>> Voltage Drop (VD) = 200% x L x Rw x Itotal Where: L = Length of the Service Drop Aneco Feeder=30mtrs Rw =Resistance of the Conductor wire (from PEC-1 , 2017, Table 10.1.1.8 page941) Rw#14.00mm2 Copper= 0.51Ώ/305m Rw#14.00mm2 Aluminum= 0.808Ώ/305m I-total = Total Load Amps of the System From Schedule of Loads section#4 Thus Itotal= 40.5 Amps To solve the VD of the Main Feeder Service Drop VD(copper)= 200% x (30m) x (0.51Ώ/305m) x 40.50 4.1 volts VOLTAGE REGULATION %= 1.00/230Volts x 100% = 1.77 % VD(Aluminum)= 200% x (30m) x (0.808Ώ/305m) x40.50 4.3 volts VOLTAGE REGULATION %= 3.4/230Volts x 100% = 1.9 %