TECHNICAL SPECIFICATION

2.01 SCOPE:
This specification covers the Design, manufacture, testing, supply and delivery
F.O.R. Destination Railway Stations in Punjab of 11KV,475 MVA 1250 A Incomers, 630A
Station Transformer, ,1250 A Bus Coupler, 630 A Capacitor control and 630 A Outgoing
VCB panels provided these Breakers are type tested as per relevant Indian standards/ IEC
to meet all technical requirements e.g. subject to withstand minimum 100 no. full short
circuit operations etc. These breaker panels should be provided with PTs/CTs, Metering
instruments, relays, supporting structures, Foundation bolts, Alarms, VCB transport trolley
(if required as per firm design) and all accessories/sundries etc. A brief description of these
is given in `Schedule of Requirements‟ in Section III. Any other parts & accessories which
may be required for proper functioning of the equipment would be deemed to have been
included by the supplier, even though the same may not have specifically been mentioned
in the schedule of requirements. The above extensible Incoming, station transformer, bus
coupler, Capacitor control VCB and Outgoing VCB panels should be suitable for lining up
in the form of panel boards/ switch boards.

The 11KV VCB panels must have front door. It shall not be possible to open the
front door while circuit breaker is on and in service position. It shall not be possible to
close the circuit breaker in service position with the front door open. The breaker can be
inserted from test position to service position only with the front door closed. The breaker
cannot be pushed in the panel beyond the test position if the front door is open.

The circuit breaker can operate only in one of the three defined positions i.e.
service, test & isolated. The breaker should not close in any of the intermediate positions.
The circuit breaker can be inserted only in the open position. Likewise CB in closed
position cannot be withdrawn. The CB cannot be inserted in service position till auxiliary
contacts are made. Similarly interlock should prevent auxiliary contacts from being
disconnected, if CB is in service position.
The power and control cables from and to the 11KV switch Boards are not
included in the scope of supply of the supplier.
Each pole of the circuit breaker shall be individually enclosed
/encapsulated.

2.02 CLIMATIC CONDITIONS:


All the Sub-Stations where these VCB panels are to be installed are located in the level
alluvial plains of the Punjab (Altitude not exceeding 1000 Metres) where climatic
conditions are as under:-

a) Shade temperature varying from 0 Deg. C to 45 Deg. C


b) Maximum outside temp. in the Sun 50 Deg.C
c) Tropical monsoon rain conditions exist for about 3 months in a year & maximum
relative humidity may be of the order of 90 to 100%
d) Heavy dust storms accompanied by lightning occur at frequent intervals. The sites
are vermin infested.
e) Heavily polluted atmosphere having acidic contents in the air causing normal
sulphonation.

1
2.03 PARTICULARS OF THE SYSTEM:
The 11 KV VCB Panels are required for use on 11KV, 3 phase 4 wire, A.C. 50 Cycles
solidly earthed system. Normally where the 11KV windings of the power transformers are
star connected, the neutral shall be solidly grounded. The highest system voltage may be
taken as 12 KV.

2.04 INSULATION LEVEL AND RATINGS:


The 11 kV VCB panels covered by this spec. are required to be used on installation in
which the apparatus is subjected to over voltages of atmospheric origin. The equipment
offered should therefore be suitable for electrically exposed installation and should have
following ratings for site conditions given in Clause-2.02:-

a) Standard Impulse withstand Voltage = 75KV (Peak)


b) One Min. Power Frequency withstand voltage = 28KV (rms)
c) Short time current ratings = Not less than 25KA for
3 sec.(the CTs
should have short time
current ratings of 25KA
for 3 sec.)

2.05 STANDARDS:
The metal enclosed 11 kV VCB panels shall comply with the requirements laid
down in ISS:3427, IEC-62271-100/IEC-62271-200/ISS:13118, IEC:298 with latest
amendments etc. All other equipments/devices shall also comply generally with the
requirements of the latest editions of relevant Indian Standards. Deviations from these
standard specifications, if any, shall be clearly brought out in the tender duly justified,
specially in “Schedule of Deviations” enclosed as Annexure-E.

2.06 TYPE AND RATING OF EQUIPMENT:


The 11 KV VCB panels shall be totally enclosed, metal clad, dust and vermin proof
suitable for floor mounting, provided with ONE SET OF 3 PHASE,1250 A, MAIN
ELECTROLYTIC COPPER BUS BARS OF MINIMUM CROSS SECTIONAL AREA
AS 1250 MM SQ. LAID IN HORIZONTAL FORMATION HAVING MAXIMUM
CURRENT DENSITY OF 1Amp. PER MM SQ. for the Incomer breaker panels, Station
Transformer Control Panels, Capacitor Control Panels, Outgoing VCB panels and bus
coupler panels. Two lengths of total 1250mm sq. of cross section bus with air gap will also
be acceptable. Panels shall be complete with all necessary frame work for securing the
panels to the floor and shall be designed as to be readily extensible to all switchgears and is
required for indoor use. Similarly the dropouts for incomer and bus coupler VCB panels
shall be of 1250Amp. Current rating with min. size as 1250mm sq. of electrolytic copper
bus bars. For Station Transformer panels, outgoing VCB panels and capacitor control VCB
panels, the drop outs shall be of 630 Amps. Current rating with min. size as 630 mm sq.
electrolytic copper bus bars. The current rating of isolating male/female contacts for
incomer and bus coupler panels shall be 2000A whereas current rating of isolating
male/female contact for Station T/F, Outgoing VCB panels & capacitor control panels shall
be 800A. Loose bus bar(s) to connect 11 KV VCB panels with bus bar shall be in Bidders
scope.

Furthermore, the 11 KV VCB bus coupler shall consist of a Bus Bar Chamber and a
Trunking Chamber , arranged in such a way that bus bar arrangement from the bottom of
bus coupler chamber to top of trunking chamber is complete in all respects. Both chambers

2
shall have similar height. Loose bus bar(s) to couple similar bus bar configuration/height
11 KV VCB panels on both sides of the bus coupler panel shall also be in Bidders scope.

The bus bar shall be of the AIR INSULATED type with adequate clearance as per
IE rules and shall be mounted in the chambers in an approved manner. Openings in the
enclosure of metal enclosed switchgear and control gear and in the partitions of
compartments through which contacts of removable or withdrawable parts engage fixed
contacts shall be provided with automatic shutters operated in normal service operations to
assure the protection of the persons as per provisions of IEC 62271-200. Shutters will
definitely operate with the movement of VCB and there shall be no chance of partially
closed shutter when VCB is moved in test/service position.

The bus bar shall be additionally covered with sleeves suitable for full system voltage.
Unsleeved portion of the bus bars viz-jointing ends of the bus bars are to be silver plated of
adequate thickness invariably to avoid oxidation and to be shrouded properly. All the Nuts
and Bolts used for bus bar connections /interconnections and for other current carrying
parts shall be of Stainless Steel.
All the three poles of circuit breakers and their associated main connections shall be of
1250A for all incoming T/F panels and bus coupler panels & of 630A for station T/f,
Outgoing VCB panels and capacitor control panels.
The operating mechanism shall be motor operated spring charged type. There shall be
provision (s) for manual charging of closing spring and emergency hand trip. The motor
used for the purpose will be suitable for 240 V AC. The operating mechanism shall work
satisfactorily between 85-110% of rated supply voltage.
Emergency hand trip device (Shaft & Bell crank type) should be at the operatable height
(80 cm. minimum) and not at the bottom. Emergency hand trip device should be provided
so that the opening of circuit breakers is manual as well as electrical through the relevant
protective relays.

2.07 TEMPERATURE RISE:


The reference maximum ambient air temperature may be taken as 45 Deg.C as against
40 Deg.C assumed in IEC-62271-100/ IEC-62271-200/ISS-13118. The permissible
temperature rise for various equipment offered should therefore be reduced accordingly.

2.08 MAKING CAPACITY AND SHORT TIME RATING


The manufacturer may offer circuit breakers having making capacities & short time
ratings as per his standard design, however, conforming to IS. The necessary data shall,
however, be indicated in the „Schedule of Guaranteed Technical Particulars‟ to be supplied
with tender.

2.09 PROTECTION
It is intended to automate the switchgears and use communicable, 61850 compliant
numerical over current relays for protection, control, metering and status monitoring along
with reporting system, disturbance recording for fault analysis . This spec is based on the
understanding that an integrated automation system along with protection shall be provided
and same shall have provisions for integration with SCADA system. All the status signals
are to be wired to the main numeric relay.

3
A) RELAY PARTICULARS :

• Numeric, Non-directional, IEC 61850 compliant, O/C relay with control functions
and having following features:-
• Minimum 12 no. of self configurable input relays.
• Minimum 08 no. of self configurable output relays.
• In addition to above, there should be 2 no. of I/P and O/P spare self configurable
potential free contacts each for future use.
• Heavy duty internal/ external contacts suitable to handle tripping of 11 kV VCB‟s
should be provided.
• Trip circuit supervision feature.
• Comprehensive self diagnostic feature with remote indication of relay failure and
alarm.
• Atleast 4 no. programmable LEDs with latching option.
• Time synchronization by IRIG-B or SNTP.
• The Relay should have proper indication for phases, type of fault etc. It should be
configured with following status inputs:
i) Closing Spring charged.
ii) Master Trip relay operated.
iii) CB ON
iv) CB OFF .
v) Ckt breaker in test position.
vi) Ckt breaker in service position
vii) Trip ckt healthy status
viii) Local/ Remote switch status
ix) Ckt breaker is not anti pumping status.
x) Auxiliary relay operated( where provided).
• Rated CT secondary : 5/1 Amp.( User Selectable ) CTs used to be protection class.
• The auxiliary supply for control and protective relay circuits, DC alarm and for
indication etc. shall be made available at 220 V DC (normal operating range : 160
to 250 V) through a two wire system from station storage battery.
• Communication Port-
1. The numeric relay should have RS-232 / RJ-45 port at the front for local
parameter settings and data download etc. and two optical ports at the rear for
parallel redundancy ( in compliance to IEC 62439-3) in the networking on IEC
61850 protocols.
• The relay should be able to communicate with all type of IEC 61850 compliant
other and similar make relays and the local and remote workstations via optical
fibre communication.

• The relay should conform to the IEC 255-5 or equivalent BS / ANSI for following:
i) Overload withstand test
ii) Dielectric withstand: 2 kV in common, 1 kV in differential mode
iii) Impulse voltage :5 kV in common, 1 kV in differential mode.
iv) Insulation resistance > 100 MΩ
v) Vibration : Shock and bump and seismic.
vi) Storing and transportation

4
vii) Radio interference : IEC 61000 for high frequency disturbance, Transient
disturbance, Electrostatic discharge. KEMI/CPRI certification for the
particular model offered with respect to IEC 61850 protocol.

• Type Tests : The Numeric Over current relay shall comply with the requirements
of following type tests as per latest edition of ISS/IEC:

i) Dielectric withstand test-IEC 60255-5


ii) High voltage impulse test class III---IEC 60255-5(5 KV peak, 1.2/50 micro sec: 3
positive and 3 negative shots at interval of 5 Sec.)
iii) DC Supply interruption---IEC 60255-11
iv) AC ripple on DC supply --- IEC 60255-11
v) Voltage dips and fault interruptions---IEC 61000-4-11
vi) High frequency disturbance---IEC 60255-22-1,class III or upgraded relevant IEC
vii) Fast transient disturbance---IEC 60255-22-4,CLASS IV
viii) Surge withstand capability---IEEE/ANSI C 37.90.1(1989) or equivalent IEC
ix) Degree of protection
x) Electromagnetic compatibility
xi) Mechanical stress/vibration test
xii) Temperature withstand
Where ever the above mentioned standards and IEC 61850 overlap the latter will
prevail.

In addition to above, the specific relay requirements for various VCB


panels are as under:-
B) INCOMING VCB PANELS

i) Protection features required in the numerical O/C relay :

In addition to the features detailed at 2.09(A), the Numeric, IEC 61850 compliant
O/C relay should have following protection elements :
Non directional, IDMT, three O/C, one E/F (both measured and derived E/F
functions) with high-set element for phase and Earth Fault of rated current 5A,TMS
range of 0.01 to 1 sec. (in steps of 0.01) with current range of 20% to 200% in steps
of 1% ( or better setting) for O/C and 5% to 40% in steps of 1% for E/F, HSU range
of 50% -1200% of rated current with instantaneous tripping for O/C and 50% to
400% for E/F in steps of 5%. The relay should have in built REF function of CT
secondary rated current 1 Amp on LT side of Power Transformer with minimum
setting range of 10 to 40% (i.e. 100mA to 400 mA). External series resistance of
suitable rating shall be provided in the VCB panel for high impedance REF
function. The relay should have CB Fail protection and time settable as per user.
The Relay should have all the standard IDMTL characteristics/IEC curves (simple
inverse, very inverse, very very inverse, LT Inverse).

ii) MASTER TRIPPING RELAY :


Master Trip Relay shall be High speed, high burden, electrical reset, suitable
for 220 V DC supply, having at least 06 NO and 4 NC contacts with supply
to the coils through NC contacts (Electromagnetic Type).

iii) AUXILIARY RELAY :


Auxiliary Relay suitable for 220 V DC supply shall have three elements, each
element of auxiliary relay having 4NO+2NC change over contacts with supply to the coils
through NC contacts. The relay shall be self reset.

5
C) OUTGOING VCB PANELS

i) Protection features required in the numerical O/C relay

In addition to the features detailed at 2.09(A), the Numeric, IEC 61850 compliant
O/C relay should have following protection elements :
Non-directional, IDMT three O/C , one E/F(both measured and derived E/F functions) &
one SEF with high-set element for phase and Earth Fault of rated current 5A,TMS range of
0.01 to 1 sec. (in steps of 0.01) with current range of 20% to 200% in steps of 1% ( or
better setting) for O/C and 5% to 40% in steps of 1% for E/F, HSU range of 50% -1200%
of rated current with instantaneous tripping for O/C and 50% to 400% for E/F in steps of
5%. The relay should have in built SEF function, of rated current 5A with minimum setting
range of 2-16% in steps of 1% with Time setting range of 0-25 Sec. in steps of 0.1 Sec. The
relay should have CB Fail protection and time settable as per user. The relay should have
features to monitor broken conductor. The Relay should have all the standard IDMTL
characteristics/IEC curves (simple inverse, very inverse, very very inverse, LT Inverse).

ii) MASTER TRIPPING RELAY :


Master Trip Relay shall be High speed, high burden, electrical reset, suitable
for 220 V DC supply, having at least 06 NO and 4 NC contacts with supply to the coils
through NC contacts (Electromagnetic Type).

D) STATION T/F VCB PANEL

(i) Protection features required in the numerical O/C relay:-


In addition to the features detailed at 2.09(A), the Numeric, IEC 61850 compliant O/C
relay should have following protection elements :
Non-directional, IDMT three O/C & one E/F(both measured and derived E/F functions)
with high-set elements for phase and Earth Fault of rated current 5A,TMS range of 0.01 to
1 sec. (in steps of 0.01) with current range of 20% to 200% in steps of 1% ( or better
setting) for O/C and 5% to 40% in steps of 1% for E/F, HSU range of 50% -1200% of rated
current with instantaneous tripping for O/C and 50% to 400% for E/F in steps of 5%. The
relay should have CB Fail protection and time settable as per user The Relay should have
all the standard IDMTL characteristics/IEC curves (simple inverse, very inverse, very very
inverse, LT Inverse).
ii) MASTER TRIPPING RELAY :
Master Trip Relay shall be High speed, high burden, electrical reset, suitable for
220 V DC supply, having at least 06 NO and 4 NC contacts with supply to the
coils through NC contacts (Electromagnetic Type).

E) BUS COUPLER PANELS:

i) Numeric Over Current Relay :-

In addition to the features detailed at 2.09(A), the Numeric, IEC 61850 compliant
O/C relay should have following protection elements:

6
Non-directional, Inverse Time, three O/C & one E/F with high-set element for phase and
Earth Fault of rated current 5A,TMS range of 0.01 to 1sec. (in steps of 0.01) with current
range of 20% to 200% in steps of 1% ( or better setting) for O/C and 5% to 40% in steps of
1% for E/F, HSU range of 50% -1200% of rated current with instantaneous tripping for
O/C and 50% to 400% for E/F in steps of 5%. The relay should have CB Fail protection
and time settable as per user. The Relay should have all the standard IDMTL
characteristics/IEC curves (simple inverse, very inverse, very inverse, LT Inverse).

ii) MASTER TRIPPING RELAY :


Master Trip Relay shall be High speed, high burden, electrical reset,
suitable for 220 V DC supply, having at least 06 NO and 4 NC contacts with supply to the
coils through NC contacts (Electromagnetic Type).

iii) Auxiliary Relay:-


Auxiliary Relay suitable for 220 V DC supply shall have three elements, each
element of auxiliary relay having 4NO+2NC change over contacts with supply to the coils
through NC contacts. The relay shall be self reset.

F) Capacitor Control VCB Panels

j) Protection features required in the numerical O/C relay

In addition to the features detailed at 2.09(A), the Numeric, IEC 61850 compliant
O/C relay should have following protection elements :
Non-directional, IDMT three O/C , one E/F (both measured and derived E/F functions)
with high-set element for phase and Earth Fault of rated current 5A,TMS range of 0.01 to 1
sec. (in steps of 0.01) with current range of 20% to 200% in steps of 1% ( or better setting)
for O/C and 5% to 40% in steps of 1% for E/F, HSU range of 50% -1200% of rated current
with instantaneous tripping for O/C and 50% to 400% for E/F in steps of 5%. The relay
should have in built NDR, Under voltage and Over voltage features. NDR having voltage
setting range of 2.5 V to 20 V in suitable steps and time range of 0.5 sec to 20 sec in steps
of 1 sec. TMS range of 0.01 to 1 in step of 0.01. Under voltage relay rating 110 V, 50 Hz,
A.C. having setting range of 30-95% in steps of 5% of rated voltage, Time delay range of 0
sec to 25.0 sec in steps of 1 sec. TMS range of 0.01 to 1 in step size of 0.01. Over voltage
relay rating 110 V, 50 Hz, A.C. having voltage setting range of 105-170% in steps of 5% of
rated voltage, time delay range of 0 to 25.0 sec in steps of 1 sec. TMS range 0.01 to 1 in
step size 0.01. The relay should have CB Fail protection and time settable as per user. The
Relay should have all the standard IDMTL characteristics/IEC curves (simple inverse, very
inverse, very very inverse, LT Inverse).

xix) MASTER TRIPPING RELAY :


Master Trip Relay shall be High speed, high burden, electrical reset, suitable
for 220 V DC supply, having at least 06 NO and 4 NC contacts with supply to the coils
through NC contacts (Electromagnetic Type).

M/s Areva/ABB/Siemens/Ashida/Easun Reyrolle/Crompton Greaves /Schneider make


relays shall be provided.
2.10 FREQUENCY OF OPERATION
The panels are mostly to be used for feeding heavily concentrated loads. As such
they may be subjected to frequent trippings on overload and earth faults. Any specific

7
design features adopted or proposed to be provided by the tenderer in the switchgear on
this account should be specifically indicated in his tender with justification.

2.11 INSTRUMENTATION
Each of 11KV VCB panels shall be provided MULTI FUNCTION METER, which
should be on MODBUS Protocol with RS 485 port for SCADA and 3 phase 4 wire HT
solid state trivector meter of approved make by PSPCL and test terminal block.
Multifunction meter is to be installed in Relay and control chamber. All instruments should
be calibrated type except HT solid state meters which may have multiplying factors.

3 phase 4 wire HT solid state trivector meter should have TTB.


HT solid state trivector meter which will be Base Mounted wherever required.
All Instruments shall be of directly calibrated type except solid state instruments.
TVM shall have provision of RS-485 Port & DLMS port to enable remote metering
and computation of data in the computer. Energy meter should be mounted at a convenient
height so that same can be read by a normal height person.
Fuses, terminal blocks & test terminal blocks for Metering purposes should also be
located in the TVM chamber. Provision for sealable PT chamber in case of incomer
breaker panels should be made. Besides this normal inter panel wiring for PT supply to
adjoining panels from incomer is also to be provided.

2.12 INSTRUMENT TRANSFORMERS


i) CURRENT TRANSFORMERS
Each of the panel shall be provided with CTs having output, accuracy and
saturation factor for the purpose for which these are required. Where REF protection is to
be provided on the 11KV incoming panel, requisite CTs having suitable ratio, output &
accuracy class should be provided. The accuracy class should be as per Sr.no.iii Current
Transformer for item no. I, II, III,IV & V of Annexure-A.
All CTs shall be 5 Amp. Secondiares & have ratio as indicated in the schedule of
requirement except those for differential and REF for which secondary current rating shall
be 0.577 A-1A respectively. The CTs for the various above protections and metering
should be capable of withstanding overload to the extent of 25%. The characteristics and
magnetizing curves of the CTs should be positively submitted along with the tender.
NOTE:
11KV ring type CTs with bushing design will not be acceptable and only integral CTs
having primary and secondary winding together in one epoxy resin cast moulding are to be
provided.

ii) POTENTIAL TRANSFORMERS


A three phase drawout type of epoxy resin cast, voltage T/F of ratio 11000/√3/110/√3 volts
having output of 30VA per phase and accuracy class 0.2 should be provided on the bus bars
of the incoming T/F panels for giving supply to the voltmeter,3 phase 4 wire HT solid state
tri-vector meter and power factor meter on the switch board.

8
2.13 AUXILIARY SUPPLY
For indication during normal operation, heaters etc. single phase 230 V 50 cycles
AC supply shall be made available through the station T/F. Supply for tripping, alarm
indication during emergency shall be available at 220V DC on 2 wire system from the
station DC battery. The DC failure indication and alarm equipment should operate on 230V
single phase AC supply.

2.14 INDICATION AND ALARMS:


Besides the mechanical ``ON‟‟ and ``OFF‟‟ indicators (Embossed),2 nos. indicating
lamp `Red‟ for `ON‟ and `Green‟ for `OFF‟ position shall be provided for circuit breaker
position indication for each breaker. In addition to the above ``ON‟‟ and ``OFF‟‟
indication, `Healthy supply‟ indicating lamp coloured `White‟ along with test push button
to test the condition of DC supply to trip coil of the breaker in both ``ON‟‟ and ``OFF‟‟
position shall be provided on every panel. An `Amber‟ coloured lamp shall also be
provided on each panel for `Auto trip‟ indication. A `Blue‟ coloured lamp may also be
provided on each panel for spring charge indication. Further an alarm, alarm cancellation
relay and indicating lamp coloured `Clear‟ with inscription on the globe reading `DC
failure‟ should also be provided on each Incomer VCB panel for DC failure. In order to
reduce DC Load, indicating lamp assemblies preferably LED type may be provided.

2.15 AUXILIARY CONTACTS


For the purpose of inter tripping, indications etc. a minimum of eight auxiliary
contacts (4 N/O and 4N/C ) shall be provided. In addition to it, eight auxiliary contacts (4
N/O and 4N/C) as spares shall also be provided. The contacts not used in the circuitary
should also be wired up to the terminal blocks. All the terminals should be accessible from
the front preferably. Its rating should be min. 600V, 25A suitable for 220V DC application
& should be either of manufactures own make or of best quality and approved make.

2.16 WIRING AND CABLE SCHEDULE


All wiring shall consist of FRLS PVC insulated cables confirming to requirement of
ASTM standards suitably coloured, marked as per table II clause 2.2.4 of ISS 373-1963 and
as per BSS No. 158 with latest amendment. The manufacturer shall have to supply
complete wiring diagram of all types of panels to complete the switch board for each Sub
Station. The wiring in the panels be laid through troughs for neat and clean wiring. 230 V
AC/220V DC terminals wherever prone to accidental touch need to be properly shrouded.

The wiring in the panel shall be coloured duly ferruled at both ends with 1100 volts
grade multi stranded single core copper PVC cable of min. 2.5mm sq. size for all purposes
except PT & CT circuits where 4mm sq. is to be provided. For CTs & PTs disconnecting
link type TBs are to be used. On ferruling, starting as well as finishing no. of each control
cable wire must be mentioned at both ends.
The control cables to be laid between the 11KV panels & other indoor equipment viz
DC panels, LT AC control panels and outdoor CTs shall be 1100 V grade PVC
insulated, unarmoured cables and shall be provided by the purchaser. A cable schedule
stating the sizes and no. of codes of each cable and the purpose for which required
should be given by manufacturer.

2.17 INTERLOCKING
2.17.01 Efficient mechanical interlocking shall be provided to meet the following
conditions:

9
i) It shall be possible to withdraw the breaker only after circuit breaker has been opened.
ii) It shall be possible to insert or withdraw the circuit breaker both when it is in fully home
position as well as it is in the isolated/test position.
iii) It shall not be possible to remove the circuit breaker until the movable plug unit having
secondary connections has been withdrawn.
iv) It shall not be possible to replace in position the moveable plug unit unless the circuit
breaker has been racked in.
v) Provision of shutters or lock off doors with locks shall be made to prevent access to bus
bars chambers and receptacles when the circuit breaker is withdrawn.
vi) Provisions shall be made for locking the circuit breaker closing mechanism in the open
position.

2.18 SPANNERS AND TOOLS


A complete set of spanners, tools and special tools which may be necessary for assembling
and dismantling the equipment during erection and maintenance are to be supplied with
each panel.

2.19 DESIGN MATERIALS & WORKMANSHIP:


The manufacturer shall assume full responsibility for coordinated and adequate design.
All material used in the construction of equipment shall be of the best quality obtainable of
their respective kinds and whole of the work shall be of the highest class, well finished and
of approved design and make. Corresponding similar components and part of the
equipment shall be interchangeable in every respect.

2.20 TROPICAL TREATMENT AND PAINT


All the corrodible parts and surfaces shall be of such material and shall be provided
with such paint or other protective finish that no part of the installed equipment shall be
injuriously affected by atmospheric moisture, sulphuric contents in air and heat.

2.21 COLOUR AND FINISH


All panels should be of Light Grey colour shade 631-IS 5(1961 latest edition) with
powder coating. All instruments should preferably be semi Matt Black colour. The inner
painting in the panels shall be of white colour.

2.22 TESTS AND INSPECTION


A TYPE TEST:
The equipment shall comply with the requirements of following type tests as per latest
edition of ISS/IEC. Copies of Type Test certificate shall be uploaded/submitted along with
the tender with regard to the following Type Tests from NABL accredited independent
Govt./Public Sector test laboratory.
a) Dielectric type test report
b) Short time rating test report
c) Temperature rise test report
d) Mechanical Endurance test report (M2 class Circuit Breakers suitable for 10000
operations)
e) Degree of Protection IP-5X test report
f) Basic short circuit test duties
g) Internal Arc test at 25KA for 0.1 sec.
h) Capacitor current Switching Test

10
Further, as per IEC 62271-100, clause 6.1.1 “Grouping of Tests”: The tests defined below
shall be carried out on maximum four test Specimens:-
a) Dielectric Type Tests Report.
b) Short Time Rating Test Report.
c) Temperature Rise Test Report.
d) Mechanical Endurance Test Report.
e) IP5X Test Report (Degree Of Protection Test).
Also,Internal Arc Test shall be performed on 1 no. VCB only, for all the chambers
i.e Panel with same serial no.
The type test certificates to be furnished along with the tender should be in respect of
specified make, type and rating of the circuit breaker intended to be offered and not
in respect of breaker manufactured by their foreign collaborators, if any. All the
drawings along with Bill of material duly authenticated by the Govt./Public Sector
Test House on which type tests have been carried out must be furnished along with
the tender. Also type tests more than 5 years old from the date of opening of tender
will not be considered. No tests conducted at own labs of the firm even if accredited
by CPRI/NABL shall be accepted.

B) ROUTINE TESTS:
All routine tests shall be conducted as per relevant ISS & IEC. In addition to the routine
tests, Temp. rise test and Part Mechanical Endurance test shall also be witnessed on one
breaker panel having highest rating free of cost as part of routine test. The equipment shall
comply with all routine tests as per relevant ISS & IEC. All the test certificates of each
item should be submitted to the purchaser for approval. No material shall be allowed to
despatch without prior inspection and approval of test certificates.

C) INSPECTION
The purchaser reserves the right to get the equipment inspected during the course of its
manufacture and also on the completion of its manufacturing. During the evaluation of the
bids, the bidder may be asked to demonstrate the interoperability of its offered relay(s)
with other make relays if required by PSTCL.

2.23 GUARANTEED DATA AND OTHER PARTICULARS:


Guaranteed & other technical particulars of the circuit breakers, bus bars, CTs, PTS &
instruments etc. are given in the form as per Annexure-C `Schedule of Guaranteed
Technical Particulars‟.

2.24 PACKING AND TRANSPORT:


All material shall be suitably packed for transport, direct to site and supplier shall be
responsible for all damages/losses due to improper packing. All boxes shall be marked with
signs indicating the up & down sides of the boxes along with the unpacking instructions, if
considered necessary by the supplier.

2.25 PERFORMANCE GUARANTEE:


All the equipment supplied against this Spec. shall be guaranteed against the
defective material, inadequate design and bad workmanship for a period of atleast12
months from the date of commissioning or 18 months from the date of despatch which ever
is earlier.

2.26 SPARES
A set of spares considered necessary for 5 years normal operation as recommended by the
manufacturer, should be listed for each 11 KV VCB Panels and their prices shall be quoted
item wise. The tenderer shall give item wise price of spares as per enclosed

11
Annexure-E. The prices shall remain valid for a period of 3 years from date of opening of
tender. The warranty of spares like meters, relay, VI etc. shall be as mentioned in the spec.
The tenderer shall separately indicate present rate of GST and F&I charges for spares.

2.27 DRAWINGS AND LITERATURE


The tenderer should submit detailed dimensional drawings of equipment offered and
of all bought out items along with illustrative and descriptive literature for each item for
approval.

2.28 VACUUM INTERRUPTERS


The vacuum interrupters of 12KV, min 25KA, 2000A should be capable of
withstanding, min. 100 full short circuit operations as per test duty 1 to 5 of relevant IEC-
62271-100. Vacuum interrupters for incomers, station transformer,outgoing, capacitor
control panels and bus coupler panels shall be of same type. The vacuum interrupters
capable of withstanding less than 100 full short circuits would not be considered and
therefore should not be offered. Literature for the Vacuum Interrupters along with
dimensional drawings should be supplied.
Approved make & type of VIs to be used are as under:
1. M/s Alstom Type V207
2. M/s CGL Type WL-33379/C/C1/M/M1/M3
3. M/s BEL Type VS-12014
4. M/s ABB Calor Emag Germany
5. M/s Siemens Type VS-17005

Vacuum Interrupters of above make/model or the latest version if any be supplied,


provided the same is type tested and of proven design.

These VIs shall bear warranty for 5 years of free replacement from date of
commissioning. Copy of type test certificates from approved Govt. test house indicating no.
of operation in respect of VIs is to be enclosed with offer. Same Vacuum Interrupter which
is used in type tested VCB shall be offered with the offered VCB. Vacuum Interrupter of
any other make/model will not be accepted.

2.29 OPERATING MECHANISM


As clearance between contacts when vacuum circuit breaker is in `OFF‟
condition, is very small, so it is quite essential that operating mechanism is such that all the
three poles should open and close simultaneously subject to maximum time difference as
per relevant IS/IEC.
The operating mechanism shall be motor operated spring charged type. There shall be
provision (s) for manual charging of closing spring and emergency hand trip. The motor
used for the purpose will be suitable for 240 V AC. The operating mechanism shall work
satisfactorily between 85-110% of rated supply voltage.

2.30 CABLE GLANDS


PSTCL has standardised the use of 1100 Volts grade PVC Cables for various purposes
as under:-
i. For CTs 4C 4mm Sq.
ii. For PTs 4C 4mm Sq.
iii. For 230 V AC 2C 2.5mm Sq.
iv. For 220V DC 2C 2.5mm Sq.
Cable glands are in the scope of manufacturer and may be provided accordingly.

12
2.31 POWER CABLE ENTRY FOR BREAKERS
In all type of breaker panels, power cable entry provision for requisite no. of
power cables as per schedule of requirement shall be from the bottom. However, no such
provision shall be provided for bus coupler panels.

2.32 COMPARTMENTS
All high voltage compartments such as bus bar, breakers and cable chambers shall be
separated from each other by metallic portion in line with IEC.These compartments must
have pressure release provision for the gases due to internal arc etc. Supplier shall submit
test report certificate from Govt. test house in this regard.

2.33 INSTRUCTION PLATES AND MARKINGS:


All name plates, instruction plates, warning signs and any marking whatsoever
on the equipment and its parts and accessories should be in English Language.
Terminal block diagram indicating function of each lead with self speaking
remarks may be affixed on the inside door of switch/control cubicle.
All name plates shall be riveted. P.O. No., date & the name of purchaser shall also
be mentioned on the name plate along with other details.

2.34 TRAINING
The firm shall provide training to PSTCL officers/officials at various locations as
desired by PSTCL.

13
SECTION –III
SCHEDULE OF TECHNICAL REQUIREMENTS

The basic enclosure should be metal enclosed in construction, having distinct


compartments i.e. circuit breaker compartments with front door, relay and instrument
chamber, TVM Chamber, Bus Bar compartment, cable chamber etc. All doors and
removable covers should be gasketted using high life neoprene or cross linked
polyurethanene gaskets. Each cubical should be vermin proof and dust protected. IP5X test
certificate in this regard have to be furnished with the tender document.

TVM shall have provision of RS-485 Port & DLMS port to enable remote metering and
computation of data in the computer. Provision for TVM should be made such that it can be
mounted at a convenient height so that same can be read by a normal height person. Panels
shall be totally enclosed, floor mounted, indoor type, dust and vermin proof fully
interlocked horizontal isolation pattern, air insulated, single 3 phase Bus, metal clad,11 KV
3 phase 4 wire 50 cycles , neutral earthed,475MVA,spring charged manually/trip free
independent motorized, electrically/manually operated switch panel boards as per ISS-
13118/IEC-62271-100/62271-200/IEC-298 (with latest amendments). The panel shall be
complete with CTs/PTs, Electrolytic Copper bus bars 1250 A/630A,necessary internal
copper connectors matching with breaker rating, small wiring labels, mounting
arrangements for cable, sealing, Power cable glands and multi core cable glands. Fuses,
earth bars, tropical, dust & vermin proof fitments, foundation bolts etc. and as detailed
briefly hereunder:-

System : 11000 V, 3 phase 50 cycles per second neutral earthed.

Breaking capacity : 475 MVA at 11KV, 3 phase.

Control : Trip free independent, spring charged manually/ motorized,


electrically & manually operated control.
Situation : Indoor.
General : Tropical & Vermin Proof.
Finish : Flush at the front as specified.
Auxiliary Supply : i) For tripping, alarm and healthy trip indication 220V DC, 230V
AC for ON/OFF indication lamps, cubicle illumination lamps and
heaters etc.

Rating of : 250 V AC, if filament type lamps used and the same should be
Indicating Lamps with resistors or neon/LED type lamps may be used. CT type
indicating lamps assembly may be used wherever feasible to
reduce power loss.

Painting & Colour : Light grey colour, shade 631 of IS-5with powder coating for Panels
and preferably semi Matt black for instruments and relays. The
inner painting in the Panels shall be of white color as per clause
2.21.

Ferrule/ Label marking : Black letters on white background. The label should be of
permanent nature type wherever provided instead of paint and
paper sticker type.

Phase Colours wiring : Red, Yellow, Blue phase colour for AC and coloured
wiring For DC supply.

14
Description Requirement : A general description of different types of panels included
in the specification is given below in brief:

Item-I 11KV, 475MVA,I/C VCB with CT primary rating 1200-600A, 900-450A as


per item-I of Annexure `A‟.

Item-II 11KV,475MVA Station T/F VCB panel with CT primary rating 100-50A as
per item-II of Annexure`A‟ .

Item-III 11KV, 475MVA, O/G VCB with CT primary rating 400-200A as per item-III
of Annexure `A‟.

Item- IV 11KV, 475 MVA bus coupler VCB with CT primary rating 1200-600A as per
item-IV of Annexure `A‟

Item- V 11KV, 475 MVA Capacitor control VCB with CT primary rating 600-300A
or 400-200 A as per item-V of Annexure `A‟

15
ANNEXURE `A’
BILL OF MATERIAL

Item-I
EXTENSIBLE TYPE INCOMING PANEL
(1200-600A, 900-450A)
Split up of quantity for,1200-600A, 900-450A (220V DC) incomers shall
be intimated at the time of placement of order/approval of drawings.

STATIONARY PORTION:
Stationary portion will consist of sheet steel cubicles of min. 2.0mm thickness
CRCA sheet complete with three phases,1250A (min. cross-sec. 1250mm sq.) electrolytic
copper bus bar , six single pole 1250 A Isolating sockets, automatic safety shutter gear
including padlocking arrangement and mounting arrangement for terminating 9 Nos. XLPE
power cables of size 1C 300mm Sq. having aluminium conductor. To avert heating
problem in the long run it is imperative on the part of successful bidders to provide 2000A
current rating male contacts in the Incomer breaker panels.

MOVEABLE PORTION:
Moveable portion complete with 11KV, 1250 A minimum 25KA/3 sec. triple pole
vacuum circuit breaker having 3 interrupters and fitted with 6 isolating plugs , trip free,
independent manually as well as motorized operated spring charged closing mechanism,
DC closing coil and shunt trip coil, min. 8 Nos. auxiliary contacts ( 4NO+4NC) along with
spare 8 Nos. Auxiliary contacts (4NO + 4NC) ,an emergency hand trip device and
mechanical `ON & `OFF‟ indicators. The circuit breaker shall be mounted on the carriage
fitted with self contained Inserting & Withdrawing gear and plug box of unbreakable
material with flexible portions. To avert heating problem in the -long run, it is imperative
on the part of successful bidders to provide 2000A current rating female contacts in the
incomer breaker panels.

CURRENT TRANSFORMERS:
All CTs shall have 25% continuous over load capacity. Ratio changeover of CTs
should be from secondary side only. Three double ratio, double core, bar type , epoxy resin
cast current T/Fs of ratio 1200-600/.577-1A,900-450/.577-1A for differential & REF
protection of power transformer with characteristics:

Core-1 VA-10, Class PS, VK>40(1+ RCT)I


(for differential Protection VK > 266V at
RCT < 5.63 Ohms ) Imag < 30 mA
Core-II VA=25,5P, ALF =15 ( For REF Protection )

Three Double ratio, double core, bar type, epoxy resin cast current T/Fs of ratio 1200-
600/5-5A, 900-450/5-5A for over current & E/F Protection and indicating instruments and
metering having characteristics.
Core-1 VA=10, Class 5P, ALF=10 (for back up protection)
Core-II VA=10, Class 0.2S, ISF less than 5 at lower tap (for metering)
NOTE: Metering core is required to be provided on all the phases. Spare core of CT
wherever exists is to be short circuited.

POTENTIAL T/Fs.
1 No. 3 phase voltage T/F of ratio 11000/√3 /110/√3 volts should be provided on the bus
bar of this panel for giving supply to voltmeter , P.F. meter ,H.T. Solid State Trivector

16
meter on the incoming feeder panels. The PT shall be epoxy resin cast type complete with
isolating contact, safety shutters etc. having VA = 30 per phase and accuracy class =0.2.

vi) INSTRUMENTS PANEL WITH HINGED FRONT DOOR AND SEPARATE


SEALABLE METERING CHAMBER.
It should be fitted with following instruments and accessories :

a) Each of 11KV VCB panels shall be provided MULTI FUNCTION METER, which
should be on MODBUS Protocol with RS 485 port for SCADA of
Accord/Siemens/AE/reputed make. Accuracy should be +/- 0.5% of indicated value
three & half digits..

1-HT solid state trivector meter 3 phase 4 wire suitable for 3 phase unbalanced load with
accuracy class 0.2S or better of L&T/Secure make shall only be acceptable. TVM shall
have provision of RS-485 Port& DLMS port to enable remote metering and computation of
data in the computer. Energy meter should be mounted at a convenient height so that same
can be read by a normal height person.

The technical parameters of the 3 phase 4 wire solid state trivector meter are annexed
at annexure `D‟. PSTCL reserves its rights to inspect these meters at the
manufacturers premises. PSTCL further reserve its rights to ask for any make of
TVM of its own choice .

c) 1-Set of testing links and terminals for TVM.


d) 2-Indicating lamps one `Red‟ for circuit breaker „ON‟ and other „Green‟ for circuit
breaker
„OFF‟ position indications.
e) 1-indicating lamp `White‟ for healthy trip circuit supervision breaker in both pre-close
and after close position through a push button only.
f) 1-indicating lamp „Amber‟ for fault indication , 1-indicating lamp `Blue‟ for spring
charged indication. All Indicating Lamps shall be of Tecknic/Venson/Reputed and
approved make.
g) 1 no. Non-directional, IEC 61850 compliant over current and earth fault relay as
specified in Section II, Technical specifications para 2.09 A and 2.09 B(i)
h) 1- no. High Speed Master Tripping Relay.
i) Cable gland plate fitted with glands including spare ones.
j) 1- Tubular gland plates fitted with glands including spare ones. 1-Tubular heaters of
reputed and approved make with switch and thermostat.1no. 15A plug and socket
alongwith one illumination lamp.

k) 1-set of small wiring with cable troughs & crimping lugs, labels/ferrules, terminal
block stud type with Perspex covering [ sliding type wherever required] and
sundaries.
l) 1-No. lockable control switch with spring return to normal position KAYCEE/Recom
make heavy duty of min. 660V of 16A rating with pistol grip handle.
m) 1 no. Local/ remote switch, 4 pole in each position, 2 way lockable and stay put type,
KAYCEE/Recom/Switron/L&T/Siemens/ABB/ALSTOM make.
n) Terminal Block stud type [ spare ] having provision of 20 Nos. connections of
Connectwell/Wago/JVS/Reputed and approved make.
o) Power cable glands of double compression type.
p) Incomers shall additionally be provided with requisite arrangement ,auxiliary relays
etc.for interlocking with bus coupler breaker panels.

17
ISOLATING CONTACTS:
Male & female isolating contacts of incomer breaker panels shall be of 2000A rating
to avoid heating problem in the long run. The thermal rating of the contacts shall be
authenticated by the bidder.

MAIN BUS BARS/DROPOUTS


Main bus bars/dropouts shall be of electrolytic copper of min. cross-sectional area
1250 mm sq. having maximum current density of 1 Amp. Per mm sq. in case of all
incoming panels.

viii) Common items to be provided on the incoming panels for alarm on VCB trip
and DC failure.
a) 1- Auxiliary Alarm initiation relay.
b) 2-Push buttons for alarm accept & alarm re-set.
c) 1-Alarm Bell for trip alarm.
d) Buzzer and auxiliary relay for DC failure indication.
e) DC failure indicating lamp coloured `Clear‟ with suitable legend on globe.
f) 2-Push buttons for DC fail test and alarm accept.

ITEM- II :
EXTENSIBLE TYPE STATION TRANSFORMER VCB PANEL (100-50A)

i) Stationary portion :Same as per incoming panels item-I above except that the
rating of movable portion shall be 11KV 630A . The
current rating of male/female contacts shall be 800A &
mounting arrangement for termination of one no. XLPE
power cable of size 3C x 300mm2 with aluminium
conductor (without epoxy sealing kit).
Moveable portion :

iii) CURRENT TRANSFORMERS:


Three Double ratio, Double Core wound primary epoxy resin cast current T/Fs of
ratio 100-50 /5-5A as the case may be for over current and earth fault protection and
indicating instruments and metering having characteristics.

Core-I : VA=10, class 5 P. ALF-20. [ for O/C & E/F Protection ]


Core-II : VA=10, Class 0.2S, ISF < 5 [ for metering ]

NOTE : Metering core is required to be provided on all the phases. Ratio changeover
should be from secondary side of the CTs only.

INSTRUMENTS PANEL WITH HINGED FRONT DOOR AND SEPARATE


SEALABLE METERING CHAMBER:

This panel should be fitted with following instruments and accessories:


a) Each of 11KV VCB panels shall be provided MULTI FUNCTION METER, which
should be on MODBUS Protocol with RS 485 port for SCADA of
Accord/Siemens/AE/reputed make. Accuracy should be +/- 0.5% of indicated value
three & half digits.

b) Cut out for accommodating TVM in future shall be provided with dummy plate.

18
c) 2 no. indicating lamps , one `RED‟ for breaker `ON‟ and one `GREEN‟ for breaker
`OFF‟ position.
d) 1-Indication lamp `WHITE‟ coloured for healthy trip indication with a push button
for the breaker preclose and after close position. 1-Indication lamp `AMBER‟
coloured for fault indication with provision for common alarm provided on incomer
panel and one indicating lamp`BLUE‟ for spring charge indication.
e) 1 no. Non-directional, IEC 61850 compliant over current and earth fault relay as
specified in Section II, Technical specifications para 2.09 A and 2.09 D(i)
f) 1no. High Speed Master Tripping Relay.
g) 1 No. Trip Circuit Supervision Relay along with an indication lamp.
h) 1no.set of testing links and terminals for TVM.
i) 1no. tubular heater of reputed and approved make with a switch and thermostat,
1no. 15 Amp. Plug and socket and one illuminating lamp.
j) 1no. set of small wiring with cable troughs & crimping lugs.
k) 1no. labels, terminal blocks (stud type or sliding link type wherever required)&
sundaries to complete the job.
l) 1-No. lockable control switch with spring return to normal position of
KAYCEE/Recom Make),heavy duty of min.660V,16A rating with pistol grip handle.
m) 1 no. Local/ remote switch, 4 pole in each position, 2 way lockable and stay put type,
KAYCEE/Recom/Switron/L&T/Siemens/ABB/ALSTOM make.
n) Terminal block stud type [spare] having provision of 20 Nos. connections.

ISOLATING CONTACTS
Male & female isolating contacts of the panels shall be of 800A rating to avoid
heating problem in the long run. The thermal rating of the contacts shall be authenticated
by the bidder.

MAIN BUS BARS/DROPOUTS


Main bus bars shall be of electrolytic copper of min. cross sectional area 1250 mm sq.
having maximum current density of 1 Amp. Per mm sq. Similarly the drop outs shall be of
electrolytic copper of min. cross sectional area of 630mm sq. having maximum current
density of 1 Amp. Per mm sq.

ITEM-III :
EXTENSIBLE TYPE OUTGOING PANELS (400-200A)

i) Stationary portion: Same as per incoming panels item-I above Except that the rating
of movable portion shall be 11 KV 630 A. The current rating
of Isolating male/female contacts shall be 800A & mounting
arrangement for termination of one no. XLPE power cable
size 3C x 300mm Sq. with aluminium conductor
ii) Moveable portion:[without epoxy sealing kit].

CURRENT TRANSFORMERS:
Three Double ratio, Double Core wound primary epoxy resin cast current T/Fs of ratio
400-200/5-5A as the case may be for over current and earth fault protection and indicating
instruments and metering having characteristics

Core-I VA=10, class 5 P. ALF-20.


[ for O/C & E/F Protection & SEF ]
Core-II VA=10, Class 0.2S, ISF < 5 at lower tap
[ for metering ]

19
NOTE: Metering core is required to be provided on all the phases. Spare core of CT
wherever exists is to be short circuited.

INSTRUMENTS PANEL WITH HINGED FRONT DOOR AND SEPARATE


SEALABLE METERING CHAMBER:

This panel should be fitted with following instruments and accessories:


a) Each of 11KV VCB panels shall be provided MULTI FUNCTION METER, which
should be on MODBUS Protocol with RS 485 port for SCADA of
Accord/Siemens/AE/reputed make. Accuracy should be +/- 0.5% of indicated value
three & half digits..
b) 2-indicating lamps, one `RED‟ for breaker `ON‟ and one `GREEN‟ for breaker `OFF‟
position. 1-Indication lamp `WHITE‟ coloured for healthy trip indication with a push
button for the breaker pre close and after close position. 1-Indication lamp `AMBER‟
coloured for fault indication with provision for common alarm provided on incomer panel
and one indicating lamp `BLUE‟ for spring charge indication.
c) 1 no. Non-directional, IEC 61850 compliant over current and earth fault relay as
specified in Section II, Technical specifications para 2.09 A and 2.09 C(i)
d) 1 no. High Speed Master Tripping Relay.
e) 1 No. Trip Circuit Supervision Relay along with an indication lamp.
f) 1-set of testing links and terminals for TVM.
g) 1- tubular heater with a switch and thermostat. 1- 15 Amp. Plug and socket and one
illuminating lamp.
h) 1-set of small wiring with cable troughs & crimping lugs. 1-labels, terminal blocks, stud
type[sliding link type wherever required] & sundries to complete the job
i). 1- No. lockable control switch with spring return to normal position (KAYCEE/Recom

j) 1 no. Local/ remote switch, 4 pole in each position, 2 way lockable and stay put type,
KAYCEE/Recom/Switron/L&T/Siemens/ABB/ALSTOM make.
k) Terminal block stud type [spare] having provision of 20 Nos. connections of
Connectwell/Wago/JVS/Reputed and approved make.
l). 1 no.3 phase 4 wire HT solid state trivector meter suitable for unbalanced load with
accuracy class 0.2S or better of Secure/L&T make with technical particulars as per
Annex.`D‟. PSTCL reserves the right to ask for TVM of its own choice. TVM shall have
provision of RS-485 Port and DLMS Port to enable remote metering and computation of
data in the computer. Energy meter should be mounted at a convenient height so that same
can be read by a normal height person.
m) Provision shall be made in the panels so as to facilitate fitting of 11KV PT at future date
besides sealing provisions for TVM chamber & CT Chamber to avoid tampering enroute.

ISOLATING CONTACTS
Male & female isolating contacts of outgoing panels shall be of 800A rating to avoid
heating problem in the long run. The bidder shall submit the dimensional drawings of
isolating contacts with the tender.The thermal rating of the contacts shall be authenticated
by the bidder.

MAIN BUS BARS/DROPOUTS


In respect of all outgoing panels, main bus bars shall be of electrolytic copper of min.
cross-sectional area 1250 mm sq. having maximum. Current density of 1 Amp. Per mm sq.

20
Similarly the drop outs shall be of electrolytic copper of min. cross sectional area of
630mm sq. having maximum current density of 1 Amp. Per mm sq.

ITEM-IV
EXTENSIBLE TYPE BUS COUPLER PANELS [1200-600A]

STATIONARY PORTION:
Stationary portion will consist of sheet steel cubicles of min. 2.0 mm thickness CRCA
sheet complete with three phases,1250A minimum cross section 1250 sq mm electrolytic
copper bus bar , six single pole 1250 A Isolating sockets, automatic safety shutter gear
including padlocking arrangement . To avert heating problem in the long run it is
imperative on the part of successful bidders to provide 2000A current rating male contacts
in the bus coupler breaker panels.

MOVEABLE PORTION:
Moveable portion complete with 11KV , 1250 A minimum 25 KA for 3 sec. triple pole
vacuum circuit breaker having 3 interrupters and fitted with 6 isolating plugs , trip free,
independent manually as well as motorized operated spring charged closing mechanism,
DC closing coil and shunt trip coil, min. 8Nos. auxiliary contacts ( 4NO+4NC) along with
spare 8 Nos. Auxiliary contacts (4NO + 4NC) ,an emergency hand trip device and
mechanical `ON & `OFF‟ push buttons/indicators. The circuit breaker shall be mounted on
the carriage fitted with self-contained Inserting & Withdrawing gear and plug box of
unbreakable material with flexible portions. To avert heating problem in the long run , it is
imperative on the part of successful bidders to provide 2000A current rating female
contacts in the bus coupler panels.

CURRENT TRANSFORMERS:
All CTs shall have 25% continuous over load capacity. Ratio changeover of CTs should be
from secondary side only. Three double ratio, double core, bar type, epoxy resin cast
current T/Fs of ratio 1200-600/5-5A for overcurrent and earth fault protection and
indicating instruments and metering having characteristics ;

Core-1 VA=10, Class 5P, ALF 10


(for O/C and E/F Protection)
Core-II VA=10, class 0.2S , ISF < 5 at lower tap [for metering ]

NOTE: Metering core is required to be provided on all the phases. Spare core of CT
wherever exists is to be short circuited.

INSTRUMENTS PANEL WITH HINGED FRONT DOOR &


SEPARATE SEALABLE METERING CHAMBER:

This panel should be fitted with following instruments and accessories:


a) Each of 11KV VCB panels shall be provided MULTI FUNCTION METER, which
should be on MODBUS Protocol with RS 485 port for SCADA of
Accord/Siemens/AE/reputed make. Accuracy should be +/- 0.5% of indicated value
three & half digits.
b) 2- Indicating lamps, one `RED‟ for breaker `ON‟ and one `GREEN‟ for breaker
`OFF‟ position.

21
c) 1-indicating lamp `White‟ for healthy trip circuit supervision in both pre-close and
after close position through a push button only.
d) 1-indication lamp `AMBER‟ for fault indication & 1- Indication lamp `BLUE‟ for
spring charged indication.
e) 1 no. Non-directional, IEC 61850 compliant over current and earth fault relay as
specified in Section II, Technical specifications para 2.09 A and 2.09 E(i)
f) 1 no. High Speed Master Tripping Relay.
g) 1 No. Trip Circuit Supervision Relay along with an indication lamp.
h) Cable gland plate fitting with glands including spare ones.
i) 1-set of small wiring with cable troughs & crimping lugs labels/ferrules, terminal
block stud type with Perspex covering (sliding type wherever required) & sundries.
j) 1 no. lockable control switch with spring return to normal position
KAYCEE/Recom make heavy duty of min. 660V, 16A rating with pistol grip handle.
k) 1 no. Local/ remote switch, 4 pole in each position, 2 way lockable and stay put
type, KAYCEE/Recom/Switron/L&T/Siemens/ABB/ALSTOM make.
l) Terminal Block stud type [spare] having provision of 20 Nos. connections.
m) 1- Tubular gland plates fitted with glands including spare ones. 1-Tubular heaters
of reputed and approved make with switch and thermostat. 1no. 15A plug and
socket along with one no. illumination lamp.
n) Power cable glands of double compression type.
o) Bus Coupler Panels shall additionally be provided with requisite
arrangement,auxiliary relays etc. for interlocking with Incomer panels.

ISOLATING CONTACTS
Male & female isolating contacts of bus coupler breaker panels shall be of 2000A
rating . The bidder shall submit the dimensional drawings of isolating contacts with the
tender .The thermal rating of the contacts shall be authenticated by the bidder.

MAIN BUS BARS/DROPOUTS


Main bus bars/dropouts shall be of electrolytic copper of min. cross sectional area 1250
mm sq. having maximum. Current density of 1 Amp. Per mm sq.

ITEM-V :
EXTENSIBLE TYPE Capacitor Control VCB Panels (600-300 A or 400-200A)

Split up quantity in respect of CT ratio 600-300A or 400-200A for capacitor control


VCB panels shall be intimated at the time of approval of drawings.

i) Stationary portion: Same as per incoming panels item-I above Except that the rating
of movable portion shall be 11 KV 630 A. The current rating
of Isolating male/female contacts shall be 800A & mounting
arrangement for termination of one no. XLPE power cable
size 3C x 300mm Sq. with aluminium conductor
ii) Moveable portion:[without epoxy sealing kit].

CURRENT TRANSFORMERS:
Three Double ratio, Double Core bar primary epoxy resin cast current T/Fs of ratio 600-
300/5-5A or 400-200/5-5A as the case may be for over current and earth fault protection
and indicating instruments and metering having characteristics :

22
Core-I VA=10, class 5 P. ALF-20.
[ for O/C & E/F Protection ]
Core-II VA=10, Class 0.2S, ISF < 5 at lower tap
[ for metering ]

NOTE: Metering core is required to be provided on all the phases. Spare core of CT
wherever exists is to be short circuited.

INSTRUMENTS PANEL WITH HINGED FRONT DOOR AND SEPARATE


SEALABLE METERING CHAMBER:

This panel should be fitted with following instruments and accessories:


a) Each of 11KV VCB panels shall be provided MULTI FUNCTION METER, which
should be on MODBUS Protocol with RS 485 port for SCADA of
Accord/Siemens/AE/reputed make. Accuracy should be +/- 0.5% of indicated value
three & half digits..
b) 2-indicating lamps, one `RED‟ for breaker `ON‟ and one `GREEN‟ for breaker `OFF‟
position.
c) one indicating lamp `BLUE‟ for spring charge indication.
d) 1-Indication lamp `AMBER‟ coloured for fault indication with provision for common
alarm provided on incomer panel and one indicating lamp `BLUE‟ for spring charge
indication.
e) 1-Indication lamp `WHITE‟ coloured for healthy trip indication with a push button for
the breaker pre close and after close position.

f) 1 no. Non-directional, IEC 61850 compliant over current and earth fault relay as
specified in Section II, Technical specifications para 2.09 A and 2.09 F(i)
g) One set of alarm annunciation equipment consisting of following :-
1 no. Auxiliary alarm cancellation relay (VAA-21 or eq.)
1 no. DC alrm bell.
1 no. push button switch complete with label marked `Accept‟.
1 no. indicating lamp `AMBER' labelled `ALARM' .
h) 1 no. Auxiliary Transformer (for external mounting) ratio 121/115 to 127V (in
steps of 1 volt) to be used for compensating the error of over voltage relay (if
required).
i) 1 no. High Speed Master Tripping Relay .
j) 1no. Tubular heater with switch (80 w) & thermostat.
k) 1 no. VCB lockable control switch with spring return to normal position
(KAYCEE/RECOM MAKE), heavy duty of min. 660 Volt,16 Amp. rating with pistol
grip handle.
l) 1 no.Terminal block stud type having provision of 20 nos. connections including spare
ones of Connectwell/Wago/JVS/Reputed and approved make.
m) 1 no. Local/ remote switch, 4 pole in each position, 2 way lockable and stay put
type, KAYCEE/Recom/Switron/L&T/Siemens/ABB/ALSTOM make.

ISOLATING CONTACTS
Male & female isolating contacts of capacitor control panels shall be of 800A rating to
avoid heating problem in the long run. The bidder shall submit the dimensional drawings
of isolating contacts with the tender.The thermal rating of the contacts shall be
authenticated by the bidder.

23
MAIN BUS BARS/DROPOUTS
In respect of all Capacitor control VCB panels, main bus bars shall be of electrolytic
copper of min. cross-sectional area 1250 mm sq. having max. current density of 1 Amp. Per
mm sq. Similarly the drop outs shall be of electrolytic copper of min. cross sectional area
of 630mm sq. having maximum current density of 1 Amp. per mm sq.

COMMON NOTES
1. Each panel mentioned above shall be provided with set of miscellaneous accessories
including special tools , earth bars and other accessories as may be required for
maintenance and operation of each type of breaker.
2. Breaker earthing shall be provided in both service and test positions of the VCB
trolley.
3. The panels shall be complete with bus bars, foundation holding down bolts and all
other accessories required for its independent usage.
4. The DC trip voltage of the panels shall be 220V DC.
5. The various 11KV CTs to be supplied for differential protection under item no.I shall
also conform to class `PS‟ of IS-2705{Part-IV}.
6. The 1200-600/.577-1A CTs & 1200-600 /5-5A CTs required for item no. I should be
interchangeable with 900-450/.577-1A, 900-450/5-5A CTs respectively. The
dimensions/fixing arrangement should be such that these can be interchanged at site
without any difficulty.
7. The space in the CT chamber should be sufficient for fixing 11KV CTs of different
reputed makes available.
8. All the CTs shall have 25% continuous overload current rating. Ring type CTs for
various cores will not be acceptable.
9. Auxiliary wiring should be laid in troughs ,each wire should be provided with suitable
crimping lugs. Terminal blocks of the stud type with prespex covering should be
provided. All spare terminals of relays, auxiliary switch etc. should be wired upto TBs.
10. In case of horizontal drawout breakers, the wipe of moveable female contacts with
fixed male contacts should be through guided motion with pinion & gear arrangement
to avoid un-necessary manual jerk pressure while racking in the VCB trolley.
11. In order to achieve proper sealing arrangement for metering it is imperative on the
part of successful bidders to offer 11KV Breakers in compartmentalized design so that
CT, PT chamber and metering chamber etc. can be sealed independently & the
possibility of tampering is ruled out.
12. The Test Terminal Block (TTB) shall be of Alsthom/JVS/Reputed and approved
make.
13. All push buttons shall be of Siemens/L&T/Tecknic/JVS/Venson/Reputed and
approved make.
14. Warranty for Vacuum Bottles, TVM & Protection relays shall be five years from the
date of commissioning.
15. M/s Areva/ABB/Siemens/Ashida/Easun Reyrolle/CGL/Schneider relays shall be
offered with the panels. Further PSTCL reserves the right to ask for free replacement
for alternate reputed make Relays with 5 years warranty from the date of
commissioning.

24
16. Detailed drawings of 11KV VCB Panels, CTs, PTs, Meters, Relays, VIs & all other
bought out items used in the panels must be submitted along with complete technical
details.

17. It shall be possible to take out moveable portion of VCB without any problem and
without any additional accessory. However if such an accessory is required, it will be
responsibility of the supplier to provide requisite arrangement with each panel.
18. ALL THE TENDERERS MUST QUOTE COMPETITIVE RATES OF SPARES OF
EACH & EVERY ITEM AS PER ANNEXURE-`E‟. The prices so given shall remain
valid for 3 years from date of tender opening. The warranty of spares like meters,
relays, VI etc. shall be as mentioned in the spec.
19. All main relays shall be draw out, flush mounted type and shall have hand reset flag
indicators where specified & shall be operated on +10% &-20% of specified voltage.

25
ANNEXURE `C'
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 11KV VCB
PANELS TO BE SUPPLIED BY THE MANUFACTURER

1. PARTICULARS OF MANUFACTURE:
a. Name of manufacturer :
b. Manufacturer`s type & :
description for equipment
c. Whether the equipment is :
indigenous or imported.
d. In case the equipment is being :
manufactured with collaboration
the name of collaborator & Country.
e. Experience of manufacturer in
this field. :
f. IFSC CODE :
g. Beneficiary (Firm‟s) A/c No. :
h. E-mail ID :
i. Contact No.

2. RATING OF BREAKERS :
a) (i) Normal :
ii) Derated current rating under
specified site conditions(Amp.)
b) Breaking Capacity: :
i) Symmetrical (KA) :
ii) Assymetrical (KA) :
c) Making capacity (Peak KA) :
d) Short time current ratings
i) 1 Second (KA) :
ii) 3 Seconds (KA).
e) Contact resistance(R,Y,B phase) : Whether between jaws or including bus bar?
f) MVAR controlling Capacity. :
(supported by Test certificates)

3. WHETHER THESE BREAKERS ARE TYPE TESTED ,IF YES, INDICATE


CERTIFICATE/ REPORT NUMBER AND ATTACH PHOTO COPY
THEREOF.

i) Short circuit test. :


ii) High voltage test. :
iii) Temperature rise test. :
iv) Mechanical endurance test :
v) IP5X test.
vi) Internal ARC test. :
vii)Basic Short Circuit Test duties :
viii) Capacitor Switching Test :

4. INSULATION VALUES:
1 Min. high voltage withstand test(KV) :
a) Impulse withstand voltage (KV Peak):

26
5. PARTICULARS OF EQUIPMENT:

a) Clearance within the equipment.


i) Phase to Phase.(Insulated parts mm)
ii) Phase to Earth.
b) Minimum working distance required for
withdrawal of circuit breaker and to
do its maintenance at front.
c) Min. working clearance required at
the back of the equipment.
d) Weight of moveable unit complete
with mechanism (Kg.)
e) Weight of complete unit(kg)

6. PARTICULARS OF VACUUM INTERRUPTORS :

a) Name of manufacturer
b) Manufacturer`s type ,max. voltage,
normal amps. and rupturing capacity
of vacuum interruptors to be used in
various types of VCB panels.
c) Whether the VIs used in
incoming, and other type of panels
are same or different ?
d) Rated impulse withstand voltage (KV)
e) No. of breaks in circuit/phase
i.e. contact stroke.
f) Total length of break per phase
i.e. contact stroke.
g) Type of main contacts and /or
control devices.
h) Degree of vacuum inside the
vacuum interruptors.
i) Opening time.
j) Break time.
k) Closing time.
l) Arc duration.
m) Contact erosion limit (mm)
n) Short time rating of VIs.
o) No. of full short circuit operations
as per test duty 1 to 5 of IEC-56
with amendments which the Vis
offered can safely withstand
(attach type test report).
p) Mechanical life (Operations).

7. CONSTRUCTIONAL DATA OF BREAKERS :

a) Method of closing.
i) Whether hand or power ? :
ii) Whether the circuit breaker is :
designed to close and latch on

27
making or is fitted with making
current release ?
iii) Whether circuit breaker is fixed
trip or trip free ? :
b) Normal operating voltage of closing :
mechanism.
c) Power at normal voltage required :
to close circuit breaker.
d) Normal voltage required for shunt trip
coil :
e) Power at normal voltage required
for shunt trip coil. :
f) Make of auxiliary switch and
NO & NC contacts available.
No of N/O & N/C contacts available
as spares.
g) Whether the breakers are of :
fixed type OR withdrawable type ?
h) In case withdrawable, whether :
horizontal isolation OR Vertical
Isolation ?
i) Rating of spring charging motor :
alongwith complete assembly
j) Whether the CB operating :
mechanism is imported
OR indegenious ?
k) Whether the breaker is suitable for :
100 no.short circuit operations?
If yes, bidder to authenticate the same
l) Category to which the Service continuity :
of Switchgear belongs: LSC1 / LSC 2A
/LSC 2B as per IEC

8. PARTICULARS OF ELECTROLYTIC COPPER BUS BAR:

a) Cross sectional Main Dropouts


area (Sq.mm) (Width X Thickness) (Width X Thickness)

i) I/C :
ii) Station T/f Control panel :
iii) Outgoing Panels :
iv) Bus Coupler panel
v) Capacitor Control Panels :
b) Material :
c) Normal current under :
specified site conditions(Amps.)
d) Rating of ISOLATING
CONTACTS in Amps.
i) I/C Panels :
ii) Station T/f Control panel :
iii) Outgoing Panels :
iv) Bus Coupler panel
v) Capacitor Control Panels : :

28
9) PARTICULARS OF INSTRUMENTS AND METERS:
a) Type of equipment ( whether flush
mounted or base mounted ?)
b) Guaranteed %age errors at
different loads.
c) Make of these instruments:
i) Multi Function meter
ii) HT Solid State TVMs
d) Whether Multi Function
meter provided is of totally
uniform scale OR not ?

e) Whether TVM has


i) DLMS port
ii) RS485 port

10. CURRENT TRANSFORMERS :

a) Make of CTs
b) Rated Primary current
c) Rated Secondary Current
d) Rated Transformer Ratio.
e) Output at rated current
& accuracy class.
f) Saturation factor.
g) Type of Construction
& Type of Insulation.
h) Knee point e.m.f.
i) Exciting current at
knee point e.m.f.
j) Resistance of secondary
winding corrected to 75 Deg.C
k) Short time rating of CT
l) Magnetisation curve(to be
submitted alongwith tender).

NOTE: The VA burden , saturation factor and accuracy Class of CTs must be as per
PSTCL specification

11. PARTICULARS OF VOLTAGE TRANSFORMERS :

a) Make of PTs.
b) Rated primary
voltage per phase.
c) Rated secondary
voltage per phase.
d) No. of phases .
e) Rated transformation ratio.
f) Rated output at rated
primary voltage.
g) Accuracy Class.

29
h) Is H.V. neutral earthed
or insulated.
i) Type of construction.
j) Whether epoxy insulated ?

12. RELAYS :

a) Make
b) Type
c) i) Current rating
ii) Voltage rating
d) Current setting range
e) Time setting range
f) No. of auxiliary contacts
available.
(Note:- Firm shall supply complete Technical certificates of the Numeric O/C &earth
fault relay proposed to be used)
13. TNC BREAKER CONTROL SWITCH

a) Make
b) Voltage/Current rating
c) Type of Breaker control switch
d) NO & NC Contacts available.

14. a) If front door is provided in the 11KV


VCB panels
b) If emergency hand trip device is at the
operatable height, indicate the
distance from ground.
c) If the panels are of light grey shade
631-IS5 with powder coating.
d) Is the provision for mounting TVM at a
convenient height? If yes, indicate the height.

15. Particulars of Capacitor Control


Panels A. (i) Rating
a) Normal current
b) Breaking capacity
c) Symmetrical (KA) at 12KV (MVA)
(ii) Asymmetrical (KA) D.C. Component.

i) Making current (A)


ii) Max. line charging current
iii) Max. Capacitor MVAR it can control
a) Single Bank (MVAR)
b) Two or more banks in parallel
(MVAR) C. Short time current
i) 1 second (KA)
ii) 3 seconds(KA)
iii) Whether Restrike free
iv) Whether tested for capacitor switching,

30
if so, give test report No.(Attach photocopy).

16.. LOCAL/REMOTE SWITCH

a) Make
b) Type
c) Contact configuration
d) AC and DC current rating
e) AC voltage rating

17. ANY OTHER PARTICULAR

31
ANNEXURE `D'

TECHNICAL PARTICULARS OF STATIC TRIVECTOR METERS

TRIVECTOR METER SHOULD CONFORM TO:

PSPCL Spec. MQP-67/2013-14/PR (including corrigendums, if any) of CE/Metering


subject to the modifications and additional following features:-

1) TRIVECTOR METER SHOULD BE OF L&T/Secure MAKE only


TVM shall be AC, 3 Phase, 4 wire, CT/PT operated fully Static and AMR compatible
Trivector Energy meters for measurement of different electrical parameters, listed
elsewhere in the document, including Active energy (KWH), reactive
Energy(KVARH), Apparent Energy (KVAH) etc. Meter shall be suitable for 3 Phase 4
Wire solidly earthed system as well as 3 phase 3 wire balanced and un-balanced loads.
Energy meter should be mounted at a convenient height so that same can be read by a
normal person.
2) The TVMs shall be provided with RS-485 Port on MODBUS Protocol and also
DLMS port compatible with AMR system.
3) The accuracy of meter shall be 0.2 S (or better).
4) Meter shall display direct reading without multiplying factor at lowest tap of the CT of
the panel on which these are to be installed. Panel manufacturers shall co-ordinate
with meter suppliers accordingly.
5) Separate sampling as per clause 31.0 of Spec. MQP-67 shall not be required. However,
the TVMs of only those manufacturers‟ shall be used whose Sample Meters have
passed the testing as per Clause 31.0 of spec. MQP-67.
6) PSPCL shall be read as PSTCL wherever marking, inscriptions etc. are to done as per
specification referred to above.

NOTE:
1. PSTCL reserves the right to incorporate any other important parameter in respect of
TVMs which shall be indicated at the time of issue of P.O. / approval of bill of materials of
successful bidders.
2. One meter selected from the lot shall be inspected at the works of Meter manufacturer
to witness/carryout all the routine tests as per relevant IS.

32
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 3 PHASE 4
WIRE CT PT OPERATED TRIVECTOR ENERGY METER :-

Item Bidder’s data


1. Type
2. Application
3. Rated Voltage
4. Rated Current
5. Frequency
6. Overload capacity
7. Minimum starting current in %
of base current
8. Power loss in potential circuit
9. Power loss in current circuit
10. Change in error due to
a. Variation in frequency
b. Variation in temperature
c. Variation in voltage
11. Accuracy Class
12. Total Weight of meter
13. Details of case
14. H.V. withstand
15. Insulation Resistance
16. Standard to which the
meter confirm
17. Type of Energy Registration
Mechanism.
18. MD Reset Mechanism
19. Insulation Test
(Voltage 50Hz for 1Min)
20. Temperature co-efficient from
10% of rated load to 100 % rated
load (5°C to 45°C)
21. Working range
Voltage Current

22. Type of load (linear, non linear,


balanced /unbalanced at any P.F.)
23. Display details
i. Display Cycle (descriptive
in order of display)
ii. Period of display of
each parameter
iii. Display scroll-lock facility
iv. Backlit LCD
24. Memory
25. Power on in absence of mains
26. Tamper data
preservation capacity

33
27. Load Survey
a. Parameter Logged
b. Logging interval
c. No. of days of Load Survey
28. Time of the day Zone
29. Capability for fraud Prevention
& detection
30. Sealing and Locking Arrangement
31. Type of communication

32. Real Time Clock

NOTE:
The above information as mentioned from Sr. No. 1 to 32 must be furnished along
with the tender.

34
ANNEXURE `E'

CTs,PTs,INSTRUMENTS METERS,RELAYS,VACCUM
INTERRUPTORS AND OTHER BOUGHT OUT ITEMS ETC.

A) CURRENT TRANSFORMERS EPOXY RESIN CAST :


1) For Incoming VCB panels

11KV Double ratio 2 core current T/F for differential and REF Protection of ratio
i) 1200-600/.577-1A
ii) 900-
450/.57
7-1A
having
charact
eristic
Core-I, : VA=10, Class-PS
Core-II : VA=25, Class-5P ALF = 15

2) For Incoming/Bus coupler VCB panels


11 kV Double ratio, double core, current T/Fs for over current & E/F
Protection and indicating instruments and metering of ratio :
i) 1200-600/5-5A,
ii) 900-
450/5-5A
having
character
istics.
Core-1 VA=10, Class 5P, ALF=10 (for back up protection)
Core-II VA=10, Class 0.2S, ISF less than 5 at lower tap (for metering)

3) 600-300/5-5A for Capacitor control VCB Panels having characteristics :

Core-I,VA=10,Class 5 P, ALF=20
Core-II,VA=10,Class-0.2S
ISF < 5 at lower tap
4) 400-200/5-5A for Outgoing/ Capacitor control VCB Panels having characteristics:

Core-I,VA=10,Class 5 P, ALF=20
Core-II,VA=10,Class-0.2S
ISF < 5 at lower tap

5) 100-50/5-5A for Station T/F VCB Panels having characteristics :-

Core-I : VA=10,Class 5 P, ALF=20


Core-II : VA=10,Class-0.2S, ISF = less than 5

B) POTENTIAL TRANSFORMERS:

11000V/√3 / 110V/ √3 three phase epoxy resin type PT having VA=30 per phase &
Accuracy class-0.2.

35
C. INSTRUMENTS AND RELAYS :
Numeric Over Current Relay :-

i) Non-directional, IEC 61850 compliant over current and earth fault relay for
Incoming VCB panels as specified in Section II, Technical specifications para
2.09 A and 2.09 B(i)
ii) Non-directional, IEC 61850 compliant over current and earth fault relay for
Outgoing VCB panels as specified in Section II, Technical specifications para 2.09
A and 2.09 C(i)
iii) Non-directional, IEC 61850 compliant over current and earth fault relay for Stn.
transformer VCB panels as specified in Section II, Technical specifications para
2.09 A and 2.09 D(i)
iv) Non-directional, IEC 61850 compliant over current and earth fault relay for Bus
coupler VCB panels as specified in Section II, Technical specifications para 2.09
A and 2.09 E(i)
v) Non-directional, IEC 61850 compliant over current and earth fault relay for
Capacitor Control VCB panels as specified in Section II, Technical specifications
para 2.09 A and 2.09 F(i)

D) VACUUM INTERRUPTORS :

i) For incoming panel


ii) For outgoing, Capacitor control and station T/f panels
iii) For Bus Coupler panel
E) OTHER RELAYS :
i) Auxiliary Alarm cancellation relay.
ii) DC failure relay.
iii) High speed tripping relay.
iv) Auxiliary relays provided for interlock schemes.
F) OTHER ITEMS:
i) Indicating Lamp.
ii) Tubular heater with switch.
vi) VCB Control switch.

36
vii) Local/ Remote switch
v) Alarm Bell/Buzzer.
vi) Push Button.
vii) Trip coil 220V DC
viii) Closing coil 220V DC
ix) Thermostat for heater
x) VCB Transport trolley
xi) Spring Charging motor

G) Complete pole assemble fitted with Vaccum Interruptors.


Note:- The above prices shall be valid for 3 years from the date of opening of tenders. The
warranty period of spares like meters, relays, Vacuum Interruptors etc. shall be as
mentioned in the spec. The above mentioned spares should be same as mentioned in the
spec.& as fitted in the VCB panel.

37