Use the following steps to determine the interior lighting power allowance by the Space-by-Space Method:
a. For each space enclosed by partitions that are 80% of the ceiling height or taller, determine the appropriate space type and the
corresponding LPD allowance from Table 9.6.1. If a space has multiple functions, where more than one space type is
applicable, that space shall be broken up into smaller subspaces, each using its own space type from Table 9.6.1. Any of these
subspaces that are smaller in floor area than 20% of the original space and less than 1000 ft2 need not be broken out
separately. Include the floor area of balconies and other projections in this calculation.
b. In calculating the area of each space and subspace, the limits of the area are defined by the centerline of interior walls, the
dividing line between subspaces, and the outside surface of exterior walls or semiexterior walls. For the purposes of this
section, semiexterior walls that separate semiheated space from conditioned space shall be considered interior walls.
c. Based on the space type selected for each space or subspace, determine the lighting power allowance of each space or
subspace by multiplying the calculated area of the space or subspace by the appropriate LPD allowance determined in
Section 9.6.1(a). For space types not listed, selection of a reasonable equivalent category shall be permitted.
d. The interior lighting power allowance is the sum of lighting power allowances of all spaces and subspaces. Trade-offs among
spaces and subspaces are permitted, provided that the total installed interior lighting power does not exceed the interior
lighting power allowance.
Table 9.6.1 Lighting Power Density Allowances Using the Space-by-Space Method and Minimum Control Requirements Using Either
Method
https://up.codes/viewer_export/juris_key/austin/pub/ashrae_901_2019/ref/9.6 1/9
1/25/23, 10:33 AM 9.6 Alternative Compliance Path: Space-by-Space Method
The control functions below shall be implemented in accordance with the descriptions found in the referenced paragraphs within
Section 9.4.1.1 For each space type:
Automatic Automatic
Daylight Daylight Automatic
Responsive Responsive Partial
Informative Note: This table is divided
Restricted Restricted Automatic
into two sections; this first section Bilevel Controls Controls OFF
to to Partial for for Full
covers space types that can be Local Lighting (See Scheduled
Manual Automatic
commonly found in multiple building Control Control Sidelighting Toplighting Section OFF Shutoff
types. The second part of this table (See ON (See ON (See (See (See (See 9.4.1.1[g] (See (See
covers space types that are typically Section Section Section Section Section Section [Full Off Section Section
found in a single building type. 9.4.1.1[a]) 9.4.1.1[b]) 9.4.1.1[c]) 9.4.1.1[d]) 9.4.1.1[e]6) 9.4.1.1[f]6) complies]) 9.4.1.1[h]) 9.4.1.1[i])
Common LPD
Space Allowances, RCR
Types1 W/ft2 Threshold a b c d e f g h i
Atrium
≥20 ft and 0.48 NA REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
≤40 ft in
height
>40 ft in 0.60 11 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
height
Auditorium 0.61 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Gymnasium 0.23 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Motion 0.27 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
picture
theater
Performing 1.16 8 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
arts theater
Religious 0.72 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
facility
All other 0.23 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2
audience
seating
areas
Banking 0.61 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Activity
Area
All other 0.71 4 REQ ADD1 ADD1 REQ REQ REQ REQ
classrooms/lecture
halls/training
rooms
Conference/Meeting/Multipurpose
0.97 6 REQ ADD1 ADD1 REQ REQ REQ REQ
Room
https://up.codes/viewer_export/juris_key/austin/pub/ashrae_901_2019/ref/9.6 2/9
1/25/23, 10:33 AM 9.6 Alternative Compliance Path: Space-by-Space Method
Confinement 0.70 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Cells
Corridor2
Facility for 0.71 width <8 ft REQ REQ REQ REQ ADD2 ADD2
the visually
impaired
(and not
used
primarily by
the staff)3
Hospital 0.71 width <8 ft REQ REQ REQ ADD2 ADD2 ADD2
All other 0.41 width <8 ft REQ REQ REQ REQ ADD2 ADD2
corridors
Courtroom 1.20 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Computer 0.94 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Room
Dining Area
Penitentiary 0.42 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Facility for 1.27 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
the visually
impaired
(and not
used
primarily by
staff)3
Bar/lounge 0.86 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
or leisure
dining
Cafeteria 0.40 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
or fast food
dining
Family 0.60 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
dining
All other 0.43 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
dining
areas
Electrical/Mechanical
0.43 6 REQ REQ REQ
Room7
Food 1.09 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Preparation
Area
Laboratory
In or as a 1.11 6 REQ ADD1 ADD1 REQ REQ REQ REQ ADD2 ADD2
classroom
All other 1.33 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
laboratories
Laundry/Washing
0.53 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Area
https://up.codes/viewer_export/juris_key/austin/pub/ashrae_901_2019/ref/9.6 3/9
1/25/23, 10:33 AM 9.6 Alternative Compliance Path: Space-by-Space Method
Lobby
Lounge/Breakroom
All other 0.59 4 REQ ADD1 ADD1 REQ REQ REQ REQ
lounges/breakrooms
Office
Enclosed 0.66 8 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
and >250
ft2
Open plan 0.61 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Pharmacy 1.66 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Area
Restroom
Stairway The space containing the stairway shall determine the LPD and control requirements for the stairway.
Storage Room
https://up.codes/viewer_export/juris_key/austin/pub/ashrae_901_2019/ref/9.6 4/9
1/25/23, 10:33 AM 9.6 Alternative Compliance Path: Space-by-Space Method
Vehicular 0.60 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Maintenance
Area
Workshop 1.26 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Chapel 0.70 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
(used
primarily by
residents)
Recreation 1.77 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
room/common
living room
(and not
used
primarily by
staff)
Convention 0.61 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
Center—
Exhibit
Space
Gymnasium/Fitness Center
Exercise 0.90 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
area
Playing 0.85 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
area
Healthcare Facility
Medical 0.62 6 (See "Storage Room" under "Common Space Types" for control requirements.)
supply
room
Library
Reading 0.96 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
https://up.codes/viewer_export/juris_key/austin/pub/ashrae_901_2019/ref/9.6 5/9
1/25/23, 10:33 AM 9.6 Alternative Compliance Path: Space-by-Space Method
area
Stacks 1.18 4 REQ ADD1 ADD1 REQ REQ REQ REQ ADD2 ADD2
Manufacturing Facility
Detailed 0.80 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
manufacturing
area
Equipment 0.76 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
room
Extra high 1.42 8 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
bay area
(>50 ft
floor-to-
ceiling
height)
High bay 1.24 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
area
(25 to 50 ft
floor-to-
ceiling
height)
Low bay 0.86 3 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
area
(<25 ft
floor-to-
ceiling
height)
Museum
General 0.31 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
exhibition
area
Restoration 1.10 6 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
room
Post Office 0.76 4 REQ ADD1 ADD1 REQ REQ REQ REQ ADD2 ADD2
—Sorting
Area
Religious Facility
Fellowship 0.54 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
hall
Worship/pulpit/choir
0.85 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
area
Retail Facilities
Mall 0.82 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
concourse
Class I 2.94 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
facility
Class II 2.01 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
facility
Class III 1.30 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
facility
Class IV 0.86 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
facility
https://up.codes/viewer_export/juris_key/austin/pub/ashrae_901_2019/ref/9.6 6/9
1/25/23, 10:33 AM 9.6 Alternative Compliance Path: Space-by-Space Method
Transportation Facility
Baggage/carousel
0.39 4 REQ ADD1 ADD1 REQ REQ ADD2 ADD2
area
Ticket 0.51 4 REQ ADD1 ADD1 REQ REQ REQ ADD2 ADD2
counter
Warehouse—Storage Area
Medium to 0.33 4 REQ ADD1 ADD1 REQ REQ REQ REQ ADD2 ADD2
bulky,
palletized
items
Smaller, 0.69 6 REQ ADD1 ADD1 REQ REQ REQ REQ ADD2 ADD2
hand-
carried
items5
1. In cases where both a common space type and a building area specific space type are listed, the building area specific space type shall
apply
2. In corridors, the extra lighting power density allowance is permitted when the width of the corridor is less than 8 ft and is not based on the
RCR.
3. A "Facility for the Visually Impaired" is a facility that can be documented as being designed to comply with the light levels in ANSI/IES RP-
28 and is licensed or will be licensed by local/state authorities for either senior long-term care, adult daycare, senior support and/or people
with special visual needs.
6. Automatic daylight responsive controls are mandatory only if the requirements of the specified sections are present.
7. An additional 0.52 W/ft2 shall be allowed, provided that the additional lighting is controlled separately from the base allowance of 0.43 W/ft2.
The additional 0.52 W/ft2 allowance shall not be used for any other purpose.
When using the Space-by-Space Method, an increase in the interior lighting power allowance is allowed for specific lighting functions.
Additional power shall be allowed only if the specified lighting is installed and controlled independently of the general lighting in
accordance with Section 9.4.1.1(j). This additional power shall be used only for the specified luminaires and shall not be used for any
other purpose unless otherwise indicated. Lighting control requirements referenced in Section 9.6.2 are the only required controls for
these applications.
An increase in the interior lighting power allowance is permitted in the following cases:
a. For each space in which lighting is specified to be installed in addition to the general lighting for the purpose of decorative
appearance or for highlighting art or exhibits not exempted in Table 9.2.3.1, Item 11, provided that the additional lighting power
shall not exceed 0.75 W/ft2 of such spaces.
b. For lighting equipment installed in sales areas and specifically designed and directed to highlight merchandise, calculate the
additional lighting power as follows:
https://up.codes/viewer_export/juris_key/austin/pub/ashrae_901_2019/ref/9.6 7/9
1/25/23, 10:33 AM 9.6 Alternative Compliance Path: Space-by-Space Method
where
Retail Area 1 = the floor area for all products not listed in Retail Areas 2, 3, or 4
Retail Area 2 = the floor area used for the sale of vehicles, sporting goods, and small electronics
Retail Area 3 = the floor area used for the sale of furniture, clothing, cosmetics, and artwork
Retail Area 4 = the floor area used for the sale of jewelry, crystal, and china
Exception to 9.6.2
Other merchandise categories may be included in Retail Areas 2 through 4 above, provided that justification documenting the need for
additional lighting power based on visual inspection, contrast, or other critical display is approved by the authority having jurisdiction.
An additional lighting power allowance shall be permitted for space types with nonmandatory controls installed as identified in Table 9.6.3
when all mandatory controls are used according to Section 9.4. This allowance is added to the interior lighting power allowance and is
calculated as follows:
where
Lighting Power Under Control = the total input watts of all lamps being controlled using the control method indicated
Control Factor = the value given in Table 9.6.3 for the corresponding space type and control method
Table 9.6.3 Control Factors Used in Calculating Additional Interior Lighting Power Allowance
Space Type
a. Control factor is limited to workstation-specific luminaires in partitioned single occupant work spaces contained within an open
office environment (i.e. direct-indirect luminaires with separately controlled downlight and uplight components, with the downward
https://up.codes/viewer_export/juris_key/austin/pub/ashrae_901_2019/ref/9.6 8/9
1/25/23, 10:33 AM 9.6 Alternative Compliance Path: Space-by-Space Method
component providing illumination to a single occupant in an open plan workstation). Within 30 minutes of the occupant leaving the
space, the downward component shall continuously dim to off over a minimum of two minutes. Upon the occupant entering the
space, the downward component shall turn on at the minimum level and continuously raise the illumination to a preset level over
a minimum of 30 seconds. The uplight component of workstation specific luminaire shall comply with Section 9.4.1.1(h)
(automatic full off).
b. In addition to the requirements described in footnote (a), the control shall allow the occupant to select their preferred light level via
a personal computer, handheld device, or similarly accessible device located within the workstation.
When using the Space-by-Space Method, an adjustment of the space LPD allowance is permitted for individual spaces where room cavity
ratio (RCR) calculated for the empty room is documented to be greater than the RCR threshold for that space type shown in Table 9.6.1.
For corridor/transition spaces, this adjustment is allowed when the corridor is less than 8 ft wide, regardless of the RCR.
The LPD allowance for these spaces may be increased by the following amount:
where Base Space LPD = the applicable LPD allowance from Table 9.6.1.