1 Astm C172.

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Testing fresh concrete

in the field
By Kim Basham

Proper testing benefits the contractor, ready mix producer, and owner

STM standards define pre- concrete to be accepted. In either ing and nonagitating equipment.

A cise procedures for per-


forming field tests to deter-
mine the quality of freshly mixed
case, poor testing penalizes the
contractor, ready mix producer,
and owner. Understanding the
Obtain composite samples by sam-
pling the concrete at least twice as
the middle portion of the batch is
concrete. Usual field tests measure scope, significance, and procedure discharged. Mix the samples into
consistency, strength, unit weight, of each test for fresh concrete is the one sample for testing. Obtain
air content, and temperature (see first step to achieving accurate re- samples randomly. Do not base
box). Many test details may seem sults. sample selection on concrete ap-
trivial, even arbitrary. However, pearance, convenience, or other bi-
ASTM standards establish unifor- Sampling fresh concrete ased criteria.
mity in the testing methods. By al- Follow procedures given in Usually concrete is sampled as
ways performing tests the same ASTM C 172 to ensure the sample it’s discharged from the mixer and
way, it’s possible to detect changes is truly representative of the fresh- transported to the forms. Some
in fresh concrete that could affect ly mixed concrete being tested. specifications may require other
concrete performance. Improper This standard gives procedures for points of sampling, such as at the
testing or even deviating from obtaining and handling composite discharge of a concrete pump line.
standard test methods may cause samples from stationary, paving, Concrete tested at these discharge
good concrete to be rejected or bad and truck mixers, and from agitat- points is not suitable for making

Figure 1. Slump is the difference between the height of the mold and height of the “true” slump. Shear slump indicates a lack of
cohesion. Collapse slump indicates a lean, harsh, or very wet mix (Ref. 1)
• Molding of strength Tips for
specimens must begin Proper Sampling
within 15 minutes after ■ Obtain at least two samples to
making the composite make a composite sample.
sample.
■ Do not take samples from the
It’s important to care-
very first or last portions of the
fully observe these time
batch.
restrictions to achieve the
most accurate test results. ■ Take samples after all water
This may be difficult on and admixtures have been
some jobs. To minimize added to the mix.
the elapsed time between ■ Carefully observe time limita-
obtaining samples and tions to ensure results of field
performing tests, mix the tests are consistent.
composite sample, and
test and mold specimens ■ Protect samples from sun,
as close as possible to the wind, rapid evaporation, and
point of sampling. c ontamination.
Specifications usually
indicate the number of Slump
tests to be made. Howev- The slump test (ASTM C 143)
Figure 2. Remove the slump mold uniformly; don’t
e r, ASTM C 94 requ ires m e asures concrete consistency, or
use a twisting or jerking motion. Note lines on mold air content, slump, and the ability of fresh concrete to flow.
marking heights of equal volume. temperature at the time Slump is commonly mistaken as a
of placement and as nec- measure of workability—the ease
essary for control checks. in which fresh concrete can be
acceptance tests for consistency, air ASTM C 94 also states placed, consolidated, and finished.
content, or potential strength. The these tests shall be made when
manipulation of concrete during specified and always when
pumping can significantly change strength specimens are made.
mix characteristics. When sam- It’s a good, but not required,
pling from a discharge stream, di- practice to run a unit weight
vert the discharge into the sample test every time strength speci-
container. Do not cause segrega- mens are made.
tion by restricting concrete flow Composite samples used to
from the mixer or chute. Regulate make specimens for strength
the discharge rate of tests must be larger than 1 cu-
revolving-drum truck mixers by bic foot. A strength test con-
slowing the rate of drum revolu- sists of the average compres-
tion, rather than by adjusting the sive strength of two cylinders.
gate opening size. Since ASTM C 94 requires
ASTM C 172 imposes three time that slump, air content, and
limitations on the technician: temperature tests be per-
formed whenever strength
• Elapsed time between obtaining specimens are made, obtain a
the first and last portions of the sample large enough to make
composite sample is 15 minutes. all the tests. ASTM allows
• Tests for slump or air content smaller samples for routine
must begin within 5 minutes af- air content, slump, and tem-
perature tests. Figure 3. Always lift filled molds carefully from
ter obtaining the final portion of the bottom with a large trowel to avoid
the composite sample. distorting the mold.
slump, the plus tolerance is 0 inch- slump loss.
es.
When the specifications for Concrete test Cylinders
slump are not written as a “maxi- ASTM C 31 covers making, cur-
mum” or “not to exceed” require- ing, protecting, and transporting
ment, ASTM C 94 tolerances are: concrete test specimens under field
Specified Slump Tolerances conditions. Procedures for com-
pression strength testing of these
2 inches and less ±1⁄2 inch
cylinders are described in ASTM C
More than 2 inches 39.
through 4 inches ±1 inch Concrete cylinders are made
More than 4 inches ±11⁄2 inch and tested for two different pur-
poses. Cylinders taken into the lab-
Slump tests are quite sensitive to oratory the day after casting and
variations within the test proce- stored under standardized mois-
Figure 4. Carefully finish the top of dures given by ASTM C 143. It’s ture and temperature conditions
cylinders with a tamping rod or,
preferably, a wood float. not uncommon for different tech- until tested are used to evaluate
nicians to measure slumps that dif- the quality of concrete as delivered
fer by as much as 1 inch for the to the job. These test results are
Though consistency and workabil- same concrete (Ref. 1). Therefore, used to determine compliance
ity are closely related, only consis- carefully observe the testing proce- with strength specifications. Cylin-
tency is considered a fundamental dures to minimize variations. ders field cured under job condi-
property of the fresh concrete. tions can indicate strength of in-
Workability must be related to the place concrete at a given time.
type of construction and placing Tips for Proper Slump Testing Tests of these cylinders are some-
and finishing methods. ■ Dampen the mold and perform times used to determine when to
The slump test is a quality-con- the test on a level, moist, non- remove formwork and shoring.
trol test because changes in the absorbent, rigid base. Plywood The standard 6-inch-diameter,
measured slump indicate changes is not acceptable since its sur- 12-inch-high test cylinder is used
in mix proportions, mixing proce- face rapidly becomes rough when the maximum size aggre-
dures, or other factors affecting the and uneven when exposed to gate does not exceed 2 inches.
nature of fresh concrete. Figure 1 moisture. Use a 16- to When the maximum size aggre-
shows three distinct types of 2 0-gage metal sheet over a
slumps. True slump is a general wood base or a premanufac-
subsidence of the mass without tured metal base. Do not run
breaking up. Shear slump usually the test on the tailgate of a
indicates a lack of cohesion, and pickup truck.
commonly occurs with harsh mix-
■ Fill mold in three layers, each
es. Collapse slumps generally indi-
about 1⁄3 the volume of the
cate a lean, harsh, or more likely,
mold, and uniformly rod each
very wet mix. Of course, improper
l a y e r. Paint stripes around the
testing can also cause concrete to
outside of the mold 25⁄8 and 61⁄8
shear or fall away.
inches from the bottom to help
It’s important to know the toler-
determine depths for equal
ance on measured slump before
volumes (Figure 2).
making a test. When project speci-
fications state a “maximum” or ■ Remove the mold by lifting it
“not to exceed” slump require- uniformly in 3 to 7 seconds.
ment, ASTM C 94 sets a 11⁄2-inch- Don’t use a twisting or jerking
minus tolerance for specified motion (Figure 2). Figure 5. Use a flat plate of glass or
slumps of 3 inches or less and a ■ Complete the test within 2 ⁄21 metal (at least 1/4 inch thick) to strike
21⁄2-inch-minus tolerance other- off and finish the concrete when
minutes to avoid the effects of running a unit weight test.
wise. Whatever the specified
port to avoid shifting of the fresh ■ Use a curing box that secures
concrete. Leave the molds undis- and cushions test cylinders
turbed for 24 ± 8 hours, maintain- during transport to the lab.
ing them at 60° to 80° F. During ini-
tial storage, every 10° F increase in Unit weight
concrete temperature can reduce Aggregate amount and relative
the compressive strength by as density, air content, and water and
much as 300 psi (Ref. 2). Compres- cement contents determine the
sive strength can be reduced by as unit weight of fresh concrete. Unit
much as 50% if the test cylinders weight for conventional concrete
freeze. Properly constructed curing can vary from 140 to 150 pounds
boxes are ideal for maintaining per cubic foot when measured ac-
curing conditions for the initial cording to ASTM C 138. Slight
storage period. changes in batch weights or air
Don’t demold cylinders if trans- content can be detected by this
porting them to the lab within 48 simple test. An increase in water
hours after molding. Cylinders content, decrease in cement con-
transported after 48 hours are de- tent, or an increase in air content
Figure 6. Not tapping the sides of the molded after 24 ± 8 hours and
bowl during the pressurization stage of will cause a measurable reduction
an air test will cause the air content placed in saturated lime water at in the unit weight of fresh concrete.
reading to be lower than the true value. 70° to 76° F until transported. Pro- A unit weight variation of more
tect test cylinders from jarring, than 1 pound per cubic foot proba-
bouncing, moisture loss, freezing, bly indicates changes in the con-
and direct sun during transporta- tents of the mix.
gate exceeds 2 inches, the sample tion. Expect low breaks for cylin- Tips for Proper Unit
must be wet sieved, or a cylinder ders tossed into the bed of a pick- Weight Testing
with a diameter three times the up truck and bounced about on
■ Recalibrate (determine the vol-
maximum size aggregate is used. the way to the lab.
Unless required by project specifi- ume) of the measuring con-
cations, don’t use cylinders smaller tainer at least once a year.
Tips for Proper Compression
than 6 inches in diameter. Place strength Testing ■ When rodding to consolidate
concrete in the standard cylinder ■ Mold cylinders on a level base the concrete, tap the sides of
mold in three equal layers, and with the axis of the mold verti- the container sharply with a
consolidate by rodding or vibrat- cal to avoid sloping ends. mallet 10 to 15 times after rod-
ing. Rod concretes with slumps ding each layer to close voids
greater than 3 inches, rod or vi- ■ After rodding each layer, tap left by the tamping rod. Vo i d s
brate concretes with slumps of 1 to the outside of the cylinder with cause the measured unit
3 inches, and vibrate concretes a mallet to close any holes left weight to be lower than the
with slumps less than 1 inch. by the rod. Rod holes or voids true value.
ASTM C 31 gives additional de- cause low cylinder breaks.
■ In the final filling of the con-
tails for properly placing and con- ■ Avoid overfilling of the last lay- t a i n e r, if it is necessary to add
solidating the concrete. Almost er because a concentration of or remove material, use con-
any deviation from the standard large aggregate at the top of crete, not mortar, so the por-
will reduce the apparent concrete the cylinder may occur. tions remain the same.
strength.
Seal the top of cylinder molds ■ Finish the top of cylinders ■ Use a flat plate of glass or
immediately after striking off to carefully with a tamping rod or, metal (at least 1/4 inch thick)
prevent moisture evaporation, p r e f e r a b l y, a wood float to strike off and finish the con-
then label and move to storage. (Figure 4). crete (Figure 5). A tamping
Lift filled molds carefully from the ■ After making cylinders, store rod, trowel, float, or straight-
bottom with a large trowel to them on a level, vibration-f r e e edge will leave high spots, re-
avoid mold distortion (Figure 3). base and maintain proper tem- sulting in a high estimate of
Keep molds vertical during trans- peratures. unit weight.
■ After strike off, clean excess so air bubbles will not stick to NVLAP-accredited (or equivalent)
concrete from the exterior of the cover and be difficult to testing laboratory that employs
the measuring container. dislodge. American Concrete Institute
(ACI)-certified technicians. The
■ When pressurizing the bowl,
Air content by the pressure National Institute of Standards
tap its sides with a mallet 10 to
method and Technology operates NVLAP
15 times to help particles of
Air tests cannot distinguish be- (National Voluntary Laboratory,
concrete move to find equilibri-
tween larger air pockets and very Accreditation Program). NVLAP
um with the new pressure
fine bubbles that improve frost re- accreditation means the testing lab
(Figure 6). Not tapping the
sistance. Unless set by the project has successfully passed an on-site
bowl at this point in the test will
specifications, ASTM C 94 gives a assessment of facilities, including
cause the air content reading
± 1.5% tolerance from the specified competence of the staff, and is par-
to be lower than the true
value when concrete is sampled at ticipating in an ongoing proficien-
value.
the point of discharge from the cy testing program. ACI-certified
transportation unit. technicians have passed written
Temperature
The ASTM C 231 procedure to and field performance examina-
Because of the important influ- tions to obtain the Concrete Field
measure air content of freshly
ence temperature has on the prop- Testing Technician—Grade I Certi-
mixed concrete observes the
erties of fresh and hardened con- fication. Using an accredited lab
change in volume of concrete with
crete, many specifications place and certified technicians helps as-
a change in pressure. This change
minimum and maximum limits on sure proper testing.
in volume is assumed to be caused
fresh concrete temperature. Tem- NVLAP publishes an annual
entirely by compression of the air
perature primarily affects rate of “Directory of Accredited Laborato-
in the concrete. Voids in the aggre-
hydration, which influences prop- ries,” that lists all accredited labs
gate affect the result of an air test
erties such as slump loss, setting and specific tests for which they
based on pressure, resulting in a
and finishing times, and rate of are accredited. It’s available from
higher air content than the true
strength gain. Fresh concrete tem- National Technical Information
value. Consequently, the pressure
perature also affects the perfor- Service, (NTIS), 5285 Port Royal
method is most applicable for con-
mance of admixtures (especially Rd.,, Springfield, VA 22161.
cretes made with relatively dense
the effectiveness of air-entraining
aggregates. Use the volumetric
agents) and resistance to early-age References
method, ASTM C 173, for concrete
freezing during cold weather. 1. S. Mindess and J. F. Young, Con-
made with lightweight aggregates crete, Prentice-Hall Inc., Englewood
or aggregates with high porosity. Cliffs, NJ, 1981.
Tips for Proper
2. ACI Committee Report 305, “Hot
Temperature Testing Weather Concreting,” ACI, Detroit.
Tips for Proper Air Testing
■ The sensor of the temperature
■ When rodding is used to con-
measuring device must have
solidate the concrete, tap the Kim Basham Ph. D., P.E. is director
at least 3 inches of concrete
sides of the air bowl sharply of engineering for CTC-G E O T E K ,
cover in all directions.
10 to 15 times with a mallet af- D e n v e r, Colo., a testing and engi-
ter rodding to close voids left ■ Leave the measuring device in neering firm specializing in fore n-
by the tamping rod. Vo i d s concrete for at least 2 minutes sic-type work. He also is an instruc-
cause a higher air content or until temperature reading tor for the ACI Concrete Field Testing
reading than the true value. stabilizes. Technician—Grade I cer t i f i c a t i o n
program.
■ If vibration is used (for slumps ■ Take temperature within 5 min-
less than 3 inches), be careful utes of obtaining sample and
not to overvibrate causing air record to nearest degree.
content readings to be lower
than the true value. Use an accredited testing
lab
■ The internal surface of the
bowl and cover need to be To receive the benefits of proper PUBLICATION #C930550
clean and wet before the test, testing, owners, engineers, and Copyright © 1993, The Aberdeen Group
contractors should use a All rights reserved

You might also like