String Test Report

Site Estidamah Module sun Power Estidamah Instrument 15L-1153


Substation α (A/°C) 0.0029 Start Time 02/02/2023 09:15:20
Inverter Inv1 β (V/°C) -0.00174 End Time
Combiner Fully Closed Rs (Ω) 0

String Name Date Irr (W/m²) Tpv (°C) FF No. Modules


String 111 02/02/2023 09:15:20 0 0.0 46 2

Electrical Data
String Name Pmpp Voc Vmpp Isc Impp
MEAS STC NOM Diff MEAS STC NOM MEAS STC NOM MEAS STC NOM MEAS STC NOM
W W W % V V V V V V A A A A A A
String 111 599 599 3,627 83.5 650.3 650.3 721.0 443.0 443.0 621.0 2.00 2.00 6.15 1.35 1.35 5.84

String 111

4
Current (A)

STC
MEAS
NOM
0
0 100 200 300 400 500 600 700
Voltage (V)
String 111 ()
String Test Report
Site Estidamah Module sun Power Estidamah Instrument 15L-1153
Substation α (A/°C) 0.0029 Start Time 02/02/2023 09:13:12
Inverter Inv1 β (V/°C) -0.00174 End Time
Combiner Fully Closed Rs (Ω) 0

String Name Date Irr (W/m²) Tpv (°C) FF No. Modules


String 122 02/02/2023 09:13:12 0 0.0 42 2

Electrical Data
String Name Pmpp Voc Vmpp Isc Impp
MEAS STC NOM Diff MEAS STC NOM MEAS STC NOM MEAS STC NOM MEAS STC NOM
W W W % V V V V V V A A A A A A
String 122 592 592 3,627 83.7 663.5 663.5 721.0 483.4 483.4 621.0 2.12 2.12 6.15 1.23 1.23 5.84

String 122

4
Current (A)

STC
MEAS
NOM
0
0 100 200 300 400 500 600 700
Voltage (V)
String 122 ()
String Test Report
Site Estidamah Module sun Power Estidamah Instrument 15L-1153
Substation α (A/°C) 0.0029 Start Time 02/02/2023 09:13:56
Inverter Inv1 β (V/°C) -0.00174 End Time
Combiner Fully Closed Rs (Ω) 0

String Name Date Irr (W/m²) Tpv (°C) FF No. Modules


String 211 02/02/2023 09:13:56 0 0.0 42 2

Electrical Data
String Name Pmpp Voc Vmpp Isc Impp
MEAS STC NOM Diff MEAS STC NOM MEAS STC NOM MEAS STC NOM MEAS STC NOM
W W W % V V V V V V A A A A A A
String 211 612 612 3,627 83.1 663.0 663.0 721.0 510.0 510.0 621.0 2.18 2.18 6.15 1.20 1.20 5.84

String 211

4
Current (A)

STC
MEAS
NOM
0
0 100 200 300 400 500 600 700
Voltage (V)
String 211 ()
String Test Report
Site Estidamah Module sun Power Estidamah Instrument 15L-1153
Substation α (A/°C) 0.0029 Start Time 02/02/2023 09:14:42
Inverter Inv1 β (V/°C) -0.00174 End Time
Combiner Fully Closed Rs (Ω) 0

String Name Date Irr (W/m²) Tpv (°C) FF No. Modules


String 222 02/02/2023 09:14:42 0 0.0 41 2

Electrical Data
String Name Pmpp Voc Vmpp Isc Impp
MEAS STC NOM Diff MEAS STC NOM MEAS STC NOM MEAS STC NOM MEAS STC NOM
W W W % V V V V V V A A A A A A
String 222 583 583 3,627 83.9 662.5 662.5 721.0 490.4 490.4 621.0 2.16 2.16 6.15 1.19 1.19 5.84

String 222

4
Current (A)

STC
MEAS
NOM
0
0 100 200 300 400 500 600 700
Voltage (V)
String 222 ()