Project TOWER-W2

Client SUPERTECH

Part of Structure SHEAR LOOP CONNECTION Date: 12/2/2015

Calculated By MI Checked By: SKS


Ref. DESIGN OF SHEAR LOOP CONNECTION
Shear loop connection is designed by taking the maximum shear force from the links modelled in ETABS

For Joint-J:-

SHEAR FROM LINK:-

The maxiumum shear force in the link for envelope case,Vu = 355 kN

Addtional Bars = 2-T16

Shear Capacity of 2-T16 = 99.6 kN

Refer Section 4-4 for Details

From Brochure

For C40/50 = 4-PVL 80

Therefore 4-PVL 80 loops & 2-T16

Loops Brochure specifies the joint capacity


Project TOWER-W2

Client SUPERTECH

Part of Structure SHEAR LOOP CONNECTION Date: 12/2/2015

Calculated By MI Checked By: SKS


Project TOWER-W2

Client SUPERTECH

Part of Structure SHEAR LOOP CONNECTION Date: 12/2/2015

Calculated By MI Checked By: SKS


Ref. DESIGN OF SHEAR LOOP CONNECTION
Shear loop connection is designed by taking the maximum shear force from the links modelled in ETABS

Calculation for Typical Storey is added below

ADDITIONAL
JOINT ID SHEAR FORCE LOOPS
BARS
Joint B 328 2-T10 4-PVL 80

Joint H' 160 - 4-PVL 80

Joint G & E 172 - 4-PVL 80

Joint K & M 291 - 4-PVL 80

Joint D 270 - 4-PVL 80

Joint A 430 - 6-PVL 80

Joint H,J,F 355 2-T16 4-PVL 80

Joint C 140 - 4-PVL 80

Loops Brochure specifies the joint capacity