSITY.
2
EXISTING BUILDING S2-01
7. CENTRELINES OF COLUMNS, CAPS AND FOOTINGS ARE COINCIDENT UNLESS OTHERWISE NOTED. 7. ALL PROCEDURES, EQUIPMENT AND MATERIALS SHALL BE APPROVED BY THE SOIL CONSULTANT WHO SHALL CONDUCT SUFFICIENT Simcoe County
8. PROVIDE SLAB DEPRESSIONS, OTHER THAN THOSE SHOWN ON THE STRUCTURAL DRAWINGS, AS REQUIRED BY THE ARCHITECTURAL AND TESTS TO ENSURE THAT THE SPECIFIED MATERIALS AND DENSITIES ARE ACHIEVED.
O O MECHANICAL DRAWINGS AND SPECIFICATIONS. District School Board
200

8. THE CONTRACTOR SHALL CO-ORDINATE WITH THE SOIL CONSULTANT AND ARRANGE A SUITABLE PROGRAM FOR SAMPLING AND
200

9. SDF = STEP DOWN FOOTING. INSPECTIONS, ETC. AND NOTIFY THE ARCHITECT ACCORDINGLY.
7 10. UNLESS OTHERWISE NOTED, ALL WALL FOOTINGS TO BE 300 mm DEEP WITH 150 mm PROJECTIONS EACH SIDE. 9. EXISTING ON-SITE MATERIAL SHALL NOT BE USED WITHIN THE BUILDING AREA FOR BACKFILLING IN TRENCHES AGAINST FOUNDATION
S2-01 11. FILL REQUIRED ON BOTH SIDES OF FOUNDATION WALLS SHALL BE PLACED AND COMPACTED SIMULTANEOUSLY ON BOTH SIDES TO
8 WALLS OR UNDER SLABS-ON-GRADE.
EQUALIZE SOIL PRESSURE. 10. REFER TO THE SPECIFICATION AND THE SOIL REPORT FOR PREPARATION OF AREAS OUTSIDE THE BUILDING ENVELOPE.
S2-01 12. THE PROJECT SUPERINTENDENT MUST NOTIFY THIS OFFICE 24 HOURS PRIOR TO PLACING STRUCTURAL CONCRETE, INCLUDING STRIP 11. PROVIDE VAPOUR RETARDER MEMBRANE BELOW ENTIRE EXTENTS OR SLAB ON GRADE.
FOOTINGS.
13. SEE ALSO TYPICAL NOTES AND DETAILS.
14. SEE COLUMN SCHEDULE FOR COLUMNS, AND COLUMN FOOTINGS. CLEARVIEW MEADOWS
10 8 7 5 15.
16.
CONCRETE STRENGTHS - SEE CONCRETE SCHEDULE.
REFER TO SITE PREPARATION NOTES ON THIS DRAWING.
ELEMENTARY SCHOOL
ADDITION
17. WHERE SHOWN THUS T.O.S. -20mm.
12 Locke Avenue
Stayner, Ontario
L0M 1S0
WHERE MECHANICAL SERVICE PIPES PASS
DRAWING TITLE
THROUGH LOAD BEARING FOUNDATION WALLS
PROVIDE STEEL SLEEVES (MIN) 50Ф) LARGER
THAN PIPE (TYPICAL) FOUNDATION PLAN

LOWER ELEVATIONS AT UNDERSIDE OF COLUMN AND WALL FOOTINGS, NOTE: EXISTING CONDITIONS AS SHOWN ON THE PROJECT NO: SCALE
STRUCTURAL DRAWINGS ARE BASED UPON INFORMATION

DATE PLOTTED: 8/1/2018 8:39:32 AM


WHERE REQUIRED, BUT NOT LIMITED TO STORM, SANITARY, WATER/FIRE 20171969 As indicated
LINES AND ELECTRICAL DUCT BANKS ETC. AVAILABLE AT THE TIME THAT DRAWINGS WERE
DRAWN BY: DRAWING NO:
THE MAXIMUM SLOPE FROM THE PIPE EXCAVATION TO THE UNDERSIDE PREPARED AND ARE TO BE VERIFIED BY THE CONTRACTOR
OF ADJACENT FOOTING ELEVATIONS SHALL NOT EXCEED 7 VERTICAL AB
ON SITE.
TO 10 HORIZONTAL. CHECKED BY:
ANY VARIATIONS ARE TO BE REPORTED AND INSTRUCTIONS
RECEIVED BEFORE PROCEEDING. JG
S1-01 3
DATE:
April 26, 2018
ROOF LINTEL SCHEDULE
10 8 7 5 MECHANICAL LINTEL SCHEDULE
REFER TO LINTEL NOTES T-A06 ON TYPICAL DETAIL DRAWINGS 90 100 190
SEE ALSO SPECIFICATION WELD WALL LINTELS IN LOAD BEARING WALLS OVER MECHANICAL DUCTS ETC.
CONT. L127x76x6.4 (LLV) + VERTICAL REINF.
DRILLED 16mm DIA. HILTI HIT MARK MATERIAL TYPE REMARKS TO LINTEL-TYP. WALL CLEAR

REVISION
HY 70 ANCHORS @800 O/C SEE PLAN AND MARK MATERIAL TYPE NOTES
R3 R7 WELD DECK ANGLES THICKNESS SPAN
MAX. WELD DECK TO ANGLE. TOGETHER @ CORNERS RL1 2-L89x89x7.9 SCHEDULE

MAY VARY
LENGTHS
S2-02 S2-02 (SLOPE ANGLE TO MATCH

ISSUED FOR PERMIT AND TENDER


(TYP.) ML1 190 200-550 175x8 PLATE
DECK SLOPE) TYP INTERIOR
HSS 203x102x6.4 + **

ISSUED FOR COORDINATION


RL3 RL2 WP1 , EACH END FACE

80% WORKING DRAWINGS


360x8mm BOTTOM PLATE SEE DETAIL DL1 / S1-02 ML2 190 550-1220 2-L90x90x6
T T HSS, SEE PLAN &
CONT. DECK ANGLE C150x12 CONT. DECK ANGLE RL3 HSS 203x102x6.4 +
LINTEL SCHEDULE ML3 240 200-550 225x8 PLATE
L76x76x6.4 (TYP.) 1800 O/C MAX. L76x76x6.4 (TYP.) 180x8mm BOTTOM PLATE
(HSS WELDED TO
650 STEEL JOIST Tf = 10kN.M TORSION CONNECTION WALL PLATE EACH
650 STEEL JOIST 1800 O/C MAX. ALL EXTERIOR LINTELS SUPPORTING FACE BRICK TO BE GALVANIZED
1800 O/C MAX.
DO END) ML4 240 550-1220 2-L100x100x8

RL2
T&B CHORD BRIDGING, SEE WELDED TO HSS / BEAM EACH END.
**

RL2
NOTES AND TYPICAL DETAILS. 85 ML5 290 200-550 275x8 PLATE

No. DATE
DO

18_08_10
18_05_22
18_04_30
(TYP.)
DO 10 360 PLATE 10
DO MASONRY CORE FILL SCHEDULE 380
ML6 290 550-1220 3-L90x90x6
1st PANEL POINT BOTTOM 175x8 PLATE

3
2
1
DO CHORD BRACING, SEE NOTES MASONRY CORE FILL SCHEDULE ML7 190 + 90 200-550
+ 80x8 PLATE
DO AND TYPICAL DETAILS. (TYP.) THE CONTRACTOR SHALL CHECK ALL DIMENSIONS
DO TYPE SIZE REINF REMARKS NOTE: 2-L90x90x6 WITH THE LATEST ISSUE OF
RL2

RL2
ML8 190 + 90 550-1220

EXTERIOR ANGLES & PLATES


GALVANIZED UNLESS NOTED
ARCHITECTURAL, MECHANICAL AND ELECTRICAL

WP

WP
BOTTOM PLATES TO TERMINATE 10mm CLEAR + 1-L90x90x6
DRAWINGS. REPORT ANY DISCREPANCIES TO THE
C1 t x 400 2-15 VERT. OF SUPPORTING MASONRY-VERIFY WITH ARCH.
DO 225x8 PLATE ARCHITECT BEFORE PROCEEDING WITH WORK.

CAVITY WALLS
DO CONT. ML9 240 + 90 200-550
+ 80x8 PLATE
DO
C2 t x 600 3-15 VERT. 2-L100x100x8 DRAWINGS ARE NOT TO BE SCALED. CONTRACTOR MUST
ML10 240 + 90 550-1220
DETAIL

B1

B1
+ 1-L90x90x6 CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS ON
S DO S
CONT.
DL1 275x8 PLATE
THE PROJECT; AND MUST REPORT ANY DISCREPANCIES
DO C3 t x 800 4-15 VERT. ML11 290 + 90 200-550 TO THE CONSULTANTS BEFORE PROCEEDING WITH THE
DO S1-02 1 : 10 + 80x8 PLATE WORK. THE USE OF THIS DRAWING OR PART THEREOF IS
CONT. FORBIDDEN WITHOUT THE WRITTEN APPROVAL OF THE
3-L90x90x6 CONSULTANTS.
ML12 290 + 90 550-1220
+ 1-L90x90x6
DO C4 t x 400 x 400 4-15 VERT.

1
DO

WP
DO CONT. 1 FOR LINTELS MARKED ML ON DRAWINGS.
BEAM SCHEDULE

1
RL2

1
STEEL ROOF DECK 38mm DP. x 0.76 BNT.
WP

C3
WP
2 FOR SPANS LESS THAN 200mm - NO LINTEL REQUIRED.
SLOPE R8 SLOPE HSS102x102x6.4 3 FOR SPANS GREATER THAN 1200mm, SEE PLANS AND MAIN
DB (DIAGONAL BRACE)

STEEL ROOF DECK 38mm DP. x 0.76 BNT.


S2-02 DO t DENOTES THE WALL THICKNESS LINTEL SCHEDULE.
DO MARK BEAM SIZE NEW

W310x39
DO ADDITION
DB MASONRY CORE FILLS NOTES:
R6 WHILE EVERY EFFORT HAS BEEN MADE TO SHOW ALL LINTELS WHICH OCCUR IN LOAD
R R 1. PROVIDE CORE FILLS AS NOTED ON PLAN AND PROVIDE REINFORCEMENT AS SHOWN IN SCHEDULE. B1 W200x27
STEEL ROOF DECK 38mm DP. x 0.76 BNT.

S2-02 BEARING MASONRY WALLS, IT IS THE CONTRACTORS RESPONSIBILITY TO ENSURE THAT


DO 2. CORE FILLS EXTEND FULL HEIGHT OF WALL, FLOOR TO FLOOR UNLESS NOTED.
190

THE CORRECT SIZES AND QUANTITY OF LINTELS ARE PROVIDED


HSS102x102x6.4 3. INSTALL ALL REINFORCEMENT FULL HEIGHT BETWEEN FLOORS AND GROUT CORE SOLID FULL HEIGHT BETWEEN FLOORS UNLESS NOTED.
DO 4. WHERE CORE FILL CONTINUES TO NEXT FLOOR ABOVE, EXTEND INDICATED VERTICAL REINFORCEMENT TO PROVIDE SPECIFIED LA B2 W200x22 LINTELS IN NON-LOAD BEARING WALLS AND PARTITIONS ARE GENERALLY NOT SHOWN
DO DB

1
SPLICE WITH REINFORCEMENT OF CORE ABOVE. WHERE MASONRY WALLS START ON TOP OF STEEL BEAMS, WELD REINFORCING BARS ON THE DRAWINGS. ALL SUCH LINTELS SHALL BE PROVIDED AS REQUIRED AND SHALL

WP
CONT 76mmx6.4mm DECK WELD PLATE TO TOP FLANGE AT STEEL BEAM AS NOTED IN THIS SCHEDULE. CONFORM TO THE NOTES & TYPICAL DETAILS ON THE STRUCTURAL DRAWINGS

C3
W/ 12mmØ x150mm LG ANCHORS DO
RL2

5. PROVIDE 15M DOWELS IN FOUNDATION WALLS FOR ALL WALL REINFORCEMENT UNLESS NOTED OTHERWISE.
@800mm o/c C150x12 HSS102x102x6.4 6. PROVIDE LAP SPLICE FOR: 15M 650 LAP PROVIDE MECHANICAL LINTELS IN ACCORDANCE WITH TYPICAL DETAILS AND
DO 7. REFER TO CORE FILLS SCHEDULE FOR DETAILS AND REINFORCEMENT. WALLS HATCHED THUS ARE NOTES FOR ALL DUCTS AND PIPES PASSING THROUGH MASONRY WALLS
8. PROVIDE CORE FILL C1 AT EACH SIDE OF OPENINGS U/N OTHERWISE NOTED ON PLANS AND/OR SECTIONS. = LOADBEARING MASONRY WALLS
(WALL REINFORCING SCHEDULES) EXISTING
DO a) PROVIDE C1 AT UNSUPPORTED ENDS OF WALLS U/N.
ROOF TOP UNIT SCHOOL
b) PROVIDE C1 AT EACH SIDE OF CONTROL JOINTS U/N.

RL2
TRIM W/ C150X12 9. PROVIDE CORE FILL C4 AT ALL WALL CORNERS U/N OTHERWISE IN PLANS AND/OR SECTIONS.
DO (Wt = 1815kg) C150x16 10. PROVIDE TITEWALL BL-A CONTROL JOINT BY BLOK-LOK OR EQUIVALENT FOR ALL VERTICAL CONTROL JOINTS WALL PLATE SCHEDULE
SEE MECH. DWGS Sim IN EXTERIOR MASONRY WALLS EXCEEDING 4m IN HEIGHT. = U.O.D. -150mm (FLAT ROOF) (LAST DIMENSION PARALLEL TO WEB)
KEY PLAN
RL2

DO R8 11. 190mm MASONRY WALL REINFORCING - 15M@800 O/C.


1

FOR LOCATIONS
WP

S2-02 12. REINFORCE ALL MASONRY SILLS, INTERIOR AND EXTERIOR, AS PER THE REINFORCING INDICATED IN THIS SCHEDULE. GROUT
C150x16 TOP COURSE OF ALL SILLS SOLID MARK MATERIAL REMARKS
DO
Qx Qx
190
WALLS SHADED AS THUS REQUIRE
= CONT. LINTEL BLOCK BOND BEAM WP1 180x15x180 (2)13Ø A.BOLTS x 150 LG.
ROOF FRAMING PLAN (SEE SECTIONS)
B1

Q C150x16 DO Q
DO Sim
1 : 100 WP2 180x15x250 (2)13Ø A.BOLTS x 150 LG.
R1 1. UNDERSIDE OF ROOF DECK AT PERIMETER AND HIGH POINTS TO BE 0.00 BELOW ROOF DATUM ELEVATION 4000mm,
DO S2-02 EXCEPT AS NOTED ON PLAN U.O.D. = UNDERSIDE OF DECK.
C150x12 2. ROOF DECK TO SLOPE TO DRAINS AS SHOWN ON THIS DRAWING.
DO 3. TOP OF STEEL BEAMS SUPPORTING STEEL DECK ARE 0.0mm BELOW U.O.D. TOP OF STEEL BEAM SUPPORTING JOISTS ARE 150mm

RL2
R1 1800 O/C MAX.
5
RL2

S2-02
BELOW U.O.D EXCEPT AS SHOWN THUS ± ON PLAN. 10 8 7
1
WP

4. OWSJ SHOES TO BE 150 DEEP UNLESS NOTED.


DO 5. FOR LOADING SEE ROOF LOADING SCHEDULE ON THIS DRAWINGS.
DO 6. OPEN WEB STEEL JOISTS SHALL BE DESIGNED TO SUPPORT TOTAL DEAD, SNOW AND SPACING AS SHOWN ON PLAN. LOADS. IN
DO ADDITION, OWSJ SHALL BE DESIGNED FOR ADDITIONAL LOADS SHOWN ON PLAN, ACCUMULATED SNOW DRIFT LOADS (ASL) AND T
FOR POINT LOADS OF BRACING AND MECHANICAL EQUIPMENT, IN EXCESS OF 3 kN PER JOIST.
DO 1 7. JOISTS AND BEARING ANCHORAGES SHALL BE DESIGNED TO RESIST UPLIFT DUE TO WIND AS REQUIRED BY THE ONTARIO
WP
SLOPE DO BUILDING CODE AND IN NO CASE LESS THAN THE GREATER OF THOSE INDICATED ON THE WIND UPLIFT KEY PLAN.
C3

DO SLOPE 8. OWSJ SHALL BE DESIGNED BY A LICENSED PROFESSIONAL ENGINEER, SHOP DRAWINGS AND CALCULATIONS BEARING THE STAMP

stephenson
RL2

HSS102x102x6.4 AND SIGNATURE OF THE PROFESSIONAL ENGINEER RESPONSIBLE FOR THE DESIGN SHALL BE SUBMITTED FOR REVIEW PRIOR TO
DB FABRICATION AND ERECTION.
DO HSS102x102x6.4
W310x39

9. PROVIDE CONTINUOUS TOP AND BOTTOM CHORD BRIDGING FOR OWSJ IN ACCORDANCE WITH CSA-S16.1 IN NO CASE LESS THAN AS ENGINEERING
DO SHOWN ON PLAN.
DO Sim 10. PROVIDE BOTTOM CHORD BRACING FOR ALL JOISTS NEAR THE FIRST BOTTOM CHORD PANEL POINT. BRIDGING CANNOT BE
R2 DB R6 2550 Victoria Park Ave. Suite 602
S2-02 S2-02
CONSIDERED AS BRACING.
S Toronto ON M2J 5A9 Tel: (416) 635 9970
Px DO Px 11. "TJ" NOTED AGAINST JOIST DENOTES "TIE JOIST" I.E EXTEND BOTTOM CHORD AND CONNECT TO SUPPORT. TIE JOIST TO BE
DESIGNED FOR 1% OF THE COLUMN AXIAL LOAD. SEE COLUMN SCHEDULE. www.stephenson-eng.com info@stephenson-eng.com
DO HSS102x102x6.4
12. LIVE LOAD DEFLECTION OF ROOF JOISTS SHALL NOT EXCEED 1/240 OF SPAN UNLESS OTHERWISE NOTED.
DO OFES SI ON A L
1

DB
WP

13. STEEL ROOF DECK SHALL BE DESIGNED TO SUPPORT SPECIFIED TOTAL DEAD AND LIVE LOADS. MINIMUM BASE NOMINAL THICKNESS PR
1
WP

C3

ED
(BNT) OF STEEL DECK SHALL BE 0.76 MM.

EN
LATERAL SUPPORT CHANNELS 18_08_10

NS

GIN
DO 14. NO HANGERS OR BRACKETS SUPPORTING MECHANICAL EQUIPMENT OR PIPING SHALL BE HUNG FROM ROOF DECK.

LI CE
FOR PARTITION WALLS. (TYP.)

EER
R
RL1

DO 15. STEEL ROOF DECK SHALL BE INSTALLED FOR DIAPHRAGM ACTION IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE CANADIAN
DO
-SEE TYPICAL DETAIL DWGS
SHEET STEEL BUILDING INSTITUTE AND TYPICAL NOTES. H.A. McCALLUM
WP B1

AND ARCH. DWGS FOR LOCATIONS. 16. LOCATION OF MECHANICAL EQUIPMENT AND MECHANICAL EQUIPMENT LOADS ARE TO BE CONFIRMED BY MECHANICAL
1

O
PR
CONTRACTOR BEFORE STRUCTURAL STEEL IS FABRICATED. REFER TO MECHANICAL DRAWINGS. UNLESS OTHERWISE APPROVED,
P P

RI
VI TA

O
MECHANICAL EQUIPMENT AND PIPING MUST BE HUNG FROM OWSJ PANEL POINTS AND HANGER SPACING SHALL NOT EXCEED 3.0 M. NC
E OF ON
RL1

C2

DO DO 17. FRAME ALL ROOF OPENINGS AND MECHANICAL UNITS AS SHOWN ON TYPICAL DETAILS UNLESS NOTED.
RL2

650 STEEL JOIST


RL1

18. SUBMIT DETAILS TO STRUCTURAL CONSULTANT FOR REVIEW FOR ALL OPENINGS OTHER THAN THOSE SHOWN ON STRUCTURAL
WELD DECK ANGLES
1800 O/C MAX. DRAWINGS. LEGEND:
TOGETHER @ CORNERS WELD DECK ANGLES
C150x12 19. "M" DENOTES MOMENT CONNECTION. FACTORED MOMENT AS SPECIFIED ON DRAWINGS IS IN kN METRES. OFES SI ON A L
(TYP.) 650 STEEL JOIST TOGETHER @ CORNERS 20. MOMENT CONNECTIONS SHALL BE DESIGNED BY A LICENSED PROFESSIONAL ENGINEER. SHOP DRAWINGS AND CALCULATIONS
PR
RL1

ED
= 0.80 kPa

EN
1800 O/C MAX.
1

1800 O/C MAX. 18_08_10


WP

WP

(TYP.)

NS

GI N
BEARING THE STAMP AND SIGNATURE OF THE LICENSED PROFESSIONAL ENGINEER RESPONSIBLE FOR THE DESIGN SHALL BE
OO OO Q

LI CE

EE R
B2 SUBMITTED FOR REVIEW PRIOR TO FABRICATION AND ERECTION. J. C. GASDIA
Sim = 1.09 kPa
1800 O/C MAX.

21. AN INDEPENDENT INSPECTION AND TESTING COMPANY IS TO INSPECT STRUCTURAL STEEL AND STEEL DECK IN THE SHOP AND IN 100169574
1800 O/C MAX.

R7
C180x15

THE FIELD FOR WELDING, CONNECTIONS, BOLT TORQUES, AND GENERAL CONFORMANCE WITH THE STRUCTURAL DRAWINGS AND
C180x15
RL3

S2-02
DO

RL3

SPECIFICATIONS.

O
PR
DO

DO

DO

DO

Sim

RI
= 1.81 kPa VI
DO

TA
DO

DO

DO

O
R7 22. NON-LOAD BEARING PARTITIONS SHALL BE A MINIMUM OF 25 mm CLEAR OF STRUCTURE. NC
E OF ON
S2-02 STEEL ROOF DECK 38mm DP. x 0.76 BNT. 23. WALL PLATES (WP) SHALL HAVE LAST DIMENSION PARALLEL TO BEAM OR JOIST WEB. SEE SCHEDULE ON DRAWINGS.
24. SEE ROOF LINTEL SCHEDULE ON THIS DRAWING. 1600 TYPICAL
25. REFER TO GENERAL NOTES AND SPECIFICATION FOR GRADES OF STRUCTURAL STEEL AND STEEL DECK.
ALL AROUND Simcoe County
26. SEE TYPICAL NOTES, TYPICAL DETAILS, COLUMN AND FOOTING SCHEDULES AND ALL OTHER DRAWINGS.
O EXISTING HSS LINTEL
O 27. FOR LOCATION OF ROOF ANCHORS AND DAVIT SUPPORTS, REFER TO ARCHITECTURAL DRAWINGS. REFER TO
WIND UPLIFT DIAGRAM
District School Board

R5
CONT. L127x76x6.4 (LLV) +
DRILLED 16mm DIA. HILTI HIT
TYPICAL DETAILS FOR CONNECTION DETAILS. SUBMIT SHOP DRAWINGS FOR REVIEW AND COORDINATION.
Px 1 : 200
CONT. L127x76x6.4 (LLV) + S2-02 HY 70 ANCHORS @800 O/C
R4
DRILLED 16mm DIA. HILTI HIT MAX. WELD DECK TO ANGLE.
HY 70 ANCHORS @800 O/C S2-02 (SLOPE ANGLE TO MATCH ROOF LOADING SCHEDULE
MAX. WELD DECK TO ANGLE.
(SLOPE ANGLE TO MATCH
DECK SLOPE) TYP
LOADING SUPERIMPOSED
P 1. LOADS NOTED ARE WIND UPLIFT VALUES AND
ARE NOT FACTORED.
DECK SLOPE) TYP ROOF USE DEAD LOAD (kPa)
SNOW LOAD (kPa) CLEARVIEW MEADOWS
CONT. DECK ANGLE 2 . ROOF JOISTS AND THEIR ANCHORAGE SHALL ELEMENTARY SCHOOL
L76x76x6.4 (TYP.)
GENERAL ROOF 1.11 2.95 +ASL
OO BE DESIGNED FOR THE MINIMUM NET UPLIFT ADDITION
VALUES AND NO LESS THAN THAT REQUIRED
IN PART 4 OF THE ONTARIO BUILDING CODE. 12 Locke Avenue
CORRIDOR ROOF 1.26 2.95 +ASL Stayner, Ontario
O L0M 1S0

IN ADDITION TO UNIFORM LOADING SHOWN, REFER TO EXISTING BUILDING DRAWING TITLE


ROOF PLAN FOR ADDITIONAL LOADING FOR ACCUMULATED
10 8 7 5 SNOW LOADS (ASL) AS SHOWN, AND FOR POINT LOADS
ROOF PLAN
OF BRACING AND MECHANICAL EQUIPMENT.
1.44 kPa

IN ADDITION TO UNIFORM LOADING SHOWN, DESIGN NOTE: EXISTING CONDITIONS AS SHOWN ON THE PROJECT NO: SCALE
STRUCTURAL DRAWINGS ARE BASED UPON INFORMATION

DATE PLOTTED: 8/1/2018 8:39:32 AM


JOISTS FOR ANY CONCENTRATED LOADS RESULTING FROM
20171969 As indicated
MECHANICAL PIPING OR AS A MINIMUM, DESIGN FOR AVAILABLE AT THE TIME THAT DRAWINGS WERE
DRAWN BY: DRAWING NO:
POINT LOAD OF 2kN AT ANY LOCATION. PREPARED AND ARE TO BE VERIFIED BY THE CONTRACTOR
3600 Author
ON SITE.
NOTE: ROOFING SINGLE PLY = 0.72 kPa HAS BEEN CHECKED BY:
ANY VARIATIONS ARE TO BE REPORTED AND INSTRUCTIONS
INCLUDED IN THE ABOVE TABLE TYPICAL R.T.U. (ASL)
ALL AROUND
RECEIVED BEFORE PROCEEDING. Checker
S1-02 3
DATE:
April 26, 2018
T 8 8 5
10 VERT. WALL REINF. SEE LOAD
BEARING MASONRY WALL
SCHEDULE. (TYP.)

REVISION
DOWELS TO MATCH
VERT. WALL REINF.

ISSUED FOR PERMIT AND TENDER


(TYP.)
PROVIDE 15@800 o/c SLAB-ON-GRADE SLAB-ON-GRADE SLAB-ON-GRADE
150mm SLAB (MIN.)

ISSUED FOR COORDINATION


DOWELS AT WINDOW -SEE PLAN NOTES -SEE PLAN NOTES REINF MASONRY SILL AS
-SEE PLAN NOTES

SEE ARCH. DWGS


SLAB-ON-GRADE

80% WORKING DRAWINGS


15@300 BEW EPOXY COATED. SLAB-ON-GRADE

WINDOW SILLS
LOCATIONS. (TYP.) (TYP.) (TYP.) PER MASONRY CORE FILL
35 MPa CLASS C1 CONCRETE (TYP.) -SEE PLAN NOTES (TYP.) -SEE PLAN NOTES NOTES AND DETAILS
-TOP OF SLAB SLOPES, SEE ARCH. (TYP.) (TYP.)
FINISHED GRADE

600
VAPOUR UNDER S.O.G.
-SEE SPEC (TYP.) VAPOUR UNDER S.O.G. VAPOUR UNDER S.O.G. VAPOUR UNDER S.O.G. VAPOUR UNDER S.O.G. -SEE ARCH. DWGS
FINISHED GRADE
-SEE SPEC (TYP.) -SEE SPEC (TYP.) -SEE SPEC (TYP.) -SEE SPEC (TYP.) (TYPICAL)
-SEE ARCH. DWGS
SLOPE

200
(TYPICAL) GROUND FLOOR GROUND FLOOR GROUND FLOOR GROUND FLOOR GROUND FLOOR
10

No. DATE
18_08_10
18_05_22
18_04_30
(TYP.)

150mm VOID
600

600

3
2
1
CONT. 2-15B (TYP.) CONT. 2-15B (TYP.) CONT. 2-15B (TYP.)
THE CONTRACTOR SHALL CHECK ALL DIMENSIONS

ELEVATION VARIES SEE PLAN


RIGID INSULATION WITH THE LATEST ISSUE OF

ELEVATION VARIES SEE PLAN

ELEVATION VARIES SEE PLAN


RIGID INSULATION -SEE ARCH. ARCHITECTURAL, MECHANICAL AND ELECTRICAL
-SEE ARCH. DRAWINGS. REPORT ANY DISCREPANCIES TO THE
ARCHITECT BEFORE PROCEEDING WITH WORK.

RIGID INSULATION
-SEE ARCH. DRAWINGS ARE NOT TO BE SCALED. CONTRACTOR MUST
CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS ON
DOWELS TO MATCH 200 CONC. WALL
THE PROJECT; AND MUST REPORT ANY DISCREPANCIES
VERT. REINF. (TYP.) DOWELS TO MATCH BEYOND / BEHIND TO THE CONSULTANTS BEFORE PROCEEDING WITH THE
DOWELS TO MATCH DOWELS TO MATCH
VERT. REINF. (TYP.) WORK. THE USE OF THIS DRAWING OR PART THEREOF IS
VERT. REINF. (TYP.) VERT. REINF. (TYP.) FORBIDDEN WITHOUT THE WRITTEN APPROVAL OF THE
CONT. 2-15B (TYP.) CONT. 2-15B (TYP.) DOWELS TO MATCH CONSULTANTS.
VERT. REINF. (TYP.)
(MIN.)

(MIN.)

(MIN.)
300

300

300

300

300
CONT. 2-15B (TYP.)

150 370 150 150 200 150 150 200 150 150 200 150

TYPICAL INTERIOR LOAD TYPICAL INTERIOR LOAD


BEARING MASONRY WALLS BEARING MASONRY WALLS
NOTE: AT DOORWAYS
TYPICAL FOUNDATION WALL REINFORCING
2 SECTION 3 SECTION (UNLESS NOTED OTHERWISE ON SECTIONS 4 SECTION 5 SECTION
S2-01 1 : 20 S2-01 1 : 20 OR SHEAR WALL ELEVATIONS) S2-01 1 : 20 S2-01 1 : 20 6 SECTION
10M @460 VEF S2-01
10M @320 HEF 1 : 20

FOR 190mm/200mm WALLS:


10M @320 VERT. CENTRE OF WALL
10M @200 HORIZ. CENTRE OF WALL

O O

GROUND FLOOR GROUND FLOOR


stephenson
ENGINEERING
2550 Victoria Park Ave. Suite 602
Toronto ON M2J 5A9 Tel: (416) 635 9970
www.stephenson-eng.com info@stephenson-eng.com

OFES SI ON A L
PR

ED

EN
18_08_10

NS

GIN
LI CE

EER
H.A. McCALLUM

O
PR

RI
VI TA

O
NC
E OF ON

OFES SI ON A L
PR

ED

EN
18_08_10

NS

GI N
LI CE

EE R
J. C. GASDIA
100169574

O
PR

RI
VI TA

O
NC
E OF ON

7 SECTION 8 SECTION Simcoe County


S2-01 S2-01 District School Board
1 : 20 1 : 20

CLEARVIEW MEADOWS
ELEMENTARY SCHOOL
ADDITION

12 Locke Avenue
Stayner, Ontario
L0M 1S0

DRAWING TITLE

FOUNDATION SECTIONS

NOTE: EXISTING CONDITIONS AS SHOWN ON THE PROJECT NO: SCALE


STRUCTURAL DRAWINGS ARE BASED UPON INFORMATION

DATE PLOTTED: 8/1/2018 8:39:33 AM


20171969 As indicated
AVAILABLE AT THE TIME THAT DRAWINGS WERE
DRAWN BY: DRAWING NO:
PREPARED AND ARE TO BE VERIFIED BY THE CONTRACTOR Author
ON SITE.
CHECKED BY:
ANY VARIATIONS ARE TO BE REPORTED AND INSTRUCTIONS
RECEIVED BEFORE PROCEEDING. Checker
S2-01 3
DATE:
April 27, 2018
T O
10 10 PARAPETS GROUTED 100% SOLID

REVISION
PARAPETS GROUTED 100% SOLID
PARAPETS GROUTED 100% SOLID -SEE ARCH. DWGS FOR EXTENTS. -SEE ARCH. DWGS FOR EXTENTS.
-SEE ARCH. DWGS FOR EXTENTS. (TYP.) (TYP.) 190

ISSUED FOR PERMIT AND TENDER


(TYP.) 190
190 PROVIDE CONT. SOLID BLOCK

ISSUED FOR COORDINATION


80% WORKING DRAWINGS
CONT. L76x76x6.4 CONT. L127x76x6.4 (LLV) COURSE AT DECK ANGLE LOCALLY REMOVE EXISTING VENEER
CONT. L76x76x6.4
WELD DECK TO ANGLE DECK ELEV. VARIES + DRILLED 16mm DIA. HILTI LOCATIONS. (TYP.) TO FACILITATE INSTALLATION OF NEW
WELD DECK TO ANGLE
(TYP.) TO SUIT ROOF SLOPES HIT HY-70 ANCHORS @800 o/c WALL PLATE/ CHANNEL. SEE ARCH
(TYP.)
(TYP.) MAX. (WELD DECK TO ANGLE) DEMO PLANS FOR COMPLETE
(TYP.) EXISTING ROOF DECK EXTENTS AND DETAILS
SLOPE U/S ROOF DECK (HP) SLOPE U/S ROOF DECK (HP) U/S ROOF DECK (HP)
U/S ROOF DECK (HP)
U/S ROOF DECK (LP) U/S ROOF DECK (LP) U/S ROOF DECK (LP) U/S ROOF DECK (LP)

No. DATE
18_08_10
18_05_22
18_04_30
200
1ST PANEL POINT BOTTOM
EXISTING 2-COURSE
CHORD BRACING. (TYP.) PROVIDE 200x12x300 WALL PLATE.

3
2
1
BOND BEAM
-SEE PLAN FOR LOCATIONS CONNECT WALL PLATE WITH 2-16mmØ
VERT. WALL REINF. SEE LOAD THE CONTRACTOR SHALL CHECK ALL DIMENSIONS
HILTI HAS RODS EPOXY WITH HILTI HIT-HY270
BEARING MASONRY WALL WITH THE LATEST ISSUE OF
EMBEDMENT DEPTH 150mm MIN, ARCHITECTURAL, MECHANICAL AND ELECTRICAL
SCHEDULE ON S1-02
SPACING 250mm MIN DRAWINGS. REPORT ANY DISCREPANCIES TO THE
(TYP.) 1ST PANEL POINT BOTTOM T&B BRIDGING EXISTING WALL ARCHITECT BEFORE PROCEEDING WITH WORK.
CHORD BRACING. (TYP.) -SEE PLAN (TYP.)
-SEE PLAN FOR LOCATIONS
AT DOOR & WINDOW LOCATIONS, CONT. LINTEL BLOCK BOND EXISTING MASONRY DRAWINGS ARE NOT TO BE SCALED. CONTRACTOR MUST
VENEER CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS ON
WELD REBAR TO TOP OF LINTELS. CONT. LINTEL BLOCK BOND BEAM, REINF. WITH 1-15M EXISTING HSS LINTEL THE PROJECT; AND MUST REPORT ANY DISCREPANCIES
(TYP.) BEAM, REINF. WITH 1-15M VERT. WALL REINF. SEE LOAD (HOOKED AT CORNERS) VERT. WALL REINF. SEE LOAD TO THE CONSULTANTS BEFORE PROCEEDING WITH THE
(HOOKED AT CORNERS) BEARING MASONRY WALL CONC. FILLED 20MPa. EXTENT BEARING MASONRY WALL WORK. THE USE OF THIS DRAWING OR PART THEREOF IS
CONC. FILLED 20MPa. EXTENT SCHEDULE ON S1-02 SHOWN ON PLAN. (TYP.) SCHEDULE ON S1-02 FORBIDDEN WITHOUT THE WRITTEN APPROVAL OF THE
(TYP.) (TYP.) CONSULTANTS.
SHOWN ON PLAN. (TYP.)

DOOR/ WINDOW
LINTELS, SEE PLAN AND LINTEL
SEE PLAN. (TYP.)
SCHEDULE FOR SIZES (TYP.)
NOTE:
LINTEL WELDED TO WALL PLATE
EACH END.

R1 SECTION
S2-02 1 : 20 R2 SECTION R3 SECTION R4 SECTION
S2-02 1 : 20 S2-02 1 : 20 S2-02 1 : 20

PARAPETS GROUTED 100% SOLID


-SEE ARCH. DWGS FOR EXTENTS. T
O 5 (TYP.)

CONT. L127x76x6.4 (LLV)


+ DRILLED 16mm DIA. HILTI
76 x 6.4 mm DECK WELD PLATE
LOCALLY REMOVE EXISTING VENEER HIT HY-70 ANCHORS @800 o/c
TO FACILITATE INSTALLATION OF NEW MAX. (WELD DECK TO ANGLE) R W/12mmØ x 150 LONG AND 75mm
HOOK ANCHORS AT 800 O/C
WALL PLATE/ CHANNEL. SEE ARCH (TYP.)
DEMO PLANS FOR COMPLETE DECK ELEV. VARIES
EXISTING ROOF DECK HSS102x102x6.4
EXTENTS AND DETAILS TO SUIT ROOF SLOPES U/S ROOF DECK (HP)
U/S ROOF DECK (HP) U/S ROOF DECK (HP) (TYP.) U/S ROOF DECK (HP)

U/S ROOF DECK (LP) U/S ROOF DECK (LP) U/S ROOF DECK (LP)
200

U/S ROOF DECK (LP)


PROVIDE CONT. SOLID BLOCK
EXISTING 2-COURSE COURSE AT DECK ANGLE
PROVIDE 200x12x300 WALL PLATE.
BOND BEAM
CONNECT WALL PLATE WITH 2-16mmØ
HILTI HAS RODS EPOXY WITH HILTI HIT-HY270
EMBEDMENT DEPTH 150mm MIN,
SEE MASONRY WALL REINFORCING
SCHEDULE FOR SIZE AND SPACING
LOCATIONS. (TYP.)

UDL DL=3.6 kN/m


stephenson
ENGINEERING
SPACING 250mm MIN DESIGN CONNECTIONS FOR ALL
L76x76x6.4 ALUM PANEL AND WINDOW. IMPLIED AXIS LOADING MOMENTS,
DIAGONAL BRACE @900 o/c VERT. WALL REINF. SEE LOAD 2550 Victoria Park Ave. Suite 602
REFER TO ARCH TORSION AND SHEAR FORCES
BEARING MASONRY WALL Toronto ON M2J 5A9 Tel: (416) 635 9970
CONT. 2 COURSE DEEP LINTEL BLOCK BOND www.stephenson-eng.com info@stephenson-eng.com
EXISTING WALL RL3 SCHEDULE ON S1-02 (TYP.)
EXISTING MASONRY BEAM, REINF. WITH 1-15M

TO SUIT ARCH
VENEER PROVIDE C130x10 @800 o/c (HOOKED AT CORNERS) OFES SI ON A L
W/CONT L89x89x6.4. C100x8 @600 o/c PR
CONC. FILLED 20MPa. EXTENT

ED

EN
ALSO PROVIDE 6.4mm GUSSET 18_08_10

NS
SHOWN ON PLAN. (TYP.)

GIN
LI CE
PLATES IN WEB OF THE BEAM

EER
L89x89x6.4 GALVANIZED
EACH SIDE @800 o/c H.A. McCALLUM
190

O
PR

RI
VI TA

O
NC
E OF ON

R8 SECTION OFES SI ON A L
S2-02 PR
1 : 20
SECTION SECTION SECTION

ED

EN
R5 R6 R7 18_08_10

NS

GI N
LI CE

EE R
S2-02 S2-02 S2-02 J. C. GASDIA
1 : 20 1 : 20 1 : 20 100169574

O
PR

RI
VI TA

O
NC
E OF ON

Simcoe County
District School Board

CLEARVIEW MEADOWS
ELEMENTARY SCHOOL
ADDITION

12 Locke Avenue
Stayner, Ontario
L0M 1S0

DRAWING TITLE

ROOF SECTIONS

NOTE: EXISTING CONDITIONS AS SHOWN ON THE PROJECT NO: SCALE


STRUCTURAL DRAWINGS ARE BASED UPON INFORMATION

DATE PLOTTED: 8/1/2018 8:39:33 AM


20171969 As indicated
AVAILABLE AT THE TIME THAT DRAWINGS WERE
DRAWN BY: DRAWING NO:
PREPARED AND ARE TO BE VERIFIED BY THE CONTRACTOR AB
ON SITE.
CHECKED BY:
ANY VARIATIONS ARE TO BE REPORTED AND INSTRUCTIONS
RECEIVED BEFORE PROCEEDING. JG
S2-02 3
DATE:
April 26, 2018
STANDARD ABBREVIATIONS A01 GENERAL NOTES A02 CAST-IN-PLACE CONCRETE NOTES A03.1 CAST-IN-PLACE CONCRETE NOTES A03.2
@ -At H (HOR) -Horizontal S -Standard Beam 1. GENERAL

REVISION
ADJ -Adjustable HEF -Horizontal Each Face SDF -Step Down Footing 1.1. DESIGN AND CONSTRUCTION IS TO CONFORM TO THE REQUIREMENTS OF THE 2012 ONTARIO BUILDING CODE, AND ANY APPLICABLE REQUREMENTS 1. GENERAL
AIFB -Asphalt Impregnated Fibre Board HIF -Horizontal Inside Face SDL -Superimposed Dead Load OR BY-LAW OF THE AUTHORITY HAVING JURISDICTION. REFER ALSO TO TYPICAL DETAILS, NOTES UNDER PLANS AND SCHEDULES ON THE STRUCTURAL 1.1. PROVIDE ALL LABOUR, MATERIALS, TOOLS AND EQUIPMENT REQUIRED TO CARRY OUT THE WORK.
ALT -Alternate HOF -Horizontal Outside Face SECT -Section DRAWINGS, AND TO THE SPECIFICATION. ALL CODES, MANUALS, STANDARDS AND SPECIFICATIONS REFERRED TO SHALL BE THE SPECIFIC EDITION 1.2. REFER ALSO TO GENERAL NOTES, NOTES UNDER PLANS AND SCHEDULES, TYPICAL DETAILS AND SPECIFICATION. 3.14 GENERAL REQUIREMENTS FOR CUTTING AND DRILLING INTO CONCRETE

ISSUED FOR PERMIT AND TENDER


ARCH -Architectural HSC -Horizontally Slotted Connection SL -Slab REFERENCED IN APPLICABLE BUILDING CODE INCLUDING ALL REVISIONS AND ADDENDA. 2. PRODUCTS (A) DO NOT DRILL INTO, CORE THROUGH, SAW-CUT OR CHIP THE CONCRETE STRUCTURE WITHOUT WRITTEN AUTHORIZATION
A. ROD(A.R.) -Anchor Rod SQ -Square 2.1. PORTLAND CEMENT, WATER AND AGGREGATES SHALL CONFORM TO CSA STANDARD A23.1. BY THE STRUCTURAL CONSULTANT.

ISSUED FOR COORDINATION


HSS -Hollow Structural Section ALL DIMENSIONS, OTHER THAN PURELY STRUCTURAL DIMENSIONS SHOWN ON THE STRUCTURAL DRAWINGS MUST BE CHECKED AGAINST THE

80% WORKING DRAWINGS


ASL -Accumulated Snow Loading SOG -Slab on Grade ARCHITECTURAL DRAWINGS AND ANY INCONSISTENCIES REPORTED TO THE ARCHITECT BEFORE PROCEEDING WITH THE WORK. STRUCTURAL DRAWINGS 2.2. PROVIDE AN APPROVED WATER REDUCING ADDITIVE IN ALL CONCRETE. PROVIDE AN APPROVED AIR ENTRAINING ADDITIVE IN ALL CONCRETE (B) UNLESS NOTED OTHERWISE, PRIOR TO CUTTING, CORING OR DRILLING INTO THE CONCRETE STRUCTURE, LOCATE EXISTING
IF -Inside Face S.P.F. -Spruce/Pine/Fir MUST NOT BE SCALED. WHICH WILL BE EXPOSED TO A FREEZE/THAW CYCLE AND/OR THE ACTION OF DE-ICING SALT. ADMIXTURES SHALL CONFORM TO CSA CONCRETE REINFORCEMENT AND EMBEDDED SERVICES AT THAT LOCATION USING SUITABLE SCANNING DEVICE (I.E. X-RAYS, GROUND
B (BOT) -Bottom INT -Interior SPEC -Specifications 1.2. REFER TO ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATIONS AND SIZES OF OPENINGS, TRENCHES, PITS, SUMPS, EQUIPMENT, STANDARD A23.1. PENETRATION RADAR (GPR), LOCAL CHIPPING OF SLAB - ONLY WHERE APPROVED BY THE STRUCTURAL CONSULTANT, ETC),
BEW -Bottom Each Way INV -Invert ST -Steel SLEEVES, DEPRESSIONS, GROOVES AND CHAMFERS NOT INDICATED ON THE STRUCTURAL DRAWINGS. UNLESS SPECIFICALLY NOTED OTHERWISE, THE 2.3. FORMWORK SHALL CONFORM TO CSA STANDARD A23.1 AND CSA STANDARD S269.1 AND FALSEWORK SHALL CONFORM TO CSA S269.1. AS AUTHORIZED BY PROPERTY MANAGER IF APPLICABLE
BLDG -Building STD -Standard ABOVE ITEMS WHERE SHOWN ON THE STRUCTURAL DRAWINGS ARE INDICATED ONLY APPROXIMATELY AS TO SIZE AND LOCATION. 2.4. IF SO INSTRUCTED, THE DESIGNS FOR THE FORMWORK SHALL BE SUBMITTED FOR REVIEW BEFORE CONSTRUCTION. FORMWORK DRAWINGS (C) GPR SCANNING MUST BE DONE BY TRAINED TECHNICIANS WITH AT LEAST 5 YEARS OF EXPERIENCE AS SUCH.
BLL -Bottom Lower Layer JT -Joint STR -Straight 1.3. UNLESS SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS, NO PROVISION HAS BEEN MADE IN THE DESIGN FOR CONDITIONS OCCURRING DURING AND DESIGN SHALL BEAR THE STAMP OF A LICENSED PROFESSIONAL ENGINEER. __mm (D) GPR SCANNING DEVICES MUST BE CAPABLE OF ACCURATELY LOCATING REBAR IN A CONCRETE SLAB TO A MINIMUM DEPTH OF 300 mm,
BM -Beam STRUCT -Structural CONSTRUCTION. THE CONTRACTOR IS TO PROVIDE ALL NECESSARY BRACING AND SHORING REQUIRED FOR STRESSES AND INSTABILITY OCCURRING 2.5. PROVIDE SLAB AND BEAM FORMS WITH AN UPWARD CAMBER AS INDICATED ON PLANS THUS . WHERE CAMBERS ARE NOT NOTED ON WITHIN A HORIZONTAL TOLERANCE OF +- 25 mm AND A VERTICAL (DEPTH) TOLERANCE OF THE LARGER OF +-25 mm OR +- 15% OF
BML -Bottom Middle Layer kg -Kilogram FROM ANY CAUSE DURING CONSTRUCTION. THE CONTRACTOR SHALL ACCEPT FULL RESPONSIBILTY FOR ALL SUCH MEASURES. IT SHALL ALSO BE THE PLANS, CAMBER SLABS AND BEAMS FOR SPAN/500 AT INTERIOR BAYS, AND CANTILEVER LENGTH/250 AT CANTILEVER. CAMBER BOTH THE THE REBAR DEPTH.
BNT -Base NominalThickness kN.m -Kilo Newton Metres T -Top UNDERSIDE AND TOP OF CONCRETE IN A PARABOLIC PROFILE, WHILE MAINTAINING THE INDICATED STRUCTURAL THICKNESS OF MEMBERS. (E) AFTER ALL THE EXISTING REINFORCEMENT AND SERVICES HAVE BEEN LOCATED, NOTIFY THE STRUCTURAL CONSULTANT, WHO WILL

No. DATE
18_08_10
18_05_22
18_04_30
RESPONSIBLITY OF THE CONTRACTOR TO PROVIDE ALL NECESSARY BRACING, SHORING, SHEET PILING OR OTHER TEMPORARY SUPPORTS OF
B.O.F. -Bottom of Footing kN/m² -Kilo Newton per Square Metre TEMP -Temperature SAFEGUARD ALL EXISTING OR ADJACENT STRUCTURES AFFECTED BY THIS WORK. CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR CONSULTANTS 2.6. PROVIDE STANDARD ADJUSTABLE MASONRY ANCHOR SLOTS FOR ALL MASONRY FACING OR ABUTTING CONCRETE FACES. REVIEW AND APPROVE THE PROPOSED LOCATION OF OPENINGS, CORES OR DRILLED HOLES. MAKE ANY NECESSARY ADJUSTMENTS TO
BP -Baseplate kN/m -Kilo Newton per Metre Tf -Factored Tension Force REVIEW. 2.7. PROVIDE AND/OR INSTALL STANDARD ADJUSTABLE INSERTS AND ALL OTHER CAST-IN INSERTS AS REQUIRED BY THE ARCHITECTURAL, THE HOLE LOCATIONS AS DIRECTED BY THE STRUCTURAL CONSULTANT.
BSMT -Basement kPa -Kilo Pascals TJ -Tie Joist 2. SHOP DRAWINGS, PLACING DRAWINGS AND BAR LISTS STRUCTURAL, MECHANICAL AND ELECTRICAL DRAWINGS AND SPECIFICATION. (F) THE REVIEW BY THE STRUCTURAL CONSULTANT IS LIMITED ONLY TO THE LOCATION OF THE PROPOSED CORES OR DRILLED HOLES
BUL -Bottom Upper Layer TLL -Top Lower Layer 2.1. FOR ALL STRUCTURAL COMPONENTS SHOWN ON THE STRUCTURAL DRAWINGS, SUBMIT COPIES OF SHOP DRAWINGS AS DIRECTED FOR REVIEW BY THE 2.8. REINFORCING STEEL UNLESS SPECIFICALLY NOTED, SHALL BE DEFORMED BARS CONFORMING TO CAN/CSA -G30.18-M GRADE 400 (58000 PSI). THROUGH THE EXISTING STRUCTURE AND IT IS BASED ON THE ASSUMPTION THAT THE X-RAY OR SCAN RESULTS LOCATING SLAB

3
2
1
L -Angle TMf -Factored Torsional Moment STRUCTURAL CONSULTANT.SHOP DRAWINGS TO SHOW COMPLETE INFORMATION FOR THE FABRICATION AND ERECTION OF THE STRUCTURAL 2.9. WELDED WIRE FABRIC TO BE SUPPLIED IN FLAT SHEETS ONLY, UNLESS APPROVED OTHERWISE. REINFORCEMENT AND EMBEDDED SERVICES ARE COMPLETE AND ACCURATE. STEPHENSON EGINEERING LTD. TAKES NO
C -Standard Channel LB. -Pounds TML -Top Middle Layer 2.10. REINFORCING SHALL BE DETAILED, BENT, PLACED AND SUPPORTED TO CONFORM TO ACI DETAILING MANUAL AND THE MANUAL OF RESPONSIBILITY FOR THE ACCURACY OF THE X-RAY OR SCAN RESULTS. THE CONTRACTOR SHALL CHECK ALL DIMENSIONS
COMPONENTS. WITH THE LATEST ISSUE OF
CA -Column Above LG -Long TOD, T/D -Top of Deck 2.2. REVIEW OF SHOP DRAWINGS BY THE STRUCTURAL CONSULTANT IS ONLY TO ASSESS THAT THE SUBMITTED SHOP DRAWINGS REFLECT THE STANDARD PRACTICE PUBLISHED BY THE REINFORCING STEEL INSTITUTE OF CANADA. (G) CORE DRILL NEW HOLES FOR PIPES TO A DIAMETER NOT LARGER THAN THE OUTSIDE PIPE DIAMETER PLUS 25MM. DO NOT CUT
2.11. DRY-PACK GROUT TO BE 1 PART PORTLAND CEMENT TO 1 1/2 PARTS SAND TO 2 PARTS OF 8 mm PEA GRAVEL WITH ONLY SUFFICIENT WATER EXISTING REINFORCEMENT OR SERVICES WITHOUT PRIOR APPROVAL OF THE CONSULTANT. ARCHITECTURAL, MECHANICAL AND ELECTRICAL
CANT -Cantilever LL -Live Load / Lower Layer T.O.F. -Top of Footing INTENT OF THE STRUCTURAL DESIGN. DRAWINGS. REPORT ANY DISCREPANCIES TO THE
C/C (o/c) -Centre to Centre LLH -Long Leg Horizontal TOS, T/S-Top of Slab 2.3. REVIEW BY THE STRUCTURAL CONSULTANT SHALL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY FOR SEEING THAT THE WORK IS TO DAMPEN MIXTURE. COMPRESSIVE STRENGTH 50MPa AT 28 DAYS. (H) WHERE RECTANGULAR OPENINGS ARE TO BE CUT, PRE-DRILL THE CORNERS USING A 100 MM DIAMETER CORE DRILL OR DRILL A ARCHITECT BEFORE PROCEEDING WITH WORK.
CJ -Control Joint LLV -Long Leg Vertical TOST -Top of Steel COMPLETE, ACCURATE AND IN CONFORMITY WITH THE STRUCTURAL DRAWINGS AND SPECIFICATIONS. 2.12. NON-SHRINK GROUT TO BE AN APPROVED PRE-MIXED PROPRIETARY PRODUCT. SERIES OF HOLES TO PREVENT OVER CUTTING OF THE CORNERS.
CL -Centreline LSSJ -Long Span Steel Joists TSF -Tons per Square Foot 3. INSPECTION AND TESTING 2.13. PROVIDE APPROVED EXTRUDED PVC WATERSTOPS OF SIZE AND STYLE INDICATED, WITH PRE-WELDED CORNERS AND INTERSECTIONS. SEE
COL -Column LVL -Laminated Veneer Lumber TUL -Top Upper Layer 3.1. A SOILS CONSULTANT AND AN INDEPENDENT INSPECTION AND TESTING COMPANY ARE TO BE ENGAGED TO CARRY OUT THE FOLLOWING SERVICES ALSO TYPICAL DETAILS. 4. QUALITY CONTROL DRAWINGS ARE NOT TO BE SCALED. CONTRACTOR MUST
COMP -Compressible TYP -Typical 3.1.1. BEARING SOIL - REFER TO NOTES ON STRUCTURAL DRAWINGS AND ALSO TO THE SOIL REPORT. 2.14. CURING AND SEALING COMPOUNDS WHERE APPROVED FOR USE TO CONFORM TO ASTM STANDARD C309. GENERALLY ALL CONCRETE 4.1 FOR INSPECTION AND TESTING, SEE GENERAL NOTES AND/OR SPECIFICATION. CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS ON
CONC -Concrete m -Metre SURFACES ARE TO BE SEALED UNLESS NOTED OTHERWISE. COMPOUNDS ARE TO BE COMPATIBLE WITH APPLIED FINISHES. THE PROJECT; AND MUST REPORT ANY DISCREPANCIES
3.1.2. FILL UNDER SLAB-ON-GRADE - CONFORM THAT FILL MATERIAL USED IS SATISFACTORY AND THAT THE REQUIRED DEGREE OF TO THE CONSULTANTS BEFORE PROCEEDING WITH THE
CONST -Construction MAX -Maximum UL -Upper Layer COMPACTION HAS BEEN ATTAINED. 2.15. SHEAR REINFORCMENT AT SLAB CONNECTION AS SHOWN ON DRAWINGS AND DETAILS, SHALL BE STUDRAILS® AS MANUFACTURED BY
WORK. THE USE OF THIS DRAWING OR PART THEREOF IS
CONST JT ( CJT) -Construction Joint MECH -Mechanical U/N -Unless Noted 3.1.3. CAST-IN-PLACE AND PRECAST CONCRETE - ROUTINE INSPECTION OF MATERIALS, INCLUDING SLUMP, CYLINDER AND AIR DECON®. THE COMPLETE AND FINISHED STUDRAILl® SHALL BE ICC ES EVALUATED AND WELDING SHALL TAKE PLACE IN A ICC ES APPROVED
CONT (CONTIN) -Continuous MEZZ -Mezzanine U.N.O. -Unless Noted Otherwise ENTRAINMENT TESTS AND REINFORCING ROD TESTS WHEN REQUIRED OR DIRECTED IN ACCORDANCE WITH CSA STANDARD A23.2. AND AUDITED FACILITY. STUDRAILS® SHALL CONFORM TO THE LATEST UPDATE OF ASTM A1044. STEEL DECK NOTES A05 FORBIDDEN WITHOUT THE WRITTEN APPROVAL OF THE
CONSULTANTS.
C/W -Complete With MIN -Minimum U/S -Underside 3.1.4. THE PROJECT SUPERINTENDENT IS TO ADVISE THE STRUCTURAL CONSULTANT A MINIMUM OF 24 HOURS IN ADVANCE OF A CONCRETE 3. EXECUTION
MISC -Miscellaneous USD -Underside of Deck POUR FOR A REVIEW OF PREPARATIONS. 3.1. MINIMUM COMPRESSIVE STRENGTH FOR CONCRETE @ 28 DAYS SHALL BE AS NOTED ON THE DRAWINGS (20MPa MINIMUM). 1. GENERAL
D.FIR -Douglas Fir ML -Middle Layer 3.1.5. STRUCTURAL STEEL AND OWSJ - ROUTINE SHOP AND FIELD INSPECTION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE 3.2. SLUMP AT THE POINT OF DISCHARGE SHALL BE CONSISTENT AT 80 mm ±30mm (3" ±1 1/8") UNLESS NOTED OTHERWISE.GREATER SLUMPS ARE 1.1. DESIGN, FABRICATION, HANDLING AND ERECTION SHALL CONFORM TO THE FOLLOWING STANDARDS:
DET -Detail MLL -Middle Lower Layer V (VERT) -Vertical REQUIREMENTS CSA S16. NOT ACCEPTABLE. 1.1.a. CSA-S136
DIAG -Diagonal mm -Millimetre VBF -Vertically Braced Framing 3.3. CONCRETE MIXING, TRANSPORTATION, HANDLING AND PLACING SHALL CONFORM TO CSA STANDARD A23.1. 1.1.b. CSSBI 10M .................... STANDARD FOR STEEL ROOF DECK.
3.1.6. STEEL DECK - SEE STEEL DECK NOTES.
Ø (DIA) -Diameter MOM, (M) -Moment VEF -Vertical Each Face 3.1.7. MASONRY - WHEN REQUIRED OR DIRECTED, CONCRETE BLOCKS SHALL BE TESTED IN ACCORDANCE WITH ASTM C140 BRICKS IN 3.4. CONSTRUCTION JOINTS FOR WALLS ARE BASED UPON VERTICAL JOINTS AT A MAXIMUM SPACING OF 10000mm (30'-0") .UNLESS CONTROL 1.1.c. CSSBI 12M .................... STANDARD FOR COMPOSITE STEEL DECK.
DIM -Dimension MPa -Mega Pascals VIF -Vertical Inside Face ACCORDANCE WITH CAN/CSA A82; AND MORTAR AND/OR GROUT IN ACCORDANCE WITH CSA A179. JOINTS ARE PROVIDED AS PER DETAIL CFW02. TOTAL LENGTH OF POUR TO BE DISCUSSED WITH ENGINEER PRIOR TO PROCEEDING. 1.1.d. ASTM A653 .................... SPECIFICATIONS FOR STEEL SHEET, ZINC COATED (GALVANIZED) OR ZINC-IRON ALLOY COATED (GALVANNEALED)
DJ -Double Joist MUL -Middle Upper Layer VOF -Vertical Outside Face 3.2. ALL INSPECTION AND TESTING SERVICES ARE TO BE PERFORMED BY COMPANIES CERTIFIED BY THE CANADIAN STANDARDS ASSOCIATION AND 3.5. CONSTRUCTION JOINTS FOR WALLS, SLABS, AND BEAMS NOT SHOWN ON THE DRAWINGS SHALL BE APPROVED BY THE STRUCTURAL BY THE HOT DIP PROCESS.
DL -Dead Load VSC -Vertically Slotted Connection FOR WELDING, INSPECTORS ARE TO BE CERTIFIED BY THE CANADIAN WELDING BUREAU. CONSULTANT BEFORE CONSTRUCTION. GENERALLY JOINTS IN SLABS SHALL BE AT RIGHT ANGLES TO THE SPANS, AT MID-SPAN IF POSSIBLE 1.1.e. WELDING SHALL CONFORM TO CSA STANDARD W59 AND BE PERFORMED BY A FABRICATOR CERTIFIED TO CSA STANDARD W47.1.
DO -Ditto N -Newton 4. FOUNDATIONS AND BE CLEAR OF SUPPORTS AND POINT LOADS. 1.2. THE STEEL DECK SHALL BE DESIGNED BY A LICENSED PROFESSIONAL ENGINEER. SHOP DRAWINGS AND CALCULATIONS BEARING THE STAMP
DWG -Drawing N-S -North-South W -Wide Flange Beam 4.1. REFER TO NOTES UNDER FOUNDATION PLANS. ALL EXTERIOR FOOTINGS OR OTHER FOOTINGS EXPOSED TO FREEZING IN THE FINISHED BUILDING SHALL 3.6. INSERTS, FRAME-OUTS, SLEEVES, BRACKETS, CONDUITS AND FASTENING DEVICES, SHALL BE INSTALLED AS REQUIRED BY THE DRAWINGS AND SIGNATURE OF THE PROFESSIONAL ENGINEER RESPONSIBLE FOR THE DESIGN SHALL BE SUBMITTED FOR REVIEW PRIOR TO FABRICATION
DWL -Dowel NF -Near Face WP -Wall Plate BE FOUNDED AT A MINIMUM OF 1200mm (4'-0") BELOW FINISHED GRADE, UNLESS OTHERWISE NOTED. FOOTINGS EXPOSED TO FROST ACTION DURING AND SPECIFICATIONS IN A MANNER THAT SHALL NOT IMPAIR THE STRUCTURAL STRENGTH OF THE SYSTEM, BE SO INSTALLED THAT THEY AND ERECTION.
DT -Double Tee NIC -Not in Contract WWF -Welded WideFlange Beam SHALL NOT REQUIRE THE CUTTING, BENDING, OR DISPLACEMENT OF THE REINFORCING OTHER THAN AS SHOWN ON THE TYPICAL DETAILS. 1.3. NO HANGERS OR BRACKETS SHALL BE HUNG DIRECTLY FROM THE FLOOR OR ROOF DECK. ALL POINT LOADS MUST BE APPLIED DIRECTLY TO
CONSTRUCTION SHALL BE PROTECTED BY A MINIMUM OF 1200mm (4'-0") OF EARTH OR ITS EQUIVALENT SUFFICIENT TO PREVENT FREEZING.
No.(#) -Number WWF (WWM) -Welded Wire Fabric/ Mesh 4.2. THE LINE OF SLOPE BETWEEN ADJACENT EXCAVATIONS FOR FOOTINGS OR ALONG STEPPED FOOTINGS SHALL NOT EXCEED A RISE OF 7 IN A RUN OF 10, 3.7. ELECTRICAL CONDUIT SHALL NOT PASS THROUGH A COLUMN, SHALL NOT BE LARGER IN OUTSIDE DIAMETER THAN 1/3 SLAB THICKNESS OR STRUCTURAL STEEL FRAMING UNLESS OTHERWISE SHOWN OR APPROVED BY THE STRUCTURAL CONSULTANT.
E-W -East-West NTS -Not to Scale MAXIMUM STEP APPROX. 600mm (2'-0"). WALL OR BEAM IN WHICH IT IS EMBEDDED, SHALL NOT BE SPACED CLOSER THAN 3 DIAMETERS ON CENTRE UNLESS APPROVED AND HAVE A 1.4 WHEREVER STRUCTURAL FRAMING PERMITS, STEEL DECK SHALL BE DESIGNED AND FABRICATED TO SPAN CONTINUOUSLY OVER AT LEAST 4
EA -Each 4.3. PIER DEPTHS AND FOOTING ELEVATIONS SHOWN ON THE STRUCTURAL DRAWINGS ARE BASED UPON INFORMATION AVAILABLE AT THE TIME OF MINIMUM CONCRETE COVER OF 25 mm (1") AND UNLESS SPECIFICALLY PERMITTED OTHERWISE, SHALL NOT RUN HORIZONTALLY IN A SUPPORTS (3 SPANS). PROVIDE AN ADEQUATE INCREASE IN THICKNESS OF METAL TO COMPENSATE FOR CONTINUITY WHEREVER FEWER
EE -Each End OWSJ -Open Web Steel Joist PREPARATION OF THE STRUCTURAL DRAWINGS. CONCRETE WALL. SUPPORTS MAY OCCUR. END LAPS TO BE 50mm (2") MIN. AND BE LOCATED OVER SUPPORTS.
EF -Each Face 4.4. IF ACTUAL JOB SITE OR SOIL CONDITIONS VARY FROM THOSE ASSUMED, THEN WRITTEN DIRECTIONS MUST BE OBTAINED FROM THE 3.8. OPENINGS AND DRIVEN FASTENERS REQUIRED IN THE CONCRETE AFTER THE CONCRETE IS PLACED SHALL BE APPROVED BY THE 1.5. ROOF DECK SHALL BE FORMED WITH INTEGRAL RIBS IN ORDER TO SAFELY SUPPORT THE LOADS GIVEN ON THE DRAWINGS OVER THE SPANS
ELECT -Electrical Pa -Pascal STRUCTURAL CONSULTANT BEFORE PROCEEDING WITH THE WORK. STRUCTURAL CONSULTANT BEFORE PROCEEDING. REQUIRED. DECK THICKNESS GIVEN ON DRAWINGS IS MINIMUM ASSUMED ALLOWABLE THICKNESS AND MUST BE DESIGNED BY THE DECK
ELEV (EL) -Elevation / Elevator PC -Precast 3.9. FINISHING, REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR REQUIRED FINISH TO EXPOSED CONCRETE. ALL HONEYCOMBING SUPPLIER.
4.5. KEEP EXCAVATIONS CONTINUOUSLY DRY BEFORE CONCRETE IS PLACED. IF THE SOIL IS SOFTENED BY WATER, THE EXCAVATION SHALL BE
EQ -Equal PL -Plate SHALL BE CUT OUT AND FILLED. FLOOR FINISHES SHALL BE AS REQUIRED BY THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS AND 1.5.a. DEFLECTION OF ROOF DECK UNDER LIVE OR SNOW LOAD ONLY SHALL NOT EXCEED 1/300TH OF SPAN.
EXTENDED BELOW THE SOFTENED MATERIAL AND THE BOTTOM OF THE FOOTINGS LOWERED TO SUIT.
ES -Each Side PLF -Pounds per Lineal Foot 5. BACKFILLING AND COMPACTION SHALL CONFORM TO CSA STANDARD A23.1. 1.6. FLOOR DECK SHALL BE FORMED WITH INTEGRAL RIBS AND EMBOSSMENTS FOR COMPOSITE ACTION WITH CONCRETE SLAB IN ORDER TO SAFELY
EW -Each Way PREL -Preliminary 5.1. SLABS-ON-GRADE AND ALL STRUCTURAL ELEMENTS FRAMING INTO WALLS WHICH RETAIN EARTH MUST BE IN PLACE BEFORE BACKFILLING. 3.10. TOLERANCES FOR PLACING STRUCTURAL CONCRETE, REINFORCING STEEL, CAST-IN HARDWARE AND FOR FLOOR AND ROOF FINISHES SHALL SUPPORT THE LOADS GIVEN ON THE DRAWINGS OVER THE SPANS REQUIRED. IN ADDITION, THE DECK SHALL SAFELY SUPPORT ALL
EXIST -Existing PROJ -Projection 5.2. AT FOUNDATION WALLS WITH GRADE BOTH SIDES, UNLESS ADEQUATELY SHORED, BACKFILL AND COMPACT EACH SIDE OF WALL SIMULTANEOUSLY. BE AS SPECIFIED IN CSA STANDARD A23.1. CONSTRUCTION LOADS WITH NO SHORING UNTIL CONCRETE IS SET. DECK THICKNESS GIVEN ON DRAWINGS IS MINIMUM ALLOWED.
EXP. JT. -Expansion Joint PSF -Pounds per Square Foot 5.3. UNDER SLAB-ON-GRADE, REMOVE SOFT SPOTS, ORGANIC AND FOREIGN MATTER IN THE SUB-GRADE. (WHERE SUB-GRADE CONSISTS OF 3.11. MINIMUM REINFORCING FOR ANY CONCRETE WALL TO BE AS SHOWN ON TYPICAL DETAIL FOR CONCRETE WALLS. 1.6.a. DEFLECTION OF COMPOSITE FLOOR UNDER LIVE LOAD ONLY SHALL NOT EXCEED 1/360TH OF SPAN.
EXT -Exterior PSI -Pounds per Square Inch COMPACTED FILL, REFER TO SPECIFIC NOTES ON THE DRAWINGS). 3.12. MINIMUM REINFORCING FOR ANY SUSPENDED SLAB SHALL BE TEMPERATURE BARS BOTTOM EACH WAY PLUS 10M @ 400 (16") DOWELS 1.7. DESIGN AND DETAIL ON SHOP DRAWINGS ALL CONNECTIONS TO SUPPORTING MEMBERS FOR ALL COMBINATIONS OF DIAPHRAGM SHEAR AND
PSL -Parallel Strand Lumber 5.4. BACKFILL UNDER SLAB-ON-GRADE, IN FOOTING EXCAVATIONS AND IN TRENCHES ONLY WITH APPROVED MATERIAL. UNLESS SPECIFICALLY NOTED 600x600 (2'-0" x 2'-0") TOP AROUND PERIMETER. REFER TO TYPICAL DETAIL OF ONE WAY SLABS. UPLIFT FORCES ACTING ON THE ROOF DECK.
FDN -Foundation PT -Pressure Treated 3.13 PERFORM SURVEYS OF SLABS AS INDICATED IN SPECIFICATIONS. 2. PRODUCTS
OTHERWISE, BACKFILLING SHALL BE CARRIED OUT IN MAXIMUM OF 200mm ( 8" )THICK LIFTS OF LOOSE FILL EACH COMPACTED TO A MINIMUM OF 95%
FF -Far Face 2.1. UNLESS OTHERWISE NOTED ROOF DECK AND / OR COMPOSITE DECK SHALL BE FORMED OF METALLIC COATED SHEET STEEL CONFORMING
STANDARD PROCTOR MAXIMUM DRY DENSITY.
FIN -Finished R -Reaction 5.5. UNLESS OTHERWISE NOTED IN GEOTECHNICAL REPORT, PROVIDE IMMEDIATELY UNDER SLABS-ON-GRADE A MINIMUM OF 200mm (8") OF COMPACTED TOASTM A653/ A653M, STRUCTURAL QUALITY GRADE ' 230' WITH A ZF75 ZINC COATING, (GALVANNEAL).
FL -Floor RAD -Radius (MTC) GRANULAR 'B' MATERIAL.COMPACTION TO ACHIEVE A MINIMUM OF 98% STANDARD PROCTOR MAXIMUM DRY DENSITY. 2.2. UNLESS OTHERWISE NOTED DECK SHALL BE SINGLE FLUTED ELEMENT WITH INTEGRAL RIBS OF DEPTH AND MIN. BASE NOMINAL THICKNESS (BNT)
FMC -Full Moment Connection REF -Reference AS NOTED ON THE DRAWINGS. DECK SHALL HAVE INTERLOCKING SIDE JOINTS BETWEEN PANELS. ( MIN.. BNT. 0.76mm (0.30")).
STANDARD LAP ABBREVIATIONS
FT -Foot / Feet REINF -Reinforcing 2.3. COVER PLATES, CELL CLOSURES, FLASHINGS AND REINFORCING STIFFENERS FOR UNSUPPORTED EDGES TO BE SUPPLIED OF SIMILAR MATERIAL
CLS -Compression Lap Splice
FTG -Footing REQ'D -Required AND ZINC COATING TO THAT FOR DECK, UNLESS NOTED.
CDL -Compression Development Length
2.4. PRIMER PAINT TO BE ZINC RICH, READY MIX TO CAN/ CGSB-1.181 FOR FIELD "TOUCH-UP" OF WELD BURNS AFTER DECK IS INSTALLED.
GA -Gauge
REV
Rf
-Revision/Revised
-Factored Vertical Reaction
HEL -Hook Embedment Length LOAD BEARING MASONRY NOTES A06 LOAD BEARING MASONRY NOTES A06 2.5. UNLESS OTHERWISE SHOWN FOR OPENINGS THROUGH ROOF DECK FROM 150mm TO 450mm (6" TO 18") ACROSS THE FLUTES THE DECK SUPPLIER
TLS -Tension Lap Splice
GALV -Galvanized R/W -Reinforced With SHALL PROVIDE NOT LESS THAN A 51x51X6.4 ANGLE (2"x2"x 1/4 L). REINFORCEMENT TO FRAME ACROSS EACH SIDE OF THE OPENING
TDL -Tension Development Length
GEN -General 1. GENERAL 3. EXECUTION PERPENDICULAR TO THE FLUTES, WELDED TO AT LEAST TWO FLUTES EACH SIDE OF THE OPENING.
1.1. UNLESS OTHERWISE NOTED OR SHOWN ON THE DRAWINGS, THE FOLLOWING INDICATES THE MINIMUM REQUIREMENTS APPLICABLE TO 3.1. BEARING ON MASONRY: 2.6. FOR ROOF OPENINGS OVER 450mm (18") ACROSS THE FLUTES AND FOR AREAS OF CONCENTRATED LOAD, REINFORCE IN ACCORDANCE WITH
STRUCTURAL LOAD BEARING MASONRY. 3.1.1. MINIMUM BEARING ON MASONRY UNLESS OTHERWISE NOTED:- STRUCTURAL FRAMING DETAILS SHOWN ON PLANS OR TYPICAL DETAILS.
1.2. REFER ALSO TO ARCHITECTURAL DRAWINGS AND / OR THE SPECIFICATION FOR REQUIREMENTS OTHER THAN STRUCTURAL, AND FOR BEAMS (STEEL, CONC., WOOD)...................... 200mm (8") NOMINAL 3. EXECUTION
NON-LOAD BEARING WALLS AND PARTITIONS. LINTELS (STEEL, CONC., WOOD) ................... 150mm (6") NOMINAL 3.1. SUPPLY AND PLACE STEEL PACKING AS REQUIRED TO PRODUCE AN EVEN BEARING PRESSURE AT SUPPORTS.
1.3. MASONRY CONSTRUCTION TO CONFORM TO CSA STANDARD S304.1. JOISTS (STEEL, WOOD) ................................... 100mm (4") NOMINAL 3.2. FOR STEEL ROOF DECK, UNLESS OTHERWISE DETERMINED DURING THE DIAPHRAGM AND UPLIFT CONNECTION DESIGN OR SPECIFIED OTHERWISE
STRUCTURAL STEEL AND STEEL JOIST NOTES A04 2. PRODUCTS SLABS (CAST-IN-PLACE, PRECAST) .............100mm (4") NOMINAL IN THE SPECIFICATIONS OR ENGINEERING DRAWINGS, THE MINIMUM ATTACHMENT OF THE DECK TO THE BEARING SURFACES AND THE MINIMUM SIDE
LAP CONNECTIONS BETWEEN DECK UNITS SHALL BE:
2.1. CONCRETE BLOCKS TO BE MODULAR UNITS AS SHOWN ON THE ARCHITECTURAL DRAWINGS AND /OR SPECIFICATION, AND UNLESS ` STEEL DECKING (ON WELD PLATE) .............100mm (4") NOMINAL

stephenson
OTHERWISE NOTED SHALL BE: 3.1.2. MASONRY BEARINGS SHALL BE OF SOLID BLOCKS (OR GROUTED SOLID) OR BRICKS LAID IN MORTAR. ALL JOINTS ARE TO BE FULLY FILLED 3.2.A. FOR 38mm DEEP DECK PROFILES, CONNECT THE FIRST, THIRD, FIFTH AND SEVENTH LOW CORRUGATIONS (36/4 CONFIGURATION), AND
1. GENERAL EACH SUPPORT PARALLEL TO FLUTE DIRECTION AT 300mm [12"] MAXIMUM CENTERS. CONNECTIONS SHALL BE MADE USING EITHER AN
1.1. STRUCTURAL STEEL AND JOIST DESIGN DETAILS AND CONNECTIONS SHALL CONFORM TO CSA STANDARD S16 AND SHALL BE DESIGNED BY A 2.1.1. FOR BELOW GRADE AND EXTERIOR EXPOSED WALLS USE NORMAL WEIGHT LOAD BEARING UNITS: WITH TYPE 'S' MORTAR.
STANDARD HOLLOW: .......TYPE H / 15 / A / M. 3.1.3. MIN. SIZE OF SOLID BEARINGS AT BEAMS AND LINTELS UNLESS NOTED SHALL BE EQUAL TO TWICE THE BEARING / WALL PLATE (WP) ARC SPOT WELD WITH 20mm [3/4"] NOMINAL TOP DIAMETER, OR MECHANICALLY FASTENED USING HILTI POWDER ACTUATED FASTENERS
LICENSED PROFESSIONAL ENGINEER EXPERIENCED IN THIS TYPE OF WORK. (X-HSN24, HILTI X-ENP19, OR EQUIVALENT). ENGINEERING
1.2. REFER ALSO TO GENERAL NOTES, NOTES UNDER PLANS AND TO THE SPECIFICATION. 75% SOLID: .......TYPE S / 15 / A / M. LENGTH AND FOR A DEPTH EQUAL TO THE BEARING / WALL PLATE (WP) LENGTH, AND IN NO CASE LESS THAN 400 LONG x 200 DEEP
100% SOLID: .......TYPE S / 15 / A / M. (16" x 8"), SYMMETRICAL UNDER BEARING POINT. 3.2.B. FOR 76mm DEEP DECK PROFILES, CONNECT THE FIRST, THIRD AND FIFTH LOW CORRUGATIONS (24/3 CONFIGURATION), AND EACH
1.3. WELDING SHALL CONFORM TO CSA STANDARD W59 AND BE PERFORMED BY A FABRICATOR CERTIFIED TO CSA W47.1. SUPPORT PARALLEL TO FLUTE DIRECTION AT 300mm [12"] MAXIMUM CENTERS. CONNECTIONS SHALL BE MADE USING EITHER AN ARC SPOT
1.4. BEAM CONNECTIONS SHALL BE DESIGNED FOR A MINIMUM OF FACTORED VERTICAL SHEAR FORCE OF 50% OF THE BEAM SHEAR CAPACITY. 2.1.2. FOR INTERIOR ABOVE GRADE WALLS USE EITHER: 3.1.4. PROVIDE A MINIMUM OF ONE CONTINUOUS COURSE 200mm (8") OF SOLID OR GROUTED VOID BLOCKS OR BRICKS LAID IN MORTAR AT THE 2550 Victoria Park Ave. Suite 602
2.1.2.1. LIGHTWEIGHT LOAD BEARING BLOCKS: TOP COURSE IMMEDIATELY BELOW ALL FLOOR AND ROOF BEARING LEVELS. WELD WITH 20mm [3/4"] NOMINAL TOP DIAMETER, OR MECHANICALLY FASTENED USING HILTI POWDER ACTUATED FASTENERS (X-HSN24, Toronto ON M2J 5A9 Tel: (416) 635 9970
UNLESS OTHERWISE NOTED, AND IN NO CASE BE LESS THAN THE LOADS SHOWN ON OR IMPLIED BY THE DRAWINGS. WHERE BOLTED HILTI X-ENP19, OR EQUIVALENT).
CONNECTIONS ARE UTILIZED, A MINIMUM OF TWO BOLTS PER CONNECTION SHALL BE USED. STANDARD HOLLOW: ......TYPE H / 15 / C / M. 3.2. TOLERANCES: www.stephenson-eng.com info@stephenson-eng.com
75% AND 100% SOLID: ......TYPE S / 15 / C / M. UNLESS OTHERWISE NOTED ON THE ARCHITECTURAL DRAWINGS AND / OR SPECIFICATION, SHALL CONFORM TO CSA A371. 3.2.C. FOR ROOF DECKS, SIDE LAPS OF ADJACENT NESTABLE UNITS SHALL BE CRIMPED TOGETHER AT 900mm [36"] CENTRES, OR FASTENED
1.5. MEMBER CONNECTIONS SHALL BE DESIGNED BY A LICENSED PROFESSIONAL ENGINEER FOR FORCES AND MOMENTS INDICATED. SHOP WITH HILTI M HWH SCREWS (SLC01, SLC02, OR EQUIVALENT).
DRAWINGS AND CALCULATIONS BEARING THE STAMP AND SIGNATURE OF THE REGISTERED PROFESSIONAL ENGINEER RESPONSIBLE FOR 2.1.2.2. ULTRA LIGHT (OR EQUIVELANT) BLOCKS: 3.3. COLD WEATHER CONSTRUCTION:- REQUIREMENTS AND PROTECTION SHALL CONFORM TO CSA A371 AND UNDER NO CIRCUMSTANCES SHALL OFES SI ON A L
3.3. FOR STEEL FLOOR DECK, UNLESS OTHERWISE DETERMINED DURING THE DIAPHRAGM CONNECTION DESIGN OR SPECIFIED OTHERWISE IN THE PR
STANDARD HOLLOW: .......TYPE H / 15 / D / M. MASONRY CONSTRUCTION BE PERMITTED WHEN THE AIR TEMPERATURE FALLS BELOW -12°C.

ED
THE DESIGN SHALL BE SUBMITTED FOR REVIEW PRIOR TO FABRICATION AND ERECTION.

EN
SPECIFICATIONS OR ENGINEERING DRAWINGS, THE MINIMUM ATTACHMENT OF THE DECK TO THE BEARING SURFACES AND THE MINIMUM SIDE LAP 18_08_10

NS
(REFER TO ARCHITECTURAL DRAWINGS AND SCHEDULES FOR LOCATIONS AND TYPES). 4. QUALITY CONTROL

GIN
2. PRODUCTS

LI CE
CONNECTIONS BETWEEN DECK UNITS SHALL BE:

EER
2.1. STRUCTURAL STEEL SECTIONS SHALL CONFORM TO CSA-G40.20/G40.21 (UNLESS NOTED OTHERWISE ON PLANS OR SECTIONS). 2.2. CLAY BRICKS: 4.1. WHEN REQUESTED SAMPLING AND TESTING SHALL CONFORM TO CSA STANDARDS S304.1 AND ASTM C140. REFER ALSO TO GENERAL NOTES.
2.1.1. S SHAPES, CHANNELS, ANGLES, PLATES AND RODS: - GRADE 300 W TO CONFORM TO ONE OR MORE OF CSA STANDARDS A82.(SERIES) SEE ARCHITECTURAL DRAWINGS AND / OR SPECIFICATIONS FOR TYPES AND 3.3.A. SIDE LAPS OF ADJACENT FLOOR UNITS SHALL BE CRIMPED TOGETHER AT 600mm [24"] MAXIMUM ON CENTRE, BUT NOT EXCEEDING THE
SPACING REQUIRED FOR THE APPLICABLE ULC FIRE RATED ASSEMBLY.
H.A. McCALLUM
2.1.2. HSS SECTIONS: - GRADE 350W ( CLASS C U/N ) STYLES OF BRICKS REQUIRED. UNLESS OTHERWISE NOTED, THE MINIMUM COMPRESSIVE STRENGTH (BRICK FLATWISE) GROSS AREA
SHALL BE 20 MPa. 3.3.B. DECK SUPPORTS PARALLEL AND PERPENDICULAR TO FLUTES SHALL BE WELDED WITH 20mm [3/4'] WELDS AT 300mm [12"] MAXIMUM

O
PR
2.1.3. WWF SHAPES, W SHAPES, WT SHAPES: - GRADE 350W

RI
SPACING, BUT NOT EXCEEDING THE SPACING REQUIRED FOR THE APPLICABLE ULC FIRE RATED ASSEMBLY. VI TA

O
2.2. JOIST CHORDS AND WEBS SHALL CONFORM TO CSA - S16. 2.3. MORTAR: NC
3.3.C. THE REQUIRED PUDDLE WELDS AT SUPPORTS MAY BE SUBSTITUTED WITH POWDER ACTUATED FASTENERS THAT PROVIDE EQUIVALENT E OF ON
2.3. BOLTS FOR CONNECTIONS TO CONFORM TO ASTM F3125/3125M, GRADE A325 OR A325M, UNLESS NOTED. TO CONFORM TO CSA A179
FOR LAYING ALL LOAD BEARING CONCRETE BLOCKS .........USE TYPE "S" MORTAR UNLESS NOTED. DIAPHRAGM SHEAR CAPACITY PER METRE.
2.4. ANCHOR RODS FOR BASE PLATES, BEARING PLATES AND WELD PLATES TO CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED. 3.4. INSTALL ALL POWDER ACTUATED AND SCREW FASTENERS ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.
2.5. NUTS AND WASHERS TO CONFORM TO ASTM A563 AND ASTM F436. FOR LAYING ALL CLAY BRICKS ................................................USE TYPE "N" MORTAR UNLESS NOTED.
2.4. MASONRY GROUT: 3.5. WELD STUD SHEAR CONNECTORS THROUGH DECK WHERE REQUIRED BY DRAWINGS.
2.6. SHEAR STUDS WHERE REQUIRED TO CONFORM TO ASTM A108, WELDING TO CONFORM TO CSA W59. OFES SI ON A L
TO CONFORM TO CSA A179. THE SLUMP SHALL BE 200mm TO 250mm (8"TO10") AND THE MINIMUM 28 DAY COMPRESSIVE STRENGTH FOR 3.6. "TOUCH-UP" GALVANIZED OR GALVANNEALED SURFACES WITH SPECIFIED PRIMER AT WELDS AND SCRAPES, ETC., BOTH UPPER AND LOWER PR
2.7. WELDING MATERIALS TO CONFORM TO CSA W48.

ED

EN
"FINE" GROUT SHALL BE 15MPa. SURFACES. 18_08_10

NS

GI N
2.8. SURFACE PREPARATION AND PRIMER PAINT FOR STRUCTURAL STEEL MEMBERS AND JOISTS INSIDE VAPOUR BARRIER TO CONFORM TO 3.7. DO NOT SUSPEND CEILING OR MECHANICAL/ELECTRICAL SERVICES FROM U/S OF STEEL DECK.

LI CE
2.5. MASONRY CONNECTORS (ANCHORS, FASTENERS AND TIES):

EE R
CISC/CPMA 1.73a OR CISC/CPMA 2.75 (IF EXPOSED TO VIEW), UNLESS NOTED ON DRAWINGS OR SPECIFICATIONS. 4. QUALITY CONTROL J. C. GASDIA
2.9. HOT DIP GALVANIZING SHALL PROVIDE A MINIMUM ZINC COATING OF 600g/sq.m UNLESS OTHERWISE SPECIFIED. SHALL CONFORM TO CSA A370, AND BE INSTALLED TO COMPLY WITH CSA A371.
SPACING, STRENGTH AND GALVANIZING OF STRIP TIES, DOVETAIL ANCHORS, BAR ANCHORS, ROD ANCHORS, STRAP ANCHORS, WALL AND 4.1. AN INDEPENDENT INSPECTION AND TESTING COMPANY IS TO BE ENGAGED TO CARRY OUT AND REPORT ON THE FOLLOWING INSPECTION 100169574
2.11. BRIDGING AND BRACING FOR JOISTS BY JOIST DESIGNER: - SEE DRAWINGS AND TYPICAL DETAILS FOR MINIMUM REQUIREMENTS. SERVICES:
3. EXECUTION PARTITION ANCHORS SHALL COMPLY WITH CSA A370.

O
PR
4.1.a. SECTION PROFILE, GAUGE AND STEEL GRADE.

RI
2.6. HORIZONTAL JOINT REINFORCEMENT FOR ALL MASONRY WALLS: VI TA

O
3.1. FABRICATION, HANDLING AND ERECTION SHALL CONFORM TO CAN/ CSA - S16. 4.1.b. ZINC COATING.
NC
E OF ON
3.2. TOLERANCES: VARIATION FROM PLUMB AND LEVELNESS OF STRUCTURAL FRAMING SHALL BE IN ACCORDANCE WITH SPECIFICATIONS AND THE FOLLOWING ARE MINIMUM REQUIREMENTS:
TYPICAL DETAILS. 2.6.1. CONFORM TO CSA STANDARDS A370 AND A371. LINTEL NOTES A07 4.1.c . WELDED JOINTS.
4.1.d. BEARINGS.
2.6.2. REINFORCEMENT SHALL BE AN APPROVED CONTINUOUS "LADDER" TYPE, PREFABRICATED WITH 3.66mm DIAMETER (9 GAUGE)
3.5. FIELD “ TOUCH-UP " BOLTS, WELDS, BURNED OR SCRAPED SURFACES AFTER ERECTION.
LONGITUDINAL AND CROSS WIRES. 4.1.e. SIDE LAP CONNECTIONS. Simcoe County
3.6. NO HOLES OTHER THAN THOSE SHOWN ON REVIEWED SHOP DRAWINGS SHALL BE MADE IN ANY STEEL MEMBER WITHOUT WRITTEN UNLESS OTHERWISE SHOWN OR NOTED ON THE STRUCTURAL DRAWINGS, PROVIDE LINTELS OVER ALL OPENINGS IN MASONRY WALLS, AS FOLLOWS: District School Board
2.6.3. SPACING:- PROVIDE REINFORCING IN THE TOP COURSE IMMEDIATELY BELOW FLOOR AND ROOF BEARING LEVELS AND THE FIRST TWO 4.1.f. TOUCH-UP PRIMER.
PERMISSION OF THE STRUCTURAL CONSULTANT. 1. FOR OPENINGS UP TO 1200 mm (4'-0") CLEAR;
COURSES ABOVE AND BELOW EVERY WALL OPENING.THE REINFORCING SHALL EXTEND 600mm (24") BEYOND SUCH OPENINGS. FOR THE 4.1.g. FIELD CUTTING AND/OR ALTERATIONS.
3.7. CO-ORDINATE WITH MECHANICAL AND ELECTRICAL CONSULTANTS AND SUB-TRADES WHOSE WORK MAY EFFECT DETAILING, FABRICATION 1.1. ONE ANGLE 90 x 90 x 6 ( 3 1/2" x 3 1/2" x 1/4") FOR EACH 100mm (4") OF WALL THICKNESS OR PORTION THEREOF.
REMAINDER OF WALLS, THE VERTICAL SPACING SHALL NOT EXCEED 400mm (16"). 4.2. REFER ALSO TO THE GENERAL NOTES, SPECIFICATIONS, AND TERMS OF REFERENCE FOR ADDITIONAL INFORMATION.
AND ERECTION OF THE STEEL STRUCTURE. OR
3.8. WHEREVER ITEMS ARE TO BE HUNG FROM JOISTS, CONNECT TO THE TOP CHORDS AT PANEL POINTS, UNLESS OTHERWISE PERMITTED. 2.6.4. OVERLAP SPLICES: 1.2. 200mm (8") DEEP MASONRY LINTEL BLOCK REINFORCED WITH 1-10M BOTTOM FOR EACH 100mm (4") OF WALL THICKNESS OR PORTION THEREOF.
3.9 PROVIDE L76X76X6.4(MIN) ANGLE SEATS FOR ALL STEEL DECK AT LOCATIONS WHERE THE CONNECTION TO SUPPORTING FRAMING IS SHALL BE A MIN. OF 150mm (6") FOR KNURLED WIRE AND 300mm (12") FOR PLAIN WIRE. 2. FOR OPENINGS FROM 1200mm (4'-0") CLEAR TO 1800mm (6'-0") CLEAR;
INTERRUPTED. (EG. AT COLUMNS) LAPS SHALL BE STAGGERED A MINIMUM OF 750mm (30") FROM COURSE TO COURSE.
REINFORCING SHALL NOT PASS THROUGH A VERTICAL CONTROL JOINT UNLESS OTHERWISE SHOWN.
2.1. ONE ANGLE 125 x 90 x 8 LONG LEG VERTICAL ( 5"x 3 1/2" x 5/16") FOR EACH 100mm (4") OF WALL THICKNESS OR PORTION THEREOF. COLD WEATHER CONCRETING A13
3.10. PROVIDE ALL NECESSARY TEMPORARY BRACING TO KEEP STRUCTURE SAFE AND PLUMB. BRACING SHOWN ON STRUCTURAL DRAWINGS IS OR
PERMANENT FOR FINISHED BUILDING ONLY. 2.6.5. CORROSION RESISTANCE: 2.2. 200mm (8") DEEP MASONRY LINTEL BLOCK REINFORCED WITH 1-15M BOTTOM FOR EACH 100mm (4") OF WALL THICKNESS OR PORTION THEREOF.
3.11. PROVIDE A MINIMUM OF 2-12 mm (1/2") DIAMETER BY 250 (10") LONG WALL ANCHORS FOR ALL BEAM AND JOIST BEARING PLATES ON JOINT REINFORCING FOR ALL WALLS IN CONTACT WITH SOIL, EXTERIOR WALLS AND WALLS IN A MOIST ENVIRONMENT SHALL BE HOT 3. ALL LINTELS TO BEAR 150mm (6") MINIMUM AT EACH END ON SOLID MASONRY, UNLESS SHOWN OTHERWISE. FOR FORECASTED AIR TEMPERATURES AT OR BELOW 5°C CLEARVIEW MEADOWS
MASONRY, OR AN APPROVED EQUAL, UNLESS OTHERWISE NOTED. BEAMS AND JOIST SHOES TO BE WELDED TO BEARING PLATES. DIPPED GALVANIZED AFTER FABRICATION TO ASTM A153,458 gm/sq.meter (1.5 oz. / sq. foot). 4. PAIRS OF LINTEL ANGLES ARE TO BE BOLTED OR WELDED TOGETHER, PRIOR TO SHIPMENT, AT MAXIMUM 450mm (18") CENTRES. ELEMENTARY SCHOOL
3.12. PROVIDE ADJUSTABLE ANCHORS TO ALL STEEL TO BE BUILT INTO, ABUTTED BY, OR FACED WITH MASONRY (REFER ALSO TO TYPICAL 2.6.6. COMPOSITE AND CAVITY WALLS: 5. MASONRY LINTEL BLOCKS MAY ONLY BE USED IN LOAD-BEARING WALLS WITH PERMISSION AND MUST BE FILLED WITH 20 MPa CONCRETE. MORTAR IS 1. ALL MATERIALS AND EQUIPMENT NEEDED FOR HEATED ENCLOSURE AND CONCRETE CURING PROTECTION SHALL BE ON HAND AND READY FOR USE ADDITION
DETAILS FOR VERTICAL SPACING .............................. 600 ( 24") MAX. CENTRES. WHERE COURSING OF WYTHES DO NOT ALIGN OF WHERE IT IS DESIRABLE AND PERMITTED TO BUILD ONE WYTHE BEFORE THE OTHER, NOT ACCEPTABLE AND WILL BE REJECTED. BEFORE CONCRETE PLACEMENT IS STARTED.
FOR HORIZONTAL SPACING ........................ 10 TIMES WALL THICKNESS* (MAX. 2000 (6'-8") CENTRES) REINFORCING SHALL BE AN APPROVED ADJUSTABLE TYPE WITH A BOX OR EYE SECTION WHICH EXTENDS INTO THE COLLAR JOINT OR 6. STEEL LINTELS ARE TO BE SUPPLIED BY STEEL CONTRACTOR BUT PLACED BY GENERAL CONTRACTOR OR MASONRY SUB- CONTRACTOR. 2. FORMS AND/OR STEEL DECK IS TO BE HEATED TO A MINIMUM OF 5°C. CONCRETE SHALL NOT BE PLACED ON ANY SURFACE BELOW 5°C.
12 Locke Avenue
( * NOTE, USE BACK-UP WYTHE THICKNESS ONLY, FOR CAVITY WALLS.) CAVITY AND RESTRAINS THE TRANSVERSE MOVEMENT OF THE TWO WYTHES. FOR CAVITY WALLS WITH RIGID INSULATION, EXTENSION SHALL BE 7. STEEL CONTRACTOR TO SUPPLY ALL NECESSARY DIRECTIONS REQUIRED FOR PLACING STEEL LINTELS. 3. FORMS AND/OR STEEL DECK MUST BE FREE OF SNOW AND ICE PRIOR TO POURING CONCRETE. THE USE OF ANY DE-ICING CHEMICAL IS NOT Stayner, Ontario
3.13. WHERE STEEL PROVIDES LATERAL BRACING ONLY TO MASONRY ( I.E. DOES NOT SUPPORT MASONRY) ANCHORS SHALL PERMIT DESIGNED TO HOLD THE INSULATION IN PLACE BY USE OF PLASTIC WEDGES OR APPROVED EQUAL. GALVANIZED HOOK STYLE "BOX TIES" OR 8. WHILE EVERY EFFORT HAS BEEN MADE TO SHOW ON THE STRUCTURAL DRAWINGS EACH AND EVERY LINTEL OVER DOORS, MECHANICAL AND PERMITTED ON THE FORMWORK OR STEEL DECK. L0M 1S0
DIFFERENTIAL VERTICAL MOVEMENT BETWEEN STRUCTURAL MEMBERS AND MASONRY. "PIN-TIES" SHALL EXTEND INTO THE FACE WYTHE TO COMPLETE THE ASSEMBLY. ELECTRICAL SERVICES, RECESSES AND POCKETS ETC., THROUGH LOAD-BEARING MASONRY WALLS, IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY 4. FOR SLABS LESS THAN 1000mm THICK THE MINIMUM CONCRETE TEMPERATURE AT TIME OF POURING IS TO BE 10°C. FOR SLABS GREATER THAN
4. QUALITY CONTROL 2.6.7. PROVIDE ALL PREFABRICATED CORNER AND TEE SECTIONS. TO CO-ORDINATE AND SUPPLY ALL LINTELS REQUIRED THROUGH ALL WALLS (INCLUDING NON-LOAD BEARING WALLS) THROUGHOUT THE PROJECT. 1000mm THICK THE MINIMUM CONCRETE TEMPERATURE AT TIME OF POURING IS TO BE 5°C. DRAWING TITLE
4.1. AN INDEPENDENT INSPECTION AND TESTING COMPANY IS TO INSPECT STRUCTURAL STEEL AND STEEL DECK IN THE SHOP AND IN THE FIELD 2.7. COMPOSITE WALLS:- SHALL HAVE THE VERTICAL COLLAR JOINTS BETWEEN WYTHES COMPLETELY FILLED WITH MORTAR OR GROUT. UNLESS OTHERWISE DIRECTED, LINTELS SHALL CONFORM TO THE ABOVE REQUIREMENTS. 5. CONCRETE TEMPERATURE SHALL BE KEPT AT A MINIMUM OF 10°C FOR AT LEAST 3 DAYS OR UNTIL THE CONCRETE REACHES 40% OF THE
2.8. BOND BEAMS:- MADE FROM LINTEL BLOCKS, OR HALF WEB BLOCKS, WHERE SHOWN ON STRUCTURAL DRAWING SHALL CONFORM TO CSA A371. 9. REFER ALSO TO TYPICAL DETAILS. SPECIFIED STRENGTH. ADDITIONAL CURING MAY BE REQUIRED IN WHICH CONCRETE SHALL BE KEPT AT A MINIMUM OF 10°C FOR AT LEAST 7 DAYS
FOR WELDING, CONNECTIONS, BOLT TORQUES, AND GENERAL CONFORMANCE WITH THE STRUCTURAL DRAWINGS AND SPECIFICATIONS.
2.9. GROUTING:- BY FILLING VOIDS OF HOLLOW UNITS AND REINFORCED HOLLOW UNITS SHALL CONFORM TO CSA A179 (MORTAR IS NOT ACCEPTABLE). OR UNTIL THE CONCRETE REACHES 70% OF THE SPECIFIED STRENGTH. GENERAL NOTES AND
4.2 SEE SPECIFICATIONS FOR ADDITIONAL INSPECTION AND TESTING REQUIREMENTS.
2.10. EXPANSION AND CONTROL JOINTS: 6. IF THE FORECASTED AIR TEMPERATURE IS TO FALL BELOW 0°C, THE TOP OF SLAB SHALL BE PROTECTED FROM FREEZING. TOP OF SLAB TYPICAL DETAILS
SHALL BE PROVIDED. SEE ARCHITECTURAL DRAWINGS AND/ OR SPECIFICATION FOR DETAILS. PROTECTION SHALL BE PLACED AS TO NOT AFFECT THE FINISH OF THE SLAB.
PROJECT NO: SCALE
7. IF THE FORECASTED AIR TEMPERATURE IS TO FALL BELOW 0°C WITH REASONABLY HIGH WINDS THE CONCRETE MUST BE PROTECTED FROM

DATE PLOTTED: 8/1/2018 8:39:34 AM


FLASH FREEZING DURING PLACEMENT AND FINISHING. THIS PROTECTION MUST REMAIN IN PLACE UNTIL TOP OF SLAB PROTECTION HAS BEEN 20171969 1:1
INSTALLED AS PER NOTE #6. DRAWN BY: DRAWING NO:
Author
* SEE ALSO CSA A23.1-09/A23.2-09 CLAUSES 7.4.1.5 AND 7.4.2 FOR ADDITIONAL INFORMATION WITH RESPECT TO COLD WEATHER CONCRETING AND
CURING. CHECKED BY:
Checker
S3-01 3
DATE:
April 30, 2018
ALTERATIONS AND / OR CONNECTIONS TO EXISTING STRUCTURE A15 POST-INSTALLED ANCHORS A16 THICKENING OF SLAB ON GRADE CG02
(READ IN CONJUNCTION WITH DETAILS CG03)

REVISION
ALTERATIONS AND/OR CONNECTIONS TO EXISTING STRUCTURE 1. GENERAL
1. COORDINATE PROPOSED SCHEDULE OF WORK WITH ALL THE SUBTRADES, CONSULTANTS AND OWNER. 1.1 PROVIDE ALL LABOUR, MATERIALS AND EQUIPMENT TO COMPLETE THE FASTENING INTO CAST-IN-PLACE CONCRETE INDICATED ON THE
2. SUBMIT PROPOSED SEQUENCE OF WORK TO CONSULTANT FOR REVIEW PRIOR TO START OF WORK. DRAWINGS AND AS SPECIFIED HEREIN. POURED CONCRETE STAIR PRECAST STAIR

ISSUED FOR PERMIT AND TENDER


3. INSPECT THE EXISTING BUILDING AND BECOME THOROUGHLY FAMILIAR WITH THE EXISTING CONDITIONS.
NOTE: DETAILS SHOWN ARE BASED ON INFORMATION FROM EXISTING BUILDING DRAWINGS ONLY.

ISSUED FOR COORDINATION


2. QUALITY ASSURANCE 15M@300x900 LG. DOWELS
SHEAR KEY TO SUIT

80% WORKING DRAWINGS


4. CHECK ALL DRAWINGS AGAINST ACTUAL SITE CONDITIONS PRIOR TO FABRICATING ANY STRUCTURAL STEEL. REPORT DISCREPANCIES 2.1 FOR POST-INSTALLED CONCRETE OR MASONRY ANCHORS, PRIOR TO COMMENCEMENT OF WORK, THE CONTRACTOR SHALL ARRANGE (15M@12"X3'-0"LG)
TO THE CONSULTANT BEFORE PROCEEDING WITH THE WORK. FOR A MANUFACTURER’S FIELD REPRESENTATIVE TO PROVIDE INSTALLATION TRAINING FOR ALL PRODUCTS TO BE USED. ONLY TRAINED PRECAST STAIR-SEE
5. PRIOR TO FABRICATION OF STRUCTURAL STEEL, OPEN UP ALL AREAS TO ALLOW THE INSTALLATION OF THE NEW STRUCTURAL WORK, AS INSTALLERS SHALL PERFORM POST-INSTALLED ANCHOR INSTALLATIONS. A RECORD OF TRAINING SHALL BE KEPT ON SITE AND BE MADE 38x89 SHEAR KEY PRECAST SUPPLIER
WELL AS THE CONNECTION OF NEW WORK TO THE EXISTING WORK. TAKE ANY AND ALL NECESSARY FIELD MEASUREMENTS. MODIFY AVAILABLE TO THE STRUCTURAL CONSULTANT OR INDEPENDENT INSPECTION AND TESTING COMPANY REPRESENTATIVE AS REQUESTED.

SLAB ON

SLAB ON
2-10M CONT. 2-10M CONT.

GRADE

GRADE
INSTALLATION METHODS AND METHODS OF CONNECTING TO SUIT SITE CONDITIONS FOUND AND TO THE APPROVAL OF THE TRAINING TO CONSIST OF A REVIEW OF THE COMPLETE INSTALLATION PROCESS FOR THE SPECIFIC POST-INSTALLED ANCHORS, AND MUST EACH SIDE EACH SIDE
CONSULTANT. CARRY OUT LOCAL REPAIRS TO THE EXISTING WORK AS NECESSARY AND AS DIRECTED BY THE CONSULTANT. INCLUDE BUT NOT BE LIMITED TO:
6. SHORE EXISTING WORK AS REQUIRED UNTIL ALL NEW WORK HAD BEEN COMPLETED AND REVIEWED BY THE CONSULTANT.
7. SHORE FLOORS AS REQUIRED TO SUPPORT CRANES, HOISTS AND OTHER CONSTRUCTION EQUIPMENT. (A) HOLE DRILLING PROCEDURE.
8. CONFORM TO ALL THE APPLICABLE CODES AND BYLAWS CONCERNING SAFETY, NOISE AND VIBRATIONS.

150

150
(6")

(6")

No. DATE
(B) HOLE PREPARATION AND CLEANING TECHNIQUE.

18_08_10
18_05_22
18_04_30
1 1
9. DO NOT CUT CONCRETE REINFORCEMENT UNLESS REVIEWED AND APPROVED BY THE CONSULTANT. (C) ADHESIVE INJECTION TECHNIQUE AND DISPENSER TRAINING/MAINTENANCE.
1 1
10. PERFORM CONCRETE SCANS (SEE NOTE #13 BELOW) AND MODIFY THE LAYOUT OF NEW THROUGH BOLTS, DRILLED ANCHORS AND OTHER (D) REBAR DOWEL PREPARATION AND INSTALLATION.

CLEAR

CLEAR
75(3")
75(3")
ANCHORING DEVICES AS REQUIRED TO AVOID DAMAGING EXISTING CONCRETE REINFORCEMENT. (E) PROOF LOADING/TORQUING. 300(12")TYP. 300(12")TYP.
11. UNLESS NOTED OTHERWISE, ALL DOWELS ARE TO BE EPOXIED INTO THE EXISTING STRUCTURE USING HILTI HIT RE-500 SYSTEM 10M@250B 10M@250B

3
2
1
ADHESIVE SYSTEM, OR APPROVED ALTERNATIVE. 2.2 ADHESIVE ANCHORS SUPPORTING SUSTAINED TENSION LOADS SHALL BE INSTALLED BY A CERTIFIED ADHESIVE ANCHOR INSTALLER (AAI) AS (10M@ 10"B) 450 (1'-6") (10M@ 10"B) 450 (1'-6")
12. CUTTING OPENINGS AND HOLES IN EXISTING STRUCTURES: CERTIFIED BY ACI/CRSI. PROOF OF CURRENT CERTIFICATION SHALL BE SUBMITTED TO THE STRUCTURAL CONSULTANT PRIOR TO 3-10M B CONT. (TYP.) 3-10M B CONT. (TYP.) THE CONTRACTOR SHALL CHECK ALL DIMENSIONS
(A) PRIOR TO CUTTING AND CORING ANY OPENINGS IN THE EXISTING BUILDING, PROVIDE THE CONSULTANT WITH A SLEEVING WITH THE LATEST ISSUE OF
COMMENCEMENT OF INSTALLATION.
ARCHITECTURAL, MECHANICAL AND ELECTRICAL
DRAWINGS INDICATING THE SIZE AND LOCATION OF THE PROPOSED NEW OPENINGS RELATIVE TO THE EXISTING GRID LINES.
DRAWINGS. REPORT ANY DISCREPANCIES TO THE
EXISTING OPENINGS IN THE VICINITY OF THE NEW OPENING MUST ALSO BE SHOWN. 3. PRODUCTS CL STAIR TREAD AND CL STAIR TREAD & ARCHITECT BEFORE PROCEEDING WITH WORK.
(B) UNLESS SPECIFICALLY NOTED OTHERWISE, LOCATE EXISTING REINFORCEMENT AND ANY EMBEDDED SERVICES BY AN APPROPRIATE 3.1 POST-INSTALLED CONCRETE ANCHORS THICKENING THICKENING
CONCRETE SCANNING METHOD (SEE NOTE #13) 3.1.1 MECHANICAL ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193 FOR CRACKED
(C) AFTER ALL THE EXISTING REINFORCEMENT AND SERVICES HAVE BEEN LOCATED, NOTIFY THE CONSULTANT WHO WILL REVIEW AND AND UNCRACKED CONCRETE, AND SEISMIC APPLICATIONS, UNLESS NOTED OTHERWISE. DRAWINGS ARE NOT TO BE SCALED. CONTRACTOR MUST
CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS ON
APPROVE THE PROPOSED OPENING/HOLE LOCATIONS PRIOR TO CUTTING/DRILLING. MAKE ANY NECESSARY ADJUSTMENTS TO THE 3.1.2 ADHESIVE ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ACI 355.4 AND ICC-ES AC308 FOR CRACKED THICKENING AT POURED THICKENING AT PRECAST THE PROJECT; AND MUST REPORT ANY DISCREPANCIES
HOLE LOCATIONS AS DIRECTED BY THE CONSULTANT. AND UNCRACKED CONCRETE, AND SEISMIC APPLICATIONS, UNLESS NOTED OTHERWISE.
(D) CORE DRILL NEW HOLES FOR PIPES TO A DIAMETER NOT LARGER THAN THE OUTSIDE PIPE DIAMETER PLUS 25MM. DO NOT CUT 3.2 POST-INSTALLED MASONRY ANCHORS CONCRETE STAIR CONCRETE STAIR TO THE CONSULTANTS BEFORE PROCEEDING WITH THE
WORK. THE USE OF THIS DRAWING OR PART THEREOF IS
EXISTING REINFORCEMENT OR SERVICES WITHOUT PRIOR APPROVAL OF THE CONSULTANT. 3.2.1 MECHANICAL ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC01 OR AC106. FORBIDDEN WITHOUT THE WRITTEN APPROVAL OF THE
(E) WHERE RECTANGULAR OPENINGS ARE TO BE CUT, PRE-DRILL THE CORNERS USING A 100 MM DIAMETER CORE DRILL OR DRILL A 3.2.2 ADHESIVE ANCHORS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC58. CONSULTANTS.
SERIES OF HOLES TO PREVENT OVER CUTTING OF THE CORNERS. 3.3 POWER DRIVEN FASTENERS
(F) IN ANY AREAS WHERE THE CONSULTANT PERMITS THE CUTTING OF EXISTING REINFORCEMENT, THE CONTRACTOR SHALL EXAMINE 3.3.1 POWER DRIVEN FASTENERS SHALL HAVE BEEN TESTED AND QUALIFIED FOR USE IN ACCORDANCE WITH ICC-ES AC70.
THE CORE/OPENING AFTER DRILLING/CUTTING TO THE DETERMINE THE SIZE, COVER AND ORIENTATION OF ANY REINFORCEMENT
THAT WAS CUT. THE CONTRACTOR IS TO MARK THIS INFORMATION ON THE SLEEVING DRAWING AND FORWARD A COPY OF IT TO 4. EXECUTION MAX. 190mm (7.5")
THE CONSULTANT FOR HIS RECORDS. 4.1 POST INSTALLED ANCHORS SHALL BE USED ONLY WHERE SPECIFIED ON STRUCTURAL DRAWINGS. WALL REINF.
13. CONCRETE SCANS 4.2 THE INSTALLATION OF POST INSTALLED ANCHORS FOR MISSING OR MISPLACED CAST IN-PLACE ANCHORS IS NOT ALLOWED UNLESS APPROVED BY STEEL STAIR WHEN SPECIFIED
(A) LOCATE EXISTING CONCRETE REINFORCEMENT USING SUITABLE SCANNING DEVICE AS AUTHORIZED BY PROPERTY MANAGER THE STRUCTURAL CONSULTANT.
(I.E. X-RAYS, GROUND PENETRATION RADAR (GPR), LOCAL CHIPPING OF SLAB - ONLY WHERE APPROVED BY THE STRUCTURAL 4.3 ANCHOR CAPACITY USED IN THE DESIGN HAS BEEN BASED ON THE TECHNICAL DATA PUBLISHED BY THE MANUFACTURER. SUBSTITUTION SLAB REINF SLAB REINF.
CONSULTANT, ETC) REQUESTS FOR ALTERNATE ANCHORS MUST BE APPROVED IN WRITING BY THE STRUCTURAL CONSULTANT PRIOR TO USE. CONTRACTOR SHALL WHEN SPECIFIED

MAX. 5000mm
WHEN SPECIFIED
(B) GPR SCANNING MUST BE DONE BY TRAINED TECHNICIANS WITH AT LEAST 5 YEARS OF EXPERIENCE AS SUCH. PROVIDE CALCULATIONS STAMPED BY LICENSED PROFESSIONAL ENGINEER DEMONSTRATING THAT THE ALTERNATIVE ANCHOR IS CAPABLE OF 150 150

SLAB ON

SLAB ON
(C) GPR SCANNING DEVICES MUST BE CAPABLE OF ACCURATELY LOCATING REBAR IN A CONCRETE SLAB TO A MINIMUM DEPTH OF 300 mm, ACHIEVING THE PERFORMANCE VALUES OF THE SPECIFIED PRODUCT. SUBSTITUTIONS WILL BE EVALUATED FOR COMPLIANCE WITH THE 2-10M CONT. 2-10M CONT. (6") (6")

GRADE

GRADE
(16'-5")
WITHIN A HORIZONTAL TOLERANCE OF +- 25 mm AND A VERTICAL (DEPTH) TOLERANCE OF THE LARGER OF +-25 mm OR +- 15% OF THE RELEVANT BUILDING CODE AND CSA A23.3 STANDARD. ADHESIVE ANCHOR EVALUATION WILL ALSO CONSIDER CREEP, IN-SERVICE TEMPERATURE EACH SIDE EACH SIDE
REBAR DEPTH. AND INSTALLATION TEMPERATURE.
(D) THE REVIEW OF REBAR SCANS OR X-RAYS BY THE STRUCTURAL CONSULTANT IS LIMITED TO THE LOCATION OF THE PROPOSED CORES 4.4 THE EXISTING REINFORCEMENT IN THE CONCRETE STRUCTURE OR EMBEDDED CONDUITS MAY CONFLICT WITH THE SPECIFIED ANCHOR
OR DRILLED HOLES THROUGH THE EXISTING STRUCTURE ONLY, BASED ON THE ASSUMPTION THAT THE X-RAY OR SCAN RESULTS ARE LOCATIONS. EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE SHALL NOT BE CUT UNLESS APPROVED BY THE STRUCTURAL

150
(6")
150
(6")
ACCURATE. STEPHENSON EGINEERING LTD. TAKES NO RESPONSIBILITY FOR THE ACCURACY OF THE X-RAY OR SCAN RESULTS. CONSULTANT. THE CONTRACTOR SHALL LOCATE THE EXISTING REINFORCEMENT AND CONDUITS AT THE PROPOSED LOCATIONS OF THE ANCHORS 1 1
BY AN APPROVED NON-DESTRUCTIVE METHODS SUCH AS GROUND PENETRATING RADAR (GPR) OR X-RAYS. MODIFY THE STRUCTURAL ANCHOR 1 1
DETAILS AS REQUIRED TO AVOID CUTTING REBAR OR CONDUITS, AND SUBMIT THE REVISED DETAILS FOR REVIEW BY STRUCTURAL CONSULTANT
PRIOR TO PROCEEDING WITH THE WORK. 10M@250B 10M@250B
4.5 ALL ANCHORS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS (MPII) IN ONJUNCTION (10M@ 10"B) (10M@ 10"B)
WITH EDGE DISTANCE, SPACING AND EMBEDMENT DEPTH AS INDICATED ON THE DRAWINGS. 450 (1'-6") CL PARTITION
3-10M B CONT. (TYP.) 3-10M B CONT. (TYP.)
4.6 ADHESIVE ANCHORS MUST BE INSTALLED IN CONCRETE AGED A MINIMUM OF 21 DAYS. AND THICKENING
NOTE:
CL STAIR BEARING REFER TO CG03 FOR SLAB THICKENING UNDER
AND THICKENING MASONRY PARTITION SEPARATING HEATED AND
UNHEATED AREAS

THICKENING AT THICKENING AT
STEEL STAIR MASONRY PARTITIONS

TYPICAL CONCRETE COVER TABLE C01 COMPRESSION-TENSION DEVELOPMENT AND LAP LENGTHS Fy = 400 MPa C02A TENSION DEVELOPMENT AND LAP SPLICE LENGTHS Fy = 400 MPa C02B
ELEMENTS EXPOSED TO EARTH PROJECT SPECIFIC COMMENTS BAR SIZE COVER (mm) NOTES
1. STANDARD ABBREVIATIONS ON PLANS AND SCHEDULES SHOULD BE AS FOLLOWS NOTES
PERMANENTLY EXPOSED TO SOIL CLS - COMPRESSION LAP SPLICE 1. STANDARD ABBREVIATIONS ON PLANS AND SCHEDULES SHOULD BE AS FOLLOW
ALL SIZES 50 TLS - TENSION LAP SPLICE
CDL - COMPRESSION DEVELOPMENT LENGTH
HEL - HOOK EMBEDMENT LENGTH TDL - TENSION DEVELOPMENT LENGTH
CAST AGAINST AND PERMANENTLY EXPOSED TO SOIL
ALL SIZES 75

TABLE NOTES
1. CONCRETE COVER SHALL BE MEASURED FROM THE DEEPEST POINT OF TEXTURED CONCRETE SURFACE TO THE NEAREST DEFORMATION OF REINFORCEMENT. REINFORCEMENT INCLUDES TIES, STIRRUPS AND MAIN BARS. COMPRESSION LAP SPLICE AND DEVELOPMENT LENGTHS (Fy = 400 MPa) TENSION LAP SPLICE AND DEVELOPMENT LENGTHS (Fy = 400 MPa)
2. THE SMALLER NUMBER IN THE TABLE CELL APPLIES TO PARKING GARAGE STRUCTURE WHERE VERTICAL ELEMENTS ARE PROTECTED BY 100mm EXTENSION OF MEMBRANE ABOVE THE FLOOR OR APPROVED SEALER. OTHERWISE THE LARGER NUMBER SHALL BE USED.
3. FOR VERTICAL ELEMENTS WITH CONCRETE COVER EXCEEDING 53mm, PROVIDE WIRE MESH REINFORCEMENT WITH MINIMUM 1.57mm DIAMETER WIRE WITH 100mm OPENINGS AT MID-POINT OF COVER.
4. FOR CONCRETE COVER FOR BUNDLED BARS, REFER TO THE DESIGN DRAWINGS. CLS: COMPRESSION LAP SPLICE LENGTH (mm)
stephenson
ENGINEERING
TLS: TENSION LAP SPLICE LENGTH (CLASS B) (mm)
UNCOATED BLACK BAR
10M 15M 20M 25M 30M 35M 45M 55M UNCOATED BLACK BAR 2550 Victoria Park Ave. Suite 602
300 440 590 730 880 1030 NOT PERMITTED 10M 15M 20M 25M 30M 35M Toronto ON M2J 5A9 Tel: (416) 635 9970
fc' Top Bottom Top Bottom Top Bottom Top Bottom Top Bottom Top Bottom www.stephenson-eng.com info@stephenson-eng.com
CDL: COMPRESSION DEVELOPMENT LENGTH (mm) 20MPa 550 420 820 630 1090 840 1710 1310 2050 1570 2390 1840
OFES SI ON A L
25MPa 490 380 740 570 980 750 1530 1170 1830 1410 2130 1640 PR
UNCOATED BLACK BAR

ED

EN
18_08_10

NS
fc'

GIN
10M 15M 20M 25M 30M 35M 45M 55M 30MPa 450 350 670 520 890 690 1390 1070 1670 1290 1950 1500

LI CE

EER
35MPa 420 320 620 480 830 640 1290 990 1550 1190 1800 1390
20MPa 250 340 420 540 640 770 940 1210
40MPa 390 300 580 450 770 600 1210 930 1450 1110 1690 1300
H.A. McCALLUM
25MPa 220 310 370 600 570 690 840 1080
45MPa 370 300 550 420 730 560 1140 880 1370 1050 1590 1230

O
PR
30MPa 200 280 340 440 530 630 770 990

RI
VI TA

O
NC
35MPa 200 280 340 440 530 630 770 990 50MPa 350 300 520 400 690 530 1080 830 1300 1000 1510 1160 E OF ON
40MPa 200 280 340 440 530 630 770 990 55MPa 330 300 500 380 660 510 1030 790 1240 950 1440 1110

> 40 MPa SEE MINIMUM VALUES FOR f'c = 40 MPa 60MPa 320 300 480 370 630 490 990 760 1180 910 1380 1060
64MPa 310 300 460 360 610 470 960 740 1150 880 1340 1030 OFES SI ON A L
NOTES: PR

ED

EN
1. IF BUNDLED BARS ARE USED THE VALUES IN THE TABLES MUST BE INCREASED: 18_08_10

NS

GI N
TDL: TENSION DEVELOPMENT LENGTH (mm) CLASS "A" LAP SPLICE

LI CE
a. MULTIPLY BY 1.1 (TWO BAR BUNDLES) b. MULTIPLY BY 1.2 (THREE BAR BUNDLES) c. MULTIPLY BY 1.33 (FOUR BAR BUNDLES)

EE R
J. C. GASDIA
UNCOATED BLACK BAR 100169574
2. FOR EMBEDMENTS ENCLOSED IN SPIRALS, MULTIPLY BY 0.75, BUT NOT LESS THAN 200mm.
10M 15M 20M 25M 30M 35M

O
PR
fc'

RI
HEL: MINIMUM TENSION EMBEDMENT LENGTH WITH STANDARD HOOK (mm) Top Bottom Top Bottom Top Bottom Top Bottom Top Bottom Top Bottom VI TA

O
NC
E OF ON
20MPa 420 330 630 490 840 650 1310 1010 1570 1210 1840 1410
UNCOATED BLACK BAR 25MPa 380 300 570 440 750 580 1170 900 1410 1080 1640 1260
fc' 10M 15M 20M 25M 30M 35M 45M 55M
30MPa 350 300 520 400 690 530 1070 830 1290 990 1500 1160 Simcoe County
20MPa 220 340 450 560 670 780 1010 1230 District School Board
35MPa 320 300 480 370 640 490 990 770 1190 920 1390 1070
25MPa 200 300 400 500 600 700 900 1100
40MPa 300 300 450 350 600 460 930 720 1110 860 1300 1000
30MPa 180 270 370 460 550 640 830 1010
45MPa 300 300 420 330 560 430 880 680 1050 810 1230 940
35MPa 170 250 340 420 510 590 770 930
50MPa 300 300 400 310 530 410 830 640 1000 770 1160 900
40MPa 160 240 320 400 470 550 720 870
55MPa 300 300 380 300 510 390 790 610 950 730 1110 850
45MPa 150 220 300 370 450 520 680 820
60MPa 300 300 370 300 490 380 760 590 910 700 1060 820
50MPa 150 210 280 350 420 490 640 780
55MPa 150 200 270 340 400 470 610 750
64MPa 300 300 360 300 470 360 740 570 880 680 1030 790 CLEARVIEW MEADOWS
NOTES:
ELEMENTARY SCHOOL
NOTES: ADDITION
1. FOR EPOXY COATED BARS THE VALUES IN THE TABLES MUST BE INCREASED: 1. FOR EPOXY COATED BARS THE VALUES IN THE TABLES MUST BE INCRESED:
a. MULTIPLY BY 1.2 (WHEN CLEAR COVER GREATER THAN 3 X BAR DIAMETER AND CLEAR SPACING GREATER THAN 6 X BAR DIAMETER) a. MULTIPLY BY 1.2 (WHEN CLEAR COVER GREATER THAN 3 X BAR DIAMETER AND CLEAR SPACING GREATER THAN 6 X BAR DIAMETER)
b. MULTIPLY BY 1.5 (WHEN COVER OR SPACING ARE LESS THAN ABOVE) b. MULTIPLY BY 1.5 (WHEN COVER OR SPACING ARE LESS THAN ABOVE) 12 Locke Avenue
2. VALUES PROVIDED ARE BASED ON NORMAL WEIGHT CONCRETE AND MUST BE INCREASED FOR LIGHTWEIGHT CONCRETES: Stayner, Ontario
2. VALUES PROVIDED ARE BASED ON NORMAL WEIGHT CONCRETE AND MUST BE INCREASED FOR LIGHTWEIGHT CONCRETES: L0M 1S0
a. MULTIPLY BY 1.2 (FOR SEMI-LOW DENSITY CONCRETE) a. MULTIPLY BY 1.2 (FOR SEMI-LOW DENSITY CONCRETE)
b. MULTIPLY BY 1.3 (FOR LOW-DENSITY CONCRETE) b. MULTIPLY BY 1.3 (FOR LOW-DENSITY CONCRETE) DRAWING TITLE
3. FOR 35M AND SMALLER BARS MULTIPLY THE VALUES IN THE TABLE BY 0.7 (BUT NOT LESS THAN 150mm) WHERE THE SIDE COVER 3. IF BUNDLED BARS ARE USED THE VAULES IN THE TABLES MUST BE INCREASED:
(NORMAL TO THE PLANE OF THE HOOK) IS AT LEAST 60mm, AND FOR 90° HOOKS WHERE COVER ON THE BAR EXTENSION BEYOND THE HOOK a. MULTIPLY BY 1.1 (TWO BAR BUNDLES)
IS AT LEAST 50mm. b. MULTIPLY BY 1.2 (THREE BAR BUNDLES) TYPICAL DETAILS
4. FOR 35M AND SMALLER BARS MULTIPLY THE VALUES IN THE TABLE BY 0.8 (BUT NOT LESS THAN 150mm) WHERE THE HOOK IS ENCLOSED c. MULTIPLY BY 1.33 (FOUR BAR BUNDLES)
WITHIN AT LEAST THREE(3) TIES OR STIRRUPS SPACED ALONG A LENGTH EQUAL TO THE INSIDE DIAMETER OF THE HOOK AT A SPACING NOT
MORE THAN 3 TIMES THE BAR DIAMETER. PROJECT NO: SCALE

DATE PLOTTED: 8/1/2018 8:39:36 AM


20171969 1:1
DRAWN BY: DRAWING NO:
Author

CHECKED BY:
Checker
S3-02 3
DATE:
April 30, 2018
SLAB ON GRADE DETAILS CG01A SLAB ON GRADE DETAILS CG01B SLAB ON GRADE DETAILS CG01C TYPICAL SLAB-ON-GRADE DETAILS CG03
(READ IN CONJUNCTION WITH DETAIL CG01B, CG01C) (READ IN CONJUNCTION WITH DETAILS CG01A, CG01C) (READ IN CONJUNCTION WITH DETAILS C02) 200 (8")
t/3 BUT NOT LESS THAN

REVISION
5mm [3/16"] 5mm [3/16"]
GRID GRID 40 (1-1/2") FOR t ≤150mm[6"] t/3 BUT NOT LESS THAN
SEE NOTE 1 FILL JOINT WITH FILL JOINT WITH
50 (2") FOR t > 150mm[6"] 40 (1-1/2") FOR t ≤150mm[6"]
APPROVED MATERIAL APPROVED MATERIAL

2xH OR 1250mm (4'-2"),


SEE EXAMPLE B

MAX. HEIGHT TO BE

ISSUED FOR PERMIT AND TENDER


SEE EXAMPLE A 50 (2") FOR t > 150mm[6"]

VARIES-SEE ARCH.
CURB, SEE ARCH,

WHICHEVER IS
TRENCH
SAW CUT EDGE OF CIRCULAR REINF. AS PER

SMALLER

ISSUED FOR COORDINATION


FOOTING BELOW

80% WORKING DRAWINGS


TYPICAL DETAIL

t
SLAB ON GRADE

t
GRID
SAW CUT SAW CUT 1500mm (5'-0") MIN.

T
PI
SEE NOTE 2
SAW CUT SLAB REINFORCEMENT

TLS
EDGE OF
PIER CENTRED IN SLAB (SEE PLANS 300mm (12") MIN.
10@200 3-10M
BELOW FOR MORE INFORMATION)
SAWCUTS PARKING LEVEL (S.O.G.)
SAWCUT CONTROL JOINT SAWCUT CONTROL JOINT

t
VARIES-SEE ARCH.
SEE NOTE 1 FOR FIBRE REINFORCED SLAB FOR SLABS WITH ONE LAYER OF REINFORCEMENT

900 (3'-0")MAX.
SEE NOTE 2 SEE NOTE 2

2t

No. DATE
18_08_10
18_05_22
18_04_30
SEE EXAMPLE C 5mm [3/16"]

SEE NOTE 2
PRIOR TO POURING THE SLAB LOCALLY CUT

H
EDGE OF SEE ALTERNATE OPTION
FILL JOINT WITH TOP BARS IN VICINITY OF SAW CUTS
CAISSON SLAB ON GRADE 900mm (36")
EDGE OF PIER BELOW

")
APPROVED MATERIAL t/3 BUT NOT LESS THAN 50 (2")

m(12
BELOW

3
2
1
2-10M

300m
SLOPES TO 2
GRID THE CONTRACTOR SHALL CHECK ALL DIMENSIONS
EDGE OF STAGGER BARS PARALLEL DRAIN SEE ARCH.
OUTLINE OF SONOTUBE
CAISSON CAP TO SAW CUT LOCATIONS 1 TYPICAL STEP IN WITH THE LATEST ISSUE OF

t
ARCHITECTURAL, MECHANICAL AND ELECTRICAL
BELOW SEE NOTE 1 SEE NOTE 2

t
SAWCUT SLAB-ON-GRADE DRAWINGS. REPORT ANY DISCREPANCIES TO THE

AD B
ARCHITECT BEFORE PROCEEDING WITH WORK.

GR SLA
HIGHER THAN 2t < 900(3'-0") MAX.

2t
SEE NOTE 2 SEE NOTE 2 CONCRETE 19x38 (1"x2") WOOD STRIP

E
ON ISED
WALL 300mm(12")
SAW CUT 300mm(12") MIN. DRAWINGS ARE NOT TO BE SCALED. CONTRACTOR MUST

RA
SAWCUT CONTROL JOINT 600mm(24") 200mm(8") CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS ON
150mm (6") BEYOND PLACE THIS CONC. NOT SAW CUT FOR SLABS WITH TWO LAYERS OF REINFORCEMENT THE PROJECT; AND MUST REPORT ANY DISCREPANCIES
TO THE CONSULTANTS BEFORE PROCEEDING WITH THE
CONCRETE COLUMNS LESS THAN 7 DAYS 5mm [3/16"]

VARIES-SEE ARCH.
CONCRETE WORK. THE USE OF THIS DRAWING OR PART THEREOF IS
75mm (3") BEYOND AFTER SURROUNDING SEE NOTE 2 5mm [3/16"] FORBIDDEN WITHOUT THE WRITTEN APPROVAL OF THE
BASEPLATE FOR STEEL AREA STEEL TROWEL COLUMN
t/3 BUT NOT LESS THAN t/3 BUT NOT LESS THAN CONSULTANTS.

2t MAX.
COLUMNS. SURFACE OF CONC. 40 (1-1/2") FOR t ≤150mm[6"] SAWCUT AND FILL WITH APPROVED 40 (1-1/2") FOR t ≤150mm[6"]

H
SAWCUT AND FILL WITH APPROVED
50 (2") FOR t > 150mm[6"] JOINT MATERIAL IF CONCRETE IS 50 (2") FOR t > 150mm[6"]
JOINT MATERIAL IF CONCRETE IS
STEEL COLUMN STEEL COLUMN STEEL COLUMN TO REMAIN EXPOSED.
TO REMAIN EXPOSED.
CONCRETE COLUMN CONCRETE COLUMN CONCRETE COLUMN SHEAR KEY PARKING LEVEL (S.O.G.)
FORMED VERTICAL SAW CUT
SLOPES TO

t
CONTROL JOINT
LS
T

t/3 OR 50 (2")

8
SAW CUT SAW CUT SAW CUT MIN. DRAIN SEE ARCH.
(SONOTUBE OR

t
SEE NOTE 2

E
METAL FORM)

2t
AD
ON ED
1
LS
T

GR
AB SS
SL PRE
1
CAISSON
CONCRETE SLAB ON GRADE SLAB ON GRADE PROVIDE DOWELS ACROSS JOINT
SHEAR KEY
PROVIDE DOWELS ACROSS JOINT TYPICAL STEP IN

DE
PIER CIRCULAR CAP WHEN SLAB IS SUBJECTED TO WHEN SLAB IS SUBJECTED TO 40mm (1 ½")
COLUMN
FOOTING STEEL VEHICULAR OR RACKING LOADS 40mm (1 ½")
t/3 OR 50 (2") MIN. VEHICULAR OR RACKING LOADS 600mm(24") 600mm(24") SLAB-ON-GRADE
COLUMN PIER (REFER TO DOWEL TABLE) (REFER TO DOWEL TABLE)
CAISSON 2t MAX.
CONSTRUCTION JOINT CONSTRUCTION JOINT
FOOTING FOOTING
SEE NOTE 1 FOR FIBRE REINFORCED SLAB FOR SLABS WITH ONE LAYER OF REINFORCEMENT MASONRY PARTITION
EXAMPLE A EXAMPLE B EXAMPLE C ALTERNATE OPTION 5mm [3/16"] SEE ARCH.

RA
IS
NOTES: SAWCUT AND FILL WITH APPROVED

ED
NOTES: t/3 BUT NOT LESS THAN COLD WARM
JOINT MATERIAL IF CONCRETE IS

ME
40 (1-1/2") FOR t ≤150mm[6"] PARKING LEVEL (S.O.G.)

CH
1. SAWCUTTING TO BE DONE AS SOON AS POSSIBLE AFTER SLAB IS PLACED. (MAX. 24 HOURS). 1. 1-15 T&Bx1500(5'-0") LG AT EACHCORNER TYP. U.N.O. TO REMAIN EXPOSED.

.P
2. JOINTS TO BE AT MAX. 24x SLAB THICKNESS FOR MAXIMUM AGGREGATE SIZE SMALLER THAN 19mm(¾") AND 30 TIMES SLAB 50 (2") FOR t > 150mm[6"]

AD
2. WHERE CORNER TRIM BARS ARE SHOWN DASHED
CONSTRUCTION JOINT DOWELS

150
(6")
THICKNESS FOR AGGREGATE SIZE LARGER THAN 19mm (¾"),BUT NOT MORE THAN 4500mm (14'-9") THEY ARE NOT REQUIRED IF SAW CUTS ARE PROVIDED 2-15M
3. MAXIMUM RATIO BETWEEN LENGTH AND WIDTH OF ANY PANEL (CREATED BY SAWCUT) SHOULD NOT EXCEED 1.5 AS SHOWN. OTHERWISE PROVIDE 1-15 T&Bx1500(5'-0") LG. SLAB
SAW CUT SLAB TYPICAL S.O.G THICKENING

t
4. COORDINATE EXACT LOCATIONS OF SAWCUTS IN SLAB ON GRADE WITH ARCHITECTURAL REQUIREMENTS. 3. READ IN CONJUNCTION WITH CG01A,C. THICKNESS PLATE DOWELS DOWEL SIZE AND SPACING
5. SAWCUT SLAB ON GRADE AT LOCATIONS SHOWN ON PLAN OR AS NOTED BELOW. ALTERNATE LOCATIONS SHALL BE SUBMITTED REINFORCEMENT
TO CONSULTANT FOR REVIEW, WELL IN ADVANCE OF POURING SLAB ON GRADE.
4. FOLLOW DETAILS UNLESS NOTED OTHERWISE ON "t"
150 150 BETWEEN HEATED AND UNHEATED
PLANS OR DETAILS. 130-150mm AS PER 20@300x250 LG
6. AFTER THE SLAB IS A MINIMUM 60 DAYS OLD, REMOVE ALL DEBRIS FROM THE SAW CUTS AND FILL WITH MORTAR CONTAINING PROVIDE DOWELS ACROSS JOINT SHEAR KEY
180-200mm MANUFACTURER 25@300x330 LG
(6") (6") AREAS (SEE CG02 FOR SLAB-ON-
CEMENT, SAND AND LATEX BONDING AGENT, OR AS NOTED IN SPECIFICATIONS. SEE NOTE 2 WHEN SLAB IS SUBJECTED TO t/3 OR 50 (2") MIN.
7. PRIOR TO SUBSTANTIAL COMPLETION OF THE PROJECT ROUT ALL CRACKS IN THE SLAB ON GRADE AND FILL WITH MORTAR VEHICULAR OR RACKING LOADS
40mm (1 ½")
230-280mm RECOMMENDATION 30@300x380 LG GRADE THICKENING UNDER
CONTAINING CEMENT, SAND AND LATEX BONDING AGENT OR AS NOTED IN SPECIFICATIONS.
8. REFER TO TYPICAL DETAIL CG01B, CG01C FOR SAW CUT DETAILS. SLAB ON GRADE (REFER TO DOWEL TABLE) INTERIOR MASONRY PARTITION)
CONSTRUCTION JOINT
FOR SLABS WITH TWO LAYERS OF REINFORCEMENT

NON-LOAD BEARING BLOCK WALL LINTELS M01A NON-LOAD BEARING BLOCK WALL LINTEL DETAILS M01B
STRUCTURAL STEEL LINTELS
WALL OPENING MASONRY BLOCK THICKNESS
CLEAR SPAN 90 (4") 140 (6") 190 (8") 240 (10") 290 (12")
IF APPLICABLE,
300mm TO 500mm 75mm X 8mm PL 125mm X 8mm PL 175mm X 8mm PL 225mm X 8mm PL 275mm X 8mm PL
LOCATION OF CONTROL
(12" TO 22") (3"x5/16" PL) (5"x5/16" PL) (7"x5/16" PL) (9"x5/16" PL) (11"x5/16" PL)
JOINTS WHERE NOTED IN
550mm TO 1200mm 1-L89x89x6.4 OR 1-L127x89x6.4 (LLH) OR ARCH DETAILS
2-L89x89x6.4 2-L102x89x6.4 (LLH) 3-L89x89x6.4
(22" TO 4'-0") 2-L44x44x4.8 2-L64x44x6.4
1200mm TO 1830mm 1-L127x89x7.9 (LLV) OR
(4'-0" TO 6'-0") 2-L51x38x6.4(LLV)
1-L127x127x7.9 OR
2-L89x64x6.4 (LLV)
2-L127x89x7.6 (LLV) 2-L102x102x7.9 3-L127x89x7.9 (LLV) LINTEL (SEE DETAILS BELOW)
SOLID MASONRY BEARING
stephenson
ENGINEERING
1830mm TO 2440mm 1-L127x127x7.9 OR
1-L127x89x7.9 (LLV) 2-L127x89x7.6 (LLV) 2-L152x102x7.9 (LLV) N/A CLEAR SPAN
(6'-0" TO 8'-0") 2-L89x64x6.4 (LLV)
200mm(8") TYP.
2440mm TO 3080mm W200x27 + W200x27 + 50mm (2") REDUCTION 2550 Victoria Park Ave. Suite 602
1-L127x89x9.5 (LLV) 1-L127x127x7.9 N/A EA. END
(8'-0" TO 10'-0") 175x6.4 PL. BOTTOM 225x6.4 PL. BOTTOM FOR DOOR FRAME Toronto ON M2J 5A9 Tel: (416) 635 9970
3080mm TO 3660mm W200x27 + W200x27 + www.stephenson-eng.com info@stephenson-eng.com
N/A N/A N/A
(10'-0" TO 12'-0") 175x6.4 PL. BOTTOM 225x6.4 PL. BOTTOM
OFES SI ON A L
STRUCTURAL STEEL LINTEL NOTES: LINTEL DETAILS PR

ED

EN
1. WHEN PROVIDING MULTIPLE ANGLES SEE DIAGRAMS FOR ORIENTATION. BOLT DOUBLE ANGLES BACK TO BACK 18_08_10

NS

GIN
LI CE

EER
USING 16mmØ BOLTS OR PROVIDE 6mmX50mm (1/4"x2") LONG WELDS @450mm (18") O/C STARTING AT 100mm (4") MAX
FROM THE EACH END OF THE LINTEL. H.A. McCALLUM
2. SAWCUT WEBS OF BLOCK IN COURSE OF BLOCK OVER OPENING AS NECESSARY TO INSTALL ANGLES.

O
3. ALTERNATIVES PROVIDED FOR CASES WHERE EXPOSED FACE OF SINGLE ANGLE IS NOT ACCEPTABLE.

PR

RI
VI TA

O
NC
MASONRY BEAM LINTELS E OF ON

WALL OPENING MASONRY BLOCK THICKNESS


SINGLE ANGLE WITH PROVIDE BLOCK ON
CLEAR SPAN 90 (4") 140 (6") 190 (8") 240 (10") 290 (12")
EXPOSED FACE EACH SIDE OF BEAM OFES SI ON A L
0mm TO 1200mm 190 (8") DEEP 190 (8") DEEP 190 (8") DEEP 190 (8") DEEP 190 (8") DEEP PR

ED

EN
(0" TO 4'-0") 1-10M T&B 1-10M T&B 2-10M T&B 2-10M T&B 2-10M T&B 18_08_10

NS

GI N
LI CE
1200mm TO 1830mm 190 (8") DEEP 190 (8") DEEP 190 (8") DEEP 190 (8") DEEP 190 (8") DEEP SINGLE ANGLE TWO ANGLE W SECTION +PLATE THREE ANGLE

EE R
(4'-0" TO 6'-0") 1-15M T&B 1-15M T&B 2-10M T&B 2-10M T&B 2-10M T&B
J. C. GASDIA
100169574
1830mm TO 2440mm 190 (8") DEEP 190 (8") DEEP 190 (8") DEEP 190 (8") DEEP
N/A

O
PR
(6'-0" TO 8'-0") 1-15M T&B 2-15M T&B 2-15M T&B 2-15M T&B

RI
STRUCTURAL STEEL LINTEL DETAILS VI TA

O
NC
2440mm TO 3080mm 390 (16") DEEP 390 (16") DEEP 390 (16") DEEP 390 (16") DEEP E OF ON
N/A
(8'-0" TO 10'-0") 2-15M T&B 2-15M T&B 2-15M T&B 2-15M T&B
MASONRY BEAM LINTEL NOTES:
REMOVE BLOCK WEB Simcoe County
1. BEAM MUST BE FILLED WITH 20MPa TYPE N CONCRETE OR APPROVED GROUT EQUIVALENT (MORTAR IS NOT 10@200 STIRRUPS District School Board
LOCALLY AS REQUIRED TO
ACCEPTABLE).
INSTALL REINFOCEMENT REINFORCE AS NOTED
2. TEMPORARILY SHORE LINTEL UNTIL GROUT HAS REACHED FULL DESIGN STRENGTH.
10@200 STIRRUPS (TOP BARS HOOKED @
EACH END)
FULL MORTAR BED STANDARD BLOCK

LINTEL LENGTH
AS NOTED
(TYP.) COURSE

190
(8")
REINFORCE AS NOTED FULL MORTAR BED
(TOP BARS HOOKED @ CLEARVIEW MEADOWS
(TYP.)
EACH END) BLOCK ELEMENTARY SCHOOL
ADDITION
MASONRY LINTEL MASONRY LINTEL WIDTH
BLOCK BLOCK
12 Locke Avenue
SINGLE COURSE MASONRY SINGLE COURSE DOUBLE COURSE SINGLE COURSE Stayner, Ontario
LINTEL MASONRY LINTEL MASONRY LINTEL PRECAST LINTEL L0M 1S0
(SINGLE REBAR T&B) (TWO REBAR T&B) DRAWING TITLE

TYPICAL DETAILS
MASONRY AND PRECAST BEAM LINTEL DETAILS
PROJECT NO: SCALE

DATE PLOTTED: 8/1/2018 8:39:38 AM


20171969 1:1
DRAWN BY: DRAWING NO:
Author

CHECKED BY:
Checker
S3-03 3
DATE:
April 30, 2018
TYPICAL DETAIL OF CONSTRUCTED CORNERS IN SINGLE
TYPICAL "DOUBLE COURSE" DEPTH REINFORCED MASONRY LINTEL BEAM M02 TYPICAL REINFORCED EXTERIOR MASONRY WALLS AND PIERS PLAN DETAIL M03 TYPICAL ELEVATION REINFORCED MASONRY WALLS AND PIERS M04 WYTHE MASONRY WALLS (NO CONTROL JOINT)
M06

REVISION
BULL NOSE IF
SPECIFIED BY
ARCHITECT

ISSUED FOR PERMIT AND TENDER


A
LINTELS, SEE STRUCTURAL DRAWINGS.

ISSUED FOR COORDINATION


80% WORKING DRAWINGS
LINE OF BLOCK AT
ALTERNATE COURSES.
VERT. REINF.
150 BEARING AND GROUT VARIES. 150 BEARING
FOR LINTEL FOR LINTEL A=A=190
ROOF FOR REINFORCING
SEE PLAN NOTES,
SCHEDULES, TYPICAL ALTERNATE COURSES

No. DATE
18_08_10
18_05_22
18_04_30
DETAILS AND
BREAK OUT PORTIONS OF SPECIFICATIONS.
BLOCKS WEBS SUFFICIENT A

VARIES
TO INSTALL REINFORCING

(TY N
STANDARD BLOCK

E
P.)

3
2
1
OP
BARS. LOCATE LAPS TO
COURSE

BULL NOSE IF THE CONTRACTOR SHALL CHECK ALL DIMENSIONS


SUIT. WITH THE LATEST ISSUE OF
FLOOR SPECIFIED BY
CONCRETE FILL SEE DETAIL ARCHITECTURAL, MECHANICAL AND ELECTRICAL
ARCHITECT DRAWINGS. REPORT ANY DISCREPANCIES TO THE
(MORTAR IS NOT ACCEPTABLE) ON M03

190 BLOCK
ARCHITECT BEFORE PROCEEDING WITH WORK.
LINTEL LENGTH

"INSPECTION OPENINGS"
AS NOTED

B
CAN BE EITHER
FULL MORTAR BED (TYP.) DRAWINGS ARE NOT TO BE SCALED. CONTRACTOR MUST
SIDE OF WALL TO SUIT
CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS ON
CONSTRUCTION. PLACE GROUT THE PROJECT; AND MUST REPORT ANY DISCREPANCIES
IN MAX. 1500 (5'-0")
MASONRY LINTEL

TO THE CONSULTANTS BEFORE PROCEEDING WITH THE


BLOCK UNITS
(BOND BEAM)

LIFTS (TYP.) WORK. THE USE OF THIS DRAWING OR PART THEREOF IS


STANDARD RETURN FORBIDDEN WITHOUT THE WRITTEN APPROVAL OF THE
REINFORCE AS NOTED S.O.G B=B=240 OR 290 CONSULTANTS.
(TOP BARS HOOKED @ EACH END) CORNER UNIT

T.O. FOOTING
PIER SIZE VARIES ALTERNATE COURSES
U/ S FOOTING

B
FOR MASONRY REINFORCING, ARCHITECTURAL DOWELS TO MATCH
MASONRY FACING AND CAVITY CONSTRUCTION VERTICALS
TEMPORARY SHORE UNTIL REFER TO ARCHITECTURAL DRAWINGS. BULL NOSE IF
CONCRETE ATTAINS DESIGN
SPECIFIED BY
STRENGTH.
WALL THICKNESS NOTE: ARCHITECT

190 BLOCK
(LINTEL WIDTH AS NOTED)
NOTE: • PROVIDE MINIMUM LAP SPLICES FOR VERTICAL REINFORCING (BASED ON 15MPa GROUT):
• 10M - 500mm (20")
1. GROUT TO CONFORM TO REQUIREMENTS OF CSA STANDARD A179-M CLAUSE 8.1 TABLE 3 "FINE GROUT". SLUMP SHALL BE ±

A
• 15M - 700mm (2'-4")
200mm A AND COMPRESSIVE STRENGTH SHALL BE A MINIMUM OF 15 MPa @ 28 DAYS.
• 20M - 1000mm (3'-4")
2. COMPRESSIVE TESTING OF GROUT SHALL BE CARRIED OUT BY THE APPROVED INSPECTION AND TESTING COMPANY IN
ACCORDANCE WITH CSA STANDARD A179-M. PREPARE A MINIMUM 3 TESTS FOR EACH STOREY OF CONSTRUCTION. 1 TEST SHALL • LAP ALL HORIZONTAL LADDER TYPE REINFORCING 500mm.
COMPRISE OF 3 CUBES FOR TESTING, 1 AT 7 DAYS AND 2 AT 28 DAYS. • ANY CROSSWIRES WITHIN LAP LENGTH SHALL BE REMOVED.
NOTE: - MORTAR IS NOT ACCEPTABLE FOR USE AS GROUT , AND IF USED PIERS SHALL BE REJECTED AND RE-CONSTRUCTED. • LAPS SHALL BE STAGGERED A MINIMUM OF 750mm FROM COURSE TO COURSE. INFILL EVERY 2nd COURSE
3. ALL CELLS CONTAINING VERTICAL REINFORCING SHALL BE COMPLETELY FILLED WITH GROUT IN LIFTS NOT EXCEEDING FROM 100% SOLID UNITS CONDITION 1, A = 290 B = 190
NOTE:
1. CONCRETE STRENGTH 20 MPa (CLASS N) UNLESS NOTED. 2400mm.GROUT SHALL BE CONSOLIDATED BY PUDDLING OR VIBRATING DURING POURING. CONDITION 2, A = 240 B = 190
2. REFER TO PLANS AND LINTEL SCHEDULE FOR LOCATION. 4. AT EACH LIFT "INSPECTION" OPENINGS SHALL BE PROVIDED AT THE BOTTOMS OF CELLS TO BE FILLED. THE CLEANOUTS ALTERNATE COURSES CONDITION 3, A = 290 B = 240
3. MAXIMUM BEARINGS AT EACH END OF LINTEL BEAM TO BE 200mm (8"). SHALL BE INSPECTED BY THE ENGINEER BEFORE BEING SEALED.
5. SEE TYPICAL DETAIL ELEVATION M04.
B

NOTE:
1. PROVIDE PREFABRICATED CORNERS FOR HORIZONTAL JOINT REINFORCING (TYPICAL).
2. REFER TO TYPICAL LOAD BEARING MASONRY NOTES AND TO THE SPECIFICATION FOR MASONRY
MATERIALS AND FOR HORIZONTAL JOINT REINFORCING
TYPICAL STEEL BEAM BEARING ON END OR CORNER OF MASONRY WALL
NON LOAD-BEARING MASONRY PARTITION REINFORCING SCHEDULEE I FaSa(0.2)<0.35 M07A.1 DETAILS OF NON LOAD-BEARING MASONRY WALLS M07B TYPICAL STEEL BEAM BEARING ON MASONRY WALL (PERPENDICULAR) M08 (MINIMUM REQUIREMENTS)
M09
AT CONCRETE SLAB AND WALL
PARTITIONS IN BASEMENT (INTERIOR) (DIFFERENTIAL PRESSURE 0.25kPa)
VERTICAL HORIZONTAL CLIP ANGLES
BLOCK HEIGHT AND
REINFORCING REINFORCEMENT SPACING FASTENER FASTENER. WELDS
LEVEL SEE-MO7, MO7A
140 ≤3800 [12'-5"] 1400 (4'-6") CLIP L100x75x6 LLH @ 'S' o/c

40 (1½")
(L4"x3"x1/4" LLH @'S' o/c) EACH WALL BEARING PLATE (WP) BOTTOM PLATE WALL BEARING PLATE (WP)
9 GA @ 400mm WHERE REQUIRED
SIDE, STAGGERED WITH 1-15 Ø
190 ≤ 5600 [18'-4"] UNREINFORCED (1'-4") o/c MAX. 1900 (6'-3")
(5/8") SELF DRILL INSERT IN WELDS
"LADDER" TYPE
EACH CLIP

stephenson

EQ

WALL, BEAM & WP


240 ≤ 7000 [22'-11"] 2400 (7'-11") CLIP ANGLE/

MIN. 400 (16")

BEAM & WP
GROUT FILL
LATERAL BRACE.
SEE-MO7, MO7A

CL
ENGINEERING

CL
INTERIOR PARTITIONS ABOVE GRADE (DIFFERENTIAL PRESSURE 0.5kPa) 25mm (1")MIN.
25 (1") 2550 Victoria Park Ave. Suite 602

EQ
VERTICAL HORIZONTAL VERTICAL HORIZONTAL CLIP ANGLES COMPRESSIBLE FILLER. 10 (3/8")
BLOCK HEIGHT AND HEIGHT AND
REINFORCING REINFORCEMENT REINFORCING REINFORCEMENT SPACING FASTENER 50 (2") 16 (5/8") MIN. Toronto ON M2J 5A9 Tel: (416) 635 9970

40 (1½")
2400 [7'-10"] < H SEE ARCH. DRAWINGS 50 (2") 50 (2") www.stephenson-eng.com info@stephenson-eng.com
140 ≤ 2400 [7'-10"] 1400 (4'-6") CLIP L100x75x6 LLH @ 'S' o/c
≤ 4200 [13'-9"] FOR SIZE AND LOCATION
(L4"x3"x1/4" LLH @'S' o/c) EACH
9 GA @ 400mm 9 GA @ 400mm OF PARTITION OR NON-LOAD SECTION OFES SI ON A L
190 ≤ 3800 [12'-5"] UNREINFORCED (1'-4") o/c MAX. 3800 [12'-5"] < H ≤ 15 @ 1200 [4'-0"] (1'-4") o/c MAX. 1900 (6'-3")
SIDE, STAGGERED WITH 1-15 PR
BEARING WALL.

ED
Ø (5/8") SELF DRILL INSERT IN ELEVATION

EN
5800 [19'-0"]
"LADDER" TYPE o/c "LADDER" TYPE 18_08_10

NS

GIN
EACH CLIP JOINT REINFORCING.

LI CE
4200 [14'-0"] < H ≤

EER
240 ≤ 4200 [14'-0"] 2400 (7'-11")
6800 [22'-8"]
t
SEE PLAN NOTES,
SCHEDULES, TYPICAL t PLAN VIEW PLAN VIEW H.A. McCALLUM
DETAILS AND SPECIFICATIONS

O
PR

RI
VI TA

O
SEE MO7, MO7A NC
E OF ON
NOTES:
ALLOWABLE PARTITION HEIGHTS ARE BASED ON 15MPa NORMAL DENSITY BLOCK w/ TYPE 'N' MORTAR.
FILL ALL CELLS WITH
LEVEL GROUT FIRST COURSE. 5 BUILD MASONRY TIGHT TO
65 (2½") MIN.
(3/16") BEAM WEB OFES SI ON A L
PR

ED

EN
18_08_10

NS

GI N
25 (1") 50 (2") 5
65 (2½") MIN.

LI CE

EE R
(3/16")
SECTION VIEW SECTION VIEW 50 (2") 16 (5/8") MIN. J. C. GASDIA
100169574
LATERAL SUPPORT OF NON LOAD-BEARING MASONRY WALLS BUILD MASONRY TIGHT TO
25 (1") GROUT(±)

O
BEAM WEB

PR
AT UNDERSIDE OF CONCRETE SLABS/PRECAST CORE SLABS*

RI
VI TA

O
NC
E OF ON
*G.C. TO COORDINATE WITH
CONTINUOUS VERTICAL DOVETAIL ANCHOR SLOTS 25 (1") GROUT(±) WP 10 (3/8")
CORE SLAB SUPPLIER

WITH SPECIFIED GROUT


CONCRETE COLUMN BEFORE PENETRATING WP 50 (2")
Simcoe County
OR WALL UNDERSIDE OF PRECAST District School Board

SOLID FILL
MIN. 2 COURSES
CORE SLABS
FACE OR END OF

GROUT FILL
ANCHORS
ANCHORS
CONCRETE

HORIZ. MASONRY REINF.


VARIES

100 (4")
MAX
CLEARVIEW MEADOWS
VERTICAL WALL REINF. ELEMENTARY SCHOOL
WHERE SPECIFIED ADDITION

12 Locke Avenue
800 O/C (31½") MAX. TYPICAL SECTION NOTE: ELEVATION Stayner, Ontario
L0M 1S0
(COORDINATE WITH ARCH.)
NOTE:
REFER TO TYPICAL DETAILS, TYPICAL NOTES, SPECIFICATION PLANS AND SCHEDULES FOR: DRAWING TITLE
DOVETAIL ANCHORS
REFER TO TYPICAL DETAILS, TYPICAL NOTES, SPECIFICATION PLANS AND SCHEDULES FOR:
PLAN VIEW AT MAX. VERTICAL PLAN VIEW • WP SIZE AND SIZE/NUMBER OF ANCHORS
SPACING 400mm (16")
• VERTICAL WALL REINFORCING TYPICAL DETAILS
• WP SIZE AND SIZE/NUMBER OF ANCHORS
MASONRY WALL ABUTTING CONCRETE MASONRY FACING CONCRETE • VERTICAL WALL REINFORCING • GROUT MIX AND EXTENT OF GROUT
• GROUT MIX AND EXTENT OF GROUT PROJECT NO: SCALE

DATE PLOTTED: 8/1/2018 8:39:39 AM


20171969 1:1
DRAWN BY: DRAWING NO:
Author

CHECKED BY:
Checker
S3-04 3
DATE:
April 30, 2018
TYPICAL DETAIL AT CONTROL JOINT IN REINFORCED MASONRY WALL M10 TYPICAL LATERAL SUPPORT AT PARTITIONS M14 ADJUSTABLE MASONRY ANCHORS TO STRUCTURAL STEEL M15 STEEL JOIST 'UPLIFT' BEARING ON MASONRY WALL M16
DECK CLOSURE 25mm(1") MIN. CLEAR FILLED WITH

REVISION
OWSJ OR LSSJ COMPRESSIBLE MATERIAL.
FACE OF STRUCTURAL MEMBER

ISSUED FOR PERMIT AND TENDER


TO SUIT 40 (1 1/2") x 5 (3/16") STEEL STRAP ANCHORS
@ 600 o/c FOR 190 & LARGER, @400 o/c FOR
MASONRY

ISSUED FOR COORDINATION


140 BLOCK.

80% WORKING DRAWINGS


FITTED INTO COURSES AND CONNECTED
TO STEEL MEMBER AS SHOWN. FACE OF CENTRE OF BEARING
CONTROL JOINT (SEE ARCH. STRUCTURAL TO BE WITHIN t/3
50 (2")
HORIZ. WIRE REINF. TO STOP 50mm(2") FOR DETAILS AND LOCATIONS) MEMBER
CLEAR OF CONTROL JOINT
t/3
PROVIDE 1 GROUTED VERTICAL BAR IN CELL
C130x10 @ 'S' o/c (C5x6.7 @ 'S' o/c) 65 (2 1/2") 90 (3 1/2")±
ADJACENT TO CONTROL JOINT JOIST
WELD TO JOISTS AND / OR LEAVE 25mm(1") MIN. 40 (1 1/2")
L-75x75x6x150 LONG (L-3x3x1/4"x6" LONG)

No. DATE
18_08_10
18_05_22
18_04_30
BEAMS. EACH SIDE OF WALL. WEDGE TIGHT TO CLEAR AROUND
25 (1") CLEAR AT T&B BRIDGING WALL ANDWELD TO JOIST OR CHANNEL OWSJ OR BEAMS WELD SHOE TO
ROOF DECK
5 (3/16") PL "U" SLEEVE WALL PLATE. SEE
WELDED TO STEEL MEMBER TYPICAL DETAIL FOR
L100x75x6LLV x 700(±)LONG (L3"x3"x¼" x 2'-4"(±) LONG)
COMPOSITE CONCRETE AND STEEL

3
2
1
C/W (3) MIN.-M12 HS1@ 'S' o/c EACH SIDE, STAGGERED. MINIMUM REQUIREMENTS
DECK FLOOR OR ROOF ELEVATION PLAN THE CONTRACTOR SHALL CHECK ALL DIMENSIONS
40 MIN. WALL PLATE WITH THE LATEST ISSUE OF

DEPTH
SHOE
(1½") TOP COURSE FILLED (SEE ROOF MEMBER ARCHITECTURAL, MECHANICAL AND ELECTRICAL

.
CONTROL JOINT (SEE ARCH. MASONRY ANCHOR DETAILS WALL PLATE SCHEDULE) DRAWINGS. REPORT ANY DISCREPANCIES TO THE
SOLID, CUT TO SUIT ARCHITECT BEFORE PROCEEDING WITH WORK.
FOR DETAILS AND LOCATIONS) PL. 100x6x700 (4"x¼"x2'-4") REFER TO ARCHITECTURAL
C/W (3) MIN.-M12 HS1 (HILTI) @ TYP.
5 (⅜") DWGS/SPECS FOR BRICK-TIES
'S' L100x75x6LLV x 100 LONG AND BLOCK REINFORCING DRAWINGS ARE NOT TO BE SCALED. CONTRACTOR MUST

320 [12 - 1/2"]


(L3"x3"x¼" x 4" LONG) 300 (1'-0") MIN. 25mm (MIN.) CLEAR DETAILS CHECK AND VERIFY ALL DIMENSIONS AND CONDITIONS ON
WALL PERPENDICULAR TO DECK 25mm(1") MIN. CLEAR FILLED INTO MASONRY. BETWEEN MASONRY AND THE PROJECT; AND MUST REPORT ANY DISCREPANCIES
EACH SIDE OF WALL TO THE CONSULTANTS BEFORE PROCEEDING WITH THE
FLUTES WITH COMPRESSIBLE WALL PARALLEL TO DECK FLUTES (TYP.) STEEL.
WORK. THE USE OF THIS DRAWING OR PART THEREOF IS
MATERIAL.-SEE ARCH. SEE ALSO DESIGN CRITERIA EXTEND BOTTOM CHORD OF
PROVIDE 1 GROUTED VERTICAL BAR IN CELL STOP HORIZ. WIRE REINFORCING (BLOK-LOK OR EQUIV.) FORBIDDEN WITHOUT THE WRITTEN APPROVAL OF THE
IF STEEL BM OR JOISTS EXCEEDS 'S' o/c ADD NOTES. JOIST AND CONNECT TO BEAM CONSULTANTS.
ADJACENT TO CONTROL JOINT 50mm(2") CLEAR OF JOINT CL STEEL BM
TOP OF STEEL L150x75x6 + 1-12 mmØ EXPANSION ANCHOR. PROVIDE COMPRESSIBLE FLANGE AT 2000 o/c
OR JOISTS TO SUIT MASONRY
BM OR JOIST. MASONRY AS
MATERIAL OR REQUIRED.
CURSING
MORTAR FILL.
BOTTOM CHORD
BRACE
LATERAL SUPPORT 1-15M BAR
L125x75X6 (L5"x3"x1/4")
LLHx150 (6") LG. L-65x65x5 (L2 1/2"x2 1/2"x3/16") ADJUSTABLE
BRACING @ 'S' o/c. CONTINUOUS CONCRETE FILLED
@ 'S' o/c EACH SIDE MASONRY ANCHORS
MASONRY LINTEL BLOCK BOND BEAM
STAGGERED 25 (1") CLEAR L-75x75x6x150 LONG ADJUSTABLE @600 o/c 25mm MIN. CLEAR BETWEEN GROUTED VERT.
(SEE PLAN FOR EXTENT) BARS AS NOTED ON
BETWEEN U/S (L- 3"x3"x1/4"x6" LONG) MASONRY ANCHORS, U/S BEAM AND TOP OF 25 MPa CONCRETE
BEAM AND TOP EACH SIDE OF WALL. EACH WAY OR MASONRY. PLANS
25 (1") CLEAR
CAVITY & FACE BRICK AT EXTERIOR OF MASONRY. WEDGE TIGHT TO WALL
CONTROL JOINT (SEE ARCH. PARTITIONS FROM SEE ALSO DESIGN CRITERIA NOTES.
CONDITION AND
FOR DETAILS AND LOCATIONS) STEEL COLUMNS.
WALL PARALLEL TO OWSJ AND/ OR BEAM WELD TO JOIST OR WALL PERPENDICULAR TO OWSJ AND/ OR BEAM
BEAM CLIP L75x75x6x150 LG.
CAVITY WALL
NOTES: @ 'S' O/C STAGGERED
AS SPECIFIED
1. PROVIDE 25mm MIN COMPRESSIBLE MATERIAL TOP OF PARTITION AND UNDERSIDE OF STRUCTURAL. TYPICAL UNLESS NOTED OTHERWISE WELDED TO U/S OF BEAM
2. UNREINFORCED MASONRY WALL (SEISMIC HAZARD INDEX <0.35). ON ARCH. DWGS.
2.1 PROVIDE LATERAL SUPPORTS FOR ALL MASONRY WALLS WHEN SPACING BETWEEN RETURN WALLS EXCEEDS 20t FOR EXTERIOR WALLS AND - EACH SIDE: SPACING `S'
36t FOR INTERIOR WALLS IN ACCORDANCE WITH THE TABLE BELOW (t = THICKNESS OF MASONRY WALL REQUIRING LATERAL SUPPORT). PLAN OF ANCHORS SECTION OF ANCHORS 90 BLOCK 800 (2'-8")
INTERIOR MASONRY PARTITION SIZES: 140 BLOCK 1200 (4'-0")
BLOCK WIDTH SPACING `S' BLOCK WIDTH SPACING `S'
AT STEEL COLUMN AT PERIMETER
PROVIDE 1 GROUTED VERTICAL BAR IN CELL STOP HORIZ. WIRE REINFORCING (BLOK-LOK OR EQUIV.) STEEL BEAM 190 AND
90 BLOCK 900 (2'-11") 190 BLOCK 1900 (6'-3")
ADJACENT TO CONTROL JOINT 50mm(2") CLEAR OF JOINT
140 BLOCK 1400 (4'-6") 240 BLOCK 2400 (7'-11")
LARGER BLOCK 1500 (5'-0") WALL
290 BLOCK 2400 (7'-11") NOTE: THICKNESS (t)
ALTERNATIVE SUITABLE PROPRIETARY BRANDS OF ADJUSTABLE MASONRY ANCHORAGE
2.2 MINIMUM LENGTH OF RETURN WALL IS 10t. IF RETURN WALL IS SHORTER THAN 10t., PROVIDE LATERAL SUPPORT PER DETAILS SHOWN ABOVE.
MECHANISMS MAY BE APPROVED FOE USE, SUCH AS: BLOCK-LOK COLUMN-LOK, DR1 NTS
2.3 MAXIMUM SPACING OF LATERAL SUPPORTS IS 1500 c/c.
2.4 SPACING OF BRACES NOT TO EXCEED 1500 c/c FOR EXTERNAL WALL AND 3000 c/c FOR INTERNAL PARTITIONS. BLOCK-LOK TYPE C WITH BL304 TIES, OR BLOCK-LOK TYPE 'B' ANCHORS WITH BLT1
NOTE: TIES.SUBMIT DETAILS FOR APPROVAL BEFORE PROCEEDING.
2.5 MAXIMUM DISTANCE FROM END OF ANY WALL TO THE CENTERLINE OF THE FIRST LATERAL SUPPORT IS 600mm
1. AT MASONRY LINTEL BOND BEAM STOP HORIZ. BARS 50mm (2")
3. REINFORCED MASONRY WALL (SEISMIC HAZARD INDEX >0.35).
CLEAR OF CONTROL JOINT. UNLESS OTHERWISE NOTED. 3.1 PROVIDE LATERAL SUPPORT FOR ALL MASONRY WALLS.
2. SEE PLANS AND TYPICAL NOTES FOR VERTICAL REINFORCING AND GROUT 3.2 SPACING AND LOCATION OF LATERAL SUPPORT TO MATCH VERTICAL REINFORCEMENT IN THE WALL.
JOIST BEARING ON MASONRY WALL FROM BOTH SIDES WITH UPLIFT
ANCHORAGE (ON COMBINED WALL PLATE)
M17 TYPICAL ROOF MEMBER WALL PLATE SCHEDULE M18 ROOF FRAMING AT OPENINGS IN ROOF DECK SR01
CENTRE OF BEARING 3000 MAX. 3000 MAX.
TO BE WITHIN t/3 ROOF / SKYLIGHT SEE TABLE ROOF / SKYLIGHT SEE TABLE
OPENING 1 OPENING 2
t/3
WELD SHOE TO

2000 MAX
WALL PLATE. SEE
TYPICAL DETAIL FOR B2 B2

stephenson
MINIMUM REQUIREMENTS

2000 MAX.
ROOF DECK
COPE AND REINF.

B1

B1
TYPICAL ROOF MEMBER WALL PLATE SCHEDULE B2 ENGINEERING
(UNLESS OTHERWISE SHOWN) B2
DECK SPAN 2550 Victoria Park Ave. Suite 602
DEPTH

WALL PLATE
SHOE

LOCATION TYPE DESCRIPTION SIZE REMARKS Toronto ON M2J 5A9 Tel: (416) 635 9970
(SEE ROOF MEMEBER www.stephenson-eng.com info@stephenson-eng.com
CORRIDOR AND SINGLE OWSJ 150x8x300 + 2-12 DIA.
WALL PLATE SCHEDULE)

2000 MAX.
OTHER CHANNEL BEAM x 320+50 HOOK ROOF / SKYLIGHT ROOF / SKYLIGHT
TOP COURSE FILLED OFES SI ON A L
SOLID, CUT TO SUIT INTERIOR WALLS OPENING 3 OPENING 4 B2 PR

ED

EN
18_08_10

2000 MAX.

NS
320 [12 - 1/2"]

COMBINED OWSJ/CHANNEL

GIN
320 (12-1/2")

150x10x460 + 2-20 DIA.

LI CE
B1

EER
OWSJ/OWSJ
WELDED ANCHORS - x 320+50 HOOK B2
CHANNEL OR BEAM
SEE SCHEDULE
OWSJ/BEAM H.A. McCALLUM
BEAM/CHANNEL B2

B1

O
PR
EXTERIOR WALL SINGLE OWSJ 150x8x300 + 2-12 DIA.

RI
VI TA

O
NC
CHANNEL BEAM x 320+50 HOOK E OF ON
3000 MAX. 3000 MAX.
BOTTOM CHORD
BRACE GP ROOM WALL SINGLE BEAM LSSJ 150x8x300 + 2-20 DIA. SEE TABLE SEE TABLE
x 320+50 HOOK OFES SI ON A L
PR

ED

EN
1-15M BAR CONT. 18_08_10

NS
TYPICAL ROOF OPENINGS IN DECK

GI N
COMBINED LSSJ/CHANNEL 150x10x460 + 2-20 DIA.

LI CE
GROUTED VERT. UPLIFT

EE R
BARS AS NOTED ON OR BEAM x 320+50 HOOK U/N ROOF OPENING J. C. GASDIA
CONTINUOUS CONCRETE FILLED BEAM 1 (B1) BEAM 2 (B2) 100169574
MASONRY LINTEL BLOCK BOND BEAM PLANS SPAN (mm)
ANGLED SINGLE OWSJ 150x8xVARIES SIZE CONNECTION SIZE CONNECTION

O
WALL

PR
(SEE PLAN FOR EXTENT) + 2-12 DIA. 0-1500 C100x8 5 kN C100x8 20 kN

RI
CHANNEL BEAM VI TA

O
1500-3000 C100x8 10 kN C150x12 25 kN NC
25 MPa CONCRETE E OF ON
THICKNESS (t) x 320+50 HOOK

WALL AND WALL PLATE Simcoe County


WALL THICKNESS (t) District School Board
CHANNEL OR BEAM
TYPICAL SKYLIGHT OPENINGS IN DECK
SKYLIGHT OPENING 2
BEAM 1 (B1) BEAM 2 (B2)
SPAN (mm)
SIZE CONNECTION SIZE CONNECTION
0-1500 C100x8 10 kN C150x12 25 kN
JOISTS/CHANNEL

1500-3000 C100x8 10 kN C200x17 30 kN


EQ
200(8")±

WALL PLATE
CLEARVIEW MEADOWS
EQ

NOTES:
1. TOP OF ALL TRIMMING STEEL AT UNDERSIDE OF STEEL DECK UNLESS OTHERWISE NOTED. ELEMENTARY SCHOOL
2. OPENINGS FRAMES ARE DESIGNED FOR THE FOLLOWING LOADS (MAX.) ADDITION
SDL=1.26kPa
JOIST OR BEAM SNOW=2.95kPa+ASL 12 Locke Avenue
3. LOCATION OF ALL MECHANICAL UNITS AND OPENINGS THROUGH ROOF IS BASED ON INFORMATION SHOWN Stayner, Ontario
COMBINED WALL PLATE ON MECHANICAL DRAWINGS. THE STRUCTURAL STEEL SUB-CONTRACTOR MUST CONFIRM ALL THESE L0M 1S0
(SEE WALL PLATE SCHEDULE) DIMENSIONS AND SIZES WITH THE MECHANICAL CONTRACTOR.
+ 2 WELDED ANCHORS PLAN VIEW OF WALL PLATE 4. O.W.S.J MUST BE DESIGNED FOR ADDITIONAL LOADS FROM MECHANICAL UNITS. DRAWING TITLE
5. IF ACTUAL LOCATIONS OR DETAILS VARY FROM THOSE SHOWN, THE STRUCTURAL CONSULTANT MUST
BE INFORMED AND INSTRUCTIONS RECEIVED BEFORE PROCEEDING WITH THE WORK. TYPICAL DETAILS
6. THE STRUCTURAL STEEL SUB-CONTRACTOR IS TO SUBMIT ERECTION DRAWINGS TO THE MECHANICAL
DR2 NTS
ENGINEER AND/ OR CONTRACTOR FOR APPROVAL OF SIZE AND LOCATION OF OPENINGS FOR MECHANICAL UNITS.
PROJECT NO: SCALE

DATE PLOTTED: 8/1/2018 8:39:39 AM


20171969 1:1
DRAWN BY: DRAWING NO:
Author

CHECKED BY:
Checker
S3-05 3
DATE:
April 30, 2018

You might also like