Professional Documents
Culture Documents
Simplex Detector Installation-Portugal - Pt.en
Simplex Detector Installation-Portugal - Pt.en
Simplex Detector Installation-Portugal - Pt.en
com
574-709 Rev. AP
*0574709AP*
This page is intentionally blank
1 Cautions, warnings and regulatory information................................................. ................... 3
two Overview................................................ .................................................... .................................................... .. 4
2.1 Special considerations................................................. .................................................... .................................................... ..................4
2.1.1 Special considerations for smoke detectors and sensors....................................... .................................................... .............4
2.1.2 Smoke detector and sensor applications................................................. .................................................... .............................................. 4
2.2 Where to place detectors and sensors................................................. .................................................... .................................................... .4
2.2.1 Correct locations for detectors and sensors................................................. .................................................... ................................................. 4
4.5 Tone definition for sound bases 4098-9773 CO and 4098-9772................................ .................................................... ...29
ELECTRICAL RISKDisconnect electrical field power when making any internal adjustments or repairs. All repairs must be
performed by an authorized representative or agent of your local Simplex product supplier.
EYE SAFETY RISKUnder some fiber optic application conditions, the optical output of this device may exceed eye safety limits.
Do not use magnification (such as a microscope or other focusing device) when viewing the device's output.
SULFURIC ACID WARNINGThe battery contains sulfuric acid, which can cause severe burns to the skin and eyes and can
destroy tissue. Replace any leaking or damaged battery and wear appropriate protective clothing. If you come into contact
with sulfuric acid, immediately flush your skin or eyes with water for 15 minutes and seek medical attention.
FCC RULES AND REGULATIONS – PART 15This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses and radiates radio frequency energy and, if not
installed and used in accordance with these instructions, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at
his own expense.
RE-ACCEPTANCE TESTING OF THE SYSTEM AFTER CHANGES IN THE SOFTWARETo ensure proper system operation, this product must be
tested in accordance with NFPA-72 after any programming operations or changes to site-specific software. Reacceptance testing is required
after any change, addition, or deletion of system components or after any modification, repair, or adjustment to system parts or wiring. All
components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. Additionally, to
ensure that other operations are not inadvertently affected, at least 10% of trigger devices that are not directly affected by the change, up
to a maximum of 50 devices, must also be tested and proper system operation must be verified.
2 Overview
This document has information on the correct application of heat and smoke detectors/sensors in conjunction with fire alarm systems.
The information in this publication should be used as a technical guide only. Ensure that the requirements of applicable codes and
standards as well as guidelines from authorities having jurisdiction (AHJs) are followed.
To provide effective advance warning of a fire situation, install smoke detectors or sensors in all areas of the protected premises. Total
coverage, as defined by NFPA 72, includes all rooms, corridors, storage areas, basements, attics, lofts, and spaces above false ceilings,
including plenum areas used as part of the HVAC system. Additionally, this includes all closets, elevator shafts, enclosed stairwells,
elevator shafts, ramps, and other accessible subdivisions and spaces.
Fire detection systems installed to meet local codes or standards may not be adequate for early fire warning. Some codes or ordinances
have minimal objectives, such as capturing elevators or preventing smoke from circulating in HVAC systems, rather than early fire
detection.
Evaluate the costs against the benefits of installing a complete fire detection system when any detection system is being installed. The
location, quantity and zoning of detectors or sensors are determined by the installation objectives, not the minimum requirements of
any local codes or standards.
Detectors or sensors may be omitted from flammable blind spaces when one of the following conditions prevails:
• Where the ceiling is attached directly to the underside of the support beams of a roof or flammable floor.
• Where the concealed space is completely filled with non-flammable insulation. In solid joist construction, insulation only needs to fill the
space from the ceiling to the bottom edge of the roof joist or floor.
• Where there are small hidden spaces in rooms, provided the space does not exceed 50 square feet or 4.6 square meters.
• In spaces formed by sets of forward-facing beams or solid beams in walls, floors or ceilings, where the distance between the forward-
facing beams or solid beams does not exceed 6 inches or 15 cm.
Detectors or sensors may also be omitted below open grid ceilings where all of the following conditions are met:
When only one detector/sensor is required in a room or space, install the detector or sensor as close to the center of the ceiling as possible.
The central location of the detector or sensor is ideal for detecting smoke or fire anywhere in the room. If a central location is not possible,
place it no closer than 4 inches or 10 cm from the wall, or if it is listed for wall mounting, it can be wall mounted. Wall-mounted detectors or
sensors should be located approximately 4 to 12 inches or 10 to 30 cm from the ceiling to the top of the detector and at least 4 inches or 10
cm from any corner wall junction, seeFigure 1.
When a supply air opening or return air duct is present in a room or space, install detectors or sensors in the airflow path toward the
return air duct opening, seeFigure 2.
Smoke tests help determine the correct placement of detectors and sensors. Note the directions and speed of smoke travel, as these
factors can affect detector and sensor performance.
Placing a detector or sensor near air conditioning or ventilation outlets may cause excessive accumulation of dust and dirt on the
detector or sensor. This dirt can cause the detector or sensor to malfunction and cause nuisance alarms. Do not place detectors or
sensors closer than 3 feet or 0.9 meters to a supply air diffuser.
Point-type detectors or sensors in properly designed systems may also be installed in return air ducts or in approved duct detector
housings designed for this application. Although duct detectors do not replace open area detectors, they can provide an effective method
for initiating building control functions and preventing smoke from being transported from the fire area to other parts of a building.
Protection of air speed Pressure Moisture Temp. <32°F (0°C) Smoke color
detection >300 feet atmospheric > 100°F (38°C)
> 93% RH
(91.4 m)/min. 3,000 feet (914 m)
altitude above the
sea
Photograph O O X X X
Beam O O X X O
Air sampling O O X X O
* See table A-5-3.6.1.1 in NFPA 72
X = May affect detector or sensor responses
O = Generally does not affect detector or sensor responses
Do not install detectors or sensors in the following areas:
• In excessively dusty or dirty areas, such as food halls, steel plants, etc. Dust and dirt can accumulate in the detection chamber of the
detector or sensor and make it overly sensitive or block the air inlets in the detection chamber and make the detector or sensor less
sensitive to smoke. Take special care to avoid areas where fumigants, mist-producing materials, or sweeping and cleaning compounds
are used. These substances can cause nuisance alarms.
• Outdoors, in stables, open storage sheds or other open structures affected by dust, drafts, excessive humidity and temperature.
• In areas with normal or excessive humidity, or near bathrooms with showers. Water droplets can accumulate inside the detection chamber
and make the detector or sensor overly sensitive. A large amount of moist air is produced during a hot shower. Moisture from this humid
air can enter the detection chamber as water vapor and then cool and condense into droplets, causing a nuisance alarm.
• In elevator lobbies, on ashtrays or where people smoke while waiting for the elevator.
• In very cold or very hot environments, or in unheated buildings or rooms, where the temperature may fall below or exceed the operating
temperature range of the detector or sensor. At temperatures below 32°F or 0°C, ice crystals or condensation may appear inside the
detection chamber and make it overly sensitive or cause a nuisance alarm. At temperatures above the detector or sensor's operating
range greater than 120°F or 49°C, internal components may not function properly.
• In or near areas where combustion particles normally exist, such as in kitchens or other areas with ovens and burners; in garages, where
combustion particles are present in vehicle exhaust; 15 feet or 4.5 meters from any type of furnace, hot water heater or gas space
heater; or in welding shops or other types of work areas, where some form of combustion is used in the activity normally carried out in
that area. When a detector needs to be located in or adjacent to this area, a fixed temperature heat detector may be appropriate.
• In air flows passing through kitchens. Air often enters a home or residential unit in a building through cracks in the front or back doors.
If the air return is in the bedroom hallway or bathroom and if air from the kitchen easily enters the air flow past the door and into the
air return, combustion particles from the kitchen can cause nuisance alarms. Install detectors or sensors so they protect rooms but
stay out of the airflow.
• In or near manufacturing areas, battery rooms or other areas where substantial quantities of vapors, gases or vapors may be present.
Strong vapors, such as excessive humidity, can make detectors or sensors overly sensitive or less sensitive than normal. In very large
concentrations, gases heavier than air, such as carbon dioxide, can make detectors or sensors more sensitive, while gases lighter than air,
such as helium, can make them less sensitive.
Aerosol particles can accumulate on detector or sensor chamber surfaces and cause nuisance alarms.
• In insect infested areas. If insects enter the detection chamber of a detector or sensor, they can cause a nuisance alarm. Perform
insect eradication procedures before installing detectors or sensors in these locations. If spraying is part of this process, do not
allow the insect to enter detectors or sensors.
• Near fluorescent lighting. The electrical noise generated by fluorescent luminaires can cause nuisance alarms. Install detectors or
sensors at least 1 foot or 0.3 meters away from these fixtures.
• When using the CO Base for CO fire detection, do not install in locations that may have potentially high levels of CO.
Underwriters Laboratories (UL) has three standards for smoke detectors:
• One for duct detectors or sensors, UL 268A.
• One for single and multiple station detectors/sensors, UL 217.
• One for system type detectors or sensors, UL 268.
Only use detectors or sensors in applications for which they are specifically listed.
The Life Safety Code NFPA 101 states that single-station smoke detectors must trigger an alarm only within an individual living unit or similar
area and must not trigger the building's fire alarm system. . It also states: "All systems and components must be approved for the purposes
for which they are installed."
In addition to possible code non-compliance, there are the following deficiencies in a number of residential smoke detectors
connected in fire alarm system mode:
• Because the fire alarm system is unsupervised, vandals or others can disconnect a detector or the entire system, leaving a building
unprotected. In this situation, residents are unaware of the serious life-threatening condition.
• Residential detectors do not lock on alarm, the detector resets automatically. A detector in alarm activates all detectors connected
together. In this situation, after the alarm condition is cleared, it is difficult to identify or locate a specific detector that initially placed the
system in alarm.
The system's detectors or sensors lock in alarm. They do not reset until power is momentarily disconnected. This makes it easier to identify
the location of the detector or sensor that caused the control panel alarm. Additionally, the system's detectors are specifically designed to
connect to a supervised control panel. Two-wire detectors require a UL compliance review to verify that the detector and panel work
properly together.
A typical apartment complex life safety fire alarm system utilizes system detectors or sensors and manual alarm stations in hallways and
common areas of the complex, in addition to single-station residential detectors and heat detectors in each apartment. The system's
detectors or sensors, manual stations, and heat detectors are connected to a supervised control panel, sound a general alarm, and
automatically notify the appropriate authorities that a fire condition exists. Residential detectors located in apartments are interconnected
only in the individual rooms of each apartment. These residential units sound an alarm in the apartment unit only.
2.4.1 Introduction
This section describes the operation of different types of detectors and sensors. For additional information on TrueAlarm sensor operation,
see the publicationTrueAlarm Concepts(PER-91-024).
connected. The monitor zone is a supervised detection circuit connected to a main control panel that takes appropriate actions to
indicate that an alarm has been reported if the zone current increases substantially.
Heat detectors are electronic, the air temperature is detected using two thermistors with a negative temperature coefficient. The resistance
of thermistors decreases with increasing temperature. A thermistor is placed in a position that detects the temperature of the outside air
very quickly (RT1). The second thermistor is positioned in a small cavity that projects out of the main body of the detector (RT2). The RT2
location detects a rapid change in air temperature, but for a slow or medium rate of temperature change, the detector does not signal an
alarm due to the ROR feature. For a slower change in temperature, the detector signals an alarm due to a set fixed temperature that is
detected by RT1. For rapid temperature rise, when a temperature difference is detected by RT1 and RT2 reaches a predetermined amount,
the detector signals an alarm.
• Smoke detectors do not operate without power. AC or DC powered smoke detectors will not operate if the power supply is cut off for
any reason.
• They do not detect fires when smoke does not reach the detectors. Smoke from fires in chimneys, walls, roofs or on the other side of
closed doors may not reach the smoke detector or trigger the alarm.
• A detector may not detect a fire on another floor of a building. For this reason, place detectors on every floor of a building.
• Smoke detectors have detection limitations. Detectors generally do not warn of fires resulting from inadequate fire protection practices,
violent explosions, escaping gases, improper storage of flammable liquids such as cleaning solvents, other safety hazards, or arson
• Smoke detectors don't last forever. They contain electronic parts. Although detectors are designed to last for many years, any of these
parts can fail at any time. Therefore, test smoke detection systems in accordance with NFPA 72 at least annually. Clean and maintain
smoke detectors regularly. See section Compatibility and testingof this publication for cleaning instructions.
3.1.2 Specifications
Table 2: Smoke Detector Specifications
note:Where there is a possibility of positive airflow from the electrical conduit or junction box, use 3M Weatherban #606, or an
equivalent nonflammable sealing compound to seal the conduit openings.
• Do not install detectors in areas where temperatures are likely to exceed 100°F or 38°C or fall below 32°F or 0°C.
• Because the 4098-9602 detector combines heat detection, DO NOT install this detector in locations where ambient temperatures exceed
100°F or 38°C or where there are temperature fluctuations greater than 6°F per minute.
• Do not install ceiling detectors within 4 inches or 10 cm of a wall.
• Do not install detectors where forced ventilation can dilute smoke before it reaches the detector.
• Do not install detectors in areas where smoke is normally present, such as kitchens, ovens, laundry rooms, loading docks, fireplace rooms,
candle rooms, welding rooms, and so on.
• Do not install detectors in areas where vapor is likely to exist, such as in hospital patient rooms with vaporizers, near showers, above large
sinks, and so on.
• Do not install detectors above ashtrays in elevator lobbies.
• Wall detectors should be located 10 to 30 inches or 10 to 30.5 centimeters from the ceiling to the detector head.
• Protect all detector heads during construction to prevent ingress of construction debris. Remove all protective covers before activating the
system.
• If using an adapter plate, tighten the mounting screws without bending it.
• Smoke detectors should not be used with detector guards unless the combination has been evaluated and found suitable for the
purpose.
note:
• For all heat detectors, provide electronic supervision with a battery backup at the fire alarm control panel.
• Where there is the possibility of positive airflow from the electrical conduit or junction box, use 3M Weatherban #606, or an equivalent
nonflammable sealing compound to seal the conduit openings.
• Refer to NFPA 72 for application, testing and maintenance requirements.
3.2.2 Specifications
Resources
4098-9613 Fixed temperature and Normal temperature fluctuations and ceiling 21 x 21 m (70 x 70 RTI = fast 6.1 X 6.1 m
rate of increase, 57°C temperatures not exceeding 38°C (100°F) ft) (20 X 70 ft)
(135°F)
4098-9614 Temp. fixed only, Abrupt and unusual temperature fluctuations and 21 x 21 m (70 x 70 RTI = fast 6.1 X 6.1 m
93°C (200°F) ceiling temperatures exceeding 38°C (100°F) but ft) (20 X 70 ft)
not exceeding 68°C (150°F)
4098-9615 Fixed temperature and Normal temperature fluctuations and ceiling 21 x 21 m (70 x 70 RTI = ultrafast 15.2 X
rate of increase, 93°C temperatures exceeding 38°C (100°F) but not ft) 15.2 m (50 X 70 ft)
(200°F) exceeding 68°C (150°F)
CAREFUL:Install the bases in this section in accordance with applicable NFPA standards, local codes, and authorities having jurisdiction
(AHJs). Failure to follow these instructions may result in the detector not initiating an alarm condition. The manufacturer is not responsible
for detectors that have been incorrectly installed, tested or maintained.
3.3.1 Assembly
The 4098-9788 base mounts to the following electrical boxes:
Note 1:
To lock and unlock a detector or sensor on a base, perform the following steps:
1. Break the plastic lock tab to engage the lock mechanism.
2. To lock a detector or sensor to a base, rotate the unit until the locking tab clicks into place.
3. To unlock a detector or sensor, insert the blade of a screwdriver into this slot and pull the handle. Rotate and remove the detector or
sensor, seeFigure 3.
Note 2:
ConsultCompatibility and testingfor detailed information about compatible detectors. Note 3:
Bases with relay modules require a 1.5-inch or 38.1-millimeter extension ring, not supplied, to be mounted to the 4-inch square or
octagonal electrical box to meet the space requirement of the relay hub and its wires . Relay modules cannot be used in single-strip
electrical box installations. Verify that the 4098-9822 relay hub is installed in the electrical box directly behind the sensor base.
Note 4:
Use the Adapter Plate Kit, 4098-9832, when mounting the following detectors or sensors in a 4-inch or 10.16 cm square or
octagonal box:
4098-9794, 4098-9770 and 4098-9771.
For this installation only, ensure adapter plates are installed with the textured side facing the electrical box. Note 5:
4098-9775, 4098-9776, 4098-9780, 4098-9789, 4098-9791, 4098-9792 and all detector bases with flush mounting (housing to be flush-
mounted or inserted 1/4” maximum).
Note 6:
4098-9770, 4098-9771, 4098-9794 with mounting only on the recessed part (box with adapter support to be recessed or inserted 1/4”
maximum).
Note 7:
4098-9772, 4098-9773: Use the 4098-9863 adapter plate kit to mount 4098-9772 or 4098-9773 to a 4” square box.
3.3.2 Wiring
All screw terminals accommodate 14 to 18 American Wire Gauge (AWG) solid or stranded wires. When tightening the bolts, the torque
range is 8 to 12 inch pounds. Connect the wiring to the terminals shown in the following figure,Figure 4TheFigure 8show typical wiring
applications for 4098 bases.
CAREFUL:Do not wrap the wire under the terminals. Split the wire path to supervise the connections.
note:
1. Break the plastic lock tab, where indicated, to engage the lock mechanism.
2. When the locking mechanism is activated, insert a screwdriver into the indicated slot to release the detector from the base.
3. Use the slotted hole indicated for the first screw when assembling the base.
Symbol Reference
• Listed Fire Alarm Control Panel 2120
• 4001 Listed Fire Alarm Control Panel
• 4002 Listed Fire Alarm Control Panel
• 4020 Listed Fire Alarm Control Panel
• 4100+ Listed Fire Alarm Control Panel
• 4100U Listed Fire Alarm Control Panel
*
• 4100ES Listed Fire Alarm Control Panel
• 4007ES Listed Fire Alarm Control Panel
• Listed 4007ES Hybrid Fire Alarm Control Panel
• 4004 Listed Fire Alarm Control Panel
• 4005 Listed Fire Alarm Control Panel
• 4006 Listed Fire Alarm Control Panel
note:
1. If used, the 4098-9830 remote LED is biased. ConsultFigure 8to connect the remote LED to the heat detector. Note the color-coded
wiring.
2. Refer to the wiring diagrams provided with the system panel for the correct value of the end-of-line (EOL) resistor.
3. Connect separate Primary 1 and Backup 2 lines with wires in accordance with local requirements.
4. For a D-style startup circuit, connect according to the dotted lines and do not use EOL resistor.
5. Break wires before connecting to Terminal 4 to maintain supervision. Do not wrap the wire under Terminal 4.
Figure 6: 4098-9683 2-wire relay base connections for Style B or D initiating circuits
note:
1. If used, the 4098-9830 remote LED is biased. ConsultFigure 8to connect the remote LED to a heat detector. Note the color-coded wiring.
4. Connect separate Primary 1 and Backup 2 lines with wires in accordance with local requirements.
5. Aux. Relay contacts, each rated 1 A at 28 VDC / 0.5 A at 125 VAC, resistive.
note:
1. The figure shows the 4098-9830 remote LED. If used, the 4098-9830 remote LED is biased. Note the color-coded wiring. ConsultFigure 8
to connect the remote LED to the heat detector.
2. Aux. Alarm Contacts - Form C - each rated 3 A at 28 VDC/115 VAC, resistive.
3. Refer to the wiring diagrams provided with the system panel for the correct value of the end-of-line (EOL) resistor.
Figure 8: Heat Detector LED Base 4098-9684 Connections for Style B or D Startup Circuits
note:
1. The figure shows the 4098-9830 remote LED. If used, the 4098-9830 remote LED is biased. Note the color-coded wiring.
2. Connect separate Primary 1 and Backup 2 lines with wires in accordance with local requirements.
3. For a D-style startup circuit, connect according to the dotted lines and do not use EOL resistor. If it is a style B startup circuit, refer to the
wiring diagrams provided with the system panel for the correct EOL resistor value.
Smoke sensor sensitivities are set and continuously monitored by the control panel. This functionality complies with NFPA 72. When
functional testing of these sensors is required in accordance with NFPA 72, use the test methods described inCompatibility and testing.
*Fixed temperature functions are software programmed and selectable from UL temperature rating.
* * Maximum ambient ceiling temperature of 38°C (100°F) at 3,600 square feet of maximum coverage, per UL. † Maximum
ambient ceiling temperature of 38°C (100°F) at 1,600 square feet of coverage, maximum per UL.
# Maximum ambient ceiling temperature of 66°C (150°F) at 3600 square feet of coverage, maximum per UL.
2. Special application sensitivities are not for general use and may be more prone to false alarms if used in inappropriate environments.
Sources of potential nuisance include steam and particles generated by cooking. Sensors configured for a special application sensitivity
are not suitable for use in areas where kitchen appliances may be used. If cooking utensils are used within the protected space, a
normal application mode or setting for that area must be used. Environments suitable for special application sensitivity configurations
include data centers, telecommunications, and clean rooms. Inappropriate environments include kitchens and living areas.
3. The settings of 0.2%/TF, 0.5%/TF and 1.0%/TF are very sensitive:Only use the 0.2%/TF setting when a sensor is located in a
temperature-controlled, completely smoke-free environment, such as a computer room or telephone exchange
4. To determine if an area is suitable for the 0.2%/TF setting, perform the following steps:
The. Set the sensitivity of the installed sensor to 1.5%/TF.
B. Monitor peak values by90 days. If you record a spike value of 0.1%/TF or higher during the 90 days,do not use the 0.2%/TF setting.
5. To determine if an area is suitable for the 0.2%/TF setting, perform the following steps:
The. Set the sensitivity of the installed sensor to 1.5%/TF.
B. Monitor peak values by90 days. If you record a spike value of 0.25%/TF or higher during the 90 days,do not usethe 0.5%/TF
setting.
6. To determine if an area is suitable for the 1.0%/TF setting, perform the following steps:
The. Set the sensitivity of the installed sensor to 1.5%/TF.
B. Monitor peak values for 90 days. If you record a peak value of 0.5%/TF or higher during the 90 days, do not use the 1.0%/TF setting.
4.3.2 Assembly
All sensors identified in the4098 TrueAlarm Sensorshave mounting on a sensor base, seeTrueAlarm 4098 Sensor Basesfor more
information. See the information below and theFigure 3when mounting TrueAlarm sensors.
*From this point on, the 4007ES and 4007ES Hybrid panels are referred to as 4007ES.
4.4.1 Specifications
The following table contains specifications for the TrueAlarm sensor bases.
Table 8: TrueAlarm Sensor Base Specifications
Sensor Base Product ID 4098-9780 Two-Wire 4098-9789, 4098-9775 4098-9791 (with relay and 4098-9792, 4098-9776
Relay Base (w/remote LED) remote LED)
Working voltage (MAPNET II/ 24 to 40 VDC 24 to 40 VDC 24 to 40 VDC 24 to 40 VDC
IDNet)
24 V working voltage — — 18 – 32 VDC —
(relay or sounder power)
Sensor Base Insulator Bases 4098-9793, 4098-9794 (sound base) 4098-9770 (base 4098-9771 (base 4098-9772
Product ID 4098-9777 of the sensor CO sound) (sound base);
CO) 4098-9773 (Base
CO sound)
working voltage 24 to 40 VDC 24 to 40 VDC 24 to 40 VDC 24 to 40 VDC 24 to 40 VDC
(MAPNET II/IDNet)
working voltage — 18 – 32 VDC — 18 – 32 VDC 16 – 32 VDC
24 V (relay
or power of
sounder)
MAPNET current 500 µA 400 µA 450 µA 500 µA 400 µA
II/IDNet* (4098-9772) 500
µA (4098-9773)
current — 270 µA — 270 µA 270 µA
standby
24V (relay or
sounder)
current — 17 mA — 17 mA 520Hz: 115mA a
24V (relay or 18 VDC 129 mA
sounder 16 VDC band
activated) wide: 125mA
18 VDC 139 mA
16 VDC
LED output — Yes — Yes Yes
Exit from — 88 dBA minimum — 88 dBA, at see the
sounder Minimum observation 1
* Current MAPNET II/IDNet with a photo sensor connected to the base
note:
1. Sounder output 4098-9772 - low frequency alarm: 86 dBA according to UL268; 80 dBA according to UL464; broadband: 87 dBA according
to UL268; 81 dBA according to UL464.
2. CO sounder output 4098-9773 - low frequency alarm: 85.5 dBA in accordance with UL268 and UL2034; 79.5 dBA according to UL464;
broadband: 87 dBA according to UL268 and UL2034; 81 dBA according to UL464.
Figure 10: Location of DIP switches for sensor bases 4098-9770, 4098-9771, 4098-9772, 4098-9773 and 4098-9794
note:The 4098-9771, 4098-9772, 4098-9773 and 4098-9794 sound bases have a 9-position DIP switch. The first eight DIP switches define the
address of the sound base. DIP switch position 9 is set to OFF or ON, depending on the sound base power source. When the sound base is
connected to a 24 VDC power source, DIP switch position 9 is set to “OFF” and the 24 VDC power is supervised by the sound base. When the
sound base is powered by the panel's notification device circuit (NAC), DIP switch position 9 is set to “ON” and power is supervised by the
NAC and not the sound base. 9770 has the same layout but does not have sounder functionality.It uses an 8-way DIP switch only.
4.4.4 Address configuration for system 4010, 4020, 4100+, 4100U, 4100ES, 4010ES,
4007ES, 4008, or 4120
1. Using the Programmer Report, find the entry for the sensor base you are installing. The device ADDRESS and CUSTOM LABEL are
located on the SYSTEM POINT SUMMARY at “M”. For example, the address M1-7 is circled on theFigure 12. M1 is the addressable
channel and “-7” is the device address on the channel. For a base with Address M1-7, verify that Address 7 is set on the base's DIP
switches (SW1).
2. Using the example provided in Step 1 as a guide, set the address on the base using the information inFigure 13. Consult Setting the base
addressto obtain the location of the DIP switches. Use a non-metallic stylus pen or equivalent to adjust the switches.
3. Mark an address label with the appropriate address for the base by shading a label box for each base DIP SWITCH in the ON
position. Apply the label near the DIP SWITCH on the base.
4. Double check the location and address of the sensor base before proceeding to electrical installation.
Figure 11: Programmer 4020 Report
Figure 12: Programmer Report 4100+, 4100U, 4100ES, 4010ES, 4007ES, 4120, 4008 or 4010
The following figure shows the DIP SWITCH settings. ConsultCompatibility and testingto obtain the compatibility information of various
FACPs.
note:The 4020, 4100+, 4100U, 4100ES, and 4120 systems support up to 127 devices on each MAPNET II channel. The 4010, 4100U, 4100ES, 4010ES, and
4007ES support up to 250 devices on the IDNet channel. The 4008 supports up to 200 devices on the IDNet channel.
4.4.5 Wiring
The sensor bases are connected to the fire alarm control panel using a single pair of wires for 4098-9770, 4098-9775, 4098-9776,
4098-9777, 4098-9780, 4098-9789, 4098-9792 and 4098 -9793 and two pairs of wire for 4098-9771, 4098-9772, 4098-9773, 4098-9791
and 4098-9794.
UsingFigure 14For reference, connect the bases to the MAPNET II/IDNet wire pair and 24V power, if used.
Important:For additions to existing installations, remove power from the panel before connecting any bases to prevent damage to the
equipment.
note:
1. If the 2098-9808 remote LED or 4098-9822 relay is used, the remote LED and relay wires are not supervised.
2. The maximum number of devices on a circuit is 127 for 4020, 4100+, 4100U/4100ES/4010ES (MAPNET) or 4120, 128 for the CDT 2120
panel, 200 for the 4008 panel and 250 for the 4010 and 4100U panel /4100ES/4010ES/4007ES (IDNET).
3. If a shield is used, wrap the shield wires together and secure them with a twist-on connector. Isolate the electrical box shield.
4. Contact A or B: Dry, Form “C” - each rated at 2 A at 24 VDC / 0.5 A at 110 VAC, resistive.
5. 18 to 32 VDC, 0.008 A typical, 0.013 A maximum.
6. Do not use a remote LED when using the 4098-9822 relay module.
7. Contact A or B: Dry, Form “C” - each rated at 3 A at 28 VDC/115 VAC, resistive.
8. Remove the protective tape over the CO sensor on the 4098-9770, 4098-9771, 4098-9773 bases only after the sensor head has been
installed.
9. The maximum wire length between the 4098-9791 sensor base and the 2098-9737 relay module is 100 feet or 30.48 meters.
10. The maximum number of sensors with sound bases 4098-9771, 4098-9772, 4098-9773, 4098-9794, 4098-9795, 4098-9798 is limited
to 43, if the output is coded, with time coding, and so on, using the MAPNET II/IDNet control. If coding is performed with a NAC or
24 VDC circuit, see note 2.
11. Maximum line resistance between panel and insulator, or between two insulators, is 10 ohms, 780 feet or 237.74 meters at 18 AWG.
12. Dry contacts, Form “C”, rated at 2 A at 30 VDC / 0.5 A at 125 VAC, resistive.
13. The maximum wire length between the 4098-9780 sensor base and the 4098-9860 relay module is 100 feet or 30.48 meters.
Figure 15shows the wiring connections for the isolator sensor base. All screw terminals accept 14 to 18 AWG gauge solid or stranded
wire. Verify that maximum torque does not exceed 12 inch-pounds.
CAREFUL:Do not wrap the wire under the terminals. Divide the walkway to provide supervision.
note:
1. Isolator base is only compatible with 4010, 4100U, 4100ES, 4010ES, 4007ES, or 4008 panels.
2. The maximum number of devices on a circuit is 250 for 4010, 4100U, 4100ES, 4010ES and 4007ES panels.
3. If shielding is used, wrap the shielding wires together and secure them with a twist-on connector. Isolate the electrical box shield.
4. Maximum line resistance between panel and insulator, or between two insulators, is 10 ohms (780 feet or 237.74 meters at 18 AWG).
ATTENTION:During installation, you may be exposed to live circuits, therefore, attention is required to ensure personal safety and
prevent damage to the product.
Model Name
4098-9747 10 Year CORC Replacement
4098-9770 10 Year SSD CO Sensor Base
4098-9771 10-year CO SSD soundbase
Expired CORC Removal
1. Remove the sensor head, not shown, and set aside for later reinstallation.
2. Insert a thin-bladed screwdriver into the slot as shown below.
Figure 16: Inserting a thin-blade screwdriver
3. Carefully release the CORC from the sensor base by pushing it inwards. Don't force it. Remove CORC and discard
Figure 17: Removing the CORC from the sensor base
3. Gently rotate the CORC inward until it clicks into place on the SSD CO sensor base.
4. Reinstall the detector head.
5. Remove the CORC dust cover as shown in the following figure.
6. CORC replacement is complete.
Figure 18: Installing the replacement CORC
note:The fire alarm panel must be set to the correct date. Otherwise, a false CORC end-of-life issue may be announced.
Figure 19: Tone definition for the 4098-9772 and 4098-9773 CO sound base
5 Accessories
This section contains information about relay module accessories.
note:
note:
1. Maximum wire length between 4098-9780 sensor and relay module is 100 feet.
2. Dry contact, Form “C”, rated at 2 A at 30 VDC / 0.5 A at 125 VAC, resistive.
note:
note:
1. Relay operation cannot be guaranteed unless it is the only device in that zone.
2. The panel compatibility identification marker is the model number of the module or panel.
3. The detector compatibility identification marker is the model number found on the detector label.
4. For detailed interconnection data, refer to specific panel wiring diagrams.
5. For additional compatibility listings, see document 579-832, Two-Wire Detector Compatibility Chart.
note:
6.3.1 Maintenance
The minimum requirement for maintenance of detectors and sensors includes cleaning the surface from dust using a vacuum cleaner.
Ensure cleaning programs comply with NFPA and local environments. Ensure that the internal chamber is cleaned only by a qualified
technical representative.
For maintenance, return them to your local branch.
6.3.2 Test
Smoke sensor sensitivities are set and continuously monitored by the control unit. Dirty or out-of-range sensors are announced by the
control unit. This functionality complies with NFPA 72.
note:When testing detectors or sensors, refer to NFPA 72 or contact your local branch.
CAREFUL:Before functionally testing detectors or sensors, disconnect the city connection, releasing extinguishing devices and systems. For
the 4120, 4006, 4008, 4020, 4010, 4100+, 4100U, 4100ES, 4010ES, or 4007ES panel, place the panel in WalkTest mode.
• Solo red cup (709-024). Use to hold aerosol spray can 553-635.
• Solo adapter (708-021) for Solo speakers. Use to adapt the 553-760 Test and Removal Tool to the Solo column.
• TrueTest 801, sensitivity testing equipment for smoke detectors.
• Smoke 400, smoke aerosol for TrueTest.
• Testifire 2000-024, smoke, heat and CO detector tester.
• Testifire 2001-024, smoke, heat and CO detector test kit (includes 2 battery sticks and
• AC/DC charger).
• TS3-024 Smoke Capsule, for use with the Testifire smoke, heat and CO detector tester.
• TC3-024 CO Capsule, for use with smoke, heat and CO detector tester.
note:The TrueTest 801 or Testifier 2000-024 are the only testers for use with the 4098-9770 and 4098-9771 bases.
detector. The following are descriptions of the detector when it is in MAG TEST:
• NORMAL-When in MAG TEST, the detector locks in alarm if the detector is within the calibration range and the visible LED remains
lit.
• MORE SENSITIVE(MORE SENSITIVE) - In MAG TEST, if the detector is more sensitive than the maximum calibration, the visible
LED flashes quickly, twice per second. After flashing six times, the detector locks into alarm and the visible LED remains lit.
• LESS SENSITIVE(LESS SENSITIVE) - In MAG TEST, if the detector is less sensitive than the minimum calibration, the visible LED
flashes slowly four times, once every two seconds. After flashing four times, the detector locks into alarm and the visible LED
remains lit.
• NON-FUNCTIONAL DETECTOR(NON-FUNCTIONAL DETECTOR) - If the detector is less sensitive than the minimum allowable sensitivity or
if there is a failure in the temperature sensing circuit (4098-9602), the visible LED will not flash normally. When in MAG TEST, the visible
LED slowly flashes four times, once every two seconds. After flashing four times, the detector does NOT lock into alarm, the LED stops
flashing and turns off.
If the detector is outside the normal operating range, clean it. If the detector still indicates abnormal sensitivity after cleaning, replace
the detector.
The following two operations to inform a qualified or trained person that a CO sensor has reached its end of life:
• The Fire Alarm Control Panel (FACP) generates a fire alarm problem.End of Life(End of life) notifying the user that a replacement sensor
is required.
• Manual standard maintenance testing by a qualified or trained technician verifies that the device is fully operational.
The TrueAlarm CO report can also be used to list all end-of-life dates for CO sensors on the dashboard. The report is a quick and easy way to
check if any sensors will expire before your next site visit.
Figure 27: Simultaneous testing note:The LED on the base may be turned ON, before flashing,
of multiple sensor technologies depending on when the individual sensors alarm is sounded. Only
the last requested LED will flash slowly. All others will be stable ON.
The LED blink test will only be performed when the IDNET CO
algorithms are disabled for testing. During WalkTest, a reset timer is
activated so that the LED resets to the OFF state without requiring a
panel reset. This reset is user programmable and can be as short as
15 seconds. This automatic reset may cause the LED on the base to
turn OFF before the test is complete. For example, it is possible that,
depending on the test tool, the LED (if all sensors are working well)
may turn ON, then reset to OFF twice, and finally flash and be reset
to OFF.
note:
The LED states are described below:
6.3.11 Cleaning
Introduction
If the sensitivity of the device does not match what is marked on the device label, clean the device using a source of compressed, oil-free,
filtered air such as Dust-Off or Tech Duster, etc.
CAREFUL:Notify appropriate building personnel before removing any detector or sensor from service.
A "Smoke Sensor is Excessively Dirty" trouble condition is reported when the average value at an individual sensor reaches a value slightly
higher than the defined threshold. At this point, the FACP no longer compensates for environmental factors, and the level of sensitivity
varies. Although an “Excessively Dirty” problem is reported, the sensor continues to operate and reports an alarm condition when one is
detected.
In addition to the two automatic trouble conditions, FACPs have digital pseudopoints that must be ON for a TrueAlarm sensor that is
close to being a dirty sensor to report as being "almost dirty." This is useful when scheduling maintenance for dirty sensors as it
provides a means of checking whether other sensors are approaching a dirty state.
The following table shows the appropriate actions to take when certain indications of problems occur:
Table 15: TrueAlarm Problems and Descriptions
Expired The Fire Alarm Control Panel (FACP) generates a problem notifying the user that a replacement
sensor is required. To resolve the issue, install a new CORC with a valid date and perform a FACP
hard reset.
The panel automatically indicates when a sensor is out of sensitivity calibration. If the sensor has an analog value below that
listed in the table, the sensor is within the sensitivity setting.
Type Almost dirty Dirty Excessively dirty
Photograph 115 120 135
To view the analog value of a sensor, refer to the FACP operating instructions.
© 2023 Johnson Controls. All rights reserved. All specifications and other information presented were current as of the document revision date and
are subject to change without notice. Other listings may apply, please contact your local Simplex® supplier for the latest status. Listings and approvals
relating to Simplex Time Recorder Co. Simplex and product names listed in this material are trademarks or registered trademarks. Unauthorized use is
strictly prohibited. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
574-709 Rev. AP