Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Installation Instructions

Model PSX-12
12 Amp Power Supply Extender

INTRODUCTION The Model PSX-12 from Siemens Industry, Inc., is a high current power supply
extender. The power supply extender works in conjunction with the PSC-12 power
supply to provide an additional 12A of regulated 24VDC for internal or external
system use.

Up to three PSX-12 modules


may be connected to one
PSC-12 power supply and
one set of batteries. The
PSX-12 has a microprocessor
controlled transfer circuit that
allows it to switch the
system power to stand-
by batteries during loss
or reduction of the AC
power.

The PSX-12 incorporates


a 18A circuit breaker on
the battery input.

The PSX-12 communi-


cates directly to the PMI/
PMI-2/PMI-3 (XLS),
FCM2041-U2 (Desigo Figure 1
Fire Safety Modular), PSX-12 12 Amp Power Supply Extender
FCM2041-U3 (Cerberus
PRO Modular) to report
fault conditions and allows the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire
Safety Modular), FCM2041-U3 (Cerberus PRO Modular) to query the status of the
power supply extender.

The PSX-12 mounts at the back of the enclosure of the FireFinder-XLS/Desigo Fire
Safety Modular/Cerberus PRO Modular system and occupies one location on the
studs in the backbox or on the optional FireFinder-XLS/Desigo Fire Safety Modular/
Cerberus PRO Modular Mounting Plate, CAB-MP.

Features The PSX-12 features are as follows:

• AC power input 120VAC - 240VAC +/- 10% @ 60Hz / 50Hz


• Off-line Switch Mode Power Converter
• Power Factor Correction
• Total Output power of 12A@24VDC
• Two separate power output terminals: one power limited terminal with 4A
max @ 24VDC capacity and one non-power limited terminal with 12A max
@ 24VDC capacity (total not to exceed 12A)
Siemens Industry
Industry,, Inc.
P/N 315-034120-20 Building Technologies Di
echnologies vision
Division
• Both output terminals have current measurement capability
• Auto resettable current protection circuits for overload and short circuit
• Access to CC-5/CC-2 System bus
• Communicates via HNET protocol

OPERATION The PSX-12 occupies one network address in the HNET network and has three func-
tional components: the Controller, the Power Supply Extender and the Interface Board.

The Controller monitors the status of the Power Supply Extender (loss of network
communication, 24VDC terminal overload and the status of the battery). This informa-
tion is relayed to the User Interface, where applicable, and is communicated to the
PMI/PMI-2/PMI-3 for system reporting. The Controller also allows the PMI/PMI-2/PMI-
3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO
Modular) to query the state of the power supply extender and its current load and
can send a diagnostics command to the PSX-12.

The Power Supply Extender has an Off-line switch mode power converter and power
factor correction circuit to improve conductive RF emission at low frequency. It is
designed to take voltage inputs of 120VAC-240VAC at 60Hz/50Hz and has one
resettable circuit breaker that can also be used as a battery power switch.

The Interface Board provides diagnostics LEDs, system connections and the terminal
connections on the PSX-12.

Terminal Blocks, The PSX-12 has one reset switch, six LEDs, three HNET/CAN address switches, one
circuit breaker, two terminal blocks, two terminal connections and two 60 pin flat
ribbon connections as shown in Figure 2.
Controls and Indicators
A reset switch is located on the top of the front panel. Pushing the reset switch re-
initializes the PSX-12 operation.

The LEDs located at the top left of the module and are defined as follows:

POWER - (Green) Normally ON. When illuminated, indicates


that the PSX-12 is powered from the AC
mains. When flashing, indicates that the
PSX-12 is powered from the battery.

MODULE FAIL - (Yellow) Normally OFF. When illuminated indicates


that the module microprocessor has failed.

CAN FAIL - (Yellow) Normally OFF. When illuminated, indi-


cates that CAN communication with the
PSX-12 has terminated (applicable only
when PSX-12 resides in a CAN network).

HNET FAIL - (Yellow) Normally OFF. When illuminated, indicates


that the HNET communication with the
PSX-12 has terminated and the card goes
to degrade mode (applicable only when
the PSX-12 resides in the HNET network).

24V 12A FAIL - (Yellow) Normally OFF. When illuminated, indicates


that the 24VDC non-power limited output
Siemens Industry, Inc. 2 P/N 315-034120-20
Building Technologies Division
REGULATED
POWER LIMITED OUTPUT has a trouble condition or the PSX-12 has
(24VDC @ 4A)
disconnected the 24VDC output due to
+
_
current overload or short circuit.
1 2

TB3 24V 4A FAIL - (Yellow) Normally OFF. When illuminated, indi-


cates that the 24VDC power limited
output has a trouble condition or the
PSX-12 has disconnected the 24VDC
PSX-12 power output due to current overload or
RESET

POWER
short circuit.
MODULE FAIL
CAN FAIL Three rotary dial switches located directly below the LEDs are used
HNET FAIL
to set the HNET/CAN network address of the PSX-12.
24V 12A FAIL

24V 4A FAIL
The terminal blocks of the PSX-12 are defined as follows (refer to
Figure 2):

TB3 24VDC Power Limited Output Terminal. This terminal


HNET/CAN
output is limited to 4A. When it is exceeded, it will shut
down, light its associated diagnostics LED and send a
fault condition to the PMI/PMI-2/PMI-3 (XLS),
FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-
U3 (Cerberus PRO Modular).
TO PSC-12, TO PSC-12,
PSX-12 PSX-12
OR CC-5/CC-2 OR CC-5/CC-2
This output is normally connected to the modules and
CIRCUIT cards located on the door of the enclosure or to the
BREAKER
remote CAN network modules. This output is power
BATTERY limited to NFPA 70 per 760. All wiring must be in
BATTERY
accordance with Article 760 of NEC or local building
OFF

ON

O —
CONNECTION
codes. (See Figure 2.)
_
P9 P12
+ GND Output Voltage: 24VDC +10%, -15%
1 2 N
H
Output Current: 4A max
+TB4 _
TB3-1: (+) terminal
REGULATED NON- POWER AC TB3-2: (-) terminal
LIMITED OUTPUT CONNECTION
(24VDC @ 12A Max.) (INPUT)
TB4 24VDC Non-Power Limited Output Terminal. This
NOTE: terminal is non-power limited and can supply up to
Positive and negative ground fault detected at:
<50K ohms for TB3 terminals 1,2 12A. When the current draw is exceeded, it shuts
<60K ohms for TB4 terminals 1,2 down, lights its associated LED and sends a fault
condition to the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2
Figure 2
Terminal Blocks, Controls and Indicators (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus
PRO Modular).

This output is normally connected to the input terminals


of the CC-5. All wiring must be in accordance with
Article 760 of NEC or local building codes. (See Figure 2.)

Output Voltage: 24VDC +10%, -15%


Output Current: 12A max
TB4-1: (+) terminal
TB4-2: (-) terminal

The total cumulative sum of the 24VDC output (power limited + non-power limited)
must not exceed 12A. Over current draw will initiate a PSX-12 shut down.

Siemens Industry, Inc. 3 P/N 315-034120-20


Building Technologies Division
The main AC power line must be turned OFF prior to installation.

P9 Connects the back-up battery to the PSX-12.

Always apply AC power first followed by the battery.

P12 AC input connector from the PTB, P4/P5.

60-pin Connects the PSX-12 to the system. It is a straight-through connection


between the two connectors. It contains the communication signals and
system signal bus that is necessary for the proper operation of the
system.
These connectors are power limited. If the PSX-12 is located in a
different row in the enclosure, an optional extended ribbon cable,
Model BCL (P/N 599-633997), must be used.

PRE-INSTALLATION The PSX-12 installation kit has the following components:


INSTALLAT ION KIT COMPONENT S

PSC-12 / PTB Kit PSX-12 PTB (Only)

Four #10-32 ½" Phillips Screws Four #10-32 ½" Phillips Screws
(for PSC-12) (for PSX-12)

Four #10 Hex Nuts (for PTB) Four #10 Hex Nuts

AC Wire Assembly, AC Wire Assembly,


P/N 600-134264 P/N 600-134264
Battery Wire Assembly, Battery Wire Assembly,
P/N 465-633943 P/N 465-633943
Battery Cable Conversion Kit 60-pin Flat Ribbon Cable,
P/N 545-634222 P/N 555-133036
Anti-Interference Capacitor Anti-Interference Capacitor
P/N A5Q00038368 P/N A5Q00038368

The following part is optional:

• If the PSX-12 is not located in the same row in the backbox (or on the same
CAB-MP) as the CC-5, an extended 60 pin flat ribbon cable,Model BCL
(P/N 599-633997), is required.

The following components must be set prior installing the module in the enclosure:

Verify that the dedicated circuit breaker for the PSX-12 is turned OFF at the mains.

• Battery Circuit Breaker: Set this circuit breaker to the OFF position.
• Network Address Switch: Set the three-digit HNET/CAN network address
for the PSX-12 using the three rotary dial address switches located near the
bottom of the front panel. (Refer to Figure 2 for the location of the
switches.) The address for the PSX-12 must be the same as the address
selected for it in the Zeus Programming Tool. To set the address, turn the
pointers on each of the three dials to the numbers for the seleted address.
For example, if the address is 123, set the pointer for the HUNDREDS dial
to “1”, set the pointer for the TENS dial to “2”, and set the pointer for the
ONES dial to “3”. The range of allowable addresses is from 001 to 251
(leading zeros must be used).

Siemens Industry, Inc. 4 P/N 315-034120-20


Building Technologies Division
INSTALLATION
POSITION 1 POSITION 2 POSITION 3 POSITION 4

Remove all system power


before installation, first
TOP THREADED POSTS
battery then AC. (To power
up, connect the AC first, then TOP

the battery.)

The PSX-12 mounts on studs


or on the optional Mounting
Plate (CAB-MP). The Mount-
ing Plate may be located CAB-MP
either inside or outside of the
enclosure to perform this
installation procedure. If the
Mounting Plate is located
inside the enclosure you will
BOTTOM THREADED POSTS
have to gain access to it by
opening the enclosure Inner
POSITION 1 POSITION 2 POSITION 3 POSITION 4
and Outer doors. If the
Mounting Plate is located
Figure 3
outside of the enclosure, Location Of The PSX-12 On The Optional CAB-MP
place it in front of you so that
the word “TOP” is at the top
and away from you.
SLIDE DOWN UNTIL
The PSX-12 can occupy any FLUSH ON TOP,
RIGHT, AND BOTTOM
position in the backbox or
on the mounting plate, but it
should be installed in the TOP

row and position that is


located directly above the
PTB to which it is con- PSX-12
CAB-MP
nected. (Refer to Figures 3
and 5). When the PSX-12 is
mounted correctly on the
optional Mounting Plate it
will be flush on the top,
bottom, and right with the
Mounting Plate and the
mounting screw holes of
the PSX-12 will align with Figure 4
the threaded posts. Mounting The PSX-12 On The Optional CAB-MP

1. Install four 10-32


screws in the threaded posts at the mounting position. Screw each of the 10-32
screws into the threaded posts 5-6 turns.
2. Place the PSX-12 over the four screws on the Mounting Plate and slide it down
or towards you to rest on the four screws. (Refer to Figure 4.) When the PSX-12
is in the correct position it will be flush with the top, bottom and right side of the
Mounting Plate.
3. Tighten the four screws.

Siemens Industry, Inc. 5 P/N 315-034120-20


Building Technologies Division
WIRING The PSX-12 has removable terminal blocks and connectors at the top and bottom of
the module. The terminal block at the top of the PSX-12 is power limited. The termi-
nals and connectors at the bottom of the PSX-12 are non-power limited. (Refer to
Figure 5.)

Use a separate or dedicated circuit breaker and run the earth ground from a suitable
source to the PSX-12. Check local requirements.

Conduit is not an acceptable Earth Ground Conductor.

Wire in accordance with local codes and Article 760 of the NEC, NFPA latest edition.
In compliance with NEC, all power limited fire protective signaling conductors must
be separated a minimum of a 1/4" from all of the following wiring located within a
control panel:

• Electric light
• Power
• Class 1 or non-power limited fire protective signaling conductor
Refer to the CAB2-BB Installation Instructions, P/N 315-033009, for wiring require-
ments to comply with NEC codes and Figure 6 for battery and AC power connections.

Figure 5
PSX-12 Wiring In The CAB Enclosures

Siemens Industry, Inc. 6 P/N 315-034120-20


Building Technologies Division
P5 TB1
CC-5 P4
TB3 TB3 TB3 TB3

PSX-12
RESET
PSC-12
RESET
PSX-12RESET
PSX-12 RESET
POWER POWER POWER POWER
MODULE FAIL MODULE FAIL MODULE FAIL MODULE FAIL
CAN FAIL CAN FAIL CAN FAIL CAN FAIL
H - NET FAIL H - NET FAIL H - NET FAIL H - NET FAIL

24V 12 FAIL 24V 12 FAIL 24V 12 FAIL 24V 12 FAIL


24V 4A FAIL 24V 4A FAIL 24V 4A FAIL 24V 4A FAIL

Siemens Industry, Inc.


HNET/CAN HNET/CAN HNET/CAN HNET/CAN

Building Technologies Division


BATTERY BATTERY BATTERY BATTERY

O — O — O —

ON
O —

ON
ON

ON
OFF

OFF
OFF

OFF
_ + P9 P12 _ + P9 TB2 P12 _ + P9 P12 P12
GND GND GND
_ + P9
GND
TB4 N
TB4 N
TB4 N
TB4
1 2 1 2 1 2 1 2 N
H H H H
_ _ _ _
+ + + +

- -

7
+ +

BATTERY BATTERY

TB3 TB4 P4 P5
PTB PTB
TB2 TB1 TB2 TB1

AC MAINS

Figure 6
Battery And AC Power Connection Diagram For PSC-12/PSX-12
(Maximum Configuration)

P/N 315-034120-20
Power Supply Load Calculations

The PSX-12 power supply load calculations are performed by the Zeus tool based on
the equipment in the physical view. Once all of the equipment is inserted into the
physical view of each enclosure and a successful compile is performed, the results
of the calculations are shown in the report view.

From the Tools menu, select Report Generation and then select System Power &
Battery Calculation Report. The report contains power supply loading results for each
PSX-12 in each enclosure. This report can be printed for a permanent record.

Battery Power Make sure that the battery circuit breaker is in the OFF position.

Use either 14 or 12 AWG for battery connection.

Battery backup is required for compliance to UL864. (15 amp hours is the minimum
size and 100 amp hours is the maximum size of the battery for the PSX-12.)

Battery Connections When BTX-1, BTX-2 or BTX-3 batteries are required, connect them to the system with
the two quick disconnects provided. Follow the steps listed below.

1. Attach one quick disconnect to the positive battery terminal and one quick
disconnect to the negative battery terminal with the 10-32 x 3/4” screws and
lock nuts supplied with the PSC-12.
2. Attach the red battery wire to the quick disconnect on the positive terminal
and the black battery wire to the quick disconnect on the negative terminal.

-
QUICK
DISCONNECT
(2 PLACES)
+
-

BTX-1, BTX-2 OR BTX-3


BATTERIES

Figure 7
Wiring BTX-1/-2/-3 Batteries To The PSX-12

Siemens Industry, Inc. 8 P/N 315-034120-20


Building Technologies Division
Anti-Interference Capacitor Install the 6.8uF, 100V bipolar Anti-Interference Capacitor as shown in Figure 8. It has
to be connected between System Ground and Earth Ground.

* *6.8uF, 100V BIPOLAR


CAPACITOR
P/N A5Q00038368

_
P5 TB1 +
1 6 1 2
1
P4 TB3
4 3
7 12
2 1

P10

PSC-12
PSX-12

Figure 8
Wiring the Anti-Interference Capacitor

ELECTRICAL RATINGS
120VAC @ 50/60Hz
Input Voltage 220VAC @ 50/60Hz
240VAC @ 50/60Hz
3.5A Max. @ 120VAC
Input Current 2.5A Max. @ 220VAC
2.0A Max. @ 240VAC

Power Limited: 4A Max.


Screw Terminal 24V Current
Non-Power Limited: 12A Max.

24V Standby Current 150mA

Output Power

8V peak to peak max.


Each HNET/XNET and CAN
Network Pair 75mA max.
(during msg transmission)

Siemens Industry, Inc. 9 P/N 315-034120-20


Building Technologies Division
Cyber security disclaimer

Siemens products and solutions provide security functions to ensure the secure operation of
building comfort, fire safety, security management and physical security systems. The security
functions on these products and solutions are important components of a comprehensive security
concept.

It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security


concept that is customized to individual security needs. Such a security concept may result in
additional site-specific preventive action to ensure that the building comfort, fire safety, security
management or physical security system for your site are operated in a secure manner. These
measures may include, but are not limited to, separating networks, physically protecting system
components, user awareness programs, defense in depth, etc.

For additional information on building technology security and our offerings, contact your Siemens
sales or project department. We strongly recommend customers to follow our security advisories,
which provide information on the latest security threats, patches and other mitigation measures.

http://www.siemens.com/cert/en/cert-security-advisories.htm

Siemens Industry, Inc. 10 P/N 315-034120-20


Building Technologies Division
This page is left intentionally blank.

Siemens Industry, Inc. 11 P/N 315-034120-20


Building Technologies Division
For CE applications in Cerberus E100 systems refer to
Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).

Siemens Industry, Inc. Siemens Canada, Ltd. Siemens Gebäudesicherheit P/N 315-034120-20
Building Technologies Division 1577 North Service Road East GmbH & Co. oHG
Document ID A6V10239125
Florham Park, NJ Oakville, Ontario D-80930 München
L6H 0H6 Canada

You might also like