Professional Documents
Culture Documents
A6V10239125 en
A6V10239125 en
Model PSX-12
12 Amp Power Supply Extender
INTRODUCTION The Model PSX-12 from Siemens Industry, Inc., is a high current power supply
extender. The power supply extender works in conjunction with the PSC-12 power
supply to provide an additional 12A of regulated 24VDC for internal or external
system use.
The PSX-12 mounts at the back of the enclosure of the FireFinder-XLS/Desigo Fire
Safety Modular/Cerberus PRO Modular system and occupies one location on the
studs in the backbox or on the optional FireFinder-XLS/Desigo Fire Safety Modular/
Cerberus PRO Modular Mounting Plate, CAB-MP.
OPERATION The PSX-12 occupies one network address in the HNET network and has three func-
tional components: the Controller, the Power Supply Extender and the Interface Board.
The Controller monitors the status of the Power Supply Extender (loss of network
communication, 24VDC terminal overload and the status of the battery). This informa-
tion is relayed to the User Interface, where applicable, and is communicated to the
PMI/PMI-2/PMI-3 for system reporting. The Controller also allows the PMI/PMI-2/PMI-
3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO
Modular) to query the state of the power supply extender and its current load and
can send a diagnostics command to the PSX-12.
The Power Supply Extender has an Off-line switch mode power converter and power
factor correction circuit to improve conductive RF emission at low frequency. It is
designed to take voltage inputs of 120VAC-240VAC at 60Hz/50Hz and has one
resettable circuit breaker that can also be used as a battery power switch.
The Interface Board provides diagnostics LEDs, system connections and the terminal
connections on the PSX-12.
Terminal Blocks, The PSX-12 has one reset switch, six LEDs, three HNET/CAN address switches, one
circuit breaker, two terminal blocks, two terminal connections and two 60 pin flat
ribbon connections as shown in Figure 2.
Controls and Indicators
A reset switch is located on the top of the front panel. Pushing the reset switch re-
initializes the PSX-12 operation.
The LEDs located at the top left of the module and are defined as follows:
POWER
short circuit.
MODULE FAIL
CAN FAIL Three rotary dial switches located directly below the LEDs are used
HNET FAIL
to set the HNET/CAN network address of the PSX-12.
24V 12A FAIL
24V 4A FAIL
The terminal blocks of the PSX-12 are defined as follows (refer to
Figure 2):
ON
O —
CONNECTION
codes. (See Figure 2.)
_
P9 P12
+ GND Output Voltage: 24VDC +10%, -15%
1 2 N
H
Output Current: 4A max
+TB4 _
TB3-1: (+) terminal
REGULATED NON- POWER AC TB3-2: (-) terminal
LIMITED OUTPUT CONNECTION
(24VDC @ 12A Max.) (INPUT)
TB4 24VDC Non-Power Limited Output Terminal. This
NOTE: terminal is non-power limited and can supply up to
Positive and negative ground fault detected at:
<50K ohms for TB3 terminals 1,2 12A. When the current draw is exceeded, it shuts
<60K ohms for TB4 terminals 1,2 down, lights its associated LED and sends a fault
condition to the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2
Figure 2
Terminal Blocks, Controls and Indicators (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus
PRO Modular).
The total cumulative sum of the 24VDC output (power limited + non-power limited)
must not exceed 12A. Over current draw will initiate a PSX-12 shut down.
Four #10-32 ½" Phillips Screws Four #10-32 ½" Phillips Screws
(for PSC-12) (for PSX-12)
Four #10 Hex Nuts (for PTB) Four #10 Hex Nuts
• If the PSX-12 is not located in the same row in the backbox (or on the same
CAB-MP) as the CC-5, an extended 60 pin flat ribbon cable,Model BCL
(P/N 599-633997), is required.
The following components must be set prior installing the module in the enclosure:
Verify that the dedicated circuit breaker for the PSX-12 is turned OFF at the mains.
• Battery Circuit Breaker: Set this circuit breaker to the OFF position.
• Network Address Switch: Set the three-digit HNET/CAN network address
for the PSX-12 using the three rotary dial address switches located near the
bottom of the front panel. (Refer to Figure 2 for the location of the
switches.) The address for the PSX-12 must be the same as the address
selected for it in the Zeus Programming Tool. To set the address, turn the
pointers on each of the three dials to the numbers for the seleted address.
For example, if the address is 123, set the pointer for the HUNDREDS dial
to “1”, set the pointer for the TENS dial to “2”, and set the pointer for the
ONES dial to “3”. The range of allowable addresses is from 001 to 251
(leading zeros must be used).
the battery.)
Use a separate or dedicated circuit breaker and run the earth ground from a suitable
source to the PSX-12. Check local requirements.
Wire in accordance with local codes and Article 760 of the NEC, NFPA latest edition.
In compliance with NEC, all power limited fire protective signaling conductors must
be separated a minimum of a 1/4" from all of the following wiring located within a
control panel:
• Electric light
• Power
• Class 1 or non-power limited fire protective signaling conductor
Refer to the CAB2-BB Installation Instructions, P/N 315-033009, for wiring require-
ments to comply with NEC codes and Figure 6 for battery and AC power connections.
Figure 5
PSX-12 Wiring In The CAB Enclosures
PSX-12
RESET
PSC-12
RESET
PSX-12RESET
PSX-12 RESET
POWER POWER POWER POWER
MODULE FAIL MODULE FAIL MODULE FAIL MODULE FAIL
CAN FAIL CAN FAIL CAN FAIL CAN FAIL
H - NET FAIL H - NET FAIL H - NET FAIL H - NET FAIL
O — O — O —
ON
O —
ON
ON
ON
OFF
OFF
OFF
OFF
_ + P9 P12 _ + P9 TB2 P12 _ + P9 P12 P12
GND GND GND
_ + P9
GND
TB4 N
TB4 N
TB4 N
TB4
1 2 1 2 1 2 1 2 N
H H H H
_ _ _ _
+ + + +
- -
7
+ +
BATTERY BATTERY
TB3 TB4 P4 P5
PTB PTB
TB2 TB1 TB2 TB1
AC MAINS
Figure 6
Battery And AC Power Connection Diagram For PSC-12/PSX-12
(Maximum Configuration)
P/N 315-034120-20
Power Supply Load Calculations
The PSX-12 power supply load calculations are performed by the Zeus tool based on
the equipment in the physical view. Once all of the equipment is inserted into the
physical view of each enclosure and a successful compile is performed, the results
of the calculations are shown in the report view.
From the Tools menu, select Report Generation and then select System Power &
Battery Calculation Report. The report contains power supply loading results for each
PSX-12 in each enclosure. This report can be printed for a permanent record.
Battery Power Make sure that the battery circuit breaker is in the OFF position.
Battery backup is required for compliance to UL864. (15 amp hours is the minimum
size and 100 amp hours is the maximum size of the battery for the PSX-12.)
Battery Connections When BTX-1, BTX-2 or BTX-3 batteries are required, connect them to the system with
the two quick disconnects provided. Follow the steps listed below.
1. Attach one quick disconnect to the positive battery terminal and one quick
disconnect to the negative battery terminal with the 10-32 x 3/4” screws and
lock nuts supplied with the PSC-12.
2. Attach the red battery wire to the quick disconnect on the positive terminal
and the black battery wire to the quick disconnect on the negative terminal.
-
QUICK
DISCONNECT
(2 PLACES)
+
-
Figure 7
Wiring BTX-1/-2/-3 Batteries To The PSX-12
_
P5 TB1 +
1 6 1 2
1
P4 TB3
4 3
7 12
2 1
P10
PSC-12
PSX-12
Figure 8
Wiring the Anti-Interference Capacitor
ELECTRICAL RATINGS
120VAC @ 50/60Hz
Input Voltage 220VAC @ 50/60Hz
240VAC @ 50/60Hz
3.5A Max. @ 120VAC
Input Current 2.5A Max. @ 220VAC
2.0A Max. @ 240VAC
Output Power
Siemens products and solutions provide security functions to ensure the secure operation of
building comfort, fire safety, security management and physical security systems. The security
functions on these products and solutions are important components of a comprehensive security
concept.
For additional information on building technology security and our offerings, contact your Siemens
sales or project department. We strongly recommend customers to follow our security advisories,
which provide information on the latest security threats, patches and other mitigation measures.
http://www.siemens.com/cert/en/cert-security-advisories.htm
Siemens Industry, Inc. Siemens Canada, Ltd. Siemens Gebäudesicherheit P/N 315-034120-20
Building Technologies Division 1577 North Service Road East GmbH & Co. oHG
Document ID A6V10239125
Florham Park, NJ Oakville, Ontario D-80930 München
L6H 0H6 Canada