Beri FINALS

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 31

EE 16

Module 6 – Protective It is required to have an early detection


Equipment and localization of faults, and then,
prompt removal from service of faulty
Protective Equipment equipment, for the purpose of:
- It is Equipment applied to electric  To safeguard the entire system to
power systems to detect abnormal and ensure continuity of supply.
 To minimize damage and repair
intolerable conditions and to initiate
costs.
appropriate corrective actions.
 To ensure safety of personnel.
- These devices include lightning
arresters, surge protectors, fuses, and Two Technology – Fuse and Protection
relays with associated circuit breakers, relays
reclosers, and so forth. - Fuse
- are applied commensurately with the • were commonly used as a
degree of protection desired or felt protection against overcurrent and
necessary for the particular system. overloads in the past and are still
very popular in some countries they
Protective devices must therefore be
are still used in LV installations and
installed on power systems: in MV cables and transformers with
- to ensure continuity of electrical rated power up to 630-1250 kVA.
service
- to limit injury to people - Protection relays
• being more reliable and accurate
- to limit damage to equipment when
and with the ability to detect other
problem situations develop.
type of faults than overloads and
All units of mechanical and electrical overcurrent that can occur in
parameters and their multiples and networks and equipment.
submultiples that are involved in the • The protective relay or simply relay
protection systems are in accordance has this specific functionality, they
with: are set to operate, and initiate
tripping, when a fault condition is
- SI (International Units System); detected.
- exceptions are made when hours (h)
may be used instead of seconds (s) Each power system protection scheme is
- temperature is °C (Celsius). made up from the following components:
 Fault detecting or measuring relays
Protection devices  Tripping and other auxiliary relays
- In order to minimize the time of a fault  Circuit breakers
switchgears and equipment are  Instrument transformers – current
provided with ___________ to detect (CT) and voltage (VT)
them and to isolate the faulty part of
Protection
installation.
- the branch of electric power - Protection is arranged in zone, which
engineering concerned with the should cover the power system
principles of design and operation of completely, having no part
equipment called ‘relays’ or ‘protective unprotected. When a fault occurs, the
relays’ that detects abnormal power protection is required to select and trip
system conditions and initiates the only the nearest circuit breaker.
corrective action as quickly as possible Stability
in order to return the power system to - This term, applied to protaection on
its normal state. distinct from power network, refers to
the ability of the system to remain inert
Quickness of response to all load conditions and fault external
- is an essential element of protective to the relevant zone.
relaying systems – response times of Speed
the order of a few milliseconds are - The function of automatic protection is
often required. to isolate fault from the power system
in a very much shorter time than could
Fundamentals of Power system be isolated manually, even with great
protection deal of supervision
- The nature of relaying Sensitivity
- Sensitivity is a term frequently used
Characteristics of protective system when referring to the minimum
- Reliability operating limit of a complete protective
- Selectivity system. A protective system is said to
- Stability be sensitive if the primary operating
- Speed current is low.
- Sensitivity
Protective devices are selected and
Protective relaying assigned to protect a specific part of the
- is an important requirement in power power system
generation, transmission and
distribution, which identifies the exact Primary zone of protections
location of the fault and gives - Responsibility of the protection device
command for isolating the faulty
portion very close to the fault by Backup or overreached zone
sensing variations in electrical - The overlapping of zones allows a
quantities for ensuring safe operation. protective device to provide backup
protection to the adjacent zone
Reliability
- The protective relay should operate Backup protection
positively and isolate the faulty portion - is intended to operate only when the
of the power system as and when primary protection fails to clear the
required. A reliable relaying system fault.
must be dependable and secure.
Selectivity Backup (defined by IEEE)
- protection that operates independently 3. Relay
of specified components in the primary - This convert the signal from a
protective system monitoring devices and give
instructions to open a circuit under
faulty conditions or to give alarms
when the equipment being protected is
approaching towards possible failure.
4. Transducers
- Commonly known as the Instrument
Transformer, current and potential
Elements of a protection system
transformer. The function of current
and potential transformers (collectively
known as transducers) is to transform
power system currents and voltages to
lower magnitudes, and to provide
galvanic isolation between the power
network and the relays and other
instruments connected to the
transducer secondary windings.

1. Battery and DC supply Factors which influence design of a


- Since the primary function of a protective system
protection system is to remove a fault, - Industry Standards
the ability to trip a circuit breaker • The Institute of Electrical and
through a relay must not be Electronic Engineers (IEEE) and
compromised during a fault, when the other organization provides industry
AC voltage available in the substation standards through ANSI or IEC These
may not be of sufficient magnitude. organizations provides industry
standards through ANSI or IEC.
2. Circuit breaker These include specific standards for
- Circuit breakers of several designs can many applications.
be found in a power system, and it’s  ANSI-C37.90-1989 Relays and
name is according to the medium used Relay System Associated with
to interrupt the fault current In Electric Power Apparatus
addition, better insulating materials,  IEEE STD 242-1975
better arc quenching systems and Recommended Practice for
faster operating requirements resulted Protection and Coordination of
in a variety of circuit breaker Industrial and Commercial
characteristics: interrupting medium of Power System
oil, gas, air or vacuum; insulating - Development of Protective Relays
medium of oil, air, gas or solid • Electro-mechanical relay
dielectric; Operating mechanisms using • Solid-state relay
impulse coil, solenoid, spring–motor– • Digital relay
pneumatic or hydraulic.
- Electro Electro-mechanical relay: - Many protection relays have adjustable
st
mechanical relay (1 generation) settings. The user programs settings
• The most commonly used (pick-up levels) that allow the relay to
• Uses the induction disc principle make a decision. The relay compares
(watt-hour meter) the inputs to these settings and
• Provides individual phase responds accordingly.
protection -
- Solid state relay (2nd generation) Processes
• Characteristic curve is obtained - Once the inputs are connected and the
through use of RC timing settings are programmed, the relay
circuits compares these values and makes a
• No moving parts decision. Depending on the need,
• Used to retrofit electro- different types of relays are available
mechanical mechanical relays for different functions.
• Fast reset Outputs
• Less maintenance - The relay has several ways of
- Digital Relay (3rd generation) communicating that a decision has
• Computer Computer-based- been made. Typically, the relay will
with CPU operate a switch (relay contact) to
• Selectable characteristic curves indicate that an input has surpassed a
and protection functions setting, or the relay can provide
• Metering and control functions notification through visual feedback
• Event and/or disturbance such as a meter or LED. One advantage
recording of electronic or microprocessor relays is
• Remote communication an ability to communicate with a
• Self-monitoring network or a PLC.
Protection relay
- is a smart device that receives inputs, Power system component needs
compares them to set points, and protection:
provides outputs. Inputs can be  Generator
current, voltage, resistance, or  Transformer
temperature. Outputs can include  Bus
visual feedback in the form of indicator  Transmission line
lights and/or an alphanumeric display,  Circuit breaker
communications, control warnings,  Motor(Load)
alarms, and turning power off and on.
Generator and motor protections
Input (rotating machinery protection)
- A relay needs information from the - involves the consideration of more
system to make a decision. These possible failures or abnormal operating
inputs can be collected in a variety of conditions than any other system
ways. In some cases, the wires in the
element. Although the frequency of
field can be connected directly to the
failure, particularly for generators and
relay.
large motors, is relatively low, the
Settings
consequences in cost and system Bus
performance are often very serious. - is one of the most critical system
elements. It is the connecting point of a
• Abnormal conditions that must be variety of elements and a number of
dealt: transmission lines, and any incorrect
 Winding faults: stator – phase operation would cause the loss of all of
and ground fault these elements.
 Overload
 Over speed
 Abnormal voltages and Power Transmission line protection
frequencies. - are one of the most important systems
under electrical power system.
• For generators we must consider:
 Under excitation Transmission system
 Motoring and start-up - is a system which between the
generation and the distribution center.
• For motors we are concerned with:
 Stalling (locked rotor) Several factors we need to consider while
 Single phase protection of transmission lines:
 Loss of excitation (synchronous  Wind and Ice
motors).  Contamination
 Vandalism
Transformer Faults (or short circuits)  External forces
- are the result of internal electrical  Equipment Failures
faults, the most common one being the  System Disturbances
phase-to-ground fault. Somewhat less  Overloading of system
common are the turn-to-turn faults.  Lightning

Common Electrical protection Common transmission line protection:


 Over current  Differential Protection
 Current Differential  Phase Comparison
 Three-phase  Over Current Protection*
 Volts-per-hertz protection  Earth fault overcurrent protection
(Use for protect from large residual
Non-Electrical Protection current)
 Pressure Devices (Buchholz relay)  Distance Protection*
 Temperature devices  Thermal overload protection (Use
for underground power system)
Bus Protection (or bus differential)
- has been the most difficult protection Types of Relays
to implement because of the severity - Protective Relays – Protective relays
of an incorrect operation on the are function as to detect the fault and
integrity of the system. also to initiate the appropriate control
- signal such as the tripping signal.
- Regulating Relays – Regulating relay is 13 - Synchronous-Speed Device
a device which manages the operation 14 - Underspeed Device
of the load of tap changer on the 15 - Speed or Frequency Matching Device
transformer. 16 - Data Communications Device
- Reclosing and Synchronizing - Relays 17 - Shunting or Discharge Switch
this is a programmable relay whose the 18 - Accelerating or Decelerating Device
function is to initiate a sequence of 19 - Starting-to-Running Transition
actions leading to the automatic Contactor
reclosing of the circuit breaker. 20 - Electrically-Operated Valve ( Solenoid
- Monitoring Relays - Monitor power Valve )
supplies (voltage, current, power, 21 - Distance Relay
phase), temperatures, and other 21G - Ground Distance
analogue signals and detects 21P - Phase Distance
abnormalities in machines and 22 – Equalizer circuit breaker
equipment by determining values 23 – Temperature control device, Heater
against alarm thresholds. 24 – Volts per hertz relay
- Auxiliary Relays - these relays which 25 – Synchronizing or synchronism-check
assist other relays by applying device
supplementary actions. 26 – Apparatus thermal device,
Temperature Switch
Device number 27 – Undervoltage relay
- are used to identify the functions of 27P - Phase Undervoltage
devices shown on a schematic diagram. 27S - DC undervoltage relay
27TN - Third Harmonic Neutral
ANSI/IEEE C37.2-2008 Undervoltage
- is one of a continuing series of revisions 27TN/59N - 100% Stator Earth Fault
of the standard, which originated in 27X - Auxiliary Undervoltage
1928. 27 AUX - Undervoltage Auxiliary Input
27/27X - Bus/Line Undervoltage
1 - Master Element 27/50 - Inadvertent Energization
2 - Time-delay Starting or Closing Relay 28 - Flame Detector
3 - Checking or Interlocking Relay, 29 - Isolating Contactor
complete Sequence 30 - Annunciator Relay
4 - Master Protective 31 - Separate Excitation Device
5 - Stopping Device, Emergency Stop 32 - Directional Power Relay
Switch 32L - Low Forward Power
6 - Starting Circuit Breaker 32H - High Directional Power
7 - Rate of Change Relay 32N - Wattmetric Zero-Sequence
7F - Rate Of Change Of Frequency Relay Directional
(ROCOF) 32P - Directional Power
8 - Control Power Disconnecting Device 32R - Reverse Power
9 - Reversing Device 33 - Position Switch
10 - Unit Sequence Switch 34 - Master Sequence Device
11 - Multifunction Device 35 - Brush-Operating or Slip-ring Short
12 - Overspeed Device Circuiting Device
36 - Polarity or Polarizing Voltage Device 50/87 - Instantaneous Differential
37 - Undercurrent or Underpower Relay 51 - AC Time Overcurrent Relay
37P - Underpower 51C - Voltage Controlled Time Overcurrent
38 - Bearing Protective Device / Bearing 51G - Ground Time Overcurrent
Rtd 51LR - AC inverse time overcurrent (locked
39 - Mechanical Condition Monitor rotor) protection relay
( Vibration ) 51N - Neutral Time Overcurrent
40 - Field Relay / Loss of Excitation 51P - Phase Time Overcurrent
41 - Field Circuit Breaker 51R - Locked / Stalled Rotor
42 - Running Circuit Breaker 51V - Voltage Restrained Time Overcurrent
43 - Manual Transfer or Selector Device 51Q - Negative Sequence Time
44 - Unit Sequence Starting Relay Overcurrent
45 - Atmospheric Condition Monitor 52 – AC circuit breaker
(fumes, smoke, fire) 52a - AC circuit breaker position (contact
46 - Reverse-Phase or Phase Balance open when circuit breaker open)
Current Relay or Stator Current Unbalance 52b - AC circuit breaker position (contact
47 - Phase-Sequence or Phase Balance closed when circuit breaker open)
Voltage Relay 53 - Exciter or Dc Generator Relay
48 - Incomplete Sequence Relay / Blocked 54 - Turning Gear Engaging Device
Rotor 55 - Power Factor Relay
49 - Machine or Transformer Thermal 56 - Field Application Relay
Relay / Thermal Overload 57 - Short-Circuiting or Grounding Device
49RTD - RTD Biased Thermal Overload 58 - Rectification Failure Relay
50 - Instantaneous Overcurrent Relay 59 - Overvoltage Relay
50BF - Breaker Failure or LBB ( Local 59B - Bank Phase Overvoltage
Breaker Back-up ) 59N - Neutral Overvoltage
50DD - Current Disturbance Detector 59NU - Neutral Voltage Unbalance
50EF - End Fault Protection 59P - Phase Overvoltage
50G - Ground Instantaneous Overcurrent 59X - Auxiliary Overvoltage
50IG - Isolated Ground Instantaneous 59Q - Negative Sequence Overvoltage
Overcurrent 60 - Voltage or Current Balance Relay
50LR - Acceleration Time 60N - Neutral Current Unbalance
50N - Neutral Instantaneous Overcurrent 60P - Phase Current Unbalance
50NBF - Neutral Instantaneous Breaker 61 - Density Switch or Sensor
Failure 62 - Time-Delay Stopping or Opening Relay
50P - Phase Instantaneous Overcurrent 63 - Pressure Switch Detector
50SG - Sensitive Ground Instantaneous 64 - Ground Protective Relay
Overcurrent 64F - Field Ground Protection
50SP - Split Phase Instantaneous Current 64R – Rotor earth fault
50Q - Negative Sequence Instantaneous 64REF – Restricted earth fault differential
Overcurrent 64S – Stator earth fault
50/27 - Inadvertent Energization 64S - Sub-harmonic Stator Ground
50/51 - Instantaneous / Time-delay Protection
Overcurrent relay 64TN - 100% Stator Ground
50/74 - Ct Trouble 65 - Governor
66 - Notching or Jogging Device/Maximum 87M - Motor Differential
Starting Rate/Starts Per Hour/Time 87O - Overall Differential
Between Starts 87PC - Phase Comparison
67 - AC Directional Overcurrent Relay 87RGF - Restricted Ground Fault
67G - Ground Directional Overcurrent 87S - Stator Differential
67N - Neutral Directional Overcurrent 87S - Percent Differential
67Ns – Earth fault directional 87T - Transformer Differential
67P - Phase Directional Overcurrent 87V - Voltage Differential
67SG - Sensitive Ground Directional 88 - Auxiliary Motor or Motor Generator
Overcurrent 89 - Line Switch
67Q - Negative Sequence Directional 90 - Regulating Device
Overcurrent 91 - Voltage Directional Relay
68 - Blocking Relay / Power Swing Blocking 92 - Voltage And Power Directional Relay
69 - Permissive Control Device 93 - Field-Changing Contactor
70 - Rheostat 94 - Tripping or Trip-Free Relay
71 - Liquid Switch, Level Switch 95 – TRIP CIRCUIT HEALTHY
72 - DC Circuit Breaker 96 – Transmitter
73 - Load-Resistor Contactor 97 – For specific applications where other
74 - Alarm Relay numbers are not suitable
75 - Position Changing Mechanism 98 – For specific applications where other
76 - DC Overcurrent Relay numbers are not suitable
77 - Telemetering Device, Speed Sensor 99 – For specific applications where other
78 - Phase Angle Measuring or Out-of-Step numbers are not suitable
Protective Relay
78V - Loss of Mains Acronyms Description
79 - AC Reclosing Relay / Auto Reclose AFD - Arc Flash Detector
80 - Liquid or Gas Flow Relay CLK - Clock or Timing Source
81 - Frequency Relay CLP - Cold Load Pickup
81O - Over Frequency DDR – Dynamic Disturbance Recorder
81R - an invalid use of R suffix - refer 7F for DFR – Digital Fault Recorder
Rate Of Change Of Frequency (ROCOF) DME – Disturbance Monitor Equipment
81U - Under Frequency ENV – Environmental data
82 - DC Reclosing Relay HIZ – High Impedance Fault Detector
83 - Automatic Selective Control or HMI – Human Machine Interface
Transfer Relay HST – Historian
84 - Operating Mechanism LGC – Scheme Logic
85 - Pilot Communications, Carrier or Pilot- MET – Substation Metering
Wire Relay PDC – Phasor Data Concentrator
86 - Lock-Out Relay, Master Trip Relay PMU – Phasor Measurement Unit
87 - Differential Protective Relay PQM – Power Quality Monitor
87B - Bus Differential RIO – Remote Input/Output Device
87G - Generator Differential RTD - Resistance Temperature Detector
87GT - Generator/Transformer Differential RTU – Remote Terminal Unit/Data
87L - Segregated Line Current Differential Concentrator
87LG - Ground Line Current Differential SER – Sequence of Events Recorder
TCM – Trip Circuit Monitor S - Synchronizing, Secondary, Strainer,
LRSS – Local/Remote selector switch Sump, or Suction (Valve)
VTFF - Vt Fuse Fail SOTF - Switch On To Fault
T - Transformer or Thyratron
TD - Time Delay
Suffixes Description TDC - Time-Delay Closing Contact
_1 - Positive-Sequence TDDO - Time Delayed Relay Coil Drop-Out
_2 - Negative-Sequence TDO - Time-Delay Opening Contact
A - Alarm, Auxiliary Power TDPU - Time Delayed Relay Coil Pickup
AC - Alternating Current THD - Total Harmonic Distortion
AN - Anode TH - Transformer (High-Voltage Side)
B - Bus, Battery, or Blower TL - Transformer (Low-Voltage Side)
BF - Breaker Failure TM - Telemeter
BK - Brake TT - Transformer (Tertiary-Voltage Side)
BL - Block (Valve) Q - Lube Oil
BP - Bypass W - Water
BT - Bus Tie F - Fuel
BU - Backup G - Gas
C - Capacitor, Condenser, Compensator, U - Under or Unit
Carrier Current, Case or Compressor X - Auxiliary
CA - Cathode Z – Impedance
CH - Check (Valve)
D - Discharge (Valve)
DC - Direct Current Module 7 – Substation layout
DCB - Directional Comparison Blocking
DCUB - Directional Comparison Unblocking In the today’s world, the need for bulk
DD - Disturbance Detector electrical power has increased. To fulfil the
DUTT - Direct Underreaching Transfer Trip required demand, huge power is needed
E - Exciter to be delivered; hence bigger generating
F - Feeder, Field, Filament, Filter, or Fan stations are to be designed. The electrical
G - Ground or Generator power generating stations may be
GC - Ground Check generating electrical energy by means, but
H - Heater or Housing not limited to, hydraulic, thermal, or
L - Line or Logic renewable sources solely contingent on
M - Motor or Metering the accessibility of resources and areas
MOC - Mechanism Operated Contact where these power stations are built. The
N - Neutral or Network areas where power stations are built might
O - Over not be nearby load centers where the load
P - Phase or Pump is consuming power. Therefore,
PC - Phase Comparison transmitting generated power to the load
POTT - Pott: Permissive Overreaching center is of great importance.
Transfer Trip There is a need for larger high voltage
PUTT - Putt: Permissive Underreaching transmission networks, called Grid, for the
Transfer Trip purpose of transmission. Usually, power is
R - Reactor, Rectifier, or Room generated in lower voltage levels and is
economical for its transmission in high  It maintains the frequency of system
voltages. However, the distribution of confined in targeted limits and has
electrical power is achieved in lower to deal with load shedding.
voltages pertinent to consumer  It controls the exchange of electrical
requirements. Therefore, for maintenance energy amid consumers and
of such voltage levels and deliverance of generating stations.
stability numerous switching stations and  It is ensuring transient stability
transformation stations are created amid along with steady-state stability of
consumer ends and electrical power the system.
generating stations. These stations are  It delivers sufficient line capacity
commonly known as the electrical hence securing supply.
substations.  It helps in reducing the flow of
reactive power, hence gaining
Electrical substation voltage control.
- a network of electrical components  Through line carrier, it performs
comprising of power transformers, bus data transmission to ensure
bars, auxiliaries, and switchgear etc. monitoring of network, protection,
- may have a single or complex circuit and control.
composed of numerous outgoing and  It helps in fault analysis and pinning
incoming circuits which are connected cause for a failure, hence improving
to a bus bar. the performance of the electrical
- may receive electrical energy directly network.
from generating stations through  It ensures reliable supply through
incoming power supply lines or from feeding network at numerous
other substations while it delivers points.
electricity to the consumers through  It assists in determining energy
outgoing transmission lines. transfer with help of transmission
- A substation which is near to the lines.
electrical power generation is also
known as grid substation. Different Substation Layouts
1. According to service requirement
- A sub-station may be called upon to
change voltage level or improve power
factor or convert a.c. power into d.c.
power etc. According to the service
requirement, sub-stations may be
classified into
• Transformer sub-stations.
 Those sub-stations which
change the voltage level of
Main Purpose of Substations electric supply are called
 It serves as protection hub of the transformer sub-stations. These
transmission system. sub-stations receive power at
some voltage and deliver it at
some other voltage. Obviously, it into d.c power with suitable
transformer will be the main apparatus to supply for such
component in such sub- purposes as traction,
stations. Most of the sub- electroplating, electric welding
stations in the power system etc.
are of this type.
• Industrial sub-stations
• Switching sub-stations  Those sub-stations which supply
 These sub-stations do not power to individual industrial
change the voltage level i.e. concerns are known as
incoming and outgoing lines industrial sub-stations.
have the same voltage.
However, they simply perform
the switching operations of
power lines. 2. According to constructional features
- A sub-station has many components
• Power factor correction sub- ( e.g. circuit breakers, switches, fuses,
stations. instruments etc.) which must be
 Those sub-stations which housed properly to ensure continuous
improve the power factor of the and reliable service. According to
system are called power factor constructional features, the sub-
correction sub-stations. Such stations are classified as :
sub-stations are generally
located at the receiving end of • Indoor sub-stations
transmission lines. These sub-  For voltages up to 11 kV, the
stations generally use equipment of the sub-station is
synchronous condensers as the installed indoor because of
power factor improvement economic considerations.
equipment. However, when the atmosphere
is contaminated with impurities,
• Frequency changer sub-stations these sub-stations can be
 Those sub-stations which erected for voltages up to 69 kV
change the supply frequency or even higher.
are known as frequency • Outdoor sub-stations
changer sub-stations. Such a  For voltages beyond 69 kV,
frequency change may be equipment is invariably installed
required for industrial out- door. It is because for such
utilisation. voltages, the clearances
between conductors and the
• Converting sub-stations space required for switches,
 Those sub-stations which circuit breakers and other
change a.c. power into d.c. equipment becomes so great
power are called converting that it is not economical to
sub-stations. These sub-stations install the equipment indoor.
receive a.c. power and convert
substations are the simplest to
operate. But they have the least
• Underground sub-stations system reliability and flexibility
 In thickly populated areas, the of operation.
space available for equipment
and building is limited and the • Sectionalized Radial Bus
cost of land is high. Under such Configuration
situations, the sub-station is  The sectionalized or split radial
created underground. bus is a modification of the
• Pole-mounted sub-stations radial bus. This configuration is
 This is an outdoor sub-station two radial buses tied together
with equipment installed over- through a sectionalizing or bus
head on H-pole or 4-pole tie circuit breaker. The
structure. It is the cheapest sectionalizing circuit breaker
form of sub-station for voltages can be operated normally open
not exceeding 11 kV (or 34.5 kV or normally closed, depending
in some cases). Electric power is on system requirements. Bus
almost distributed in localities faults or the failure of a breaker
through such sub- stations. For (other than the tiebreaker) to
complete discussion on pole- operate for a fault requires an
mounted sub-station. outage of only the affected bus
3. According to bus configurations section. Breaker bypass
- The industry has developed several switches can be applied in
standard bus configurations that vary in sectionalized radial bus
complexity, cost, and reliability. The substations and operate the
layout of a substation for any particular same as in radial bus
configuration may vary to substations.
accommodate differences in • Main and Transfer Bus
equipment type, size and arrangement,  The main and transfer bus is
and site-specific criteria. another modification of the
radial bus. This configuration
• Radial Bus Configuration consists of a main bus and a
 The radial bus configuration transfer bus. All circuits are
consists of one main bus and a connected to the main bus
single breaker, also called single through circuit breakers and to
bus, single breaker. The the transfer bus through
transmission lines, transfer switches. The main and
transformers, and shunt transfer buses are connected
capacitor banks for extra high through a transfer bus circuit
voltage application, are breaker.
connected to the main bus  The transfer bus circuit breaker
through circuit breakers, circuit protects a circuit during
switchers, or motor operated or maintenance of its associated
manually operated disconnect circuit breaker.
switches. Radial bus
• Single Breaker Double Bus must be tripped to isolate a
Configuration faulted line or transformer. In
 The single breaker double bus the case of the one-half breaker
configuration is a modification configuration, one of the
of the sectionalized radial bus. breakers is usually at the other
This configuration consists of end of the transmission line. In
two main buses connected the Figure below, Substations A,
through a tie circuit breaker. B, C, D, and E form an extended
• Ring Bus Configuration ring bus.
 The ring bus configuration is, in • Breaker and One Half Bus
reality, a series of sectionalized Configuration
radial buses connected together  The breaker and one-half
to form a ring. Each bus is called configuration consist of two
a position. Sometimes a main buses. Connected
transmission line and a between the main buses are
transformer are paired on one bays which consist of three
ring position. In this circuit breakers. A circuit is
configuration, only one position terminated between each two
is removed from service for a circuit breakers.
circuit or bus fault. The circuit • Double Breaker Double Bus
breakers which serve the Configuration
faulted position are opened.  The double breaker double bus
The failure of a breaker to configuration consists of two
operate for a line or bus fault main buses. Connected
will cause two positions to be between the main buses are
removed from service. bays consisting of two circuit
 This configuration allows for any breakers, and between the
circuit breaker to be removed circuit breakers, a circuit. In this
from service for maintenance configuration, each circuit has
without an outage on any two dedicated circuit breakers.
circuit. Line disconnect
switches are often installed to Module 8 – Substation High
allow a line to be removed from Voltage Equipment
service and the ring to remain
intact. The two circuit breakers Electrical substations are the interface
sourcing the line are opened, between parts of the distribution grid and
the line disconnect switch is transmission systems. It transforms
opened, and then the two voltage from high to low, or vice versa, or
circuit breakers are closed. perform any of several other important
• One-Half Breaker Configuration functions. Between the generating station
 The one-half breaker and consumer, electric power may flow
configuration is a variation of through several substations at different
the ring bus concept on a voltage levels. A substation may include
multiple substation basis. As transformers to change voltage levels
with the ring bus, two breakers
between high transmission voltages and - double breaker configuration consists
lower distribution voltages, or at the of two main buses, each normally
interconnection of two different energized. Electrically connected
transmission voltages. between the buses are two circuit
breakers and, between the breakers,
Single bus configuration one circuit.
- consists of one main bus that is
energized at all times and to which all --- --- --- --- --- ---
circuits are connected. This High Voltage Electrical Equipment
arrangement is the simplest but - Major electrical equipment such as
provides the least amount of system transformers, switchgear and circuit
reliability breakers are all part of the power plant
design. Together with these major
Sectionalized bus components are the protection and
- is basically two or more single bus instrumentation.
schemes, each tied together with bus
sectionalizing breakers. The most  Transformer
common configuration is the double • is a static machine used for
bus single breaker configuration. transforming power from one circuit
to another without changing the
Main and Transfer Bus frequency. As there are no rotating
- consists of two independent buses, one or moving parts, a transformer is
of which, the main bus, is normally classified as a static device.
energized. Under normal operating Transformer operates on an AC
conditions, all incoming and outgoing supply. Transformers operate based
circuits are fed from the main bus on the principle of mutual
through their associated circuit induction. Power transformers are
generally used in transmission
breakers and switches.
network for stepping up or down
Ring bus configuration the voltage level. It operates mainly
- is an extension of the sectionalized bus during high or peak loads and has
arrangement and is accomplished by maximum efficiency at or near full
interconnecting the two open ends of load. Distribution transformer steps
the buses through another down the voltage for distribution
sectionalizing breaker. purpose to domestic or commercial
users. It has good voltage regulation
Breaker and a half configuration and operates 24 hrs a day with
- consists of two main buses, each maximum efficiency at 50% of full
normally energized. Electrically load. Instrument transformers
connected between the buses are include C.T and P.T which are used to
three circuit breakers and, between reduce high voltages and current to
each two breakers lesser values which can be
measured by conventional
The double bus instruments.
• Types of Transformers
 Step up transformers - converts  Dry type transformer - air
the low voltage (LV) and high cooling is used instead.
current from the primary side of
the transformer to the high
voltage (HV) and low current
value on the secondary side of
the transformer.
 Step down transformers -
converts the high voltage (HV)
• Types of transformer windings –
and low current from the
core type and shell type, and also
primary side of the transformer
berry type transformers
to the low voltage (LV) and high
 A core type transformer - has
current value on the secondary
side of the transformer. two vertical legs or limbs with
 Three phase transformer - two horizontal sections named
generally used in three phase yoke. The core is rectangular in
power system as it is more cost shape with a common magnetic
effective than single phase circuit. Cylindrical coils (HV and
transformers.
 Single phase transformer - But
when size matters, it is
preferable to use a bank of
three single phase transformer
vs a three-phase transformer, as
it is easier to transport than one
single three phase transformer
unit.
 Two winding transformer - is
generally used where the ratio LV) are placed on both the
between the high voltage and
limbs.
low voltage side is greater than
2.
 A shell type transformer - has a
 Autotransformer - where the
ratio between the high voltage central limb and two outer
and low voltage sides is less limbs. Both HV, LV coils are
than 2. placed on the central limb. The
 Outdoor transformer - outdoor double magnetic circuit is
transformers are designed for present.
installing outdoors.  In a berry type transformer, the
 Indoor transformers - are core looks like the spokes of a
designed for installing at wheel. Tightly fitted metal sheet
indoors. tanks are used for housing this
 Oil cooled transformer - the type of transformer, with
cooling medium is transformer transformer oil filled inside.
oil.
 Switchgear
 Circuit breaker • Switchgear is a general term used to
• An electrical circuit breaker is a refer to a range of switches, circuit
switching device which can be breakers, fuses, etc., which are used
operated manually and in an electric power system to
automatically for controlling and control, regulate and switch the
protecting an electrical power circuit on and off. By controlling the
system. As the modern power circuit, switchgear protects and
system deals with huge currents, isolates electrical equipment from
special attention should be given the power supply,
during designing of a circuit breaker enabling testing, maintenance and
to ensure it is able to safely fault clearing work to be
interrupt the arc produced during undertaken.
the closing of a circuit breaker.
• Switchgear has two types
• Types of circuit breaker of components:
 Oil circuit breaker  Power-conducting component
 Air circuit breaker s: These conduct or interrupt
 Gas (SF6) circuit breaker the power flow; such as
 Vacuum circuit breaker switches, circuit breakers, fuses,
• According to their services: isolators,
 Outdoor circuit breaker. relays, lightning arrestors, and
 Indoor breaker. so on.
• According to the operating  Control systems:
mechanism: These monitor, control and
 Spring operated circuit breaker. protect the power-
 Pneumatic circuit breaker. conducting components; such
 Hydraulic circuit breaker. as control panels,
• According to the voltage level: current transformers,
 High voltage circuit breaker. potential transformers,
 Medium voltage circuit breaker. associated circuitry, and so on.
 Low voltage circuit breaker.
• Switchgear is directly linked to the
supply system and, based on the
• According to tank used voltage level, can be classified as
 Dead Tank either:
 Live Tank  Low voltage switchgear (LV).
 Medium voltage switchgear
(MV).
 High voltage switchgear (HV).

 Protective Relay
• A relay is automatic device which
senses an abnormal condition of
electrical circuit and closes its  General requirements. The dc
contacts. These contacts in turns system, consisting of a station
close and complete the circuit battery, chargers and dc
breaker trip coil circuit hence make distribution panels, provides a
the circuit breaker tripped for continuous and reliable source
disconnecting the faulty portion of of dc control voltage for system
the electrical circuit from rest of the protection during normal
healthy circuit. Selection of relays operation and for emergency
and coordination of their settings so shutdown of the power plant.
that the correct circuit breaker trips Battery will be nominal 125
when it is supposed to, and does not volts, mounted on wooden
trip when it is not supposed to is a racks or metal racks with PVC
subject too broad to be covered covers on the metal supporting
herein. For the purpose of this surfaces. Lead calcium cells
document the listings below will set having pasted plates or other
forth those protective relay types suitable cells will be considered
which will be considered. For the for use.
relay, using IEC or IEEE standards are  Duty cycle. Required capacity
widely used in today’s engineering. will be calculated on an 8-hour
duty cycle basis taking into
 Emergency power system account all normal and
• Those portions of the station service emergency loads. The duty
load that must be operable for a cycle will meet the
safe shutdown of the unit, or that requirements of the steam
are required for protection of the generator burner control
unit during shutdown, will be fed system, emergency cooling
from a separate 480-volt unit systems, control bench board,
emergency power bus. A suitable relays and instrument panels,
emergency diesel engine driven emergency lighting system, and
generator will be installed and all close/trip functions of the
arranged to start automatically and medium voltage and 480-volt
carry these loads if the normal circuit breaker systems.
source of power to this bus is lost.  Battery chargers.
The loads fed from this bus might  Two chargers capable of
include such things as emergency maintaining a 2.17 the
lighting, communication system, proper float and equalizing
battery charger, boiler control voltage on the battery will
system, burner control system, be provided. Each charger
control boards, annunciator, will be capable of restoring
recorders and instrumentation. the station battery to full
Design of these systems will provide charge in 12 hours after
for them to return to operation after emergency service
a brief power outage. discharge. Also, each unit
will be capable of meeting
• Battery and charger.
50 percent of the total dc 6. Temperature meter with selector
demand including charging switch for stator temperature
current taken by the detectors
discharged battery during 7. D.C. volmeter for excitation voltage
normal conditions 8. D.C. ammeter for field current
 Battery room. Only the battery
will be located in a ventilated b. Stepup transformer.
battery room. The chargers 1. Voltmeter on high voltage side with
maybe wall or floor mounted, selector switch
together with the main dc 2. Ammeter with selector switch
distribution panel, immediately 3. Wattmeter
outside the battery room. 4. Varmeter
 DC distribution panel. The 5. Power factor meter
distribution panel will utilize
molded case circuit breakers or c. Auxiliary transformer.
fuses selected to coordinate 1. Switch
with dc breakers furnished in 2. Voltmeter on low voltage side with
control panels and switchgear. selector
The breakers will be equipped 3. Ammeter with selector switch
with thermal magnetic trip 4. Wattmeter
devices, and for 20 kA dc 5. Varmeter
interrupting rating. 6. Power factor meter

General facilities design d. Common.


Input adjustments will be designed to be 1. Voltmeter with selector switch for
delegated to automatic control systems each bus
except during start up, shutdown, and 2. Synchroscope
abnormal operating conditions when the
operator displaces or overrides automatic e. Integrating meters. The following
control functions. The following integrating meters will be provided but
instruments will be mounted on the need not be mounted on the control
control board in the operating room to board:
provide the operator with information 1. Generator output watt-hour meter
needed for operations: 2. Auxiliary transformer watt-hour
meter for each auxiliary transformer
a. Generator.
1. Ammeter with phase selector switch Electrical Control System
2. Voltmeter with phase selector For the integration of the electrical
switch systems the control system has to be
3. Wattmeter designed to fulfill some important
4. Varmeter requirements:
5. Power factor meter Frequency - Monitoring
meter • Monitoring of the electrical system
has to be possible at workplaces of
the control room, workplaces
dedicated to control of the electrical
system and workplaces for
maintenance. Graphic displays have
to be available presenting the status
of the overall or parts of the
electrical system.
• To be able to take immediate action
in case of disturbances, it is also
important to be aware of all alarms
and have a quick overview in which
part / area alarms are active.
- Manual or remote operation
• The manual (remote) operations of
electrical devices have to be
supported by consistent means;
e.g., faceplates in the or locally at
the device cubicle using push-
buttons or control panels.
- Automatic operation
• From a power plant control system
point-of-view, automatic operation
means that electrical devices
are part of automatic control
sequences executed in an
automation controller. This
requirement applies only for those
devices that interact with process
control.
- Recording
• For purposes of disturbance
analysis, documentation, reporting
and optimization, the plant control
system has to be capable
of recording electrical system status
signals, alarms, event and
measured values.
EE 6 Three kinds of losses in induction motors
Module 3 – Induction Motor 1. Copper losses in the stator and
rotor.
The actual conversion of electrical power 2. Iron losses i.e., hysteresis and
into mechanical power always takes place eddy current.
in the rotor of a motor. In the induction 3. Friction and windage losses in
motor, the power input to the rotor is not the stator.
applied directly ie. conductively, but is
transferred across on air – gap inductively. Three tests to determine the efficiency of
induction motor
The total power delivered to the rotor 1. No-load test
power per phase consists of two parts: 2. Load test
3. Stator Resistance test
1.) the power that causes a copper loss
2.) the electric power that is converted
No-Load Test
into the mechanical power on a per – when the two-wattmeter method is
is phase basis. used to measure the power input the total
Rotor Torque power is the difference between the
wattmeter readings because the no load pf
- the force tending to produce is considerably less than 0.5.
rotation.
- It is usually expressed in pound-feet Load Test
(lb-ft) except in the case of very – the wattmeter reading is additive
small motors given in terms of because the pf is much greater than 0.5.
ounce-inches (oz-in).
Stator Resistance Test
Starting Torque – it is measurement of the stator
- the torque developed by a motor at winding per phase. It is customary to
the instant it is started. In some measure the resistance between three
pairs of stators these values is then divided
cases, it is greater than the normal
by 2 to obtain the resistance per phase, a
running torque while in others it
Y-connected having been assumed AC
may be somewhat less than this.
resistance is higher than DC resistance, the
Since the starting torque occurs resistance is usually multiplied by factor of
when the slip is unity. about 1.25 to obtain.
Induction motor efficiency
Blocked rotor test
- the calculation of the efficiency of - the values of the rotor resistance and
an induction motor follows the rotor reactance, whether of the
essentially the same procedure as it squirrel cage or wound rotor type can be
does for DC generator, alternator, determined by this test. In this method
and the transformer. three rheostats in the line wires, adjusting
the 3-phase motor voltage to a value at
w/c approximately rated current flows
when the rotor is blocked and cannot vary the supply frequency (because
rotate. Ns = 120f/P).

All the instant the motor is started, the 2. It is not inherently self-starting. It
rotor is not turning. The friction and has to be run up to synchronous
windage loss in therefore zero. However, speed by some means, before it can
the iron loss at starting will be greater be synchronized to the supply.
than the normal operating value because
the rotor frequency is the same as the 3. It is capable of being operated
stator frequency. under a wide range of power
factors, both lagging and leading.
Furthermore, if the blocked rotor test Hence, it can be used for power
had been made at rated voltage, the stator factor correction purposes.
current with the rotor blocked would have
been equal to (Vrated/Vbr) x Ibr and the
Two factors determine the speed of SM
power input w/ rotor blocked would have
1. The frequency of the supply source
been (Vrated/Vbr)² x Pbr w/ there ie is
2. The number of poles in the machine
possible to calculate the starting.
Advantages of Synchronous Motor
1. They can be made to operate at the
Module 4 - Synchronous Motor leading pf and thereby improve the
pf of an industrial plant from one
Synchronous Motor
that is normally lagging to one that
- Operates at an absolutely average
is close to unity.
constant speed regardless of the
load: it departs from this average
2. They are less costly in certain
speed only during load changes. The
horsepower and speed ranges.
regulation of this type is therefore
zero.
3. They usually operate and
- It is electrically identical with an
constructed at higher efficiency
alternator, when driven
especially in the low-speed unity pf
mechanically or as a motor, when
ranges. Synchronous motors are
driven electrically. Most
frequently used for pf correction
synchronous motors are rated
purposes only.
between 150KW to 15MW and run
at speeds ranging from 150 to
1800rpm. Synchronous Condenser/ Capacitor

Characteristics of Synchronous Motors The ability of a SM to take a very low


1. It runs either at synchronous speed leading pf current makes it behave like a
or not at all while running it capacitor. The overall pf of the system is
maintains a constant speed. The improved and with-it transmission
only way to change its speed is to efficiency and regulation as well as the
general operating performance of the 4. A DC excitation is required by
other apparatus. synchronous motor but not by
induction motor.
The proper selection of a motor for a given
application always involve a complete 5. Synchronous motors are usually
understanding of essential operating and more costly and complicated than
physical requirements. Such information is induction motors, but they are
gained only through first-hand experience particularly attractive for low-speed
in the installation and operation of actual drives (below 300 rpm) because
industrial equipment. Necessary to consult their power factor can always be
specialists when expert advice is needed adjusted to 1.0 and their efficiency
about motor installation. is high. However, induction motors
are excellent for speed above
However, manufacturers have developed 600rpm.
standard types of motors having
characteristics that meet the general and 6. Synchronous motors can be run at
special needs of most kinds of mechanical ultra-low speeds by using high
equipment. Such motors are usually tested power electronic converters which
in catalogue and bulletins in w/c are generate very low frequencies. Such
motors of 10MW range are used for
indicated such important items such as hp
driving crushers, rotary kilns and
output, speed range, starting torque,
variable-speed ball mills etc.
starting amperes, etc.

SYNCHRONOUS MOTOR APPLICATIONS


Comparison between synchronous and Synchronous motors find extensive
induction motor application for the following classes of
1. For a given frequency, the service:
synchronous motor runs at a 1. Power Factor Correction
constant average speed whatever 2. Constant-speed, constant-load
the load, while the speed of an drives
induction motor falls somewhat 3. Voltage Regulation
with increase in load.
A. Power Factor Correction
2. The synchronous motor can be
operated over a wide range of - Overexcited synchronous
power factors, both lagging and motors having leading power
leading, but induction motor always factor are widely used for
run with lagging power factor which improving power factor of
may become very low at light loads. those power systems which
employ a large number of
3. A synchronous motor is inherently
induction motors and other
not self-starting.
devices having lagging power
factor such as welders and When line voltage decreases
fluorescent lights, etc. due to inductive load, motor
excitation is increased, thereby
raising its power factor which
compensates for the line drop.
If, on the other hand, line
B. Constant Speed Applications voltage rises due to line
- Because of their high efficiency capacitive effect, motor
and high speed, synchronous excitation is decreased, thereby
motors (above 600 rpm) are making its power factor lagging
well-suited for loads where which helps to maintain the line
constant speed is required such voltage at its normal value.
as centrifugal pumps, belt-
driven reciprocating
compressors, blowers, line
shafts, rubber and paper mills,
etc. Low speed synchronous
motors (below 600 rpm) are
used for drives such as
centrifugal and screw-type
pumps, ball and tube mills,
vacuum pumps, chippers and
metal rolling mills, etc.

C. Voltage Regulation
- The voltage regulation at the
end of a long transmission line
varies greatly especially when
large inductive loads are
present. When an inductive
load is disconnected suddenly,
voltage tends to rise
considerably above its normal
value because of the line
capacitance.
- By installing a synchronous
motor with a field regulator (for
varying its excitation), this
voltage rise can be controlled.
EE 14 that receiving end voltage (VR) of
the line is generally less than the
Transmission line
sending end voltage (VS).
- Has three constants R, L and C - The difference in voltage at the
distributed uniformly along the receiving end of a transmission line
whole length of the line. **between conditions of no load
Resistance and Inductance form the series and full load
impedance - Is the rise in voltage at the receiving
end, expressed in percent of full
The Capacitance existing between load voltage, when full load at a
conductors for 1-phase line or from a specified power factor is removed
conductor to neutral for a 3-phase line while the sending-end voltage is
forms a shunt path throughout the length held constant
of the line.
Shunt conductance
Capacitance effects introduce
complications in transmission line - It represents the conductance
calculations. between conductors or between
conductor and ground and accounts
Short transmission line for the leakage current at the
- When the length of an overhead insulators. It is very small in case of
transmission line is up to about 50 overhead lines and may be assumed
km and the line voltage is zero.
comparatively low (< 20 kV) Transmission efficiency
- When the length of an overhead
transmission line is about 50-150 - The power obtained at the receiving
km and the line voltage is end of a transmission line is
moderately high (>20 kV < 100 kV) generally less than the sending end
- When the length of an overhead power due to losses in the line
transmission line is more than 150 resistance.
km and line voltage is very high (> - The ratio of receiving end power to
100 kV) the sending end power of a
transmission line.
While studying the performance of a
transmission line, it is desirable to End Condenser Method
determine its voltage regulation and - In this method, the capacitance of
transmission efficiency. the line is lumped or concentrated
Voltage Regulation at the receiving or load end.
- Limitations:
- When a transmission line is carrying o There is a considerable error
current, there is a voltage drop in (about 10%) in calculations
the line due to resistance and because the distributed
inductance of the line. The result is capacitance has been
assumed to be lumped or Service Switch
concentrated.
- A disconnecting means or
o This method overestimates
"disconnect switch" must be
the effects of line capacitance
provided in the service entrance to
Nominal T Method disconnect all the wiring in the
building from the electrical power
- In this method, the whole line
supply. This may be accomplished
capacitance is assumed to be
with a separate switch called a
concentrated at the middle point of
service switch or main disconnect.
the line and half the line resistance
Many years ago, it was common to
and reactance are lumped on its
install a separate switch next to the
either side.
fuse box to shut the power off. In
Nominal pi Method modern residences, the service
- In this method, capacitance of each switch is actually the main breaker
conductor (i.e., line to neutral) is housed inside the breaker box
divided into two halves; one half which shuts off power to all the
being lumped at the sending end other breakers in the box.
and the other half at the receiving - The size of the service switch or
end. main breaker depends on the
electrical load served. Service
Classification of Transmission lines switches come in standard sizes of
- Short transmission lines 30, 60, 100, 150, 200, 400 and
- Medium transmission lines larger. The National Electrical Code
- Long transmission lines requires a minimum 100-amp
service size for all residences,
EE 15 – FINALS although many newer houses
Metering typically use a 150 amp or larger
service.
Service Entrance
Service Panel
- is where the wires connected to the
load side of the meter enter the - The National Electrical Code
house or building. The service requires electrical services to have a
entrance in a residence is commonly service entrance panel commonly
thought of as a breaker or fuse box. called a breaker or fuse box. A
In larger more complicated modern service entrance panel
commercial or industrial electrical consists of an enclosure housing the
systems, the service entrance may breakers or fuses and associated
be a main disconnect panel or a wiring. If located outside, the
trough where up to six main enclosure must be weatherproof
switches are present. which keeps rain and moisture from
interfering with the electrical parts.
The breakers or fuses protect the required in front of the smaller
wires leaving the breaker box from disconnects.
overloading and being damaged.
- A ground wire connects inside the
service entrance panel to the
neutral connections to provide a
Branch Circuits
ground for the customer's service.
The ground wire extends to below - A branch circuit is defined as that
ground level where it attaches to a part of an electric circuit extending
ground rod. The ground rod serves beyond the last circuit breaker or
as an easy path for lightning to get fuse. The branch circuits start at the
into the earth if it strikes the utility breaker box and extend to the
line or the customer’s electrical
electrical devices connected to the
service.
service. Branch circuits are the last
Large Services part of the circuit supplying
electrical devices. These circuits are
- For large customers such as classified in two different ways,
apartment buildings or commercial according to the type of loads they
and industrial customers the service serve or according to their current-
can become more complicated. In carrying capacity.
these systems, the National
Electrical Code allows up to six
separate disconnects for each
electrical service as long as they are
grouped together.
- An example would be an apartment
complex where each electrical
service provided power for six
apartments. It would be common
for the service drop to be connected
to six separate disconnect switches,
each controlling an individual
apartments' electrical service. The
electrical wires from one disconnect
switch are connected to an electrical
meter to measure that particular
apartments' energy use and then
wires run from the meter to the
breaker or fuse box in the
corresponding apartment.
- If there are more than six electrical
disconnects, a main disconnect is
- Switchgear is electrical equipment
that is used to protect, control, and
isolate electrical equipment in
power systems. It works by
interrupting or isolating electrical
circuits when a fault occurs,
EE 15 preventing damage to equipment
Switch Gear and minimizing the risk of electrical
hazards.
Switchgear - Switchgear typically includes
- Switchgear is a general term switches, fuses, circuit-breakers,
covering switching devices and their relays, and other components that
combination with associated are used to control and protect
control, measuring, protective and electrical power systems. When a
regulating equipment, also fault occurs, the switchgear detects
assemblies of such devices and it and isolates the faulty
equipment with associated component or circuit to prevent
interconnections, accessories, damage to other parts of the
enclosures and supporting system.
structures, intended in principle for - Switchgear also helps to control the
use in connection with generation, flow of electricity in the system,
transmission, distribution and allowing operators to switch
conversion of electric energy circuits on and off and control the
[Source: IEC 60947-1-2020]. power output of generators.
Additionally, it can provide backup
Main Components of Switchgear power to critical systems in the
 Circuit-breakers event of a power outage or other
 Residual current devices emergency.
 Isolators - Switchgear can be found in a wide
 Fuse-combination units range of settings, from power plants
 Switches and substations to industrial
 Surge protective devices facilities and commercial buildings.
 Contactors It plays a crucial role in ensuring
 Motor-starters the safe and reliable operation of
electrical power systems.
 Protective relays
 Transformers
 Disconnectors Switchgear Types
 Switch-disconnectors
1. High-Voltage Switchgears
 Busbars - High-voltage switchgear is designed
How Does Switchgear Work? to operate at voltages above 52 kV
AC. It is typically used in power medium maybe oil, SF6, and
transmission and distribution vacuum.
systems, as well as in large industrial
facilities such as chemical plants and 3. Low-Voltage Switchgear
refineries. - Low-voltage switchgear is used in
- High voltage circuit-breakers (such power systems with voltage levels
as SF6 circuit-breaker or vacuum below 1000 V AC or 1500 V DC. It is
circuit-breaker) are the main typically used in residential and
component of HV switchgear. Hence commercial applications and plays a
high voltage circuit-breaker should crucial role in controlling and
have special features for safe and protecting the electrical equipment
reliable operation. in these environments. The key
- Faulty tripping and switching components of low-voltage
operation of high voltage circuit- switchgear include circuit-breakers,
breakers are comparatively very fuses, switches, relays, and
rare. Most of the time these circuit- transformers.
breakers remain at ON condition
Is there a Difference Between Switchgear
and may be operated after a long
and Switchboards?
period of time. So Circuit-breakers
must be reliable enough to ensure - Yes, there is a difference between
safe operation, as when required. switchgear and switchboards.
Switchboard is an assembly of switchgear
2. Medium-Voltage Switchgear with or without instruments, but the term
- Medium-voltage switchgear is does not apply to groups of local switches
designed to operate at voltages in final circuits.
between 1 kV and 52 kV [2] AC.
- Medium voltage switchgear is Switchgear refers to the electrical
mainly used for the distribution of equipment that is used to control, protect,
electrical energy connected to and isolate electrical power systems. It
various electrical networks. They typically includes components such as
include most of the substation circuit-breakers, fuses, switches, and
equipment such as minimum oil relays, and is designed to operate at high
circuit-breakers, bulk oil circuit- voltages and currents.
breakers, air magnetic, SF6 gas- Switchboards are typically low-voltage
insulated, vacuum, and gas- distribution boards that are used to
insulated switchgear. distribute power to various electrical loads
- They may metal-enclosed indoor within a building or facility. They usually
type, metal-enclosed outdoor type, consist of panels with multiple switches,
outdoor type without a metal fuses, and other protective devices, as well
enclosure, etc. The interruption as metering equipment to monitor power
usage.
Switchgear and switchboards are used to Ambient air temperature is that existing in
control and distribute electrical power, the vicinity of the equipment if supplied
switchgear is typically used in high-voltage without enclosure, or in the vicinity of the
applications such as power generation and enclosure if supplied with an enclosure.
transmission, while switchboards are used
Equipment intended to be used in ambient
in low-voltage applications such as
air temperature above +40 °C (e.g. in
commercial and industrial buildings.
forges, boiler rooms, tropical countries) or
below –5 °C (e.g. –25 °C, as required by IEC
61439 (all parts) for outdoor installed low-
voltage switchgear and controlgear
How Can I Extend the Life of My assemblies) shall be designed and used
Switchgear? according to the relevant product standard
Electrical switchgear is an important or, where applicable, according to an
component of electrical power systems, agreement between manufacturer and
and its proper maintenance is essential for user. Information given in the
ensuring the safe and reliable operation of manufacturer’s documentation may take
the system. the place of such an agreement.

Here are some ways to extend the life of NOTE – Ambient air temperature(s) for
your switchgear: certain types of equipment, e.g. circuit-
breakers or overload relays for starters, is
 Regular maintenance.
indicated in the relevant product standard.
 Use recommended operating
procedures. Altitude.
 Upgrades and retrofits. - The altitude of the site of
 Training and education. Provide installation does not exceed 2 000
training and education to your m.
personnel who operate and - For equipment to be used at higher
maintain the switchgear. altitudes, it is necessary to take into
 Monitoring and testing. account the reduction of the
 Normal Service Conditions dielectric strength and the cooling
 Ambient air temperature. effect of the air. Electrical
equipment intended to operate
 The ambient air temperature - under these conditions shall be
does not exceed +40 °C designed and used in accordance
 its average over a period of 24 h with an agreement between
does not exceed +35 °C. manufacturer and user. Information
 The lower limit of the ambient given in the manufacturer’s
air temperature is – 5 °C. documentation may take the place
of such an agreement.
Humidity.
- The relative humidity of the air does
not exceed 50 % at a maximum
temperature of +40 °C. Higher
relative humidities may be
permitted at lower temperatures,
e.g. 90 % at +20 °C. Special
measures may be necessary in cases
of occasional condensation due to
variations in temperature.

You might also like