USER MANUAL

AUTOMATIC POWER FACTOR RELAY ‘ATSO 12’

SPECIFICATIONS:
1. APFC unit (ATSO) should work on single phase, single CT

2. Working parameters:
a. Input voltage range: 140 VAC – 270 VAC
b. Input Current: Single CT sensing –Secondary/ 5 Amp
c. Frequency: 45 to 65 Hz
d. Power Factor Accuracy: +/ 1%

3. Display: Four, Single digit 7 – segment displays, red color, of size 0.56 inch

4. LEDs: 16 LEDs (one LED for each 12 relays, one for lead indication, one for lag indication, one for
Auto mode & one for Manual mode)

1|P a g e www.runcon.co.in
5. Switches: Four Big tact switches for programming & setting parameters
a. Mode Switch: Auto / Manual mode selection
b. Enter Switch: Save parameters
c. UP Switch: Increase parameters
d. Down Switch: Decrease parameters

6. Relays: In hardware, there should be provision of 12 relays (230VAC @ 7A), which can be
controlled by program for 06 relays max, 08 relays max or all 12 relays operable.

7. Fuse: Two fuse provisions (inside the controller)


a. COM signal of all relays should connect with COM pin of connector through PCB
mountable fuse (Fuse holder)
b. A fuse provision as above in between transformer output and rectifier.

8. Working Temperature: The working range of controller is 10°C to 70°C.

PROGRAMMING & PARAMETERS TO SET:


1. Mode: Auto Mode & manual mode
a. Default mode: Auto mode
b. Mode can be changed through ‘MODE’ switch
c. Press mode switch for 20 seconds to change mode
d. Auto mode / manual mode LED should ON as per mode selection

2. Programming (Auto mode): To set parameters for Auto mode


(Note: User can set these parameters in Auto mode only)
a. Programming unlock
I . Initially programming mode is Locked
ii. Press ‘ENTER’ switch for 15 seconds to unlock the programming
iii. ‘UnLC’ should display on FND when programming unlocked
iv. Now, again press ‘ENTER’ switch to set first parameter
b. CT ratio: Primary CT value setting
i. Press ‘ENTER’ switch after unlocking the programming , ‘Ct.P’ will display on FND
ii. Default value – 100
iii. Range – 01 to 5000
iv. Step size – 01
v. This value can be change through UP/Down switch
vi. Press ‘ENTER’ to save the set value & move on next parameter to set
c. Stages: There are three models – 6 relays, 8 relays and 12 relays.
i. ‘StG’ will display on FND
ii. Default Value – 6 for 6 relay, 8 for 8 relay and 12 for 12 relay model
iii. Range: 1 to 6 for 6 relay, 1 to 8 for 8 relay and 1 to 12 for 12 relay model
iv. Number of stages can be change by UP/down switch
v. Press ‘ENTER’ to save the set value & move on next parameter to set
d. Target Power Factor:
i. ‘t.PF’ will display on FND
ii. Default Value – 0.99 LEAD
iii. Range: 0.70 LAG to 0.7LEAD

2|P a g e www.runcon.co.in
iv. Step size – 0.01
v. This value can be change by UP/down switch
vi. LEAD & LAG LEDs should also ON as per target set
vii. Press ‘ENTER’ to save the set value & move on next parameter to set
e. Dead Band:
i. ‘DBnD’ will display on FND
ii. Default Value – 2
iii. Range: 1 to 10
iv. Step size – 0.01
v. This value can be change by UP/down switch
vi. Press ‘ENTER’ to save the set value & move on next parameter to set
LAG UNITY LEAD
.90.91.92.93.04.95.96.97 .98 .99 1 .99 .98 .97.96.95.94.93.92.91.9
DEAD BAND 002

f. ON time delay:
i. ‘DLOn’ will display on FND
ii. Default Value – 4
iii. Range: 5 to 60 (seconds)
iv. Step size – 1
v. This value can be change by UP/down switch
vi. Press ‘ENTER’ to save the set value & move on next parameter to set
g. OFF time delay:
i. ‘DLOF’ will display on FND
ii. Default Value – 4
iii. Range: 5 to 60 (seconds)
iv. Step size – 1
v. This value can be change by UP/down switch
vi. Press ‘ENTER’ to save the set value & move on again on first parameter to set
h. Programming Lock:
i. Press ‘ENTER’ switch for 15 seconds to Lock the programming
ii. ‘LC’ should display on FND when programming locked
i. Current Sensitivity:
i. ‘Curr’ Display on FND
ii. Default Value – 2
iii. Range – 1 to 9
iv.Current sensitivity parameter setting of controller will be as according to table below:

Set parameter 1 2 3 4 5 6 7 8 9
Current 0.2 % 0.6% 1% 1.5% 2% 2.5% 3% 3.5% 4%
sensitivity % of
C/T ratio

j. Power Factor Correction:


I. ‘PFCr’ Display on FND
ii. Default value 0
iii. Range – 0 to 5

3|P a g e www.runcon.co.in
3. Programming (Manual mode): To set relays ON/OFF manually
(Note: These settings can be done in Manual mode only)
a. REL1: Relay 1 ON/OFF setting in manual mode
i. Press ‘ENTER’ switch once, only REL1 LED will start flashing, not relay
ii. If ‘UP’ switch pressed, REL and its LED will ON
iii. If ‘Down’ switch pressed, REL and its LED will OFF
iv. Now, press ‘ENTER’ to save the set value & move on next relay to set
v. Similarly all relays as per stages can be set

FUNCTIONS:
1. Power ON:
a. Unit should start switching relays after 15 20 seconds of power ON.
b. Current PF will display on FND in normal condition.
c. No load fault or CT reverse fault will display on FND
d. Lead / Lag LEDS should be ON as per conditions.
e. Last settings should remain save in unit, not status.
2. Auto mode:
a. In this mode, automatic switching of relays should be done as per rotational FIFO Method
to achieve the target PF as close as possible. One individual LED is associated with each
relay that should be ON with respective relays. Relays should ON or OFF one by one with
their saved delay times.
b. No load condition: When load is less than 2% of CT ratio, this condition will considered as
‘NO LOAD CONDITION’
i. At power ON: FND should display ‘LOC’ and the unit will not start switching any relay
automatically.
ii. At working condition: FND should display ‘LOC’ and the unit will switch OFF all relays one
by one.
c. CT reversal condition: If CT connections are reversed; display will show ‘Ct.r’.
3. Manual Mode:
a. In this mode, the relay on/off done by manually.

IMPORTANT INSTRUCTIONS:
1. Always install C/T on Maximum Load Current & connect on same phase
2. Set current sensitivity to avoid hunting at Load Current
3. Always install capacitor in increasing order as given in table:
Stage 1 2 3 4 5
KVAR 1 2 4 8 15
4. Install C/T before APFC panel & factory load
5. Always Set ampere sensitivity to avoid hunting at low current
6. Fix capacitors on LT Side of Transformer for Transformer PF Compensation (If Energy Meter is
installed on HT Line)

4|P a g e www.runcon.co.in
CONNECTION DIAGRAM:

Thanks for using our APFC Relay ATSO 12

M AU RY A EN T ERPRI SES
ADD: 7 5 A M AI N 6 0 FEET ROAD V I SH WASH N AGAR SH AH DARA DELH I -1 1 0 0 3 2
Mfg APFC RELAY MDI CONTROL RELAY PHASE SEQUENCE REALY ENGINE RELAY
CAPACITORS APFC PANELS ELECTRICAL PANELS Etc

Mob +91 9717152559, 9310821045


Email runconcapacitor011@gmail.com , sunil.morrya@gmail.com
Web: www.runcon.co.in , www.runcon.in

5|P a g e www.runcon.co.in

You might also like