Professional Documents
Culture Documents
9ARD171384-600 - en System 800xa 6.0 IEC 61850 Engineering Workflow
9ARD171384-600 - en System 800xa 6.0 IEC 61850 Engineering Workflow
9ARD171384-600 - en System 800xa 6.0 IEC 61850 Engineering Workflow
IEC 61850
Engineering Workflow
System Version 6.0
ABB may have one or more patents or pending patent applications protecting the intel-
lectual property in the ABB products described in this document.
The information in this document is subject to change without notice and should not be
construed as a commitment by ABB. ABB assumes no responsibility for any errors that
may appear in this document.
In no event shall ABB be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB be
liable for incidental or consequential damages arising from use of any software or hard-
ware described in this document.
This document and parts thereof must not be reproduced or copied without written per-
mission from ABB, and the contents thereof must not be imparted to a third party nor used
for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license. This
product meets the requirements specified in EMC Directive 2004/108/EC and in Low Volt-
age Directive 2006/95/EC.
TRADEMARKS
All rights to copyrights, registered trademarks, and trademarks reside with their respec-
tive owners.
Section 1 - Introduction
Objective..........................................................................................................................17
Classification ...................................................................................................................17
9ARD171384-600 5
Table of Contents
Index
6 9ARD171384-600
About This User Manual
Any security measures described in this User Manual, for example, for user
access, password security, network security, firewalls, virus protection, etc.,
represent possible steps that a user of an 800xA System may want to consider
based on a risk assessment for a particular application and installation. This risk
assessment, as well as the proper implementation, configuration, installation,
operation, administration, and maintenance of all relevant security related
equipment, software, and procedures, are the responsibility of the user of the
800xA System.
This user manual describes the IEC 61850 (Ed1) Engineering Workflow in 800xA.
The intention is to execute typical engineering use cases which the user may come
across while implementing the actual engineering. This manual provides a step-by-
step procedure to engineer Substation Automation (SA) and Process Automation
(PA) in an integrated manner. This manual also provides the rules and guidelines for
the engineering workflow.
This manual:
• Provides a guaranteed and optimized solution to perform IEC 61850 (Ed1)
Engineering Workflow in 800xA.
• Concentrates on the following ways to perform the IEC 61850 (Ed1)
Engineering Workflow in 800xA.
– Simplified workflow with CCT600 or IET600 Tool
The main topics covered in this manual are:
• Overview of IEC 61850 (Ed1) Engineering with 800xA.
• Substation Engineering Workflow.
• Maintenance.
9ARD171384-600 7
Assumption About This User Manual
Assumption
In this manual, user works with different tools with respect to Substation
Automation and Process Automation. This manual helps the user to understand the
usage of these tools in an integrated manner to perform complete IEC 61850 (Ed1)
Engineering.
It is assumed that the user has undergone a suitable training program and has the
working knowledge of tools. For example, Control Builder/CCT, IET600 and PCM
600 should be known to SA engineer and 800xA to plant engineer.
8 9ARD171384-600
About This User Manual Exclusions
It is also expected that the user has an adequate understanding of IEC 61850 (Ed1)
standard and different abbreviations such as SCD, CID, ICD, GOOSE, MMS, and
IED.
Exclusions
This user manual does not cover the basic installation and configuration of 800xA
and other associated tools that contribute to the workflow.
Methodology
The user should execute the following engineering use cases in a structured manner:
• Complete Substation Engineering use case is executed based on an actual
customer project. The procedure starts with normal inputs from the customer
and ends with a completely configured substation with respect to Substation
Automation and Process Automation.
• Maintenance use cases such as addition/deletion of IEDs, signal change
through GOOSE and MMS, addition/deletion of Logical Nodes, and change of
faulty IED with new one.
• Modifying use cases such as change in IED name, IP address, change in LN
name, change in tag name for primary equipment, and alarm severity
modification.
• Complex use cases such as redundancy handling and multiple subnetworks in
one SCD.
• Other use case such as handling of special IEDs. For example, REF541,
REF542+, REF500 and 3rd party IEDs.
9ARD171384-600 9
Feature Pack About This User Manual
Feature Pack
The Feature Pack content (including text, tables, and figures) included in this User
Manual is distinguished from the existing content using the following
two separators:
Feature Pack Functionality______________________________________________________________________
Unless noted, all other information in this User Manual applies to 800xA Systems
with or without a Feature Pack installed.
Warning icon indicates the presence of a hazard that could result in personal
injury.
Caution icon indicates important information or warning related to the concept
discussed in the text. It might indicate the presence of a hazard that could result
in corruption of software or damage to equipment/property.
Information icon alerts the reader to pertinent facts and conditions.
Tip icon indicates advice on, for example, how to design your project or how to
use a certain function
10 9ARD171384-600
About This User Manual Terminology
Although Warning hazards are related to personal injury, and Caution hazards are
associated with equipment or property damage, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
fully comply with all Warning and Caution notices.
Terminology
A complete and comprehensive list of Terms is included in the System 800xA,
Engineering Concepts instruction (3BDS100972*). A complete and comprehensive
list of terms is included in System 800xA System Guide Functional Description
(3BSE038018*). The listing includes terms and definitions that apply to the 800xA
System where the usage is different from commonly accepted industry standard
definitions and definitions given in standard dictionaries such as Webster’s
Dictionary of Computer Terms. Terms that uniquely apply to this User Manual are
listed in the following table.
Term/Acronym Description
800xA ABB automation system (eXtended Automation).
AC 800M ABB Controller 800M series, general purpose process
Controller series by ABB.
AC 800M Controller Any Controller constructed from the units and units
connected to the AC 800M hardware platform.
AE Alarm and Event.
Append Function for creating objects (based on object types) in
the 800xA Control Structure.
CCT Communication Configuration Tool.
CDC Common Data Class, is a Data Type definition in
IEC61850.
CDC Block CDC representation in Control Builder M Project
Explorer.
CET Communication Engineering Tool.
9ARD171384-600 11
Terminology About This User Manual
Term/Acronym Description
CID Configured IED Description file.
CI868 Module CI868 module for IEC 61850 (Ed1). Communication
Interface Module for AC 800M controller. These modules
are connected over the CEX bus and contain
implementation of a specific communication protocol.
Control Builder M Controller Builder M (Control Builder Professional or
Compact Control Builder).
DA Data Access / Data Attribute.
DO Data Object
FBD Feeder Block Diagram.
FB Function Block
GOOSE Generic Object Oriented Substation Event. Based on the
VLAN and priority tagging, GOOSE is used for very fast
peer-to-peer data exchange between IEC 61850 (Ed1)
compliant IEDs, also termed as Horizontal
Communication.
GCB GOOSE Control Block.
HMI Human Machine Interface.
I/O Input and Output.
ICD IED Capability Description. A type of SCL file.
IEC International Electrotechnical Commission.
IEC 61850 (Ed1) IEC standard for Communication Networks and Systems
in Substations.
12 9ARD171384-600
About This User Manual Terminology
Term/Acronym Description
LD Logical Device: A virtual device which enables
aggregation of Logical Nodes and Datasets for
communication purposes. Additionally, Logical Devices
contain convenient lists of frequently accessed or
referred to information. For example, datasets.
LN Logical Node.
MMS Manufacturing Message Specification (MMS) is an
international standard (ISO 9506) dealing with
messaging system for transferring real time process data
and supervisory control information between network
devices and/or computer applications.
Node A computer communicating on a network, for example
the Internet, Plant, Control or IO network. Each node
has a unique node address with a format depending on
the network it is connected to.
OCS Open Control System.
OPC OLE for Process Control. A set of standard interfaces
based on COM technology.
OT Object Type, object template in Object Type Structure in
800xA.
PA Process Automation.
Plant Explorer Process Portal A.
PGS Power Generation Solutions.
PMS Power Management Solutions.
RCB Report Control Block.
Retrieve Function for collecting information regarding a control
network.
SA Substation Automation.
SBO Select Before Operate Command
9ARD171384-600 13
Released User Manuals and Release Notes About This User Manual
Term/Acronym Description
SCD Substation Configuration Description, type of SCL file.
SCL Substation Configuration Language.
SLD Single Line Diagram.
Upload Retrieve + Append.
XML eXtensible Markup Language.
14 9ARD171384-600
Section 1 Introduction
9ARD171384-600 15
Section 1 Introduction
8 0 0xA Pl a nt N e t w or k
Aspe c t Se r ve r
+
I EC 6 1 8 5 0 CS
+
AC8 0 0M CS
8 0 0xA Cont r ol N e t w or k
CI 8 6 8 PM8 xx
I EC 6 1 8 5 0 MMS
Subst a t i on
I EC 6 1 8 5 0 Ri ng N e t w or k
I ED De vi c e s
Subne t w or k
16 9ARD171384-600
Section 1 Introduction Objective
Objective
In general, the implementation of 800xA-IEC 61850 (Ed1) integration program
shall comprise of the following:
1. IEC 61850 (Ed1) Client/OPC Server implementation in Connectivity Server
for connectivity between IEC 61850 (Ed1) compliant Protection and Control
IEDs and 800xA Aspect Servers.
2. IEC 61850 (Ed1) Communication Interface in AC 800M (through CI868
module).
3. Implementation of an IEC 61850 (Ed1) Configuration environment that works
in tandem with Control Builder.
Classification
The following is the classification of the workflow for IEC 61850 (Ed1) integration
in System 800xA:
1. Substation Engineering
– Exporting CI868 IED file from Control Builder
– Exporting other IED file using PCM600
– Creating SCD file using IEC 61850 (Ed1) engineering tools such as ABB
CCT600 and ABB IET600.
– Updating IED configuration with SCD file
– IED application logic building and CID file generation for ABB-IEDs
using PCM 600 or third party vendors having their own IED specific
device configuration tools.
– CI868 IED Engineering with Control Builder M
2. 800xA Engineering
– OPC Server configuration for MMS using the CET tool.
– Object type creation using the 800xA Uploader.
9ARD171384-600 17
Classification Section 1 Introduction
CI 8 6 8 I ED Engi ne e r i ng
Cont rol Builder
Expor t CID /ICD Fi l e
Confi gur e CI868 IED Templ ate + Impor t CID Fi l e Subst at ion Conf igurat ion Communicat ion Conf igurat ion
Impor t CID Fi l e
Substati on Str uctur e
I ED Appl i c a ti on Engi ne e r i ng Data Set Confi gur ati on
Si ngl e Li ne di agr am
Assi gn LN to Conducti ve Equi pment
PCM 600 Stati on Confi gur ati on Di agr am
RCB Confi gur ati on
Expor t IED Confi gur ati on Feeder Bl ock Di agr am GCB Confi gur ati on
Ex
po
rt
SC
D
Fil
e
18 9ARD171384-600
Section 1 Introduction Classification
Plant Explor er
Impor t SCD Fi l e
Confi gur ati on
IEC 61850 OPC Ser ver
IEC 61850 Al ar ms & Events
Impor t SCD Fi l e +
Impor t SCD Fi l e
Downl oad CI868 Confi gur ati on
i nto AC 800M Contr ol l er
9ARD171384-600 19
Classification Section 1 Introduction
20 9ARD171384-600
Section 2 Substation Engineering
This section explains the simplified 800xA IEC 61850 (Ed1) Engineering Workflow
for substation automation based on bottom-up approach of substation engineering.
This workflow approach adapts CI868 as an IED and user can define the CI868 IED
by configuring associated LDs and LNs within Control Builder hardware tree
structure and export it as CID / ICD file.
The new workflow supports export of multiple CID / ICD files, one for each
configured CI868 IED and also supports import of one SCD file per CI868.
IEC 61850 (Ed1) Wizard handles one SCD file per CI868 board for a complete
configured substation, enabling the user to have flexible and distributed engineering
to work on different SCD files.
The process of workflow for substation engineering begins with the creation of CID
/ ICD file for CI868 in the Control Builder. The CI868 ICD file along with the ICD /
CID files of other IEDs and OPC Server are imported into IET600 / CCT 600 or any
other third party tool to perform communication engineering for GOOSE and MMS
mapping and generate a configured SCD file.
The configured SCD file is then imported into,
• Control Builder using IEC 61850 Wizard tool and downloaded to CI868 IEC
61850 communication interface (IED) controller after IO channel assignment
and application engineering.
• CET tool for configuring IEC 61850 (Ed1) OPC server Alarm and Events and
for vertical communication with IEDs.
• 800xA by Uploader to instantiate objects in 800xA Control Structure and
Functional Structure using the information from SCD file.
• PCM600 tool only for ABB IEDs or respective IED Engineering Tool for
downloading the configuration to the corresponding IED.
9ARD171384-600 21
Inputs Required Section 2 Substation Engineering
With the new Engineering Workflow, the use of IET-CCT tool is not required.
The following sub sections describes the steps to perform IEC 61850 (Ed1)
Engineering Workflow:
1. Configuring CI868 IED on page 32
2. Configuring other IEDs on page 57
3. Substation Communication Engineering in CCT600 / IET600 on page 83.
a. Communication Engineering using CCT600 on page 83.
b. Communication Engineering using IET600 on page 119.
4. Updating IED configuration with SCD file on page 160
Application Engineering of IED is not required if the IED is preconfigured from
the vendor as per requirement. IED CID file can be created from the
configuration present in IED.
5. CI868 IED Engineering with Control Builder M on page 168
6. IEC 61850 Connect Engineering on page 221
Inputs Required
This section describes the inputs required before starting 800xA IEC 61850 (Ed1)
Engineering.
Project Inputs
Following project inputs required Before starting 800xA IEC 61850 (Ed1)
Engineering:
1. Single Line Diagram.
2. Functionalities such as protection and control, and interlocking functions. The
functionality can be a device function number according to IEEE. The IEC
61850 (Ed1) offers the concept of logical nodes (LN) for formally defining
functions.
3. Constraints such as the existing network and the geographical situations onsite.
4. Preconfigured CID file for OPC server
22 9ARD171384-600
Section 2 Substation Engineering ABB Engineer or Project Inputs
9ARD171384-600 23
Sample Inputs with Signal List Section 2 Substation Engineering
I _ S LA 1
C B _ L5 R I _ S LB 1
MBI101
MBI102
TR 1 _ 1 1 0 3 3
I _ S LB 2
MP_107 M
B 1 _ L4
24 9ARD171384-600
Section 2 Substation Engineering Sample Inputs with Signal List
Table 2 lists the customer identified IEDs to be used for this Bay.
Sl.
IED Name IED Type Vendor Purpose Remark
No.
1 BC101(1) REC670 ABB Bay Protection and Control Preconfigured IED
9ARD171384-600 25
Sample Inputs with Signal List Section 2 Substation Engineering
Sl.
IED Name IED Type Vendor Purpose Remark
No.
2 TC102(1) RET670 ABB Transformer Protection and Preconfigured IED
Control
3 PC103 CI868 ABB DCS command, control and CI868 as an IED
Report handling Type
(1) Typically the naming convention for IED Name in real time environment is, Substation>Voltage>Bay+ IED Name. In
this document, for illustration purpose, only the IED Name is used. For example: BC101(for REC_670 IED Type),
TC102 (for RET_670 IED Type).
1 0 . 1 4 0 . 4 3. 1 1 0 OP C 1
1 0 . 1 4 0. 4 3 . 1 0
1 0 . 1 4 0. 4 3 . 5 1 10.140.43.52
P C103
B C1 0 1 TC 1 0 2
26 9ARD171384-600
Section 2 Substation Engineering Sample Inputs with Signal List
Table 3 lists the GOOSE signals that are used for Interlocking and Protection.
Table 4 Lists the MMS Signals that are used for Control and Measurements.
9ARD171384-600 27
Sample Inputs with Signal List Section 2 Substation Engineering
28 9ARD171384-600
Section 2 Substation Engineering Sample Inputs with Signal List
9ARD171384-600 29
Sample Inputs with Signal List Section 2 Substation Engineering
30 9ARD171384-600
Section 2 Substation Engineering Tools Required
Tools Required
Following tools are required for 800xA IEC 61850 (Ed1) configuration and
planning:
• Control Builder M (Compact / Professional)
• ABB IET600 or ABB CCT600 Tool
• PCM600 for ABB IEDs
• CET for IEC 61850 OPC Server
• 800xA Uploader for SCD file upload
9ARD171384-600 31
Configuring CI868 IED Section 2 Substation Engineering
32 9ARD171384-600
Section 2 Substation Engineering Configuring CI868 IED
2. Enter the name of the project in the Name field and click Ok.
The Control Builder project name is independent of any parameter such as CI868
IED or AC 800M IED description or Substation name in SCD file.
9ARD171384-600 33
Configuring CI868 IED Section 2 Substation Engineering
34 9ARD171384-600
Section 2 Substation Engineering Configuring CI868 IED
4. Right-click... and select Insert Unit from the context menu of 'Hardware
AC800M'. The Insert Unit appears.
9ARD171384-600 35
Configuring CI868 IED Section 2 Substation Engineering
5. Select the Unit and select the CI868 position in Position option.
Figure 12 shows the CI868 object in the Control Builder tree structure after
insertion.
36 9ARD171384-600
Section 2 Substation Engineering Configuring CI868 IED
6. Double-click CI868 object in tree view to open the CI868 IED Editor and set
the communication parameters for the CI868 Access Point.
9ARD171384-600 37
Configuring CI868 IED Section 2 Substation Engineering
7. Right-click CI868 object and select Insert Unit from the context menu.
Renaming of CI868, MyIED, IED, LD and Send LN's objects are disabled.
38 9ARD171384-600
Section 2 Substation Engineering Configuring CI868 IED
8. In the Insert Unit for CI868, select MyIED and click Insert.
The IED object displayed represents other IEDs in the SCD file. This must not be
selected, as it does not represent the CI868 IED. Only MyIED object must be
selected.
a. Double-click MyIED object to open the MyIED editor and configure
MyIED name in Settings Tab. Replace the default value (CI868IED).
9ARD171384-600 39
Configuring CI868 IED Section 2 Substation Engineering
40 9ARD171384-600
Section 2 Substation Engineering Configuring CI868 IED
9ARD171384-600 41
Configuring CI868 IED Section 2 Substation Engineering
LD Name value must be unique (among LDs objects within CI868 object) and
must not contain space or other special characters ({, _ is allowed).
Wizard displays an error message Configuration invalid at LD node(s) and export
operation is stopped.
42 9ARD171384-600
Section 2 Substation Engineering Configuring CI868 IED
12. Right-click LD object and select Insert Unit to open Insert Unit for LD.
Logical Nodes library with all supported LNs are listed as shown in Figure 22.
9ARD171384-600 43
Configuring CI868 IED Section 2 Substation Engineering
13. Insert the mandatory logical nodes LN0 followed by LPHD. Similarly insert
other required Logical Nodes under LD, by providing the position.
It is mandatory to position the logical node LN0 first, then LPHD logical node
and followed by other required logical nodes in the Control Builder hardware tree
structure.
In case LN0 nodes is not positioned first, IEC61850 Wizard will automatically
position the LN0 node first.
In the IEC 61850 subnetwork, the logical node ITCI under CI868 represents and
activates CI868 as MMS Client.
44 9ARD171384-600
Section 2 Substation Engineering Configuring CI868 IED
14. The selected LNs are listed in the Tree View as shown in Figure 23.
The configuration of CI868 is automatically stored as part of Control Builder
project.
Logical Nodes QC1 ARCO and VC1 AVCO are newly introduced logical nodes
that are same as previously existing QC ARCO and VC AVCO, but contains
corrected names of Data Objects in IO channels as per IEC 61850 (Ed1)
specification 7-4 for AVCO and ARCO.
9ARD171384-600 45
Configuring CI868 IED Section 2 Substation Engineering
By default the LN name field is blank. The LN name field must be configured
with an appropriate name, else an error message is displayed during export of
CID file. Following parameters must be considered while configuring the LN
Name:
• LN name field cannot be blank.
• LN name must not contain special or space character ({, _ is allowed).
• For LN0, the LN name must be LLN0.
• For LPHD and ITCI, the LN name must be LPHD<Instance Num> and
ITCI<Instance Num>, where Num can range from 1 to 253.
• The naming of other LNs must be in the following format:
<LN Prefix><LN Class Name><LN Instance Num>
For example: <LS><GAPC><1>. The LN instance Num should be within the
range of 1 to 253.
• The LN name must be unique within an LD.
This completes the configuration of CI868 module in Control Builder.
If required, repeat Step 6 through Step 15 to configure multiple CI868 Access
Points (Maximum of 12 CI868 are allowed per AC 800M / Redundant
Controller).
46 9ARD171384-600
Section 2 Substation Engineering CI868 CID File Export using IEC 61850 Wizard
9ARD171384-600 47
CI868 CID File Export using IEC 61850 Wizard Section 2 Substation Engineering
To view all the messages generated by IEC 61850 Wizard, right-click IEC
61850 Wizard and select View Log. List of all logs generated during export is
displayed in the IEC 61850 Wizard Window.
The logs can also be viewed by opening the IEC 61850ImportWizard.log located
in installed folder.
For Compact Control Builder: C:\ABB Industrial IT Data\Engineer IT
Data\Compact Control Builder AC 800M\LogFiles\Importwizard.log.
For Control Builder Professional: C:\ABB Industrial IT Data\Engineer IT Data\
Control Builder M Professional\LogFiles\Importwizard.log.
3. In the File Path, click Browse to locate the destination folder for CID file.
48 9ARD171384-600
Section 2 Substation Engineering CI868 CID File Export using IEC 61850 Wizard
CID file name is generated in the following format. User can modify the file if
required.
CI868_n_IEDName_TimeStamp.cid
– n is the instance of CI868 where the IEC wizard is invoked.
– IEDName is read from MyIED name parameter of MyIED hardware unit
in Control Builder.
– TimeStamp is the system date and time. The timestamp will be in the
DD-MM-YYYY HH-MM-SS format.
9ARD171384-600 49
CI868 CID File Export using IEC 61850 Wizard Section 2 Substation Engineering
The File Revision and Version settings are generated while exporting the CID
file. These values can be edited or updated every time the CID file is exported
from Control Builder, with a new version and revision.
While exporting as CID file, IEC61850 Wizard checks for the last imported SCD
file to retain the configured Data Sets and GCBs. For more information on
retaining the Data Sets and GCBs, refer to Retaining Data Set and GCBs in
Configured CID File on page 53.
50 9ARD171384-600
Section 2 Substation Engineering CI868 CID File Export using IEC 61850 Wizard
The CID file contains Header, Communication, IED and Data Type Templates
sections based on CI868 configuration from Control Builder. Figure 30 is an
example of a generated CI868 CID file.
9ARD171384-600 51
CI868 CID File Export using IEC 61850 Wizard Section 2 Substation Engineering
The generated CID file is further used in CCT or other IEC 61850 engineering tools
for substation communication configuration to perform signal configuration.
52 9ARD171384-600
Section 2 Substation Engineering CI868 CID File Export using IEC 61850 Wizard
9ARD171384-600 53
CI868 ICD File Export using IEC 61850 Wizard Section 2 Substation Engineering
54 9ARD171384-600
Section 2 Substation Engineering CI868 ICD File Export using IEC 61850 Wizard
9ARD171384-600 55
CI868 ICD File Export using IEC 61850 Wizard Section 2 Substation Engineering
56 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
9ARD171384-600 57
Configuring other IEDs Section 2 Substation Engineering
2. In the PCM 600 dialog box, select File > Open/Manage Project to create a
new project.
58 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
9ARD171384-600 59
Configuring other IEDs Section 2 Substation Engineering
5. Select the project and click Open Project to open the project tree structure in
PCM 600.
60 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
9. Right-click the substation and select New > General > Voltage Level to create
a new voltage level under substation.
9ARD171384-600 61
Configuring other IEDs Section 2 Substation Engineering
11. In the Object Properties dialog box, select the actual voltage level value
available in CCT from the VoltageRange drop-down list. In this example,
select 110-220 kV.
12. Right-click the voltage level and select New > General > Bay to create a new
Bay.
62 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
13. Right-click the bay level and select New > Transmission IED > REC 670 IEC
to create a new IED under the bay level.
In this example, the first IED is REC 670 IEC and the second IED is RET 670
IEC.
The context menu shows the available 670 series IEDs to be inserted, on the bay
level in the Plant Structure, according to the installed connectivity package.
The technical key in the physical IED and IED object in PCM600 must be the
same for communication between the IED and PCM600, otherwise it is not
possible to download a configuration.
Each IED in a PCM600 project must have a unique technical key. Therefore, it
is not possible to set the same technical key for several IEDs in the same
PCM600 project.
The IED is delivered with a factory default technical key. The validation of the
technical keys between PCM600 and the IED does not occur if the IED contains
the factory default technical key.
9ARD171384-600 63
Configuring other IEDs Section 2 Substation Engineering
The technical key property in PCM600 corresponds to the IED name attribute in
SCL files. Avoid changing the IED name attribute outside PCM600, because data
in PCM600 may get lost when importing the SCL files.
The technical key can be read from the IED and updated to PCM600, or the
PCM600 technical key can be written to the IED. Alternatively, a user-defined
technical key can be defined.
When writing a configuration to the IED, PCM600 checks for a mismatch
between the IED object and the physical IED technical key and appropriate
message is displayed.
Ensure that the IED object in PCM600 has the same IP address as the physical
IED that is intended to be connected through the technical key concept.
The technical key for an IED object can be changed in the Object Properties
dialog box in PCM600.
14. In Configuration Mode, select the mode of IED configuration. IED
Configuration can be done in two ways.
– Online Configuration
– Offline Configuration.
64 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
9ARD171384-600 65
Configuring other IEDs Section 2 Substation Engineering
66 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
b. Select the Port and enter the correct IP address of the physical IED to be
configured.
9ARD171384-600 67
Configuring other IEDs Section 2 Substation Engineering
c. Click Scan to scan/read the IED Type and IED Version for the IED that is
online.
The user cannot scan data from the IED or proceed further if the IED is not online
or if the IP address is not correct.
68 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
d. Click Next to open the Housing Selection Page and select the Housing
and Display type of the IED.
e. The Setup Complete Page dialog shows the summary of the IED Type,
IED Version, IP Address of IED and Order Number. Click Finish to
complete the online IED configuration.
9ARD171384-600 69
Configuring other IEDs Section 2 Substation Engineering
After completing online configuration, read the configuration from the IED to
ensure that the IED object in PCM600 has the same configuration data as the
physical IED.
70 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
9ARD171384-600 71
Configuring other IEDs Section 2 Substation Engineering
72 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
Verify that PCM600 tool detects the IP address entered for the IED in the project
tree structure.
d. Click Next.
9ARD171384-600 73
Configuring other IEDs Section 2 Substation Engineering
f. Browse and select the Order Specific File and click Next.
74 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
If the order specific file is not available, select the No Order Specific File check
box and proceed to the next wizard. The order code can be configured later when
the IED is online.
g. Click Next.
In case of customer specific IEDs, select the corresponding housing type series.
9ARD171384-600 75
Configuring other IEDs Section 2 Substation Engineering
17. The following page appears after completing the selected IED configuration.
76 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
19. In IED application, create GOOSE data receiver channel. Right-click the IED
level and select Application Configuration from the context menu to open the
Application Configuration page.
9ARD171384-600 77
Configuring other IEDs Section 2 Substation Engineering
20. The Application Configuration window for the selected IED opens. Create an
Application logic.
The meaning of this application is that this IED receives GOOSE data on
channels 'GooseData1' to 'GooseData4'. This block converts first channel data
into its quality and value. Signal 1 value appears at 'OUT1VAL' while its
quality appears at 'OUT1'. These signals are sent to the Binary output module
of IED.
78 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
Perform the application logic for other tabs and save the work.
For more details on configuring application logic, refer to the respective PCM
600 IED Manual.
9ARD171384-600 79
Configuring other IEDs Section 2 Substation Engineering
21. Right-click the IED and select Export to export the CID file.
22. In the Export dialog box, browse the path to export the CID file and select
Configured IED Description (*.cid) from the Save as type drop-down list.
80 9ARD171384-600
Section 2 Substation Engineering Configuring other IEDs
9ARD171384-600 81
Configuring other IEDs Section 2 Substation Engineering
24. Clear the selection of Export Private Sections check box and click Export.
The CID file is generated for the selected IED.
82 9ARD171384-600
Section 2 Substation Engineering Substation Communication Engineering in CCT600 / IET600
9ARD171384-600 83
Communication Engineering using CCT600 Section 2 Substation Engineering
84 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
3. Enter a Project Name and the Project Path and click Ok.
9ARD171384-600 85
Communication Engineering using CCT600 Section 2 Substation Engineering
4. In Substation Section,
to create Voltage Level, right-click substation name and select create new
Voltage Level from the option menu.
The substation, Voltage, and Bay name must match with the project tree structure
created in PCM.
86 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
a. To create a Bay, right-click Voltage Level and select Create new Bay
from the context menu.
9ARD171384-600 87
Communication Engineering using CCT600 Section 2 Substation Engineering
5. In Communication Section,
a. To create a Bus, right-click Communication Section and select Create
new Bus from the context menu.
88 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
6. To import ICD file(s), right-click IED Section and select Import ICD File(s)
from the context menu.
9ARD171384-600 89
Communication Engineering using CCT600 Section 2 Substation Engineering
7. In the Import ICD Files(s) dialog box, click Add File to browse the CID file.
8. In the Browse window, select the required CID / ICD file(s) of CI868 and other
IEDs to display in the list.
The Customer Name of other IEDs in CCT should be modified, as entered in the
Caption Field in PCM as shown in Figure 75.
90 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
9. Import IEC 61850 OPC Server ICD file. Use one or more of the following
OPC Server ICD file variants available with 800xA IEC 61850 Connect
package.
– OPC Server with 1 sub network.icd
– OPC Server with 16 sub network.icd
IEC 61850 OPC Server ICD file can be configured in CCT, only if the IEC 61850
Connect is installed in 800xA System.
By default the IEC 61850 OPC Server ICD file is located in C:\Program
Files(x86)\ABB\61850 OPC Server, with the default name and it can be renamed
as required.
9ARD171384-600 91
Communication Engineering using CCT600 Section 2 Substation Engineering
10. Select the Import check box of respective IEDs and click Import All Files.
IED name can be modified if necessary in the IED Name in CCT column.
Incase of importing same ICD file as template for multiple IED instances, it is
required to use IED Name in CCT option to configure individual IED names.
When AC 800M with multiple access points are imported into CCT600 as
individual configured CID files, it is recommended to modify the individual IED
names with CI868 Access Point name in IED name in CCT column, otherwise
the AC 800M access point is overwritten. After importing the CID files, retain the
client mapping as mentioned in Retaining Data Set and GCBs in Configured CID
File on page 53.
11. Modify the OPC Server name in the IED Name in CCT column.
Modification of OPC Server name is necessary as the OPC Server ICD file
contains default name.
Incase of importing same OPC Server ICD file as template for multiple OPC
Server instances, it is required to use IED Name in CCT option.
92 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
9ARD171384-600 93
Communication Engineering using CCT600 Section 2 Substation Engineering
13. Assign the IP address for IEDs, if correct IP address is not configured in
imported CID file.
94 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
9ARD171384-600 95
Communication Engineering using CCT600 Section 2 Substation Engineering
96 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
9ARD171384-600 97
Communication Engineering using CCT600 Section 2 Substation Engineering
98 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
3. Repeat the Step 1 and Step 2 for other Primary Equipment according to Table 6
and save the changes.
9ARD171384-600 99
Communication Engineering using CCT600 Section 2 Substation Engineering
3. By default, the IED tools generate CID files which have predefined datasets.
Figure 84 shows the dataset and RCB defined for IED already.
Create all the signal engineering for an IED under LD0.LLN0. Keep LD0.LLN0
selected to view all the data engineering fields as shown in Figure 84.
100 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
4. Select LD0.LLN0 for an IED and on the right pane select IEC 61850 Data
Engineering tab and then select the Data Set Engineering tab.
5. On the Data Sets panel, click Add, a new dataset named new_ds is created. If
required rename it.
9ARD171384-600 101
Communication Engineering using CCT600 Section 2 Substation Engineering
6. Navigate to the desired signal in the IED data Model panel and click Add.
For example, if the Circuit breaker CB_L5R position must be sent through
MMS from the signal list, then add this signal in the dataset.
102 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
9ARD171384-600 103
Communication Engineering using CCT600 Section 2 Substation Engineering
104 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
For GCB Data Set, the signals must be assigned at Data Attribute (DA) level.
Ensure that for each configured GCB Data Set, Quality (q), Time (t), and Signal
Attribute is available. Time attribute is optional for GOOSE signals.
For example: stVal, ctlModel, q
SCD file import is cancelled, if the configured SCD file does not contain Signal
Attribute.
It is recommended Not to configure RCB datasets containing Data Attributes of
Functional Constraint type CO as it is used for Control purpose
It is recommended to have a maximum of 10 data objects per GCB dataset. Use
additional datasets to add more than 10 data objects.
7. Similarly, add other signals in the signal list for this IED. Dataset is defined and
save the settings.
For GCB Datasets signals sending to and from CI868, include the signals
mentioned in Table 3.
For RCB Datasets to CI868, include signals as mentioned in Table 4.
8. Define Report Control Block for this dataset. Select the Report Control
Engineering tab and click Report Control.
9ARD171384-600 105
Communication Engineering using CCT600 Section 2 Substation Engineering
The datset column can also have configured RCB datasets that have Data objects
of LLN0 and LPHD logical nodes sending data from other IEDs to CI868
module.
11. The check boxes selected by default in Figure 94 indicate the following:
– Selected dataset will be buffered for 500 ms.
– 5 MMS clients can access this data simultaneously.
– Data is reported if there is a data update or quality update.
106 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
9ARD171384-600 107
Communication Engineering using CCT600 Section 2 Substation Engineering
Figure 95.
108 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
9ARD171384-600 109
Communication Engineering using CCT600 Section 2 Substation Engineering
10. In IEC 61850 GSE Applications dialog box, select GSE Application from the
list and click Select.
110 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
9ARD171384-600 111
Communication Engineering using CCT600 Section 2 Substation Engineering
The appID field must not be left empty in the GOOSE Control Block Definition
even if the 3rd party IEDs are present in the configuration.
11. Define the IED to act as the receiver of the above GOOSE message. According
to the signal list, this message is relevant to IED AA1E1Q01_BC101. Drag and
drop AA1CI868IED_PC103 into the name field of the GOOSE control block.
112 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
9ARD171384-600 113
Communication Engineering using CCT600 Section 2 Substation Engineering
12. Repeat Step 1 to Step 11 for configuring other IEDs according to the signal list.
See another example shown in Figure 105.
GCB datasets can be automated using the procedure defined above for RCB. For
more details refer to CCT Manual.
13. Update the Dataflow. This step identifies the IED from which the GOOSE
receives the inputs. Each RCB present in the configuration, sets IEC 61850
OPC Server / ITCI from CI868 as a client.
114 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
14. After successful update data flow, the tree structure appears as shown in
Figure 107.
9ARD171384-600 115
Communication Engineering using CCT600 Section 2 Substation Engineering
116 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using CCT600
9ARD171384-600 117
Communication Engineering using CCT600 Section 2 Substation Engineering
118 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
9ARD171384-600 119
Communication Engineering using IET600 Section 2 Substation Engineering
120 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
2. The Projects window provides access to the projects stored in your computer
and enables the addition and removal of projects.
3. Click New, to create a new Project and enter the name and directory.
The project files are then stored into specified path. The default location of the
IET600 project file is located under C:\Data\IETProjects.
The engineering process for an IEC 61850 (Ed1) based substation automation
system involves the following steps:
• IED Data Engineering
• Communication Network Configuration
The engineering workflow of IET600 is depicted below.
a. Export IEDs - CID (icd) files from IED configuration tool such as PCM
600 for ABB IEDs.
b. Import specific IEDs cid/icd file for each IED type that is used in
substation.
c. Define full substation topology from Single Line diagram (SLD)
d. Map Logical Nodes of the IED to the primary elements in the Bay
9ARD171384-600 121
Communication Engineering using IET600 Section 2 Substation Engineering
Substation Engineering
Open the Substation tab in the Menu to access the IET600 functions to build the
substation topology. The Build group contains the following functions:
• Substation
• Voltage Level
• Bay
• IED
Alternatively, these functions can be accessed through the context menu of the
respective nodes in the Navigation Tree.
• To create the substation node:
a. Select the project node and right click to open the Substation dialog.
Alternatively, select the Substation function in the menu to open the same dialog.
122 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
c. Click OK and a new Voltage Level node is created in the Navigation view.
• To create a new Bay:
a. Select the Voltage Level node, right click and select “Create New Bay” or
click on the Bay function in the menu to open the Bay dialog.
b. Enter an Object name for the new Bay in the dialog.
c. Click OK and a new bay node is created in the Navigation view.
To define the full topology of the substation, repeat the steps for each successive
bay. The full substation topology is viewed from the voltage level node.
9ARD171384-600 123
Communication Engineering using IET600 Section 2 Substation Engineering
124 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
e. The tree in the dialog window shows the node that is used to create the
IED.
f. Enter the name of the IED and click OK.
• Updating IEDs:
During the later stages in the project engineering, an IED is updated in the
IET600 project whenever there is a change in the IED.
Updating an IED can be done,
– as a simple Update from a file (old IED content is removed and then
created newly from the file).
– as a Merge that allows user to merge parts of the IED in IET600 with parts
from the file.
To update an IED:
9ARD171384-600 125
Communication Engineering using IET600 Section 2 Substation Engineering
b. Select any valid SCL file (SCD, ICD, CID file) and click Open.
126 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
c. Click OK.
The IED is imported from the file.
To check the differences between the Source and the Destination IED,
click <> in the Compare column. The following window appears.
Check the differences and click Merge to import the IED from the file.
The IED is imported into IET600.
9ARD171384-600 127
Communication Engineering using IET600 Section 2 Substation Engineering
b. Select any valid SCL file (SCD, ICD file) in Import SCL File and click
Open.
128 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
IET600 automatically matches the IEDs with the same name in IET600
and in the source file.
The Update column allows you to select or deselect individual IEDs for updating.
Only the selected IEDs are updated.
Perform Step c available in To update an IED to compare and merge the
source IEDs with the destination IEDs.
• Deleting IEDs:
IEDs can be deleted from its context menu. IEDs can either be completely
deleted or its content be removed.
• Mapping LNs to Substation Elements:
LN in any IED can be mapped to any node in the Substation Tree. However,
IET600 has mapping restrictions for efficient engineering and correct mapping
of specific LN types. For example, LN CSWI can be mapped only to
equipment of type CBR or DIS.
Some IEDs having LNs are mapped to an equipment from another Bay or to a
station level equipment.
Following restrictions are applied while mapping LNs to bay:
9ARD171384-600 129
Communication Engineering using IET600 Section 2 Substation Engineering
– LN type CSWI and SCILO can only be mapped to equipment of the type
Circuit Breaker (CBR) or Disconnector (DIS).
– LN type XCBR and RSYN can only be mapped to equipment of the type
CBR.
– LN type XSWI can only be mapped to equipment of the type DIS.
– LN type MMXU can only be mapped to equipment of the type Current
Transformer (CT) or Voltage Transformer (VT).
– LN type LLN0 and LPHD can only be mapped to the bay.
An exception to the above rules is that all LN types can be mapped to the
bay. For more details, refer to IET600 manual.
Communication Engineering
This section explains on creating subnetwork and connecting the subnetwork to the
IEDs in the communication tree. Creating a subnetwork can be done using any of
the following methods:
• Creating Subnetwork from Main Menu on page 130
• Creating Subnetwork from Context Menu on page 132
130 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
9ARD171384-600 131
Communication Engineering using IET600 Section 2 Substation Engineering
132 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
9ARD171384-600 133
Communication Engineering using IET600 Section 2 Substation Engineering
After connecting the IEDs, the communication tree is updated and the
connected IED is seen under the new Subnetwork.
134 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
An IED can have several Access Points that can be connected to different
Subnetworks. However, IED with two Access Point should not be connected to
the same Subnetwork.
Mapping of two Access Points of the same IED to the same Subnetwork by
should be avoided by sorting, for example. First sort the Access Point and then on
the IED.
Use the Fill Down mechanism to connect multiple IEDs/Access Points to a
Subnetwork.
9ARD171384-600 135
Communication Engineering using IET600 Section 2 Substation Engineering
The Communication Tree is updated and the IED is seen under the new
Subnetwork.
Unconnected IEDs/Access Points appear directly under the root node.
136 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
Editing IP Addresses.
Perform the following steps to edit an IP address that is mapped to a subnetwork.
1. Select the Subnetwork Editor.
9ARD171384-600 137
Communication Engineering using IET600 Section 2 Substation Engineering
Dataflow Engineering
This section explains on the functionality and configuration of the dataflow required
for exchanging data between different IEDs. To configure the dataflow, the data
model of the IEDs and the communication (the connection between the IEDs) must
be defined. The IEC 61850 (Ed1) standard distinguishes:
• A Dataset that specifies what data are sent among the IEDs.
• A Control Block that specifies how the data are sent. IEC 61850 (Ed1) defines:
– Report Control Blocks (RCBs)
– GOOSE Control Blocks (GCBs)
IET engineering specifies two ways of communication engineering:
1. Vertical communication from bay level IEDs to HMIs or NCC Gateways. The
vertical communication includes:
– configuring Datasets, either manually or by rules.
– configuring Report Control Blocks, either manually or by rules.
– configuring Clients for the Report Control Blocks in a matrix.
2. Horizontal communication between IEDs with similar functionality (typically
between. The horizontal communication includes:
– configuring Datasets, either manually or by rules.
– configuring Goose Control Blocks, either manually or by rules.
– configuring receivers for Goose Control Blocks in a matrix.
138 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
9ARD171384-600 139
Communication Engineering using IET600 Section 2 Substation Engineering
4. Right-click and select Insert new row from the context menu.
140 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
5. The Create New Dataset window appears as shown in Figure 136. Select an
LN, and enter a name for the Dataset.
The name entered must be a valid. Duplicate names or special characters are not
allowed for a particular node.
Editing Datasets.
In the Dataset Editor, the name and the description of a Dataset can be edited. If
name is changed, the attached RCBs or GCBs are automatically updated.
9ARD171384-600 141
Communication Engineering using IET600 Section 2 Substation Engineering
2. The selected Dataset determines the IED. The first list shows the available LDs.
3. Select LD > LN > DObject > DAttr.
It is recommended Not to configure RCB or GCB datasets containing Data
Objects and Data Attributes of Functional Constraint type CO as it is used for
Control purpose.
142 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
SCD file import is cancelled, if the configured SCD file does not contain
Signal Attribute.
• For RCB Data Set, the signals must be assigned at Data Object (DO) level
that includes the attributes of the DO (Signal, Quality (t), and Time (t)).
For example: Pos, EnaOpn, EnaCls
9ARD171384-600 143
Communication Engineering using IET600 Section 2 Substation Engineering
144 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
2. To create RCB, you can preselect an appropriate node in the Substation, IEDs,
Communication Navigation Tree or select the Project node Figure 141.
9ARD171384-600 145
Communication Engineering using IET600 Section 2 Substation Engineering
146 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
4. Right-click and select Insert new row from the context menu.
5. Create New RCB window appears as shown in Figure 144. Select an LN, and
enter a name for the Dataset.
The name entered must be a valid. Duplicate names or special characters are not
allowed for a particular node.
9ARD171384-600 147
Communication Engineering using IET600 Section 2 Substation Engineering
Editing RCBs.
The RCB configuration can be edited in the RCB editor. Following must be
observed during renaming:
• An RCB cannot be renamed. To rename an RCB, delete it and create a new
RCB with the intended name.
• Removing a Dataset from an RCB will automatically put the RCB into a
deleted state.
• Configuration changes will cause the configRev value to be increased to the
next multiple of 10,000. This will happen only once between import and
export, not with every change.
148 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
9ARD171384-600 149
Communication Engineering using IET600 Section 2 Substation Engineering
2. Make the AP column visible in the RCB Client Editor, if IEDs have more than
one Access Points.
3. To configure the IEDs/Access Points with Default and RCB clients:
– Click Clear All to remove all the existing clients.
– Click Configure Empty to configure clients for those IEDs/Access Points
that have no clients configured yet.
– Click Configure All to delete all the existing clients and replace them
with default configuration.
150 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
Creating GCBs/Datasets/Clients.
GCBs/Datasets can be generated:
• from the context menu of an IED.
• from the context menu of an IED under a node.
1. To generate GCBs/Datasets, right-click a node and select Generate
GCBs/Datasets from the context menu.
9ARD171384-600 151
Communication Engineering using IET600 Section 2 Substation Engineering
152 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
9ARD171384-600 153
Communication Engineering using IET600 Section 2 Substation Engineering
4. Right-click and select Insert new row from the context menu.
5. Repeat Step 2 to Step 4 to create GCBs from the context menu
154 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
9ARD171384-600 155
Communication Engineering using IET600 Section 2 Substation Engineering
– Right-click and select Remove all GCB Client connections to remove all
existing connections in the editor and all related inputs.
If this action is preformed, all the configured mappings in the Signal Matrix in
PCM600 is lost. This can be avoided by setting the filters and hiding all the IEDs
that are configured for GCB clients.
– Right-click and select Connect all GCBs to Clients to connect all GCBs
in rows to all Clients in the columns.
3. Export SCL File dialog window appears. Select the directory to save the file
and with an appropriate SCD file name.
156 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
9ARD171384-600 157
Communication Engineering using IET600 Section 2 Substation Engineering
2. Export SCL File dialog window appears. Select the directory to save the file
and with an appropriate SCD file name.
158 9ARD171384-600
Section 2 Substation Engineering Communication Engineering using IET600
This completes the creation of a fully configured SCD file in IET600 Tool.
9ARD171384-600 159
Updating IED configuration with SCD file Section 2 Substation Engineering
160 9ARD171384-600
Section 2 Substation Engineering Updating IED configuration with SCD file
9ARD171384-600 161
Updating IED configuration with SCD file Section 2 Substation Engineering
The question mark appearing on an IED icon might be a PCM 600 error. Close
the PCM 600 and reopen to clear the question mark.
162 9ARD171384-600
Section 2 Substation Engineering Updating IED configuration with SCD file
9ARD171384-600 163
Updating IED configuration with SCD file Section 2 Substation Engineering
8. In the Signal Matrix tool, define the Hardware input/output connection to the
variables defined in application logic. Define the Goose matrix.
Notice that the tab named Goose Receive is created.
9. Select the Goose Receive tab and perform the signal mapping of GOOSE
sending and receiving channels.
Figure 162 explains that signal Tr1 from CI868 IED will be assigned to channel
GooseData1 in the IED REC670.
10. A function block is defined in an application logic. This enables the digital
output to be switched on while receiving GOOSE data. Map the function block
channels to real hardware outputs in the Binary Outputs tab. Similarly, LED
outputs can also be mapped.
164 9ARD171384-600
Section 2 Substation Engineering Updating IED configuration with SCD file
9ARD171384-600 165
Updating IED configuration with SCD file Section 2 Substation Engineering
166 9ARD171384-600
Section 2 Substation Engineering Updating IED configuration with SCD file
IED restarts after the download is complete. The IED is then ready to exchange both
MMS and GOOSE data.
15. Repeat Step 1 to Step 14 for other IEDs.
IED parameters can be set through Parameter setting tool in the PCM 600. Do not
set hysteresis values to very low for analog values (that is, voltage, current). This
results in unnecessary fluctuation in the indication of analog values.
9ARD171384-600 167
CI868 IED Engineering with Control Builder M Section 2 Substation Engineering
168 9ARD171384-600
Section 2 Substation Engineering CI868 IED Engineering with Control Builder M
9ARD171384-600 169
CI868 IED Engineering with Control Builder M Section 2 Substation Engineering
170 9ARD171384-600
Section 2 Substation Engineering CI868 IED Engineering with Control Builder M
3. Click Browse to locate the .scd file folder. Select the SCD file and click Open.
9ARD171384-600 171
CI868 IED Engineering with Control Builder M Section 2 Substation Engineering
IEC 61850 wizard detects all CI868 IEDs and the corresponding access points in
SCD file and lists in Select IED Name drop-down list.
The list can also have AC800M IED.
4. Select the corresponding CI868 IED from the Select IED Name and click
Verify to validate any errors only for the selected CI868 IED access point in
the configured SCD file.
If any errors are found in the selected access point of the SCD file, they are
logged in the IEC61850 Wizard log file. A generic message is displayed to refer
the IEC61850ImportWizard.log file.
5. Click Import to import the SCD file into the existing CI868 module in Control
Builder hardware.
For projects with multiple CI868 IEDs, the correct instance of CI868 module has
to be selected for SCD file import. For rules regarding the selection criteria, refer
to AC800 M configuration manual (9ARD171385*).
172 9ARD171384-600
Section 2 Substation Engineering CI868 IED Engineering with Control Builder M
SCD file import is cancelled, if the Main Signal data attribute is not configured in
k
the inputs sections of the SCD file. A warning message appears as shown in
Figure 173. To configure the Main Signal attribute perform Step 6 and Step 7
explained in Configuring Vertical Communication for MMS Protocol on page 99
6. Notice the progress bar showing the progress of import as shown in Figure 174.
9ARD171384-600 173
CI868 IED Engineering with Control Builder M Section 2 Substation Engineering
7. The Tree View Comparator opens after importing the SCD file as shown in
Figure 175.
174 9ARD171384-600
Section 2 Substation Engineering CI868 IED Engineering with Control Builder M
After import, the SCD file is saved in Control Builder project folder (Compact
Control Builder) or Aspect Directory (Control Builder professional). For every
subsequent import, the SCD file is overwritten and the last imported SCD file per
CI868 IED is saved. Only one SCD file is stored per CI868.
Deleting the CI868 object in the Control Builder tree structure deletes the stored
SCD file.
The Get SCD button in the IEC61850 Wizard window retrieves the last saved and
imported SCD file. This SCD file is used for retaining configured Data set and
GOOSE Control Blocks during subsequent CID file export. For more
information, refer to Retaining Data Set and GCBs in Configured CID File on
page 53.
10. In the IEC61850 Wizard tool, click CCF tab.
CCF tab is viewed or used only for maintenance purpose.
9ARD171384-600 175
CI868 IED Engineering with Control Builder M Section 2 Substation Engineering
Select the CCF file of the access point to verify the number of datasets available in
the corresponding CCF file.
176 9ARD171384-600
Section 2 Substation Engineering CI868 IED Engineering with Control Builder M
9ARD171384-600 177
CI868 IED Engineering with Control Builder M Section 2 Substation Engineering
11. Right-click the IEC 61850 Wizard screen and from the context menu select
View Log to view the log information as shown in Figure 181.
178 9ARD171384-600
Section 2 Substation Engineering CI868 IED Engineering with Control Builder M
9ARD171384-600 179
CI868 IED Sending GOOSE Signals Section 2 Substation Engineering
The position of the GOOSE objects in the Control Builder hardware tree structure
is between 1 to 199, for MMS Diagnostics the numbering is 200, and for MMS
objects it is between 201 to 254. IEC 61850 Wizard generates the numbering
sequence during SCD file import.
The naming convention of MMS objects in the Hardware tree is as follows:
<LN Prefix>_<LN Instance> <LN name>. For example, CV_2 MMXU
Use the Hide Unused Channels option to hide the IO channels that have empty
Protocol Info for all the Hardware objects in CI868 hardware library.
180 9ARD171384-600
Section 2 Substation Engineering CI868 IED Receiving GOOSE Signals
The protocol information path for GOOSE data sent from other IEDs to CI868 in
IEC 61850 is in the following format:
SubNetworkName.IEDName.LogicalDeviceName.LogicalNodeName.Dat
aObjectName.
For example. AA1WA1.AA1A1.LD0.SP16.GGIO.2.Ind, where
• AA1WA1 is Subnetwork
• AA1A1 is IED
• LD0 is Logical Device
• SP16.GGIO.2 is Logical node
• Ind is Data Object
9ARD171384-600 181
CI868 IED Receiving GOOSE Signals Section 2 Substation Engineering
182 9ARD171384-600
Section 2 Substation Engineering CI868 IED Receiving GOOSE Signals
9ARD171384-600 183
CI868 IED Receiving GOOSE Signals Section 2 Substation Engineering
Figure 186. SCD file - Logical Node ATCC, Inputs Section Level
184 9ARD171384-600
Section 2 Substation Engineering CI868 IED Receiving GOOSE Signals
9ARD171384-600 185
CI868 IED MMS Command Signal Section 2 Substation Engineering
186 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
9ARD171384-600 187
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
188 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
9ARD171384-600 189
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
190 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
9ARD171384-600 191
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
192 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
9ARD171384-600 193
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
6. Define a sample application logic to enable the CI868 to send a trip signal to
the IED whenever the Power exceeds the MaxPower. The IED sends Current
and Voltage signal to CI868 through GOOSE.
7. Define the signals for the Load Shed application as shown in Figure 200.
8. For example, define a sample logic for loadshed as shown in Figure 201.
Control Builder Application for Circuit Breaker Control with MMS Commands
This section explains how to use the Controller Application for Motor Feeder with
controlled circuit breaker via IEC 61850 communication.
Under ProcessObjectBasicLib, IEDCommandSend and IEDStatusReceive function
blocks are available for mapping process control commands to IEC 61850 control
commands. IEDCommandSend object performs MMS based Direct and Select
Before Operate (SBO) Functions to control circuit breakers or switches and
generate feedback timeout error signals. Circuit Breaker control functionality is
typically used for operator commands from CI868 to other IEDs.
194 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
IEDStatusReceive object is used to receive status information from the IED and
provide actual feedback status information to process object function blocks.
IEDCommandSend and IEDStatusReceive function blocks can be used with any
library. The sample application in Figure 210 shows function block of
Uni_Simple from processObjectBasicLib library.
Perform the following steps to create Control Builder Application for Circuit
Breaker Control via MMS:
1. To create a new program, right-click Applications, Select New > Program
from the context menu as shown in Figure 202.
9ARD171384-600 195
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
in Figure 204.
196 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
9ARD171384-600 197
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
5. Define the variables for the SBO application as shown in Figure 206.
198 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
9ARD171384-600 199
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
7. A typical Application with SBO created for Circuit Breaker Control is shown
in Figure 210.
The IEDStatusReceive and IEDCommandSend function blocks can be used
with any Library. In this example, the sample application shows using
UniSimple_1 function block from ProcessObjBasicLib.
For more information on IEDCommandSend and IEDStatusReceive function
block, refer to AC 800M IEC 61850 Configuration for CI868 (9ARD171385*)
Manual.
200 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
The Out0 and Out1 parameter of UniSimple function block sends Open and
Close command respectively, which is received by Open and Close input
parameter of IEDCommandSend_1 function block. The CTLCMD parameter in
IEDCommandSend function block sends the necessary Control Commands to
the respective IED. The feedback from the IED is received by PosStatus
parameter of IEDStatusReceive function block and further sent to the
UniSimple function block as actual feedback.
9ARD171384-600 201
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
202 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
Alarms and Events generated using Signal ID is used for External / IED time
stamp.
9ARD171384-600 203
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
2. Create a sample logic for Alarm Cond and Event Detector as shown in
Figure 212.
204 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
9ARD171384-600 205
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
The Alarms are generated for the IEDs, only if the Generate Alarm parameter is
set to Enable for the corresponding IED hardware object as shown in Figure 213.
For more details on Alarms and Event generation using SignalID, refer to AC
800M Configuration for CI868 (9ARD171385*) Manual.
206 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
Figure 214 shows Alarm and Event list with Process Alarms for the application
logic for Alarm Cond and Event Detector.
9ARD171384-600 207
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
2. The Reserve dialog window appears, enter the comment and click OK.
208 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
3. Select the application to be connected to the Controller and click Ok. The
application is added under Controller > Connected Applications as shown in
Figure 217.
4. To connect the task (that is, cycle interval) for Application and Program,
right-click the Application and select Properties > Task Connection from the
context menu as shown in Figure 219.
9ARD171384-600 209
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
5. The Task Connection window appears as shown in Figure 220. Select the task
from the list and click Ok.
210 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
9ARD171384-600 211
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
4. For assigning GOOSE Data, open the hardware editor of LN of the IED
AA1A2 and assign the program variables as shown in Figure 224.
5. Similarly, open the hardware editor of LN of the CI868 IED and assign the
program variables as shown in Figure 225.
212 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
6. For assigning MMS Data Receive, open the hardware editor of LN of the IED
AA1E1Q01 as shown in Figure 226 and assign the program variables.
9ARD171384-600 213
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
214 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
2. In the System Identity window, enter the IP address and click Ok.
3. Double-click the IED to open the Hardware editor. In the Hardware editor
window, enter the IP address of the Controller at the Ethernet level.
9ARD171384-600 215
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
In this example, the power is more than Maxpower. AC 800M sends the TripSignal
to AA1A1.
6. Open the Application Configuration page of the IED in PCM 600 and use
online option to check whether the signal is reached into the selected IED.
216 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
Figure 233 shows a sample screen shot of the IED in PCM 600 in online mode.
7. Simulate the current value to zero and observe that TripSignal is no longer
True.
9ARD171384-600 217
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
218 9ARD171384-600
Section 2 Substation Engineering Control Builder Application Engineering with IEC 61850 Communication
9. Figure 235 shows the online view of the Alarm Cond and Simple Event
Detector.
Figure 236. Alarm Cond and Simple Event Detector Online View
9ARD171384-600 219
Control Builder Application Engineering with IEC 61850 Communication Section 2 Substation
Figure 214 shows sample Alarm and Event list with Process Alarms for the
application logic for Alarm Cond and Event Detector.
220 9ARD171384-600
Section 2 Substation Engineering IEC 61850 Connect Engineering
9ARD171384-600 221
IEC 61850 OPC Server Configuration Section 2 Substation Engineering
222 9ARD171384-600
Section 2 Substation Engineering IEC 61850 OPC Server Configuration
9ARD171384-600 223
IEC 61850 OPC Server Configuration Section 2 Substation Engineering
3. In CET, right-click the project and select New > Communication > Computer
Node.
4. Right-click the computer node and select New > IEC 61850 > IEC 61850
OPC Server to create OPC Server object.
224 9ARD171384-600
Section 2 Substation Engineering IEC 61850 OPC Server Configuration
5. Rename the OPC Server object. It is recommended to maintain the same name
as the subnetwork. In this example, it is AA1MainNorth1.
For one subnetwork in SCD file, define one OPC Server object.
CET can support SCD files configured with one or more subnetworks (max 16)
under one OPC Server object.
6. Right-click the OPC Server level and select SCL Import.
9ARD171384-600 225
IEC 61850 OPC Server Configuration Section 2 Substation Engineering
c. Click Import.
226 9ARD171384-600
Section 2 Substation Engineering IEC 61850 OPC Server Configuration
Table 8 details the communication Options field available in the IEC61850 OPC
Server SCL Import screen.
9ARD171384-600 227
IEC 61850 OPC Server Configuration Section 2 Substation Engineering
After successful import, all the IEDs, LDs and LNs are created for the selected
subnetwork.
228 9ARD171384-600
Section 2 Substation Engineering IEC 61850 OPC Server Configuration
This client name should be entered in the Report Control Identity field of OPC
Server object properties.
This defines the client for OPC Server and OPC attributes get updated on data
change automatically.
9ARD171384-600 229
IEC 61850 OPC Server Configuration Section 2 Substation Engineering
230 9ARD171384-600
Section 2 Substation Engineering IEC 61850 OPC Server Configuration
9. In the Management dialog box, click Update configuration and then click
Reload configuration.
9ARD171384-600 231
IEC 61850 OPC Server Configuration Section 2 Substation Engineering
The configuration (which is actually an XML at the back end) is written to the OPC
Server. The OPC sever starts and requests the IED for all the data defined in
datasets.
10. Right-click the IED and select Online diagnostic.
11. When IED is providing the requested data to OPC Server, the status is visible in
Online diagnostic window as shown in Figure 254.
232 9ARD171384-600
Section 2 Substation Engineering IEC 61850 OPC Server Configuration
12. If the IED is not connected, the status shown in Figure 255 is visible in the
Online diagnostics window.
13. When OPC Server reads all the OPC items, the status is visible in the Online as
shown in Figure 256.
9ARD171384-600 233
IEC 61850 OPC Server Configuration Section 2 Substation Engineering
14. Check the Online diagnostics for data objects to see the online values. For
example, Figure 257 shows the OPC item values for XCBR.pos.
OPC Server configuration is complete when the data quality is shown 'GOOD'.
To view the error logs in CET IEC 61850 OPC Server, open the EventLog.txt log
file located in C:\Program Files (x86)\ABB\61850 OPC
Server\OPC_61850\bin\OPCS_IEC61850_instance number\
For more information on Redundancy OPC Server, refer to System 800xA IEC
61850 Connect Configuration (9ARD171387*) Manual.
234 9ARD171384-600
Section 2 Substation Engineering IEC 61850 OPC Server Configuration
2. Refer to the signal list provided by customer to find the signals for which the
customer needs Alarms and Events and with what priority.
3. Map the table as shown in Figure 258 into the CET for Alarm and Event
configuration.
9ARD171384-600 235
IEC 61850 OPC Server Configuration Section 2 Substation Engineering
4. For example, to generate alarm when Circuit Breaker trips, navigate to the
Circuit Breaker object in CET and select Pos. Open Object Properties
window of Pos.
236 9ARD171384-600
Section 2 Substation Engineering IEC 61850 OPC Server Configuration
9ARD171384-600 237
IEC 61850 OPC Server Configuration Section 2 Substation Engineering
9. Reload this configuration to OPC Server. Now OPC Server generates the
alarms and events for the circuit breaker position. Similarly, define the
configuration for other signals.
For detailed information on configuring Analog Alarms in IED / OPC Server,
System and Process Alarm, SCD Consistency Check, Area Name and
Description, and Event templates Export/Import, refer to System 800xA, IEC
61850 Connect Configuration (9ARD171387*) Manual.
238 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
9ARD171384-600 239
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
240 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
9ARD171384-600 241
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
242 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
2. Click Add and select a Connectivity Server from the Select Connectivity
Server(s) window as shown in Figure 266.
9ARD171384-600 243
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
3. In the Additional Arguments window, select the OPC Server from Selected
OPC Server, ProgID field and click Create as shown in Figure 267.
244 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
6. Browse the SCD file and select the Subnetwork name in the Uploader window
as shown in Figure 269.
Ensure that the same subnetwork that is imported in the OPC Server (to which the
OPC data source definition aspect of OPC Server object is pointing) is chosen
here as well.
9ARD171384-600 245
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
For more information on IEC 61850 Uploader Aspect, refer to System 800xA IEC
61850 Connect Configuration (9ARD171387*) Manual.
246 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
9. Observe that OPC control connection shows the quality of data items as Good
in the Control Structure after upload as shown in Figure 272.
9ARD171384-600 247
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
Using the control connection data, the faceplates and trends for the signals can be
created.
The Primary Equipment in the Function Structure does not contain any default
Faceplates. Use the available Control Connection properties to create and
customize faceplates.
Faceplates for Primary Equipment are available as an add-on installation
package. For more details, refer to System 800xA Operation Library for
Substation Equipment (2PAA108626*) Manual.
248 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
9ARD171384-600 249
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
3. Enter a name for the service group. It is recommended to enter the subnetwork
name as the event collector service group name.
4. Select the newly created service group and select the Service Group
Definition aspect. In the aspect preview, add a service provider.
250 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
5. For the service provider, select the Node name in which this service runs (that
is, connectivity server node).
6. Select the Service Group Definition aspect of the required service group.
Select the Special Configuration tab in the aspect preview.
9ARD171384-600 251
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
252 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
10. Select IEC 61850 Connect Source Name Interpreter from the Source
Translator drop-down list.
9ARD171384-600 253
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
254 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
9ARD171384-600 255
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
3. Select the Alarm Collection Definitions object and select the Alarm Priority
Mapping aspect.
256 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
Alarm severity is defined in CET for circuit breaker tripping as 800/600 and for
circuit breaker Operation (open or close) as 400. Together with this mapping table it
results in Alarm of priority 1 when CB trips and an Event of priority 2 when CB
operates.
5. Define the Alarm and Event Configurations in the Library Structure.
9ARD171384-600 257
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
258 9ARD171384-600
Section 2 Substation Engineering 800xA Control and Functional Structure Configuration
9ARD171384-600 259
800xA Control and Functional Structure Configuration Section 2 Substation Engineering
5. Select the corresponding configuration for alarm list and event list.
6. When the circuit breaker trips, the alarm appears in the alarm list as shown in
Figure 295.
260 9ARD171384-600
Section 2 Substation Engineering Summary
7. After resolving the problem triggered by the alarm, the alarm appears as shown
in Figure 296.
8. Right-click the alarm to navigate to the source object, that is, Logical Node.
Configuration of MMS communication, and Alarms and Events in 800xA system is
complete.
Summary
In this use case, from the beginning of the engineering workflow, following tasks
were performed:
• Collecting Project inputs
• Configuring CI868 IED in Control Builder
• Configuring Other IEDs
• Generating SCD file using CCT 600/IET600
• PCM600 Engineering
• Control Builder M Engineering
• IEC 61850 Connect Engineering
The procedure to handle complexity at various levels is not explained in this
document. For example, the steps to configure redundant OPC Server or steps to
handle two CI868 modules in an AC 800M Controller.
For advance configuration, refer to AC 800M IEC 61850 Configuration for CI868
(9ARD171385*) and System 800xA, IEC 61850 Connect Configuration
(9ARD171387*) Manual.
9ARD171384-600 261
Summary Section 2 Substation Engineering
262 9ARD171384-600
Section 3 Handling the Changes at Different
Levels of Engineering and Commissioning
The use cases mentioned in this section are applicable for a configured substation
and updates are required during commissioning or run-time.
Following use cases are explained in this section:
1. Addition of a LN, for example, SPGGIO in one of the IED.
2. Addition of new 3rd party IED in the configuration.
3. Addition of new signal through MMS.
4. Addition of new GOOSE signal between AC 800M and an IED.
5. Modification in the IED name and its IP address.
6. Modification in LN name.
7. Replace burnt out IED with a new one.
8. IED application logic change.
9. Alarm and Event related modification - Addition/Deletion, severity change,
Alarm text change.
Use case 1 is referred throughout while discussing all use cases. It is
recommended to understand use case 1 perfectly before proceeding further.
9ARD171384-600 263
Addition of a LN, for example, SPGGIO in one of the IED Section 3 Handling the Changes at
264 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Addition of
6. Open CCT600 and at the IED level, import the new CID file. After importing
the CID file, notice the new LN created in CCT.
7. This newly created LN is not assigned to the Bay. Drag and drop this LN to the
Bay.
Once the CID file is imported in CCT, the GOOSE client configuration is lost for
this IED. Goose client configuration needs to be performed again. Drag and Drop
the IED “AA1A1”as client to GCB configuration. (This was the case before
importing the CID file)
9ARD171384-600 265
Addition of a LN, for example, SPGGIO in one of the IED Section 3 Handling the Changes at
8. Follow the same steps of Update data flow > Compile > Generate SCD file,
as described in use case 1.
266 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Addition of
9. The SCD file containing new LN is ready. Import the SCD file in CET for OPC
Server configuration. Notice that new LN appears under the IED.
9ARD171384-600 267
Addition of a LN, for example, SPGGIO in one of the IED Section 3 Handling the Changes at
12. After successful upload, notice the LN created in the Plant Explorer.
13. New LN is now added to the configuration. Check the online values in Control
Connection aspect of this LN. Now, the faceplates and trends can be created.
268 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Addition of
SL. IED
IED Type Vendor Purpose Remark
No. Name
1 BC101 REC670 V1.1 ABB Bay Protection and Control Preconfigured IED
2 TC102 RET670 V1.1 ABB Transformer Protection and Preconfigured IED
Control
3 PC103 AC 800M PM864 + ABB DCS command and control
CI868
4 TP104 387E SEL Over current Protection Preconfigured IED
In this use case, SEL IED is considered. It can also be any third party IED.
9ARD171384-600 269
Addition of a New Third Party IED in the Configuration Section 3 Handling the Changes at Different
2. Notice the Generic IED listed in CCT. Right-click the IED and select Import
SCD File to IED to import the CID file.
3. After the CID import, notice the LDs and LNs listed under the IED.
4. Drag and drop (that is, assign) all the LDs for this IED to the Bay.
5. Complete the required communication engineering, that is, define Dataset,
GCB, and RCB configuration as explained in use case 1. In this example, the
270 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Addition of
GOOSE communication between SEL IED and ABB IED, SEL IED and
CI868 IED, both receiving and sending has been defined.
6. Save, compile, and generate the SCD file.
7. Import the file using IEC61850 Wizard in Control Builder. Download to AC
800M Controller. Notice that CI868 IED has sent GOOSE data to both SEL
IED and ABB IED.
8. Import the file to PCM 600, open Signal Matrix and download to IED.
9ARD171384-600 271
Addition of a New Third Party IED in the Configuration Section 3 Handling the Changes at Different
After import of SCD file in PCM 600, tree structure contains SEL IED as shown in
Figure 307.
When the Signal Matrix is opened, the message shown in Figure 308 is displayed.
272 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Addition of
In Signal Matrix, the entries for SEL IED are also present.
9. Import the SCD file in the SEL IED configuration tool, and download to SEL
IED.
10. Import the SCD file in CET, and download the configuration to OPC Server.
9ARD171384-600 273
Addition of a New Third Party IED in the Configuration Section 3 Handling the Changes at Different
11. Import the SCD file in Uploader and create the object types in Plant Explorer.
274 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Addition of
9ARD171384-600 275
Addition of New Signal through MMS Section 3 Handling the Changes at Different Levels of
2. Open CCT and navigate to the LN which contains this signal. This signal is
under LN PHPIOC1 for device AA1FP1, that is, TC102.
276 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Addition of
5. The SCD file containing the new signal in the RCB is ready. Import this SCD
in CET tool for OPC Server configuration and then in Plant Explorer using IEC
61850 Object Type Uploader.
6. Create the faceplates and trend logs which use this signal.
9ARD171384-600 277
Addition of New GOOSE Signal between CI868 and an IED Section 3 Handling the Changes at
The last two rows (13 and 14 in the above table) with GOOSE signals intend that
when IED reports overload condition, CI868 sends the trip command.
2. Open CCT600 and add these signals to respective GOOSE dataset. Add only
signal and its quality. Do not add time.
Figure 314 shows the dataset of CI868, that is, PC103.
278 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Addition of
Figure 315 shows the dataset of IED AA1FP1, that is, TC102.
3. Update the dataflow. Notice the message in the CCT output window.
24 GOOSE signals are transferred between all the IEDs involved. In this example,
there must be 20 signals (10 actual signals and corresponding 10 quality attribute)
before this update because four more signals (two actual signals and their quality)
are added.
4. Compile and generate the SCD file.
5. Both CI868 and IED must be made aware of this new GOOSE transaction.
First, perform it for CI868.
6. Open Control Builder and import the new SCD file.
9ARD171384-600 279
Addition of New GOOSE Signal between CI868 and an IED Section 3 Handling the Changes at
7. The TreeView Comparator window of the Import Wizard shows the changes.
8. Click Create.
280 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Addition of
9. After the import, the hardware tree structure in Control Builder is updated.
Notice the signals in Hardware editor.
9ARD171384-600 281
Addition of New GOOSE Signal between CI868 and an IED Section 3 Handling the Changes at
11. Go online with the Controller to notice a red triangle on the IED.
The red triangle on IED indicates that the IED AA1FP1 is still not aware of new
GOOSE configuration. The configuration revision of GCB is now changed, and new
SCD to IED needs to be downloaded.
12. Open PCM 600, and import the SCD file.
282 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Addition of
13. Open Signal Matrix to see the report as shown in Figure 323. Click Close.
14. In Signal Matrix, assign the receiver for the new GOOSE signal from CI868.
15. Save and download Signal Matrix to IED. After download, IED restarts.
16. In the Control Builder, verify that the red triangle on the IED does not appear.
IED and CI868 IED are in GOOSE communication with new signal.
9ARD171384-600 283
Addition of New GOOSE Signal between CI868 and an IED Section 3 Handling the Changes at
284 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning
9ARD171384-600 285
Modification in Name at Different Levels Section 3 Handling the Changes at Different Levels of
4. Open Substation Configuration Diagram. Select the IED and change its name
in Properties window.
286 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning
6. Open CCT and notice that the new IED name is effective.
9ARD171384-600 287
Modification in Name at Different Levels Section 3 Handling the Changes at Different Levels of
10. Rename the Bay and IED in PCM 600 tree structure.
This is because the IED name is changed irrespective of the OPC Server.
16. Rename the IED in CET configuration and upload the SCD file.
17. Update configuration and download to OPC Server.
288 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning
If the name of the Logical Nodes is customized, save the configuration before
importing the new SCD file. The changes may not be recovered after the import.
9ARD171384-600 289
Replace Burnt Out IED with New One Section 3 Handling the Changes at Different Levels of
290 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning IED
3. Open PCM 600 and download IED application logic using CAP531.
4. Open Signal Matrix and download.
5. Open Parameter setting tool from context menu and select to download all the
parameters.
6. Download Graphical Display.
7. New IED is in Operation now.
9ARD171384-600 291
IED Application Logic Change Section 3 Handling the Changes at Different Levels of Engineering
For more information on the Function block that corresponds the respective IEC
61850 LN, refer to the IED user manual.
For situation (a), open PCM 600 and then the application logic. Do the required
modification, compile and download to the IED.
292 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Alarm and
9ARD171384-600 293
Alarm and Event Related Modification Section 3 Handling the Changes at Different Levels of
2. Select the LN which contains the signal. Open the properties of the signal.
3. This signal generates an alarm and event based on the Indication event
'TripSignalFromGeneral".
294 9ARD171384-600
Section 3 Handling the Changes at Different Levels of Engineering and Commissioning Alarm and
9ARD171384-600 295
Alarm and Event Related Modification Section 3 Handling the Changes at Different Levels of
When there is a trip condition for this signal, alarms/events are displayed according
to the configuration.
296 9ARD171384-600
Index
A T
About 7 Terminology 11
About This Book 7
Addition of a LN 264 W
Addition of a New Third Party IED 269 Warning, Caution, Information, and Tip Icons 10
Addition of New GOOSE Signal 277
Addition of New Signal 275
Alarm and Event Related Modification 293
Assumption 8
C
Classification 17
Communication Engineering in CCT 119, 160
I
IED Application Logic Change 291
Inputs Required 22
Introduction 15
M
Methodology/Approach 9
Modification in Name 285
O
OPC Server Configuration 221
R
Replace Burnt Out IED 290
S
Sample Inputs 23
Single Line Diagram 24
9ARD171384-600 297
Index
298 9ARD171384-600
Contact us
9ARD171384-600
www.abb.com/800xA
www.abb.com/controlsystems All rights reserved.