Professional Documents
Culture Documents
Beri FINALS
Beri FINALS
Beri FINALS
Protective Relay
• A relay is automatic device which
senses an abnormal condition of
electrical circuit and closes its General requirements. The dc
contacts. These contacts in turns system, consisting of a station
close and complete the circuit battery, chargers and dc
breaker trip coil circuit hence make distribution panels, provides a
the circuit breaker tripped for continuous and reliable source
disconnecting the faulty portion of of dc control voltage for system
the electrical circuit from rest of the protection during normal
healthy circuit. Selection of relays operation and for emergency
and coordination of their settings so shutdown of the power plant.
that the correct circuit breaker trips Battery will be nominal 125
when it is supposed to, and does not volts, mounted on wooden
trip when it is not supposed to is a racks or metal racks with PVC
subject too broad to be covered covers on the metal supporting
herein. For the purpose of this surfaces. Lead calcium cells
document the listings below will set having pasted plates or other
forth those protective relay types suitable cells will be considered
which will be considered. For the for use.
relay, using IEC or IEEE standards are Duty cycle. Required capacity
widely used in today’s engineering. will be calculated on an 8-hour
duty cycle basis taking into
Emergency power system account all normal and
• Those portions of the station service emergency loads. The duty
load that must be operable for a cycle will meet the
safe shutdown of the unit, or that requirements of the steam
are required for protection of the generator burner control
unit during shutdown, will be fed system, emergency cooling
from a separate 480-volt unit systems, control bench board,
emergency power bus. A suitable relays and instrument panels,
emergency diesel engine driven emergency lighting system, and
generator will be installed and all close/trip functions of the
arranged to start automatically and medium voltage and 480-volt
carry these loads if the normal circuit breaker systems.
source of power to this bus is lost. Battery chargers.
The loads fed from this bus might Two chargers capable of
include such things as emergency maintaining a 2.17 the
lighting, communication system, proper float and equalizing
battery charger, boiler control voltage on the battery will
system, burner control system, be provided. Each charger
control boards, annunciator, will be capable of restoring
recorders and instrumentation. the station battery to full
Design of these systems will provide charge in 12 hours after
for them to return to operation after emergency service
a brief power outage. discharge. Also, each unit
will be capable of meeting
• Battery and charger.
50 percent of the total dc 6. Temperature meter with selector
demand including charging switch for stator temperature
current taken by the detectors
discharged battery during 7. D.C. volmeter for excitation voltage
normal conditions 8. D.C. ammeter for field current
Battery room. Only the battery
will be located in a ventilated b. Stepup transformer.
battery room. The chargers 1. Voltmeter on high voltage side with
maybe wall or floor mounted, selector switch
together with the main dc 2. Ammeter with selector switch
distribution panel, immediately 3. Wattmeter
outside the battery room. 4. Varmeter
DC distribution panel. The 5. Power factor meter
distribution panel will utilize
molded case circuit breakers or c. Auxiliary transformer.
fuses selected to coordinate 1. Switch
with dc breakers furnished in 2. Voltmeter on low voltage side with
control panels and switchgear. selector
The breakers will be equipped 3. Ammeter with selector switch
with thermal magnetic trip 4. Wattmeter
devices, and for 20 kA dc 5. Varmeter
interrupting rating. 6. Power factor meter
All the instant the motor is started, the 2. It is not inherently self-starting. It
rotor is not turning. The friction and has to be run up to synchronous
windage loss in therefore zero. However, speed by some means, before it can
the iron loss at starting will be greater be synchronized to the supply.
than the normal operating value because
the rotor frequency is the same as the 3. It is capable of being operated
stator frequency. under a wide range of power
factors, both lagging and leading.
Furthermore, if the blocked rotor test Hence, it can be used for power
had been made at rated voltage, the stator factor correction purposes.
current with the rotor blocked would have
been equal to (Vrated/Vbr) x Ibr and the
Two factors determine the speed of SM
power input w/ rotor blocked would have
1. The frequency of the supply source
been (Vrated/Vbr)² x Pbr w/ there ie is
2. The number of poles in the machine
possible to calculate the starting.
Advantages of Synchronous Motor
1. They can be made to operate at the
Module 4 - Synchronous Motor leading pf and thereby improve the
pf of an industrial plant from one
Synchronous Motor
that is normally lagging to one that
- Operates at an absolutely average
is close to unity.
constant speed regardless of the
load: it departs from this average
2. They are less costly in certain
speed only during load changes. The
horsepower and speed ranges.
regulation of this type is therefore
zero.
3. They usually operate and
- It is electrically identical with an
constructed at higher efficiency
alternator, when driven
especially in the low-speed unity pf
mechanically or as a motor, when
ranges. Synchronous motors are
driven electrically. Most
frequently used for pf correction
synchronous motors are rated
purposes only.
between 150KW to 15MW and run
at speeds ranging from 150 to
1800rpm. Synchronous Condenser/ Capacitor
C. Voltage Regulation
- The voltage regulation at the
end of a long transmission line
varies greatly especially when
large inductive loads are
present. When an inductive
load is disconnected suddenly,
voltage tends to rise
considerably above its normal
value because of the line
capacitance.
- By installing a synchronous
motor with a field regulator (for
varying its excitation), this
voltage rise can be controlled.
EE 14 that receiving end voltage (VR) of
the line is generally less than the
Transmission line
sending end voltage (VS).
- Has three constants R, L and C - The difference in voltage at the
distributed uniformly along the receiving end of a transmission line
whole length of the line. **between conditions of no load
Resistance and Inductance form the series and full load
impedance - Is the rise in voltage at the receiving
end, expressed in percent of full
The Capacitance existing between load voltage, when full load at a
conductors for 1-phase line or from a specified power factor is removed
conductor to neutral for a 3-phase line while the sending-end voltage is
forms a shunt path throughout the length held constant
of the line.
Shunt conductance
Capacitance effects introduce
complications in transmission line - It represents the conductance
calculations. between conductors or between
conductor and ground and accounts
Short transmission line for the leakage current at the
- When the length of an overhead insulators. It is very small in case of
transmission line is up to about 50 overhead lines and may be assumed
km and the line voltage is zero.
comparatively low (< 20 kV) Transmission efficiency
- When the length of an overhead
transmission line is about 50-150 - The power obtained at the receiving
km and the line voltage is end of a transmission line is
moderately high (>20 kV < 100 kV) generally less than the sending end
- When the length of an overhead power due to losses in the line
transmission line is more than 150 resistance.
km and line voltage is very high (> - The ratio of receiving end power to
100 kV) the sending end power of a
transmission line.
While studying the performance of a
transmission line, it is desirable to End Condenser Method
determine its voltage regulation and - In this method, the capacitance of
transmission efficiency. the line is lumped or concentrated
Voltage Regulation at the receiving or load end.
- Limitations:
- When a transmission line is carrying o There is a considerable error
current, there is a voltage drop in (about 10%) in calculations
the line due to resistance and because the distributed
inductance of the line. The result is capacitance has been
assumed to be lumped or Service Switch
concentrated.
- A disconnecting means or
o This method overestimates
"disconnect switch" must be
the effects of line capacitance
provided in the service entrance to
Nominal T Method disconnect all the wiring in the
building from the electrical power
- In this method, the whole line
supply. This may be accomplished
capacitance is assumed to be
with a separate switch called a
concentrated at the middle point of
service switch or main disconnect.
the line and half the line resistance
Many years ago, it was common to
and reactance are lumped on its
install a separate switch next to the
either side.
fuse box to shut the power off. In
Nominal pi Method modern residences, the service
- In this method, capacitance of each switch is actually the main breaker
conductor (i.e., line to neutral) is housed inside the breaker box
divided into two halves; one half which shuts off power to all the
being lumped at the sending end other breakers in the box.
and the other half at the receiving - The size of the service switch or
end. main breaker depends on the
electrical load served. Service
Classification of Transmission lines switches come in standard sizes of
- Short transmission lines 30, 60, 100, 150, 200, 400 and
- Medium transmission lines larger. The National Electrical Code
- Long transmission lines requires a minimum 100-amp
service size for all residences,
EE 15 – FINALS although many newer houses
Metering typically use a 150 amp or larger
service.
Service Entrance
Service Panel
- is where the wires connected to the
load side of the meter enter the - The National Electrical Code
house or building. The service requires electrical services to have a
entrance in a residence is commonly service entrance panel commonly
thought of as a breaker or fuse box. called a breaker or fuse box. A
In larger more complicated modern service entrance panel
commercial or industrial electrical consists of an enclosure housing the
systems, the service entrance may breakers or fuses and associated
be a main disconnect panel or a wiring. If located outside, the
trough where up to six main enclosure must be weatherproof
switches are present. which keeps rain and moisture from
interfering with the electrical parts.
The breakers or fuses protect the required in front of the smaller
wires leaving the breaker box from disconnects.
overloading and being damaged.
- A ground wire connects inside the
service entrance panel to the
neutral connections to provide a
Branch Circuits
ground for the customer's service.
The ground wire extends to below - A branch circuit is defined as that
ground level where it attaches to a part of an electric circuit extending
ground rod. The ground rod serves beyond the last circuit breaker or
as an easy path for lightning to get fuse. The branch circuits start at the
into the earth if it strikes the utility breaker box and extend to the
line or the customer’s electrical
electrical devices connected to the
service.
service. Branch circuits are the last
Large Services part of the circuit supplying
electrical devices. These circuits are
- For large customers such as classified in two different ways,
apartment buildings or commercial according to the type of loads they
and industrial customers the service serve or according to their current-
can become more complicated. In carrying capacity.
these systems, the National
Electrical Code allows up to six
separate disconnects for each
electrical service as long as they are
grouped together.
- An example would be an apartment
complex where each electrical
service provided power for six
apartments. It would be common
for the service drop to be connected
to six separate disconnect switches,
each controlling an individual
apartments' electrical service. The
electrical wires from one disconnect
switch are connected to an electrical
meter to measure that particular
apartments' energy use and then
wires run from the meter to the
breaker or fuse box in the
corresponding apartment.
- If there are more than six electrical
disconnects, a main disconnect is
- Switchgear is electrical equipment
that is used to protect, control, and
isolate electrical equipment in
power systems. It works by
interrupting or isolating electrical
circuits when a fault occurs,
EE 15 preventing damage to equipment
Switch Gear and minimizing the risk of electrical
hazards.
Switchgear - Switchgear typically includes
- Switchgear is a general term switches, fuses, circuit-breakers,
covering switching devices and their relays, and other components that
combination with associated are used to control and protect
control, measuring, protective and electrical power systems. When a
regulating equipment, also fault occurs, the switchgear detects
assemblies of such devices and it and isolates the faulty
equipment with associated component or circuit to prevent
interconnections, accessories, damage to other parts of the
enclosures and supporting system.
structures, intended in principle for - Switchgear also helps to control the
use in connection with generation, flow of electricity in the system,
transmission, distribution and allowing operators to switch
conversion of electric energy circuits on and off and control the
[Source: IEC 60947-1-2020]. power output of generators.
Additionally, it can provide backup
Main Components of Switchgear power to critical systems in the
Circuit-breakers event of a power outage or other
Residual current devices emergency.
Isolators - Switchgear can be found in a wide
Fuse-combination units range of settings, from power plants
Switches and substations to industrial
Surge protective devices facilities and commercial buildings.
Contactors It plays a crucial role in ensuring
Motor-starters the safe and reliable operation of
electrical power systems.
Protective relays
Transformers
Disconnectors Switchgear Types
Switch-disconnectors
1. High-Voltage Switchgears
Busbars - High-voltage switchgear is designed
How Does Switchgear Work? to operate at voltages above 52 kV
AC. It is typically used in power medium maybe oil, SF6, and
transmission and distribution vacuum.
systems, as well as in large industrial
facilities such as chemical plants and 3. Low-Voltage Switchgear
refineries. - Low-voltage switchgear is used in
- High voltage circuit-breakers (such power systems with voltage levels
as SF6 circuit-breaker or vacuum below 1000 V AC or 1500 V DC. It is
circuit-breaker) are the main typically used in residential and
component of HV switchgear. Hence commercial applications and plays a
high voltage circuit-breaker should crucial role in controlling and
have special features for safe and protecting the electrical equipment
reliable operation. in these environments. The key
- Faulty tripping and switching components of low-voltage
operation of high voltage circuit- switchgear include circuit-breakers,
breakers are comparatively very fuses, switches, relays, and
rare. Most of the time these circuit- transformers.
breakers remain at ON condition
Is there a Difference Between Switchgear
and may be operated after a long
and Switchboards?
period of time. So Circuit-breakers
must be reliable enough to ensure - Yes, there is a difference between
safe operation, as when required. switchgear and switchboards.
Switchboard is an assembly of switchgear
2. Medium-Voltage Switchgear with or without instruments, but the term
- Medium-voltage switchgear is does not apply to groups of local switches
designed to operate at voltages in final circuits.
between 1 kV and 52 kV [2] AC.
- Medium voltage switchgear is Switchgear refers to the electrical
mainly used for the distribution of equipment that is used to control, protect,
electrical energy connected to and isolate electrical power systems. It
various electrical networks. They typically includes components such as
include most of the substation circuit-breakers, fuses, switches, and
equipment such as minimum oil relays, and is designed to operate at high
circuit-breakers, bulk oil circuit- voltages and currents.
breakers, air magnetic, SF6 gas- Switchboards are typically low-voltage
insulated, vacuum, and gas- distribution boards that are used to
insulated switchgear. distribute power to various electrical loads
- They may metal-enclosed indoor within a building or facility. They usually
type, metal-enclosed outdoor type, consist of panels with multiple switches,
outdoor type without a metal fuses, and other protective devices, as well
enclosure, etc. The interruption as metering equipment to monitor power
usage.
Switchgear and switchboards are used to Ambient air temperature is that existing in
control and distribute electrical power, the vicinity of the equipment if supplied
switchgear is typically used in high-voltage without enclosure, or in the vicinity of the
applications such as power generation and enclosure if supplied with an enclosure.
transmission, while switchboards are used
Equipment intended to be used in ambient
in low-voltage applications such as
air temperature above +40 °C (e.g. in
commercial and industrial buildings.
forges, boiler rooms, tropical countries) or
below –5 °C (e.g. –25 °C, as required by IEC
61439 (all parts) for outdoor installed low-
voltage switchgear and controlgear
How Can I Extend the Life of My assemblies) shall be designed and used
Switchgear? according to the relevant product standard
Electrical switchgear is an important or, where applicable, according to an
component of electrical power systems, agreement between manufacturer and
and its proper maintenance is essential for user. Information given in the
ensuring the safe and reliable operation of manufacturer’s documentation may take
the system. the place of such an agreement.
Here are some ways to extend the life of NOTE – Ambient air temperature(s) for
your switchgear: certain types of equipment, e.g. circuit-
breakers or overload relays for starters, is
Regular maintenance.
indicated in the relevant product standard.
Use recommended operating
procedures. Altitude.
Upgrades and retrofits. - The altitude of the site of
Training and education. Provide installation does not exceed 2 000
training and education to your m.
personnel who operate and - For equipment to be used at higher
maintain the switchgear. altitudes, it is necessary to take into
Monitoring and testing. account the reduction of the
Normal Service Conditions dielectric strength and the cooling
Ambient air temperature. effect of the air. Electrical
equipment intended to operate
The ambient air temperature - under these conditions shall be
does not exceed +40 °C designed and used in accordance
its average over a period of 24 h with an agreement between
does not exceed +35 °C. manufacturer and user. Information
The lower limit of the ambient given in the manufacturer’s
air temperature is – 5 °C. documentation may take the place
of such an agreement.
Humidity.
- The relative humidity of the air does
not exceed 50 % at a maximum
temperature of +40 °C. Higher
relative humidities may be
permitted at lower temperatures,
e.g. 90 % at +20 °C. Special
measures may be necessary in cases
of occasional condensation due to
variations in temperature.