The Advisor
The Advisor
Your Circuit Protection
Resource.
110 110
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Think of this catalog — and our people
— as your circuit protection advisors.
There’s a reason this catalog is called your equipment, your power requirements, and the
“The Advisor.” problems you’re facing. Contact us for fast, accurate
The name “Advisor” has been on the cover of our answers on these and countless other circuit protec-
catalog for years. Yet the idea behind that name is as tion topics:
pertinent as ever: In the increasingly complex world of
➤ Motor Control — AC, DC, single-speed, or vari-
circuit protection, you need more than a comprehen-
able-speed...you name it, our squad of industrial-
sive selection of smartly engineered fuses, holders,
protection design and applications engineers is
and accessories....
familiar with all kinds of motor control protection
You need advice.
problems. And they’ll bring that experience to
Advice on choos-
bear on solving yours.
ing the right fuse for the
application. On coordinat- ➤ Power Electronics — Turn to our semiconductor
ing it with upstream and protection experts for know-how on circuit protec-
downstream devices. On tion solutions for today’s sensitive solid-state
complying with interna- components, be they engineered to European,
tional standards. And on a North American, or other world standards.
whole range of other com-
➤ Rapid Prototyping — Need a custom solution
plicated circuit protection
for a new product design? Our team will employ
and business issues.
computer modeling, on-site run-testing, and accel-
Of course, sound advice is only valuable if
erated manufacturing systems to cut traditional
it’s there when you need it. Which is why we offer you
development time by 75%. So, source the fuse
three easy ways to access our expertise. Starting with
supplier who can keep pace with your develop-
this latest, completely revised edition of The Advisor.
ment schedule.
Take a look! You’ll see dozens of improvements that
speed-up fuse specification, changeouts, and ordering, ➤ Circuit Protection Software — Ferraz Shawmut
including: leads the industry in developing proprietary soft-
ware to help you specify the right fuse fast. Do
Improved
delineation
SMARTSPOT INDICATOR AMP-TRAP 2000®
photography
➤ Solid State SmartSpot Indicator
➤ Time delay for motor starting and transformer inrush
➤ 300kA interrupting rating - self-certified,
for improved — and, for the benefit of our customers who export,
UL witnessed tests
➤ Extremely current limiting for low peak let-thru current
visual reference
➤ Most current limiting UL class fuse
➤ Small footprint requires less mounting space and
manufacture offshore,
allows smaller, more economical fuse blocks
➤ Easy 2-to-1 selectivity for prevention of nuisance
shutdowns
➤ Unique Class J dimensions prevent replacement errors
Highlights Indicator (70 to 600A General Loads ➤ AC: 1 to 600A AJT (1-600):
characteristics
of our North American
➤ Bus Duct DC: 1 to 600A
Standard 248
➤ Load Centers 500VDC, 100kA I.R. ➤ CSA Certified to
Standard C22.2 Easy-reference
and compliance No. 248.8
➤ IEC 269-2-1
charts & curves
symbols
AJT (70-600) EI:
➤ UL Listed File E2137
➤ DC Tested to UL
Standard 248
sales offices, worldwide
A2 manufacturing, and a
listing of the companies who comprise Ferraz Shawmut,
visit us @ us.ferrazshawmut.com.
It’s just more evidence that we’ll go to the
A team of advisors dedicated
ends of the earth to show you where the world turns
to your field.
for circuit protection.
Nowadays, you don’t have the time or the resources
Fax us your circuit protection problem at
to “educate” your fuse supplier on the product or plant
800-535-8103 in the U.S. or (416) 252-6572 in
application that needs protection. So, we’ve assembled
Canada. Or visit our website at us.ferrazshawmut.com.
a team of experts who have extensive experience in
product-specific disciplines — experts who know about Cover image Boston, Massachusetts.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Table of Contents
FUSE QUICK SELECTOR Typical applications and recommended fuse types . . . . . . . . . . . . . . . . . . . Page 2
PRODUCT GUIDE Visual summary of product families and descriptions . . . . . . . . . . . . . . Pages 3-12
AMP-TRAP 2000® FUSES Premium time delay Amp-Trap® fuses recommended for “No-damage” protection
of equipment and electrical systems. A
NORTH AMERICAN
POWER FUSES
Popular time delay and non-time delay fuses for power circuits and equipment
protection. B
C
MIDGET, MINIATURE and Small dimension fuses from 5 mm x 20 mm to 1-1/2” x 13/32” and fuses for .
PC MOUNT FUSE direct mounting on PC boards.
D
SEMICONDUCTOR FUSES Ferrule-type fuses, bolt-in type fuses and Series Q square body fuses for the
protection of semiconductors rated 130V to 1200V.
MEDIUM VOLTAGE FUSES 5.5kV and 15.5kV “E” Rated fuses; 2.4, 4.8 and 7.2kV “R” Rated fuses and 2.4,
4.8, 5.0 & 7.2kV PT fuses. E
INTERNATIONAL FUSES EURO/IEC Cylindrical, DO Neozed, D Diazed and DIN NH dimension fuse-links, bases
and accessories. Canadian Class C, Class CA & CB, HRCII-MISC and Class H fuses F
G
SPECIAL PURPOSE FUSES Amp-Trap® Cable Protectors, Welder Protectors and Form 600 fuses, In-line
fuses, Plug fuses, Telecommunications fuses and Forklift Truck fuses.
H
FUSE BLOCKS and HOLDERS Class H, K, T and R Fuse Blocks, ULTRASAFE™ fuse holders, in-line holders,
panel-mount holders and fuse clips.
POWER DISTRIBUTION
BLOCKS
FSPDB (finger-safe power distribution blocks) Large, Intermediate and Mini Series
blocks, safety covers and end barriers. I
J
CIRCUIT PROTECTION Fuse reducers, Fuse Pullers, Clip clamps, Blown-fuse Indicators, Triggers,
ACCESSORIES Actuators and Switches.
K
DISCONNECT SWITCHES Fusible Disconnect Switches, Non-Fusible Disconnect Switches, Load Break Disconnect .
Switches, Enclosed Disconnect Switches, Engineered Switches, AC Disconnect Switches
APPLICATION INFORMATION Covers all common electrical applications plus short circuit calculations,
definitions and fuse specifications. L
CROSS REFERENCE and INDEX
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Fuse Quick Selector
The following are U.S. Trademarks of Ferraz Shawmut and apply to the products described herein.
AMP-TRAP SHAWMUT
TPMOV PowerBar
TRI-ONIC
Surge-Trap™ TRIGGER ULTRASAFE
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
2
Product Guide
Class J Time Delay Class L Time Delay Class RK1 Time Delay Class CC Time Delay
1 to 600A 100 to 6000A 1/10 to 600A 1-1/2” x 13/32”
600V AC, 200kA I.R. 600V AC, 200kA I.R. A2D: 250V AC, 200kA I.R. UL Listed
300kA I.R. UL Witnessed 300kA I.R. UL Witnessed A6D: 600V AC, 200kA I.R. CSA Certified
500V DC, 100kA I.R. 601 to 3000A DC all ratings ATDR:
Current Limiting 600V DC, 100kA I.R. Current Limiting 1/4 to 30A
UL Listed Current Limiting UL Listed 600V AC, 200kA I.R.
CSA Certified U.L. Listed (601 to 6000A) CSA Certified 300V DC, 100kA I.R.
Smart Spot Indicator CSA Certified (601 to 6000A) Smart Spot Indicator For motor protection.
Motor, motor controller, control The most current-limiting Class Motor controller and motor ATQR:
transformer, and circuit breaker L fuse available today. For in- overcurrent protection. Very 1/10 to 30A
back-up protection. Space saving creased protection of AC and DC current limiting. Arc Flash 600V AC, 200kA I.R.
dimensions. Very current limiting. equipment. Arc Flash Mitigating. Mitigating. For transformer protection.
Arc Flash Mitigating.
A2 A5 A8 A 13 / A 16
B 20 B 23 B 27 B 31
Midget, Miniature
North American Power Fuses & PC Mount Fuses
AG ATMR OT ATQ
OTN
OTS
B 35 B 37 B 39 C2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
4
Product Guide
C5 C6 C 12 C 13
Semiconductor
Fuses
PCF
C 21 C 22 C 25 D2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
5
Product Guide
DIN BS88 Fuses DIN 000 Fuses DIN BS88 Fuses DIN 00 Fuses
gRB-URB, Size: 17x49 German Standard Protistor Fuses Protistor Fuses
12 to 100A gRB-URB, Size: 000 gRB/URB Size: 000 gRB/URB Size: 00
690V AC, 200kA I.R. 20 to 400A 690V (660V AC, 20 to 400A 16 to 450A
gR Class to 90A VDE 636-23 200kA I.R. tested) 315A, 660V, 690V (660V AC, 200kA I.R. 690V AC, 200kA I.R.
aR Class (100A) VDE 636-23 350 & 400A, 500V, 500V AC, tested) 315A, 660V, 350 & 450A, 600V
and IEC 269.4 120kA I.R. tested 400A, 500V, 500V AC, 120kA 690V AC,
Extremely high gR Class to 125A VDE 636-23 I.R. tested 200kA I.R. (tested)
interrupting rating aR Class (100A) VDE 636-23 gR Class to 125A VDE 636-23 gR Class to 160A VDE 636-23
UL & CSA Recognized and IEC 269.4 aR Class (75 to 400A) VDE aR Class to
German std w/o BFI Extremely high 636-23 and IEC 269.4 450A VDE 636-23
German std w/separate BFI interrupting rating Extremely high interrupting and IEC 269.4
DIN 43623/00C 3 Models to DIN 43653-00C rating Extremely high interrupting rat-
British std w/o BFI are UL & CSA Recognized UL & CSA Recognized ing, DIN 43653/00C
British std w/separate BFI 1 Model to DIN 43620 2 Models to BS 88-4 and EN DIN 43620/00
BS 88-4 60 269.4 std (solid blades)
D 48 D 50 D 56 D 58
Medium Voltage
A240R
A480R
E 36 E 39 F2 G2
G 26 G 31 G 35 G 37
H2 H 10, H 13, H 15 H 17 H 28
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
9
Product Guide
H 33 H 36 H 44 H 45
H 64 I2 I4 J2
Disconnect
Switches
AOS-Q
AOS-S
J4 J6 J8 K2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
11
Product Guide
on Application
Disconnect Switches (cont.) Information
K 42 K 53 K 56 L2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
12
Amp-Trap 2000®
Fuses
For Type 2, no damage
circuit protection in all the
configurations you need.
• Class L / A4BQ
Our solution: By opening in less than 1/4 cycle under short
circuit conditions, Amp-trap 2000® fuses current limit enough
to prevent undue downstream damage — and therefore comply • Class RK1 / A2D & A6D
with the extra-stringent IEC, Type-2 standard. In addition, their
current-limiting ability ranks among the industry’s highest,
• Class CC / ATDR
allowing for motor starting and transformer inrush current
without nuisance opening.
• Class CC / ATQR
Want more information fast? For more technical or application-
specific information, please call our Amp-trap 2000® experts, at
978-462-6662; 416-252-9371 in Canada; or visit our website at
us.ferrazshawmut.com.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SMARTSPOT INDICATOR AMP-TRAP 2000®
Features/Benefits
➤ Solid State SmartSpot Indicator
➤ Time delay for motor starting and transformer inrush
➤ 300kA interrupting rating - self-certified,
UL witnessed tests
➤ Extremely current limiting for low peak let-thru current
➤ Most current limiting UL class fuse
➤ Recommended for Arc Flash energy reduction
➤ Small footprint requires less mounting space and
allows smaller, more economical fuse blocks
➤ Easy 2-to-1 selectivity for prevention of nuisance
shutdowns
➤ Unique Class J dimensions prevent replacement errors
➤ High-visibility orange label gives instant recognition
➤ Metal-embossed date and catalog number for
HIGHLIGHTS: APPLICATIONS: traceability and lasting identification
➤ Smart Spot Indicator ➤ Motor Circuits ➤ Fiberglass body provides dimensional stability in harsh
industrial settings
➤ Time Delay ➤ Mains ➤ High-grade silica filler ensures fast arc quenching
➤ Highly Current Limiting ➤ Feeders ➤ Optional EI Indicator/Switch mount for AJT70 to
➤ Arc Flash Mitigating ➤ Branch Circuits 600 open fuse indication
➤ DC Ratings ➤ Lighting, Heating & Ratings Approvals
➤ Optional Mechanical General Loads
Indicator (70 to 600A ➤ Transformers ➤ AC: 1 to 600A AJT (1-600):
600VAC, 200kA I.R. ➤ UL Listed to
fuses) ➤ Control Panels (self certified for Standard 248-8
➤ Circuit Breaker Back-up 600VAC, 300kA I.R., File E2137
UL witnessed) ➤ DC Listed to UL
➤ Bus Duct
Standard 248
➤ Load Centers DC: 1 to 600A
500VDC, 100kA I.R. ➤ CSA Certified to
➤ Note: See Motor Fuse Standard C22.2
Applications Tables on No. 248.8
page L9 ➤ IEC 269-2-1
AJT (70-600) EI:
➤ UL Listed to File E60314
➤ DC Tested to UL
Standard 248
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A
SMARTSPOT INDICATOR AMP-TRAP 2000®
1-60A
70-600A
Dimensions
AMPERE A B C D E F G H
RATING In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. mm
1-30 2-1/4 57 13/16 21 - - - - - - - - - - - -
31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - -
61-100 4-5/8 117 1-1/16 27 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7
101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7
201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 14 13/32 10
401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A
SMARTSPOT INDICATOR AMP-TRAP 2000®
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A
AMP-TRAP 2000®
A
Amp-trap 2000® A4BQ fuses are 20% more current
limiting than any other Class L fuse on the market.
When correctly coordinated, they bring a superior
level of protection to service entrance equipment.
Downstream circuit components have maximum
protection against short circuit let-thru current.
A4BQ’s built-in, 4-second time delay characteristic
(at 500% of rated current) accommodates harmless
inrush currents with no nuisance opening.
Features/Benefits
➤ Fastest operation under short circuit conditions:
Let-thru currents are typically 20% lower, with a
corresponding let-thru energy (clearing I2t) up to 40%
lower than the next fastest Class L fuse
➤ Time delay for high inrush loads such as motors and
transformers, without nuisance opening
➤ 300kA interrupting rating - self-certified,
UL witnessed tests
➤ Most current limiting for lowest peak let-thru current;
even at fault currents up to 300kA
➤ Recommended for Arc Flash energy reduction
➤ Pure silver links ensure lowest let-thru current and
longer fuse life
➤ Easy 2-to-1 selectivity for prevention of nuisance
shutdowns and “blackouts”
➤ Rejection-style design prevents replacement errors
➤ High-visibility orange label gives instant recognition
➤ Reduced inventory because A4BQ can replace all older
HIGHLIGHTS: APPLICATIONS: types of Class L fuses now in service
➤ Metal-embossed date and catalog number for traceability
➤ Time Delay ➤ Mains, Feeders and lasting identification
➤ Industry’s Most ➤ Large Motors ➤ Fiberglass body provides dimensional stability in harsh
Current-Limiting industrial settings
➤ Lighting, Heating & ➤ High-grade silica filler ensures fast arc quenching
Class L Fuse General Loads
➤ Arc Flash mitigating ➤ Circuit Breaker Back-up
➤ Pure Silver Elements ➤ DC Rated: UPS DC Ratings Approvals
➤ AC & DC Rated ➤ Links, Battery
➤ AC: 100 to 6000A ➤ UL Listed to Standard
Disconnects, Other 600VAC, 200kA I.R. 248-10 (601-6000A)
DC Applications (self certified for File E2137
600VAC, 300kA I.R.,
UL witnessed) 4- ➤ DC Listed to UL
second delay at 500% Standard 248
rating (601-3000A)
*Please contact factory for special trigger actuator ➤ CSA Certified to
➤ DC: 601 to 3000A
500VDC, 100kA I.R. Standard C22.2
No. 248.10
(601-6000A)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A
AMP-TRAP 2000®
3001-4000A
100-800A
Dimensions 801-2000A
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
A4BQ601 to 6000
A
Melting Time – Current Data, 600V Fuses
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A
SMARTSPOT INDICATOR AMP-TRAP 2000®
1/10
15/100
2/10
A2D1/10R
A2D15/100R
A2D2/10R
A6D1/10R
A6D15/100R
A6D2/10R
3-1/2
4
4-1/2
A2D3-1/2R
A2D4R
A2D4-1/2R
A6D3-1/2R
A6D4R
A6D4-1/2R
50
60
70
A2D50R
A2D60R
A2D70R
A6D50R
A6D60R
A6D70R
A
3/10 A2D3/10R A6D3/10R 5 A2D5R A6D5R 75 A2D75R -
4/10 A2D4/10R A6D4/10R 5-6/10 A2D5-6/10R A6D5-6/10R 80 A2D80R A6D80R
1/2 A2D1/2R A6D1/2R 6 A2D6R A6D6R 90 A2D90R A6D90R
6/10 A2D6/10R A6D6/10R 6-1/4 A2D6-1/4R A6D6-1/4R 100 A2D100R A6D100R
8/10 A2D8/10R A6D8/10R 7 A2D7R A6D7R 110 A2D110R A6D110R
1 A2D1R A6D1R 8 A2D8R A6D8R 125 A2D125R A6D125R
1-1/8 A2D1-1/8R A6D1-1/8R 9 A2D9R A6D9R 150 A2D150R A6D150R
1-1/4 A2D1-1/4R A6D1-1/4R 10 A2D10R A6D10R 175 A2D175R A6D175R
1-4/10 A2D1-4/10R A6D1-4/10R 12 A2D12R A6D12R 200 A2D200R A6D200R
1-6/10 A2D1-6/10R A6D1-6/10R 15 A2D15R A6D15R 225 A2D225R A6D225R
1-8/10 A2D1-8/10R A6D1-8/10R 17-1/2 A2D17-1/2R A6D17-1/2R 250 A2D250R A6D250R
2 A2D2R A6D2R 20 A2D20R A6D20R 300 A2D300R A6D300R
2-1/4 A2D2-1/4R A6D2-1/4R 25 A2D25R A6D25R 350 A2D350R A6D350R
2-1/2 A2D2-1/2R A6D2-1/2R 30 A2D30R A6D30R 400 A2D400R A6D400R
2-8/10 A2D2-8/10R A6D2-8/10R 35 A2D35R A6D35R 450 A2D450R A6D450R
3 A2D3R A6D3R 40 A2D40R A6D40R 500 A2D500R A6D500R
3-2/10 A2D3-2/10R A6D3-2/10R 45 A2D45R A6D45R 600 A2D600R A6D600R
0-60A
61-600A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A
SMARTSPOT INDICATOR AMP-TRAP 2000®
A2D15 to 600
Melting Time – Current Data, 250V Fuses
Current in Amperes
Time in Seconds
A2D1/10 to 10
Melting Time – Current Data, 250V Fuses
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A 10
SMARTSPOT INDICATOR AMP-TRAP 2000®
A6D15 to 600
A
Melting Time – Current Data,600V Fuses
Current in Amperes
Time in Seconds
A6D1/10 to 8
Melting Time – Current Data, 600V Fuses
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A 11
SMARTSPOT INDICATOR AMP-TRAP 2000®
A
Amp-trap 2000® ATDR small-dimension fuses can
provide IEC Type 2 “no damage” protection to your
facility’s increasingly sensitive branch circuit com-
ponents and small motors – minimizing the risk of
fault-related damage. ATDR Class CC fuses deliver
the best time delay characteristics in their class with
excellent cycling ability for small motor loads.
Features/Benefits
HIGHLIGHTS: Applications:
➤ Time Delay ➤ Small Motors
➤ Best Choice for Small ➤ Contactors
Motor Protection ➤ Lighting, Heating & Ratings Approvals
➤ Highly Current- General Loads
Limiting ➤ AC: 1/4 to 30A ➤ UL Listed to
➤ Branch Circuit Protector 600VAC, 200kA I.R. Standard 248-4
➤ AC & DC Rated File 2137
➤ DC: 1/4 to 30A ➤ CSA Certified to
300VDC, 100kA I.R. Standard C22.2
No. 248.4
➤ DC Listed to
UL Standard 248
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A 13
AMP-TRAP 2000®
Dimensions
A
Melting Time – Current Data, 600V Fuses
Current in Amperes
Time in Seconds
Features/Benefits
➤ Time delay for control transformer inrush loads without
nuisance opening
➤ Highly current limiting for low peak let-thru current
➤ Rejection-style design prevents replacement errors
(when used with recommended fuse blocks)
➤ High-visibility orange label ensures instant recognition,
and simplifies replacement
➤ Metal-embossed date and catalog number
for traceability and lasting identification
➤ Fiberglass body provides dimensional stability in harsh
industrial settings
➤ High-grade silica filler ensures fast arc quenching and
high current limitation
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A 16
AMP-TRAP 2000®
A
AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG
RATING NUMBER RATING NUMBER RATING NUMBER RATING NUMBER
1/10 ATQR1/10 8/10 ATQR8/10 2-8/10 ATQR2-8/10 7-1/2 ATQR7-1/2
1/8 ATQR1/8 1 ATQR1 3 ATQR3 8 ATQR8
3/16 ATQR3/16 1-1/8 ATQR1-1/8 3-2/10 ATQR3-2/10 9 ATQR9
2/10 ATQR2/10 1-1/4 ATQR1-1/4 3-1/2 ATQR3-1/2 10 ATQR10
1/4 ATQR1/4 1-4/10 ATQR1-4/10 4 ATQR4 12 ATQR12
3/10 ATQR3/10 1-1/2 ATQR1-1/2 4-1/2 ATQR4-1/2 15 ATQR15
4/10 ATQR4/10 1-6/10 ATQR1-6/10 5 ATQR5 17-1/2 ATQR17-1/2
1/2 ATQR1/2 1-8/10 ATQR1-8/10 5-6/10 ATQR5-6/10 20 ATQR20
6/10 ATQR6/10 2 ATQR2 6 ATQR6 25 ATQR25
3/4 ATQR3/4 2-1/4 ATQR2-1/4 6-1/4 ATQR6-1/4 30 ATQR30
2-1/2 ATQR2-1/2 7 ATQR7
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A 17
AMP-TRAP 2000®
Peak Let-Thru Current Data–ATQR1/4 to 30, 600 Volts AC Melting Time-Current Data ATQR 3/16 to 1-8/10, 600 Volts
Maximum Instantaneous Peak Let-Thru Amperes
Time in Seconds
Current in Amperes
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
A 18
North American
Power Fuses
The most popular North American
power fuses — to meet the most
popular protection priorities.
Our solution: Ferraz Shawmut’s comprehensive power fuse • Class L / Amp-trap® A4BT
offering covers a complete range of applications and a complete • Class T / Amp-trap® A3T & A6T
range of circuit-protection needs. Whether it’s the characteristics
• Class RK1 /
of our Tri-onic® time-delay fuses. The high current-limiting capacity Amp-trap® A2K & A6K
of our original Amp-trap® power fuses. The cost-efficient protec-
• Class RK1/Amp-trap® HSRK
tion of our One-Time fuses. Or some other application-specific
power fuse solution. • Class G / Amp-trap® AG
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TRI-ONIC®
Features/Benefits
➤ Solid State SmartSpot Indicator
➤ Time delay for motor start-ups and transformer inrush
currents without nuisance opening
➤ Current limiting for low peak let-thru current
➤ Rejection-style design prevents replacement errors
(when used with recommended fuse blocks)
➤ Easy-to-read label for quick recognition
and replacement
➤ Metal-embossed date and catalog number for
traceability and lasting identification
➤ Fiberglass body provides dimensional stability in
harsh industrial settings
➤ High-grade silica filler ensures fast arc quenching and
high current limitation
HIGHLIGHTS: Applications:
➤ Time Delay ➤ Motor Circuits
➤ Current Limiting ➤ Mains
Ratings Approvals
➤ AC & DC Rated ➤ Feeders
➤ Branch Circuits ➤ TR ➤ UL Listed to Standard
AC: 1/10 to 600A 248-12 File E2137
➤ Transformers 250VAC, 200kA I.R.
➤ CSA Certified to
➤ Service Entrance ➤ DC: 1/10 to 2 8/10A Standard C22.2
Equipment & 35 to 400A, 250VDC, No. 248.12
➤ General-purpose 20kA I.R.; 3 to 30A &
450 to 600A, 160VDC, ➤ DC Listed to UL
Protection 20kA I.R. Standard 248 TRS only
➤ TRS
AC: 1/10 to 600A
600VAC, 200kA I.R.
➤ DC: 1/10 to 12A,
600VDC, 20kA I.R.;
15 to 60A, 300VDC,
20kA I.R. 70 to 600A,
600VDC, 100kA I.R.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
TRI-ONIC®
0-60A
61-600A
Dimensions
AMPERE A B C D E Recommended Fuse Blocks With
RATING In. mm In. mm In. mm In. mm In. mm Box Connectors For Tri-onic®
250V-TR FUSES
Class RK5 Fuses
0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - - Fuse Catalog Number
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25 Ampere 250V 600V
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35 Rating 1 Pole 3 pole 1 pole 3 pole
201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48 0-30 20306R 20308R 60306R 60308R
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57 31-60 20606R 20608R 60606R 60608R
600V-TRS FUSES 61-100 21036R 21038R 61036R 61038R
0-30 5 127 13/16 21 - - - - - - 101-200 22001R 22003R 62001R 62003R
31-60 5-1/2 139 1-1/16 27 - - - - - - 201-400 24001R 24003R 64001R 64003R
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25 401-600 2631R 2633R 6631R 6633R
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
TRI-ONIC®
Current in Amperes
Time in Seconds
TR1/10 to 12
Melting Time – Current Data, 250V Fuses
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
TRI-ONIC®
TRS15 to 600
Melting Time – Current Data , 600V Fuses
Current in Amperes
Time in Seconds
TRS1/10 to 12
Melting Time – Current Data. 600V Fuses
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
TRI-ONIC®
Features/Benefits
➤ DC rated for mine duty and other long time-constant
applications
➤ Time delay for motor start-ups and high inrush loads
without nuisance opening
➤ Rugged glass melamine body for superior
➤ Reliability in harsh environments
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
TRI-ONIC®
0-60 Amperes
61-400 Amperes
Dimensions
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
TRS-RDC60 to 400
Melting Time – Current Data, 600V Fuses
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
AMP-TRAP®
Features/Benefits
➤ Optimized over-load capability for withstanding
elevated levels of current during electronic
motor controller starts
Ratings Approvals
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B
AMP-TRAP®
Dimensions
Fig 1 Fig 2
AMPERE A B C D E F G H
RATING In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. mm
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 10
AMP-TRAP®
B
15 0.02 0.36 0.15 0.23 0.12 2.6
17.5 0.03 0.45 0.19 0.29 0.15 3.5
20 0.04 0.58 0.24 0.37 0.19 3.7
25 0.08 1.2 0.50 0.77 0.40 4
30 0.16 2 0.84 1.3 0.66 4.1
35 0.16 1.5 0.63 0.96 0.50 5.3
40 0.27 2.3 1.0 1.5 0.76 5.5
45 0.32 3.3 1.4 2.1 1.1 6
50 0.44 5.5 2.3 3.5 1.8 6.8
60 0.72 8.0 3.4 5.1 2.6 8.4
70 1.2 12 5.0 7.7 4.0 10
80 1.6 15 6.3 9.6 5.0 11
90 2.3 21 8.8 13 6.9 13
100 2.7 23 9.7 15 7.6 14
110 2.3 21 10 13.9 8 18
125 3.4 29 14 19 11 19
150 5.1 41 20 27 16 22
175 8.0 60 29 40 23 24
200 14 92 44 61 35 26
225 14 110 53 73 42 30
250 16 130 62 86 49 36
300 26 200 96 132 76 38
350 37 290 139 191 110 40
400 63 450 216 297 171 42
450 67 500 240 330 190 58
500 98 600 288 396 228 59
600 141 900 432 594 342 68
1.0 1.0
Correction Factor for Watts Loss
.8 .8
Correction Factor for I2t
110-600 AMP
.6 .6
.4 .4
.2 .2
15-100 AMP
0
0 100 200 300 400 500 600 50 60 70 80 90 100
Operating Voltage (AC RMS Volts) Percent Rated Current
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 11
AMP-TRAP®
Clearing I2t at 500 VDC 100kA, L/R = 10mS DC Voltage vs. Time Constant
AMPERE CLEARING I2t @ 500 VDC
RATING L/R = 10 ms (A2s X 103)
15 0.12
17.5 0.18
20 0.24
25 0.46
DC Voltage Capability
30 0.91
35 0.60
40 0.92
45 1.3
50 2.2
60 3.2
70 4.8
80 6.2
90 8.9
100 10
110 8.8
125 13
150 19
175 28
200 46
225 52
250 59
300 96
350 136
400 230
450 270
500 390
600 560 L/R Time Constant (mS)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 12
AMP-TRAP®
B
Time in Seconds
Features/Benefits
➤ High current limitation for low peak let-thru current
➤ Unique dimensions prevent replacement by other fuse
classes
➤ Fiberglass body provides dimensional stability in
harsh industrial environments
➤ Easy-to-read imprint label for quick recognition
and replacement
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 14
AMP-TRAP®
B
6 A4J6 70 A4J70 250 A4J250
10 A4J10 75 A4J75 300 A4J300
15 A4J15 80 A4J80 350 A4J350
Dimensions
AMPERE A B C D E F G H
RATING In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. mm
1-30 2-1/4 57 13/16 21 - - - - - - - - - - - -
31-60 2-3/8 60 1-1/16 27 - - - - - - - - - - - -
61-100 4-5/8 117 1-1/8 29 1/8 3.2 3/4 19 1 25 3-5/8 92 3/8 10 9/32 7
101-200 5-3/4 146 1-5/8 41 3/16 4.8 1-1/8 29 1-3/8 35 4-3/8 111 3/8 10 9/32 7
201-400 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 13 13/32 10
401-600 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 15
AMP-TRAP®
A4J30 to 600
Melting Time – Current Data, 600V Fuses
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 16
AMP-TRAP®
A4BY CLASS l
Features/Benefits
➤ Unique dimensions prevent replacement by other
fuse classes
➤ Blade stamped catalog numbers for permanent
identification
➤ Glass melamine body and plated terminals
provide superior reliability in harsh environments
Indicators
Optional built-in fuse indicators (-TI) are available. Consult factory.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 17
AMP-TRAP®
4001-6000A
200-800A
801-2000A
Dimensions
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
200-600 8-5/8 219 2 51 5/16 8 1-5/8 41 2-13/32 61
601-800 8-5/8 219 2-1/2 63 3/8 9 2 51 2-13/32 61
801-1200 10-3/4 273 2-1/2 63 3/8 9 2 51 3-15/32 88
1201-1600 10-3/4 273 3 76 7/16 11 2-3/8 60 3-15/32 88
1601-2000 10-3/4 273 3-1/2 89 1/2 13 2-3/4 70 3-15/32 88
2001-2500 10-3/4 273 4-1/2 114 3/4 19 3-1/2 89 3-15/32 88
2501-3000 10-3/4 273 5 127 3/4 19 4 102 3-15/32 88
3001-4000 10-3/4 273 5-3/4 146 3/4 19 4-3/4 121 3-15/32 88
4001-5000 10-3/4 273 6-1/4 159 1 25 5-1/4 133 3-15/32 88
5001-6000 10-3/4 273 7-1/8 181 1 25 5-3/4 146 3-15/32 88
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 18
AMP-TRAP®
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 19
AMP-TRAP®
Features/Benefits
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 20
AMP-TRAP®
200-800A
801-2000A
Dimensions
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 21
AMP-TRAP®
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 22
AMP-TRAP®
Features/Benefits
HIGHLIGHTS: Applications:
Ratings Approvals
➤ Fast Acting ➤ Loadcenters
➤ Extremely Current ➤ Panelboards ➤ A3T ➤ UL Listed to
AC:1 to 1200A Standard 248-15
Limiting ➤ Switchboards File E2137
300VAC, 200kA I.R.
➤ Small Physical Size ➤ Circuit Breakers DC: 1 to 1200A ➤ CSA Certified to
➤ DC Ratings ➤ Metering Centers 160VDC, 50kA I.R. Standard C22.2
No. 248.15
➤ A6T
AC: 1 to 800A ➤ DC Listed to UL
Recommended Fuse Blocks With Box Connectors for 600VAC, 200kA I.R. Standard 248
Amp-trap Class T Fuses DC: 1 to 800A
300VDC, 100kA I.R.
Catalog Number
Ampere 300V 600V
Rating 1-pole 3-pole 1-pole 3-pole
30 30306T 30308T 60306T 60308T
60 30606T 30608T 60606T 60608T
100 31031T 31033T 61031T 61033T
200 32031T 32033T 62031T 62033T
400 34031T 34033T 64031T –
600 36031T – 66031T –
A3T A6T
A3T 1-60
A6T 1-30
A6T 31-60
A3T 61-1200
AMPERE A B C D F G J
RATING In. mm In. mm In. mm In. mm In. mm In. mm In. mm
A3T
1-30 .88 22.4 .41 10.3 - - - - - - - - - -
31-60 .88 22.4 .56 14.1 - - - - - - - - - -
61-100 2.16 54.9 .81 20.6 .12 3.2 .75 19.0 1.56 39.6 .28 7.1 .82 20.8
101-200 2.44 62.0 1.06 26.9 .19 4.8 .88 22.4 1.70 43.2 .34 8.6 .83 21.1
201-400 2.75 69.8 1.33 33.8 .25 6.4 1.00 25.4 1.84 46.7 .41 10.4 .84 21.3
401-600 3.06 77.7 1.62 41.1 .31 7.8 1.25 31.8 2.03 51.6 .48 12.2 .84 21.3
601-800 3.38 85.8 2.08 52.8 .38 9.7 1.75 44.4 2.22 56.4 .55 14.0 .88 22.4
801-1200 4.00 102 2.52 64.0 .44 11.2 2.00 50.8 2.53 64.3 .61 15.5 1.03 26.2
A6T
1-30 1.50 38.1 .57 14.5 - - - - - - - - - -
31-60 1.57 39.9 .81 20.6 1.51 38.4 1.00 25.4 - - - - - -
61-100 2.95 75.0 .82 20.8 .12 3.2 .75 19.0 2.35 59.7 .28 7.1 1.58 40.1
101-200 3.26 82.8 1.07 27.2 .19 4.8 .88 22.4 2.51 63.7 .34 8.6 1.61 41.0
201-400 3.62 92.1 1.62 41.3 .25 6.4 1.00 25.4 2.72 69.1 .41 10.4 1.70 43.2
401-600 3.98 101.2 2.06 52.4 .31 7.9 1.25 31.8 2.95 75.0 .48 12.2 1.70 43.2
601-800 4.33 110.0 2.50 63.5 .37 9.5 1.75 44.4 3.17 80.5 .56 14.1 1.70 43.2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 24
AMP-TRAP®
A3T30 to 1200
Melting Time – Current Data, 300V Fuses
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 25
AMP-TRAP®
Current in Amperes
Time in Seconds
Features/Benefits
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 27
AMP-TRAP®
Dimensions
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
250V-A2K FUSES
0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - -
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35
201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
600V-A6K FUSES
0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 28
AMP-TRAP®
A2K30 to 600
Melting Time – Current Data, 250V Fuses
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 29
AMP-TRAP®
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 30
AMP-TRAP®
B
conductor fuse performance with NEC branch circuit
compliance. The fuse was designed with two specific
applications in mind:
1. To provide semiconductor fuse performance
to solid state drive applications but in the
larger RK body sizes that have been typically
installed in older systems.
2. To provide industrial power applications with
the most current limiting fuse available,
which in turn provides the best arc flash
mitigation available to power systems using
the larger RK size fuses.
Features/Benefits
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 31
Amp-trap®
Standard Fuse Ampere Ratings, Catalog Numbers Recommended Fuse Blocks With Box
Connectors For Amp-trap® Class RK1 Fuses
Ampere Catalog # Ampere Catalog #
Rating 600V Rating 600V Fuse Catalog Number
Ampere 600V
70 HSRK70R 200 HSRK200R Rating 1 pole 3 pole
80 HSRK80R 225 HSRK225R
61-100 61036R 61038R
90 HSRK90R 250 HSRK250R
101-200 62001R 62003R
100 HSRK100R 300 HSRK300R
201-400 64001R 64003R
110 HSRK110R 350 HSRK350R
401-600 6631R 6633R
125 HSRK125R 400 HSRK400R
150 HSRK150R 450 HSRK450R A variety of pole configurations and ter-
mination provisions are available. Refer
175 HSRK175R 500 HSRK500R
to the fuse block section of this catalog
600 HSRK600R for details.
70-600A
Dimensions
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
600V-HSRK FUSES
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 19 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 66 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 32
Amp-trap®
Max Clearing
Ampere Pre-arc (A2s I2t @ 600V AC
B
Rating (A) X 103)
(A2s X 103)
70 1.2 14
80 1.6 17
90 2.3 24
100 2.7 26
110 2.3 23
125 3.4 32
150 5.1 45
175 8.0 65
200 14 100
225 14 110
250 16 130
300 26 200
350 37 290
400 63 450
450 67 500
500 98 600
600 141 900
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 33
Amp-trap®
Watts Loss Data HSRK70 — 600R, 600V AC Peak Let-Thru Data HSRK70 — 600R, 600V AC
AG class G
Features/Benefits
AMPERE A B C
Standard Fuse Ampere Ratings, RATING In. mm In. mm In. mm
Catalog Numbers
1/2-15A 1.31 33.3 .406 10.3 .28 7.1
AMPERE CATALOG AMPERE CATALOG
RATING NUMBER RATING NUMBER 20A 1.41 35.8 .406 10.3 .28 7.1
4 AG4 40 AG40
5 AG5 45 AG45
6 AG6 50 AG50
8 AG8 60 AG60
10 AG10
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 35
AMP-TRAP®
Current in Amperes
Time in Seconds
AG15 to 60
Melting Time – Current Data, 480V Fuses
Current in Amperes
Time in Seconds
Maximum Instantaneous Peak Let-Thru Amperes
ATMR class CC
Features/Benefits
➤ Rejection style design prevents replacement errors
when used with recommended fuse blocks
➤ Versatile design for individual component and
branch circuit protection
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 37
AMP-TRAP®
Refer to the Class CC Fuse Block section of this catalog for other details.
ATMR1/10 to 30
Melting Time – Current Data, 600V Fuses
Current in Amperes
Time in Seconds
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 38
ONE-TIME
Features/Benefits
➤ Easy to read imprint label for quick recognition and
replacement
➤ Low cost for high protection value
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 39
ONE-TIME
* In Canada
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 40
ONE-TIME
Current in Amperes
B
Time in Seconds
OTS30 to 600
Melting Time – Current Data, 600V Fuses
Current in Amperes
Time in Seconds
Peak Let-Thru Current Data – OT, OTN & OTS30 to 600, 250 and 600 Volts AC
Maximum Instantaneous Peak Let-Thru Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 41
RENEWABLE
Features/Benefits
➤ Knurled bushings for ease of disassembly
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 42
RENEWABLE Class h Fuses/links RF/rfS & rl/rls
Standard Fuse Ampere Ratings, Catalog Numbers
Ampere Catalog Number Ampere Catalog Number Ampere Catalog Number
Rating 250V 600V Rating 250V 600V Rating 250V 600V
1 RF1/RL1 RFS1/RLS1 45 RF45/RL45 RFS45/RLS45 225 RF225/RL225 RFS225/RLS225
2 RF2/RL2 RFS2/RLS2 50 RF50/RL50 RFS50/RLS50 250 RF250/RL250 RFS250/RLS250
3 RF3/RL3 RFS3/RLS3 60 RF60/RL60 RFS60/RLS60 300 RF300/RL300 RFS300/RLS300
5
6
10
RF5/RL5
RF6/RL6
RF10/RL10
RFS5/RLS5
RFS6/RLS6
RFS10/RLS10
70
80
90
RF70/RL70
RF80/RL80
RF90/RL90
RFS70/RLS70
RFS80/RLS80
RFS90/RLS90
350
400
450
RF350/RL350
RF400/RL400
RF450/RL450
RFS350/RLS350
RFS400/RLS400
RFS450/RLS450
B
15 RF15/RL15 RFS15RLS15 100 RF100/RL100 RFS100/RLS100 500 RF500/RL500 RFS500/RLS500
20 RF20/RL20 RFS20/RLS20 110 RF110/RL110 RFS110/RLS110 600 RF600/RL600 RFS600/RLS600
25 RF25/RL25 RFS25/RLS25 125 RF125/RL125 RFS125/RLS125
30 RF30/RL30 RFS30/RLS30 150 RF150/RL150 RFS150/RLS150
35 RF35/RL35 RFS35/RLS35 175 RF175/RL175 RFS175/RLS175
40 RF40/RL40 RFS40/RLS40 200 RF200/RL200 RFS200/RLS200
61-600A
Dimensions
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
250V-RF FUSES
0-30 2 51 9/16 14 - - - - - -
31-60 3 76 13/16 21 - - - - - -
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 18 1 25
101-200 7-1/8 181 1-9/16 40 3/16 5 1-1/8 28 1-3/8 35
201-400 8-5/8 219 2-1/16 54 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
600V-RFS FUSES
0-30 5 127 13/16 21 - - - - - -
31-60 5-1/2 139 1-1/16 27 - - - - - -
61-100 7-7/8 200 1-5/16 34 1/8 3 3/4 18 1 25
101-200 9-5/8 244 1-13/16 46 3/16 5 1-1/8 28 1-3/8 35
201-400 11-5/8 295 2-9/16 67 1/4 6 1-5/8 41 1-7/8 48
401-600 13-3/8 340 3-1/8 80 1/4 6 2 51 2-1/4 57
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
B 43
• Amp-trap® ATQ
• Amp-trap® A6Y-2B
• Amp-trap® ATM
• Tri-onic® TRM
• FSM
• OTM One-time
• GGU
• GFN Indicating
Our solution: Our international range of midget and miniature • GSD/GSD-V; GSF/GSF-V
dimension and new PC mount fuses offers you all the protection • GGX; GAB; GSR-V
you require. A wide range of ratings. Special characteristics like
• SMG/SMG-V; STG/STG-V
time-delay and low I2t. All within a footprint of 1-1/2” x 13/32”
• MRF, MRT
or less.
• SFRT; SFRB; SFRG; FSFE
Want more information fast? For more technical or application- • AF; AF2; AF3
specific information, please call our midget and miniature dimen-
• AFH
sion fuse experts, at 978-462-6662; 416-252-9371 in Canada; or
visit our website at us.ferrazshawmut.com. • PCF; PCS; PCT
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AMP-TRAP®
Melting Time – Current Data 1/10 - 3-1/2 Amperes, 500 Volts AC Melting Time – Current Data 4 - 30 Amperes, 500 Volts AC
Time in Seconds
Time in Seconds
C
HIGHLIGHTS: Applications: Ratings Approvals
➤ Ferraz Shawmut Inc.
➤ Fast Acting ➤ Supplemental protection ➤ AC: 1/4 to 3A
600VAC, 10kA I.R.; Certified
of 600V (up to 3A) and
3-2/10 to 15A
500V (3-2/10-15A)
500VAC, 10kA I.R.
AC circuits
➤ Small motors,
transformers, and Melting Time – Current Data 1/4 - 3 Amperes, 600 Volts AC
control circuits 3-2/10 - 15 Amperes, 500 Volts AC
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C
AMP-TRAP®
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C
tri-onic®
Melting Time – Current Data 1/10 - 3-1/2 Amperes, 250 Volts AC Melting Time – Current Data 4 - 30 Amperes, 250 Volts AC
Time in Seconds
Time in Seconds
Features/Benefits
➤ For the protection of multi-meters
➤ 1000V AC/DC for full range protection
➤ 100% Current Rated for continuous current
carrying capability
➤ Glass melamine body and plated terminals provide
superior reliability and performance
HIGHLIGHTS: DIMENSions:
➤ Fast-Acting
➤ 1000 Volts AC/DC 10ms Catalog No. A B
FSM44/100 1.375” 0.406”
➤ 20,000A Interrupting Rating @ 1000V AC/DC for all FSM11 1.500” 0.406”
ratings FSM15 1.500” 0.406”
Cross Reference
Ferraz Shawmut FSM replaces the
Bussmann: DMM-B
Littelfuse: FLU
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C
MULTI-METER PROTECTION FUSE
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C
C
ONE TIME
20 OTM20
25 OTM25
30 OTM30
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C
GGU 1-1/2” x 13/32” MIDGET FUSES
C
Standard Fuse Ampere Applications: Ratings Approvals
Ratings, Catalog Numbers
➤ AC: 1 to 30A ➤ UL Recognized 20-30A
AMPERE CATALOG ➤ General Purpose 125VAC, 10kA I.R.
RATING NUMBER ➤ 125 Volt AC Circuits
3 GGU3 ➤ Supplemental Protection
4 GGU4
5 GGU5
8 GGU8
10 GGU10
15 GGU15
20 GGU20
25 GGU25
30 GGU30
Time in Seconds
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C
GFN 1-1/2” x 13/32” MIDGET FUSES
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 10
AMP-TRAP®
30 A25Z30-2 360
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 11
SBS 1-3/8” x 13/32” FERRULE FUSES
Cross Reference: SBS will replace Bussmann BBS, Littelfuse BLS fuses
Time in Seconds
Standard Standard
Fuse Ampere Ratings Fuse Ampere Ratings
CATALOG AXIAL LEAD AMPERE CATALOG AXIAL LEAD AMPERE
VOLTS I.R. NUMBER CAT. NO RATING VOLTS I.R.
NUMBER CAT. NO RATING
1. 250VAC @ 35A I.R./125VAC @ 10kA I.R. 1. 250VAC @ 35A I.R./125VAC @ 10kA I.R.
2. 250VAC @ 100A I.R./125VAC @ 10kA I.R. 2. 250VAC @ 100A I.R./125VAC @ 10kA I.R.
3. 250VAC @ 200A I.R./125VAC @ 10kA I.R. 3. 250VAC @ 200A I.R./125VAC @ 10kA I.R.
4. 250VAC @ 750A I.R./125VAC @ 10kA I.R. 4. 125VAC @ 10kA I.R.
5. 250VAC @ 400A I.R./125VAC @ 10KA I.R. 5. 32VAC @ 300A I.R.
6. 125VAC @ 400A I.R.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 13
ELECTRONIC/GLASS FUSES
1. 250VAC @ 35A I.R./125VAC @ 10kA I.R. 1. 250VAC @ 35A I.R./125VAC @ 10kA I.R.
2. 250VAC @ 200A I.R./125VAC @ 10kA I.R. 2. 250VAC @ 100A I.R./125VAC @ 10kA I.R.
3. 250VAC @ 10kA I.R. 3. 250VAC @ 200A I.R./125VAC @ 10kA I.R.
4. 125VAC @ 10kA I.R. 4. 125VAC @ 10kA I.R.
5. 32VAC @ 1000A I.R. 5. 250VAC @ 100A I.R.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 14
ELECTRONIC/GLASS FUSES
Standard Standard
Fuse Ampere Ratings Fuse Ampere Ratings
CATALOG AXIAL LEAD AMPERE CATALOG AXIAL LEAD AMPERE
NUMBER CAT. NO RATING VOLTS I.R. NUMBER CAT. NO RATING VOLTS I.R.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 15
ELECTRONIC/GLASS FUSES
Standard Standard
Fuse Ampere Ratings Fuse Ampere Ratings
CATALOG AXIAL LEAD AMPERE CATALOG AXIAL LEAD AMPERE
NUMBER CAT. NO RATING VOLTS I.R. VOLTS I.R.
NUMBER CAT. NO RATING
* IEC Standards for 5x20mm fuses do not include ratings above * IEC Standards for 5x20mm fuses do not include ratings above
6.3 amperes. 6.3 amperes.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 16
ELECTRONIC/GLASS FUSES
1/6A through 10A, 250VAC, UL & CSA Recognized 1/2A through 8/10A, 250VAC
1A through 6-3/10A, 250VAC, SEMKO Approved 1A through 6-3/10A, 250VAC, SEMKO, VDE Approved
1A through 6-3/10A, 250VAC, VDE Approved 1A through 10A, 250VAC, UL and CSA Recognized
IEC 127-2 Standard Sheet 1* IEC-127-2 Standard Sheet 5*
Standard Standard
Fuse Ampere Ratings Fuse Ampere Ratings
CATALOG AXIAL LEAD AMPERE CATALOG AXIAL LEAD AMPERE
NUMBER CAT. NO RATING VOLTS I.R. VOLTS I.R.
NUMBER CAT. NO RATING
GSD1/16 GSD-V1/16 1/16A 250V 1 GSF1/2 GSF-V1/2 1/2A 250V 1
GSD8/100 GSD-V8/100 8/100A 250V 1 GSF630/1000 GSF-V630/1000 630/1000A 250V 1
GSD1/10 GSD-V1/10 1/10A 250V 1 GSF8/10 GSF-V8/10 8/10A 250V 1
GSD1/8 GSD-V1/8 1/8A 250V 1 GSF1 GSF-V1 1A 250V 1
GSD16/100 GSD-V16/100 16/100A 250V 1 GSF1-1/4 GSF-V1-1/4 1-1/4A 250V 1
GSD2/10 GSD-V2/10 2/10A 250V 1 GSF1-6/10 GSF-V1-6/10 1-6/10A 250V 1
GSD1/4 GSD-V1/4 1/4A 250V 1 GSF2 GSF-V2 2A 250V 1
GSD315/1000 GSD-V315/1000 315/1000A 250V 1 GSF2-1/2 GSF-V2-1/2 2-1/2A 250V 1
GSD4/10 GSD-V4/10 4/10A 250V 1 GSF3-15/100 GSF-V3-15/100 3-15/100A 250V 1
GSD1/2 GSD-V1/2 1/2A 250V 1 GSF4 GSF-V4 4A 250V 1
GSD630/1000 GSD-V630/1000 630/1000A 250V 1 GSF5 GSF-V5 5A 250V 1
GSD8/10 GSD-V8/10 8/10A 250V 1 GSF6-3/10 GSF-V6-3/10 6-3/10A 250V 1
GSD1 GSD-V1 1A 250V 1 GSF8 GSF-V8 8A 250V 1
GSD1-1/4 GSD-V1-1/4 1-1/4A 250V 1 GSF10 GSF-V10 10A 250V 1
GSD1-6/10 GSD-V1-6/10 1-6/10A 250V 1
GSD2 GSD-V2 2A 250V 1
GSD2-1/2 GSD-V2-1/2 2-1/2A 250V 1 1. 250VAC @ 1500A I.R.
GSD3-15/100 GSD-V3-15/100 3-15/100A 250V 1
GSD4 GSD-V4 4A 250V 1 * IEC Standards for 5x20mm fuses do not include ratings above
GSD5 GSD-V5 5A 250V 1 6.3 amperes.
GSD6-3/10 GSD-V6-3/10 6-3/10A 250V 1
GSD8 GSD-V8 8A 250V 1
GSD10 GSD-V10 10A 250V 1
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 17
C 17
ELECTRONIC/GLASS FUSES
1/2A through 10A, 250VAC, UL Listed 1/8A through 20A, 250VAC, 1/10A through 15A, 125VAC,
12A through 20A, 250V AC, UL Recognized UL Listed and CSA Certified UL Recognized and CSA Certified
25A through 30A, 125V AC, UL Recognized 25A through 30A, 250VAC
1. 250VAC @ 35A I.R./125VAC @ 10kA I.R. 1. 250VAC @ 35A I.R./125VAC @ 10kA I.R. 1. 125VAC @ 50A AC/300A DC I.R.
2. 250VAC @ 100A I.R./125VAC @ 10kA I.R. 2. 250VAC @ 100A I.R./125VAC @ 10kA I.R.
3. 125VAC @ 10kA I.R./250VAC @200A I.R. 3. 250VAC @ 200A I.R./125VAC @ 10kA I.R.
4. 125VAC @ 200A I.R. 4. 250VAC @ 750A I.R./125VAC @ 10kA I.R.
5. 125VAC @ 100A I.R. 5. 250VAC @ 1000A I.R./125VAC @ 10kA I.R.
6. 250VAC @ 400A I.R./125VAC @ 10kA I.R.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 18
ELECTRONIC/GLASS FUSES
1/10A & 3/8A, 250VAC, UL Listed CSA Certified 3/8A 250VAC, UL Listed and CSA Certified
1/8A through 7A, 350VAC, UL and CSA Recognized 1/4A through 7A, 350VAC, UL and CSA Recognized
8A & 10A, 125VAC
Standard Standard
Fuse Ampere Ratings Fuse Ampere Ratings
CATALOG AXIAL LEAD AMPERE VOLTS CATALOG AXIAL LEAD AMPERE VOLTS
I.R. NUMBER CAT. NO RATING I.R.
NUMBER CAT. NO RATING
SMG1/10 SMG-V1/10 1/10A 250V 1 STG1/4 STG-V1/4 1/4A 350V 2
SMG1/8 SMG-V1/8 1/8A 350V 2 STG3/8 STG-V3/8 3/8A 250V 1
SMG1/4 SMG-V1/4 1/4A 350V 2 STG1/2 STG-V1/2 1/2A 350V 2
SMG3/8 SMG-V3/8 3/8A 250V 1 STG6/10 STG-V6/10 6/10A 350V 2
SMG1/2 SMG-V1/2 1/2A 350V 2 STG3/4 STG-V3/4 3/4A 350V 2
SMG3/4 SMG-V3/4 3/4A 350V 2 STG8/10 STG-V8/10 8/10A 350V 2
SMG1 SMG-V1 1A 350V 2 STG1 STG-V1 1A 350V 2
SMG1-1/2 SMG-V1-1/2 1-1/2A 350V 2 STG1-1/4 STG-V1-1/4 1-1/4A 350V 2
SMG2 SMG-V2 2A 350V 2 STG1-1/2 STG-V1-1/2 1-1/2A 350V 2
SMG2-1/2 SMG-V2-1/2 2-1/2A 350V 2 STG2 STG-V2 2A 350V 2
SMG3 SMG-V3 3A 350V 2 STG2-1/2 STG-V2-1/2 2-1/2A 350V 2
SMG3-1/2 SMG-V3-1/2 3-1/2A 350V 2 STG3 STG-V3 3A 350V 2
SMG4 SMG-V4 4A 350V 2 STG3-1/2 STG-V3-1/2 3-1/2A 350V 2
SMG5 SMG-V5 5A 350V 2 STG4 STG-V4 4A 350V 2
SMG6 SMG-V6 6A 350V 2 STG5 STG-V5 5A 350V 2
SMG7 SMG-V7 7A 350V 2 STG6 STG-V6 6A 350V 2
SMG8 SMG-V8 8A 125V 3 STG7 STG-V7 7A 350V 2
SMG10 SMG-V10 10A 125V 3
1. 250VAC @ 35A I.R./125VAC @ 10kA I.R. 1. 250VAC @ 35A I.R./125VAC @ 10kA I.R.
2. 350VAC @ 100A I.R./140VDC @ 150A I.R. 2. 350VAC @ 100A I.R./125VAC @ 10kA I.R.
3. 125VAC @ 10kA I.R. 3. 1140V DC @ 150A I.R.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 19
radial lead miCro fuses
MRF MRT
Fast Acting Microfuse Time Delay Microfuse
Thermoplastic body and cap, UL 94-V0 Thermosplastic body and cap, UL 94-V0
Pins are Tin-lead plated copper alloy Pins are Tin-lead plated copper alloy
50mA to 6.3A, 250VAC - UL Recognized and CSA Accepted 80mA to 6.3A, 250VAC - UL Recognized and CSA Accepted
Standard Standard
Fuse Ampere Ratings Fuse Ampere Ratings
Catalog Ampere Catalog Ampere
Number Rating Volts I.R. Number Rating Volts I.R.
MRF50 50mA 250V 1 MRT80 80mA 250V 1
MRF63 63mA 250V 1 MRT100 100mA 250V 1
MRF80 80mA 250V 1 MRT125 125mA 250V 1
MRF100 100mA 250V 1 MRT160 160mA 250V 1
MRF125 125mA 250V 1 MRT200 200mA 250V 1
MRF160 160mA 250V 1 MRT250 250mA 250V 1
MRF200 200mA 250V 1 MRT315 315mA 250V 1
MRF250 250mA 250V 1 MRT400 400mA 250V 1
MRF315 315mA 250V 1 MRT500 500mA 250V 1
MRF400 400mA 250V 1 MRT630 630mA 250V 1
MRF500 500mA 250V 1 MRT800 800mA 250V 1
MRF630 630mA 250V 1 MRT1 1A 250V 1
MRF800 800mA 250V 1 MRT1.25 1.25A 250V 1
MRF1 1A 250V 1 MRT1.6 1.6A 250V 1
MRF1.25 1.25A 250V 1 MRT2 2A 250V 1
MRF1.6 1.6A 250V 1 MRT2.5 2.5A 250V 1
MRF2 2A 250V 1 MRT3.15 3.15A 250V 1
MRF2.5 2.5A 250V 1 MRT4 4A 250V 1
MRF3.15 3.15A 250V 1 MRT5 5A 250V 1
MRF4 4A 250V 1 MRT6.3 6.3A 250V 1
MRF5 5A 250V 1
MRF6.3 6.3A 250V 1 1. 250VAC @ 50A I.R.
SFRB
C
SFRT
Twist-Lock In-Line Fuseholders for FSFE fuses. Bayonet Knob In-Line Fuseholders for FSFE fuses.
Used at 32V or less with fuses rated up to 20A Used at 32V or less with fuses rated up to 20A
when proper spring for fuse size is installed. when proper spring for fuse size is installed.
Includes fuse listed
Standard
Standard Fuse Ampere Ratings
Fuse Ampere Ratings CATALOG FUSE
NUMBER INSTALLED
CATALOG FUSE
NUMBER INSTALLED SFRB4 FSFE4
SFRB6 FSFE6
SFRT4 FSFE4 SFRB7-1/2 FSFE7-1/2
SFRT6 FSFE6 SFRB9 FSFE9
SFRT7-1/2 FSFE7-1/2 SFRB14 FSFE14
SFRT9 FSFE9 SFRB20 FSFE20
SFRT14 FSFE14
SFRT20 FSFE20
SFRG FSFE
In-Line Fuseholder for 5 x 20mm fuses. Glass Body
Max. current rating for 5x20mm fuses - 10A @ 32V Fast Acting
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 21
Automotive fuses
AF AF2
Automotive Fuse Automotive Fuse
Fast Acting Fast Acting
1A through 40A, 32VAC/DC Plastic Body/Silver-Plated Terminals
1000kA I.R. 2A through 30A, 32VDC
1000kA I.R.
Standard
Standard Fuse Ampere Ratings
Fuse Ampere Ratings CATALOG AMPERE VOLTS BODY
NUMBER RATING COLOR
CATALOG AMPERE VOLTS BODY
NUMBER RATING COLOR AF2-2 2A 32V GREY
AF2-3 3A 32V VIOLET
AF-1 1A 32V BLACK AF2-4 4A 32V PINK
AF-2 2A 32V GREY AF2-5 5A 32V TAN
AF-3 3A 32V VIOLET AF2-7-1/2 7-1/2A 32V BROWN
AF-4 4A 32V PINK AF2-10 10A 32V RED
AF-5 5A 32V TAN AF2-15 15A 32V BLUE
AF-7-1/2 7-1/2A 32V BROWN AF2-20 20A 32V YELLOW
AF-10 10A 32V RED AF2-25 25A 32V NATURAL
AF-15 15A 32V BLUE AF2-30 30A 32V GREEN
AF-20 20A 32V YELLOW
AF-25 25A 32V NATURAL
AF-30 30A 32V GREEN
AF-35 35A 32V BLUE GREEN
AF-40 40A 32V AMBER
AF3
Automotive Fuse
Time Delay
Plastic Body/Silver-Plated Terminals
20A through 80A, 32VDC, 1000kA I.R.
Standard
Fuse Ampere Ratings
CATALOG AMPERE VOLTS BODY
NUMBER RATING COLOR
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 22
AFH, AF2H, AF3H AUTOMOTIVE FUSE HOLDERS
C
AFH20-16 AF Fuse/ 20A 32V Yellow #16/Black
AFH20-16Y AF Fuse/ 20A 32V Yellow #16/Black
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 23
AFH, AF2H, AF3H AUTOMOTIVE FUSE HOLDERS
Time in Seconds
Melting Time – Current Data Standard Fuse Ampere Ratings, Catalog Numbers
AMPERE CATALOG AMPERE CATALOG
RATING NUMBER RATING NUMBER
Slot Mount
1 PCF1-R 8 PCF8-R
2 PCF2-R 10 PCF10-R
3 PCF3-R 12 PCF12-R
4 PCF4-R 15 PCF15-R
5 PCF5-R 20 PCF20-R
6 PCF6-R 25 PCF25-R
7 PCF7-R 30 PCF30-R
Double Hole Mount
1 PCF1-H 8 PCF8-H
Time in Seconds
2 PCF2-H 10 PCF10-H
3 PCF3-H 12 PCF12-H
4 PCF4-H 15 PCF15-H
5 PCF5-H 20 PCF20-H
6 PCF6-H 25 PCF25-H
7 PCF7-H 30 PCF30-H
30/50 PCF30/50-H
Surface Mount
1 PCF1-S 8 PCF8-S
2 PCF2-S 10 PCF10-S
3 PCF3-S 12 PCF12-S
4 PCF4-S 15 PCF15-S
5 PCF5-S 20 PCF20-S
6 PCF6-S 25 PCF25-S
7 PCF7-S 30 PCF30-S
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 25
PCS SERIES PC MOUNT FUSES
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 26
PCS SERIES PC MOUNT FUSES
I t at 600VDC,100kA, L/R = 10 ms
2
I t at 600VAC, 100kA
2
Watts Loss Data
C
20 41 330
20 200 35 3.3 6.4
25 69 440
25 260 40 3.6 7.0
30 132 860
30 520
35 197 1300
35 780
40 276 1800
40 1100
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 27
PCT SERIES PC MOUNT FUSES
Time in Seconds
1 PCT1-H 8 PCT8-H
2 PCT2-H 10 PCT10-H
3 PCT3-H 12 PCT12-H
4 PCT4-H 15 PCT15-H
5 PCT5-H 20 PCT20-H
6 PCT6-H 25 PCT25-H
7 PCT7-H 30 PCT30-H
Surface Mount
1 PCT1-S 8 PCT8-S
2 PCT2-S 10 PCT10-S
3 PCT3-S 12 PCT12-S
4 PCT4-S 15 PCT15-S
5 PCT5-S 20 PCT20-S
6 PCT6-S 25 PCT25-S
7 PCT7-S 30 PCT30-S
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 28
PCF/PCS/PCT SERIES PC MOUNT FUSES
C
FOR .062 (1.6) NOMINAL
MOUNTING HOLE DETAIL CIRCUIT BOARD
THICKNESS
MAXIMUM RECOMMENDED
SCREW SIZE #6 (3.5mm)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
C 29
Semiconductor Fuses
Semiconductor technology is
widespread. Not by coincidence,
so’s our semiconductor fuse line.
• DIN 6,9gRB-URB;6,6gRB-URB
Want more information fast? For more technical or application-
specific information, please call our Semiconductor Fuse experts, • PSC / N. American Series /
A070URD / A130URD
at 978-462-6662; 416-252-9371 in Canada; or visit our website
at us.ferrazshawmut.com. • PSC / European Series /
6.6URD / 12.5 URD
• French Cylindrical
• British Standard
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AMP-TRAP®–Form 101
short circuit
➤ Controlled arc voltage reduces stress to circuit
components during fuse clearing
➤ Choice of mounting types provides options for unique
termination requirements
Ratings Approvals
➤ AC: 1-6000A ➤ UL Recognized
150VAC, 100kA I.R. Component
UL File E60314
➤ DC: 1-6000A
150VDC, 100kA I.R. ➤ AC: UL Guide No.
JFHR2 (1-4000A)
➤ DC Tested to UL
Standard 198L
parameters (1-4000A)
HIGHLIGHTS: APPLICATIONS:
Catalog Numbering System A 15 QS 400 - 4 TI
➤ Fast Acting ➤ Protection of heavy
Amp-trap Fuse A
duty devices such
®
➤ Current Limiting
➤ Low l t 2 as electrochemical
rectifiers Rated Volts - 250 15
➤ Indicator Options
Available QS
Style
Amperes * 400
Mounting Types*
Ferrule 1
Ferrule, midget dims. 2
(1-1/2” x 13/32”)
Single Pole Fuse Blocks for A15QS Fuses Blades, bolt-in
Hockey puck, bolt-in
4
128
FUSE FUSE BLOCK
Integral Blown-Fuse
AMPERE CATALOG Indicator
RATING NUMBER Trigger Indicator TI
Trigger Actuator IL
1-30 30311
31-60 U71006
61-100 P243D * For ampere ratings and types not listed, consult the factory.
101-200 P243D ** For harsh duty appllications, refer to the A13X product family. Consult
201-450 P243D the factory or OEM Central web site for A13X application information.
Http://www.ferrazshawmut.com/oem
500-600 P243G
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D
AMP-TRAP®–Form 101
D
25 A15QS25-2 1 175 A15QS175-4TI 2 1000 A15QS1000-4IL 3
30 A15QS30-2 1 200 A15QS200-4 2 1000 A15QS1000-4TI 2
35 A15QS35-1 1 200 A15QS200-4IL 3 1000 A15QS1000-128 4
40 A15QS40-1 1 250 A15QS250-4 2 1000 A15QS1000-128IL 5
40 A15QS40-4TI 2 250 A15QS250-4TI 2 1200 A15QS1200-128 4
45 A15QS45-1 1 300 A15QS300-4 2 1200 A15QS1200-128IL 5
50 A15QS50-1 1 300 A15QS300-4IL 2 1200 A15QS1500-128 4
50 A15QS50-4 2 300 A15QS300-4IL 3 1500 A15QS1500-128IL 5
60 A15QS60-1 1 350 A15QS350-4 2 2000 A15QS2000-128 4
*For ampere ratings, technical information, and styles not listed, call Technical Services.
1 - 60 AMP 175
Correction Factor for I2t
TYPE 1, 2
DC Voltage Capability
125
20 - 450 AMP
TYPE 4 75
D
15 3.0 350 40
20 4.0 400 45
25 5.2 450 50
30 5.6 500 30
35 9 550 33
40 10 600 35
45 12 700 50
50 13 750 66
60 14 800 57 71
20 1.5 900 67
25 2.0 1000 75 88 Percent Rated Current
30 2.2 1200 100
35 2.6 1500 130
40 3.1 1600 132
45 3.4 1800 149
50 4.0 2000 165
60 4.7 2500 195
70 5.6 3000 240
80 8.0 3500 260
90 9.0 4000 270
5000 330
6000 400
Max ARC Voltage vs System Voltage Peak Let Thru Data A15QS 1 to 4000
Max Instantaneous Let -Thru I
Max Peak Arc Voltage
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D
AMP-TRAP®–Form 101
Melt Time - Current Data A15QS 1 to 30 Melt Time - Current Data A15QS 20 to 100
Time in Seconds
Time in Seconds
Melt Time - Current Data A15QS 125 to 1000 Melt Time - Current Data A15QS 750 to 4000
Time in Seconds
Time in Seconds
Features/Benefits
D
➤ Low I2t minimizes damage to protected component on
short circuit
➤ Controlled arc voltage reduces stress to circuit
components during fuse clearing
➤ Choice of mounting types helps in equipment design
Ratings Approvals
➤ AC: 1- 4500A ➤ UL Recognized
300VAC, 200kA I.R. Component
UL File E60314
➤ DC: 300VDC, 100kA I.R.
L/R= 10ms ➤ AC: UL Guide No.
HIGHLIGHTS: APPLICATIONS: JFHR2 (35-4500A)
➤ Fast Acting ➤ Protection of 300 volt ➤ CSA
➤ Current Limiting (or less) heavy duty
➤ Low I2t rectifiers and similar
heavy duty power
➤ Indicator Options supplies Catalog Numbering System
A 30 QS 600 - 4 TI
Availible
➤ Superior DC Amp-trap Fuse
®
A
Capabilities
Rated Volts - 300 30
Style QS
C US
Amperes * 600
Single Pole Fuse Blocks for A30QS Fuses Mounting Types*
Ferrule 1
FUSE FUSE BLOCK Blades, bolt-in
AMPERE CATALOG 4
Hockey puck, bolt-in 128
RATING NUMBER
1-30 70316 Integral Blown-Fuse
31-60 P243G Indicator
61-100 P243 Trigger Indicator TI
Trigger Actuator IL
101-200 P243
201-400 P243G
* For ampere ratings and types not listed, call Technical Services.
401-600 P243G
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D
AMP-TRAP®–Form 101
Dimensions
OUTLINE MOUNTING FIG. DIMENSIONS - INCHES (mm) TAP
REF. TYPE A B C D E F G H
A30QS1 to 30 1 1 2.00 0.56 - - - - - - -
(51) (14) - - - - - - -
A30QS35 to 60 4 2 3.19 .081 1.63 2.50 2.25 0.34 .72 0.13 -
(81) (21) (41) (64) (58) (9) (18) (3) -
A30QS70 to 200 4 3 3.13 1.22 1.63 2.44 2.19 0.31 1.22 0.19 -
(80) (31) (41) (62) (55) (8) (31) (5) -
A30QS225 to 700 4, 4IL* 3,4* 3.84 1.50 1.59 3.10 2.28 0.41 1.00 0.25 -
(98) (38) (40) (74) (58) (10) (25) (6) -
A30QS700 to 1200 128 5 2.59 3.00 2.34 2.50 1.50 - - - 3/8-24-1/2 Deep (2)
(66) (76) (59) (64) (38) - - - -
A30QS1500 to 2500 128, 128IL* 6, 7* 2.59 3.50 2.34 3.00 1.50 1.50 - - 3/8-24-1/2 Deep (4)
(66) (89) (59) (76) (38) (38) - - -
A30QS3000 to 4500 128, 128IL* 6, 7* 2.59 4.50 2.34 3.75 1.50 1.50 - - 1/2-20-1/2 Deep (4)
(66) (114) (59) (95) (38) (38) - - -
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D
AMP-TRAP®–Form 101
1 - 5 AMP
Correction Factor For I2t
TYPE 1
6 - 30 AMP
TYPE 1
Working Voltage (AC RMS Volts) Working Voltage (AC RMS Volts)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D
AMP-TRAP®–Form 101
Watts Loss at Rated Current Clearing I2t at 300VDC, 100kA, L/R = 10ms
Watts loss vs. Percent Rated Current DC Voltage Capability vs. Circuit Time Constant (ms)
Correction Factor for Watts Loss
DC Voltage
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 10
AMP-TRAP®–Form 101
Melting Time - Current Data A30QS 1 to 60 Melting Time - Current Data A30QS 70 to 800
Time in Seconds
Time in Seconds
Melting Time - Current Data A30QS 700 to 4500 Peak Let Thru Data
Maximum Instantanius Peak Let Thru
Time in Seconds
Current in Amperes
Available Current in RMS Symmetrical Amps
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 11
AMP-TRAP®–Form 101
Ratings Approvals
➤ AC: 35-60A ➤ UL Recognized
500VAC, 200kA Component
I.R. 70-1200A UL File 60314
500VAC, 200kA I.R.
➤ AC: UL Guide No. JFHR2
➤ DC: 35-1200A
➤ DC Tested to UL
500VDC, 100kA I.R.
Standard 198L
parameters (70-1200A)
➤ CSA Certified
LR12636
Features/Benefits
➤ Lowest l2t for greatest protection of semicon-
ductor circuits
➤ Low watts loss for cooler operation
➤ Superior cycling ability gives an equipment design
HIGHLIGHTS: APPLICATIONS: advantage
➤ 500V AC/DC Rated ➤ State-of-the-art protection for 500 volt equipment
➤ Protection of 500V or
➤ Ultra compact sizes allow down-sizing of existing
➤ Lowest l2t less motor drives, equipment
➤ Low Watts Loss ➤ UPS, inverters, etc.
➤ Superior Cycling
Ability
Catalog Numbering System A 50 QS 250 - 4
Amp-trap Fuse
®
A
Single Pole Fuse Blocks for A50QS Fuses Rated Volts - 500 50
Style QS
FUSE FUSE BLOCK
AMPERE MOUNTING CATALOG
RATING TYPE NUMBER Amperes * 250
1 - 30 Mounting Type*
35-200 4 P243E Blades, bolt-in 4
225-600 4 P266C
700-800 4 1SC375
* For ampere ratings and types not listed, consult the factory.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 12
AMP-TRAP®–Form 101
A50QS35 to 100 4 3.63 1.00 2.13 2.94 2.75 0.31 0.75 0.13
(92.2) (25.4) (54.1) (74.7) (69.9) (7.9) (19.1) (3.3)
A50QS125 to 200 4 3.63 1.22 2.13 2.94 2.81 0.31 1.00 0.19
(92.2) (31.0) (54.1) (74.7) (71.4) (7.9) (25.4) (4.8)
A50QS225 to 400 4 4.34 1.50 2.09 3.41 2.78 0.41 1.00 0.25
(110) (38.1) (53.1) (86.6) (70.6) (10.4) (25.4) (6.4)
A50QS450 to 600 4 4.47 2.00 2.22 3.53 2.91 0.41 1.50 0.25
(114) (50.8) (56.4) (89.7) (73.9) (10.4) (38.1) (6.4)
A50QS700 to 800 4 6.47 2.38 2.22 5.00 3.44 .53 2.00 .38
(164.3) (60.3) (56.4) (127.0) (87.3) (13.5) (50.8) (9.8)
A50QS900 to 1200 4 6.97 2.88 3.22 5.47 4.47 .63 2.38 .44
(177.0) (76.2) (81.8) (138.9) (113.5) (15.9) (60.3) (11.1)
40 7 300 49
50 8 350 57
60 10 400 65
70 12 450 69
80 14 500 77
90 15 600 92
100 17 700 110
125 21 800 130
150 25 900 140
175 29 1000 160
200 33 1200 175
225 37
Time in Seconds
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 14
AMP-TRAP®–Form 101
I2t DATA
FUSE MAX. CLEARING I2t @ 500VAC 500 VAC Fault Load 500 VAC Fault Load
AMPERE MELTING I t 1 FUSE (Fig A) 2 FUSES IN SERIES
2
D
125 .94 5.6 3.4
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 15
AMP-TRAP®–Form 101
Features/Benefits
➤ Low l t minimizes damage to protected components on
2
short circuit
➤ Controlled arc voltage reduces stress to circuit
components during fuse clearing
➤ Choice of mounting types helps in equipment design
Ratings Approvals
➤ AC: 10-1200A ➤ UL Recognized
500VAC, 100kA I.R. Component
➤ DC: 35-1000A UL File 60314
450VDC, 79kA I.R.
L/R = 10ms ➤ AC: UL Guide No.
JFHR2 (10-800A)
➤ DC: UL Guide No.
JFHR2 (35-800A)
HIGHLIGHTS: APPLICATIONS:
* Contact technical services for applications data.
➤ Very Fast Acting ➤ Protection of DC
drives, UPS and other
Catalog Numbering System
➤ Current Limiting A 50 P 100 - 4 TI
➤ Low l t 2 equipment of 500
volts or less Amp-trap Fuse
®
A
➤ Indicator Options
Available
Rated Volts - 500 50
Style P
Amperes *
Single Pole Fuse Blocks for A50P Fuses 100
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 16
AMP-TRAP®–Form 101
D
100 A50P100-4 3 300 A50P300-4TI 3 800 A50P800-4TI 5
100 A50P100-4TI 3 325 A50P325-4 3 900 A50P900-4 3
125 A50P125-4 3 350 A50P350-4 3 1000 A50P1000-4 3
125 A50P125-4TA 4 350 A50P350-4TI 3 1000 A50P1000-4TI 3
125 A50P125-4TI 3 400 A50P400-4 3 1200 A50P1200-4 3
150 A50P150-4 3 400 A50P400-4TA 4 1200 A50P1200-4TI 3
150 A50P150-4TI 3 400 A50P400-4TI 3
For ampere ratings and styles not listed, call Technical Services.
Figure 1
Figure 4
Figure 3
Figure 2
Features/Benefits
➤ Lowest l t of any fuse this size for greater protection
2
Ratings Approvals
➤ AC: 5-40A ➤ UL Recognized
600VAC, 200kA I.R. Component
➤ DC: 5-40A ➤ AC: UL Guide JFHR2
600VDC, 100kA I.R.
L/R = 10ms File E60314
➤ DC: UL File E60314
HIGHLIGHTS: APPLICATIONS:
Catalog Numbering System A 60 Q 30 - 2
➤ 600VAC/DC Rated ➤ Protection of small
Amp-trap Fuse A
➤ Extremely Fast Acting inverters and drives,
®
degree of protection Q
➤ Excellent Cycling Style
Ability
Amperes 30
Mounting Type
Ferrule, midget dims. 2
(1-1/2” x 13/32”)
Standard Fuse Ampere Ratings, Catalog Numbers
AMPERE CATALOG AMPERE CATALOG
RATING NUMBER RATING NUMBER fuse holders for a60Q fuses
5 A60Q5-2 20 A60Q20-2 USM Series . . . . UltrasafeTM Fuse Holders
6 A60Q6-2 25 A60Q25-2 303 Series . . . . . Midget Fuse Blocks
8 A60Q8-2 30 A60Q30-2
10 A60Q10-2 35 A60Q35-2
12 A60Q12-2 40 A60Q40-2 1-1/2”
15 A60Q15-2 (38.1 mm) 13/32”
(10.3 mm)
For ampere ratings and styles not listed, call Technical Services.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 18
AMP-TRAP®–Form 101
A60Q5 to 40
D
Melting Time – Current Data, 600V Fuses
I t at 600VDC,100kA, L/R = 10 ms
2
5 40
8 42
10 70
12 90
15 110
20 200
25 260
30 520
35 780
40 1100
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 19
AMP-TRAP®–Form 101
Features/Benefits
➤ Low l t minimizes damage to protected components on
2
short circuit
➤ Controlled arc voltage reduces stress to circuit
components during fuse clearing
➤ Choice of mounting types helps in equipment design
Ratings Approvals
➤ AC: 1-2000A ➤ UL Recognized
600V, 100kA I.R. Component
UL File E60314
➤ AC: UL Guide No.
JFHR2 (35-800A)
HIGHLIGHTS: APPLICATIONS:
➤ Fast Acting ➤ Protection of heavy
➤ Current Limiting traction and electro-
chemical as well as Catalog Numbering System
➤ Low l t 2
A 60 X 600 - 4 TI
rectifiers and other
➤ Indicator Options heavy-duty equipment Amp-trap Fuse
®
A
Available
Rated Volts - 600 60
Style X
Amperes * 600
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 20
AMP-TRAP®–Form 101
D
30 A60X30-1 1 225 A60X225-4 3 800 A60X800-4 5
35 A60X35-4 2 250 A60X250-4 3 800 A60X800-4TA 6
40 A60X40-4 2 250 A60X250-4TA 4 800 A60X800-128 7
45 A60X45-4 2 250 A60X250-4TI 3 1000 A60X1000-128 8
50 A60X50-4 2 300 A60X300-4 3 1200 A60X1200-128 8
55 A60X55-4 2 300 A60X300-4TA 4 1500 A60X1500-128 8
60 A60X60-4 2 300 A60X300-4TI 3 1600 A60X1600-128 8
70 A60X70-4 3 350 A60X350-4 3 1800 A60X1800-128 8
80 A60X80-4 3 350 A60X350-4TA 4 2000 A60X2000-128 8
For ampere ratings and styles not listed, call Technical Services.
Figure 1 Figure 4
Figure 2 Figure 3
Figure 5
Figure 6 Figure 7 Figure 8
Dimensions
OUTLINE MOUNTING FIG. DIMENSIONS - INCHES (mm) TAP
REF. TYPE A B C D E F G H
Current in Amperes
D
*Type 4 **Type 128
I t DATA
2
FUSE CLEARING AT 600V Watts Loss vs. % Rated Current (Types 1 & 4)
AMPERE MELTING 1 FUSE 2 FUSES IN
RATING (FIG. A) SERIES (FIG. B)
(A2s) (A2s) (A2s)
Correction Factor for Watts Loss
Features/Benefits
➤ International 10 X 38 mm (1 1/2 X 13/32) size for
worldwide acceptance
➤ Ferrule mount 1 to 30A for design versatility
➤ Low I2t for improved semiconductor protection
➤ gR Class according to VDE 636-23 and IEC 269.4
Ratings Approvals
➤ AC: 1-30A ➤ UL Recognized
160kA, 700V Component
UL File E76491
➤ DC: 550VDC, L/R =
10mS ➤ IEC 269-4 Compliance
➤ AC: UL Guide No. JFHR2
HIGHLIGHTS: APPLICATIONS:
➤ Extremely Fast Acting ➤ Protection of small
➤ Current Limiting inverters, UPS
➤ Low l t 2 systems, motor drives
and similar 700v or
➤ Excellent Cycling less equipment
Capability
➤ gR
38 (1.50)
10
fuse holders for a070gRB fuses
USM Series . . . . UltrasafeTM Fuse Holders
303 Series . . . . . Midget Fuse Blocks
x10, 3 (.406)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 24
PROTISTOR
WATTS LOSS
RATED Clearing I2t @
BODY SIZE AMPERE Melting I2t
VOLTAGE Rated Voltage @ 80% RATED @ 100% RATED CATALOG NUMBER REFERENCE NUMBER
(mm) RATING (A2s)
(VAC) (A2s) CURRENT CURRENT
D
5 8.6 27.5 1.4 2.7 A070GRB05T13 D330007
10 X 38 700
6 15 48.5 1.5 2.9 A070GRB06T13 E330008
8 3.3 36.3 1.35 2.4 A070GRB08T13 F330009
10 5.4 60.5 1.85 3.4 A070GRB10T13 G330010
12.5 8.5 90.2 1.9 3.4 A070GRB12.5T13 H330011
16 16 160 2.3 4.1 A070GRB16T13 J330012
20 30 275 2.4 4.3 A070GRB20T13 K330013
25 58 520 2.7 4.7 A070GRB25T13 L330014
30 96 815 2.9 5 A070GRB30T13 M330015
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 25
Protistor
Melting Time Current Data (1 to 6A) Peak Let Thru Current Data (1 to 6A)
Current in Amperes
Melting Time Current Data (8 to 30A) Peak Let Thru Current Data (8 to 30A)
Max Instantanious Peak Let Thru
Time in Seconds
Features/Benefits
➤ International 14x51mm (2”x9/16”) and 22x58mm
(2-1/4”x13/16”) sizes for worldwide acceptance
➤ Ferrule mount up to 100A for design versatility
➤ Very low I2t for improved semiconductor protection
➤ 690V IEC rated, tested at 760VAC; can be used up to
750VAC in U.S.
➤ 700VDC rated for dc protection of equipment with
L/R ≤10ms
➤ Superior cycling ability for longer life on difficult cyclic
loading applications
➤ aR characteristic for semiconductor short-
circuit protection
Amp-trap Fuse
®
Family
Style/Design
Mounting:
Amperes
•US14 or US22 “finger-safe” IP 20 grade holders,
Size-14F=14x51mm
DIN rail or screw mount, with striker actuated microswitch 22F=22x58mm
indication available. Optional Striker-I
•703 Series open fuse blocks
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 28
AMP-TRAP®
D
40 0.13 0.70 10.7 A70QS40-14F A70QS40-14FI
50 0.28 1.50 11.6 A70QS50-14F A70QS50-14FI
10 0.0043 0.025 4.0 A70QS10-22F A70QS10-22FI
15 0.008 0.049 6.2 A70QS15-22F A70QS15-22FI
20 0.013 0.076 8.0 A70QS20-22F A70QS20-22FI
25 0.02 0.125 10.0 A70QS25-22F A70QS25-22FI
32 0.49 0.27 11.0 A70QS32-22F A70QS32-22FI
40 0.88 0.48 13.0 A70QS40-22F A70QS40-22FI
22 x 58 50 0.16 0.80 14.9 A70QS50-22F A70QS50-22FI
63 0.35 1.85 16.0 A70QS63-22F A70QS63-22FI
70 0.52 2.80 16.5 A70QS70-22F A70QS70-22FI
80 0.73 3.80 17.8 A70QS80-22F A70QS80-22FI
90 1.10 5.64 17.0 A70QS90-22F A70QS90-22FI
100 1.56 8.00 19.0 A70QS100-22F A70QS100-22FI
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 29
AMP-TRAP®
These curves indicate, for each rated current, the pre-arcing (melting) time vs. the R.M.S. current.
Clearing I2t vs. Operating Voltage Peak arc voltage vs. Operating Voltage
Operating Voltage
Operating Voltage
K
Correction factor for I2t
1,2 2000
1
1600
0,8
1200
0,6
800
0,4
0,2 400
0 100 200 300 400 500 600 700 0 100 200 300 400 500 600 700
U(V)
DC Voltage Capabilities vs. Time Constant Peak Arc voltage vs. DC circuit voltage
L (ms)
R
80 Um(V)
1000
900
60
50 800
40
30
700 D
600
20
500
10
DC Voltage Capabilities vs. Time Constant Peak Arc voltage vs. DC circuit voltage
L (ms)
R
80 Um(V)
1100
70
Peak Arc Voltage
Time Constant L/R
1000
60
900
50
40 800
30 700
20 600
10
100 200 300 400 500 600 700
U(V)
0 100 200 300 400 500 600
U(V)
DC Voltage Capability DC Circuit Voltage
These curves provide the DC voltage capability of These curves show the peak value Um of the arc voltage
the fuse as a function of circuit time constant. which appears across the fuse link as a function of the
(L/R ratio) operating voltage U.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 31
AMP-TRAP®–Form 101
Features/Benefits
➤ Very Low l t for improved protection of equipment
2
Ratings Approvals
➤ AC: 35-800A ➤ UL Recognized
700VAC, 200kA I.R. Component, AC/DC UL
File E60314
➤ DC: 35-800A
700VDC, 100kA I.R. ➤ AC: Guide No. JFHR2
HIGHLIGHTS: APPLICATIONS: L/R = 10ms
➤ DC: Tested to UL
➤ 700V AC/DC Rated ➤ Protection of 700V Standard 198L
➤ Very Low l t 2
or less motor drives, Parameters (35-800A)
➤ Low Watts Loss UPS, inverters, etc. ➤ CSA Certified
➤ Superior Cycling File LR 12636
Ability
Catalog Numbering System
A 70 QS 150 - 4
A
Amp-trap Fuse
®
Style QS
Single Pole Fuse Blocks for A70QS Fuses
Amperes * 150
Fuse Fuse Fuse Block
Mounting Ampere Catalog Mounting Types*
Type Rating Number Blades, bolt-in 4,4K
A70QS-4 35-200 P243C
A70QS-4K 125-200 P266A
A70QS-4 225-600 P266A * For ampere ratings and types not listed, consult the factory.
A70QS-4K 450-600 FH70F3
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 32
AMP-TRAP®–Form 101
Dimensions
CATALOG MOUNTING DIMENSIONS - INCHES (mm)
D
NUMBER TYPE A B C D E F G H
A70QS35 to 100 4 4.38 1.00 2.88 3.69 3.50 0.31 0.75 0.13
(111) (25.4) (73.0) (93.6) (88.9) (7.9) (19.0) (3.2)
A70QS125 to 200 4 4.38 1.22 2.88 3.69 3.56 0.31 1.00 0.19
(111) (31.0) (73.0) (93.6) (90.5) (7.9) (25.4) (4.8)
A70QS125 to 200 4K 5.09 1.22 2.88 4.19 3.50 0.41 1.00 0.19
(129) (31.0) (73.0) (106) (88.0) (10.3) (25.4) (4.8)
A70QS225 to 400 4 5.09 1.50 2.84 4.16 3.53 0.40 1.50 0.25
(129) (38.1) (72.2) (106) (89.7) (10.3) (38.1) (6.4)
A70QS450 to 600 4 5.09 2.00 2.84 4.16 3.53 0.41 1.50 0.25
(129) (50.8) (72.2) (106) (89.7) (10.3) (38.1) (6.4)
A70QS450 to 600 4K 7.09 2.00 2.84 6.16 3.53 0.53 1.50 0.25
(180) (50.8) (72.2) (156) (89.7) (13.5) (38.1) (6.4)
A70QS700 to 800 4 7.09 2.50 2.84 5.28 4.91 0.53 2.00 0.38
(180) (63.5) (72.2) (134) (125) (13.5) (50.8) (9.5)
I2t DATA
FUSE CLEARING AT 700V AC 700 VAC Fault Load 700 VAC Fault Load
AMPERE MELTING 1 FUSE 2 FUSES IN
RATING (FIG. A) SERIES (FIG. B)
Fig. A Fig. B
(A2s x 103) (A2s x 103) (A2s x 103)
35 0.13 0.47 0.27
40 0.16 0.58 0.33
50 0.24 0.86 0.49 Clearing I t vs. AC Operating Voltage
2
Current in Amperes
100kA, L/R = 10 ms
35 0.25
40 0.35
50 0.60
70 1.3
80 1.8
90 2.4
100
125
150
3.1
5.3
8.1
D
175 12
200 16
225 21.5
Circuit Voltage (Volts RMS)
250 27.5
300 42 Watts Loss at Rated Current
350 63
400 85 AMPERE WATTS AMPERE WATTS
450 115 RATING LOSS (w) RATING LOSS (w)
500 150 35 6.2 200 41
600 201 40 7.5 225 37
700 325 50 9.8 250 42
800 450 60 12 300 53
70 15 350 64
80 18 400 75
90 20 450 78
100 24 500 92
125 22 600 116
150 29 700 125
175 35 800 143
DC Voltage Capability vs. Time Constant Watts Loss vs. % Rated Current
Correction Factor for Watts Loss
DC Voltage Capability
short circuit
➤ Controlled arc voltage reduces stress to circuit
components during fuse clearing
➤ Choice of mounting types helps in equipment design
Ratings Approvals
➤ AC: 10-1000A ➤ UL Recognized
700VAC, 100kA I.R. Component
UL File E60314
➤ DC: 10-800A
650VDC, 100kA I.R. ➤ AC: Guide No. JFHR2
L/R=10ms (10-1000A)
➤ DC: Tested to UL
Standard 198L param-
eters (10-800A)
HIGHLIGHTS: APPLICATIONS:
➤ Very Fast Acting ➤ Protection of 700V or *Contact technical services for application data.
A
Available
Rated Volts - 700 70
Style P
(Faster acting, lower l t than X)
2
Amperes * 300
Single Pole Fuse Blocks for A70P Fuses Mounting Types*
Ferrule 1
FUSE FUSE BLOCK
Blades, bolt-in 4
AMPERE CATALOG 128
Hockey puck, bolt-in
RATING NUMBER
10-30 (Type 1) 70316
31-60 P243C Integral Blown-Fuse Indicator
TI
61-100 P243C Trigger Indicator
TA
Trigger Actuator
101-200 P266A
201-400 P266A
401-600 P266F * For ampere ratings and types not listed, consult the factory.
601-800 1SC375
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 36
AMP-TRAP®–Form 101
D
40 A70P40-4TI 3 200 A70P200-4 3 800 A70P800-4 5
50 A70P50-4 3 200 A70P200-4TA 4 800 A70P800-4TI 5
60 A70P60-4 3 200 A70P200-4TI 3 900 A70P900-4 6
60 A70P60-4TA 4 225 A70P225-4 3 1000 A70P1000-4 6
60 A70P60-4TI 3 250 A70P250-4 3 1200 A7OP1200-4 7
70 A70P70-4 3 250 A70P250-4TA 4
70 A70P70-4TI 3 250 A70P250-4TI 3
For ampere ratings and styles not listed, call Technical Services.
Figure 1
Figure 2 Figure 3
Figure 4
Dimensions Figure 5 Figure 6
A70P125 to 200 4, 4TA*, 4TI 3, 4* 5.09 1.50 2.84 4.16 3.53 .41 1.00 .25 -
(129) (38.1) (72.1) (106) (89.7) (10.4) (25.4) (6.4) -
A70P225 to 400 4, 4TA*, 4TI 3, 4* 5.09 2.00 2.84 4.16 3.53 .41 1.50 .24 -
(129) (50.8) (72.1) (106) (89.7) (10.4) (38.1) (6.4) -
A70P450 to 600 4, 4TA*, 4TI 3, 4* 7.09 2.50 2.84 5.25 4.94 .53 2.00 .38 -
(180) (63.5) (72.1) (133) (125) (13.5) (50.8) (9.7) -
A70P700 to 800 4, 4TI 5 6.81 2.88 3.31 5.31 - .63 2.00 .38 .31
(173) (73.2) (84.1) (135) - (16.0) (50.8) (9.7) (7.9)
A70P900 to 1000 4, 4TI 6 7.59 3.50 3.84 5.97 5.22 .63 2.75 .50 1.38
(193) (88.9) (97.5) (152) (133) (16.0) (69.9) (12.7) (35.1)
A70P1200 4 7 10.84 4.5 3.84 6.84 5.84 9.34 9.59 3.5 .63 .75
(275.4) (114.3) (97.6) (173.7) (148.3) (237.3) (243.6) (88.9) (15.9) (19.1)
* Optional
Courtesy of Steven Trigger Actuator
Engineering, Inc.-230(TA)
Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 37
AMP-TRAP®–Form 101
Features/Benefits
➤ Lowest l t of any fuse in this voltage rating for best
2
overall protection
➤ 700V AC, 650V DC rating allows protection of greater
variety of circuits
➤ Solid fill technology for extra reliability in performance
Ratings Approvals
➤ AC: 35-600A ➤ UL Recognized
700VAC, 100kA I.R. Component
➤ DC: 35-600A UL File E60314
650VDC, 100kA I.R.
L/R=10ms ➤ AC: Guide No. JFHR2
➤ DC: Tested to UL
Standard 198L
Parameters (35-600A)
HIGHLIGHTS: APPLICATIONS:
➤ Extremely Fast Acting ➤ Protection of inverters
➤ Current Limiting and other equipment
➤ Lowest l t 2 requiring the best AC
or DC protection in
this voltage range *Contact technical services for application data.
Catalog Numbering System A 70 Q 500 - 4
Amp-trap Fuse
®
A
Amperes * 500
FUSE FUSE BLOCK
AMPERE CATALOG Mounting Types*
RATING NUMBER Blades, bolt-in 4
35-100 P243C
125-400 P266A
450-600 P266F
* For ampere ratings and types not listed, consult the factory.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 38
AMP-TRAP®–Form 101
D
80 A70Q80-4 250 A70Q250-4 Figure 1
90 A70Q90-4 300 A70Q300-4
For ampere ratings and styles not listed, call Technical Services.
Dimensions
CATALOG MOUNTING DIMENSIONS - INCHES (mm)
NUMBER TYPE A B C D E F G H
A70Q35 to 60 4 4.37 1.22 1.96 3.69 2.91 .34 1.00 .19
(111) (31.0) (49.8) (93.7) (73.9) (8.6) (25.4) (4.8)
A70Q70 to 100 4 4.37 1.22 1.96 3.69 2.91 .41 1.00 .19
(111) (31.0) (49.8) (93.7) (73.9) (10.4) (25.4) (4.8)
A70Q125 to 200 4 5.09 1.50 1.96 4.16 2.91 .41 1.00 .25
(129) (38.1) (49.8) (106) (73.9) (10.4) (25.4) (6.4)
A70Q250 to 400 4 5.09 2.00 1.96 4.00 2.94 .56 1.50 .25
(129) (50.8) (49.8) (102) (74.7) (14.2) (38.1) (6.4)
A70Q450 to 600 4 7.09 2.50 1.96 5.72 3.25 .56 2.00 .38
(180) (63.5) (49.8) (145) (82.6) (14.2) (50.8) (9.7)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 39
AMP-TRAP®–Form 101
Features/Benefits
➤ Low l t minimizes damage to protected components on
2
short circuit
➤ Controlled arc voltage reduces stress to circuit
components during fuse clearing
➤ Wide range of ampere ratings
Ratings Approvals
➤ AC: 15-30A1000VAC, ➤ UL Recognized
100kA I.R. Component
35-1000A
➤ AC: UL Guide No.
1000VAC, 100kA I.R.
JFHR2 (60-800A)
➤ DC: 15-1000A
➤ DC: Ferraz Shawmut
750VDC, 100kA I.R.
HIGHLIGHTS: APPLICATIONS: Certified
Style P
Amperes * 80
Mounting Types* 1
Ferrule 4
Single Pole Fuse Blocks for A100P Fuses Blades, bolt-in
Integral Blown-Fuse
FUSE FUSE BLOCK Indicator TI
AMPERE CATALOG Trigger Indicator
RATING NUMBER
35-100 P266G
125-400 P266L
* For ampere ratings and types not listed, consult the factory.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 40
AMP-TRAP®–Form 101
D
80 A100P80-4 2 300 A100P300-4TI 2 1000 A100P1000-4 5
80 A100P80-4TI 2 350 A100P350-4 2
For ampere ratings and styles not listed, call Technical Services.
Figure 1
Figure 2 Figure 3
Figure 4 Figure 5
Dimensions
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 41
AMP-TRAP®–Form 101
Current in Amperes
Time in Seconds
Fig. A
I2t DATA
FUSE CLEARING
AMPERE MELTING @ 1000VAC
RATING FIG. A Clearing I t vs. AC Operating Voltage
2
D
25 .047 1.3
30 .057 1.5
35 .29 2.2
15 3.4 225 40
20 5.9 250 45
25 9 300 55
30 12.8 350 65
35 7.3 400 70
40 8.3 500 90
50 11 600 110
60 13 650 120
70 13 700 125
80 14 800 140
100 18 1000 190
125 23
150 28
200 36
Percent Rated Current
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 43
AMP-TRAP®–Form 101
Features/Benefits
➤ 1000 Volt DC rated for wide range of circuits
➤ Compact size fits in where competitive sizes will not fit
Ratings Approvals
➤ AC: 1/2-30A ➤ Ferraz Shawmut
1200VAC, 100kA I.R. Certified
➤ DC: 1/2-30A
1000VDC, 100kA I.R.
L/R = 10ms
Catalog Numbering System A 120 X 25 - 1
* For ampere ratings and types not listed, call Technical Services.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 44
AMP-TRAP®–Form 101
Current in Amperes
D
Time in Seconds
FUSE I t DATA
2
Features/Benefits
➤ 1500 Volt AC rated for wide range of applications
➤ Heavy Duty Links
➤ Rugged Fiberglass Body
Ratings Approvals
➤ AC: 1A to 1000A ➤ Ferraz Shawmut
1500VAC, 100kA I.R. Certified
➤ DC: 1A to 1000
1000VDC, 100kA I.R.
L/R = 100ms
Figure 1
HIGHLIGHTS: APPLICATIONS:
➤ Fast Acting ➤ Protection of traction
➤ Current Limiting drive and auxiliary
➤ Low l t 2 circuits, etc.
Figure 2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 46
AMP-TRAP®–Form 101
Melting Time – Current Data, 1500V Fuses Peak Let-Thru Data – A150X15 to 1000, 1500 VAC
Current in Amperes
I2t DATA - 1500 VAC, 100kA
90 50 100
100 61 128
125 100 215
150 138 290
175 188 395
200 245 515
250 383 804
300 551 1157
400 980 2057
450 1240 2603
500 1530 3213
600 2204 4629
800 3918 8829
1000 6122 12860
Features/Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors as per IEC
standard 269.4
➤ 690V Voltage Rating as per IEC 33
➤ gR Class [Current rating 12 to 90A] as per
VDE 636-23
-Full range protection
-Improved safety and protection
-Allows selective coordination
➤ aR Class [Current Rating 100A] According to VDE
636-23 and IEC 269.4
➤ Connections as per:
-German standard DIN 43653/00C
-British standard BS 88-4
➤ These fuses are UL Recognized
C US
APPLICATIONS DATA
Voltage Current MELTING Total clearing Watt losses
rating Class rating I2t @ 1 ms I2t @ Tested Estimated
0.8 IN IN interrupting rating
UN( V ) IN( A ) (A2s)
RATED VOLTAGE interrupting rating
(A2s)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 48
DIN/BS88 FUSES
D
German Standard with separate blown fuse Current Rating Catalog No. REF #
trip-indicator DIN 43623/00C
12 6,9 gRB 17 DO8P 12 X221004
16 6,9 gRB 17 DO8P 16 Y221005
20 6,9 gRB 17 DO8P 20 Z221006
25 6,9 gRB 17 DO8P 25 A221007
32 6,9 gRB 17 DO8P 32 B221008
35 6,9 gRB 17 DO8 P 35 C221009
40 6,9 gRB 17 DO8P 40 D221010
45 6,9 gRB 17 DO8P 45 E221011
50 6,9 gRB 17 DO8P 50 F221012
55 6,9 gRB 17 DO8P 55 G221013
63 6,9 gRB 17 DO8P 63 H221014
75 6,9 gRB 17 DO8P 75 J221015
80 6,9 gRB 17 DO8P 80 K221016
90 6,9 gRB 17 DO8P 90 L221017
Weight: 40 g
100 6,9 URB 17 DO8P 100 M221018
Packaging: 10 pieces
British Standard without blown fuse indication Current Rating Catalog No. REF #
12 6,9 gRB 17/12 W220957
16 6,9 gRB 17/16 X220958
20 6,9 gRB 17/20 Y220959
25 6,9 gRB 17/25 Z220960
32 6,9 gRB 17/32 A220961
35 6,9 gRB 17/35 B220962
40 6,9 gRB 17/40 C220963
45 6,9 gRB 17/45 D220964
50 6,9 gRB 17/50 E220965
55 6,9 gRB 17/55 F220966
63 6,9 gRB 17/63 G220967
75 6,9 gRB 17/75 H220968
80 6,9 gRB 17/80 J220969
Weight: 37 g 90 6,9 gRB 17/90 K220970
Packaging: 10 pieces 100 6,9 URB 17/100 L220971
British Standard with separate blown fuse Current Rating Catalog No. REF #
trip-indicator BS 88-4
12 6,9 gRB 17P12 D220987
16 6,9 gRB 17P16 E220988
20 6,9 gRB 17P20 F220989
25 6,9 gRB 17P25 G220990
32 6,9 gRB 17P32 H220991
35 6,9 gRB 17P35 J220992
40 6,9 gRB 17P40 K220993
45 6,9 gRB 17P45 L220994
50 6,9 gRB 17P50 M220995
55 6,9 gRB 17P55 N220996
63 6,9 gRB 17P63 P220997
75 6,9 gRB 17P75 Q220998
80 6,9 gRB 17P80 R220999
Weight: 37 g 90 6,9 gRB 17P90 S221000
Packaging: 10 pieces 100 6,9 URB 17P100 T221001
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 49
DIN 000 FUSES
APPLICATIONS DATA
Voltage Current MELTING Total clearing Watt losses
rating Class rating I2t @ Tested Estimated
I2t @ 1 ms interrupting rating
UN( V ) IN( A ) 660 VAC 0.8 IN IN interrupting rating
(A2s) (A2s)
20 12 80 3.8 7
25 20 150 5.0 9
32 39 270 5.5 10
690 40 70 460 6.6 12 200 k A
gRB 50 102 730 7.7 14 300 k A
63 210 1500 8.8 16 @ 660 V
@ 660 V
80 475 2900 9.9 18
100 970 6000 11 20
125 1900 11800 11.6 21
80 390 2500 11.6 21
100 690 4200 12.7 23
125 1300 8900 14.3 26 200 k A
690 160 2700 16000 17.0 31
URB 300 k A
200 5250 31500 19.8 36 @ 660 V
@ 660 V
250 9900 52000 24.8 45
660 315 15500 82000 31.9 58
500 350 22400 110000 31.9 58 120 k A
URB
400 33200 160000 36.3 66 @ 500 V
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 50
DIN 000 FUSES
C US
German Standard without blown fuse indicator SIZE Catalog No. REF # I/IN*
20 6,9 GRB 000 D08 / 020 D330030 1
25 6,9 GRB 000 D08 / 025 E330031 1
32 6,9 GRB 000 D08 / 032 F330032 1
40 6,9 GRB 000 D08 / 040 G330033 1
50 6,9 GRB 000 D08 / 050 H330034 1
63 6,9 GRB 000 D08 / 063 J330035 1
80 6,9 GRB 000 D08 / 080 A330073 1
100 6,9 GRB 000 D08 / 100 S330112 1
125 6,9 GRB 000 D08 / 125 T330113 0,9
80 6,9 URB 000 D08 / 080 K330036 1
100 6,9 URB 000 D08 / 100 L330037 1
125 6,9 URB 000 D08 / 120 M330038 0,9
160 6,9 URB 000 D08 / 160 N330039 0,85
200 6,9 URB 000 D08 / 200 P330040 0,85
250 6,9 URB 000 D08 / 250 Q330041 0,8
315 6,9 URB 000 D08 / 315 R330042 0,7
Weight: 110 g 350 5 URB 000 D08 / 350 V330114 0,7
Packaging: 6 pieces 400 5 URB 000 D08 / 400 D330191 0,65
* Fuse Base: SI 000 DIN 80
Ref. Number: C 220710
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 51
DIN 000 FUSES
C US
German Standard with blown fuse indication I/N FUSE BASE*
Current Rating Catalog No. REF #
20 6,9 gRB 000 DO8V/020 P330017 1
25 6,9 gRB 000 DO8V/025 Q330018 1
32 6,9 gRB 000 DO8V/032 R330019 1
40 6,9 gRB 000 DO8V/040 S330020 1
48 50 6,9 gRB 000 DO8V/050 T330021 1
63 6,9 gRB 000 DO8V/063 V330022 1
80 6,9 gRB 000 DO8V/080 G330102 1
38.5 100 6,9 gRB 000 DO8V/100 Q330110 1
8. 125 6,9 gRB 000 DO8V/125 R330111 0,9
5
80 6,9 URB 000 DO8V/080 W330023 1
100 6,9 URB 000 DO8V/100 X330024 1
8.5 125 6,9 URB 000 DO8V/125 Y330025 0,95
5 160 6,9 URB 000 DO8V/160 Z330026 0,85
77. 00
1 200 6,9 URB 000 DO8V/200 A330027 0,85
20 250 6,9 URB 000 DO8V/250 B330028 0,8
315 6,9 URB 000 DO8V/315 C330029 0,7
350 5 URB 000 DO8V/350 W330115 0,7
400 5 URB 000 DO8V/400 E330192 0,65
* Fuse Base: SI 000 DIN 80
Ref. Number: C 220710
C US
German Standard with separate blown fuse Current Rating Catalog No. REF # I/N FUSE BASE*
trip-indicator
20 6,9 gRB 000 DO8L/020 J330173 1
25 6,9 gRB 000 DO8L/025 K330174 1
32 6,9 gRB 000 DO8L/032 L330175 1
48 40 6,9 gRB 000 DO8L/040 M330176 1
50 6,9 gRB 000 DO8L/050 N330177 1
63 6,9 gRB 000 DO8L/063 P330178 1
80 6,9 gRB 000 DO8L/080 Q330179 1
55.5 100 6,9 gRB 000 DO8L/100 R330180 1
125 6,9 gRB 000 DO8L/125 S330181 0,9
80 6,9 URB 000 DO8L/080 T330182 1
8. 100 6,9 URB 000 DO8L/100 V330183 1
5
125 6,9 URB 000 DO8L/125 W330184 0,9
160 6,9 URB 000 DO8L/160 X330185 0,85
8.5 200 6,9 URB 000 DO8L/200 Y330186 0,85
5
77. 250 6,9 URB 000 DO8L/250 Z330187 0,8
1 0
0 315 6,9 URB 000 DO8L/315 A330188 0,7
20 350 5 URB 000 DO8L/350 B330189 0,7
400 5 URB 000 DO8L/400 F330193 0,65
Microswitch
MC 4L 2-5 B6 + PRES Ref. Number: F210156
MC 4L 2-5 B2 + PRES Ref. Number: G210157
*Fuse Base: SI 000 DIN 80 Ref. Number: C220710
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 52
DIN 000 FUSES
Total Clearing I t 2
8 ms (1,8 ms)
7 ms (1,5 ms)
6 ms (1,3 ms)
3 ms (0,6 ms)
2 ms (0,4 ms)
10 ms (5 ms)
10 5
10 4
D
10 3
10 2 10 3 10 4 10 5
Ip (A)
Above: Horizontal curves show, for each rated current, values of total
clearing I2t as a function of prospective current Ip. @ UN with cosj =
0.15. Horizontal lines indicate total clearing duration It, with associated
pre-arcing duration in brackets.
Clearing I2t vs. AC Operating Voltage Maximum Arc voltage vs. System Voltage
K
Um(V)
1.4
Correction Factor for I2t
1.2
1400
1
0.2
600
0
0 200 400 500 660 U (V)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 53
DIN 000 FUSES
t (s) t (s)
URB
200
315
gRB
100
50
100
125
160
250
350
400
125
80
20
25
32
40
63
80
10 4 10 4
10 3 a=130 10 3 a=130
A2=0.6 A2=0.6
B1=1.25 B1=1.25
10 2 10 2 B2=0.6
B2=0.6
Cf3=0.8
Time in Seconds
Cf3=0.8
Time in Seconds
C C'
C C'
10 10
1 1
10-1 10-1
10-2 10-2
10-3 10-3
10-4 10-4
10 10 2 10 3 10 4 I (A) 10 10 2 10 3 10 4 10 5 I (A)
Curves show, for each rated current, pre-arcing (melt) time vs. R.M.S. pre-arcing current.
Ip(A)
Max Instantanious Peak Let Thru Current
Ia(A)
10
2.5
5
Ip
2
=
gRB URB
E
Ic
=
2.5
Ip
400 A
350 A
Ic
2
=
315 A
E
250 A
Ic
200 A
=
10 4 125 A 160 A
Ic
100 A 125 A
80 A
63 A 100 A
50 A 80 A
40 A
32 A
25 A
20 A
10 3
10 2
10 2 10 3 10 4 10 5 10 6 10 2 10 3 10 4 10 5 10 6
Available Current in RMS Symmetrical Amperes Available Current in RMS Symmetrical Amperes
Curves show, for each rating, value of peak-let-through current Ic as a function of availible fault current lp.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 54
DIN 000 FUSES
0
100
200
300
400
500
600
700
0
100
200
300
400
500
600
700
Provides the DC voltage capability of a fuse as a Above: Curve indicates peak arc
function of circuit time constant (L/R ratio). voltage Um which may appear across
Curve a: Ratings from 20 to 160 A fuse terminals at DC working voltage U.
Curve b: Ratings 200 A
Curve c: Ratings from 250 to 315 A
Curve d: Ratings from 350 to 400 A
P/Pn
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
I/In
0.5
0.6
0.7
0.8
0.9
1.0
1.1
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 55
DIN FUSES
PROTISTOR® FUSES
500-690V AC
gRB/URB FROM 20 TO 400A
Size: 000
Features/Benefits
C US APPLICATIONS DATA
Current MELTING Total Watt losses
Voltage Class TESTED Estimated
rating I2t @ 1 ms clearing
rating IN( A ) interrupting rating interrupting rating
UN( V ) I2tp (A2s) I2t @ UN 0.8 IN IN
I2tt (A2s)
20 12 80 3.8 7
25 20 150 5.0 9
32 39 270 5.5 10
gRB 40 70 460 6.6 12
690 50 730 200 k A 300 k A
102 7.7 14
63 210 1500 8.8 16 @ 660 V @ 660 V
80 475 2900 9.9 18
100 970 6000 11 20
125 1900 11800 11.6 21
75 350 2250 11.2 20.5
80 390 2500 11.6 21
100 690 4200 12.7 23
110 950 6800 13.5 24.5
690 URB 125 1300 8900 14.3 26 200 k A 300 k A
160 2700 16000 17.0 31 @ 660 V @ 660 V
200 5250 31500 19.8 36
250 9900 52000 24.8 45
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 56
AMP-TRAP®–Form 101
C US
British Standard without open fuse indicator
Current Rating Catalog No. REF #
20 6,9 gRB 000 BS88/020 T330044
25 6,9 gRB 000 BS88/025 V330045
32 6,9 gRB 000 BS88/032 W330046
40 6,9 gRB 000 BS88/040 X330047
50 6,9 gRB 000 BS88/050 Z330049
63 6,9 gRB 000 BS88/063 A330050
50 80 6,9 gRB 000 BS88/080 N330108
100 6,9 gRB 000 BS88/100 H330103
21.5 125 6,9 gRB 000 BS88/125 P330109
1.5 75 6,9 URB 000 BS88/075 B330051
8.
7
12.7
4
80
100
110
6,9 URB 000 BS88/080
6,9 URB 000 BS88/100
6,9 URB 000 BS88/110
C330052
D330053
E330100
D
70 ± 4 125 6,9 URB 000 BS88/125 E330054
36 9 150 6,9 URB 000 BS88/150 F330101
160 6,9 URB 000 BS88/160 F330055
200 6,9 URB 000 BS88/200 G330056
250 6,9 URB 000 BS88/250 H330057
315 6,9 URB 000 BS88/315 J330058
350 5 URB 000 BS88/350 X330116
400 5 URB 000 BS88/400 G330194
C US
British Standard with external open fuse Current Rating Catalog No. REF #
trip-indicator
20 6,9 gRB 000 BS88P/020 Y330117
25 6,9 gRB 000 BS88P/025 Z330118
32 6,9 gRB 000 BS88P/032 A330119
40 6,9 gRB 000 BS88P/040 B330120
50 50 6,9 gRB 000 BS88P/050 C330121
63 6,9 gRB 000 BS88P/063 D330122
27 80 6,9 gRB 000 BS88P/080 E330123
1.5 100 6,9 gRB 000 BS88P/100 F330124
125 6,9 gRB 000 BS88P/125 G330125
12.7 75 6,9 URB 000 BS88P/075 H330126
8. 80 6,9 URB 000 BS88P/080 J330127
7 4
70 ± 94 100 6,9 URB 000 BS88P/100 K330128
36 110 6,9 URB 000 BS88P/110 L330129
125 6,9 URB 000 BS88P/125 M330130
150 6,9 URB 000 BS88P/150 N330131
160 6,9 URB 000 BS88P/160 P330132
200 6,9 URB 000 BS88P/200 Q330133
250 6,9 URB 000 BS88P/250 R330134
315 6,9 URB 000 BS88P/315 S330135
The use of MC 6.3 GR 2-5N blown fuse remote sensing microswitch is possible. 350 5 URB 000 BS88P/350 T330136
Ref. Number: Y 310015 mounted on separate trip-indicator. 400 5 URB 000 BS88P/400 H330195
See Microswitch section page J10, J12.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 57
DIN fuses
APPLICATIONS DATA C US
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 58
DIN FUSES
D
GERMAN STANDARD ACCORDING TO DIN 43653/00C 400 6,9 URB 00 D08L 400 M330245 0.70
DIN 80 & 110 450 6 URB 00 D08L 450 N330246 0.65
7.5
16 6,9 gRB 00 D11L 016 W330276 1
20 6,9 gRB 00 D11L 020 P330247 1
25 6,9 gRB 00 D11L 025 Q330248 1
32 6,9 gRB 00 D11L 032 R330249 1
89.5 6,9 gRB 00 D11L 040 S330250 1
40
65 gRB 50 6,9 gRB 00 D11L 050 T330251 1
2 DIN 110 63 6,9 gRB 00 D11L 063 V330252 1
80 6,9 gRB 00 D11L 080 W330253 1
+0.25 100 6,9 gRB 00 D11L 100 X330254 1
DIN80 / DIN 110 77 / 107 -1.4 125 6,9 gRB 00 D11L 125 Y330255 0.9
+0.76
DIN80 / DIN 110 100 / 130 -1.3 160 6,9 gRB 00 D11L 160 Z330256 0.9
54 maxi.
80 6,9 URB 00 D11L 80 A330257 1
100 6,9 URB 00 D11L 100 B330258 1
30 10.2 26.5 125 6,9 URB 00 D11L 125 C330259 0.9
160 6,9 URB 00 D11L 160 D330260 0.85
10.2 URB 200 6,9 URB 00 D11L 200 E330261 0.85
Weight : 140 g(D08) - 190 g(D11) DIN 110 250 6,9 URB 00 D11L 250 F330262 0.80
Packaging : 3 pieces 315 6,9 URB 00 D11L 315 G330263 0.75
Microswitches: MS 4L 2.5 B6 - Part #: L076646 350 6,9 URB 00 D11L 350 H330264 0.75
6.3 clips
or MC 4L 2.5 B6 + PRES - Part #: F210156 400 6,9 URB 00 D11L 400 J330265 0.70
2.8 clips MS 4L 2.5 B2 - Part #: G076642 450 6 URB 00 D11L 450 K330266 0.65
or MC 4L 2.5 B2 + PRES - Part #: G210157
Fuse-base: SI 00 DIN 80 - Part #: Q098040
Current catalog No. ref #
rating I/IN Fuse-base
16 6,9 gRB 00 PV/016 L330267 1
GERMAN STANDARD ACCORDING TO DIN 43620/00 20 6,9 gRB 00 PV/020 W330207 1
25 6,9 gRB 00 PV/025 X330208 1
8.5 49.4 32 6,9 gRB 00 PV/032 Y330209 1
gRB 40 6,9 gRB 00 PV/040 Z330210 1
DIN 43620 50 6,9 gRB 00 PV/050 A330211 1
63 6,9 gRB 00 PV/063 B330212 0.90
60 80 6,9 gRB 00 PV/080 C330213 0.90
15 100 6,9 gRB 00 PV/100 D330214 0.90
125 6,9 gRB 00 PV/125 E330215 0.85
160 6,9 gRB 00 PV/160 F330216 0.85
52 ±1
6 ±0.1
78.5 ±1.4
30 80 6,9 URD 00 PV0080 Z320159 0.90
Weight : 210 g 100 6,9 URD 00 PV0100 D320163 0.90
Packaging : 3 pieces
Microswitches: 125 6,9 URD 00 PV0125 F320165 0.85
6.3 clips or MC 4L 2.5 B6 + PRES - Part #: F210156 160 6,9 URD 00 PV0160 K320169 0.85
2.8 clips 200 6,9 URD 00 PV0200 M320171 0.85
or MC 4L 2.5 B2 + PRES - Part #: G210157 250 6,9 URD 00 PV0250 R320175 0.80
Fuse-base: 41002-G URD 315 6,9 URD 00 PV0315 W320179 0.75
DIN 43620
I/IN : Ratio RMS steady current / current rating for fuses in base.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 59
DIN FUSES
10 ms (2.5 ms)
7.5 ms (1.3 ms)
9 ms (1.8 ms)
6.5 ms (1 ms)
6 ms (0.8 ms)
5 ms (0.6 ms)
4 ms (0.4 ms)
3 ms (0.2 ms)
10 ms (5 ms)
9 ms (1.8 ms)
6.5 ms (1 ms)
6 ms (0.8 ms)
5 ms (0.6 ms)
4 ms (0.4 ms)
3 ms (0.2 ms)
10 ms (5 ms)
I2t (A2s)
10 6
10 5
450 A
160 A 10 5 400 A
350 A
315 A
10 4 125 A 250 A
Clearing I2t
Clearing I2t
100 A 200 A
80 A 10 4 160 A
125 A
63 A 100 A
10 3
50 A 80 A
10 3 63 A
40 A
50 A
32 A 40 A
25 A 32 A
10 2 20 A 10 2 25 A
16 A 20 A
16 A
10 1
10 1 10
6
10 1 10 2 10 3 10 4 10 5 10 6
10 1 10 2 10 3 10 4 10 5 10 6
The flat curves show for each rated current the maximum values of total clearing I2t (I2tt) as a function of a prospective current Ip. @ UN.with cosj = 0.15.
The crosswise lines indicate the total clearing duration Tt and the associated pre-arcing duration in brackets.
K Um (V)
1.2 1600 L/R = 80 ms
L/R = 25 ms
1400
1
Correction Factor
Correction Factor
1200 L/R = 10 ms
0.8
Correction factor to 1000 Determines the peak arc
0.6
determine I2t value for a voltage across the fuse
800
fuse operating below its terminals as a function if
0.4 rated voltage. 600
applied voltage.
400
0.2
200
0
U (V) 0
0
100
200
300
400
500
600
700
800
P/Pn
1
0.9
0.8
0.7
I/In
0.5
0.6
0.7
0.8
0.9
1.0
1.1
% of Rating
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 60
DIN FUSES
0
100
200
300
400
500
600
700
800
900
1000
100
200
300
400
500
600
700
800
900
D
0
Ip Ip
Ip
Ip
2.5 2
Ic 2.5
2
IC(A) IC(A) = =
=
Ic
=
Ic
Max Peak Let Thru Currents
101 101
10 1
10 2
10 3
104
10 5
10 6 101 102 103 104 105 106 Ip (A)
Symmetrical Current in Amperes Symmetrical Current in Amperes
Melting Time - Current Data - gRB Melting Time - Current Data - URB
32
80
160
250
350
50
20
32
80
50
20
t (s) t (s)
100
125
160
16
25
40
63
100
125
200
315
400
450
16
25
40
63
104
104
a=130 a= 130
103 A2=0.6 A2=0.67 These curves
B1=1.25 103 B1= 1.25 indicate, for each
B2=0.6 B2= 0.67 rated current, the
Cf3=0.8 Cf3= 0.8 pre-arcing time vs.
102
102 the R.M.S. pre-arcing
C current.
Time in Seconds
Time in Seconds
10-2
10-2
10-3
10-3
10-4
I (A) 10-4
10 102 103 104 10 102 103 104 I (A)
Current in Amperes Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 61
PSC SQUARE BODY
All fuse links are equipped with a low voltage trip-indicator. This
trip-indicator can operate a field mountable microswitch which is
easily mounted directly onto the fuse even while in service.
32 60 32 16 30 27 101.6 134.6
6 E
33 74.5 40 20 37.2 34.25 101.6 134.6
A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 63
PSC SQUARE BODY
DIMENSIONS - In/(mm)
Types TTI and TTF
BODY SIZE TYPE A B C
C
30 1.57 1.00 5/16-18 X .35
6.7 (40) (25)
31 2.00 1.19 5/16-18 X .35
TTI (50.8) (30.2)
B A 32 2.37 1.50 3/8-16 X .35
(60.3) (38.1)
33 2.94 1.81 1/2-13 X .35
(74.6) (46)
DIMENSIONS - In/(mm)
BODY SIZE TYPE A B C
50.6
(1.99) 30 40 26 M8 X 1.25 X 6 DP
31 TTF 51 30 M8 X 1.25 X 9 DP
32 60 38 M10 X 1.50 X 9 DP
33 74.5 46 M12 X 1.75 X 9 DP
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 64
PSC SQUARE BODY
Outline Dimensions
Type EF
D 47.6 MAX 6
C
B 62
E
F
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 65
PSC
** Watts loss data is published for both blade and tapped style mounting configurations. When two watts loss values are shown this represents tapped/blade values respectively.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 66
PSC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 67
PSC
Watts Loss vs. % Rated Current Clearing I2t vs. Operating Voltage
Correction Factor for Watts Loss
Correction factor to determine the watts loss value of a Correction factor to determine the clearing I2t value for a fuse
fuse operating below its rated current operating below its rated voltage
Maximum Arc Volts vs. System Voltage Ampere Rating Correction Factor vs. Air Flow Speed
Peak Arc Voltage (Volts)
Correction Factor
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 70
PSC SQUARE BODY
DC Voltage Capability
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 71
PSC SQUARE BODY
WEIGHT
size Catalog No. REF # (g)
6,9 URD 232 TTF 1000 T300213
6,9 URD 232 TTF 1250 V300214 1240
6,9 URD 232 TTF 1400 G300087
2 x 32 6,9 URD 232 TDF 1600 W300215
6,9 URD 232 TDF 1800 X300216
3300
6,6 URD 232 TDF 2000 Y300217
5,5 URD 232 TDF 2200 D301993
6,9 URD 233 TTF 1250 D300268
6,9 URD 233 TTF 1400 E300269 1900
6,9 URD 233 TTF 1600 F300270
6,9 URD 233 PLAF 1800 B300427
6 URD 233 PLAF 2000 R302235
6 URD 233 PLAF 2200 Q302234
6 URD 233 PLAF 2500 P302233
2 x 33 6 URD 233 PLAF 2800 N302232
5,5 URD 233 PLAF 3000 L301977
2000
5,5 URD 233 PLAF 3200 M301978
5 URD 233 PLAF 3600 N301979
5 URD 233 PLAF 4000 P301980
4 URD 233 PLAF 4500 Q301981
4 URD 233 PLAF 5000 R301982
Dimensions in mm
SIZE A B C D E F G H J K d e L M N
2x32 TT 60 138,5 172 11 67,6 66,5 100 35 61 40 M 10 4 107,5 48 72
PLAF
Studs and
microswitches
supplied
separately
WEIGHT
size Catalog No. REF # PACK.
(g)
33 6,9 URD 33 PPAF 1250 - 910 3
6,9 URD 33 PPAF 1400 -
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 72
PSC SQUARE BODY
Current in Amperes
Clearing I2t Data 2X32
Time-current characteristics
Above, left: Curves indicating melting time for each rated
current as a function of RMS value of melting current I.
- Tolerances on this current = 8%
- Beyond 30 sec or 10 sec, small overloads must be eliminated
by another device
- Curve CC’ represents the maximum times taken by the associ-
ated device to clear small overloads; only its horizontal line is
represented. Its oblique line must be plotted according to sketch,
Clearing I2t
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 73
PSC
Size 2 x 33
c c’
Time-current characteristics
Above, left: Curves indicating pre-arcing time for each rated
current as a function of RMS value of pre-arcing current I.
- Tolerances on this current +- 8%.
- Beyond 30 sec small overloads must be eliminated
by another device
Clearing I2t
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 74
PSC SQUARE BODY
North American Reference Numbering System European / IEC Reference Numbering System
A 130 URD 71 I 350 12,5 URD 71 I 350
A.C.
Outline Dimensions
4.7
6 E
Types LI and LLI North American Straight Blade, Types LI & LLI
DIMENSIONS - In/(mm)
J B BODY SIZE TYPE A B C D E F G H J
70 LI 40 25 12.5 21 18 91.4 130.4 152.4 10.5
(1.57) (0.98) (0.49) (0.83) (0.71) (3.60) (5.13) (6.00) (0.41)
72.5 MAX
(2.85) 71 LLI 51 25 12.5 25.5 22.5 91.4 130.4 152.4 14.6
F (2.01) (0.98) (0.49) (1.00) (0.89) (3.60) (5.13) (6.00) (0.57)
G
H 72 60 32 16 30 27 97.6 132.4 157.4 14.6
LI (2.36) (1.26) (0.63) (1.18) (1.06) (3.84) (5.2) (6.20) (0.57)
A
73 74.5 40 20 37.2 34.2 98.8 132.4 157.4 15.9
(2.93) (1.57) (0.79) (1.46) (1.35) (3.89) (5.21) (6.20) (0.63)
D
6 E
(.24)
5.03
A
(.2)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 76
PSC SQUARE BODY
Packaging: 6 pairs
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 77
PSC SQUARE BODY
** Watts loss data is published for both blade and tapped style mounting configurations. When two watts loss values are
shown this represents tapped/blade values respectively.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 78
PSC SQUARE BODY
D
160 1300 2.6 22 46 A130URD71LLI0160 A130URD71TTI0160
200 1300 4.7 40 54 A130URD71LLI0200 A130URD71TTI0200
250 1300 8.9 76 61 A130URD71LLI0250 A130URD71TTI0250
280 1300 12 102 68/70 A130URD71LLI0280 A130URD71TTI0280
315 1300 16 138 73/76 A130URD71LLI0315 A130URD71TTI0315
350 1300 22 190 76/80 A130URD71LLI0350 A130URD71TTI0350
71
400 1300 38 330 76/80 A130URD71LLI0400 A130URD71TTI0400
450 1300 47 405 87/95 A130URD71LLI0450 A130URD71TTI0450
500 1200 68 500 90/100 A120URD71LLI0500 A120URD71TTI0500
550 1200 84 620 98/112 A120URD71LLI0550 A120URD71TTI0550
630 1100 125 930 105 A110URD71LLI0630 -
630 1200 125 930 120 - A120URD71TTI0630
280 1300 10 90 72 A130URD72LI0280 A130URD72TTI0280
315 1300 15 130 76 A130URD72LI0315 A130URD72TTI0315
350 1300 21 180 77 A130URD72LI0350 A130URD72TTI0350
400 1300 32 285 80 A130URD72LI0400 A130URD72TTI0400
450 1300 44 380 87/89 A130URD72LI0450 A130URD72TTI0450
500 1300 57 500 94/98 A130URD72LI0500 A130URD72TTI0500
72 550 1300 68 590 110/120 A130URD72LI0550 A130URD72TTI0550
630 1200 105 920 113 A120URD72LI0630 -
630 1300 105 920 125 - A130URD72TTI0630
700 1100 145 1040 122 A110URD72LI0700 -
700 1200 145 1040 140 - A120URD72TTI0700
800 1100 215 1590 125 A110URD72LI0800 -
800 1200 215 1590 146 - A120URD72TTI0800
315 1300 12 102 84 A130URD73LI0315 A130URD73TTI0315
350 1300 17 150 86 A130URD73LI0350 A130URD73TTI0350
400 1300 25 220 93 A130URD73LI0400 A130URD73TTI0400
450 1300 35 310 99/100 A130URD73LI0450 A130URD73TTI0450
500 1300 44 390 110/112 A130URD73LI0500 A130URD73TTI0500
550 1300 57 500 116/120 A130URD73LI0550 A130URD73TTI0550
630 1300 84 730 125/132 A130URD73LI0630 A130URD73TTI0630
700 1300 110 960 135/146 A130URD73LI0700 A130URD73TTI0700
800 1200 190 1630 136 A120URD73LI0800 -
73 800 1300 190 1630 148 - A130URD73TTI0800
900 1100 250 2160 150 A110URD73LI0900 -
900 1300 250 2160 170 - A130URD73TTI0900
1000 1100 370 2430 152/174 A100URD73LI1000 A110URD73TTI1000
1100 1000 445 2580 168/208 A100URD73LI1100 A100URD73TTI1100
1250 1000 585 3480 186/200 A100URD73LI1250 A100URD73TTI1250
1400 900 755 3880 210/228 A090URD73LI1400 A090URD73TTI1400
1600 700 1430 5630 203 A070URD73LI1600 A070URD73TTI1600
1800 650 2040 7600 206 A065URD73LI1800 A065URD73TTI1800
** Watts loss data is published for both blade and tapped style mounting configurations. When two watts loss values are
shown this represents tapped/blade values respectively.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 79
PSC SQUARE BODY
Operating Voltage
Watts Loss vs. Rated Current Maximum Arc Voltage vs. System Voltage
Max Peak Let Thru Current Data
Correction factor (Watts)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 82
PSC SQUARE BODY
2000 c 22000
2200 c 24000
2500 d 27000
2800 d 30000
Above: Ipm (1) values indicate the minimum breaking current in amperes (A).
DC Working Voltage
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 83
PSC SQUARE BODY
WEIGHT
size Catalog No. REF # (g)
12,5 URD 73 PPAF 0315 H300640
12,5 URD 73 PPAF 0350 J3002641
12,5 URD 73 PPAF 0400 K300642
12,5 URD 73 PPAF 0450 L300643
12,5 URD 73 PPAF 0500 M300644
12,5 URD 73 PPAF 0550 N300645
73 12,5 URD 73 PPAF 0630 P300646
12,5 URD 73 PPAF 0700 Q300674 1250
12,5 URD 73 PPAF 0800 R300648
12 URD 73 PPAF 0900 S300649
10 URD 73 PPAF 1000 T300650
9,5 URD 73 PPAF 1100 V300651
9 URD 73 PPAF 1250 T300719
8,5 URD 73 PPAF 1400 V300720
12,5 URD 272 TTF 0630 W300721
12,5 URD 272 TTF 0700 X300722
12,5 URD 272 TTF 0800 Y300723
12,5 URD 272 TTF 0900 Z300724 1750
12,5 URD 272 TTF 1000 A300725
12,5 URD 272 TTF 1100 B300726
2 X 72 11 URD 272 TTF 1250 -
11 URD 272 TTF 1400 D300728
10 URD 272 TTF 1600 L302230
9 URD 272 TTF 1800 E301994 1900
7,5 URD 272 TTF 2000 F301975
6,5 URD 272 TTF 2200 G301996
6,5 URD 272 TTF 2500 H301997
12,5 URD 273 TTF 800 F300730
12,5 URD 273 TTF 900 G300731 Microswitches and threaded studs supplied
12,5 URD 273 TTF 1000 H300732 separately (see pages J8)
12,5 URD 273 TTF 1100 J300733 2600
12,5 URD 273 TTF 1250 K300734
11 URD 273 TTF 1400 K302229
11 URD 273 TTF 1600 -
11 URD 273 TTF 1800 J302236
2 X 73 10 URD 273 TTF 2000 P300738 2800
9,5 URD 273 TTF 2200 Q300739
9,5 URD 273 PLAF 2200 M301909
9 URD 273 PLAF 2500 R300740
8,5 URD 273 PLAF 2800 S300741 2700
6 URD 273 PLAF 3000 K301999
6 URD 273 PLAF 3200 M302001
5,5 URD 273 PLAF 3600 N302002
SIZE A B C D E F G H J K d e L M N
2X72 TTF 60 138,5 172 11 91 65,5 100 35 66 39 M 10 4 131 48 72
Dimensions in mm
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 84
PSC SQUARE BODY
Time-current characteristics
Above, left: Curves indicating pre-arcing time for each rated
current as a function of RMS value of pre-arcing current I.
- Beyond 30 sec or 10 sec, small overloads must be eliminated
by another device
- Curve CC’ represents the maximum times taken by the
associated device to clear small overloads; only its horizontal
line is represented. Its oblique line must be plotted according
to sketch, top right corner.
- The intersection of the fuse and CC’ curves indicate the
minimum breaking current Ipm of the fuse.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 85
PSC SQUARE BODY
Time-current characteristics
Above, left: Curves indicating pre-arcing time for each rated
current as a function of RMS value of pre-arcing current I.
- Beyond 30 sec small overloads must be eliminated
by another device
- The intersection of the fuse and CC’ curves indicate the
minimum breaking current of the fuse.
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 86
FRENCH CYLINDRICAL
PROTISTOR® FUSES
600V AC URD from 0.10 up to 0.80A**
500V AC URB/URD/URL from 1 up to 30A
Size: 10 x 38
Features/Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors according to
IEC 269.1 and 4
➤ 500-600V AC Voltage Rating
➤ aR Class according to VDE 636-23 and IEC 269.4
➤ Without blown fuse indication according to NF C
63210 and 63211 - 0.10 up to 0.80A**
➤ With built in Trip-Indicator (1 up to 30A)
Ferraz Specialty*
D
APPLICATIONS DATA
Voltage Current Melting Total clearing I2t @ UN Tested
I2t @ 1 ms Watt losses
rating Class rating I2tt (A2s) interrupting
UN( VAC ) IN (A) I2tp (A2s) 0.8 IN IN rating
100 mA 1.2 10 -3 0.23 0.4
125 mA 2.3 10 -3 0.25 0.44
160 mA 5.2 10 -3 0.28 0.48
200 mA 8 10 -3 0.34 0.58
600 V 250 mA 0.35 0.60
18 10 -3
without blown URD 315 mA 33 10 -3 0.42 0.73
fuse indication 200 kA
400 mA 56 10 -3 0.46 0.80 @ 600 V
500 mA 0.100 0.46 0.80
630 mA 0.18 0.52 0.90
800 mA 0.44 0.58 1
1A 0.49 1.3 0.4 0.7
1.25 A 0.13 1.7 0.52 0.91
1.6 A 0.31 2.2 0.58 1
2A 0.65 3.1 0.63 1.1
URD 2.5 A 1.65 5.9 0.63 1.1 50 kA
3.15 A 2.80 9 0.86 1.5 @ 500 V
4A 5.30 16 1.1 1.8
500 V 5A 12.7 36 1.1 1.8
with 6A 1.3 47 0.73 1.35
trip-indicator 8A 2.3 80 0.83 1.55
10 A 3.6 110 1 1.9
URB 12 A 5.25 150 1.3 2.3 50 kA
16 A 9.30 200 1.7 3.1 @ 500 V
20 A 16 290 1.7 3.2
25 A 37 580 2.9 4.25 50 kA
URL 30 A 58 900 3.5 5.1 @ 500 V
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 87
FRENCH CYLINDRICAL
PART NUMBERS
* UL Recognized
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 88
FRENCH CYLINDRICAL
Features/Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors according to
IEC 269.1 and 4
➤ 690V AC Voltage Rating
➤ aR Class according to VDE 636-23 and IEC 269.4
➤ Two Models according to NF C 63210 and 63211 with
D
and without blown fuse built-in trip-indicator for sizes
14 x 51 and 22 x 58
➤ UL RECOGNIZED (Except 6A)*
APPLICATIONS DATA
Voltage Current Melting Total clearing I2t @ (A2s) Tested
I2t @ 1 ms Watt losses
rating Size Class rating 660 V interrupting
UN(VAC) IN (A) I2tp (A2s) 0.8 IN IN rating
6 1.3 17.5* 1.1 2
8 2.4 27.5 1.6 2.8
10 4.3 40 2 3.5
12 5.4 60 2.45 4.4
16 13.2 100 2.7 4.8
URC 20 27 160 2.9 5.2 100 kA
14 x 51 25 53 275 3.2 5.8 @ 690 V
32 98 500 3.9 7
40 (1) 130 700 6 10.7
50 (1) 280 1500 6.3 11.6
690 V
7 IN < Ip < 30 IN Ip ≥ 30 IN
URD 40 (2) 130 850 700 6 10.7 100 kA
50 (2) 280 1850 1500 6.3 11.6 @ 690 V
25 22 125 5.2 10
32 49 275 5.7 11
40 88 480 6.8 13
22 x 58 URD 50 155 800 7.8 14.9 100 kA
63 350 1850 8.4 16 @ 690 V
80 730 3800 9.4 17.8
100 1560 8000 10 19
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 89
FRENCH CYLINDRICAL
14x51 - Without blown fuse indication Current Rating Catalog No. Ref #
14x51 - With blown fuse trip-indicator Current Rating Catalog No. Ref #
22x58 - Without blown fuse indication Current Rating Catalog No. Ref #
58
25 A 6.900 CP URD 22x58/25 B093956
32 A 6.900 CP URD 22x58/32 Z094828
22,2
22x58 - With blown fuse trip-indicator Current Rating Catalog No. Ref #
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 90
FRENCH CYLINDRICAL
These curves indicate, for each rated current, the pre-arcing (melting) time vs. the R.M.S. current.
Clearing I2t vs. Operating Voltage Peak arc voltage vs. Operating Voltage
22x58 URD
22x58 URD
Um(V)
Max Peak Arc Voltage
K
1,2 2000
1
1600
0,8
1200
0,6
800
0,4
0,2 400
0 100 200 300 400 500 600 700 0 100 200 300 400 500 600 700
U(V)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 91
FRENCH CYLINDRICAL
DC Voltage Capabilities vs. Time Constant Peak Arc voltage vs. DC circuit voltage
L (ms)
R
80 Um(V)
1000
900
60
50 800
40 700
30 600
20
500
10
DC Voltage Capabilities vs. Time Constant Peak Arc voltage vs. DC circuit voltage
L (ms)
R
80 Um(V)
1100
70
Peak Arc Voltage
Time Constant L/R
1000
60
900
50
40 800
30 700
20 600
10
100 200 300 400 500 600 700
U(V)
0 100 200 300 400 500 600
U(V)
DC Voltage Capability DC Circuit Voltage
These curves provide the DC voltage capability of These curves shows the peak value Um of the arc voltage
the fuse as a function of circuit time constant. which appears across the fuse link as a function of the
(L/R ratio) operating voltage U.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 92
FRENCH CYLINDRICAL
Features/Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors according to
IEC 269.1 and 4
➤ 600V-690V AC Voltage Rating
➤ aR Class according to VDE 636-23 and IEC 269.4
➤ Model according to NF C 63210 and 63211 with
D
built-in blown fuse indication
APPLICATIONS DATA
Voltage Current Melting Total clearing I2t @ UN
rating rating I2t @ 1 ms Watt losses Tested
Class
I2tp (A2s) I2tt (A2s)
UN( VAC ) I N( A ) 0.8 IN IN interrupting rating
63 405 1840 12 22
80 860 3750 13.5 24.6
690 V URGD 6800 200 kA
100 1620 15 27
125 3425 13600 16 29.5 @ 690 V
160 6480 24600 17 32.5
200 13700 61500 18.5 35.7
600 V URGD 250 29600 107000 21 40 200 kA @ 600 V
Minimum operating voltage for trip-indicator: 20 V
PART NUMBERS
Current
27x60 - With blown fuse trip-indicatior Type Voltage rating Catalog No. REF #
60,3
7 63 A 6,921 CP URGD 27x60/ 63 A 076820
80 A 6,921 CP URGD 27x60/ 80 B 076821
100 A 6,921 CP URGD 27x60/100 C 076822
URGD 690 V 125 A 6,921 CP URGD 27x60/125 D 076823
Ø 27
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 93
FRENCH CYLINDRICAL
Time in Seconds
These curves indicate, for each rated current, the pre-arcing (melting) time vs. the R.M.S. pre-arcing current.
Clearing I2t vs. AC Operating Voltage Peak arc voltage vs. Operating Voltage
K
Correction factor for I2t
1,2 Um(V)
2000
1
Max Arc Volts
0,8
0,6
1000
0,4
0,2
0 200 400 600 Correction factor to deter- 0 100 200 300 400 500 600 700
These curves
U(V) mine the clearing I2t of a determine the peak
Operating Voltage fuse operating below its
System Voltage arc voltage across
rated voltage. the fuse terminals
250A URGD 250A URGD
as a function of the
K applied voltage.
Correction factor for I2t
1,2 Um(V)
2000
1
Max Arc Volts
0,8
0,6
1000
0,4
0,2
0 100 200 300 400 500 600 0 100 200 300 400 500 600 700
U(V)
Operating Voltage System Voltage
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 94
FRENCH CYLINDRICAL
690V - 1000V AC
URB/URQ/URS from 32 up to 250A
Size: 27 X 60
Features/Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors according to
IEC Standard 269.1 and 4
➤ 690V-1000V AC Voltage Rating
➤ aR Class according to VDE 636-23 and IEC 269.4
➤ Model according to NF C 63210 and 63211 with
built-in blown trip-indicator
➤ 690V URQ and 1000V URB are UL Recognized D
APPLICATIONS DATA
Voltage Current Melting Total clearing I2t @ UN Watt losses Tested
rating Class rating I2t @ 1 ms I2tt (A2s) interrupting
UN(VAC) IN (A) I2tp (A2s) 0,8 IN IN rating
50 110 610 8.4 16
63 155 860 11.1 21
80 350 1880 12.6 24
100 625 3210 14.2 27
690 V URQ 125 1400 6970 15.7 30 200 kA
160 3150 15000 17.7 34 @ 690 V
200 6580 30000 19.4 38
250 15570 63000 22.6 45
125 2790 13000 14.5 25
URS
160 5500 24000 17.5 30
32 33 250 7.4 14.5
40 60 450 8.7 17
50 110 840 9.7 19
1000 V URB 63 200 1470 11.3 22 100 kA
80 435 3300 12.3 24 @ 1000 V
100 975 6000 14 27
125 1910 12500 16 31
160 3890 26700 18 35
170 4710 36000 19 37
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 95
FRENCH CYLINDRICAL
PART NUMBERS
Ø5
40 A 1021 CP URB 27x60/ 40 R081297
50 A 1021 CP URB 27x60/ 50 Q081296
63 A 1021 CP URB 27x60/ 63 P081295
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 96
FRENCH CYLINDRICAL
Time in Seconds
D
a = 130 B1 = 1,25
A2 = 0,6 B2 = 0,6
Cf3 = 0,8
Time in Seconds
Current in Amperes
These curves indicate, for each rated current, the pre-arcing time vs. the R.M.S. pre-arcing current.
For each rated current tolerance for the mean pre-arcing current ± 8%.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 97
FRENCH CYLINDRICAL
Um(V)
Um(V)
Um(V) Um(V)
Um(V)
Um(V) Um(V)
Um(V)
Um(V)
2000 2000
2000
2000 2000
2000 2000 2000
2000
1000 1000
1000
1000 1000
1000 1000 1000
1000
0 0 0
0 100
0 0100
200100
200
300200
300
400300
400
500400
500
600500
600
700600
700700 500 500
600500700
600 700
600800
700800
900800
9009001000
1000 1000
0 200100
0 0100
100 200
300200
300
400300
400
500400
500
600500
600
700600
700700
U(V) U(V)
U(V) U(V) U(V)
U(V) U(V) U(V)
U(V)
System Voltage System Voltage System Voltage
Determines the peak arc voltage across the fuse terminals as a function of the applied voltage.
Correction factor to determine the clearing I2t for a fuse operating below its rated voltage.
L
(ms)
R In ≤ 160 A
80
70
Time Constant
60
In ≤ 200 A
50
40 In ≤ 250 A
30
Provides the DC voltage capabilities of
20
the fuse as a function of circuit time
10 constant. (L/R ratio)
0
100 200 300 400 500 600
U(V)
DC Voltage Capability
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 98
FRENCH CYLINDRICAL
800V AC
gRB from 8 to 110A
SizeS: 27 X 60
Features/Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors complying
with IEC standards 269-1 and 4
D
-Full range protection
-Improved safety and protection
-Allows selective coordination
➤ With built in Trip Indicator
Dimensions
APPLICATIONS DATA
Voltage Current Melting Total clearing Watt losses Tested
rating Class rating I2t @ 1 ms I2t @ UN interrupting CATALOG NO. REF
UN( V ) I N( A ) I2tp (A2s) I2tt (A2s) 0.8 IN IN rating
8 4.25 70 1.2 2.0 821 CP GRB27.60 8 R221436
10 8.0 100 1.3 2.3 821 CP GRB27.60 10 S221437
12 17.0 180 1.4 2.5 175 kA 821 CP GRB27.60 12 T221438
16 26.5 250 1.9 3.5 @ 700 V 821 CP GRB27.60 16 V221439
20 38.5 350 2.4 4.0 821 CP GRB27.60 20 W221440
25 73.0 600 2.8 5.0 821 CP GRB27.60 25 X221441
800 gRB 32 130 1000 3.5 6.0 821 CP GRB27.60 32 Y221442
40 195 1400 4.7 8.0 821 CP GRB27.60 40 Z221443
90 kA
50 430 2700 4.8 8.5 821 CP GRB27.60 50 A221444
@ 800 V
63 965 5500 5.6 10 821 CP GRB27.60 63 B221445
80 1890 11000 6.4 11.5 821 CP GRB27.60 80 C221446
100 3480 19000 7.4 13 821 CP GRB27.60 100 D221447
110 4670 27000 7.7 14 821 CP GRB27.60 110 E221448
Minimum operating voltage for trip-indicator: 20 V
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 99
FRENCH CYLINDRICAL
Current in Amperes
Curves show, for each rated current, pre-arcing time vs. R.M.S. pre-arcing current.
Tolerance for mean pre-arcing current ± 8%.
Clearing I2t
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 100
FRENCH CYLINDRICAL
Um (V)
2000
1800
1600
Correction Factor (watts)
Max Peak Arc Voltage
1400
1200
1000
800
600
400
200
0
0 100 300 500 700 800 U (V)
System Voltage % of Rating
Determines the peak arc voltage across the fuse terminals as a Correction factor to determine watts loss value of a fuse operating
function of applied voltage. below its rated current.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 101
BRITISH STANDARD
Features/Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors according to
IEC 269.1 and 4
APPLICATIONS DATA
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 102
BRITISH STANDARD
PART NUMBERS
D
SIZE Catalog No. REF #
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 103
BRITISH STANDARD
Features/Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors according to
IEC 269.1 and 4
APPLICATIONS DATA
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 104
BRITISH STANDARD
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 105
BRITISH STANDARD
Features/Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors according to
IEC 269.1 and 4
APPLICATIONS DATA
200 kA
@ 690V
200 kA
690V @ 690V
200 kA
@ 690V
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 106
BRITISH STANDARD
D
6,9 URS 17/20 H 075884
6,9 URS 17/25 J 075885
6,9 URS 17/32 K 075886
6,9 URS 17/35 L 075887
6,9 URS 17/40 M 075888
17x49 6,9 URS 17/45 N 075889
6,9 URS 17/50 P 075890
6,9 URS 17/55 Q 075891
6,9 URS 17/63 R 075892
6,9 URS 17/75 S 075893
6,9 URS 17/80 T 075894
Time in Seconds
Time in Seconds
Current in Amperes Current in Amperes Current in Amperes
• These curves indicate, for each rated current, the pre-arching time vs. the R.M.S. current.
Clearing I2t vs. Operating Voltage Maximum Arc Voltage vs. Applied Voltage
Correction factor for I2t
PROTISTOR® FUSES
690V
URR/URGL/URU/URGM from 75 to 800A
SizeS: 36 X 55 & 2 X 36 x 55
Features/Benefits
APPLICATIONS DATA
200 kA
@690V
200 kA
@690V
690V
200 kA
@690V
200 kA
@690V
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 109
BRITISH STANDARD
PART NUMBERS
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
D 110
Medium Voltage
Fuses
Various configurations.
Different types of ratings.
One solution.
Our solution: Welcome to the Ferraz Shawmut Amp-Trap® • Amp-Trap® R-Rated / A240R
medium voltage UL fuse line. Our E-Rated models for trans- • Amp-Trap® R-Rated / A480R-1HE
formers and distribution systems are UL Listed. They’re
• Amp-Trap® R-Rated / A480R-1HE
available in 5.5kV, 10E to 900E and 15.5kV, 10E to 300E
ratings. And they come in three configurations. Additionally, • Amp-Trap® R-Rated /
A072F / A072B
our R-Rated models (rated for 4800V, 2R to 36R and 7200V,
2R to 24R) are UL Recognized — and provide reliable short • Amp-Trap® R2CL20CF
circuit protection for MV motor controllers and motors. We • Amp-Trap® E-Rated /
also offer fuses to protect M.V. capacitors up to 5.5kV. Potential Transformer
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
AMP-TRAP®
Features/Benefits
➤ UL Listed for compatiblity with UL listed equipment
➤ Ferrule mounting for standard clips and
interchangeability with other brands of fuses
➤ Current Limiting for superior equipment protection
➤ Blown-fuse indicator gives positive identification
of open fuse
HIGHLIGHTS: Applications: ➤ Non-venting for silent operation
➤ E-Rated ➤ Protection for 5.5, ➤ Metal Embossed Catalog Number and
➤ UL Listed 5.5kV and15.5kV 8.25 manufacturing date for lasting identification
➤ Complies with ANSI C37.46 ➤ or 15.5kV transformers
or distribution system.
Ratings Approvals
Definitions: ➤ A055F ➤ UL Listed to JEEG,
AC: 5E to 450E “Fuses Over 600 Volts”
E-rating 5.5kV, 63kA I.R. Sym.
E-rated fuses operate as follows: UL File # E143362
100E or less - must melt in 300 seconds (5 mins.) ➤ A825X
AC: 10E to 200E
at 200 to 240% of E (ampere) rating. 8.25kV, 50kA I.R. Sym.
Over 100E - must melt in 600 seconds (10 mins.)
at 220 to 264% of E (ampere) rating. ➤ A155F
AC: 5E TO 200E
Example - A 100E fuse must melt in 300 seconds with an 15.5kV, 50kA I.R. Sym.
applied current of 200 to 240 amperes.
E
Figure A Figure B Figure C
A055F1CORO-5E A550X5E-1B 5E 5E
7E 7E-1B 7E
10E 10E-1B 10E
15E 15E-1B 15E
20E 20E-1B 20E 1 A 14.11 2.2 .19 63,000
25E 25E-1B 25E (358) (56) (4.8)
30E 30E-1B 30E Tripped
40E 40E-1B 40E Force
50E 50E-1B 50E 1 lb.
65E 65E-1B 65E
5.5kV Max. – Ferrule Mounted Style – 12” (305mm) Clip Centers – 3” (76.2mm) Barrel Diameter
A055F1CORO – 5E to 65E
Total Clearing Time – Current Data, 5.5kV Fuses
Current in Amperes
Time in Seconds
A055F1CORO – 5E to 65E
Minimum Melting Time – Current Data, 5.5kV Fuses
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E
AMP-TRAP®
Time in Seconds
E
Current in Amperes
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E
AMP-TRAP®
3
(76)
.38
(9.6)
3 (76)
.50 (13)
2 LB TRIP FORCE
15.88 REF
(403)
Figure A
3
(76)
E
.38 (9.6)
3 (76)
.50 (13)
2 LB TRIP FORCE
15.88 REF
(403)
Figure B
NUMBER INTERRUPTING
AMPERE
CATALOG NUMBER OF FIG. RATING RMS
RATING
BARRELS SYM. AMPERES*
8.25kV MAX. FERRULE MOUNTED STYLE - 12” (305 mm) CLIP CENTER - 3” (76.2 mm) BARREL DIAMETER
A825X10E-1 10E 1 A
A825X15E-1 15E 1 A
A825X20E-1 20E 1 A
A825X25E-1 25E 1 A
A825X30E-1 30E 1 A 50,000
A825X40E-1 40E 1 A
A825X50E-1 50E 1 A
A825X65E-1 65E 1 A
A825X80E-1 80E 1 A
A825X100E-1 100E 1 A
A825X125E-1 125E 2 B
A825X150E-1 150E 2 B 50,000
A825X200E-1 200E 2 B
Current in Amps x 10
Current in Amps x 10
E
Figure A Figure B Figure C
15.5kV Max.. – Ferrule Mounted Style – 18” (457mm) Clip Centers – 3” (76.2mm) Barrel Diameter
Minimum Melting Time – Current Data, 15.5kV Fuses Total Clearing Time – Current Data, 15.5kV Fuses
Time in Seconds
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 10
AMP-TRAP®
Current in Amperes
E
Time in Seconds
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 11
AMP-TRAP®
A155F1DORO – 65E to 100E and A155F2DORO – 125E to 200E A155F1DORO – 65E to 100E and A155F2DORO – 125E to 200E
Minimum Melting Time – Current Data, 15.5kV Fuses Total Clearing Time – Current Data, 15.5kV Fuses
Time in Seconds
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 12
AMP-TRAP®
Peak Let-Thru Current Data, 15.5kV CS-3 Fuses Peak Let-Thru Current Data, 15.5kV CS-3 Fuses
Maximum Instantaneous Peak Let-Thru Amperes
Available Current in RMS Symmetrical Amperes Available Current in RMS Symmetrical Amperes
A155F1DORO – 65E to 100E
A155F2DORO – 125E to 200E
Features/Benefits
➤ UL Listed for compatibility with UL listed equipment
➤ Bolt-in mounting for direct connection to bus or
terminals
➤ Current Limiting for superior equipment protection
➤ Blown-fuse indicator gives positive identification
of open fuse
➤ Non-venting for silent operation
➤ Metal Embossed Catalog Number and manufacturing
HIGHLIGHTS: Applications: date for lasting identification
➤ E-Rated ➤ Protection for 5.5kV
➤ UL Listed transformers or distri-
➤ Complies with bution systems
Ratings Approvals
ANSI C37.46
➤ A055B ➤ UL Listed to JEEG,
AC: 10E TO 900E “Fuses Over 600 Volts”
5500V max, 63kA I.R. UL File # E143362
Sym.
Definitions:
E-rating
E-rated fuses operate as follows:
Over 100E - must melt in 600 seconds (10 mins.)
on 220 to 264% of E (ampere) rating.
Example - A 750E fuse must melt in 600 seconds with an
applied current of 1650 to 1980 amperes.
General Purpose Current-Limiting Fuse
A general purpose current-limiting power fuse is one that is
capable of interrupting all currents from its rated interrupting
rating down to the current that causes melting of the fusible
element in one hour.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 14
AMP-TRAP®
Figure A
Figure B
A 0 5 5 B 1 D A R 0 - 50 E
E
Ampere Rating
Revision/No.
Special Features
Diameter (D=3”) Figure C
No. of Barrels
Style (B= Bolt-in Mount)
Max. Voltage Rating (055=5.5kV)
Amp-trap Fuse
Current in Amps
Time in Seconds
Current in Amps
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 16
AMP-TRAP®
Current in Amps
E
Time in Seconds
Current in Amps
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E
E 17
17
AMP-TRAP®
22.37
Indicator Flush with Surface
(568) in Untripped Position
11.62
E
(296)
.38
(10)
25.11
(638)
3.00
(76)
1.50
.44 .81 .44 Blown Fuse
(12) x (24) (12) 1.26
(38) 23.73 (32)
(603)
INTERRUPTING
NEW CATALOG OLD CATALOG AMPERE NUMBER OF RATING
NUMBER NUMBER RATING BARRELS RMS SYM.* AMPERES
5.5kV Max. – Bolt-in Style – 23.73” (603mm) Hole Centers – 3” (76.2mm) Barrel Diameter
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E
E 19
19
AMP-TRAP®
Minimum Melting Time – Current Data, 5.5kV Fuses Total Clearing Time – Current Data, 5.5kV Fuses
Time in Seconds
Time in Seconds
Current in Amperes
Current in Amperes
Figure A Figure B
5.5kV Max. – Clip Lock Style – 21.25” (540mm) Clip Centers – 3” (76.2mm) Barrel Diameter
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 22
AMP-TRAP®
Current in Amperes
Current in Amperes
E
Time in Seconds
15.5kV Max. – Clip-Lock Style – 21.25” (540mm) Clip Centers – 3” (76.2mm) Barrel Diameter
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 24
AMP-TRAP®
Current in Amperes
Current in Amperes
E
Time in Seconds Time in Seconds
Features/Benefits
➤ Ferrule mounting for standard clips and
interchangeability with other brands of fuses
➤ 7.2kV series has the same dimensions as 4.8kV fuses,
allowing compact, higher voltage rated designs
➤ 7.2kV bolt-in design is available for improved design
flexiblity
➤ Optional hookeye on 4.8kV for non load-break
isolation by hookstick
HIGHLIGHTS: Applications:
➤ R-Rated ➤ Short circuit
➤ All voltage ratings protection of medium Ratings Approvals
UL Recognized voltage motors and
motor controllers ➤ A240R ➤ UL Recognized
AC: 1R to 36R Component A240R
2750V, 65kA I.R. Sym. @ 2600V,
65kA, Sym.
➤ A480R A480R @ 5080V,
AC: 2R to 36R 50kA, Sym.
5500V, 63kA I.R. Sym. A072 @ 7200V
Definitions: 50kA, Sym.
➤ A072F, A072B
R-Rating: AC: 2R to 24R UL File #E93367
An “R” rated fuse will melt in the range of 15 to 35 seconds
at a value of current equal to 100 times the “R” rating.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 26
AMP-TRAP®
AMP-TRAP®
A240R
A240R MEDIUM VOLTAGE FUSES / R-RATED
MEDIUM VOLTAGE FUSES/R-RATED
2.4kV Ferrule Style
2.4kV Ferrule Style
Indicator Flush with Surface
2 Lb. Force
Indicator (Tripped)
Flush with Surface 0.5 3.312 0.5 3.312 3.312 0.5
(12.7) (84.1) (12.7) (84.1) (84.1) (12.7)
2 Lb. Force (Tripped) 0.5 3.312 0.5 3.312 3.312 0.5
(12.7) (84.1) (12.7) (84.1) (84.1) (12.7)
3
(76)
3
(76)
L L L
L L L
3 3 3 3 3 3
(76) (76)
3 (76)
3 (76)
3 (76)
3 (76)
3
(76) (76) (76) (76) (76) (76)
E
Catalog Numbering System, Ratings, Dimensions, 2.4kV
Catalog Numbering System, Ratings, Dimensions, 2.4kV
CATALOG CONTINUOUS MINIMUM 1 PHASE INTERRUPTING RATING
CATALOG
NUMBER CONTINUOUS
AMPERE MINIMUM
INTERRUPTING 1 PHASE
UL INTERRUPTING
COMPONENTS RATING
MAXIMUM
NUMBER AMPERE
RATING DIM. INTERRUPTING
RATING MAXIMUMTESTED
RECOGNITION
FIG. STANDARD SIZE RATING
at 40˚C DIM.
L RMSRATING
AMPERES RMS Asym RMSTESTED
Sym RMS Asym RMS Sym
A240R
FIG. STANDARD SIZE at 40˚C L RMS AMPERES RMS Asym RMS Sym
A240R1R 1R 35 100
A240R A240R2R 2R 70 170
A240R3R
A240R2R 3R
2R 100
70 250
170
A A240R4R
A240R3R 4R
3R 130
100 340
250
A A240R5R
A240R4R 5R
4R 150
130 420
340
A240R6R 6R 170 10-7/8 500 100kA70kA
65kA 100kA
45kA 65kA
A240R9R
A240R9R 9R
9R 200
200 (276mm)
(276mm) 760
760 @ @ @ @@ @
A24OR12R
A24OR12R 12R
12R 230
230 1000
1000 2750V
2600V 2750V2750V
2600V 2750V
BB A24OR18R
A24OR18R 18R
18R 390
390 1500
1500
A240R24R
A240R24R 24R
24R 450
450 1950
2000
C
C A240R36R
A240R36R 36R**
36R** 650
650 2900
2900
** This
This rating
rating defines
defines the
the fuse’s
fuse’s long-term
long-term thermal
thermal capability
capability per
per ANSI
ANSI C37.
C37. 46-1
46-1 and
and should
should not
not be
be the
the sole
sole factor
factor for
for selecting
selecting aa specific
specific RR rating.
rating.
**
** Not
Not recommended
recommended for for use
use in
in fuse
fuse clips
clips which
which grasp
grasp only
only one
one barrel.
barrel.
E 30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E
E 27
27
AMP-TRAP®
Current in Amperes
Current in Amperes
Time in Seconds Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 28
AMP-TRAP®
1.0
E
(76) (76) (76) (76) (76) (76) (25.4)
* This rating defines the fuse’s long-term thermal capability per ANSI C37 46-1981 and should not be the sole factor for selecting a specific R rating.
** Not recommended for use in fuse clips which grasp only one barrel.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 29
AMP-TRAP®
Current in Amperes
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 30
AMP-TRAP®
3 3 7.62
(194)
15.88 15.88
.25
E
(403) (403)
(6.3)
19.25
(488)
.44 x .91
3 3 3 (11 x 23)
(76) (76) (76)
17.88
(454.2) 1.53
Catalog Numbers, Ratings, Dimensions, 7.2kV (38.8)
Ferrule Type
A072F1DORO-2R 2R 70 190
A072F1DORO-3R 3R 100 225
A072F1DORO-4R 4R 130 330
A A072F1DORO-5R 5R 150 400 80kA 50kA
A072F1DORO-6R 6R 170 500 @ @
A072F1DORO-9R 9R 200 740 7200V 7200V
A072F1DORO-12R 12R 230 955
A072F2DORO-18R 18R 390 1440
B
A072F2DORO-24R 24R 450 1910
Bolt-in Type
A072B1DARO-2R 2R 70 190
A072B1DARO-3R 3R 100 225
A072B1DARO-4R 4R 130 330 80kA 50kA
C A072B1DARO-5R 5R 150 400 @ @
A072B1DARO-6R 6R 170 500 7200V 7200V
A072B1DARO-9R 9R 200 740
A072B1DARO-12R 12R 230 955
A072B2DARO-18R 18R 390 1440
D
A072B2DARO-24R 24R 450 1910
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 31
AMP-TRAP®
A072F and A072B, 7200 Volts A072F2 and A072B, 7200 Volts
Current in Amperes
Current in Amperes
Time in Seconds Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 32
AMP-TRAP®
Features/Benefits
➤ Clip Mount DIN 45: R-rated fuses with North American
E
ANSI characteristics in a standard DIN 442mm size.
Ratings Approvals
➤ A033D1 ➤ UL Recognized
AC: 2R to 19R* Component
3300V max, 65kA I.R. Sym. UL File #E93367
➤ A055D1
AC: 2R to 19R*
5300V max, 65kA I.R. Sym.
➤ A072D1 * Note: Ratings above 19R may
HIGHLIGHTS: Applications: AC: 2R to 19R* be achieved by paralleling fuses.
7200V max, 65kA I.R. Sym. Please consult factory for details.
➤ R-Rated ➤ Short circuit protec-
➤ UL Recognized tion of medium voltage Spring-Reinforced Clip
motors and motor
controllers MR45 & Spring ref.# L096472
Fuse-Holder: SI 24/442 Ref # K209425
In compliance with IEC 282-1, DIN standard 43625.
.78 (20)
Definitions:
2.75 (70)
R-Rating:
An “R” rated fuse will melt in the range of 15 to 35 seconds
at a value of current equal to 100 times the “R” rating.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 33
AMP-TRAP®
Figure A
* 13R, 16R and 19R are not standard ratings defined in ANSI C37.46.
** This rating defines the thermal capability of the fuse per ANSI 37.46 and should not be the sole factor in fuse selection.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 34
AMP-TRAP®
Current in Amps
E
Time in Seconds
Current in Amps
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 35
AMP-TRAP®
Features/Benefits
➤ Current limiting protection for transformers
➤ Ferrule mounting for ease of installation in standard-
clips
➤ Compact size saves valuable mounting space
➤ Fiberglass melamine body provides dimensional
stability in harsh industrial environments
➤ Metal embossed catalog number for lasting
identification
Ratings
➤ A240T ➤ A500T
AC: 1/2E to 5E AC: 1/2E to 5E
2400VAC, 50kA I.R. Sym. 5000VAC, 50kA I.R. Sym.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 36
AMP-TRAP®
A240T1/2E to 5E A480T1/2E to 5E
Melting Time – Current Data - PT Fuses - 2400V Melting Time – Current Data - PT Fuses - 4800V
Time in Seconds E
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 37
AMP-TRAP®
Melting Time – Current Data - PT Fuses - 5000V Melting Time – Current Data - PT Fuses - 7200V
Time in Seconds
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 38
AMP-TRAP®
E
solutions and a large choice of equivalent products
to users.
Applications:
➤ Capacitor Protection
➤ Power Factor Correction Equipment
➤ Harmonic Filtering Equipment
➤ Induction Heating System
➤ High Power Drive
➤ Welders
Features/Benefits Ratings
➤ High interrupting capacity ➤ A100C
AC: 25 to 125 Amps, 1000 V Maximum,
➤ Current limitation 50 kA I.R. Sym.
➤ Blown fuse indication ➤ A150C
AC: 25 to 200 Amps, 1500 V Maximum,
➤ Direct mount 40 kA I.R. Sym.
➤ Clip style mount ➤ A250C
➤ Bus mount AC: 25 to 200 Amps, 2500 V Maximum,
50 kA I.R. Sym.
➤ Non-venting for silent operation
➤ A300C
AC: 50 to 175 Amps, 3000 V Maximum,
50 kA I.R. Sym.
Catalog Numbering System ➤ A430C
AC: 6 to 100 Amps, 4300 V Maximum,
A 250 C 125 - 30 65 kA I.R. Sym.
➤ A550C
AC: 6 to 50 Amps, 5500 V Maximum,
65 kA I.R. Sym.
Voltage Rating ÷ 10 Current Rating
(250 = 2.5kV)
AC Voltage Capacitor Fuse Mounting Configuration
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E
E 39
39
AMP-TRAP®
1/2 - 13 UNC 2A
E
1/2 - 13 U
C B D
INDICATOR A
F D
SIDE TYPE 10 B C
A INDICATOR
SIDE
TYPE 20
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 40
AMP-TRAP®
E
1.5 kV Max Type 40 external female to external female
A150C100-40 100 125 140
A150C110-40 110 125 180
A150C125-40 125 130 230
A150C130-40 130 130 230 40 kA 6.84 4.78 .51 1.75 .75
A150C140-40 140 150 285 @1500V (173.6) (121.4) (13.0) (27.9) (19.1)
RMS Sym
A150C150-40 150 185 315
A150C160-40 160 185 360
A150C175-40 175 225 410
A150C200-40 200 300 560
1.5 kV Max Type 50 screw to bolt (L bracket) A B C D E F
A150C25-50 25 3.2 6.5
A150C50-50 50 13 27
A150C60-50 60 18 38
A150C75-50 75 30 60
A150C90-50 90 35 72
A150C100-50 100 52 105 40 kA 8.11 5.74 .75 1.10 7.49 1.41
A150C110-50 110 58 120 @1500V (206.0) (145.8) (19.1) (27.9) (190.2) (35.8)
RMS Sym
A150C120-50 120 73 150
A150C125-50 125 82 165
A150C130-50 130 90 190
A150C135-50 135 90 190
A150C140-50 140 105 220
A150C150-50 150 120 240
A150C160-50 160 185 480
A150C165-50 165 185 480 8.71 6.51 .70 1.42 8.08 1.25
A150C175-50 175 225 600 (221.1) (165.2) (17.8) (36.0) (205.2) (31.8)
A150C200-50 200 300 800
Ø.53
INDICATOR SIDE
E INDICATOR SIDE 1/2 - 13 UNC 2A
1/2 - 13 UNC 2B E INDICATOR SIDE
D C B F
C C E
D B B 3/8 - 16 UNC 2B
A F D A A
TYPE 30 1/2 - 13 UNC 2B TYPE 40 TYPE 50
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 41
AMP-TRAP®
Total Clearing Time-Current Data 1.0kV Type 30 Total Clearing Time-Current Data 1.5kV Type 40
A100C (Amp Rating) - Type 30 A150C (Amp Rating) - Type 40
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 42
AMP-TRAP®
Minimum Melting Time-Current Data 1.0kV Type 30 Minimum Melting Time-Current Data 1.5kV Type 40
A100C (Amp Rating) - Type 30 A100C (Amp Rating) - Type 40
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 43
AMP-TRAP®
Peak Let-Thru Current Data 1.0kV Type 30 Peak Let-Thru Current Data 1.5kV Type 40
1/2 - 13
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 44
AMP-TRAP®
E
A250C150-10 150 130 460
A200C165-10* 165 150 350 40 kA 7.67 6.92 .75 1.42
A200C175-10* 175 165 440 @2000V (194.8) (175.8 (19.1) (36.0)
RMS Sym
A200C200-10* 200 225 500
2.5 kV Max Type 30 external female to bolt (L bracket)
A250C25-30 25 3 9
A250C50-30 50 12 35
A250C65-30 65 18 60
A250C75-30 75 25 85 50 kA 9.41 6.66 .75 1.10 8.79 1.25
A250C80-30 80 25 85 @2500V (239.0) (169.2) (19.1) (27.9) (223.2) (31.8)
RMS Sym
A250C100-30 100 45 150
A250C110-30 110 60 190
A250C125-30 125 75 240
2.5 kV Max Type 50 screw to bolt (L bracket)
A250C25-50 25 3 9
A250C50-50 50 12 35
A250C65-50 65 18 60
A250C75-50 75 25 85
50 kA 9.11 6.74 .75 1.10 8.49 1.25
A250C80-50 80 25 85
@2500V (231.4) (171.2) (19.1) (27.9) (215.6) (31.8)
A250C100-50 100 45 150 RMS Sym
A250C110-50 110 60 190
A250C125-50 125 75 240
A250C135-50 135 115 395 9.29 6.92 .75 1.42 8.67 1.25
A250C150-50 150 130 460 (236.0) (175.8) (19.1) (36.0) (220.2) (31.8)
A200C165-50* 165 150 350 40 kA 6.92 .75 1.42 8.67 1.25
9.29
A200C175-50* 175 165 440 @2000V (175.8) (19.1) (36.0) (220.2) (31.8)
(236.0)
RMS Sym
A200C200-50* 200 225 500
E
INDICATOR SIDE
D C B F
C B D E
A C B A
D
A F
TYPE 10 TYPE 50
TYPE 30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 45
AMP-TRAP®
A250C (25 to 150) - Type 10 & 50 A200C (165 to 200) - Type 10 & 50
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 46
AMP-TRAP®
A250C (25 to 150) - Type 10 & 50 A250C (165 to 200) - Type 10 & 50
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 47
AMP-TRAP®
1/2 - 13
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 48
AMP-TRAP®
E
A300C150-10 150 105 350
A300C175-10 175 165 530
3.0 kV Max Type 20 screw to bolt (flat bracket)
A300C50-20 50 12 35
A300C60-20 60 18 65 10.59 9.33 .75 1.10 3.00 1.25
A300C75-20 75 26 80 (269.1) (237.0) (19.1) (27.9) (76.2) (31.8)
A300C95-20 95 45 140
A300C100-20 100 45 140
50 kA
A300C115-20 115 60 200
@3000V
A300C125-20 125 75 260 RMS Sym
10.59 9.33 .75 1.42 3.00 1.25
A300C130-20 130 75 260 (269.0) (237.0) (19.1) (36.0) (76.2) (31.8)
A300C150-20 150 105 350
A300C175-20 175 165 530
3.0 kV Max Type 60 bolt (L bracket) to bolt (L bracket)
A300C50-60 50 12 35
A300C60-60 60 18 65 13.27 9.41 .47 1.10 12.02 1.25
A300C75-60 75 26 80 (337.1) (239.0) (11.9) (27.9) (305.2) (31.8)
A300C95-60 95 45 140
A300C100-60 100 45 140 50 kA
A300C115-60 115 60 200 @3000V
125 75 260 RMS Sym
A300C125-60
13.27 9.41 .47 1.42 12.02 1.25
A300C130-60 130 75 260 (337.1) (239.0) (11.9) (36.0) (305.2) (31.8)
A300C150-60 150 105 350
A300C175-60 175 165 530
Ø.53
Ø.56
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 49
AMP-TRAP®
A300C (Amp Rating) - Type 10, 20 & 60 A300C (Amp Rating) - Type 10, 20 & 60
1/2 - 13 UN
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 50
AMP-TRAP®
E
RMS Sym
A430C35-15 35 9 41.4
A430C45-15 45 12 54.6
A430C50-15 50 15 68
A430C65-15 65 29 84
A430C75-15 75 36 100
A430C80-15 80 42 120
A430C90-15 90 58 160
A430C100-15 100 66 180
4.3 kV Max Type 70 tube to tube
A430C6-70 6 0.4 2.49
A430C8-70 8 0.73 4.31
A430C10-70 10 1.14 6.38
A430C12-70 12 1.6 8.64
A430C18-70 18 3 15
A430C20-70 20 4.5 22.1
A430C25-70 25 6.5 31.2 10.00 7.12 1.00 2.00 8.00 .63
65 kA
A430C30-70 30 7.7 36.2 (254.0) (180.8) (25.4) (50.8) (203.2) (15.9)
@ 4300V
A430C35-70 35 9 41.4 RMS Sym
A430C45-70 45 12 54.6
A430C50-70 50 15 68
A430C65-70 65 29 84
A430C75-70 75 36 100
A430C80-70 80 42 120
A430C90-70 9 58 160
A430C100-70 100 66 180
INDICATOR SIDE
1/2 - 13 UNC - 2B 1/2 - 13 UNC - 2A INDICATOR SIDE
F
1.00
C C
F B F B D
E C E
A D
A
TYPE 15 TYPE 70
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 51
AMP-TRAP®
A430C (Amp Rating) - Type 15 & 70 A430C (Amp Rating) - Type 15 & 70
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 52
AMP-TRAP®
E
A550C35-15 35 9 41.4
A550C40-15 40 12 54.6
A550C50-15 50 15 68
A550C65-15 65 35 156 50 kA @ 5500V
A550C75-15 75 43 186 RMS Sym
5.5 kV Max Type 70 tube to tube
A550C6-70 6 0.4 2.49
A550C8-70 8 0.73 4.31
A550C10-70 10 1.14 6.38
A550C12-70 12 1.6 8.64
A550C18-70 18 3 15
65 kA @ 5500V 10.00 7.12 1.00 2.00 8.00 .63
A550C20-70 20 4.5 22.1
RMS Sym (254.0) (180.8) (25.4) (50.8) (203.2) (15.9)
A550C25-70 25 6.5 31.2
A550C30-70 30 7.7 36.2
A550C35-70 35 9 41.4
A550C40-70 40 12 54.6
A550C50-70 50 15 68
A550C65-70 65 35 156 50 kA @ 5500V
A550C75-70 75 43 186 RMS Sym
INDICATOR
1/2 - 13 UNC - 2B 1/2 - 13 UNC - 2A SIDE
1.00 F
F F C C
B
E C B D
A D
E
TYPE 15 INDICATOR A
SIDE
TYPE 70
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 53
AMP-TRAP®
A550C (Amp Rating) - Type 15 & 70 A550C (Amp Rating) - Type 15 & 70
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
E 54
International Fuses
A world of circuit protection
solutions — in your backyard.
gF gI-gG gI-gG aM aM
Full Range Full Range Full Range Short Circuit
Short Circuit Protection
Protection Protection Protection Protection
➤ 7 physical sizes ➤ 4 physical sizes Fuse-links with ➤ 4 physical sizes Fuse-links with
from 6.3 x 23m to from 8 x 31mm Striker from 8 x 31mm Striker
10.3 x 38 mm to 22 x 58 mm to 22 x 58mm
➤ 2 sizes- ➤ 2 sizes -
➤ 250 and 400 Volt ➤ 400, 500 and 690 ➤ 400, 500 and 690 14 x 51mm
ratings - Volt ratings - 0.5A 14 x 51mm
and 22 x 58mm Volt ratings - . and 22 x 58mm
0.5A through 32A through 125A 16A through 125A
➤ 400, 500 and ➤ 400, 500 and
➤ Most ratings available ➤ Most ratings available ➤ Most ratings 690 Volt ratings -
with indicator with indicator 690 Volt ratings -
4A through 125A available with 2A through 125A
➤ Meet IEC, NFC, ➤ Meet IEC, NFC and indicator
➤ All ratings include ➤ All ratings include
UNE and British UNE standards ➤ Meet IEC, NFC and striker
standards striker
➤ Approved by UNE standards
➤ Meet IEC, NFC and ➤ Meet IEC, NFC and
Lloyds Register of ➤ Approved by Lloyds UNE standards
Shipping and UNE standards
Register of Shipping
Bureau Veritas ➤ Approved by Lloyds and Bureau Veritas ➤ Approved by Lloyds
Register of Shipping Register of Shipping
and Bureau Veritas and Bureau Veritas
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F
EURO/IEC Fuses & Accessories
gF CYLINDRICAL FUSE-LINKS
Catalog Numbers, Ratings – gF (Optional Blown-Fuse Indicator)
F
12 10633-G 12633-G
16 10635-G 12635-G
20 10637-G 12637-G
25 10639-G 12639-G
10839-G
16 400V 10835-G 12835-G 20,000 10/100
10.3 x 31.5 20 10837-G 12837-G
25 10839-G 12839-G
2 400V 11013-G 13013-G 20,000 10/100
4 11019-G 13019-G
6 11023-G 13023-G
11035-G 8.5 x 36 10 11031-G 13031-G
16 11035-G 13035-G
20 11037-G 13037-G
25 11039-G 13039-G
32 11043-G 13043-G
10.3 x 38 25 400V 11239-G 13239-G 20,000 10/100
32 11243-G 13243-G
11243-G
1 Ceramic body
2 Sand
3 Indicator contact
4 Lower contact
5 Contact ring
6 Melting element Dimensions
7 Indicator FUSE SIZE Blown-Fuse Indicator
(mm x mm) A B C
6.3 X 23 6.3 23 5
8.5 X 23 8.5 23 5
10.3 x 25.8 10.3 25.8 6.3
8.5 x 31.5 8.5 31.5 6.3
10.3 x 31.5 10.3 31.5 10
8.5 x 36 8.5 36 6.3
10.3 x 38 10.3 38 10 BEFORE AFTER
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F
EURO/IEC Fuses & Accessories
gF CYLINDRICAL FUSE-LINKS
Current in Amperes
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F
EURO/IEC Fuses & Accessories
F
32 400V 16043-G 16243-G
1 690V 17011-G - 80,000
2 17013-G 17213-G
4 17019-G 17219-G
6 17023-G 17223-G
8 17027-G 17227-G
10 17031-G 17231-G
14 X 51 12 17033-G 17233-G 10/50
17039-G 16 17035-G 17235-G
20 17037-G 17237-G
25 17039-G 17239-G
32 500V 17043-G 17243-G 120,000
40 17047-G 17247-G
50 400V 17051-G 17251-G
Blown-Fuse Indicator
Dimensions
FUSE SIZE A B C
8 x 31 8.5 31.5 6.3
10 x 38 10.3 38 10.5
14 x 51 14.3 51 13.8
22 x 58 22.2 58 16.2
BEFORE AFTER
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F
EURO/IEC Fuses & Accessories
Dimensions
FUSE SIZE A B C D E
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F
EURO/IEC Fuses & Accessories
Temperature
Temperature rise reached by gI-gG fuse-links at In, measured on their upper contact.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F
EURO/IEC Fuses & Accessories
aM CYLINDRICAL FUSE-LINKS
Catalog Numbers, Ratings – aM (Optional Blown-Fuse Indicator)
SIZE RATED In RATED CATALOG NUMBER INTERRUPTING STANDARD
(mm x mm) CURRENT (A) VOLTAGE w/o Indicator w/Indicator RATING (A) PACK/CTN.
1 400V 15511-G - 20,000
2 15513-G -
4 15519-G -
8 x 31 6 15523-G - 10/100
15519-G
8 15527-G -
10 15531-G -
0.16 500V 16503-G - 120,000
0.25 16507-G -
0.5 16509-G -
1 16511-G 16711-G
16535-G 2 16513-G 16713-G
4 16519-G 16719-G
6 16523-G 16723-G
10 X 38 8 16527-G 16727-G 10/100
10 16531-G 16731-G
12 16533-G 16733-G
16 16535-G 16735-G
20 16537-G 16737-G
25 400V 16539-G 16739-G
32 16543-G
0.25 690V 17507-G - 80,000
0.5 17509-G -
1 17511-G 17711-G
2 17513-G 17713-G
4 17519-G 17719-G
6 17523-G 17723-G
17535-G 8 17527-G 17727-G
10 17531-G 17731-G
14 X 51 12 17533-G 17733-G 10/50
16 17535-G 17735-G
20 17537-G 17737-G
25 17539-G 17739-G
32 500V 17543-G 17743-G 120,000
40 17547-G 17747-G
45 17549-G 17749-G
50 400V 17551-G 17751-G
4 690V 18519-G 18719-G 80,000
6 18523-G 18723-G
8 18527-G 18727-G
10 18531-G 18731-G
12 18533-G 18733-G
16 18535-G 18735-G
22 x 58 20 18537-G 18737-G 10/50
25 18539-G 18739-G
18555-G 32 18543-G 18743-G
40 18547-G 18747-G
50 18551-G 18751-G
63 18555-G 18755-G
80 18559-G 18759-G
100 500V 18563-G 18763-G 120,000
Blown-Fuse Indicator 125 400V 18565-G 18765-G
Dimensions
FUSE SIZE A B C
8 x 31 8.5 31.5 6.3
10 x 38 10.3 38 10.5
14 x 51 14.3 51 13.8
BEFORE AFTER 22 x 58 22.2 58 16.2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F
EURO/IEC Fuses & Accessories
aM CYLINDRICAL FUSE-LINKS
Catalog Numbers, Ratings – aM with Striker
F
16 18935-G
22 X 58 20 18937-G 10/50
25 18939-G
32 18943-G
40 18947-G
BEFORE AFTER
50 18951-G
63 18955-G
80 500V 18959-G 120,000
100 400V 18963-G
125 18965-G
Dimensions
FUSE SIZE A B C D E
Melting Time - Current Data – 1-125 Amperes Peak Let-Thru Current Data – 1-125 Amperes
Maximum Instantaneous Peak Let-Thru Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F
EURO/IEC Fuses & Accessories
aM CYLINDRICAL FUSE-LINKS
Power Loss (Watts) at Rated Current In
I2t Characteristics – Discrimination
RATED In SIZE
CURRENT
(A) 10 x 38 14 x 51 22 x 58
1 0.1 W
2 0.2 W 0.3 W
4 0.3 W 0.4 W 0.5 W
6 0.4 W 0.5 W 0.6 W
8 0.5 W 0.6 W 0.8 W
10 0.6 W 0.8 W 1.0 W
I2t (Ampere2 Seconds)
IEC 269-2 10 x 38 14 x 51 22 x 58
NFC 63210 16 A 50 A 100 A
UNE 21103 1.2 W 3W 7W
Fuse-link In (A)
These values are much lower than those allowed by the standards.
_ _ _ _ _690V
_ _ _ _ _ 500V Operating I2t
_ _ _ _ _ 400V
Temperature
Temperature rise reached by aM fuse-links at In, measured on their upper contact.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 10
EURO/IEC Fuses & Accessories
Ratings
➤ AC: 400 Volts
Approvals
➤ Meet IEC, VDE and
F
AC,100kA interrupting UNE Standards:
rating IEC 269-3, 3A
VDE 0636
UNE 21103
1 Ceramic body
2 Sand
3 Upper contact
4 Contact top
5 Lower contact
6 Melting element
26035-G 26055-G
7 Indicator
2 26013-G PINK
4 26019-G BROWN
DO1 6 26023-G GREEN E 14 10/50
10 26031-G RED
16 26035-G GRAY
20 26037-G BLUE
25 26039-G YELLOW Dimensions
DO2 35 26045-G BLACK E 18 5/25
50 26051-G WHITE
DO1 DO2 DO3
63 26055-G COPPER
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 11
EURO/IEC Fuses & Accessories
A 12 16.5 27
Adapter Rings
2 26313-G - -
4 26319-G - -
DO1 6 26323-G - - 50
10 26331-G - - 26331-G
Protecting Rings
DO1-DO2 - 26340-G - - 50
26340-G
CATALOG STANDARD
SIZE POLES NUMBER PACK
DO1-DO2 1 26450-G 50
DO1-DO2 3 26451-G 10
DO3 1 26452-G 20
26450-G Dimensions
DO1-2 DO1-2 DO3
unipolar tripolar unipolar
A 27 81 45
Adapter Spring – For Screw Cap B 60 60 60
C 23 23 -
DO2 - 26550-G 25 D 3 3 5
E 45.5 45.5 45.5
DO3 - 26551-G 25
26550-G F 18 18 18
- - 26600-G 1
26600-G
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 12
EURO/IEC Fuses & Accessories
DO1 16 4 26802-G 1 1 20
SCREW DO2 63 25 26804-G 2 2 20
DO2 63 25 26806-G 3 2 20
DO3 100 50 26810-G 3 2 10
DO1 16 4 26912-G 1 1 20
DIN RAIL DO2 63 25 26914-G 2 2 20 26804-G 26916-G
DO2 63 25 26916-G 3 2 20
DO3 100 50 26920-G 3 2 10 Dimensions
* Connection types -
DO1 DO2 DO3
A 26 26.5 44
B 55 60 86
C 36 36 50
D 3 3 4.5
E 20 20 32
F 22 22 32
G 64 64 74
H 45 45 53
F
I 39 39.5 44
J 8 8 7.5
K 34 34 60
Single Pole Fuse Bases - For Assembly on Copper Bus Bars
MOUNTING RATED In MAXIMUM CATALOG CONNECTIONS* STD.
METHOD SIZE CURRENT (A) WIRE SIZE NUMBER IN OUT PACK
BOLTED DO2 63 15mm x 3mm 27024-G - 2 20
20mm x 5mm
27034-G 27024-G
* Connection types
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 13
EURO/IEC Fuses & Accessories
Dimensions
DO1 DO2
A 80.5 80.5
B 55 60
C 36 36
D 4 4
F 74 74
G 64 64
H 56 56
I 38 39.5
J 8 8
K 60 60
Watts loss and temperature rise measured in point (*). Values obtained in both cases by Ferraz fuses are extremely low.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 14
EURO/IEC Fuses & Accessories
Current in Amperes
F
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 15
EURO/IEC Fuses & Accessories
Ratings Approvals
➤ AC: 500 Volts AC, ➤ Meet IEC, VDE and
75kA interrupting UNE Standards:
rating IEC 269-3, 3A
VDE 0636
➤ gL-gG Performance UNE 21103
Characterisitic ➤ Approved by Lloyds
Register of Shipping
and Bureau Veritas
D FUSES – Catalog Numbers, Ratings
RATED In CAP CATALOG STANDARD
SIZE CURRENT (A) THREAD NUMBER PACK/CTN
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 16
EURO/IEC Fuses & Accessories
Gauge Ring
Screw Caps
RATED In CAP CATALOG STANDARD Dimensions
SIZE CURRENT (A) THREAD NUMBER PACK
KII KIII KIV
KII 25 E 27 28039-G 50
KIII 63 E 33 28055-G 50
A 38 48 63
KIV 100 R 1-1/4” 28063-G 24 28063-G
Adapter Rings
DIII - DII 28100-G 24
28100-G
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 17
EURO/IEC Fuses & Accessories
28202-G 28312-G
A 54 54 75 55 55
B 80 83 105 82 84
DIN RAIL EZPII 25 E 27 28312-G 24 C 36 46 58 90 94
EZPIII 63 E 33 28314-G 24 D 20 21 46 65 67
E 47 56 77 46 55
F 4.5 4.5 8 - -
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 18
EURO/IEC Fuses & Accessories
10 min.
5 min.
1 min.
10 s
Time in Seconds
1s
100 ms
F
10 ms
1 ms
Current in Amperes
100A
80A
63A
50A
40A
35A
32A
25A
20A
16A
10A
5A
4A
2A
_ _ _ _ _ 500V
_ _ _ _ _ 380V Operating I2t
_ _ _ _ _ 220V
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 20
EURO/IEC Fuses & Accessories
gG gG aM aM
Full Range Full Range short circuit Short Circuit
Protection Protection Protection Protection
➤ Sizes 000, 00, 0, 1, 2, Fuse-link with Striker
➤ Sizes 000, 00, 0, 1, Fuse-link with Striker
3, 4, 4a ➤ Sizes 0, 1, 2, 3 2, 3 ➤ Sizes 0, 1, 2, 3
➤ 500 and 690 ➤ 500 and 690 Volt ➤ 400, 500 and 690 ➤ 500 and 690
Volt ratings - ratings - 32A through Volt ratings - 2A Volt ratings -
2A through 800A 630A through 800A 32A through 630A
➤ All ratings include ➤ All ratings include ➤ All ratings include ➤ All ratings include
indicator striker indicator striker
➤ All equipped for ➤ All equipped for ➤ Certification
microswitch mounting microswitch mounting DIN 57636
VDE 60269
NFC 63210, 63211
0% Lead IEC 269-1, 2, 2A
UNE 21103
0% Cadmium ➤ Approved by Lloyds
Register of Shipping
and Bureau Veritas
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 21
EURO/IEC Fuses & Accessories
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 22
EURO/IEC Fuses & Accessories
Dimensions
Rated current
Size a1 a2 a3 a4 b c1 e1 e2 e4 h
in A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 23
EURO/IEC Fuses & Accessories
Dimensions
0 1 2 3
L 59 65 72.5 86
M 60 61 61 61
N 3 3 3 3
O 41.5 45 - -
P 47 52 60 60
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 24
EURO/IEC Fuses & Accessories
Current in Amperes
Striker
Peak Let-Thru Current Data – 6-800 Amperes
Maximum Instantaneous Peak Let-Thru Amperes
BEFORE AFTER
RATED In 00 0 1 2 3 4
CURRENT (A) 100A 160A 250A 400A 630A 1000A
VDE 0660 (500V)
IEC 269-2-1 (690V) 12.0 W 25 W 32 W 45 W 60 W 90 W
UNE 21103 (500V)
NFC 63210 (500V)
VDE 0636 (690V) 10.0 W - 23 W 34 W 48 W 70 W
VDE 0636 (500V) 7.5 W 16 W 23 W 34 W 48 W 110 W
IEC 269 (500V) 7.5 W 16 W 23 W 34 W 48 W 90 W
UNESA (500V) - 17 W 26 W 32 W 48 W -
WDE W (500V) 7.5 W 16 W 21 W 32 W 42 W -
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 26
EURO/IEC Fuses & Accessories
_ _ _ _ _ 690V
_ _ _ _ _ 500V Operating I2t
_ _ _ _ _ 400V
_ _ _ _ _ Pre-arcing I2t
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 27
EURO/IEC Fuses & Accessories
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 28
EURO/IEC Fuses & Accessories
Dimensions
Rated current
Size a1 a2 a3 a4 b c1 e1 e2 e4 h
in A
NH 690 V aM with voltage-conducting grip lug
SIZE 000 2-35A 79 53,8 45 49 15 35,8 40 20 6 47,8
SIZE 00 40-100A 79 53,8 45 49 15 35,8 48 30 6 47,8
SIZE 1 16-160A 135 75 64 68 20 40 44 30 6 52
SIZE 1 200A 135 75 64 68 20 40 47 39 6 52
SIZE 2 35-100A 150 75 64 68 26 48 44 30 6 60
SIZE 2 125-315A 150 75 64 68 26 60 47 39 6 72
SIZE 3 250/300A 150 75 64 68 26 60 47 39 6 72
SIZE 3 315-425A 150 75 64 68 33 60 58 51 6 72
SIZE 3 500A 150 75 64 68 33 60 70 64 6 72
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 29
EURO/IEC Fuses & Accessories
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 30
EURO/IEC Fuses & Accessories
F
Current in Amperes
_ _ _ _ _ 690V
_ _ _ _ _ 500V Operating I2t
_ _ _ _ _ 440V
I2t (Ampere2 Seconds)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 32
CLASS C CANADIAN FUSES
Class c fuses
Ferraz Shawmut Class C fuses have British standard
(BS88) dimensions and are exact replacements for
the British fuses and older HRCII-C fuses. Class
C fuses are not dimensionally or electrically
interchangeable with other North American fuses.
They feature ceramic bodies and bolt-in mounting.
They are for short-circuit protection only, in motor
controllers, for example, where overload protection
is provided by an overload relay.
Ratings Approvals
➤ AC: 2 to 600A ➤ CSA Certified
600VAC, 200kA I.R. HRCII-MISC
F
IEC269-2-1
➤ DC: 460V DC, 40kA I.R.
FES (2-60),
HIGHLIGHTS: APPLICATIONS: FESF (250-400),
FESC (250-400),
➤ BS88 Dimensions ➤ Short circuit and 450V DC, 40kA I.R.
➤ Fast-Acting back-up protection of FESC (450-600)
350V DC, 40kA I.R.
motor controllers and
FES (80-100),
components FESC (80-200)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 33
CLASS C CANADIAN FUSES
I2t Data at 200kA
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 34
CLASS C CANADIAN FUSES
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 35
CLASS CA & CB CN, CNS/CANADIAN FUSES
Ratings Approvals
➤ AC: 1 to 30A ➤ CSA Certified
600VAC, 200kA I.R. to Standard C22.2,
No. 248.3
Class CA – Catalog Numbers & Dimensions Class CB – Catalog Numbers & Dimensions
AMPERE CATALOG DIMENSIONS in mm AMPERE CATALOG DIMENSIONS in mm
RATING NUMBER A D E F H K L M RATING NUMBER A D E F K M
1 C1N 1 CNS1
3 C3N 3 CNS3
6 C6N 62 13.9 0.8 11.1 4.7 36.5 44.5 14.3 6 CNS6
10 C10N 10 CNS10 62 14.5 0.8 11.0 35.5 11.65
15 C15N 15 CNS15
20 C20N 20 CNS20
25 CNS25
30 CNS30
Class CA & CB – I2t at 200kA
Call for technical information
CATALOG
2 2
I t (A Secs.)
NUMBER PRE-ARC @ 460V @ 600V
C3N, CNS3 0.8 1.5 2.2
C6N, CNS6 7.6 15 21
C10N, CNS10 40 76 110
C15N, CNS15 130 280 370
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 36
NIT & NS HRCII/CANADIAN FUSES
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 37
NIT & NS HRCII/CANADIAN FUSES
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 38
CLASS H NRN/NRS/CANADIAN FUSES
F
(181) (41.4) (4.76) (28.7) (35.1)
225-400 8.63 2.13 0.25 1.63 1.88
(219) (54.1) (6.35) (41.4) (47.8)
450-600 10.4 2.63 0.25 2.00 2.25
(264) (66.8) (6.35) (50.8) (57.2)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 39
CLASS H CRN/CRS/CANADIAN FUSES
Ratings Approvals
➤ CRN: 15 to 600A ➤ CSA Certified Type “D”
250VAC, 10kA I.R.
➤ CRS: 15 to 600A
600VAC, 10kA I.R.
250V CRN Fuses – Dimensions
250V Fuse Ampere Ratings, Catalog Numbers* 600V Fuse Ampere Ratings, Catalog Numbers**
AMPS CATALOG NO. AMPS CATALOG NO. AMPS CATALOG NO. AMPS CATALOG NO. AMPS CATALOG NO. AMPS CATALOG NO.
15 CRN15 60 CRN60 200 CRN200 15 CRS15 60 CRS60 200 CRS200
17-1/2 CRN17-1/2 70 CRN70 225 CRN225 17-1/2 CRS17-1/2 70 CRS70 225 CRS225
20 CRN20 80 CRN80 250 CRN250 20 CRS20 80 CRS80 250 CRS250
25 CRN25 90 CRN90 300 CRN300 25 CRS25 90 CRS90 300 CRS300
30 CRN30 100 CRN100 350 CRN350 30 CRS30 100 CRS100 350 CRS350
35 CRN35 110 CRN110 400 CRN400 35 CRS35 110 CRS110 400 CRS400
40 CRN40 125 CRN125 450 CRN450 40 CRS40 125 CRS125 450 CRS450
45 CRN45 150 CRN150 500 CRN500 45 CRS45 150 CRS150 500 CRS500
50 CRN50 175 CRN175 600 CRN600 50 CRS50 175 CRS175 600 CRS600
* For 1/10 - 12A ratings use Tri-onic TR-R. ** For 1/10 - 12 ratings use Tri-onic TRS-R.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
F 40
Special Purpose
Products
A world of circuit protection
solutions under one roof.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SURGE TRAP® DIN RAIL TVSS SURGE SUPPRESSION
APPLICATION:
➤ Transient Voltage Surge Suppressors
➤ AC/DC Distribution
➤ High Voltage Power Supplies
➤ Telecom
➤ Motor Control Systems
➤ PLC Applications
➤ Power Transfer Equipment
Features/Benefits
Ratings Approvals ➤ High Energy Capacity
➤ Din-Rail Mountable (35mm)
➤ MCOV 150 to 550 ➤ UL 1449 file E210793
Second Edition 2005 ➤ IP20 - Fingersafe
➤ 50kA 8/20us Capacity Component Recognition
per mode ➤ Built in Visual/Remote Indication
➤ RoHs Compliant
➤ Built in Thermal Protection
Dimensions ➤ 100kA Interrupting Rating
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G
SURGE TRAP® DIN RAIL TVSS SURGE SUPPRESSION
Surge Trap Selection guide:
STEP 1: Select electrical voltage configuration from first column
STEP 2: Select proper modes of protection from third column
STEP 3: Select corresponding catalog number from fourth column
STEP 4: Add an M to the catalog number if you require remote indication
G
A B C D E
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G
VSP MOV PROTECTOR SURGE SUPPRESSION FUSES
Features/Benefits
➤ VSP fuses rated 600VAC, 200kA I.R.
➤ Surge Ratings of 5-100kA 8 x 20 µSec Capacity
➤ Designed to help meet UL1449 Second Edition Requirements
➤ Various Mounting Configurations
Ferrules, Blade, Bolt-In, pc board mount
Ratings Approvals
Catalog voltage 8x20 µSEC Melting l2t CLEARING l2t IPEAK @ 100KA,
Number rating (AC) surge Rating (A s) (A s) 60 Hz (A)
APPLICATION:
2 2
(connection suffix)
VSP5-2,-R,-H,-S 600V 5,000 341 936 3,652
➤ Protection of TVSS VSP10-2,-R,-H,-S 600V 10,000 1,541 3,744 5,794
Devices VSP15-2,-R,-H,-S 600V 15,000 3,072 8,424 7,591
VSP20-2,-R,-H,-S 600V 20,000 4,992 14,400 9,194
➤ Coordination with other VSP30, -2 600V 30,000 12,507 33,696 12,044
protection devices VSP40, -2 600V 40,000 19,543 59,904 14,588
VSP50, -2 600V 50,000 32,020 93,600 16,925
VSP60, -2 600V 60,000 42,808 134,784 19,110
VSP70, -2 600V 70,000 61,152 183,456 21,176
VSP80, -2 600V 80,000 79,872 239,616 23,146
VSP90, -2 600V 90,000 99,000 303,264 25,034
VSP100, -2 480V 100,000 121,500 374,400 26,854
VSP100-XL 600V 100,000 121,500 374,400 26,854
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G
VSP MOV PROTECTOR SURGE SUPPRESSION FUSES
VSP (5-20)-2,R,H,S VSP (30-100)-2
-2
.12
(3.0)
1.53 .08 .334
(1.8) .816
.12
-R (30.9)
.02 (3.0)
(.4) .28
.04 (7.2)
(1.0)
.04 10.5
(1.0) MAX. REF
.080
.483
MOUNTING HOLE DETAIL FOR .062(1.6) NOMINAL 2.250
CIRCUIT BOARD .500 3.040
THICKNESS 3.592
VSP100-XL
DOUBLE HOLE MOUNT (ROUND HOLES)
.50
(12.6)
.38
(9.7)
G
.28 .75
(7.1) (19.0)
-H .05
(1.4)
1.53±.01 .15 .12
.03 .03 (3.8) .05 2.62 (3.0)
(1.3) (30.9) (.8) (1.2) .20 (66.5)
4 PLCS (5.1) 1.12
.41 3.62 .50
.20 (10.5) (91.9) (12.7) (28.4)
(5.1) 4.62
MAX REF
FOR .062 (1.6) NOMINAL (117.3)
MOUNTING HOLE DETAIL CIRCUIT BOARD THICKNESS
.46
(11.7)
.03
(.8) MAXIMUM RECOMMENDED
SCREW SIZE #6 (3.5mm)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G
SOCOMEC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G
SOCOMEC
SS200
ss200-4
G
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G
SOCOMEC
HADSS200
O - OFF
3.15
80
90°
2.56
65
I - ON 4.73 0.67
120 17
o -OFF
50
2"
2.78
70.5
11 4" 90°
ø 31
-ON
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 10
AMP-TRAP®
G
1/0 CP1/0C1 -
2/0 CP2/0C1 -
➤ Fiberglass bodies for dimensional stability in harsh 4/0 CP4/0C1 CP4/0A1
environments 250kcmil CP250C1 CP250A1
Cable to
1 350kcmil CP350C1 CP350A1
➤ Catalog number stamped into terminal for permanent Cable
400kcmil CP400C1 CP400A1
identification 500kcmil CP500C1 CP500A1
600kcmil CP600C1 CP600A1
➤ Crimp terminals for aluminum cable include oxide 750kcmil CP750C1 CP750A1
inhibitor 1000kcmil CP1000C1 -
Type C3 – Dimensions
CP2C3 #2 8.87 (225) 1.44 (37) 1.12 (28) 1.75 (44) 3.50 (88.9) 3.62 (92) .96 (24) .31 (7.9) .42 (11)
CP1/0C3 1/0 8.87 (225) 1.44 (37) 1.12 (28) 1.75 (44) 3.50 (88.9) 3.62 (92) .96 (24) .39 (9.9) .52 (13)
CP2/0C3 2/0 8.87 (225) 1.44 (37) 1.12 (28) 1.75 (44) 3.50 (88.9) 3.62 (92) .96 (24) .44 (11) .56 (14)
CP4/0C3 4/0 8.87 (225) 1.44 (37) 1.12 (28) 1.75 (44) 3.50 (88.9) 3.62 (92) .96 (24) .55 (14) .68 (17)
CP250C3 250kcmil 9.00 (229) 1.44 (37) 1.12 (28) 1.88 (48) 3.50 (88.9) 3.62 (92) .96 (24) .62 (16) .75 (19)
CP350C3 350kcmil 9.12 (232) 1.62 (41) 1.12 (28) 2.00 (51) 3.50 (88.9) 3.62 (92) .96 (24) .71 (18) .88 (22)
CP400C3 400kcmil 9.12 (232) 1.62 (41) 1.12 (28) 2.00 (51) 3.50 (88.9) 3.62 (92) .96 (24) .75 (19) .88 (22)
CP500C3 500kcmil 10 .00 (254) 1.88 (48) 1.62 (41) 2.88 (73) 3.50 (88.9) 3.62 (92) 1.19 (30) .85 (22) 1.05 (27)
CP600C3 600kcmil 10 .13 (257) 2.50 (64) 2.00 (51) 2.88 (73) 3.50 (88.9) 3.75 (95) 1.31 (33) .94 (24) 1.07 (27)
CP750C3 750kcmil 10.13 (257) 2.50 (64) 2.00 (51) 2.88 (73) 3.50 (88.9) 3.75 (95) 1.31 (33) 1.06 (27) 1.32 (34)
CP1000C3 1000kcmil 10.63 (270) 3.00 (76) 2.00 (51) 3.13 (79) 3.75 (95) 3.75 (95) 1.56 (40) 1.16 (29) 1.50 (38)
Type C5 – Dimensions
CATALOG CABLE* DIMENSIONS - INCHES (mm)
NUMBER SIZE A B D J L M
CP4/0C5 4/0 10.37 1.44 1.12 3.62 .96 1.12
(263) (37) (28) (92) (24) (28)
CP250C5 250kcmil 10.37 1.44 1.12 3.62 .96 1.12
(263) (37) (28) (92) (24) (28) TYPE 1
CP350C5 350kcmil 10.37 1.62 1.12 3.62 .96 1.12
(263) (41) (28) (92) (24) (28)
CP400C5 400kcmil 10.37 1.62 1.12 3.62 .96 1.12 TYPE 3
(263) (41) (28) (92) (24) (28)
CP500C5 500kcmil 10.37 1.88 1.62 3.62 1.19 1.50 TYPE 5
(263) (48) (41) (92) (30) (38)
CP600C5 600kcmil 10.50 2.50 2.00 3.75 1.31 2.00
(267) (64) (51) (95) (33) (51) TYPE 6
CP750C5 750kcmil 10.50 2.50 2.00 3.75 1.31 2.00
(267) (64) (51) (95) (33) (51)
TYPE 8
* kcmilEngineering,
Courtesy of Steven = MCM Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 12
AMP-TRAP®
Type C6 – Dimensions
CP4/0C6 4/0 7.87 1.44 1.75 3.62 2.50 .55 .52 .68
(200) (37) (44) (92) (64) (14) (13) (17)
CP250C6 250kcmil 8.00 1.44 1.88 3.62 2.50 .62 .58 .75
(203) (37) (48) (92) (64) (16) (14) (19)
CP350C6 350kcmil 8.12 1.62 2.00 3.62 2.50 .71 .68 .88
(206) (41) (51) (92) (64) (18) (17) (22)
CP500C6 500kcmil 9 .38 1.88 2.88 3.62 2.88 .85 .81 1.05
(238) (48) (73) (92) (73) (22) (21) (27)
CP750C6 750kcmil 9.51 2.50 2.88 3.75 2.88 1.06 1.00 1.32
(427) (64) (73) (95) (73) (27) (25) (34)
Type C8 – Dimensions
* kcmil = MCM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 13
AMP-TRAP®
Type A1 – Dimensions
Type A3 – Dimensions
CP4/0A3 4/0 12.25 1.44 1.12 3.62 .96 .55 2.50 .85
(311) (37) (28) (92) (24) (14) (64) (22)
CP250A3 250kcmil 12.25 1.44 1.12 3.62 .96 .59 2.50 .94
(311) (37) (28) (92) (24) (15) (64) (24)
CP350A3 350kcmil 12.25 1.62 1.12 3.62 .96 .71 2.50 1.13
(311) (41) (28) (92) (24) (18) (64) (29)
CP500A3 500kcmil 13.00 1.88 1.62 3.62 1.19 .85 2.88 1.33
(330) (48) (41) (92) (30) (22) (73) (34)
CP750A3 750kcmil 13.12 2.50 2.00 3.75 1.31 1.06 2.88 1.62
(333) (64) (51) (95) (33) (27) (73) (41)
Type A6 – Dimensions
Type C1, Copper Cable – Dimensions Type C3, Copper Cable – Dimensions
CABLE A CATALOG NO. CABLE PROTECTOR CABLE A CATALOG NO. CABLE PROTECTOR
SIZE INCHES (mm) WITH HEAT SHRINKABLE TUBING SIZE INCHES (mm) WITH HEAT SHRINKABLE TUBING
4/0 7.12 (180) CP4/0C1-HS 4/0 8.87 (225) CP4/0C3-HS
250kcmil 7.38 (188) CP250C1-HS 250kcmil 9.00 (229) CP250C3-HS
350kcmil 7.62 (194) CP350C1-HS 350kcmil 9.12 (232) CP350C3-HS
500kcmil 9.38 (238) CP500C1-HS 500kcmil 10.00 (254) CP500C3-HS
750kcmil 9.51 (242) CP750C1-HS 750kcmil 10.13 (257) CP750C3-HS
Type C5, Copper Cable – Dimensions Type C6, Copper Cable – Dimensions G
CABLE A CATALOG NO. CABLE PROTECTOR CABLE A CATALOG NO. CABLE PROTECTOR
SIZE INCHES (mm) WITH HEAT SHRINKABLE TUBING SIZE INCHES (mm) WITH HEAT SHRINKABLE TUBING
* Transparent heat shrinkable tubing is supplied separately with -HS Catalog No. Maximum curing conditions: 5 seconds at 450˚F.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 15
AMP-TRAP®
Type A1, Copper Cable – Dimensions Type A3, Copper Cable – Dimensions
CABLE A CATALOG NO. CABLE PROTECTOR
SIZE INCHES (mm) WITH HEAT SHRINKABLE TUBING CABLE A CATALOG NO. CABLE PROTECTOR
SIZE INCHES (mm) WITH HEAT SHRINKABLE TUBING
4/0 13.88 (353) CP4/0A1-HS
4/0 12.25 (311) CP4/0A3-HS
250kcmil 13.88 (353) CP250A1-HS 250kcmil 12.25 (311) CP250A3-HS
350kcmil 13.88 (353) CP350A1-HS 350kcmil 12.25 (311) CP350A3-HS
500kcmil 15.38 (391) CP500A1-HS 500kcmil 13.00 (330) CP500A3-HS
750kcmil 15.50 (394) CP750A1-HS 750kcmil 13.12 (333) CP750A3-HS
Type A6, Copper Cable – Dimensions Type 5 – Use Copper Cable Protectors Type C5
CABLE A CATALOG NO. CABLE PROTECTOR Type 8 – Use Copper Cable Protectors Type C8
SIZE INCHES (mm) WITH HEAT SHRINKABLE TUBING
4/0 11.25 (286) CP4/0A6-HS
250kcmil 11.25 (286) CP250A6-HS
350kcmil 11.25 (286) CP350A6-HS
500kcmil 12.38 (314) CP500A6-HS
750kcmil 12.50 (318) CP750A6-HS
** Molded rubber insulating sleeves are ordered by their own catalog numbers, and not as suffixes to the cable protector catalog numbers.
Neoprene coated except as noted.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 16
AMP-TRAP®
Current in Amperes
Time in Seconds G
Peak Let-Thru Current Data
Copper & Aluminum Cable Protectors - #2-750kcmil - 600V
Maximum Instantaneous Peak Let-Thru Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 17
AMP-TRAP®
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 18
AMP-TRAP®
Features/Benefits
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 19
AMP-TRAP®
Current in Amperes
Ratings Approvals
➤ 600VAC, 200kA I.R. ➤ Ferraz Shawmut
Certified
➤ 100-600A
G
Standard Fuse Ampere Ratings,
Catalog Numbers
CATLOG NUMBER
AMPERE CLASS K CLASS J
RATING DIMENSION DIMENSION
100 A4BX100-150 -
125 A4BX125-150 - CLASS K
150 A4BX150-150 -
200 A4BX200-150 A4BX200-150J
225 A4BX225-150 A4BX225-150J
CLASS J
A4BX ( ) - 150; Class K Dimensions
AMPERE INCHES
RATING A B C D E F G H
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 21
AMP-TRAP®
Current in Amperes
Time in Seconds
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 22
AMP-TRAP®
G
AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG AMPERE CATALOG
RATING NUMBER RATING NUMBER RATING NUMBER RATING NUMBER RATING NUMBER
1 A2Y1-1 30 A2Y30-1 80 A2Y80-4 175 A2Y175-4 400 A2Y400-4
2 A2Y2-1 35 A2Y35-1 90 A2Y90-3 200 A2Y200-3 450 A2Y450-3
3 A2Y3-1 40 A2Y40-1 90 A2Y90-4 200 A2Y200-4 450 A2Y450-4
5 A2Y5-1 45 A2Y45-1 100 A2Y100-3 250 A2Y250-3 500 A2Y500-3
6 A2Y6-1 50 A2Y50-1 100 A2Y100-4 250 A2Y250-4 500 A2Y500-4
8 A2Y8-1 60 A2Y60-1 125 A2Y125-3 300 A2Y300-3 500 A2Y500-5
10 A2Y10-1 70 A2Y70-3 125 A2Y125-4 300 A2Y300-4 600 A2Y600-3
15 A2Y15-1 70 A2Y70-4 150 A2Y150-3 350 A2Y350-3 600 A2Y600-4
20 A2Y20-1 70 A2Y70-5 150 A2Y150-4 350 A2Y350-4 600 A2Y600-5
25 A2Y25-1 80 A2Y80-3 175 A2Y175-3 400 A2Y400-3
TYPE 4 650-1200A
Type 5, 125-600 Amperes/Hinge Disconnect type – Dimensions
AMPERE INCHES
RATING A B C D E F G H J P
600 VAC/500 VDC - A6Y (Amp) - 5
125-200 10-3/4 1-1/2 3/16 1-1/8 3-7/16 8-1/4 3/4 17/64 2-25/32 11/16
225-400 13-1/4 2 1/4 1-5/8 4-7/16 9-3/4 7/8 21/64 2-25/32 15/16
450-600 15-3/16 2-1/2 1/4 2 5-5/16 11-1/8 1 25/64 2-25/32 1
TYPE 5 125-600A
AMPERE INCHES
RATING A B D E F J K Q
600 VAC only - A6Y (Amp) - 5
650-1200 12-1/8 3 2 3-3/8 7-7/8 3-3/4 1-5/16 5/8
TYPE 5 650-1200A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 24
AMP-TRAP®
G
Current in Amperes
DC Capability
10-600 Amperes, 250 or 600 Volts 800-1200 Amperes, 600 Volts only Catalog No. Ampere DC Voltage
Prefix Rating Rating*
Peak Let-Thru Current Data A2Y 1-600 500
A6Y 1-600 500
Maximum Instantaneous Peak Let-Thru Amperes
Features/Benefits
➤ All fuses rated 170VDC, 100kA I.R.
➤ Extremely current limiting
➤ Blue & white labels for easy identification
HIGHLIGHTS APPLICATIONS:
➤ Various mounting configurations
➤ DC Rated ➤ Distribution Switching Panels
➤ Highly Current ➤ Battery Back-up Systems
Limiting ➤ Power Supplies Telecom Fuse Cross Reference
➤ Fast Acting ➤ Switching Substations Competitor Part Number Ferraz Part Number
➤ Rejection Style ➤ Telephone Switching Rectifiers TPL TGL
TPN TGN
TPS TGS
Ratings Approvals
➤ TGL: 70-800 A ➤ UL Recognized Recommended Fuse Holder
170VDC, Components FUSE AMPERE 1 Pole 3 Pole
100kA I.R.
➤ File #E60314 TGL 70-250A P243D
➤ TGN: 1-600 A 300-800A P243G
170VDC, TGN 0-30 20306R 20308R
100kA I.R. 31-60 20606R 20608R
➤ TGS: 1-70 A 61-100 21036R 21038R
170VDC, 101-200 22001R 22003R
100kA I.R. 201-400 24001R 24003R
401-600 2631R 2633R
TGS 0-70A 30656T 30658T
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 26
TGN telecommunications / SPECIAL PURPOSE
Catalog Numbers, Standard Ampere Rating
Catalog Ampere Catalog Ampere Catalog Ampere
Number Rating Number Rating Number Rating
TGN1 1A TGN40 40A TGN175 175A
A B
TGN3 3A TGN45 45A TGN200 200A
0-60A
TGN5 5A TGN50 50A TGN225 225A
TGN6 6A TGN60 60A TGN250 250A
TGN10 10A TGN70 70A TGN300 300A
TGN15 15A TGN80 80A TGN350 350A
TGN20 20A TGN90 90A TGN400 400A
TGN25 25A TGN100 100A TGN450 450A
TGN30 30A TGN110 110A TGN500 500A C
TGN35 35A TGN150 150A TGN600 600A
A B
61-600A
Dimensions
AMPERE A B C D E
RATING In. mm In. mm In. mm In. mm In. mm
170 VDC TGN FUSES
0-30 2 51 9/16 14
Melting Time - Current Data 31-60 3 76 13/16 21
61-100 5-7/8 149 1-1/16 27 1/8 3 3/4 19 1 25
G
101-200 7-1/8 181 1-9/16 40 3/16 5 3/4 19 1-3/8 35
201-400 8-5/8 219 2-1/16 53 1/4 6 1-5/8 41 1-7/8 48
401-600 10-3/8 264 2-9/16 66 1/4 6 2 51 2-1/4 57
Time in Seconds
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 27
TGL telecoMMUNICATIONS/SPECIAL PURPOSE Fuses
1.00
(25.4)
1.25
ø 1.50
(31.0)
(38.1)
2.13
(54.1)
2.75
(69.9)
3.50
(88.9) Fig. 2 CN(300A) – CZH(800A)
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 28
TGS telecoMMUNICATIONS/SPECIAL PURPOSE Fuses
G
Peak Let - Thru Current Data
Maximum Instantaneous
Peak Let - thru Amperes
Time in Seconds
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 29
GMS Telecommunications / SPECIAL PURPOSE
GMS
➤ Color Coded
➤ Body Material PPS UL 94V-0
➤ Rated 125V AC, 60V DC
➤ Carry 100% load - 10 minutes, min.
clear 150% load - 5 minutes, max.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 30
FORKLIFT TRUCK FUSES SPECIAL PURPOSE
Features/Benefits
G
➤ All fuses are AC and DC rated
➤ Expanded Ampere Ratings
➤ Time Delay and General Purpose types
➤ Link is visible through window (CNL/CNN)
HIGHLIGHTS: APPLICATIONS:
➤ AC/DC Ratings ➤ Forklift Trucks Ratings Approvals
➤ Embossed Catalog Nos. ➤ Battery Hand Trucks ➤ ACK: 1-400 Amperes ➤ UL Recognized
125VAC, 10kA I.R. Components
➤ Stud Mounted ➤ Motorized Work 125VDC, 10kA I.R. (All Products)
File #E60314
➤ Time Delay - ACK Platforms ➤ ACL: 30-120 Amperes
125VAC, 10kA I.R.
➤ General Purpose - ACL,ALS ➤ Battery Systems 125VDC, 10kA I.R.
➤ ALS: 100-500 Amperes
125VAC, 10kA I.R.
Forklift Truck Fuse 125VDC, 10kA I.R.
Fuse Blocks ➤ CNL: 35-500 Amperes
80V AC/DC, 2500A I.R.
FUSE FUSE BLOCK
ACK(70-100) P243C ➤ CNN: 10-800 Amperes
ACL(70-120) P243E 130VAC, 80VDC, 2500A I.R.
CNL FTFH
CNN FTFH
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 31
FORKLIFT TRUCK FUSES SPECIAL PURPOSE
ACK Fuse
Figure 1 Figure 2
Dimensions
CATALOG OUTLINE
NUMBER FIGURE A B C D E F G
In. (mm) In. (mm) In. (mm) In. (mm) In. (mm) In. (mm) In. (mm)
ACK 1-30 1 3.07 (77.9) 2.5 (63.5) .56 (14.3) .5 (12.7) .28 (7.1) .593 (15) .03 (.8)
ACK 35-60 1 3.74 (95) 3 (76.2) .81 (20.6) .75 (19.1) .34 (8.7) .86 (21.8) .047 (1.2)
ACK 70-100 1 4.46 (113.4) 3.5 (88.9) 1.06 (26.9) 1 (25.4) .38 (9.5) 1.12 (28.5) .06 (1.6)
ACK 120-200 1 4.72 (119.8) 3.75 (95.4) 1.06 (26.9) 1 (25.4) .38 (9.5) 1.12 (28.5) .06 (1.6)
ACK 225-400 1 4.71 (119.7) 3.75 (95.4) 1.06 (26.9) 1 (25.4) .38 (9.5) 1.12 (28.5) .06 (1.6)
ACL 30-60 1 3.07 (77.9) 2.5 (63.5) .56 (14.3) .5 (12.7) .28 (7.1) .593 (15) .03 (.8)
ACL 70-120 1 3.49 (88.6) 2.75 (69.9) .81 (20.6) .75 (19.1) .34 (8.7) .86 (21.8) .047 (1.2)
ALS 100-500 1 4.71 (119.7) 3.75 (95.4) 1.06 (26.9) 1 (25.4) .38 (9.5) 1.12 (28.5) .06 (1.6)
CNL/CNN 2 3.188 (80.9) 2.44 (61.9) .89 (22.6) .75 (19.0) .34 (8.7) –– ––
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 32
FORKLIFT TRUCK FUSES SPECIAL PURPOSE
Melting Time – Current Data – ACK1–60 Melting Time – Current Data – ACK70–400
Time in Seconds
Time in Seconds
ACK70
ACK80
ACK90
ALS100
ALS120
ALS140
ALS160
ALS175
ALS200
ALS225
ALS250
Time in Seconds
Time in Seconds
ALS300
ALS400
Melting Time – Current Data – CNL35–400 Melting Time – Current Data – CNN50–800
Time in seconds
Time in seconds
Current in amperes
Current in amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 34
SLR, SMF, SHR 300 VOLT/IN-LINE FUSES AND HOLDERS
G
SLR FUSES SMF FUSES SHR FUSE HOLDERS
Ratings Ratings Ratings
➤ 300VAC, 100A I.R. ➤ 300VAC, 100A I.R. ➤ 300VAC: 15A
125VAC, 10kA I.R. 125VAC, 10kA I.R. Withstand Rating: 10kA I.R.
1/2 to 15A 3/10 to 10A Dielectric Strength: 2,000 V
AMPere CAtalog
rating number
FUSE HOLDERS
300mA SMF3/10
SINGLE TWO
500mA SLR1/2 SMF1/2 WIRE WIRE
600mA SMF6/10 SHR-1 SHR
800mA SMF8/10
1A SLR1 SMF1 Note: Both holders are compatible
1-1/4A SMF1-1/4 with all fluorescent light fuses
1-1/2A SLR1-1/2
1-6/10A SLR1-6/10 SMF1-6/10
2A SLR2 SMF2
2-1/2A SLR2-1/2 SMF2-1/2
2-8/10A SMF2-8/10 .26
7.0
3A SLR3 SMF3 mm
3-2/10A SMF3-2/10
.25
4A SLR4 SMF4 (6.35 mm)
5A SLR5 SMF5
.5
6A SLR6
6 1/4A SMF 6 1/4 1.9
(48 mm)
7A SLR7 SMF7
8A SLR8 SMF8
9A SLR9
10A SLR10 SMF10
12A SLR12
15A SLR15
LOAD WIRE
.5 (BLACK)
STRIPPED .13
WIRE LENGTH
.5
STRIPPED
WIRE LENGTH LINR WIRE .28
(RED)
.51
6 2.32
.670
GRIPS ONTO
.202 .18 AWG WIRE
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 36
PLUG FUSES SPECIAL PURPOSE
PLUG fuses: G/GP/TD/GW/GTL/GT/GSL
Ratings Approvals
➤ 125V AC, 10kA I.R.
➤ 3 to 30 Amperes
➤ UL Listed
Guide JEFV, File E76208 G
➤ CSA Certified
➤ Choice of Edison Base, Class 142301, File 15525
Types “P”, “D”, or “S”
3 GW3 G3 - - - - -
6 GW6 G6 - - - - -
10 GW10 G10 - - - - -
15 GW15 - GTL15 GP15 GT15 TD15 GSL15 TYPE S PLUG FUSE ADAPTORS
20 GW20 - GTL20 GP20 GT20 TD20 GSL20 CAT. NO/RATING FUSE RANGE - AMPS
25 GW25 - GTL25 GP25 GT25 TD25 GSL25
30 GW30 - GTL30 GP30 GT30 TD30 GSL30 SAG3-2/10 1-8/10 - 3-2/10
SAG6-1/4 3-1/2 - 6-1/4
FR15 Rejector Rings available SAG15 7 - 15
FRW Rejection removal tool available to remove FR15 SAG20 20
*Must be used with an SAG adaptor to fit an Edison base fuse holder. SAG30 25 - 30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 37
440VDC ferrule fuses/SPECIAL PURPOSE
440 V DC
gLB from 2 to 160 A
Sizes 14x51, 22x58, 27x60
Dimensions
main characteristics
Size current
RATING intertupting watts loss catalog number ref. number
mm iN(A) 0.8 IN IN
2 0.29 0.5 CC 4.421 CP gLB 14x51/2 E075720
6 0.74 1.3 CC 4.421 CP gLB 14x51/6 Q094084
8 1.1 1.8 CC 4.421 CP gLB 14x51/8 F075721
10 1.1 1.9 CC 4.421 CP gLB 14x51/10 G075722
12 @ 440 V DC 1.2 2.0 CC 4.421 CP gLB 14x51/12 R094085
14x51 16 100 kA 1.2 2.1 CC 4.421 CP gLB 14x51/16 H075723
20 L/R = 30 ms 1.4 2.5 CC 4.421 CP gLB 14x51/20 L221132
25 1.6 2.8 CC 4.421 CP gLB 14x51/25 J075724
32 2.4 4.2 CC 4.421 CP gLB 14x51/32 S098410
40 2.9 5.0 CC 4.421 CP gLB 14x51/40 T098687
50 3.3 5.7 CC 4.421 CP gLB 14x51/50 H076620
50 3.9 6.7 CC 4.421 CP gLB 22x58/50 L076968
@ 440 V DC
63 4.9 8.5 CC 4.421 CP gLB 22x58/63 M221133
22x58 100 kA
80 6.2 10.8 CC 4.421 CP gLB 22x58/80 J098563
100 L/R = 30 ms 7.5 13.2 CC 4.421 CP gLB 22x58/100 K099507
125 @440 C DC 100 kA 12.6 22 CC 4.421 CP gLB 27x60/125 H098562
27x60 160 L/R = 30 ms 13.8 24.2 CC 4.421 CP gLB 27x60/160 M075704
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 38
440VDC ferrule fuses/SPECIAL PURPOSE
electrical characteristics
DC Voltage Capability
G
Melting Time-Current Data
Time in Seconds
+
–10% tolerance for mean
pre-arcing (melting) current
Current in Amperes
Above Curves indicate, for each rated current, pre-arcing (melting) time vs. R.M.S
pre-arcing (melting) current
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 39
660VDC ferrule fuses/special purpose
Size: 27x60
Ratings Features/Benefits
➤ Dimensions
60,3
60,3
77mm
indicator
Ø 27 travel
• 27 Ø5mm
• 5
APPLICATIONS DATA
Watts loss
Size Current Interrupting 0.8 IN IN catalog number Ref. number
(mm) rating rating
IN(A)
electrical characteristics
DC Voltage Capability vs. Time Constant
Peak Arc Voltage vs. Working Voltage
Time Constant L/R
+
–10% tolerance for mean
pre-arcing (melting) current
Current in Amperes
Above Curves indicate, for each rated current, pre-arcing (melting) time vs. R.M.S
pre-arcing (melting) current
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 41
1000V DC ferrule fuses/special purpose
Ratings Features/Benefits
Standard Fuse Amp ratings, catalog numbers, I 2t (at 50,000 Amps –1000VDC L/R = 10ms)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 42
1000V DC ferrule fuses/special purpose
G
Current in Amperes
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 43
1000V DC ferrule fuses/special purpose
Size: 20x127
Ratings Features/Benefits
➤ Dimensions
x 20.6 CC 1051 x 5
APPLICATIONS DATA
Watts loss
Size Current Interrupting catalog number Ref. num-
0.8 IN IN
rating rating ber
IN(A) NEW OLD
Blown fuse indicator minimum trip voltage: 50 V •Use R.M.S. current less than 56 A when mounting in fuse holder.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 44
1000V DC ferrule fuses/special purpose
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
L/R (ms)
90
Time Constant L/R
80
800
900
1000
1100
1200
DC Voltage Capability
Above: Curve indicates the maximum permissible value of time
constant L/R as a function of DC working voltage.
Circuit Voltage
1-L/R = 50ms
travel 2-L/R = 25ms
3-L/R = 15ms
G
t (s) 6 to 63A
10
12
16
20
25
32
40
50
63
6
10 4
10 3
10 2
10
Time in Seconds
1
+ 9% tolerance for mean
-
pre-arcing melting current
10-1
10-2
10-3
10-4
I(A)
1 10 10 2 10 3 10 4
Current in Amperes
Above: Curves indicate, for each rated current, pre-arcing time vs. R.M.S. pre-arcing (melting) current.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 45
1000V DC ferrule fuses/special purpose
1000 V DC
gRB-gRC from 25 to 100 A
Size 36x127
Ratings Features/Benefits
➤ Dimensions
mm
Minimum
indicator
travel
MAIN characteristics
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 46
1000V DC ferrule fuses/special purpose
electrical characteristics
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
Time Constant L/R
Current in Amperes
Above Curves indicate, for each rated current, pre-arcing time vs. R.M.S pre-arcing (melting) current
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 47
1500V DC ferrule fuses/SPECIAL PURPOSE
Ratings Features/Benefits
CC 1551 CP gRB
➤ 0.8 to 5 Amps
➤ 1000vdc at 100kA
➤ L/R=100mSec
CC 1500 CP gRB
➤ 0.8 to 5 Amps
➤ 1000vdc 30kA
L/R=30mSec
➤ Max AC Voltage
(50/60Hz)
➤ Dimensions 2500V @ 50k A I.R.
127
7 mm
indicator
travel
x 20.6 x5
Indicator Trip Force: 4.5N (1lb) at 0mm-2.5N )1/2lb) at 7mm (1/4”) - when so equipped*
APPLICATIONS DATA
Watts loss
Size Current Interrupting 0.8 IN IN catalog number Ref.
(mm) rating rating number
IN(A) new old
0.8 0.5 0.9 CC 1551 CP gRB 20x127/0.8 D 150 gRB 0.8 VI E075743
1 0.5 0.9 CC 1551 CP gRB 20x127/1 D 150 gRB 001 VI F075744
1.5 @ 1000V DC 0.8 1.4 CC 1551 CP gRB 20x127/1.5 D 150 gRB 01.5 VI G075745
2 100kA 0.9 1.6 CC 1551 CP gRB 20x127/2 D 150 gRB 002 VI B088367
3.15 L/R = 100ms 1.2 2.1 CC 1551 CP gRB 20x127/3.15 D 150 gRB 3.15 VI H075746
4 1.3 2.1 CC 1551 CP gRB 20x127/4 D 150 gRB 004 VI J075747
5 1.4 2.3 CC 1551 CP gRB 20x127/5 D 150 gRB 005 VI C088368
0.8 0.5 0.9 CC 1500 CP gRB 20x127/0.8 D 150 gRB 0.8 V J081842
1 0.5 0.9 CC 1500 CP gRB 20x127/1 D 150 gRB 001 V R079894
1.5 @ 1500V DC 0.8 1.4 CC 1500 CP gRB 20x127/1.5 D 150 gRB 01.5 V K081843
20
2 30kA 0.9 1.6 CC 1500 CP gRB 20x127/2 D 150 gRB 002 V Y099243
x
3.15 L/R = 30ms 1.2 2.1 CC 1500 CP gRB 20x127/3.15 D 150 gRB 3.15 V L081844
127
4 1.3 2.1 CC 1500 CP gRB 20x127/4 D 150 gRB 004 V Z099244
5 1.4 2.3 CC 1500 CP gRB 20x127/5 D 150 gRB 005 V A099245
6 3.4 6.3 CC 1500 CP gRD 20x127/6 D 150 gRB 006 V E082804
8 3.3 6.0 CC 1500 CP gRD 20x127/8 D 150 gRB 008 V Z080867
10 @ 1500V DC 3.5 6.1 CC 1500 CP gRD 20x127/10 D 150 gRB 010 V F081655
12 30kA 3.9 6.8 CC 1500 CP gRD 20x12712 D 150 gRB 012 V B080593
16 L/R = 55ms 5 8.9 CC 1500 CP gRD 20x127/16 D 150 gRB 016 V Q081457
20 5.3 9.6 CC 1500 CP gRD 20x127/20 D 150 gRB 020 V D082803
25 6.6 12 CC 1500 CP gRD 20x127/25 D 150 gRB 025 V A080431
DC Voltage Capability vs. Time Constant Peak Arc Voltage vs. Working Voltage
gRD
L/R (ms)
90 4000
80
Time Constant L/R
70
1400
1800
2200
2600
500
1000
1500
2000
Above: Curves indicate maximum permissible value of time
constant L/R as a function of DC working voltage. Circuit Voltage
Curve 1: gRD @ L/R = 30ms
Curve 2: gRB @ L/R = 60ms
Curve 3: gRD @ L/R = 15ms
Curve 4: gRB @ L/R = 30ms
3.15
0.8
1.5
10
12
16
20
25
10 4
1
2
4
5
4
5
6
8
10
10-1
10-2
10-3
10-4
1 10 10 2 10 3 1 10 10 2 10 3 1 10 10 2 10 3
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 49
1500V DC ferrule fuses/SPECIAL PURPOSE
Size: 20x190
Ratings Features/Benefits
➤ Dimensions
190 7mm
x 20.6 x 5
Weight: 176 g
Indicator Trip Force: 4.5N (1lb) at 0mm - 2.5N (1/2lb) at 7mm (1/4”) - when so equipped*
APPLICATIONS DATA
Watts loss
Size Current Interrupting 0.8 IN IN catalog number Ref.
(mm) rating rating number
IN(A)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 50
1500V DC ferrule fuses/SPECIAL PURPOSE
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
L/R (ms)
90 Um (V)
80
Time Constant L/R
70 4500
60
1200
1400
1600
1800
2000
U (V) 0
U (V)
500
1000
1500
2000
DC Voltage Capability
Above: Curve indicates maximum permissible value of time Circuit Voltage
constant L/R as a function of DC working voltage. 1-L/R = 45ms
2-L/R = 15ms
a=130
6
8
A2=0.6
10 3 B1=1.25
B2=0.6
Cf3=0.8
10 2
10-1
10-2
10-3
10-4 I (A)
10 10 2 10 3 10 4
Current in Amperes
Above: Curves indicate, for each rated current, pre-arcing (melting) time vs. R.M.S.
pre-arcing (mellting) current.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 51
1500V DC ferrule fuses/SPECIAL PURPOSE
1500 V DC
gRC-gRD from 40 to 100 A
Size 36x190
Ratings Features/Benefits
➤ Dimensions
Trip Force: 4.5N (1lb) at 0 mm-2.5N (1/2lb) at 7mm (1/4”) when so equipped
MAIN characteristics
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 52
1500V DC ferrule fuses/SPECIAL PURPOSE
electrical characteristics
DC Voltage Capability vs. Time Constant Peak Arc Voltage vs. Working Voltage
Time Constant L/R
Current in Amperes
Above: Curves
Courtesy of Steven Engineering, indicate,
Inc.-230 for each
Ryan Way, ratedSan
South current, pre-arcing
Francisco, CA (melting) time vs. R.M.S.
94080-6370-Main pre-arcing
Office: (melting) current.Local Area: (800) 258-9200-www.stevenengineering.com
(650) 588-9200-Outside
G 53
4000V DC ferrule fuses/SPECIAL PURPOSE
4000 V DC
gRC from 0.8 to 20 A
Size 36x400
Ratings Features/Benefits
➤ Dimensions
400
(15.75”)
36
(1.41”)
MAIN characteristics
current
size rating interrupting rating watts loss catalog number ref. number
(mm) In(a) 0.8IN IN
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 54
4000V DC ferrule fuses/SPECIAL PURPOSE
electrical characteristics
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
Circuit Voltage
DC Voltage Capability
Above, left and right: Curves indicate, for each rated current, pre-arcing (melt- + 10% tolerance for mean
ing) time vs. R.M.S. pre-arcing (melting) current. -
pre-arcing (melting) current
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 55
750V DC Square-body fuses/SPECIAL PURPOSE
➤ Dimensions
181 39
124 6
APPLICATIONS DATA
Time in Seconds
50 42500 8500 4.4 8.1 CC 7,5 gRC 120 EF 0050 Y084776
63 75500 15000 5.7 10.4 CC 7,5 gRC 120 EF 0063 R085207
@ 750V=
80 125000 24500 7.3 13.4 CC 7,5 gRC 120 EF 0080 Q085206
100kA
100 200000 40000 9.1 16.7 CC 7,5 gRC 120 EF 0100 P085205
L/R = 100ms
125 315000 62500 11.5 21 CC 7,5 gRC 120 EF 0125 R086242
160 485000 100000 15 27 CC 7,5 gRC 120 EF 0160 N085204
120 50 42500 8500 4.4 8.1 CC 7,5 gRC 120 TTF 0050 B220824
63 75500 15000 5.7 10.4 CC 7,5 gRC 120 TTF 0063 Q082400
80 125000 24500 7.3 13.4 CC 7,5 gRC 120 TTF 0080 Z090435
@ 900 V=
100 200000 40000 9.1 16.7 CC 7,5 gRC 120 TTF 0100 R082401
100kA
125 315000 62500 11.5 21 CC 7,5 gRC 120 TTF 0125 P085251
L/R = 40ms
160 485000 100000 15 27 CC 7,5 gRC 120 TTF 0160 R085253
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 56
750V DC square-body fuses/SPECIAL PURPOSE
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
Um(V)
L/R (ms)
90
80
70 2400
1
60
2000
50 2
40 1600
30 1200
20
10 800
0 400
0
U (V)
600
700
800
900
1000
1100
U (V)
0
200
400
600
800
1000
DC Voltage Capability Circuit Voltage
Above: Curve indicates maximum permissible value of time 1-L/R = 45ms
constant L/R as a function of DC working voltage. 2-L/R = 15ms
50 to 160A
G
Time in Seconds
I (A)
Current in Amperes
Above: Curves indicate, for each rated current, pre-arcing (melting) time vs. R.M.S. pre-arcing (melting) current.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 57
750V DC Square-body fuses/SPECIAL PURPOSE
➤ Dimensions
51
191 6
129
APPLICATIONS DATA
200 @ 750V DC 755000 150000 20.5 37.5 CC 7,5 gRC 121 EF 0200 A086710
250 100kA 1250000 250000 25.5 46.7 CC 7,5 gRC 121 EF 0250 M085203
L/R = 100ms
121 755000 150000 20.5 37.5 CC 7,5 gRC 121 TTF 0200 N085250
200 @900V DC
250 100kA 1250000 250000 25.5 46.7 CC 7,5 gRC 121 TTF 0250 Q085252
L/R = 40ms
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 58
750V DC square-body fuses/SPECIAL PURPOSE
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
Um(V)
L/R (ms)
90
80
70 2400
60 2000
50
40 1600
30 1200
20
800
10
0 400
0
U (V)
600
700
800
900
1000
1100
U (V)
0
200
400
600
800
1000
DC Voltage Capability Circuit Voltage
Above: Curve indicates maximum permissible value of time 1-L/R = 100ms
constant L/R as a function of DC working voltage. 2-L/R = 40ms
G
200
250
10 4
a=130
A2=0.6
B1=1.25
10 3 B2=0.6
Cf3=0.8
10 2
10
Time in Seconds
10-1
10-2
10-3
10-4
10 10 2 10 3 10 4 I (A)
Current in Amperes
Above: Curves indicate, for each rated current, pre-arcing (melting) time vs. R.M.S. pre-arcing (melting) current.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 59
750V DC square-body fuses/SPECIAL PURPOSE
➤ Dimensions
206 60
6
129
APPLICATIONS DATA
250 1.25x106 250,000 25.5 46.7 CC 7,5 gRC 122 EF 0250 A087331
315 2x106 400,000 31.5 58 CC 7,5 gRC 122 EF 0315 B087332
@ 750V DC 2.5x106
350 500,000 35 64.5 CC 7,5 gRC 122 EF 0350 W221141
100kA 3.1x106
400 600,000 40.5 74.5 CC 7,5 gRC 122 EF 0400 L089388
L/R = 100ms 4x106
450 800,000 49 90 CC 7,5 gRD 122 EF 0450 P220951
500 6.2x106* 1.25x106* 52 95 CC 7,5 gRD 122 EF 0500 Q220952
122 250 250,000 25.5 46.7 CC 7,5 gRC 122 TTF 0250
1.25 x106 B090437
315 2x106 400,000 31.5 58 CC 7,5 gRC 122 TTF 0315 M085249
350 2.5x106 500,000 35 64.5 CC 7,5 gRC 122 TTF 0350 G220898
@ 900 V DC=
400 3.1x106 600,000 40.5 74.5 CC 7,5 gRC 122 TTF 0400 C090438
100kA
450 4x106 800,000 49 90 CC 7,5 gRD 122 TTF 0450 R220953
L/R = 40ms
500 6.2x106* 1.25x106* 52 95 CC 7,5 gRD 122 TTF 0500 S220954
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 60
750V DC square-body fuses/SPECIAL PURPOSE
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
0
200
400
600
800
1000
U (V)
500
600
700
800
900
1000
1100
10 4
a=130
A2=0.6
10 3 B1=1.25
B2=0.6
Cf3=0.8
10 2
Time in Seconds
Time in Seconds
10
10-1
10-2
10-3
10-4 I (A)
10 2 10 3 10 4 10 5
CC 7.5gRB, gRD
➤ 630 to 750 Amp
➤ Dimensions 75
➤ 750vdc@100kAL/
206
R=50mSec 129 6
13
➤ 660vdc@100kA 28 Weight: 1,820 g
L/R=50mSec 171
131 75
129
CC.... 123 TTF ...
M12 75
87 90.5
Tapped Weight: 1,800 g
9mm deep
APPLICATIONS DATA
@ 660V DC
800 12.15x106 2.6x106 90 CC 6.6 gRB 123 EF 0800 G220944
100kA
800 12.15x106 2.6x106 90 CC 6.6 gRB 123 TTF 0800 J220946
L/R = 50ms
Contact factory for holder
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 62
660-750V DC square-body/SPECIAL PURPOSE
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
0
200
400
600
800
1000
500
600
700
800
900
1000
1100
U (V)
Circuit Voltage
DC Voltage Capability
Above: Curves indicate maximum permissible value of time 1-L/R = 100ms
constant L/R as a function of DC working voltage. 2-L/R = 40ms
t (s)
500
630
800
10 4
a=130
A2=0.6
10 3 B1=1.25
B2=0.6
Cf3=0.8
10
1
+ 7% tolerance for mean
-
pre-arcing (melting)
10-1 current
10-2
10-3
10-4
10 2 10 3 10 4 10 5 I (A)
Current in Amperes
Above: Curves indicate, for each rated current, pre-arcing (melting) time
vs. R.M.S. pre-arcing (melting) current.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 63
750V DC square-body/SPECIAL PURPOSE
750 V DC
gRC - gRD from 500 to 900 A
Size 2x122
➤ Dimensions
Weight: 2,825 g
MAIN characteristics
Size Current Interrupting Maximum I2t (A2s) catalog number Ref. number
rating rating @900V=L/R 40ms Watts loss
IN(A) ip=10IN ip=50IN 0.8 IN IN
500 5 106 1 106 51 94 CC 7,5 gRC 2122 TTF 0500 Q 090473
630 8 106 1.6 106 63 116 CC 7,5 gRC 2122 TTF 0630 R 090474
@ 900V DC
800 12.4 106 2.4 106 81 149 CC 7,5 gRC 2122 TTF 0800 S 090475
100kA
900 16 106 3.2 106 98 180 CC 7,5 gRD 2122 TTF 0900 T 220955
L/R = 40ms
2 x 122 maximum I2t (A2s)
@ 750 V DC @800V DC L/R 40ms
100kA ip=10IN ip=50IN
L/R = 100ms
1000 25 106 4,8 106 104 190 CC 7,5 gRD 2122 TTF 1000 V 220956
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 64
750V DC square-body/SPECIAL PURPOSE
electrical characteristics
G
Melting Time vs. Current Characteristics
Time in Seconds
Time in Seconds
750 V DC
gRC - gRB - grD from 1000 to 1600 A
Size 2x123
➤ Dimensions
MAIN characteristics
1250 @ 750V DC 30 106 6 106 148 CC 7,5 gRB 2123 TTF 1250 D 098558
2 x 123 1400 100kA 40 106 8 106 164 CC 7,5 gRB 2123 TTF 1400 B 090483
1500 L/R = 50ms 40 106 8 106 164 CC 7,5 gRD 2123 TTF 1500 K 220947
@ 660V DC
1600 100kA 48.6 106 10 106 180 CC 6.6 gRB 2123 TTF 1600 L 220948
(660 V) L/R = 50ms
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 66
660-750V DC square-body/SPECIAL PURPOSE
electrical characteristics
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
Time Constant L/R
Time in Seconds
1200 V DC
SRG from 160 to 420 A
Size 72
➤ Dimensions
MAIN characteristics
Size Current Interrupting Maximum I2t catalog number (1) Ref. number
rating rating @1000V= Watts loss
IN(A) L/R=15ms L/R=45ms 0.8 IN IN
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 68
1200V DC square-body/SPECIAL PURPOSE
electrical characteristics
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
Time Constant L/R
Time in Seconds
2000 V DC
SRC from 20 to 215 A
Size 120
➤ Dimensions
MAIN characteristics
Size Current Interrupting Maximum i2t catalog number (1) Ref. number
Time in Seconds
rating rating @1600V= Watts loss
IN(A) L/R=15ms L/R=45ms 0.8 IN IN
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 70
2000V DC square-body/SPECIAL PURPOSE
electrical characteristics
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
Time Constant L/R
Current in Amperes
Above: Curves indicate, for each rated current, pre-arcing (melting) time vs. R.M.S. pre-arcing (melting) current.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 71
2000V DC square-body/SPECIAL PURPOSE
2000 V DC
SRD from 160 to 400 A
Size 122
➤ Dimensions
MAIN characteristics
Size Current Interrupting Maximum I2t catalog number (1) Ref. number
rating rating @1600V= Watts loss
IN(A) L/R=15ms L/R=45ms 0.8 IN IN
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 72
2000V DC square-body/SPECIAL PURPOSE
electrical characteristics
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
Time Constant L/R
Time in Seconds
3500-4000 V DC
gRB - grD from 6 to 125 A
Size 600
➤ Dimensions
MAIN characteristics
size current interrupting rating watts loss catalog number (1) ref. number
rating 0.8IN IN
6 5.3 9.5 CC 35 gRB 600 QF 0006 S 083736
8 7 12.7 CC 35 gRB 600 QF 0008 R 083735
10 @ 3500 V DC 10.2 18.5 CC 35 gRB 600 QF 0010 N 089390
12 30kA 11 20 CC 35 gRB 600 QF 0012 V 082220
16 L/R = 30 ms 13.1 24 CC 35 gRB 600 QF 0016 P 089391
20 14 25.4 CC 35 gRB 600 QF 0020 Q 089392
600 25 18 32.5 CC 35 gRB 600 QF 0025 R 089393
32 25.5 46 CC 40 gRB 600 QF 0032 A 086963
40 @ 4000 V DC 35 63 CC 40 gRB 600 QF 0040 B 086964
50 30kA 29 52 CC 40 gRB 600 QF 0050 C 086965
63 L/R = 30 ms 42 76.5 CC 40 gRB 600 QF 0063 D 086966
80 51 92 CC 40 gRB 600 QF 0080 E 086967
80 @ 4000 V DC 3.9 67 CC 40 gRD 600 QF 0080 B 075763
100 30kA 50.5 88 CC 40 gRD 600 QF 0100 C 075764
125 L/R = 30 ms 63 110 CC 40 gRD 600 QF 0125 D 075765
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
G 74
3500-4000V DC square-body/SPECIAL PURPOSE
electrical characteristics
DC Voltage Capabilities vs. Time Constant Peak Arc Voltage vs. Working Voltage
Time Constant L/R
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
USCC & USM 24, 48 & 600 VOLT/uLTRASAFE FUSEHOLDERS TM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
USCC & USM 24, 48 & 600 VOLT/uLTRASAFE FUSEHOLDERS TM
USCC1 1 pole
USCC1I 1 pole with indicator
USCC2 2 pole
USCC2I 2 pole with indicators
USCC3 3 pole
USCC3I 3 pole with indicators
USCC3IN 3 pole with indicators and a 4th neutral pole
USCC3N 3 pole with a 4th neutral pole
USCC4 4 pole
USCC4I 4 pole with indicators
Dimensions
DIMENSION mm In
A 17.5 0.69
B 35.0 1.38
C 52.5 2.07
D 70.0 2.76
E 78.0 3.07
F 2.5 0.10
G 78.0 3.07
H 59.0 2.32
I 42.5 1.67
J 5.0 0.20
K 45.0 1.77
Ratings Approvals
➤ 600VAC: 30A-UL/CSA ➤ All Ultrasafe Fuse
Modules meet the
➤ 690VAC: 32A-IECA
requirements of UL512
➤ Short Circuit
➤ UL Listed, Class CC
Current Rating:
CC, 200kA-UL/CSA ➤ Guide IZLT, File E52283
Highlights: Applications: Midget, up to 100kA
➤ UL Recognized
w/midget fuse dependent
➤ Dedicated 3-pole fuse ➤ Primarily for motor Component Midget
on fuse I.R.
module circuits to replace ➤ Guide IZLT2, File E52283
➤ 100kA-IEC
➤ Finger Safe circuit breakers for ➤ CSA Certified
➤ Compact Footprint higher SCCR ratings
➤ Class CC & Midget
with 45mm width ➤ Other circuits up to
600 volts for control ➤ C22.2, Class 6225 01
➤ Auxiliary Contact
Option (1NO/1NC) circuits, transformers, ➤ File 32169
etc. ➤ IEC 269
➤ Ability to padlock in
OPEN position with ➤ Non-load disconnect ➤ 690VAC, 32A
1/4” shank diameter ➤ Padlock compliance
➤ 10x38mm version only
➤ DIN rail mount with
tool free removal
RECOMMENDED FUSE USAGE
➤ Quick, easy fuse
change USFMCC . . . . . use with ATDR, ATMR, ATQR
USFMM . . . . . . use with ATQ, ATM, A6Y-2B, A25Z-2
➤ Optional indicator TRM, OTM, A15QS, GFN, GGU, A60Q-2
lights USFM10 . . . . . use with IEC 10x38mm gG, aM, gR fuses
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
USFM 600 VOLT/ULTRASAFE™ FUSE MODULES
USFM10MI 3 pole fuse module with microswitch style auxiliary contact and indicators M
(13) (14)
IEC
Accessories IEC
CATALOG NO. DESCRIPTION 1 3 5
USFMFC1 Flexible connector to mate with IEC contactor 45mm lead length F1
USFMFC2 Flexible connector to mate with IEC contactor 70mm lead length 16
USFMFC3 Flexible connector to mate with IEC contactor 85mm lead length 28
2 4 6
USFMBB2 Busbar to connect 2 modules together
USFMBB3 Busbar to connect 3 modules together
H
1 3 5
USFMBB4 Busbar to connect 4 modules together A1
USFMBB5 Busbar to connect 5 modules together K1
A2
USFMBBC1 Busbar connector terminal 2 4 6
DIMENSIONS
UL/CSA (ANSI)
Wiring Diagrams
UL/CSA (ANSI)
L1 1L1 T1
(1) (2)
(L1) (T1)
L2 1L2 T2
(3) (4) MOTOR
(L2) (T2)
L3 1L3 T3
(5) (6)
(L3) (T3)
1 2
NO
(late make/early break)
START
STOP USFMACII
M
(27) (28) (A1) (A2)
(13) (14)
IEC
1 3 5
Terminal screws: Pozidriv#2, Suggested screw torque: 13 Lbs-in (1.5 N-m), Connector type: Pressure plate, Wire range: #10 15 to #16 AWG 27 (1-4)mm (75ºC solid/stranded
2
Cu only), Load-break disconnect: No (when auxiliary contact is installed in fuse module and properly
F1
wired to adjacent IEC contactor the load will be dropped out prior to
disconnection between fuse and clip inside holder upon operation of the fuse extractor handle).
16
28
2 4 6
1 3 5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H K1
A1
A2
2 4 6
US3J & US6J 600 VOLT/uLTRASAFE FUSE HOLDERS TM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H
US3J & US6J 600 VOLT/uLTRASAFE FUSE HOLDERS TM
Catalog Numbers & Descriptions – For use with 30A Class J Fuses
US3J1 1 Pole
US3J2 2 Pole
US3J3 3 Pole
US3J1I 1 Pole with Indicator
US3J2I 2 Pole with Indicators
US3J3I 3 Pole with Indicators
US3JN 1 Pole - Neutral
US3J2PAK 2 Pole Assembling Kit
US3J3PAK 3 Pole Assembling Kit
US3J4PAK 4 Pole Assembling Kit
Catalog Numbers & Descriptions – For use with 60A Class J Fuses
US6J1 1 Pole
US6J2 2 Pole
US6J3 3 Pole
US6J1I 1 Pole with Indicator
US6J2I 2 Pole with Indicators
US6J3I 3 Pole with Indicators
US6JN 1 Pole - Neutral
US6J2PAK 2 Pole Assembling Kit
US6J3PAK 3 Pole Assembling Kit
US6J4PAK 4 Pole Assembling Kit
H
Dimensions
US3J US6J
DIMENSION
mm In mm In
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H
US14 & US22 750 VOLT/ultrasafe fuse holders TM
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H
US14 & US22 750 VOLT/ultrasafe fuse holders TM
H
US14S3P2 US22S3P2 2 Microswitches for 3 pole
K E
Dimensions F
A
I
US14 US22
DIMENSION
mm In mm In
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
HH
CLASS J 600 VOLT/FUSE BLOCKS
Ratings Approvals
➤ 600VAC: ➤ All fuse blocks meet
30A, 60A, 100A, the requirements of
200A, 400A, 600A UL Std. 512
➤ Short Circuit Current ➤ UL Listed,
Rating: 200kA Guide IZLT, File E52283
➤ CSA Certified
Class 6225, File 32169
RECOMMENDED FUSE USAGE
Class J Blocks (600V) . . . . . . . use with AJT, A4J, HSJ
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 10
10
CLASS J 600 VOLT/FUSE BLOCKS
30A figures are standard dimension fuse blocks. See also 30A space-saving “SJ” Series.
Recommended mounting screws for all 30A, 60A and 100A fuse blocks: 1/4” (.250” dia.)
H
2 #2-14 60302J 60307J 3
3 60303J 60308J 4
ADDER 60310J 60315J 1
30 1 SCREW Cu 60311J 60316J 2 20
GFPC 2 #10-14 60312J 60317J 3
INSULATOR 3 60313J 60318J 4
ADDER 60320J 60325J 1
1 PRESSURE Cu 60321J 60326J 2 20
2 PLATE #10-14 60322J 60327J 3
3 60323J 60328J 4
ADDER - 60355J 1
1 BOX Cu* - 60356J 2 35
2 #4-14 - 60357J 3
3 - 60358J 4
ADDER 60600J 60605J 1
1 BOX Al/Cu 60601J 60606J 2 45
60 2 #2-14 60602J 60607J 3
GFPC 3 60603J 60608J 4
INSULATOR
ADDER - 60655J 1
1 BOX Cu* - 60656J 2 45
2 #4-14 - 60657J 3
3 - 60658J 4
1 BOX Al/Cu - 61036J 5
100
2 2/0-#6 - 61037J 6 120
PHENOLIC
3 - 61038J 7
INSULATOR 1 BOX Cu* - 61006J 5
2 2/0-#12 - 61007J 6 50
3 - 61008J 7
Note: To convert 30A or 60A adder pole to single pole, use end barrier #U09617.
* Fuse blocks have copper box connectors and clips and are for copper wires only. These are specifically designed with the same
coefficient of expansion as copper wire for improved heat cycling and meet or exceed OEM “no aluminum” specifications.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 11
11
CLASS J 600 VOLT/FUSE BLOCKS
Figure 5 Figure 6
600 Volt, 200, 400 & 600 Ampere Class J Fuse Blocks
CONNECTOR
CATALOG N0. CONNECTOR
AMPERE WIRE SPRING FIG. TORQUE
RATING POLES TYPE RANGE REINFORCED In - lb
1 BOX Al/Cu 62001J 1 375
200 3 SIDE-CLIP 350kcmil-#6 62003J 2
PHENOLIC
INSULATOR 1 BOX Cu** 62051J 1 275
3 SIDE-CLIP 350kcmil-#6 62053J 2
1 BOX* AL/Cu 64001J 3 375
3 SIDE-CLIP 1000-250kcmil 64003J 4
1 BOX AL/Cu 64031J 5 275
400 3 IN-LINE CLIP (2) 350kcmil-#4 64033J 6
PHENOLIC
INSULATOR
1 BOX* Cu** 64051J 3 375
3 SIDE-CLIP 1000-250kcmil 64053J 4
1 BOX Cu** 64061J 5 275
3 IN-LINE CLIP (2) 350kcmil-#6 64063J 6
1 BOX Al/Cu 6631J 7 500
600 3 IN-LINE CLIP (2) 500kcmil-#4 6633J 8
PHENOLIC
1 BOX Cu** 6661J 7 375
INSULATOR
3 IN-LINE CLIP (2) 500kcmil-#4 6663J 8
Ratings Approvals
➤ 600VAC:
30A, 100A
➤ All fuse blocks meet
the requirements of
UL 512
H
RECOMMENDED FUSE USAGE ➤ Short Circuit Current
Rating: 200kA ➤ UL Listed,
Class J Blocks (600V) . . . . . . . use with AJT, A4J, HSJ Guide IZLT, File E52283
➤ CSA Certified
Class 6225, File 32169
SCREW
PRESSURE
PLATE
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 13
13
SJ SERIES 600 VOLT/FUSE BLOCKS
Recommended mounting
screws for 30A fuse blocks:
1/4” (.250” dia.)
Note: To convert 30A “SJ” adder pole to single pole, use end barrier #U09372.
* Fuse blocks have copper box connectors and clips and are for copper wires only. These are specifically designed with the
same coefficient of expansion as copper wire for improved heat cycling and meet or exceed OEM “no aluminum” specifications.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 14
14
MIDGET & CLASS CC 600 VOLT/FUSE BLOCKS
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 15
15
MIDGET & CLASS CC 600 VOLT/FUSE BLOCKS
Recommended mounting screws for all Midget and Class CC fuse blocks: #8 (.164” dia.)
Note: Please see fuse block accessories (H 66 ) for information regarding fuse block accessories; DFC3M, DFC3LP or DRM.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 16
16
FEB, FEC, FEX, FEY 600 VOLT/IN-LINE FUSE HOLDERS
HIGHLIGHTS APPLICATIONS:
➤ Breakaway version quickly disconnects line side ➤ Street lighting
during pole knockdown in compliance with state and ➤ Parking lot lighting
federal highway commission standards
➤ 3 O-rings per pole for water tight applications
➤ Traffic signaling
➤ Sports lighting
H
➤ Colored O-rings for quick detection ➤ Boats and marinas
➤ Single and dual poles ➤ Humid/corrosive environments
➤ Accepts midget or Class CC fuses
➤ Wide assortment of terminal variations Ratings Approvals
➤ High heat, impact resistant insulator ➤ 600 VAC, 30A ➤ UL Listed
➤ Captive nut or screw for quick installations Short Circuit Current Class CC
Rating: Guide IZLT, File E52283
➤ Polarized dual pole provides simultaneous Midget Fuse 100kA,
disconnection Class CC, 200kA ➤ UL Recognized Component
Midget
➤ Permanently installed neutral versions quickly ➤ Temperature Rating Guide IZLT2, File E52283
identified by white nuts 155ºC
➤ CSA Certified
➤ Tulip fuse clip for improved contact and low losses Class CC and Midget
Class 6225, File 32169
➤ Environmentally friendly-no lead solder used
➤ Highly visible catalog number even with insulation Recommended Fuse Usage
boots installed FEB and FEX holders will accomodate these Ferraz Shawmut Fuses:
Midget (1-1/2” x 13/32”, 10 x 38mm): ATQ, ATM, TRM, OTM, GGU, GFN,
➤ Wire gage size identified on insulation boots for A13X-2, A25Z-2, A60Q-2, A6Y-2B
quick, accurate trimming FEC and FEY holders will accomodate these Ferraz Shawmut Fuses:
Class CC: ATDR, ATMR, ATQR
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 17
17
FEB, FEC, FEX, FEY 600 VOLT/IN-LINE FUSE HOLDERS
FEB- 1 1 - 1 1 -BA
Nomenclature Legend
Cu Double 1
91 #2–#12 Yes Yes
Seet Screw each
Al single
82 #2–#12 1 Yes Yes
Set Screw
Al double 1
92 #2–#12 Yes Yes
Set Screw each
Notes:
1. Non-breakaway units do not include insulator boots. These optional cone shaped boots are available to
provide a watertight installation. The insulator boots are designed to form a watertight seal over conductors,
but due to varying wire insulation sizes it is suggested that tape wrap be utilized for best results.
FSB1 = Single conductor boot (used to cover all crimp type & single set screw terminals)
FSB2 = Double conductor boot (used to cover all double set screw (Y-type) terminals)
Insulator boot trimming instructions: Locate wire gage size to be utilized marking on the boot and cut just
beneath it.
2. Tightening torque for single and double set screw terminations: 35 lbs.-in.
3. Tightening torque for dual pole fastening screw: 10-15 lbs.-in.
4. FEBN versions have a permanently mounted dummy fuse for neutral applications.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 18
FEB, FEC, FEX, FEY 600 VOLT/IN-LINE FUSE HOLDERS
1 Y8MRB-1 WT-111M
2 Y2MR TBM2/TBM5 BLUE DIE, WT-115-A DIE O
3 Y2MR TBM2/TBM5 GREY DIE, WT-115-A DIE E
4 Y2MR TBM2/TBM5 BROWN DIE, WT-115-A DIE F
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 19
FEB, FEC, FEX, FEY 600 VOLT/IN-LINE FUSE HOLDERS
4.3” (110mm)
8.0” (203mm) Assembled Length with Optional FSB1 Boots
4.7” (119mm)
5.8” (147mm) Assembled Length
9.0” (229mm) Assembled Length
4.3” (109mm)
4.2” (106mm)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 20
20
CLASS H, K & R 250 & 600 VOLT/FUSE BLOCKS
H
➤ 600VAC: ➤ UL Listed,
30A, 60A, 100A, Guide IZLT, File E52283
200A, 400A, 600A
RECOMMENDED FUSE USAGE ➤ UL Recognized
➤ Short Circuit Component
Class R Blocks (250V) . . . . . . . use with A2D-R, A2K-R, TR-R Current Ratings: Guide IZLT2, File E52283
Class R Blocks (600V) . . . . . . . use with A6D-R, A6K-R, TRS-R 250 & 600VAC
w/class H fuses - 10kA ➤ CSA Certified
Class H & K Blocks (250V) . . . use with OT, RF, A2Y types 1 & 3 Class 6225, File 32169
OTN, CRN, NRN w/class K fuses - 50kA
w/class R fuses - 200kA
Class H & K Blocks (600V) . . . . use with OTS, RFS, A6Y types 1 & 3
CRS, NRS
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 21
21
CLASS H, K & R 250 VOLT/FUSE BLOCKS
Recommended mounting screws for all 30A and 60A fuse blocks: #10 (.190” dia.)
CATALOG NUMBER
CONNECTOR TYPE OF CLIP
Note: To convert 30A adder pole to single pole, use end barrier #U09322. To convert 60A adder pole to single pole, use end barrier #U09365.
* 1-pole, 30A block does not accept adder pole.
** Fuse blocks have copper box connectors and clips and are for copper wires only. These are specifically designed with the same coefficient of expansion as copper wire
for improved heat cycling and meet or exceed OEM “no aluminum” specifications.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 22
CLASS H, K & R 250 VOLT/FUSE BLOCKS
10.5”
10.5” 5.5”
H
200A, 3-pole - 5/16” (.313” dia.)
Figure 5 Figure 6
250
CATALOG NUMBER
CONNECTOR TYPE OF CLIP
Note: To convert 100A adder pole to single pole, use end barrier #U09363.
* Fuse blocks have copper box connectors and clips and are for copper wires only. These are specifically designed with the same
coefficient of expansion as copper wire for improved heat cycling and meet or exceed OEM “no aluminum” specifications.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 23
CLASS H, K & R 250 VOLT/FUSE BLOCKS
Figure 6
Figure 5
250 Volt, 400 & 600 Ampere Class H, K and R Fuse Blocks
Recommended
CATALOG NUMBER
mounting screws
CONNECTOR TYPE OF CLIP for all 400A and 600A
CLASS H & K CLASS R CONNECTOR fuse blocks: 5/16
AMPERE WIRE SPRING SPRING FIG. TORQUE (.313” dia.)
RATING POLES TYPE RANGE REINFORCED REINFORCED In - lb
1 BOX* Al/Cu 24001 24001R 1 375
3 SIDE-CLIP 1000-250kcmil 24003 24003R 2
1 BOX* Cu** 24051 24051R 1 375
400 3 SIDE-CLIP 1000-250kcmil 24053 24053R 2
PHENOLIC
INSULATOR 1 BOX AL/Cu 24031 24031R 3 275
3 IN-LINE CLIP (2) 350kcmil-#4 24033 24033R 4
1 BOX Cu** 24061 24061R 3 275
3 IN-LINE CLIP (2) 350kcmil-#6 24063 24063R 4
Recommended mounting screws for all 30A and 60A fuse blocks: 1/4” (.250” dia.)
Note: To convert 30A or 60A adder pole to single pole, use end barrier #U09361.
* Fuse blocks have copper box connectors and clips and are for copper wires only. These are specifically designed with the same coefficient of expansion as copper wire
for improved heat cycling and meet or exceed OEM “no aluminum” specifications.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 25
25
CLASS H, K & R 600 VOLT/FUSE BLOCKS
Note: Adder poles can only be added to other fuse blocks. There is no end barrier to convert them to single pole fuse blocks.
* Fuse blocks have copper box connectors and clips and are for copper wires only. These are specifically designed with the same
coefficient of expansion as copper wire for improved heat cycling and meet or exceed OEM “no aluminum” specifications.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 26
CLASS H, K & R 600 VOLT/FUSE BLOCKS
Recommended mounting
screws for all 400A and
600A fuse blocks: 5/16
(.313” dia.)
Figure 3 Figure 4
Figure 1 Figure 2
Figure 5
600 Volt, 400 & 600 Ampere Class H, K and R Fuse Blocks
Figure 6
H
CATALOG NUMBER
CONNECTOR TYPE OF CLIP
Ratings Approvals
➤ 300VAC: ➤ All fuse blocks meet
30A, 60A, 100A, the requirements of
200A, 400A, 600A UL Std. 512
➤ 600VAC: ➤ UL Listed,
30A, 60A, 100A, Guide IZLT, File E52283
RECOMMENDED FUSE USAGE 200A, 400A, 600A
➤ UL Recognized
Class T Blocks (300V) . . . . . . . use with A3T ➤ Short Circuit Component
Class T Blocks (600V) . . . . . . . use with A6T Current Rating: Guide IZLT2, File E52283
200KA
➤ CSA Certified
Class 6225, File 32169
CONNECTORS FOR
SPRING REINFORCED SPRING REINFORCED
30A & 60A CLIPS 30A & 60A CLIPS CONNECTORS CONNECTORS
30A - 60A
300V - 60A SCREW
100A BOX 600A BOX
30A - 60A
600V - 60A
PRESSURE PLATE 200A BOX
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 28
28
CLASS T 300 VOLT/FUSE BLOCKS
H
3 30308T 4
4 30309T 5
ADDER 30315T 1
1 Cu 30316T 2
30 2 SCREW #10-14 30317T 3 20
GFPC 3 30318T 4
INSULATOR 4 30319T 5
ADDER 30325T 1
1 PRESSURE Cu 30326T 2
2 PLATE #10-14 30327T 3 20
3 30328T 4
4 30329T 5
ADDER 30355T 1
1 Cu* 30356T 2
2 BOX #4-14 30357T 3 35
3 30358T 4
4 30359T 5
ADDER 30615T** 1
1 Cu 30616T** 2
2 SCREW #10-14 30617T** 3 20
3 30618T** 4
4 30619T** 5
60 ADDER 30605T 1
GFPC 1 Al/Cu 30606T 2
INSULATOR 2 BOX #2-14 30607T 3 45
3 30608T 4
4 30609T 5
ADDER 30655T 1
1 Cu* 30656T 2
2 BOX #4-14 30657T 3 45
3 30658T 4
4 30659T 5
Note: * Fuse blocks have copper box connectors and clips and are for copper wires only. These are specifically designed with the same coefficient of expansion as
copper wire for improved heat cycling and meet or exceed OEM “no aluminum” specifications.
Engineering,
Courtesy of Steven ** UL Component
Inc.-230Recognized
Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 29
29
CLASS T 300 VOLT/FUSE BLOCKS
300 Volt, 100, 200, 400 & 600 Ampere Class T Fuse Blocks
† Note: Height includes nominal fuse blade
CONNECTOR CATALOG NO. TORQUE (IN-LBS)
AMPERE WIRE SPRING thickness
RATING POLES TYPE RANGE REINFORCED FIG. CONNECTOR FUSE BOLT Recommended base mounting
1
BOX Al/Cu
31031T 1 screws:
100 2
SIDE-CLIP 2/0-#6
31032T 2 120 – 100A & 200A, #10 (.190” dia.)
PHENOLIC 3 31033T 3 400A & 600A, 1/4” (.250” dia.)
INSULATOR 1 31001T 4
Cu*
2 BOX 31002T 5 50 72
2/0-#12
3 31003T 6
200 1 Al/Cu 32031T 7
BOX 275 132
PHENOLIC 3 350 kcmil-#6 32033T 8
INSULATOR 1 Cu* 32051T 7
BOX 275 132
3 350 kcmil-#6 32053T 8
400 1 Al/Cu 34031T 9
BOX 600 228
PHENOLIC 3 600 kcmil-#2 34033T 10
INSULATOR 1 Cu* 34051T 9
BOX 375 228
3 600 kcmil-#2 34053T 10
600 1 BOX Al/Cu
36031T 11 600 360
PHENOLIC (2) 600 kcmil-#2
INSULATOR 1 BOX Cu*
36051T 11 375 360
(2) 600 kcmil-#2
Note: * Fuse blocks have copper box connectors and are for copper wires only. These are specifically
designed with the same coefficient of expansion as copper wire for improved heat cycling and
meet or exceed OEM “no aluminum” specifications.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 30
CLASS T 600 VOLT/FUSE BLOCKS
H
RATING POLES TYPE RANGE REINFORCED In - lb
ADDER 60305T 1
1 BOX Al/Cu 60306T 2
2 #2-14 60307T 3 35
3 60308T 4
ADDER 60315T 1
1 SCREW Cu 60316T 2
30 2 #10-14 60317T 3 20
GFPC 3 60318T 4
INSULATOR ADDER 60325T 1
1 PRESSURE Cu 60326T 2
2 PLATE #10-14 60327T 3 20
3 60328T 4
ADDER 60355T 1
1 BOX Cu* 60356T 2
2 #4-14 60357T 3 35
3 60358T 4 FIGURE 8
ADDER 60615T** 5
1 SCREW Cu 60616T** 6
2 #10-14 60617T** 7 20
3 60618T** 8
60 ADDER 60605T 5 Recommended mounting screws:
GFPC 1 BOX Al/Cu 60606T 6 30A, #10 (.190” dia.)
INSULATOR 2 #2-14 60607T 7 45
3 60608T 8 60A, 1/ “ (.250” dia.)
4
ADDER 60655T 5
1 BOX Cu* 60656T 6
2 #4-14 60657T 7 45
3 60658T 8
Note: * Fuse blocks have copper box connectors and clips and are for copper wires only. These are specifically
designed with the same coefficient of expansion as copper wire for improved heat cycling and
meet or exceed OEM “no aluminum” specifications.
** UL Component Recognized
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 31
CLASS T 600 VOLT/FUSE BLOCKS
FIGURE 6
600 Volt, 100, 200, 400 & 600 Ampere Class T Fuse Blocks
CONNECTOR CATALOG NO. TORQUE (IN-LBS)
AMPERE WIRE SPRING
RATING POLES TYPE RANGE REINFORCED FIG. CONNECTOR FUSE BOLT
1 Al/Cu 61031T 1
100 2 BOX 2/0-#6 61032T 2 120 72
PHENOLIC 3 61033T 3
INSULATOR 1 Cu* 61051T 1
2 BOX 2/0-#12 61052T 2 50 72
3 61053T 3
200 1 BOX Al/Cu 62031T 4 275 132
PHENOLIC 3 350 kcmil-#6 62033T 5
INSULATOR 1 BOX Cu* 62051T 4 275 132
3 350 kcmil-#6 62053T 5
400 1 BOX Al/Cu 64031T 6 600 228
PHENOLIC 600 kcmil-#2
INSULATOR 1 BOX Cu* 64051T 6 375 228
600 kcmil-#2
600 1 BOX Al/Cu 66031T 7 600 360
PHENOLIC (2) 600 kcmil-#2
INSULATOR 1 BOX Cu* 66051T 7 375 360 FIGURE 7
(2) 600 kcmil-#2
Note: * Fuse blocks have copper box connectors and are for copper wires only. These are specifically
designed with the same coefficient of expansion as copper wire for improved heat cycling and
meet or exceed OEM “no aluminum” specifications. † Note: Height includes nominal fuse blade thickness
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 32
32
CLASS G 480 & 600 Volt/Fuse blocks
Features/Benefits
➤ Unique integral DIN rail adapters for 15, 20 &
30A blocks
➤ Unique adder-block design (all ampere ratings) for
design flexibility
➤ Spring reinforcing standard for 60A clips
➤ Features high conductivity copper alloy fuse clips
H
Ratings Approvals
➤ 600VAC: 15A & 20A ➤ All fuse blocks meet the
requirements of UL Std. 512
➤ 480VAC: 30A & 60A
➤ UL Listed
➤ Short Circuit Current Rating:
Guide IZLT, File E52283
100kA using screw, pressure
plate or box connections, ➤ CSA Certified
10kA using quick connects. Class 6225, File 32169
➤ Temperature/flammability:
GFPC insulators rated 125ºC
RTI, 94V-0 flammability
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 33
33
CLASS G 480 & 600 Volt/Fuse blocks
.17x.10 DP
.17x.10 DP
3.05 3.78
1.53 1.89
.17 .25 1.11 1.88
.16 .26 1.11 1.87
.34
.77 .85 1.62 2.39 .35
.76 .86 1.62 2.38
1.45 1.40
.64 .52
600 Volt, 15 & 20 Ampere; 480 Volt 30 & 60 Ampere Class G Fuse Blocks
CONNECTOR
CONNECTOR
AMPERE WIRE TORQUE
RATING POLES TYPE RANGE CATALOG NUMBER FIG IN-LB
ADDER SCREW W/DOUBLE 40110G 1
1 QUICK CONNECTS AT Cu 40111G 2 20
2 BOTH ENDS #10-14 40112G 3
3 40113G 4
15 ADDER PRESSURE PLATE 40120G 1
GFPC 1 (SEMS) W/DOUBLE Cu 40121G 2 20
INSULATOR 2 QUICK CONNECTS AT #10-14 40122G 3
3 BOTH ENDS 40123G 4
ADDER 40150G 1
1 COPPER Cu 40151G 2 35
2 BOX #6-14 40152G 3
3 40153G 4
ADDER SCREW W/DOUBLE 40210G 1
1 QUICK CONNECTS AT Cu 40211G 2 20
2 BOTH ENDS #10-14 40212G 3
3 40213G 4
20 ADDER PRESSURE PLATE 40220G 1
GFPC 1 (SEMS) W/DOUBLE Cu 40221G 2 20
INSULATOR 2 QUICK CONNECTS AT #10-14 40222G 3
3 BOTH ENDS 40223G 4
ADDER 40250G 1
1 COPPER Cu 40251G 2 35
2 BOX #6-14 40252G 3
3 40253G 4
ADDER 40350G 1
1 COPPER Cu 40351G 2 35
2 BOX #6-14 40352G 3
3 40353G 4
ADDER 40605G 5
1 ALUMINUM Al/Cu 40606G 6 45
60 2 BOX #2-14 40607G 7
GFPC 3 40608G 8
INSULATOR
ADDER 40655G 5
1 COPPER Cu 40656G 6 45
2 BOX #4-14 40657G 7
3 40658G 8
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 34
34
5X20QC1/6X32QC1 FUSE BLOCKS
5X20QC1 6X32QC1
SINGLE POLE FUSE BLOCK for 5mm x 20mm fuses SINGLE POLE FUSE BLOCK for 1/4” x 1-1/4”
H
fuses
➤ Tin plated clips
➤ Polyester insulator ➤ Tin plated phosphor bronze clips
➤ 3/16” quick-connect terminals ➤ Phenolic insulator
➤ Rated 15A, 250V ➤ 1/4” quick-connect terminals
➤ UL Recognized ➤ Rated 30A, 250V - UL Recognized
Anti-rotation stud
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 35
35
GPM SERIES PANEL MOUNT/FUSE HOLDERS
GPM PANEL MOUNT FUSE HOLDERS
Ferraz Shawmut GPM Panel Mount Fuse Holders
are in sizes to accommodate Class CC and Midget
(1-1/2” x 13/32”) fuses. All 30A holders have glass-
filled thermoplastic insulators for extra dependability
and trouble-free installation. Patented design allows
same body to accept screw or bayonet knob. Flange
design allows front or rear mounting.
Approvals
➤ UL Recognized, Guide IZLT2, File E52283
CSA Certified, Class 6225, File 32169
GPM-B 1 1/4 Turn Bayonet Knob 30 600 1-1/2” x 13/32” 1/4” Quick-connect/Solder
GPM-B90 2 1/4 Turn Bayonet Knob 30 600 1-1/2” x 13/32” 1/4” Quick-connect/Solder, Right Angle
GPM-BRR 1 1/4 Turn Bayonet Knob 30 600 Class CC 1/4” Quick-connect/Solder
GPM-BRR90 2 1/4 Turn Bayonet Knob 30 600 Class CC 1/4” Quick-connect/Solder, Right Angle
Figure 2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 36
GPM SERIES PANEL MOUNT/FUSE HOLDERS
Ferraz Shawmut GPM Panel Mount Fuse Holders will accommodate 1” x 1-1/4” 3AG fuses and 5mm x 20mm fuses;
most are approved by U.L. and CSA. Cap and body material is bakelite or polycarbonate and function as a screw-in or
bayonet style closure. Finger-grip or screwdriver slots are available. All holders are rated for up to 250 volts with amp
ratings ranging from 3A to 15A.
CAT. NO. CAP TYPE VOLTS AMPS FUSE SIZE TERMINAL TYPE APPROVALS
GPM-A Finger-grip/Screw-in 250 10 5mm x 20mm Solder UR/CSA
GPM-A1 Finger-grip/Screw-in 250 10 5mm x 20mm Solder
GPM-A2 Finger-grip/Screw-in 250 10 5mm x 20mm Solder UR/CSA
GPM-A3 Finger-grip/Screw-in 250 3 5mm x 20mm Solder UR/CSA
GPM-A4 Finger-grip/Screw-in 250 6.3 5mm x 20mm Solder, right angle
GPM-A5 Screwdriver Slot 250 10 5mm x 20mm Solder
GPM-A6 Screwdriver Slot 250 6.3 5mm x 20mm Solder, right angle UR/CSA
GPM-A8 Screwdriver Slot 250 10 5mm x 20mm Solder, right angle UR/CSA
GPM-A9 Screwdriver Slot 250 6.3 5mm x 20mm Solder, right angle UR/CSA
GPM-A10 Screwdriver Slot 250 6.3 5mm x 20mm 3/16”Solder/QC UR/CSA
GPM-A11 Screwdriver Slot 250 10 5mm x 20mm Solder, right angle UR/CSA
GPM-A GPM-A1
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 37
37
GPM SERIES PANEL MOUNT/FUSE HOLDERS
GPM-A2 GPM-A3
GPM-A4 GPM-A5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 38
GPM SERIES PANEL MOUNT/FUSE HOLDERS
GPM-A6 GPM-A8
GPM-A9 GPM-A10
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 39
GPM SERIES PANEL MOUNT/FUSE HOLDERS
GPM-A11
CAT. NO. CAP TYPE VOLTS AMPS FUSE SIZE TERMINAL TYPE APPROVALS
GPM-G Finger-grip/Screw-in 250 15 3AG 3/16” Solder/QC UR/CSA
GPM-G1 Finger-grip/Screw-in 250 10 3AG 3/16” Solder/QC UR/CSA
GPM-G2 Finger-grip/Screw-in 250 10 3AG Solder
GPM-G3 Screwdriver Slot 250 10 3AG Solder UR/CSA
GPM-G5 Finger-grip/Bayonet 250 10 3AG 1/4” Solder/QC UR/CSA
GPM-G6 Finger-grip/Bayonet 250 10 3AG Solder UR/CSA
GPM-G7 Screwdriver Slot 250 15 3AG 3/16” Solder/QC UR/CSA
GPM-G8 Finger-grip/Screw-in 250 15 3AG Quick-connect
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 40
40
GPM SERIES PANEL MOUNT/FUSE HOLDERS
GPM-G GPM-G1
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 41
41
GPM SERIES PANEL MOUNT/FUSE HOLDERS
GPM-G2 GPM-G3
GPM-G5 GPM-G6
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 42
42
GPM SERIES PANEL MOUNT/FUSE HOLDERS
GPM-G7 GPM-G8
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 43
AMP-TRAP® –Form 101
Figure 2
Figure 1
Figure 3
Dimensions
DIMENSIONS - INCHES
FOR USE AMPERES CATALOG STUD SIZE TORQUE
WITH NO. FIG. A B C D E F (in lbs)
A13X, A15QS 70-450 P243D 2 4.40 1.50 2.79 2.20 2.06 1.17 1/4-20 36
A13X, A15QS 500-600 P243G 2 4.40 1.50 2.79 2.20 2.44 0.98 5/16-18 84
A25X, A25Z, A30QS 35-60 P243G 2 4.40 1.50 2.79 2.20 2.44 0.98 5/16-18 84
A25X, A25Z, A30QS 70-200 P243 1 4.50 1.50 2.50 2.25 2.38 1.06 1/4-20 36
A25X, A25Z, A30QS 225-600 P243G 2 4.40 1.50 2.79 2.20 2.44 0.98 5/16-18 84
A50P 35-60 P243G 2 4.40 1.50 2.79 2.20 2.44 0.98 5/16-18 84
A50P, A50QS 70-200 P243E 2 4.40 1.50 2.79 2.20 2.88 0.76 1/4-20 36
A50P, A50QS 225-600 P266C 1 6.00 2.00 3.00 3.00 3.28 1.36 3/8-16 144
A60X, A60Z, A70QS-4 35-200 P243C 2 4.40 1.50 2.79 2.20 3.62 0.39 1/4-20 36
A60X, A60Z, A70QS-4 225-600 P266A 1 6.00 2.00 3.00 3.00 4.06 0.97 3/8-16 144
A70P, A70Q, A70QS-4 35-100 P243C 2 4.40 1.50 2.79 2.20 3.62 0.39 1/4-20 36
A70QS-4K 125-200 P266A 1 6.00 2.00 3.00 3.00 4.06 0.97 3/8-16 144
A70P, A70Q 125-400 P266A 1 6.00 2.00 3.00 3.00 4.06 0.97 3/8-16 144
A70P, A70Q, A70QS-4K 450-600 P266F 1 8.00 2.50 3.00 4.00 5.09 1.45 3/8-16 144
A100P 35-100 P266G 1 6.00 2.00 2.50 3.00 4.25 0.88 1/4-20 36
A100P 125-400 P266L 1 6.00 2.00 3.00 3.00 4.66 0.67 3/8-16 144
A120X 1-30 P292 3 - - - - - - - -
A30QS 700-800 FH25F4 1 6.00 2.00 3.00 3.00 2.66 1.67 3/8-16 144
A50QS 700-800 FH50F4 1 8.00 2.50 3.00 4.00 4.21 1.84 1/2-13 360
A50QS 900-1000 FH50F5 1 8.00 2.50 3.00 4.50 4.97 1.50 1/2-13 360
A70QS-4K 450-600 FH70F3 1 8.00 2.50 3.00 4.00 5.09 1.91 1/2-13 360 Note: FH Blocks are 1” thick.
* Not UL or CSA Certified
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 44
1SC/1MSC Modular semiconductor FUSE BLOCKS
Ferraz Shawmut 1SC and 1MSC semiconductor
fuse blocks feature modular mounting that offers
greater flexibility in adjusting to various fuse lengths.
Both stud type and integral box connector versions
are offered to allow for user preference of wire
terminations. The integeral box connector versions
also provide for greater heat dissipation. All modular
blocks are supplied in pairs but need to be ordered
as two items to suit one fuse. Mounting hardware is
supplied with the blocks.
Highlights:
➤ Modular two-piece design
➤ Compact footprint
➤ Stud versions
➤ Heat dissipating integeral box connector versions
➤ Accommodates a large range of semiconductor
REV. DATE ECO DESCRIPTION
1031
CONTROL No:____________
BY CK APP
fuses
➤ Rugged phenolic insulators
1031
CONTROL No:____________
35.13 - 10/13/2006 NA INITIAL RELEASE LDB NA NA
REV. DATE ECO DESCRIPTION BY CK APP
1.383
42.88 - 10-12-06 NA INITIAL RELEASE LDB NA NA
30.05 1.688
1.183
37.80
5.08 1.488
Fig. 2
.200 5.16
.203
Fig. 1
THREAD
M8X1.25 OR 1/4-20UNC
THREAD
M10X1.5 OR 3/8-16UNC
Ratings Approvals
27.81
1.095
35.67
1.405
➤ 600VAC (1MSC) ➤ UL Recognized
Component
H
➤ 1000 VAC (1SC)
62.26 97
3.82
2.45
Guide IZLT2,
53.85
2.120
25.40
1.000
➤ up to 800 amperes File E171957
47.63 17.78
1.875 .700
SIGN: SIGN:
400A 1000V 701315
DATE: DATE: SHEET 1 OF 1
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 46
703, U705, U710 semiconductor fuse holders
Figure 5 Figure 6
Recommended mounting
screws; #10 (.190”dia)
H
FUSE SIZE TORQUE (IN-LB)
NUMBER Rating TYPE WIRE RANGE
U70505 Adder 1
U70506 1 Al/Cu 2
14 x 51 50 Box 35
U70507 2 #2-14 3
U70508 3 4
Figure 7
70315 Adder 1
70316 1 Cu 2
14 x 51 30 Screw 20
70317 2 #10-14 3
70318 3 4
70325 Adder 1
70326 1 Pressure Cu 2
14 x 51 30 20
70327 2 Plate #10-14 3
70328 3 4
70355 Adder 1
70356 1 Cu* 2
14 x 51 30 Box 35
70357 2 #4-14 3
70358 3 4
U71005 Adder 5
U71006 1 A1/Cu 6
22 x 58 100 Box 35
U71007 2 #2-14 7
U71008 3 8
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 47
PS 20x127 Ferrule fuse holders and no-load disconnectors
Fuse Holders
and Fuse no-load Disconnectors
for 20x127 Ferrule-type fuses
HIGHLIGHTS:
➤ Solid assembly offers good thermal and
mechanical withstand rating
➤ Fuse mounting in holders or no-load
disconnectors with or without open fuse indicating
microswitches
➤ Phenolic resin models for basic applications,
fiber-glass polyester for applications in corrosive
atmospheres or applications for traction
➤ Voltage = 1,500 V and 2,500 V
Dimensions
Fire and
Insulation Fuse current Maximum operating current of fuse (A) Advised copper fumes class
NF F 16-
DESCRIPTION voltage rating Ui rating wire size
1000 V =1000 V =1000 V =1500 V =1500 V 101
AC 50/60 Hz or DC IN(A) mm2 and 102
gLB gRC gRB gRB gRD and UL
PSI 20X127 50 10 basic
1500 V without 50 model
terminal covers 12-F1
63 56 No 16 UL 94 V1
PSI 20X127 PRE 2500 V with
terminal covers 80 80 Operating 25 salt
PSII 20X127 PRE and only salt spray-proof
PSIII 20X127 PRE spray-proof model 100 90 Limit 35 model
50 I1 - F1
PSIV 20X127 PRE 125 100 UL 94 VO
Connecting with 50 mm2 max. cable with copper terminals or with a 15 x 8 max. rigid or flexible bar.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 48
PS 20x127 Ferrule fuse holders and disconnectors
H
V: Connecting distance between centers
W: Clip for rail mounting in two positions Number
W’: With terminal cover length of poles A B
Y: Space factor with a 90° fuse carrier position
Z: Without terminal cover, space factor with a 180° fuse carrier position 1 35 50
Z’: With terminal cover, space factor with 180° fuse carrier position 2 69 84
3 103 118
4 137 152
Description (basic model) Catalog Number
Preisolating and blown fuse
PSI 20x127 PRE F 097203 indicating microswitch features
PSII 20x127 PRE G 097227 Microswitch Non-inductive circuit
PSIII 20x127 PRE H 097228 rated current interrupting rating
PSIV 20x127 PRE J 097229 3A - 50 Hz 3A - 50 Hz
PSI 20 x 127 PRE+MC PS H 097205 3A - DC 3A - DC
PSII 20 x 127 PRE+MC PS D 097293 Reliable minimum operating voltage/current:
PSIII 20 x 127 PRE+MC PS E 097294 10V - 10mA
PSIV 20 x 127 PRE+MC PS F 097295 Connecting with 6.35 mm lug
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 50
EURO/IEC Fuse Bases
23002-G 23210-G
H
23414-G
23618-G
CC.14 – 50A, 690VAC
Fits 30A, 250V Class H, K, R and 14 x 51mm Fuse-links CC.22 – 125A, 690VAC, Fits 22 x 58mm Fuse-links
Width Width
CATALOG NUMBER CATALOG NUMBER
(No. of17.5mm (No. of17.5mm
POLES SCREW MOUNT RAIL MOUNT MODULES) POLES SCREW MOUNT RAIL MOUNT MODULES)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 51
European Fuse Bases
Dimensions
A B C D E F G H I K L M
A B C D E F G H I J K L M N
CC.14 62 15.5 1 7.25 94 45.5 127 27 20.3 15.2 112 85 6 58
(2.44) (.61) (.04) (.29) (3.70) (1.79) (5.00) (1.06) (.80) (.60) (4.41) (3.35) (.24) (2.29)
Accessories
CC.8 CC.10 CC.14 CC.22
POLES CATALOG NO. CATALOG NO. CATALOG NO. CATALOG
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 52
EURO/IEC Fuse Bases
Assembly Pins
Dimensions – mm (Inches) No. of CATALOG
A B C D E F G H J K L POLES NUMBER
2 14030-G
59 78 45 12.5 42.5 17.5 78 2.5 35 52.5 70
3 14031-G
(2.32) (3.07) (1.77) (.49) (1.67) (.69) (3.07) (.098) (1.38) (2.07) (2.76)
4 14032-G
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 53
53
EURO/IEC Fuse Bases
N 29000-G 1,5
1 29002-G 29004-G 29020-G 29120-G 1,5
1+N 29010-G 29011-G 3
2 29012-G 29013-G 29021-G 29121-G 50A 32A 25A 3.5 3
3 29014-G 29015-G 29024-G 29124-G 4,5
3* 29025-G* 29125-G* 6
3+N 29016-G 29017-G 29026-G 29126-G 6
4 29019-G 6
*2 microswitches
Accessories(***)
No. of
CATALOG
Description 17.5mm
NUMBER
Modules
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 54
EURO/IEC Fuse Bases
N 29200-G 1,5
1 29202-G 29204-G 29220-G 29320-G 1,5
1+N 29210-G 29211-G 3
2 29212-G 29213-G 29221-G 29321-G 125A 100A 80A 4.5 3
3 29214-G 29215-G 29224-G 29324-G 4,5
3* 29225-G* 29325-G* 6
3+N 29216-G 29217-G 29226-G 29326-G 6
4 29219-G 6
*2 microswitches
Accessories(***)
No. of
H
CATALOG
Description 17.5mm
NUMBER
Modules
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 55
55
EURO/IEC Fuse Bases
1 1
2
4
6
8
10
12
16
CMS 22 690 8 20 20 20 4 4
25 25 25 6
32 32 42 10
40 40 40 10
50 50 50 10
63 51 63 16
80 64 60 25
100 100 74 70 35
125 100 35
Lock installation
Padlock Catalog Number 29057-G
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 56
56
EURO/IEC Fuse Bases
Microswitch options
CLICK!
CLICK!
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 57
57
EURO/IEC Fuse Bases
Assembly
Disassembly
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 58
EURO/IEC Fuse Bases
40002-G 40006-G
RATED CATALOG
SIZE CURRENT (A) NUMBER
00-E 160 40002-G
00-EB 160 40003-G
0-E 160 40004-G
0-P 160 40006-G
H
1-P 250 40008-G
2-P 400 40010-G
3-P 630 40012-G
4-P 1250 40014-G
40510-G
A 33 32 32 55 55 55 80
B 20 20 25 32 35 40 45
C 118.5 269 166 210 227 241 312
D 100 151 150 175 200 210 262
E* 8 8.5 8.5 11 11 11 11
F - - - 30 30 30 45
G 14.5 14 14 22 22 22 -
H 25 25 25 25 25 25 30
I 145 185 185 250 250 250 -
J 21.5 29 29 35 35 35 45
K 8 8 8 10 10 12 16
L 55 72 74 84 84 84 111
M 52.5 60 60 71 89 103 145
N 80 85 85 100 100 127 -
O 84 120 120 148 148 148 192
P 34 47 47 62 69 82 -
Q 1 2 2 2 2 2 -
R 101 126 126 177 190 213 -
* 8mm for all multiple pole bases; dimensions in chart for single pole bases.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 60
60
EURO/IEC Fuse Bases
Connection Detail
SCREW CLAMP
H
POLES SCREW CONNECTOR PRESSURE PLATE CONNECTOR
SCREW MT. RAIL MT. SCREW MT. RAIL MT.
Dimensions
00-EP
A 32
B 20
C 117
D 100
E 8
F 2
G 14
H 25
I 145
J 21.5
K 8
L 56
M 52
N 85
0 84
P 34
Q 1
R 104
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 61
61
EURO/IEC Fuse Bases
1 41502-G 42502-G
2 41512-G 42512-G
3 41514-G 42514-G
4 41519-G 42519-G
M 59 61 71 89 103
N 95 95 122.5 122.5 142.5
O 122 122 146 146 146
P 48.5 48.5 65.5 65.5 81.5
Q 94 94 125.5 125.5 141.5
R 142 142 191 191 223
S 190 190 256.5 256.5 304.5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 62
EURO/IEC Fuse Bases
Separators
0 160 44604-G 2
1-2 400 44610-G 2
3 630 44612-G 2 44610-G
44702-G
Fuse Shields Terminal Shields
00 100 44802-G 3 00 100 44702-G 6
0 160 44804-G 3 0 160 44704-G 6
44802-G
1-2 400 44810-G 3 1-2 400 44710-G 6
Dimensions of Terminals
CATALOG
NUMBER A B C M
45421-G 18 26 34 6
45423-G 24 35 52 8
45425-G 26 41 58 10
45427-G 36 53 68 12
45431-G 18 26 39 6
45433-G 24 35 82 8
45435-G 26 41 84 10
45437-G 36 53 98 12
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 63
DFC SERIES DEAD-FRONT FUSE COVERS
WARNING: To avoid electrical shock, TURN POWER OFF before installing, removing or servicing.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 64
64
DFC SERIES DEAD-FRONT FUSE COVERS
Ferraz Shawmut Fuses and Fuse Blocks for use with DFC
H
A2Y(0-30) 203xx -9I, -9 RF(35-60) 206xx -1I, -1
A2Y(35-60) 206xx -1I, -1 RF(65-100) 210xx -4I, -4
A2Y(70-100) 210xx -4I, -4 RFS(0-30) 603xx -2I, -2
A25X(1-30)-1 203xx -9I, -9 RFS(35-60) 606xx -5I, -5
25Z(1-30)-2 303xx -7I, -7 RFS(65-100) 610xx -8I, -8
A4J(1-30) 603xxJ -1I, -1 TR(0-30)R 203xx -9I, -9
A4J(1-30) 603xxSJ -10I, -10 TR(35-60)R 206xx -1I, -1
A4J(35-60) 606xxJ -6I, -6 TR(70-100)R 210xx -4I, -4
A4J(70-100) 610xxJ -3I, -3 TRM(0-30) 303xx -7I, -7
A4J(70-100) 6100xxSJ -11I, -11 TRS(0-30)R 603xxR -2I, -2
A50P(10-30) 203xx -9I, -9 TRS(35-60)R 606xxR -5I, -5
A6D(0-30)R 603xxR -2I, -2 TRS(65-100)R 610xxR -8I, -8
A6D(35-60)R 606xxR -5I, -5 TRS(35-60)RDC 606xxR -5I, -5
A6D(70-100)R 610xxR -8I, -8 TRS(70-100)RDC 610xxR -8I, -8
A6K(0-30)R 603xxR -2I, -2
Note: DFC Covers fit single pole blocks and each pole of multi-pole blocks.
Consult factory for data sheets of DFC trim instructions for safety switches.
WARNING: To avoid electrical shock, TURN POWER OFF before installing, removing or servicing.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 65
DFC3M/DFC3LP/DRM FUSE BLOCK ACCESSORIES
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 66
66
FUSE CLIPS fOR Ferrule fuseS / pc board MOUNT
.280”
SDC6 (7.1mm)
PC BOARD clips
.425”
(0.8mm)
➤ PC board mount fuse clip
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H 67
228-700 SERIES MEDIUM VOLTAGE/FUSE CLIPS
CL-14 Fuse A
Catalog Number Dimensions - Inches
A055C1DORO-(10E-150E) 13.25
A055C1DORO-(200E-400E) 19.25
A055C2DORO-(450E-600E) 19.25
A155C1DORO-(10E-50E) 16.25
A155C1DORO-(65E-100E) 19.25
A155C2DORO-(125E) 19.25
A155C3DORO-(150E-300E) 19.25
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
H
H 68
68
Power Distribution
Blocks
One powerful way to
manage your power
distribution problems.
Our solution: Well beyond circuit protection solutions. Ferraz • Power Distribution
Shawmut offers you an arsenal of circuit management products. Blocks / 62000-63000
Mini Series
One of which is our line of polycarbonate 600V / 90 to 1520A
Power Distribution Blocks. Safe and convenient, durable and easy
to install, they’re the simple way to split primary power circuits • Power Distribution
Blocks / 66000-67000
into secondary circuits — or provide fixed-junction tap-off points.
Intermediate Series
Either way, our full range of sizes accommodates any gauge
aluminum or copper conductor. Exclusive adder poles snap onto
the 1-, 2-, or 3-pole blocks for maximum pole flexibility . . . and • Power Distribution
Blocks / 68000-69000
safety covers are available.
Large Series
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
FSPDB finger-safe/POWER DISTRIBUTION BLOCKS
Features/Benefits Ratings
➤ Finger-Safe ➤ Ampere ratings
Fully insulated block ensures touch safe isolation of live parts. from 175 to 840A
Recessed termination screws and wire openings provide IP20
grade protection and qualify as “finger-safe” per IEC 529. ➤ 600V rated
➤ Short Circuit Current Rating
➤ Compact Modularity 100kA with proper fuse.
Single or multiple pole configurations in the most compact foot- Contact Technical Services for
print. Allows users to build smaller or higher density panels. instruction sheet.
➤ Snap on DIN Rail Mounting
Sizes 1 to 4 feature integral DIN rail adaptors allowing for quick
and easy installations on 35mm DIN rail yielding lower installed Approvals
costs.
➤ UL Recognized Component -
➤ Captive Termination Screws Guide XCFR2, File E73571
Unique channel design ensures captive metric wire termination ➤ CSA Certified:
screws. Screws can never be lost. Class 6228, File 69363
➤ Available Accessories
For multi-pole panel mounting, simply snap in pins for rigid fit.
Cap plugs provide the ability to maintain touch safety on unused
openings. Circuit identification markers simply snap into blocks
to ID circuits. End anchors provide rigid end stops.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
I
FSPDB finger-safe/POWER DISTRIBUTION BLOCKS
Catalog Numbers and Ratings
Catalog Number Line Load
ampere rating Wire Range Wire Range Short
Aluminum Copper (Based on NEC circuit
(Connector rated for (Connector rated for Table 310-16 for AWG/ Openings AWG/ Openings Current
75° C Cu wire) mm2 mm2
90° C Cu/AL wire) 75° C Cu wire only) kcmil per pole kcmil per pole rating
FSPDB1A FSPDB1C 175 2/0-#14 70-2.5 1 2/0-#14 70-2.5 1 *100kA
I
D 45.1 1.78 51.6 2.03 59.8 2.36 75.5 2.97 - -
for 350, 400 & 600 kcmil
E 39.4 1.55 39.4 1.55 51.5 2.03 50.1 1.97 50.1 1.97
max. conductors
F 72.6 2.86 87.7 3.45 100.8 3.97 145.5 5.73 145 5.71
FSCAP1 Cap plug for spare 2/0 openings
G 59.6 2.35 74.6 2.94 82.4 3.24 120.6 4.75 127.5 5.02 FSCAP2 Cap plug for spare 350 kcmil
H 5.3 0.21 5.1 0.20 6.5 0.26 7 0.28 3 0.12 openings
I - - - - 31.5 1.24 - - 52 2.04 FSCP3 Cap plug for spare 600 kcmil
J 5.3 0.21 6.4 0.25 6.5 0.26 6.5 0.26 6.5 0.26 opening
K 10 0.40 11.7 0.46 8.9 0.35 16 0.63 8.5 0.34 FSEA Pair of end anchors
H
I
H
K
Figure 1 Figure 2 K
G G
B
F B
F
E J
D E J
A
D
C A
C
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
I
62000-69000 SERIES POWER DISTRIBUTION BLOCKS
VERSATILE Power distribution blockS
for cable terminatIONS
Ferraz Shawmut Power Distribution Blocks afford a safe, convenient
way of splicing cables, splitting primary power into a variety of
secondary circuits or providing a fixed junction tap-off point. Power
block options include single or dual primary connections with up to
30 secondary connections.
Features/Benefits
➤ Adder Poles
All series have optional adder poles which snap onto the 1, 2 or 3- pole blocks
and lock together to form as many poles as required. Adder poles with a variety of
terminations can be combined to match special wire size combinations.
➤ Wire Connectors
Standard aluminum box connectors accommodate aluminum or copper wire, 1
conductor per opening. Standard copper box connections are for copper wire only,
1 conductor per opening. Connectors are all 1 piece and tin plated.
➤ Insulators
Insulators are virtually unbreakable, glass-filled polycarbonate on all series.
“See-Through” Safety Covers are available which give greater safety and provide
Service Entrance ratings for large and intermediate series blocks.
Ratings Approvals
➤ Ampere ratings from 90 ➤ Most sizes are
to 2660 UL Recognized Component -
Guide XCFR2, File E73571
➤ 600V rated
➤ Most sizes are
➤ Short Circuit current rat- CSA Certified:
ing 100kA with proper fuse.
Contact technical services Series 62, 63, 66, 68 -
for sizing table. Class 6228,File 69363
Series 67, 69 -
Class 3211, File 15469
HIGHLIGHTS: Applications:
➤ Mini - ➤ Box, stud and quick-
62000 and 63000 Series connect terminations
for copper and/or
➤ Intermediate - aluminum cables
66000 and 67000 Series
➤ Large -
68000 and 69000 Series
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
I
MINI 62000-63000 SERIES/POWER DISTRIBUTION BLOCKS
Sizes, Ratings, Catalog Numbers – Mini Series 62000 and 63000
Ampere rating based on NEC Table 310-16 for 75º copper wire.
PRIMARY SECONDARY CATALOG NUMBER SHORT
WIRE RANGE OPENINGS WIRE RANGE OPENINGS AMP ALUMINUM (Connector
90º C
Cu/Al
rated for
wire)
(Connector rated for
COPPER
90º C Cu wire only)
CIRCUIT
AWG/kcmiL or STUDS AWG/kcmil or STUDS RATING CURRENT
or STUD SIZE* PER POLE or STUD SIZE* PER POLE CSA UL ADDER 1 POLE 2 POLE 3 POLE ADDER 1 POLE 2 POLE 3 POLE RATING
Box to Box
#4-14 1 #4-14 1 90 85 63100 63101 63102 63103 62100 62101 62102 62103 •
4 63160 63161 63162 63163 62160 62161 62162 62163 •
2/0-#14 1 63150 63151 63152 63153 62150 62151 62152 62153 •
2/0-#14 1 #2-14 2 185 175 63190 63191 63192 63193 62190 62191 62192 62193 •
#4-14 4 63130 63131 63132 63133 62130 62131 62132 62133 •
Box to Stud
2/0-#14 1 1/4-20 x 5/8 1 185 175 63140 63141 63142 63143 62140 62141 62142 62143 •
1 1/4-20 x 1/2 1 62170 62171 62172 62173 •
Tapped hole
Stud to Stud
1/4-20 x 5/8 1 1/4-20 x 5/8 1 240 240 - - - - 62200 62201 62202 62203 •
Box to Quick Connect
#4-14 1 1/4 x .032QC 4 90 95 - - - - 62210† 62211† 62212† 62213† -
*Studs are furnished with nuts and washers. Recommended stud torque: (1/4-20) - 72 in. lbs. †Quick connector, not CSA Certified.
Note: Blocks for 5, 6 and 10 poles are also available. To order, simply modify the Adder catalog number. Example: 63100 becomes 63106 for 6 poles.
•Short circuit current rating with correctly sized fuse 100kA except adder block. Contact Ferraz technical services for fuse type and maximum ampere required.
NUMBER DIMENSION
I
OF POLES A (Inches)
Example for 10 poles:
ADDER .812
A= (.812 x 10) + .273 = 8.39
1 1.09
2 1.90
3 2.71
N (.812 x N) + .273
PRIMARY SECONDARY CATALOG NUMBER SHORT
WIRE RANGE OPENINGS WIRE RANGE OPENINGS ALUMINUM (90º C Cu/Al wire) COPPER (75º C Cu wire only) CIRCUIT
AWG/kcmiL or STUDS AWG/kcmil or STUDS AMPERE CURRENT
or STUD SIZE PER POLE or STUD SIZE PER POLE RATING ADDER 1 POLE 2 POLE 3 POLE ADDER 1 POLE 2 POLE 3 POLE RATING
Box to Box
Box to Stud
350-#6 1 3/8-16 x 1 1 310 67250 67251 67252 67253 66250 66251 66252 66253
500-#4 1 3/8-16 x 1-1/16 1 380 67220 67221 67222 67223 66220 66221 66222 66223
1/4-20 x 1-1/16 2 380 67240 67241 67242 67243 66240 66241 66242 66243
Stud to Stud
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
I
INTERMEDIATE 66000-67000 SERIES/POWER DIST. BLOCKS
Dimensions – 66000 and 67000 Series
Power Distribution Blocks
NUMBER DIMENSION A
OF POLES (Inches)
ADDER 1.64
1 1.94
2 3.57
3 5.20
N (1.635 x N) + .30
Example for 10 poles:
A= (1.635 x 10) + .30 = 16.65 inches
I
Flexural Strength psi D790 13,200 Polycarbonate end barriers snap on to PDB Adder blocks
Flexural Modulus psi D790 325,000 to form 1-pole blocks. Use one barrier per block.
Tensile Strength psi D638 9,000
Compressive Strength psi D695 12,500
Water Absorption 24 hrs-% D570 .15
Hardness Rockwell D785 M-85
Dielectric Stength D149
60 hertz, 25°C, s/t vpm 425
60 hertz, 25°C, s/s vpm 425
Dielectric constant D150
60Hz-dry 3.01
1 Mhz-dry 2.96
Volume resistivity ohm-cm D257 >1016
Heat deflecting °F D648 270
(°F@264 psi)
Flammability (UL 94) 94 V-O
Note: Above data represents approximate values and are for reference only.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
I
LARGE 68000-69000 SERIES/POWER DISTRIBUTION BLOCKS
Sizes, Ratings, Catalog Numbers – Large Series 68000 and 69000
Ampere rating based on NEC Table 310-16 for 75º copper wire.
PRIMARY SECONDARY CATALOG NUMBER SHORT
CIRCUIT
WIRE RANGE OPENINGS WIRE RANGE OPENINGS AMPERE ALUMINUM (90º C Cu/Al wire) COPPER (75º C Cu wire only) CURRENT
AWG/kcmil PER POLE AWG/kcmil PER POLE RATING ADDER 1 POLE 2 POLE 3 POLE ADDER 1 POLE 2 POLE 3 POLE RATING
Box to Box
2/0-#14 6 69170 69171 69172 69173 68170 68171 68172 68173 •
350-#6 1 #4-14 12 310 69150 69151 69152 69153 68150 68151 68152 68153 •
#10-14* 20 69630** 69631** 69632** 69633** 68630** 68631** 68632** 68633**
600-#2 1 600-#2 1 420 69640 69641 69642 69643 68640 68641 68642 68643 •
#4-14 2 #4-14 12 170 69180 69181 69182 69183 68180 68181 68182 68183 •
2/0-#14 2 #4-14 12 350 69160 69161 69162 69163 68160 68161 68162 68163 •
#10-14* 20 69600 69601 69602 69603 68600 68601 68602 68603 •
350-#6 2 69120 69121 69122 69123 68120 68121 68122 68123 •
4/0-#6 4 69320** 69321** 69322** 69323** - - - -
350-#6 2 4/0-#10 4 620 - - - - 68320** 68321** 68322** 68383**
2/0-#14 6 69130 69131 69132 69133 68130 68131 68132 68133 •
#4-14 12 69140 69141 69142 69143 68140 68141 68142 68143 •
500-#4 2 69090 69091 69092 69093 68090 68091 68092 68093 •
4/0-#6 4 69310 69311 69312 69313 - - - -
500-#4 2 4/0-#10 4 760 - - - - 68310 68311 68312 68313 •
2/0-#14 6 69100 69101 69102 69103 68100 68101 68102 68103 •
#4-14 12 69110 69111 69112 69113 68110 68111 68112 68113 •
*Copper wire only **Not UL Recognized or CSA Certified ***These pole blocks are triple width (7.81”)
†These 1 pole blocks are double width (5.31”)
•Short Circuit current rating with correctly sized fuse 100kA except adder block. Contact Ferraz technical services for fuse type and maximum ampere required.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
I
LARGE 68000-69000 SERIES/POWER DISTRIBUTION BLOCKS
Sizes, Ratings, Catalog Numbers – Large Series 68000 and 69000 (continued)
Ampere rating based on NEC Table 310-16 for 75º copper wire.
NUMBER DIMENSION A
OF POLES (Inches)
ADDER 2.50
1 2.81
2 5.31
3 7.81
N (2.50 x N) + .31
Example for 10 poles:
A= (2.50 x 10) + .31 = 25.31
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
I
Circuit Protection
Accessories
You maintain the circuit.
We’ll maintain an inventory
of accessories to help.
Your problem: The little things that make your job easier add
up. Maybe it’s a lockable cabinet to keep your spares from being
scattered across the plant. Maybe it’s having the right fuse puller,
• Box Covers
so your people don’t put themselves at risk by “improvising”
during fuse changeouts. Or maybe you’re an OEM designer or • Fuse Reducers
specifying engineer, and that circuit protection problem you’ve • Fuse Pullers, Clip Clamps
been wrestling with would disappear if fuses came with a special • Trigger® Indicator
gadget that . . .
• Shawmut Trigger®
Our solution: Look no further than Ferraz Shawmut’s line of • Trigger® Actuator
Circuit Protection Accessories. Cabinets, box covers, reducers, • Blown Fuse Indicators
pullers, blown-fuse indicators, add-on switches . . . they’re all
• Add-on Switches
here. In stock. Under one roof. And ready to meet your circuit
protection system maintenance needs — or help you solve • IL Indicator
• Protistor Microswitches
Want more information fast? For more technical or application-
specific information, please call our Circuit Protection Accessories
experts, at 978-462-6662; 416-252-9371 in Canada; or visit our
website at us.ferrazshawmut.com.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
BOX COVERS ACCESSORIES
BOX COVERS
Ferraz Shawmut Box Covers
fit all standard size boxes with
a variety of plug fuse, switch
and receptacle combinations.
They provide easy access to
local protection and control
of 125V motors and other
COU COW COX equipment. Long life
corrosion-protected steel
bases.
Rating & Approval
➤ Rated 125V AC 15A
➤ UL Listed
CATALOG NO. BOX COVER FEATURES TO MOUNT ON: CATALOG NO. BOX COVER FEATURES TO MOUNT ON:
COU Edison-Base Fuse Holder 2-1/4” Handy Box CSX Edison-Base Fuse Holder 4” Octagon Box
COW Edison-Base Fuse Holder 2-3/4” Switch Box and Single Pole Switch
COX
COY
Edison-Base Fuse Holder
Edison-Base Fuse Holder
4” Octagon Box
4” Square Box
CSY
COY-B
Edison-Base Fuse Holder
and Single Pole Switch
2 Edison-Base Fuse Holders
4” Square Box
4” Square Box
J
CRU Edison-Base Fuse Holder 2-1/4” Handy Box
and Grounding Receptacle CSY-L Edison-Base Fuse Holder
Single Pole Switch and 4” Square Box
CRW Edison-Base Fuse Holder 2-3/4” Switch Box Pilot Light
and Grounding Receptacle
CSY-RL Edison-Base Fuse Holder 4” Square Box
CRX Edison-Base Fuse Holder 4” Octagon Box Grounding Receptacle
and Grounding Receptacle Single Pole Switch and
Pilot Light
CRY Edison-Base Fuse Holder 4” Square Box
and Grounding Receptacle CCY 2 Edison-Base Fuse Holders 4” Square Box
and 2 Single Pole Switches
CSU Edison-Base Fuse Holder 2-1/4” Handy Box
and Single Pole Switch CKA 2 Edison-Base Fuse Holders 4-11/16” Square Box
& 250V Grounding Receptacle
CSW Edison-Base Fuse Holder 2-3/4” Switch Box
and Single Pole Switch CTY 2 Edison-Base Fuse Holders 4” Square Box
and one 2-Pole Switch
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
J
FUSE REDUCERS ACCESSORIES
FUSE REDUCERS
Ferraz Shawmut Fuse Reducers allow the use of
lower rated fuses in existing equipment having clips
with higher ampere ratings. The use of closer rated
time-delay fuses can improve circuit protection.
For example, renewable or one-time fuses feeding a
motor can be replaced with fuses sized closer to the
motor nameplate current. Non-rejection Reducers
will allow Class H, K or R fuses to fit Class H or K
clips. Rejection-type Reducers will allow only Class
R fuses to fit Class R clips or only Class J fuses to fit
Class J clips. Class J fuse reducers are not for bolt
on applications.
Ratings Approvals
➤ For 250 and 600 Volt ➤ UL Listed
Class H, K and R fuses Guide No. IZZR
➤ For 600 Volt ➤ CSA Certified
Class J fuses
➤ 30 to 600 amperes
➤ Tested to 200,000A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
J
FUSE PULLERS/CLIP CLAMPS ACCESSORIES
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
J
BLOWN FUSE INDICATORS ACCESSORIES
TRIGGER® INDICATOR
The Trigger Indicator (Catalog Number suffix
TI) is available on many blade type fuses,
primarily Form 101 semiconductor fuses and
some Class L fuses. The TI allows blown fuses
Before to be identified visually, eliminating the need
for resistance or continuity testing.
After
After
Before
Catalog Numbers
The Shawmut Trigger Indicator is a field-mountable blown-fuse indicator which is wired in TI-130 0-130 2
TI-600 0-600 2
parallel with the fuse to be monitored. The striker pin exerts a static force of one pound and may TI-1500 0-1500 3-1/2
be used to actuate a switch. It is available in 130 volt (TI-130), 600 volt (TI-600), and 1500 volt
(TI-1500) ratings. The TI-600 Trigger is a UL Listed accessory. The Shawmut Trigger is not a
fuse and should only be used in parallel with fuses rated 70A or higher. To mount the Trigger,
use two midget fuse clips (for 13/32” diameter fuses) found in the Fuse Clip section.
TRIGGER® actuator
The Trigger Actuator (catalog number suffix TA) has two functions and is an option available
on many Amp-trap® fuses. First, it provides visual indication of an open fuse and second, it
provides a mount for an Add-On-Switch (AOS-) which can indicate a blown fuse via a signal
light or initiate appropriate control action. The Trigger Actuator has no measurable I2t or arc
voltage effect on fuses rated 65A or higher. It will add 2 to 5 amperes of long term rating and
requires a minimum circuit voltage of 5 to 10 volts to activate.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
J
BLOWN FUSE INDICATORS ACCESSORIES
AOS-Q
add-on-switch
Add-On-Switches contain one single-pole double-
throw contact rated 4 amperes resistive and 1 ampere
inductive at 250V AC maximum. Two versions of the
Add-On-Switch are available. Catalog number AOS-S has
screw terminals. Catalog number AOS-Q accommodates
push-on connectors.
AOS-S Mounted
on fuse
AOS-S
IL INDICATOR
The new “IL” indicator, developed from proven designs,
provides a blown fuse indication system which does not
sacrifice the excellent I2t characteristics of Ferraz fuses. Its
low voltage design requires just 0.9 volts to activate the
indicator, thus insuring reliable fuse performance under all
conditions. The red pop up button is located in the center
of the fuse body for ease of visibility and optimum voltage
isolation. Interference with buss bar and cable connection
is significantly less than other designs. The addition of the
“IL” indicator provides blown fuse indication on virtually all
Ferraz fuses. Optional auxiliary microswitches for remote
signaling are also available for use with the “IL” indicator.
Features/benefits J
➤ Visual Indication or Remote Signaling
HIGHLIGHTS:
➤ Optional Auxiliary Microswitches
➤ Low Voltage Design ➤ Same Size for All Fuses
➤ Center Location
➤ Retains Optimum Performance
➤ Rugged Construction
➤ Operation at All Times Above 0.9 Volts
➤ Proven Reliability
➤ AC or DC
➤ UL Recognized
- For blown fuse indication on general purpose fuses, please consult factory.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
J
MICROSWITCHES & STUDS ACCESSORIES
Features/benefits
➤ Microswitch systems adapted to the following fuses:
- PSC sizes 30, 31, 32, 33 / 70, 71, 72, 73
- Blade-type PSC (PA) sizes 0-1, 2-3 / 70, 71, 72, 73
- PSC sizes 000 / 00
Applications Data
AC IMPULSE
INTERRUPTING RATING
AC POSITIVE RATED NATURE OF VOLTAGE VOLTAGE FIRE
CODE VOLT OPERATING CURRENT CURRENT NON -INDUCTIVE CIRCUIT INDUCTIVE CIRCUIT WITHSTAND TEST CLASS
*** VOLT/CURRENT 30V 110V 250V 30V 110V 250V TEST UIMP 1.2/50 UL 94
MS 3V 1-5 1000 V 20 V 10 A 50/60 Hz 10A 10A 10A 10A 10A 10A 8,5 kV* 14 kV**
MS PA 2-5 1500 V 20 V 50/60 Hz 10A 10A 10A 10A 10A 10A 9 kV* 13 kV**
10 A VO
MS PA 2-9 50 mA DC 8A 0,4A 0,2A 4A 0,2A 0,1A
MS 4L 2-5 B6 1000 V 20 V 50/60 Hz 10A 10A 10A 10A 10A 10A 8 kV* 10 kV**
10 A VO
50 mA DC 8A 0,4A 0,2A 4A 0,2A 0,1A
* Between power circuit and microswitch terminals as per IEC 60 and 694 and NFC 64010 (50/60 Hz 1 min. duration in dry air)
** Between power circuit and microswitch terminals Uimp: impulse voltage as per IEC 947-1
***Between power circuit and microswitch terminals
EACH MICROSWITCH WEIGHS LESS THAN 100 g, THEREFORE NO FUME AND SMOKE GRADE IS REQUIRED BY NF F 16-102 STANDARD
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
J
PSC MICROSWITCHES ACCESSORIES
2
MS 3V Fuse Sizes: 30 - 33
1
4
X31
MS30014
V1-5
Fig. 1 Ref. Indication Weight
Fuse Size Code Number Style (g)
42
34.6
X310014
MS3V1-5 32.7 Fig. 2 MS 3V 1-5 ET R310009 Low level NO-NC 34
(fig. 3)
10
4.75 x 0.5
1
4 R310009
MS3V1-5 ET
Fig. 3
(4) Same dimensions as fig. 1 but with 2 microswitches side by side
32.7
Sizes
10
70, 71, MS 7V 1-9 BS P310007 Double pole NO-NC 55
72, 73 (8) low level
4.75 x 0.5
1
2
MS 7V 1-5 ET S310010 Low level NO-NC 55
4
S310010
MS7V1-5 ET
Fig. 5 (fig. 5) IP 50 (9)
32.7
MS PA Fuse Sizes: 0 - 70 J
Ref. Indication Weight
Fuse Size Code Number Style (g)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
J
PSC MICROSWITCHES ACCESSORIES
Fig. 1 Fig. 2
8,5
23 2,8
33 26
28,5 15
22,5
Catalog Number Reference Weight
Number (g)
23,6
27
MC 36 GR 2-5
for British standard fuses
with internal indicator P 092496 10
8,4
27 and 36
13 3,4
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
J 10
PROTISTOR FUSE MICROSWITCHES ACCESSORIES
PROTISTOR® FUSES
Microswitch systems for round and
square-body fuses (not for PSC Fuses)
Features/benefits
➤ Remote signaling systems for fitting on Ferraz Shawmut
fuses equipped with microswitch support
➤ Indication of fuse status
➤ Manual Reset
➤ Standard and low current models with different
insulation ratings
➤ Watertight types for use in corrosive atmospheres
CHARACTERISTICS
AC or DC
AC voltage Impulse Positive
Insulation inductive circuit
voltage test operating Current Non-inductive circuit
TYPE CATALOG NUMBER voltage withstand test L/R = 25ms
Uimp 1,2/50 hs min.voltage rating Current
rating (*)
(**) /min.current
Ui (V) 30 V 110 V 250 V 30 V 110 V 250 V
MC3E 1-5N 1250V 15 kV 20 kV 20 V 50/60 Hz 10 A 10 A 7A 6A
Standard 5A
MCR3E 1-5N 2200V 20 kV 30 kV 50 mA DC 5A 0.5 A 1.6 A 0.3A
MC3E 1-5NBS
1250V 15 kV 20 kV
MC3E 1-9NBS
50/60 Hz 3A 3A 3A 2A 1A 1A
MCR3E 1-5NBS 20 kV (1) 10 V
J
Low level 2200V 30 kV 3A
MCR3E 1-9NBS 23 kV (2) 10 mA
24 kV (1) DC 3A 0.5 A 0.25 A 3A 0.2 A 0.1 A
MC2R3E 1-5BS
6000V 26 kV (2) 40 kV
MC2R3E 1-9NBS 32 kV (3)
MC3E 1-5NET 1250V 11 kV 16 kV 3A 3A 1A 1A
Watertight 10 V 50 Hz
MCR3E 1-5NET 2200V 20 kV (1) 30 kV 3A
IP 50 10 mA DC 0.5A 0.2 A
MC2R3E 1-5NET 6000V 24 kV (2) 40 kV
Catalog Numbering system: MC3E 1-5 single pole microswitch - MC3E 1-9 double pole microswitch - MCR, MC2R reinforced insulation microswitch
* Between power circuit and microswitch terminals as per IEC 60 and 694 and NFC 64010 (50/60 Hz 1 min. duration in dry air)
** Between power circuit and microswitch terminals Uimp: impulse voltage accordong to IEC 947-1
***Between power circuit and microswitch terminals
EACH MICROSWITCH WEIGHS LESS THAN 100g, THEREFORE NO FUME AND SMOKE GRADE IS REQUIRED BY NF F16-102 STANDARD
(1) for short body fuses (sizes 30 - 31 - 32 - 33 - 70 - 71 - 72 - 73 - 83 - 84) Except PSC
(2) for sizes 100 - 91 - 92 - 93 - 94 - 123 - 124 fuses and longer
(3) for sizes 171 - 172 - 173 - 174 fuses and longer
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
J 11
Semiconductor Fuses
SSeSem iiccioconondnduducuctctootror rFFuFususesesess
emm
Microswitches
Microswitches
Microswitches
Microswitches
Microswitch Systems Protistor®
Fuses
Microswitch
PROTISTOR
Microswitch
Microswitch Systems
FUSE
Systems
Systems Protistor
MICROSWITCHES ®
®Fuses
Protistor
Protistor Fuses
Fuses
®
ACCESSORIES
REMOTE SIGNALING WITH 1250 V AC/DC INSULATION VOLTAGE
REMOTE
Remote SIGNALING
Signalling WITH
with 1250 1250Insulation
VWITH
AC/DC V AC/DC INSULATION VOLTAGE
Voltage
REMOTE
REMOTE SIGNALING
SIGNALING WITH 1250
1250 V V AC/DC
AC/DC
Quantity INSULATION
INSULATION
of NO-NC VOLTAGE
VOLTAGE
Catalog Ref. Weight Pack.
Contact Number
separated circuits Number (g) (1)
Quantity of NO-NC Catalog Ref. Weight Pack.
Quantity
Quantity
Quantity of of NO-NC
Contact
of NO-NC standard Number Catalog
Catalog
Catalog Ref.
Ref. Weight
Ref. Weight Pack.
WeightPack.
Pack.
separated 1NO-NC
circuits
separated circuits Contact
Contact MC3E
Contact Number 1-5NNumber
Number D310020
Number (g) 39.5 (1) (1)3
separated
separated circuits
circuits Number Number (g)
Number (g) (g) (1) (1)
1 1 1 standard lowstandard
levelMC3EMC3E 1-5NBS
1-5N
MC3E E310021 39.5
1-5N D310020
D310020 39.5 3 3 3
39.5
1 1 standardMC3E
standard MC3E1-5N D310020 39.5
1-5N D310020 39.5 3 3
1 2 1 lowlow
low level level
levelMC3E MC3E
MC3E 1-5NBS
1-9NBS
1-5NBS E310021 39.5
F310022 39.5
E310021 45.7 3 3 3
1 12 low low lowlevel
level MC3E
level MC3E
MC3E1-5NBS
1-9NBS E310021 39.5
1-5NBSE310021
F310022 45.7
39.5 33 3
2 1 lowwatertight
level MC3E MC3E L310027 45.740.2 3 3
1-5NETF310022
1-9NBS
2 21 low low
levellevelMC3E
watertight MC3E1-9NBS
MC3E 1-5NET L310027 40.245.7
F310022 45.7
1-9NBSF310022 33 3
1 watertight MC3E 1-5NET L310027 40.2 3
1 1 watertight
watertight MC3EMC3E L310027 40.2
1-5NETL310027
1-5NET 40.2 3 3
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
SOCOMEC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K
SOCOMEC
K
Direct mounted handle (requires removing collar from switch) HAD60M HAD60M HAD60M HAD60M
OTHER VERSIONS AVAILABLE: Switch with Direct Mounted Handles AMPERE RATING 16 20 25 30
CATALOG NUMBER: 3 POLE LBSM16DH LBSM20DH LBSM25DH LBSM30DH
Please consult factory for availability of switches with direct mounted
handles. Options same as above.
Door mounted switches AMPERE RATING 16 20 25 30
CATALOG NUMBER: 3 POLE LBSDM16 LBSDM20 LBSDM25 LBSDM30
SHAFT LENGTH
SELECT A SHAFT CATALOG NUMBER
(inches/mm)
2.75 / 70 SM70-5L SM70-5L SM70-5L SM70-5L SM70-5L SM70-5L
4.72 / 120 SM120-5L SM120-5L SM120-5L SM120-5L SM120-5L SM120-5L
7.9 / 200 SM200-5L SM200-5L SM200-5L SM200-5L SM200-5L SM200-5L
12.0 / 305 SM300-5L SM300-5L SM300-5L SM300-5L SM300-5L SM300-5L
OR OR OR OR OR OR
NEMA IEC
SELECT A HANDLE DEFEATABLE COLOR CATALOG NUMBER
TYPE TYPE
1,3R, 12 IP54 YES Black HDPB HDPB HDPB HDPB HDPB HDPB
1, 3R, 12 IP54 YES Red/Yellow HDPR HDPR HDPR HDPR HDPR HDPR
1, 3R,12 IP54 NO Black HDPBND HDPBND HDPBND HDPBND HDPBND HDPBND
1, 3R, 12 IP54 NO Red/Yellow HDPRND HDPRND HDPRND HDPRND HDPRND HDPRND
SELECT A SHAFT SHAFT LENGTH
CATALOG NUMBER
(inches/mm)
4.72/120 SD120-5L SD120-5L SD120-5L SD120-5L SD120-5L SD120-5L
7.9/200 SD200-5L SD200-5L SD200-5L SD200-5L SD200-5L SD200-5L
12.6/320 SD320-5L SD320-5L SD320-5L SD320-5L SD320-5L SD320-5L
15.75/400 SD400-5L SD400-5L SD400-5L SD400-5L SD400-5L SD400-5L
OR OR OR OR OR OR
NEMA IEC
SELECT A HANDLE DEFEATABLE COLOR CATALOG NUMBER
TYPE TYPE
1,3R, 12 IP54 YES Black HGPB HGPB HGPB HGPB HGPB HGPB
1, 3R, 12 IP54 YES Red/Yellow HGPR HGPR HGPR HGPR HGPR HGPR
1, 3R,12, 4, 4X IP65 YES Black HGPB4 HGPB4 HGPB4 HGPB4 HGPB4 HGPB4
1, 3R, 12, 4, 4X IP65 YES Red/Yellow HGPR4 HGPR4 HGPR4 HGPR4 HGPR4 HGPR4
SELECT A SHAFT SHAFT LENGTH
CATALOG NUMBER
(inches/mm)
4.72/120 SG120-5L SG120-5L SG120-5L SG120-5L SG120-5L SG120-5L
7.9/200 SG200-5L SG200-5L SG200-5L SG200-5L SG200-5L SG200-5L
12.6/320 SG320-5L SG320-5L SG320-5L SG320-5L SG320-5L SG320-5L
15.75/400 SG400-5L SG400-5L SG400-5L SG400-5L SG400-5L SG400-5L
LBS M
Rating 16 A 20 A 25 A 30 A
Approval UL508/cUL UL508/cUL UL508/cUL UL508/cUL
Short-circuit rating kA at 600 V AC w/fuse 5 5 5 5
Branch circuit fuse type RK5 RK5 RK5 RK5
Max fuse rating (A) 30 30 30 30
Maximum UL Horsepower 208V AC 3 5 7.5 7.5
ratings (3-ph) 220-240V AC 5 5 7.5 7.5
440-480V AC 10 10 15 15
600V AC 10 15 20 20
Maximum UL Horsepower 120 V AC 1 1.5 2 2
ratings (1-ph) 240 V AC 2 3 3 5
DC ratings 125 V DC 16 20 25 30
2 pole in series
Terminal lugs wire type Cu Cu Cu Cu
wire size (solid) #10-#14 #10-#14 #10-#14 #10-#14
wire size (stranded) #6-#14 #6-#14 #6-#14 #6-#14
Weight (lb) 0.32 0.32 0.32 0.32
LBS M
THERMAL CURRENT Ith (40 °C) 16 A 20 A 25 A 32 A
Rated insulation voltage Ui (V) 800 800 800 800
Rated impulse withstand Uimp (kV) 8 8 8 8
OPERATIONAL CURRENT (A)
400 V AC AC 22 A 16 20 25 32
AC 23 A 16 20 25 32
500 V AC AC 22 A 16 20 25 32
AC 23 A 16 16 20 25
690 V AC AC 22 A 16 20 25 32
AC 23 A 16 16 20 20
MOTOR POWER (KW)
400 V AC AC 23 7 9 11 15
K
500 V AC AC 23 9 9 11 15
690 V AC AC 23 11 11 15 15
OVERCURRENT CAPACITY
Short-circuit current with gG fuses (kA Rms) 50 50 50 50
Maximum rating for associated gG fuses (A) 16 20 25 32
Cut-off current (kA peak) 5.9 5.9 5.9 5.9
Short-time withstand current Icw 1s (kA) 1.2 1.2 1.2 1.2
MECHANICAL ENDURANCE (# of operations) 100 000 100 000 100 000 100 000
CONNECTION
Cu (mm2) 3p/4p 1.5 to 16 1.5 to 16 1.5 to 16 1.5 to 16
Note: 4-pole made by using modular 4th pole (see options, page K3, ie PPM16 or PPDM16)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K
SOCOMEC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K
SOCOMEC
1L1 3 L2 5 L3
2 T1 4 T2 6 T3
A 0.51 / 13
Ø 0.47 / 12
0.34�
1.5�
38
0.34� 8.5
8.5
B
B
L
1.26�
L
32
D A 30-40 A
2.13 / 54 J 4 poles
E
Ø 0.47 / 12
1.54�
1.22�
39
31
0.34�
8.5
B
K
1.22�
L
31
A B D E J K L
NUMBER
RATING OF POLES
In mm In mm In mm In mm In mm In mm In mm
LBS M 16 A
LBS M 20 A
3P 1.42 36 3.15 80 2.76 70 1.76 44.5 0.87 22 2.92 74 - -
LBS M 25 A
LBS M 30 A
LBS R 30 A 3P 2.01 51 2.76 70 2.71 69 1.66 42 1.89 48 - - 0.17 4.2
LBS R 40 A 4P 2.42 61.5 2.76 70 2.71 69 1.66 42 2.38 60.5 - - 0.17 4.2
LBS R 60 A
LBS R 80 A 3P 2.09 53 3.35 85 2.87 73 1.69 43 1.99 50.5 - - 0.17 4.2
LBS R 100 A
LBS R 125 A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K
SOCOMEC
1.50� 0.47�
0.51� 1.54� 12
38 1.26� 13 39 1.22�
32 31
2.76� 2.72�
70 69
60 - 80 - 100 - 125 A
3 poles
1.65�
42
0.59�
15
2.87�
0.17� 73
4.2
1.65� 1.69�
42 43
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K
SOCOMEC
SELECTOR HANDLE TYPE M FOR LBS M AND LBS R PISTOL HANDLE TYPE D FOR LBS M AND LBS R
2.44 0.49 1 16"
-ON
62 12.4 ø 2.2 DOOR DRILLING
90° 2.58 1.83 1 8"
16
ø 31
2.44
62
-OFF
50
OFF
2"
7 8"
ø 23
2.48
63
90°
-ON
0.69 0.31
17.5 8
1.5
38
o -OFF
50
2"
2.78
70.5
11 4" 90°
ø 31
-ON
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K
SOCOMEC
door
door
�
L� � L
L = X-1.34� L = X-1.54�
L = X-34 L = X-39
door
door
� L L�
L = X-1.10� �
L = X-1.30�
L = X-28 L = X-33
X � 1.02� X � 1.02�
3.74� 26±1 3.89� 26±1
X min = X min =
95 99
door
door
� L � L
L = X-0.79� L = X-1.02�
L = X-20 L = X-26
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 10
SOCOMEC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 11
SOCOMEC
EXTERNAL OPERATION
SELECT A HANDLE NEMA IEC DEFEATABLE COLOR CATALOG NUMBER
TYPE TYPE
1,3R, 12, 4 4X IP65 NO Black HMSB — — — —
1, 3R, 12, 4, 4X IP65 NO Red/Yellow HMSR — — — —
SELECT A SHAFT
SHAFT LENGTH CATALOG NUMBER
(inches/mm)
7.9 / 200 SM200-5 — — — —
12.6 / 320 SM320-5 — — — —
15.7 / 400 SM400-5 — — — —
OR
– or –
NEMA IEC DEFEATABLE COLOR CATALOG NUMBER
TYPE TYPE
SELECT A HANDLE
1,3R, 12 IP54 YES Black HDPB — — — —
1, 3R, 12 IP54 YES Red/Yellow HDPR — — — —
1, 3R,12 IP54 NO Black HDPBND — — — —
1, 3R, 12 IP54 NO Red/Yellow HDPRND — — — —
SHAFT LENGTH CATALOG NUMBER
(inches/mm)
4.7/120 SD120-5 — — — —
SELECT A SHAFT 7.9/200 SD200-5 — — — —
12.6/320 SD320-5 — — — —
15.7/400 SD400-5 — — — —
19.7/500 SD500-5 — — — —
– or –
OR
NEMA IEC DEFEATABLE CATALOG NUMBER
SELECT A HANDLE
TYPE COLOR
TYPE
1,3R, 12 IP54 YES Black HGPB HGPBL HGPBL HGPBL HGPBL
1, 3R, 12 IP54 YES Red/Yellow HGPR HGPRL HGPRL HGPRL HGPRL
1, 3R,12, 4, 4X IP65 YES Black HGPB4 HGPB4L HGPB4L HGPB4L HGPB4L
1, 3R, 12, 4, 4X IP65 YES Red/Yellow HGPR4 HGPR4L HGPR4L HGPR4L HGPR4L
SELECT A SHAFT SHAFT LENGTH CATALOG NUMBER
(inches/mm)
7.9/200 SG200-5 SG200-10 SG200-10 SG200-10 SG200-10
12.6/320 SG320-5 SG320-10 SG320-10 SG320-10 SG320-10
15.7/400 SG400-5 SG400-10 SG400-10 SG400-10 SG400-10
19.7/500 SG500-5 SG500-10 SG500-10 SG500-10 SG500-10
DIRECT OPERATION
SELECT A HANDLE COLOR CATALOG NUMBER
This function can be achieved using side operated 60-400 A
Black HADB1 Non-Fusible Disconnect Switches with direct handle as on page K 14
SELECT A SWITCH
EXTERNAL OPERATION
NEMA IEC
SELECT A HANDLE DEFEATABLE COLOR CATALOG NUMBER
TYPE TYPE
1,3R, 12, 4, 4X IP65 YES Black HHPB4SC HHPB4SC HHPB4SC HHPB4SC HHPB4SC
1, 3R, 12, 4, 4X IP65 YES Red/Yellow HHPR4SC HHPR4SC HHPR4SC HHPR4SC HHPR4SC
1, 3R,12, 4, 4X IP65 NO Black HHPB4NDSC HHPB4NDSC HHPB4NDSC HHPB4NDSC HHPB4NDSC
1, 3R, 12, 4, 4X IP65 NO Red/Yellow HHPR4NDSC HHPR4NDSC HHPR4NDSC HHPR4NDSC HHPR4NDSC
SELECT A SHAFT
SHAFT LENGTH
CATALOG NUMBER
(inches/mm)
7.9 / 200 SH200-15 SH200-15 SH200-15 SH200-15 SH200-15
15.7 / 400 SH400-15 SH400-15 SH400-15 SH400-15 SH400-15
DIRECT OPERATION
SELECT A HANDLE COLOR CATALOG NUMBER
Black HADB5 HADB5 HADB5 HADB5 HADB5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 13
SOCOMEC
DIRECT OPERATION
SELECT A HANDLE
PADLOCKABLE COLOR CATALOG NUMBER
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 14
SOCOMEC
UL, cUL AND CSA TECHNICAL CHARACTERISTICS FOR FRONT & SIDE OPERATION
Catalog number SCV60/SCV604 SCV100/SCV1004 SCV200/SCV2004 SCV400/SCV4004
SCV30
SCV60SO/SCV604SO SCV100SO/SCV1004SO SCV200SO/SCV2004SO SCV400SO/SCV4004SO
Rating A 30 60 100 200 400
Operating voltage V 600 600 600 600 600
Max horsepower rating/
Max motor FLA current
Three phase
208 V 5/17.5 15/48.5 25/78.5 50/150 100/286
240 V 7.5/22 15/42 30/80 60/154 125/312
480 V 15/21 30/40 60/77 125/156 250/302
600 V 20/22 50/52 75/77 150/144 350/336
DC 125 V (1) 3/25 (1) 3/25 (1) 7.5/58 (1) 15/112 (1) 20/148
DC 250 V (1) 5/20 (2) 10/38 (2) 20/72 (2) 40/140 (2) 50/173
Short circuit rating with fuses kA 65 200 200 200 200
Branch circuit fuse type J or CC J J J J
Max fuse rating (A) 30 60 100 200 400
Dimension 3 pole (front operated switches) H in 4.56 5.87 5.87 8.13 14.31
W in 3.78 6.69 6.69 9.52 11.93
D in 2.59 3.89 3.89 3.42 4.92
Shaft size square (front operated switches) in 0.2 x 0.2 0.4 x 0.4 0.4 x 0.4 0.4 x 0.4 0.4 x 0.4
mm 5x5 10 x 10 10 x 10 10 x 10 10 x 10
3-pole switch operating torque (front operation) lb. in. 21 88 88 106 130
Terminal lugs kit (# lugs per kit) Integral Integral Integral Optional (6) Optional (6)
Wire range AWG (# wire holes per lug) #10-#14 (1) #3-#10 (1) #3-#10 (1) 3/0-#6 (1) 600 kcmil-#2 (2)
Wire tightening torque lb. in. 27 58 58 200 500
(1) 2 pole in series
(2) 3 pole in series
K
Rated Insulation voltage Ui (V) V 800 750 750 750 800
Rated impulse voltage (Uimp) 8 kV 8 kV 8 kV 8 kV 8 kV
Operation current Ie (A)
400 V AC AC 22A 32 63 100 200 400
AC 23A 32 63 100 200 400
690 V AC AC 22A 32 63 100 200 400
AC 23A 32 63 100 200 315
Motor Power (kW)
400 V AC AC 23A 15 30 51 100 220
500 V AC AC 23A 18.5 40 63 140 220
690 V AC AC 23A 25 55 90 185 295
Max. peak let through current (gG) kA peak 5.5 17.6 17.6 32 40
Connection
Minimum Cu cable section mm2 6 10 25 50 185
Minimum CU busbar section mm2 — — — — —
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 15
SOCOMEC
UL, cUL AND CSA TECHNICAL CHARACTERISTICS FOR FRONT & SIDE OPERATION
Catalog number SC400 / SC4004 SC600 / SC6004 SC800 / SC8004 SC1000 / SC10004 SC1200 / SC12004
Rating 400 600 800 1000 1200
Operating voltage 600 600 600 600 600
Max horsepower rating/
Max motor FLA current
Three phase
208 V 125/360 150/415 200/554 200/554 200/554
240 V 125/312 200/480 250/602 250/602 250/602
480 V 250/302 400/447 500/590 500/590 500/590
600 V 350/336 350/336 500/472 500/472 500/472
DC 125 V (1) 20/148 (1) 20/148 — — —
DC 250 V (2) 50/173 (2) 50/173 — — —
Short circuit rating with fuses 200 200 100 100 100
Branch circuit fuse type J J L L L
Max fuse rating (A) 400 600 800 1000 1200
Dimension 3 pole (front operated switches) 12.60 12.60 13 13 13
11.02 11.02 14.64 14.64 14.64
5.51 5.51 5.51 5.51 5.51
Shaft size square (front operated switches) 0.59 x 0.59 0.59 x 0.59 0.59 x 0.59 0.59 x 0.59 0.59 x 0.59
15 x 15 15 x 15 15 x 15 15 x 15 15 x 15
3-pole switch operating torque (front operation) 320 320 320 320 320
Terminal lugs kit (#lugs per kit) Optional (6) Optional (6) Optional (6) Optional (12) Optional (12)
Wire range AWG (# wire holes per lug) 600 kcmil-#2 (2) 600 kcmil-#2 (2) 600 kcmil-#2 (3) 600 kcmil-#2 (2) 600 kcmil-#2 (2)
Wire tightening torque 500 500 500 500 500
(1) 2 pole in series
(2) 3 pole in series
Catalog number SC400 / SC4004 SC600 / SC6004 SC800 / SC8004 SC1000 / SC10004 SC1200 / SC12004
Rating 400 600 800 1000 1250
Rated Insulation voltage Ui (V) 1000 1000 1000 1000 1000
Rated impulse voltage (Uimp) 12 kV 12 kV 12 kV 12 kV 12 kV
Operation current Ie (A)
400 V AC 400 630 800 1000 1200
400 630 800 1000 1000
690 V AC 400 500 630 630 630
200 200 400 400 400
Motor Power (kW)
400 V AC 220 355 450 560 560
500 V AC 280 450 560 560 560
690 V AC 185 185 400 400 400
Max. peak let through current (gG) 48 48 75 75 75
Connection
Minimum Cu cable section 185 2 x 150 2 x 185 2 x 240 —
Minimum CU busbar section — 2 x 30 x 5 2 x 40 x 5 2 x 50 x 5 2 x 60 x 5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 16
SOCOMEC
SIRCO V 30 A
SCV30
C A
Y J J1
K1
X
B K
SIRCO V 60-100A
SCV60
SCV604
C 0.40� 1.14� J J1
SCV100 10.3 29
SCV1004
Y
K1
5� X K B
126.5
Y A K
RATING NUMBER A B C H H1 H2 H3 J J1 K K1 Y
OF
POLES In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm
V 30 A 3P 3.78 96 4.56 116 2.59 66 — — — — — — — — 1.47 37.5 0.59 15 3.13 79.5 1 25.5 1.12 28.5
3P 6.69 170
V 60 A 5.87 149 3.89 99 — — — — — — — — 1.5 38 2.75 69.5 5.25 133.5 2.63 66.5 0.95 24.5
4P 8.19 208
3P 6.69 170
V 100 A 5.87 149 3.89 99 — — — — — — — — 1.5 38 2.75 69.5 5.25 133.5 2.63 66.5 0.95 24.5
4P 8.19 208
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 17
SOCOMEC
SIRCO V 200 A
SCV200 C .40� 1.14� J J1
SCV2004 10.3 29
M8
H2
Y
K1
5� X 6.53�
K B
126.5 166
H3
H2
Y A
SIRCO V 400 A
H2
Y
K1
5� X 6.93�
B K
126.5 176
H3 H2
J
Y
A
RATING NUMBER A B C H H1 H2 H3 J J1 K K1 Y
OF
POLES In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm
3P 9.52 242 3.68 93.5
V 200 A 8.13 206.5 3.42 87 — — — — 6.87 174.5 4.39 111.5 2.44 62 7.5 190.5 3.74 95 0.95 24.5
4P 11.97 304 4.66 118.5
3P 11.93 303
V 400 A 14.31 363.5 4.92 125 — — — — 7.04 179 6.59 167.5 2.84 72 2.04 52 8.82 224 4.41 112 1.06 27
4P 14.76 375
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 18
SOCOMEC
SIRCO 400-600 A
C J
SC400
SC4004 Y J1
SC600
SC6004 Ø 0.51�
Ø 13
H
Y K1
X
K2
K B
H2 H
3.15�
H1 80
A
SIRCO 800-1000-1200 A
SC800
C 1.57� J
SC8004 40
SC1000 Y J1
Ø 0.43�
0.78� 0.78�
SC10004
20
Ø 11
SC1200
20
SC12004
H
Y
K1
X
11.42�
B K2
K 290
2 1
8.48� 8.85�
215.5 225 H K
1 2
H1 4.72�
120
A
RATING NUMBER A B C H H1 H2 J J1 K K1 K2 Y
OF
POLES In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm
400 A 3P 11.02 280 10.04 255 5 127.5
12.60 320 5.51 140 9.05 230 5.43 138 8.66 220 6.88 175 2.34 59.5 1.10 28 1.85 47
600 A 4P 14.17 360 13.19 335 6.59 167.5
800 A 3P 14.64 372 13.66 347 6.83 173.5
1000 A 13 330 5.51 140 9.05 230 5.43 138 — — 6.88 175 2.34 59.5 1.10 28 1.85 47
1200 A 4P 19.37 492 18.38 467 9.19 233.5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 19
SOCOMEC
SCV1004SO
K1
5�
Y K B
126.5
X
Y A
SIRCO V 200 A
SCV200SO C
SCV2004SO .40� 1.14� J J1
C1
10.3 29
M8
Y
H2
K1
X 5� 6.53� K B
126.5 166
H3
H2
J
Y
A
RATING NUMBER A B C C1 H2 H3 J J1 K K1 Y
OF
POLES In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm
3P 5.45 138.5
V 60 A 5.86 149 3.89 99 1.57 40 — — — — 1.49 38 2.32 59 5.25 133.5 2.62 66.5 0.96 24.5
4P 6.95 176.5
3P 7.09 180
V 100 A 5.86 149 3.89 99 1.47 37.5 — — — — 1.49 38 2.32 59 5.25 133.5 2.62 66.5 0.96 24.5
4P 9.13 232
3P 9.47 240.5
V 200 A 8.13 206.5 3.42 87 1.47 37.5 6.87 174.5 4.39 111.5 2.44 62 4.47 113.5 7.5 190.5 3.74 95 0.96 24.5
4P 11.9 302.5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 20
SOCOMEC
SIRCO V 400 A
SCV400SO
SCV4004SO C
0.40� 1.14� J J1
1.49� 10.3 29 M 10
38
H2
K1
X 5� 6.93� K
B 126.5 176
H3 H2
J
Y
RATING NUMBER A B C H2 H3 J J1 K K1 Y
OF
POLES In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm
3P 10.9 277
V 400 A 14.31 363.5 4.92 125 7.04 179 6.59 167.5 2.84 72 1.89 48 8.82 224 4.41 112 1.06 27
4P 13.74 349
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 21
SOCOMEC
5 8"
16
2.44
62
-OFF
50
OFF
2"
7 8"
ø 23
2.48
63
90°
0.69 0.31 -ON
17.5 8
1.5
38
50 2"
50 2"
o -OFF
50
2"
2.78
70.5
7.48
190
31 1 1 4 "
11 4" 90°
126.5
4.98
ø 31
-ON
G1
4.5 1 8"
G2
3.93
100
door
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 22
SOCOMEC
0.87�
min.
X 22�
1.2� 0.87�
max. min.
30.5 X 22�
1.2�
PISTOL HANDLE TYPE H max.
30.5
SC400 L = X-0.86�
L
SC4004 L = X-22
SC600
SC6004
SC800
SC8004
SC1000
SC10004
SC1200
SC12004
2.36�
KK
98
60
7.48�
190
3.35�
85
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 23
SOCOMEC
HANDLE TYPE F
HADB4
R 0.96� 0.70�
24.5� 18
�
0.84�
21.5
5.59�
142
1.29� 0.94� 0.12�
33 24 3
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 24
SOCOMEC
38.1
1�
2�
1�
1�
1� 3�
2� 3�
16�
38.8
81
28.6
1�
8�
1�
39.7
16�
9�
1�
2.4
32�
3�
1 wire 3/0 - #6 1 wire 600 MCM-2
16
9�
1�
2�
63
2�
1�
1�
3� 9�
8� 3�
16�
80
90.5
K
7�
8�
73
2�
76
3�
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 25
SOCOMEC
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 26
SOCOMEC
EXTERNAL OPERATION
SELECT A HANDLE NEMA IEC DEFEATABLE COLOR CATALOG NUMBER
TYPE TYPE
1,3R, 12, 4, 4X IP65 NO Black HMSB HMSB — — —
1, 3R, 12, 4, 4X IP65 NO Red/Yellow HMSR HMSR — — —
SELECT A SHAFT
SHAFT LENGTH CATALOG NUMBER
(inches/mm)
7.9 / 200 SM200-5 SM200-5 — — —
12.6 / 320 SM320-5 SM320-5 — — —
15.7 / 400 SM400-5 SM400-5 — — —
OR OR
NEMA IEC DEFEATABLE COLOR CATALOG NUMBER
TYPE TYPE
SELECT A HANDLE
1,3R, 12 IP54 YES Black HDPB HDPB — — —
1, 3R, 12 IP54 YES Red/Yellow HDPR HDPR — — —
1, 3R,12 IP54 NO Black HDPBND HDPBND — — —
1, 3R, 12 IP54 NO Red/Yellow HDPRND HDPRND — — —
DIRECT OPERATION
SELECT A HANDLE COLOR CATALOG NUMBER
This function can be achieved using side
Black HADB1 HADB2 operated Fusible Disconnect Switches with
direct handle as on page K 30
(1) Compact Design Fusible Disconnect Switch accommodates up to 4 auxiliary contacts for FBCC30CDT and up to 2 auxiliary contacts for FBJ30CDT on the switch
(2) ACHCD accommodates up to 4 additional auxiliary contacts for FBCC30CDT and FBJ30CDT
ACH accommodates up to 8 additional auxiliary contacts
Two AC5 or one AC6 can be side mounted
(3) See NFPA 79 requirements and our solutions page L 33
(4) HADB6 requires the use of “G” type handle (IE: HGPB)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 27
SOCOMEC
SELECT A SWITCH
AMPERE RATING 100 200 400 600 800
CATALOG NUMBER: 3 POLE FBJ100 FBJ200 FBJ400 FBJ600 FBL800
CATALOG NUMBER: 4 POLE FBJ1004 FBJ2004 FBJ4004 FBJ6004 FBL8004
FUSE CLASS J J J J L
EXTERNAL OPERATION
SELECT A HANDLE NEMA IEC
DEFEATABLE COLOR CATALOG NUMBER
TYPE TYPE
1,3R, 12 IP54 YES Black HGPBL HGPBL HGPBL — —
1, 3R, 12 IP54 YES Red/Yellow HGPRL HGPRL HGPRL — —
1, 3R, 12, 4, 4X IP65 YES Black HGPB4L HGPB4L HGPB4L HHPB4FB HHPB4FB
1, 3R, 12, 4, 4X IP65 YES Red/Yellow HGPR4L HGPR4L HGPR4L HHPR4FB HHPR4FB
1, 3R, 12, 4, 4X IP65 NO Black — — — HHPB4NDFB HHPB4NDFB
1, 3R, 12, 4, 4X IP65 NO Red/Yellow — — — HHPR4NDFB HHPR4NDFB
SELECT A SHAFT SHAFT LENGTH
CATALOG NUMBER
(inches/mm)
7.9 / 200 SG200-10 SG200-10 SG200-10 SH200-15 SH200-15
12.6 /320 SG320-10 SG320-10 SG320-10 — —
15.7/400 SG400-10 SG400-10 SG400-10 SH400-15 SH400-15
19.7/500 SG500-10 SG500-10 SG500-10 — —
DIRECT OPERATION
SELECT A HANDLE COLOR CATALOG NUMBER
This function can be achieved using side
Black operated Fusible Disconnect Switches with HADB5 HADB5
direct handle as on page K 30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 28
SOCOMEC
SELECT A SWITCH
AMPERE RATING 100 200 400 — —
CATALOG NUMBER: 3 POLE FBJ100T FBJ200T FBJ400T — —
CATALOG NUMBER: 4 POLE FBJ1004T FBJ2004T FBJ4004T — —
FUSE CLASS J J J — —
SELECT A HANDLE
NEMA IEC
DEFEATABLE COLOR CATALOG NUMBER
TYPE TYPE
1, 3R, 12, 4, 4X IP65 YES Black HGPBT4L HGPBT4L HGPBT4L — —
1, 3R, 12, 4, 4X IP65 YES Red/Yellow HGPRT4L HGPRT4L HGPRT4L — —
SELECT A SHAFT SHAFT LENGTH
CATALOG NUMBER
(inches/mm)
K
7.9 / 200 SG200-10 SG200-10 SG200-10 — —
12.6 /320 SG320-10 SG320-10 SG320-10 — —
15.7/400 SG400-10 SG400-10 SG400-10 — —
19.7/500 SG500-10 SG500-10 SG500-10 — —
OPTIONS CATALOG NUMBER
Terminal Lugs Kit (6 lugs per kit - for 3 pole fuse switches) TL100 TL200 TL400 — —
(8 lugs per kit - for 4 pole fuse switches) TL1004 TL2004 TL4004 — —
3-pole Terminal Shrouds Kit(3) (for line or load side) TS1OOFB TS2OOFB — — —
4-pole Terminal Shrouds Kit(3) (for line or load side) TS1004FB TS2004FB — — —
3-pole Terminal Screen (for line or load side) — — TS4OOFB (4)
— —
4-pole Terminal Screen (for line or load side) — — TS4004FB (4)
— —
Shorting Links Kit (3 links per kit) SL100 SL200 SL400 — —
Auxiliary Contacts Holder(2) ACH ACH ACH — —
(1) N/O, 10A, 600VAC snap-on contact block, A600-Q600 AC3 AC3 AC3 — —
(1) N/C, 10A, 600VAC snap-on contact block, A600-Q600 AC4 AC4 AC4 — —
(1) NO+NC side mount contact block, A600-N600 AC7 AC7 AC7 — —
(2) NO+NC side mount contact blocks, A600-N600 AC8 AC8 AC8 — —
(1) Compact Design fusible disconnect switch accommodates up to 4 auxiliary contacts for FBCC30CDT and up to 2 auxiliary contacts for FBJ30CDT on the switch
(2) ACHCD accommodates up to 4 additional auxiliary contacts for FBCC30CDT and FBJ30CDT, ACH accommodates up to 8 additional auxiliary contacts, Two AC7 or one AC8 can
be side mounted
(3) Line side Shrouding supplied as standard with switch
(4) As replacement part for line or load side (two terminal screens supplied as standard with switch)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 29
SOCOMEC
DIRECT OPERATION
SELECT A HANDLE
PADLOCKABLE COLOR CATALOG NUMBER
OPTIONS FOR FLANGE & DIRECT OPERATION HANDLE FROM 30 TO 60 A CATALOG NUMBER
Terminal Lugs Kit For 3 and 4 pole fuse switches Integral Integral Integral
Terminal Shrouds For 3 and 4 pole fuse switches Integral Integral Integral
Shorting Links Kit (3 links per kit - for 3 pole fuse switches) — — SL60
Auxiliary Contacts(4) (1) NO + NC side mount contact block, A600-N600 AC5 AC5 AC5
(2) NO + NC side mount contact blocks, A600-N600 AC6 AC6 AC6
SELECT A SWITCH
AMPERE RATING 100 200 400
CATALOG NUMBER: 3 POLE FBJ100SO FBJ200SO FBJ400SO
CATALOG NUMBER: 4 POLE FBJ1004SO FBJ2004SO FBJ4004SO
FLANGE OPERATED HANDLE FUSE CLASS J J J
SELECT A HANDLE
NEMA TYPE IEC TYPE DEFEATABLE PADLOCKABLE CATALOG NUMBER (1)
DIRECT OPERATION
SELECT A HANDLE
PADLOCKABLE COLOR CATALOG NUMBER
OPTIONS FOR FLANGE & DIRECT OPERATION HANDLE FROM 100 TO 400 A CATALOG NUMBER
Terminal Lugs Kit (6 lugs per kit - for 3 pole fuse switches) TL100 TL200 TL400
(8 lugs per kit - for 4 pole fuse switches) TL1004 TL2004 TL4004
3-pole Terminal Shrouds Kit (for line or load side)
(5)
TS100FB TS200FB —
4-pole Terminal Shrouds Kit(5) (for line or load side) TS1004FB TS2004FB —
3-pole Terminal Screen (for line or load side) — — TS400FB(6)
4-pole Terminal Screen (for line or load side) — — TS4004FB(6)
Shorting Links Kit (3 links per kit - for 3 pole fuse switches) SL100 SL200 SL400
Auxiliary Contacts(4) (1) NO+NC side mount contact block, A600-N600 AC5 AC5 AC5
(2) NO+NC side mount contact blocks, A600-N600 AC6 AC6 AC6
(1) Flange handle includes the flange operator and the coupling mechanism to connect switch and cable together
(2) All external metal parts are sheet steel - (3) All external metal parts are either stainless steel or a chrome-plated non-ferrous die casting
(4) Two AC5 or one AC6 can be side mounted
(5) Line side Shrouding supplied as standard with switch
(6) As replacement part (two terminal screens supplied as standard with switch)
Note: Side-external handle and shaft available, consult with factory.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 30
SOCOMEC
UL, cUL AND CSA TECHNICAL CHARACTERISTICS FOR FRONT & SIDE OPERATION
Catalog number FBCC30 / FBCC304 FBJ30 / FBJ304
FBCC30CDT FBJ30CDT FBCC30T / FBCC304T FBJ30T / FBJ304T
FBCC30SO / FBCC304SO FBJ30SO / FBJ304SO
Rating 30 30 30 30
Fuse type A CC J CC J
Operating voltage V 600 600 600 600
Max horsepower rating/
Max motor FLA current
Three phase
208 V 5/17.5 5/17.5 5/17.5 5/17.5
240 V 7.5/22 7.5/22 7.5/22 7.5/22
480 V 15/21 15/21 15/21 15/21
600 V 20/22 20/22 20/22 20/22
}
DC 125 V 2 poles in series
DC 250 V except (1)
3/25
5/20
3/25
5/20
3/25
5/20
3/25
5/20
Short circuit rating with fuses kA 65 65 100 200
Branch circuit fuse type CC J CC J
Max fuse rating (A) 30 30 30 30
Dimension 3 pole (front operated switches) H in 4.56 4.56 5.87 5.87
W in 3.78 4.13 5.63 6.72
D in 3.28 3.89 3.89 5.62
Shaft size square (front operated switches) in 0.2 x 0.2 0.2 x 0.2 0.4 x 0.4 0.4 x 0.4
mm 5x5 5x5 10 x 10 10 x 10
3-pole switch operating torque (front operation) lb. in. 21 21 53 88
Terminal lugs kit (# of lugs per kit) Integral Integral Integral Integral
Wire range AWG (# of wire holes per lug) #10-#14 (1) #10-#14 (1) #10-#14 (1) #3-#10 (1)
Wire tightening torque lb. in. 27 27 48 58
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 31
SOCOMEC
UL, cUL AND CSA TECHNICAL CHARACTERISTICS FOR FRONT & SIDE OPERATION
Catalog number FBJ60 / FBJ604 FBJ100 / FBJ1004 FBJ200 / FBJ2004 FBJ400 / FBJ4004
FBJ60T / FBJ604T FBJ100T / FBJ1004T FBJ200T / FBJ2004T FBJ400T / FBJ4004T FBJ600 / FBJ6004 FBL800 / FBL8004
FBJ60SO / FBJ604SO FBJ100SO / FBJ1004SO FBJ200SO / FBJ2004SO FBJ400SO / FBJ4004SO
Rating 60 100 200 400 600 800
Fuse type J J J J J L
Operating voltage 600 600 600 600 600 600
Max horsepower rating/
Max motor FLA current
Three phase
208 V 15/48.5 25/78.5 50/150 100/286 150/415 200/554
240 V 15/42 30/80 60/154 125/312 250/602 250/602
480 V 30/40 60/77 125/156 250/302 500/590 500/590
600 V 50/52 75/77 150/144 350/336 500/472 500/472
}
DC 125 V 2 poles in series
DC 250 V except (1)
3/25
10/38
7.5/58
20/38
15/112
40/140(1)
20/148
50/173(1)
—
—
—
—
Short circuit rating with fuses 200 200 200 200 200 200
Branch circuit fuse type J J J J J L
Max fuse rating (A) 60 100 200 400 600 800
Dimension 3 pole (front operated switches) 5.87 7.19 8.13 14.31 14.25 14.25
6.72 8.26 9.44 11.93 17.18 17.18
5.62 5.63 6 5.56 12.87 12.87
Shaft size square (front operated switches) 0.4 X 0.4 0.4 X 0.4 0.4 X 0.4 0.4 X 0.4 0.59 x 0.59 0.59 x 0.59
10 x 10 10 x 10 10 x 10 10 x 10 15 x 15 15 x 15
3-pole switch operating torque (front operation) 88 88 106 132 350 350
Terminal lugs kit (# lugs per kit) Integral Optional (6) Optional (6) Optional (6) Optional (6) Optional (6)
Wire range AWG (# of wire holes per lug) #3-#10 (1) 2/0-#14 (1) 3/0-#6 (1) 600 kcmil-#2 (2) 600 kcmil-#2 (2) 600 kcmil-#2 (3)
Wire tightening torque 58 120 200 500 500 500
(1) 3 pole in series
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 32
SOCOMEC
FUSERBLOC CD 30A CC
FBCC30CDT
C A
Y J J1
Y
K1
X
B K
H1
FUSERBLOC CD 30A J
FBJ30CDT
C
A
Y
J J1
Y
K1
X
B K
RATING NUMBER A B C H H1 H2 H3 J J1 K K1 Y
OF
POLES In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm
30A CC 3P 3.78 96 4.56 116 3.28 83.5 — — 5.19 132 — — — — 1.47 37.5 0.59 15 3.13 79.5 1 25.5 1.12 28.5
CD type
30A J 3P 4.13 105 4.56 116 3.89 99 — — — — — — — — 1.47 37.5 0.59 15 3.30 84 1 25.5 1.12 28.5
CD type
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 33
SOCOMEC
FBJ604 / FBJ604T 5� X
B K
126.5
Y A
H2
Y
K1
5� X K3 K B
126.5
H3
H2
H
Y J
10.24� A
260
RATING NUMBER A B C H H2 H3 J J1 K K1 K3 Y
OF
POLES In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm
3P 5.63 143
30A CC 5.87 149 3.89 99 — — — — — — 1.14 29 2.38 60.5 5.31 135 2.63 66.5 — — 1.21 31
4P 6.77 172
3P 6.72 171
30A J 5.87 149 5.62 143 — — — — — — 1.5 38 2.75 69.5 5.31 135 2.63 66.5 — — 0.95 24.5
4P 8.23 209
3P 6.72 171
60A J 5.87 149 5.62 143 — — — — — — 1.5 38 2.75 69.5 5.31 135 2.63 66.5 — — 0.95 24.5
4P 8.23 209
3P 8.26 210
100A J 7.19 182.5 5.63 143 4.06 103 5.27 134 3.66 93 2.05 52 3.28 83.5 6.61 168 3.28 83.5 5.55 141 1 26
4P 10.31 262
3P 9.44 240 3.68 93.5
200A J 8.13 206.5 6 152 7.27 184.5 6.87 174.5 4.79 122 2.44 62 7.56 192 3.75 95.5 6.53 166 1.03 26
4P 11.89 302 4.66 118.5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 34
SOCOMEC
H2
Y
6.53� K1
166
5� X K
B 126.5
H
H3
H2
J
Y
H1 A
Ø 0.43�
0.78� 0.78�
C
20
Ø 11
H3 J J1
20
4.17� 5.98�
106 152
H2
K1
B X K 12.67
9.52�
242 322
2
K
1
9.17�
233 H
9.52�
242
1 2
Y 4.72�
120
H1 A
RATING NUMBER A B C H H1 H2 H3 J J1 K K1 Y
OF
POLES In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm
3P 11.93 303
400A J 14.31 363.5 5.56 141.5 5.28 134.5 11.41 290 7.04 179 6.59 167.5 2.84 72 2.04 52 8.83 224 4.41 112 1.06 27
4P 14.76 375
600A J 3P 17.18 436.5 13.58 345
14.25 362 12.87 327 9.74 247.5 11.06 281 8.66 220 7.75 197 1.51 38.5 9.84 250 4.92 125 7.48 190
800A L 4P 21.9 556.5 18.30 465
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 35
SOCOMEC
Y K1
X B 5�
126.5 K
Y
A
K1
X 5� K3 K B
126.5
H3
H2
H
J
Y
A
10.24�
260
RATING NUMBER A B C H H2 H3 J J1 K K1 K3 Y
OF
POLES In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm
3P 4.37 111
30A CC 5.87 149 3.89 99 — — — — — — 1.14 29 1.97 50 5.31 135 2.63 66.5 — — 1.21 31
4P 5.51 140
3P 5.45 138.5
30A J 5.87 149 5.62 143 — — — — — — 1.5 38 2.32 59 5.31 135 2.63 66.5 — — 0.95 24.5
4P 6.95 176.5
3P 5.45 138.5
60A J 5.87 149 5.62 143 — — — — — — 1.5 38 2.32 59 5.31 135 2.63 66.5 — — 0.95 24.5
4P 6.95 176.5
3P 7.09 180
100A J 7.19 182.5 5.63 143 4.06 103 5.27 134 3.66 93 2.05 52 2.86 73 6.61 168 3.28 83.5 5.55 141 1 26
4P 9.13 232
3P 9.47 240.5
200A J 8.13 206.5 6 152 7.27 184.5 6.87 174.5 4.79 122 2.44 62 4.47 113.5 7.56 192 3.75 95.5 6.53 166 1.03 26
4P 11.9 302.5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 36
SOCOMEC
FUSERBLOC 400A J
FBJ400SO
FBJ4004SO C
1.49� 0.40� 1.14� J J1
38 10.3 29
M10
H2
K1
6.93�
176
X 5�
B K
126.5
H
H3 H2
Y J
H1 A
RATING NUMBER A B C H H1 H2 H3 J J1 K K1 Y
OF
POLES In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm
3P 10.9 277
400A J 14.31 363.5 5.57 141.5 5.29 134.5 11.42 290 7.04 179 6.59 167.5 2.84 72 1.89 48 8.82 224 4.41 112 1.06 27
4P 13.74 349
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 37
SOCOMEC
5 8"
16
2.44
62
-OFF
50
OFF
2"
7 8"
ø 23
2.48
63
90°
0.69 0.31 -ON
17.5 8
1.5
38
65ϒ 50 2"
50 2"
o -OFF
50
2"
2.78
70.5
7.48
190
31 1 1 4 "
11 4" 90°
126.5
4.98
ø 31
-ON
G1
4.5 1 8"
G2
3.93
100
door
0.87� 0.87�
min. min.
X 22� X 22�
1.2� 1.2�
max. max.
30.5 30.5
KK
PISTOL HANDLE TYPE P PISTOL HANDLE TYPE P
HADB2
HADB1
3.86�
98
4.56�
116
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 39
SOCOMEC
7.48�
190
3.35�
85
0.84�
21.5
4.01�
102
1.29�
33 0.78� 0.12�
20 3
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 40
SOCOMEC
TERMINAL LUGS
tl100 tL200 tl400
for use with FUSERBLOC 100 J for use with FUSERBLOC 200 J for use with FUSERBLOC 400 A
1� 7� 15� 17�
4� 16� 16� 32�
ø 6.9 ø 11.6 ø 23.8 ø 13.5
25
1�
38.1
1�
2�
1�
15.4
5�
8�
7� 1�
1� 3�
8� 2� 3�
16�
22.3 38.8
81
28.6
1�
8�
19.8
1�
3�
4�
39.7
16�
9�
1�
2.4
32�
3�
tl600 tl800
for use with FUSERBLOC 400 J - 600 J - 800 L
3�
8�
ø 10.2
for use with FUSERBLOC 800 L
7�
16�
ø 11
K
1�
2�
38
1�
16
9�
1�
2�
63
2�
1�
1�
3� 9�
8� 3�
16�
80
90.5
7�
8�
73
2�
76
3�
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 42
ENCLOSED DISCONNECT SWITCHES
NEMA Enclosure Type 4X 4X
3 Pole, 600V 16-125A, Non-Fused, Selector Handle 1 3R 12 4 Stainless Non-Metallic
Amp Rating Catalog No. Catalog No. Catalog No. Catalog No. Catalog No. Catalog No.
16 EALBS163RS0 EFLBS163RS0 ECLBS163RS0 EHLBS163RS0 EBLBS163RS0 EDLBS163RS0
20 EALBS203RS0 EFLBS203RS0 ECLBS203RS0 EHLBS203RS0 EBLBS203RS0 EDLBS203RS0
25 EALBS253RS0 EFLBS253RS0 ECLBS253RS0 EHLBS253RS0 EBLBS253RS0 EDLBS253RS0
K
3 Pole, 600V 30-800A, Fused, Pistol Handle 1 3R 12 4 Stainless Non-Metallic
Amp Rating Fuse Type Catalog No. Catalog No. Catalog No. Catalog No. Catalog No. Catalog No.
30, compact CC EAFBCC303RP0 EFFBCC303RP0 ECFBCC303RP0 EHFBCC303RP0 EBFBCC303RP0 EGFBCC303RP0
30, compact J EAFBJC303RP0 EFFBJC303RP0 ECFBJC303RP0 EHFBJC303RP0 EBFBJC303RP0 EGFBJC303RP0
30 CC EAFBC303RP0 EFFBC303RP0 ECFBC303RP0 EHFBC303RP0 EBFBC303RP0 EGFBC303RP0
Notes: Each of the above enclosed switches are provided with a red/yellow handle. Simply replace the “RS” or “RP” with a “BS” or “BP” to receive with a black selector or black pistol handle at no
additional cost. The non-metallic enclosures are comprised of “ED” polycarbonate boxes and “EG” polyester fiberglass boxes.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 43
ENCLOSED DISCONNECT SWITCHES
Part Numbering Guideline
ED LBS 30 3 R S O -
Color of handle: Type of handle:
Number of Auxiliary contacts:
Enclosure Type Switch Type Amp Rating R = Red/yellow S = Selector Other options
Poles See chart below
B = Black P = Pistol
Other Options
Please consult factory for availability and suffix for any other options including:
• Neutral blocks
• Special Request
- Pilot Lights
- Pushbuttons
- 2 or 3 position selector switches
Terminal lugs/shrouding are integral to the following enclosed disconnect switches: For those enclosed disconnects where terminal
- LBS (16-125A) lugs or customer supplied ring lug connections
- SCV (30-100A) are made, shrouding for the line side of the
- FBCC/FBJ (30-60A) switch is always supplied. Load side shrouds
For all other enclosed switches, terminal lugs are available for separate purchase are also available for separate purchase with
where the number following the TL represents the ampacity of the lug. part numbering as follows:
Catalog numbers for the lugs appear below: Non-Fused Fused
- TL100 - TL600 - TS200SC - TS100FB
- TL200 - TL800 - TS400SC - TS200FB
- TL400 - TL1200 - TS600SC - TS400FB
- TS1200SC - TS800FB
All enclosed switches are provided with a standard integral ground lug
Box type Switch type Ground lug wire size *IEC Enclosure Type (IP65)
IP65 16 – 30A 6mm (~#10)
2
Amp Rating Catalog #
NEMA/UL 16–60A (2) #4 – #14 16 EELBS163RSO
NEMA/UL 80 – 125A (2) 1/0 – #14 20 EELBS203RSO
NEMA/UL 200 – 400A (2)600kcmil – #2 25 EELBS253RSO
NEMA/UL 600A & above Consult Factory 30 EELBS303RSO
4X Non-Metallic 7.00 5.03 5.02 6.18 4.21 2.5 2 1 12.00 12.00 6.00 9.00 11.00 16.0 2
1 6.00 6.00 4.00 6.75 4.00 5.2 2 3R 12.00 10.00 6.00 13.00 3.00 17.6 1
60A 12 12.00 12.00 6.00 12.75 10.00 21.6 1
30A 3R 6.00 6.00 4.00 7.00 3.00 5.5 1 (SCV)
(LBSR) 12 6.00 6.00 4.00 6.75 4.00 5.2 1 UL98 4 12.00 12.00 6.00 12.75 10.00 21.9 1
UL508
4 6.00 6.00 4.00 6.75 4.00 5.4 1 4X Stainless 11.81 9.84 5.91 11.10 7.28 17.4 2
Pistol
Handle 4X Stainless 6.00 6.00 4.00 6.75 4.00 5.2 1 4X Non-Metallic 13.30 11.29 7.10 12.75 8.01 12.9 1
4X Non-Metallic 7.00 5.03 4.02 6.18 4.21 1.8 2 1 12.00 12.00 6.00 9.00 11.00 16.0 2
1 5.91 5.91 4.72 5.20 3.35 5.7 2 3R 12.00 10.00 6.00 13.00 3.00 17.6 1
100A 12 12.00 12.00 6.00 12.75 10.00 21.6 1
40A 3R 8.00 8.00 6.00 9.00 3.00 9.7 1
(SCV)
(LBSR) 12 5.91 5.91 4.72 5.20 3.35 5.7 2 UL98 4 12.00 12.00 6.00 12.75 10.00 21.9 1
UL508
4 5.91 5.91 4.72 5.20 3.35 5.8 2 4X Stainless 12.00 10.00 6.00 12.75 8.00 18.6 1
Selector
Handle 4X Stainless 5.91 5.91 4.72 5.20 3.35 5.9 2 4X Non-Metallic 13.30 11.29 7.10 12.75 8.01 12.9 1
4X Non-Metallic 7.00 5.03 5.02 6.18 4.21 2.6 2 1 30.00 20.00 8.62 27.50 15.00 68.6 2
1 6.00 6.00 4.00 6.75 4.00 5.2 2 3R 30.00 14.00 8.00 31.00 13.00 88.6 1
3R 6.00 6.00 4.00 7.00 3.00 5.5 1 200A 12 30.00 20.00 8.00 28.50 18.50 70.1 2
40A
(SCV)
(LBSR) 12 6.00 6.00 4.00 6.75 4.00 5.2 1 4 30.00 20.00 8.00 28.50 18.50 70.1 2
UL98
UL508
Pistol 4 6.00 6.00 4.00 6.75 4.00 5.4 1 4X Stainless 30.00 20.00 10.00 28.50 18.50 71.0 1
Handle 4X Stainless 6.00 6.00 4.00 6.75 4.00 5.2 1 4X Non-Metallic 32.87 25.00 11.81 34.72 22.91 59.3 1
4X Non-Metallic 7.00 5.03 4.02 6.18 4.21 1.8 2 1
1 5.91 5.91 4.72 5.20 3.35 5.8 2 3R
60A 3R 8.00 8.00 6.00 9.00 3.00 9.7 1 400A 12
(LBSR) (SCV)
12 5.91 5.91 4.72 5.20 3.35 5.8 2 UL98 4
UL508
Selector 4 5.91 5.91 4.72 5.20 3.35 5.8 2 4X Stainless
Handle 4X Stainless 5.91 5.91 4.72 5.20 3.35 5.8 2 4X Non-Metallic
4X Non-Metallic 7.00 5.03 5.02 6.18 4.21 5.9 2 1
1 8.00 8.00 6.00 5.00 7.00 8.5 2 3R
60A 3R 8.00 6.00 4.00 9.00 3.00 6.8 1 600A 12
(LBSR) (SC)
12 8.00 6.00 6.00 8.75 4.00 8.2 1 4
UL508 UL98
Pistol 4 7.87 5.91 4.72 5.20 3.35 6.7 2 4X Stainless
Handle 4X Stainless 8.00 6.00 4.00 8.75 4.00 7.0 1 4X Non-Metallic
4X Non-Metallic 7.00 5.03 4.02 6.18 4.21 2.0 2 1
1 8.00 8.00 6.00 5.00 7.00 9.1 2
K
3R
16–25A 3R 8.00 8.00 6.00 9.00 3.00 9.9 1 800A 12
(LBSM) 12 8.00 6.00 6.00 8.75 4.00 8.8 1 (SC)
UL508 UL98 4
Selector 4 7.87 5.91 4.72 5.20 3.35 7.3 2 4X Stainless
Handle 4X Stainless 7.87 5.91 4.72 5.20 3.35 7.3 2 4X Non-Metallic
4X Non-Metallic 7.00 5.03 5.02 6.18 4.21 2.9 2
1
1 10.00 8.00 6.00 7.00 7.00 10.6 2
3R
3R 10.00 8.00 6.00 11.00 3.00 11.1 1 1000A
80A (SC) 12
(LBSR) 12 10.00 8.00 6.00 10.75 6.00 12.3 1 UL98 4
UL508 4 10.00 8.00 6.00 10.75 6.00 11.8 1
4X Stainless
4X Stainless 9.84 7.87 5.91 9.13 5.31 9.8 2
4X Non-Metallic
4X Non-Metallic 9.30 7.31 4.96 8.74 4.01 6.0 1
1
1 10.00 8.00 6.00 7.00 7.00 10.6 2
3R
3R 10.00 8.00 6.00 11.00 3.00 11.1 1 1200A
100A 12
(LBSR) 12 10.00 8.00 6.00 10.75 6.00 12.3 1 (SC)
UL98 4
UL508 4 10.00 8.00 6.00 10.75 6.00 11.8 1
4X Stainless
4X Stainless 9.84 7.87 5.91 9.13 5.31 9.8 2
4X Non-Metallic
4X Non-Metallic 11.31 9.31 5.43 10.75 6.02 7.6 1
Consult factory for 400A and above ratings since enclosure sizes can vary
depending upon wiring method employed.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 45
FUSED DISCONNECT SWITCHES
MH MW
H W D Shipping
Switch Enclosure mounting mounting Figure
height width depth Weight
Rating Type height width No.
(in) (in) (in) (lbs)
(in) (in)
1 8.00 8.00 6.00 5.00 7.00 9.4 2
30A 3R 8.00 8.00 6.00 9.00 3.00 10.3 1
(FBCC 12 9.84 7.87 5.91 9.13 5.31 10.8 1
Compact)
UL98 4 9.84 7.87 5.91 9.13 5.31 10.8 1
4X Stainless 9.84 7.87 5.91 9.13 5.31 11.3 2
4X Non-Metallic 11.31 9.31 5.43 10.75 6.02 7.8 1
1 10.00 10.00 6.00 7.00 9.00 13.9 2
3R 8.00 8.00 6.00 9.00 3.00 12.1 1
30A
(FBCC) 12 10.00 8.00 6.00 10.75 6.00 14.4 1
UL98 4 10.00 8.00 6.00 10.75 6.00 13.9 1
4X Stainless 11.81 9.84 5.91 11.10 7.28 16.5 1
4X Non-Metallic 11.31 9.31 6.93 10.75 6.02 9.7 1
1 10.00 10.00 6.00 7.00 9.00 12.4 2
3R 8.00 8.00 6.00 9.00 3.00 10.6 1
30A
(FBJ 12 9.84 7.87 5.91 9.13 5.31 11.0 2
Compact) 4 10.00 8.00 6.00 10.75 6.00 13.3 1
UL98
4X Stainless 9.84 7.87 5.91 9.13 5.31 11.7 2
4X Non-Metallic 11.31 9.31 5.43 10.75 6.02 8.2 1
1 12.00 12.00 8.00 9.00 11.00 18.3 2
3R 12.00 12.00 10.00 13.00 5.00 23.2 1
30A 12 12.00 10.00 8.00 12.75 8.00 21.9 1
(FBJ)
UL98 4 13.78 11.81 7.87 13.07 9.25 22.4 2
4X Stainless 13.78 11.81 7.87 13.07 9.25 24.3 2
4X Non-Metallic 15.32 13.30 8.19 14.75 10.00 17.1 1
1 12.00 12.00 8.00 9.00 11.00 18.2 2
3R 12.00 12.00 10.00 13.00 5.00 23.1 1
60A 12 12.00 10.00 8.00 12.75 8.00 14.6 1
(FBJ)
UL98 4 13.78 11.81 7.87 13.07 9.25 24.2 2
4X Stainless 13.78 11.81 7.87 13.07 9.25 24.2 2
4X Non-Metallic 15.32 13.30 8.19 14.75 10.00 17.5 1
1 20.00 16.00 8.62 17.88 11.00 35.2 2
3R 20.00 20.00 8.00 21.00 13.00 50.3 1
100A 12 20.00 16.00 8.00 18.50 14.50 35.2 1
(FBJ)
UL98 4 20.00 16.00 8.00 18.50 14.50 39.0 2
4X Stainless 20.00 16.00 8.00 18.50 14.50 38.1 2
4X Non-Metallic 19.31 17.31 9.58 18.74 12.00 25.6 1
1 30.00 20.00 8.62 27.50 15.00 68.8 2
3R 30.00 24.00 8.00 31.00 13.00 88.8 1
Exterior Mounting - Figure 1
200A 12 30.00 20.00 8.00 28.50 18.50 70.3 2
(FBJ)
UL98 4 30.00 20.00 8.00 28.50 18.50 70.3 2 Interior Mounting - Figure 2
4X Stainless 30.00 20.00 10.00 28.50 18.50 71.2 1
4X Non-Metallic 32.87 25.00 11.81 34.72 22.91 59.5 1
1
3R
400A 12
(FBJ)
UL98 4
4X Stainless
4X Non-Metallic
1
3R
600A
(FBL) 12
UL98 4
4X Stainless
4X Non-Metallic
1
3R
800A 12
(FBL)
UL98 4
4X Stainless
4X Non-Metallic
Consult factory for 400A and above ratings since enclosure sizes can vary
depending upon wiring method employed.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 46
SOCOMEC
Application: NORMAL/EMERGENCY
K
ing possibilities (DIN rail, phase inversion
➤ By-pass (upstream and ➤ VDE 0660 Teil 107
backplate or door (1992)
mounting) downstream isolation in
➤ Large number of one operation)
configurations (I-II, I-0-II, ➤ Earthing switch
I-0-II by-pass, I-I+II-II)
➤ Choice of external and
direct handles
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 47
SOCOMEC
OPTIONS FOR I-II / I-0-II / BY-PASS / I-I+II-II CHANGEOVER SWITCHES CATALOG NUMBER
Back plate mounting device 4259 9040 4259 9040 4259 9080
DIN rail mounting device 4259 9001 4259 9001 4259 9001
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 48
SOCOMEC
OPTIONS FOR I-II / I-0-II / BY-PASS / I-I+II-II CHANGEOVER SWITCHES CATALOG NUMBER
K
Back plate mounting device 4259 9080 4259 9080 4259 9080
DIN rail mounting device 4259 9001 4259 9001 4259 9001
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 49
SOCOMEC
1.9/50
2.2/56
2.5/64
1.9
2.5
1.9
48
64
48
0.5 1.4
12.5 36 min. 2.9 0.4
75 10
L 1.9 0.5 0.4 1.9
48 12.5 10 48
25 A I - 0 - II I - II I - I+II - II I - 0 - II BY-PASS
COMO C 3P 4P 3P 4P 3P 4P 3+6P 4+8P
L 1.99/50.5 2.38/60.5 1.99/50.5 2.38/60.5 1.99/50.5 2.38/60.5 2.77/70.5 3.17/80.5
COMO C - 40 A
Door mounted with direct operation Back mounted with direct operation Back mounted with external operation
1.9/50
2.2/56
2.5/64
2.5
64
0.4
10
min. 2.9 0.4
L 2.36 0.4 2.36 75 10
60 10 60
40 A I - 0 - II I - II I - I+II - II I - 0 - II BY-PASS
COMO C 3P 4P 3P 4P 3P 4P 3+6P 4+8P
L 2.37/60.3 2.85/72.3 2.37/60.3 2.85/72.3 2.37/60.3 2.85/72.3 3.32/84.3 3.79/96.3
0.57
Back mounted with direct operation
0.57
Back mounted with external operation
1.42
K
14.5 14.5 36
1.42 1.42
36 36
2.96/75.2
2.96/75.2
2.8/71
2.8/71
0.6 0.4
16.5 min. 3.15 10
L 2.6 0.6 0.4 2.6 80
66 16.5 10 66
0.16 max�
4 max
A
B
E
Ø
C
D
8�
Ø
E 0.1
Ø
4.5
35
1.38�
8�
4.5
0.18�
0.1
Ø .5
4
9�
0.1
Ø 5
8�
0.1
Ø 4.5
D
35
1.38�
8 �
0.1
Ø 4.5
1.4
COMO C COMO C 36
1.9
48
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 52
ENGINEERED SWITCHES
K
➤ NEMA 12, 3R, 4 or 4X enclosure available.
FEATURES/BENEFITS:
➤ Fused switch – provides high current limitation and short
circuit withstand Ratings Approvals
➤ Padlockable handle – allows panel to be locked with switch ➤ 600 VAC: 30A, 60A, ➤ UL 1087 Molded-Case
in the off position ensuring load side power isolation during Switch
servicing ➤ 100A, 200A &400A
➤ Shunt trip – allows for remote tripping of the main line power ➤ UL 50
➤ Withstand rating:
prior to the application of water in elevator 200kA I.R. ➤ NEMA 1, 12, 3R, 4, 4x
➤ Sprinkler system applications
➤ UL512
➤ UL/cUL Listed Control
Panel
VOLTAGE
ES2T20R1KRN2A2 240 VAC 3
480 VAC 3
5 5 5 10 10 10 20 20 15
10 10 10 30 25 20 50 40 30
50 40 30
100 75 75
125 75 75
250 150 150
Select fusible shunt trip switch: 600 VAC 3 15 15 10 30 30 25 60 50 40 125 100 100 250 200 200
Option No. Description Catalog No. Horsepower values in the above table are intended for estimating
the size of the switch only. For light duty applications size switch
1 Control Transformer for a minimum of 1.5 times the motors full load amps. Medium O
208VAC to 120VAC T20
or General duty applications size for a minimum of 1.75 times the
240VAC to 120VAC T24
full load amps of the motor. For Heavy Duty applications use a
480VAC to 120VAC T48
600VAC to 120VAC T60 maximum of 2.25 times the full load amps of the motor.
2 Fire Safety Relay 3PDT
with Voltage Monitoring
120VAC coil R1
D W
24VDC coil R2
24VAC coil R3
3 Keyswitch
Key to test switch, 120V, with legend plate K
4 Pilot light – power enabled
Red R
Green G
White W
Yellow Y
H
5 Isolated Neutral Lug
30-60A (for 200% oversize use N1) N6
100A (for 200% oversize use N2) N1
200A (for 200% oversize use N4) N2
400A (for 200% oversize use two N4) N4
6 Mechanical Interlocked Auxiliary Contacts
1 Form C auxiliary contact A
2 Form C auxiliary contacts B
1 Form C auxiliary contacts
and 1 Form C auxiliary alarm contact C
7 Enclosure options
NEMA 1 standard - Fusible Shunt Trip Switch Dimensions and Optional Neutral Lug Sizes
NEMA 12 2 30 AMP 60 AMP 100 AMP 200 AMP 400 AMP
VOLTAGE H xWxD H xWxD H xWxD H xWxD H xWxD
NEMA 3R 3 208 VAC 3 24 x 20 x 8 24 x 20 x 8 24 x 20 x 8 30 x 24 x 8 36 x 30 x 8
NEMA 4 4 240 VAC 3 24 x 20 x 8 24 x 20 x 8 24 x 20 x 8 30 x 24 x 8 36 x 30 x 8
NEMA 4X X 480 VAC 3 24 x 20 x 8 24 x 20 x 8 24 x 20 x 8 30 x 24 x 8 36 x 30 x 8
600 VAC 3 24 x 20 x 8 24 x 20 x 8 24 x 20 x 8 30 x 24 x 8 36 x 30 x 8
Neutral Lug Size 350 - #6 350 - #6 350 - #6 500 - #4 600 - #2
Notes:
1. Options must be selected in above order for part number to be valid.
2. Elevator panels must include a control transformer, fire safety relay
with voltage monitoring and mechanical interlocked auxiliary contact.
3. Options 1, 2, and 6 are required. Options 3, 4, 5, and 7 are optional.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 54
ENGINEERED SWITCHES
FUSE
FUSE
OPTION 5
PRIMARY AUXILIARY
GND CONTACT
H1 H4
SECONDARY AUXILIARY X1 X4
CONTACT OR ALARM
CONTACT (OPTIONAL)
FUSE
GND
OPTION 3
OPTION 2
FIRE ALARM
THIS CONTACT IS FROM A FIRE DETECTING
MONITOR RELAY
DEVICE LOCATED IN THE FIELD
POWER ON
AUTO TEST OPTION 3 OPTION 4
FUSE
OPTION 5
PRIMARY AUXILIARY
GND CONTACT
K
(OPTIONAL)
H1 H4
SECONDARY AUXILIARY X1 X4
CONTACT OR ALARM
CONTACT (OPTIONAL)
FUSE
GND
OPTION 2
AUTO
OPTION 3 OPTION 4
TEST POWER ON
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 55
AC DISCONNECT SWITCHES
INNOVATIVE DESIGN PROVIDES FEATURE
PACKED AC DISCONNECT
Built for maximum performance, durability and ease of
use, Ferraz Shawmut’s AC disconnects are the solution
today’s single phase commercial and residential appli-
cations require. Available in a full range of fusible, non-
fusible, switched and pullout styles, these disconnects
are easy to install, easy to use, and rugged enough to
ensure years of reliable service. The innovative versions
with GFCI receptacles are the easiest to install in the
industry.
Designed to meet the requirements of NEC210.63,
406.8(B)(1), 440-14, Ferraz Shawmut’s AC discon-
nects feature both UL and cUL approvals. The 30 and
60 ampere units are rated for 3 and 10 horsepower at
240 VAC respectively.
Ratings
➤ 240VAC
➤ 30 or 60 amperes
Features/Benefits ➤ 10kA Short Circuit Current Rating
➤ Side opening cover affords large work area and maximum visibility
during installation and use.
➤ Pre-wired 15A GFCI and standard receptacles with stripped wire Approvals
ends makes for quick and easy installations.
➤ Angled receptacle mounting eliminates the possibility of crushing SWITCHED MODELS PULLOUT MODELS
portable electrical cord plugs when closing “while in use” cover. ➤ UL Listed ➤ UL Listed
➤ Cord holders provided on receptacle models via retaining clips to Guide WIAX Guide WGEU
secure cord with “while in use” cover. File E198597 File E198598
➤ Finger Safe Contacts provides IP20 grade of protection to safeguard ➤ cUL Guide WIAX7 ➤ cUL
both installers and end users. File E198597 Guide WGEU7
➤ Integrated hanger bracket for easy wall mounting. File E198598
➤ Captive set screws on wiring compartment cover ensures screws
can never be lost. Combination flat, phillips and hex screw heads
further simplify installation.
➤ Safety Lockout – integrated safety latch prevents unauthorized
access. ➤ NEMA 3R enclosure with high quality gray powder coat
finish featuring ultra UV protection for long life and
➤ Switched versions eliminate the risk of losing or mis-installing the durability.
pullout and clearly identifies whether the switch is in the ON or OFF
position. ➤ Multiple knockouts provide maximum installation flexibility
and mounts easily anywhere.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 56
AC DISCONNECT SWITCHES
R=self contained
15A standard (non-GFCI)
receptacle present
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
K 57
Application
Information
Need to know how?
You’ve turned to the
right place . . . literally.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
application information
FUSE DEFINITIONS
Current-Limiting Range Overload
The available fault currents a fuse will clear in less than 1/2 cycle, The operation of conductors or equipment at a current level that
thus limiting the actual magnitude of current flow. will cause damage if allowed to persist.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L
application information
FUSE DESCRIPTIONS
High voltage (over 34,500V) ➤ PT Fuses - Potential transformers require current limiting
Expulsion-Type power fuses are available for nominal voltages fuses or equivalent on the primary connection side. Standard
of 46, 69, 115, 138 and 161KV in current ratings up to 400 PT primary voltages range from 2.4kV to 36kV. Since the power
amperes. ANSI (American National Standards Institute) Standards requirement is low (for relays, metering, etc.) fuses of the proper
are followed. voltage are applied in the 1/2 to 5 ampere range. Several voltage
ratings are available, physical sizes vary among
Medium Voltage (601-34,500V) manufacturers.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L
application information
➤ If a fuse has been selected, the designer can use the curve
for that fuse to check its opening time versus a given overcur -
rent. Example: Using the 30 ampere fuse curve, what is the fuse
opening time in seconds at a current of 160 amperes? At the
bottom of the sheet (Current in Amperes) find 160 amperes (Pt.
A) and follow that line straight up to the point where it intersects
the 30A curve (Pt. B). Then follow that line to the left edge (Time
in Seconds) and read 10 seconds. (Pt. C). This tells us that the
AJT30 will open in 10 seconds on a current of 160 amperes.
➤ Likewise, for the same fuse we might want to know what cur -
rent will open the fuse in 0.1 second. On the vertical axis (Time
in Seconds) find 0.1 second (Pt. D) and follow that line to the
Time in Seconds
right until it intersects the 30A curve (Pt. E). Then follow that line
straight down to the horizontal axis (Current in Amperes) and
read 320 amperes (Pt. F). This shows that the AJT30 requires an
overcurrent of 320 amperes to open in 0.1 second.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L
application information
Overload Protection
The NEC or CEC allows fuses to be used as the sole means of
Contactor
overload protection for motor branch circuits. This approach is often
practical with small single phase motors. If the fuse is the sole
means of protection, the fuse ampere rating must not exceed the
values shown in Table 1. Overload Relay
L
wound-rotor:
Squirrel Cage
Fuse Selection Guidelines Other than Design E 300 175
What fuse type and ampere rating is best for a given application? Design E 300 175
Synchronous 300 175
The answer depends upon the application and objective to be Wound rotor 150 150
met. Here are some suggestions. Direct-current (constant voltage) 150 150
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L
application information
Minimum - This sizing is recommended if motor acceleration times do not exceed 2 seconds. Minimum sizing with RK1, RK5, and Class J fuses will provice overload relay
back up protection but may not coordinate with some NEMA Class 20 overload relays. Minimum sizing is generally not heavy enough for motors with code letter G or higher.
Typical - Suggested for most applications. Will coordinate with NEMA Class 20 overload relays. Suitable for motor acceleration times up to 5 seconds.
Heavy Load - Maximum fuse size in accordance with Table 2. If this fuse size is not sufficient to start the load, RK1, RK5, and J time delay fuse size may be increased to a
maximum of 225% of full load amperes. Class CC fuses may be increased to 400% of full load amperes. The Heavy Load column should be used for Design E and high
efficiency Design B motor fuse sizing.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L
application information
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L
application information
Minimum - This sizing is recommended if motor acceleration times do not exceed 2 seconds. Minimum sizing with RK1, RK5, and Class J fuses will provice overload relay
back up protection but may not coordinate with some NEMA Class 20 overload relays. Minimum sizing is generally not heavy enough for motors with code letter G or higher.
Typical - Suggested for most applications. Will coordinate with NEMA Class 20 overload relays. Suitable for motor acceleration times up to 5 seconds.
Heavy Load - Maximum fuse size in accordance with Table 2. If this fuse size is not sufficient to start the load, RK1, RK5, and J time delay fuse size may be increased to a
maximum of 225% of full load amperes. Class CC fuses may be increased to 400% of full load amperes. The Heavy Load column should be used for Design E and high
efficiency Design B motor fuse sizing.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 10
application information
Minimum - This sizing is recommended if motor acceleration times do not exceed 2 seconds. Minimum sizing with RK1, RK5, and Class J fuses will provide overload relay
back up protection but may not coordinate with some NEMA Class 20 overload relays. Minimum sizing is generally not heavy enough for motors with code letter G or higher.
Typical - Suggested for most applications. Will coordinate with NEMA Class 20 overload relays. Suitable for motor acceleration times up to 5 seconds.
Heavy Load - Maximum fuse size in accordance with Table 2. If this fuse size is not sufficient to start the load, RK1, RK5, and J time delay fuse size may be increased to a
maximum of 225% of full load amperes. Class CC fuses may be increased to 400% of full load amperes. The Heavy Load column should be used for Design E and high
efficiency Design B motor fuse sizing.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 11
application information
Minimum - This sizing is recommended if motor acceleration times do not exceed 2 seconds. Minimum sizing with RK1, RK5, and Class J fuses will provice overload relay
back up protection but may not coordinate with some NEMA Class 20 overload relays. Minimum sizing is generally not heavy enough for motors with code letter G or higher.
Typical - Suggested for most applications. Will coordinate with NEMA Class 20 overload relays. Suitable for motor acceleration times up to 5 seconds.
Heavy Load - Maximum fuse size in accordance with Table 2. If this fuse size is not sufficient to start the load, RK1, RK5, and J time delay fuse size may be increased to a
maximum of 225% of full load amperes. Class CC fuses may be increased to 400% of full load amperes. The Heavy Load column should be used for Design E and high
efficiency Design B motor fuse sizing.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 12
application information
TIME
are given an R rating, and not an ampere rating. An R-rated fuse will
safely interrupt any current between its minimum interrupting rating
and its maximum interrupting rating. The minimum interrupting
rating is verified during UL tests for UL component recognition.
A medium voltage starter is usually engineered for a specific Motor Full Load Currents for R-Rated Fuses*
motor and application. For this reason the starter manufacturer
selects the proper fuse R rating and provides the fuses as part of MAX. MOTOR FULL-LOAD CURRENT
the starter package. Unless the user has good reason, no devia - FUSE FOR FULL VOLTAGE START - AMPERES
tion should be made from the R rating recommended by the R RATING 10 sec. start 3 sec. start
starter manufacturer. If the user has an existing starter which is to
be applied to a new or different motor, the application should be 2R 28 32
reviewed with the starter manufacturer. Recalibration of the over - 3R 40 45
load relay(s) or fuses of a different R rating may be required. 4R 55 65
6R 80 95
Properly sized R-rated fuses should provide a service life approach - 9R 125 140
ing that of the contactor. If fuse openings are experienced with no 12R 165 190
faults present, the fuses, overload relay or both may be improperly 18R 250 280
sized. The table in this section is offered as a guideline and shows 24R 330 360
the maximum motor full load current appropriate for a given R rating. 36R 500 550
In addition to this table it is advisable to compare the fuse minimum
melt time-current curve and the nominal time-current characteristic *Note: Always round up to the next larger R rating.
curve for the overload relay. These curves should intersect at (B) no
less than 120% of motor locked rotor current (see figure). This will
assure that the contactor will open before the fuse during locked
rotor conditions.
L
The 10 or 3 Second Start listed in the table is a start during
which the motor accelerates from standstill to rated speed in 10
(or 3) seconds or less. For reduced voltage starting, motor start -
ing current should not exceed 75% of the fuse minimum melt
current for the required motor acceleration time.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 13
application information
TRANSFORMER PROTECTION
This section summarizes transformer overcurrent protection as
required by the National Electrical Code (NEC) and Canadian Secondary Fuses
Electric Code. Selecting fuses for the secondary is simple once rated secondary
current is known. Fuses are sized at 125% of secondary FLA or
Transformers - Primary 600 Volts or Less the next higher rating; or at maximum 167% of secondary FLA,
If secondary fuse protection is not provided, primary fuses are to see Table 2 for rules. The preferred sizing is 125% of rated sec -
be selected according to Table 1. If both primary and secondary ondary current Isec or next higher fuse rating. To determine Isec,
fuses are used, they are to be selected according to Table 2. first determine transformer rating (VA or kVA), secondary voltage
(Vsec) and use formula’s below.
Table 1- Primary Fuse Only 1. Single Phase : Isec = Transformer VA
Vsec
TRANSFORMER or Transformer kVA x 1000
PRIMARY MAXIMUM PRIMARY Vsec
AMPERES FUSE % RATING
2. Three Phase : Isec = Transformer VA
9 or more 125* 1.73 x Vsec
2 to less than 9 167
less than 2 300 or Transformer kVA x 1000
1.73 x Vsec
Table 2- Primary & Secondary Fuses When Isec is determined, multiply it by 1.25 and choose that
fuse rating or next higher rating. [ Isec x 1.25 = Fuse Rating ]
* Where fuse sizes do not correspond to a standard ampere rating, the next
higher standard rating shall be permitted.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 14
application information
Recommended Primary Fuses for 480 & 600 Volt, Three Phase Transformers
L
750 902 - - 1400 1600 2000 722 - - 1200 1400 1600
1000 1203 - - 1800 2000 2500 962 - - 1600 1800 2000
1500 1804 - - - 3000 4000 1443 - - 2000 2500 3000
2000 2406 - - - 4000 5000 1925 - - - 4000 4000
2500 3007 - - - 5000 6000 2406 - - - 5000 5000
*When using these fuses, the secondary of the transformer must be fused to comply with the Code.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 15
application information
A 50E rating (Ferraz Shawmut A055F1DORO-50E or equivalent) Unless special conditions are noted, the 133% primary fuse
is correct. Lower ratings may open when transformer is energized. rating is correct. For this application use a 100E rating
A155F2DORO-100E or equivalent which will allow normal
overload operations of transformer up to 133% of rating.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 16
application information
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 17
application information
The above fuses will withstand 40 x FLA for .01 second except where noted.
+
Secondary fusing required. * Fuse will withstand 30 x FLA for .01 second. ** Fuse will withstand 35 x FLA for .01 second.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 18
application information
SEMICONDUCTOR PROTECTION
Solid state devices have progressed through several generations Solid state devices have relatively short thermal time constants.
of sophistication since their introduction in the 1940s. Fuse An overcurrent which may not harm an electro-mechanical
designs have changed to match solid state protection demands. device can cause catastrophic failure of a solid state device.
The protection task looks simple- choose a fuse of correct volt - Many solid state devices have an overcurrent withstand rating
age and ampere rating which will protect a solid state device which is termed “I2t for fusing”. These values are found in most
(diode, silicon-controlled rectifier, triac, etc.) through a wide power semiconductor application handbooks.
range of overcurrents, yet carry normal rated loads without dete -
rioration through a long life. Fuses intended for solid state device protection are rated in
terms of total clearing I2t.. Fuses and devices are matched so
Solid state power devices operate at high current densities. that the total clearing I2t of the fuse is less than the withstand I2t
Cooling is a prime consideration. The fuse should be cooled with for the device.
the solid state device. Cycling conditions must be considered.
The ability of solid state devices to switch high currents at high The published fuse total clearing I2t values are derived from
speed subjects fuses to thermal and mechanical stresses. Proper short-circuit test oscillograms of the fuse under controlled
fuse selection is mandatory for long-term reliability. conditions. The end application can vary significantly from the
tested conditions. The specifier must take these differences into
account since they will affect fuse clearing I2t.
For application guidelines, request the Ferraz Shawmut publication titled Power Semiconductor Fuse Application Guide,
and the software program, Select a Fuse for Power Electronics.
2n
- 1.5
n
t is time constant in seconds Where Isc = short circuit current, n = number of time constants
L is inductance in henrys
R is resistance in ohms Example.
Given: Voltage = 600VDC
If rated voltage is applied, 63% of rated current will be reached
in one time constant.
Circuit Resistance (R) = 0.1 ohm
Circuit Inductance (L) = 1.0 x 10-3 henry L
Isc = 600 Volts = 6000 Amperes
DC Short Circuit 0.1 ohm
Graph A shows the relationship of current as a function of time t (time constant) = L/R = 1.0 x 10-3 henry = .01 second
during a DC short circuit. 0.1 ohm
In the example, if a short circuit occurs, the instantaneous cur -
rent will rise to .63 x 6000 = 3780 amperes in .01 second (one
time constant). In .05 second (5 time constants) the short-circuit
current will reach its ultimate value of 6000 amperes.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 19
application information
DC CIRCUIT PROTECTION
Typical Time Constants Table 1 shows the voltage ratings and time constants associated
The time constant of a circuit is a function of the resistance and with these standards.
inductance of the components in the circuit. Here are typical
time constants associated with the different DC voltage sources: Ferraz Shawmut fuses which have been tested and rated for
DC by third party certification agencies are shown in Table 2
Less than 10 milliseconds Battery supply of capacitor bank and Table 3. The Ferraz Shawmut Applications Engineering
Less than 25 milliseconds Bridge circuit Department should be contacted for assistance with applications
10 to 40 milliseconds Armature circuit of DC motor not served by these products.
1 second* Field winding of DC motor
* Where time constants exceed 100 milliseconds, we do not Table 1- DC Parameters of UL and MSHA Standards
recommend the use of fuses. A fuse can be used to interrupt STANDARD VOLTAGE TIME CONSTANT TEST CURRENT
short circuits in these cases, but only under conditions where
UL248 Up to 600V DC .01 second 10kA or higher
the inductance (load) is effectively by-passed.
MSHA & 300 or 600V DC .016 second 10kA or higher
Maximum parallel conductor inductance can be assumed to be less UL198M .008 second 1kA to 9.99kA
than .5 x 10–6 henry per foot of conductor. Graph B approximates .006 second 100A to 999A
conductor inductance based on conductor size and spacing. .002 second Less than 100A
Peak let-thru current (lp) and I2t are two measures of the degree
of current limitation provided by a fuse. Maximum allowable lp
and I2t values are specified in UL standards for all UL listed
current-limiting fuses, and are available on all
semiconductor fuses.
Let-Thru Current Figure 3 illustrates the use of the peak let-thru current graph.
Let-thru current is that current passed by a fuse while the fuse Assume that a 200 ampere Class J fuse (#AJT200) is to be
applied where the available fault current is 35,000 amperes
RMS. The graph shows that with 35,000 amperes RMS available,
the peak available current is 80,500 amperes (35,000 x 2.3)
and that the fuse will limit the peak let-thru current to 12,000
amperes.
Current
Time
Ip 35kA
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 21
application information
stood that the “I” in I2t is really IRMS, and the RMS is dropped for
the sake of brevity.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 22
application information
Table 2 - Class L, A4BY Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 601 800 1000 1200 1600 2000 2500 3000 4000
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp irms lp irms lp irms lp
15,000 11 24 13 29 15 35 15 35 15 35 15 35 15 35 15 35 15 35
20,000 12 26 14 32 16 37 19 43 20 46 20 46 20 46 20 46 20 46
25,000 13 29 15 34 18 40 20 46 24 55 25 58 25 58 25 58 25 58
30,000 13 30 16 36 19 43 21 49 25 58 29 67 30 69 30 69 30 69
35,000 14 32 17 38 20 45 23 52 27 61 30 70 33 76 35 81 35 81
40,000 15 34 17 40 21 47 24 54 28 64 32 73 35 79 37 86 40 92
50,000 16 36 19 43 22 51 25 58 30 68 34 78 37 86 41 95 50 115
60,000 17 38 20 45 24 54 27 62 31 72 37 84 40 91 44 100 53 121
80,000 18 42 22 50 26 59 29 67 35 80 40 92 44 100 48 110 58 133
100,000 20 45 24 54 28 64 32 73 38 87 43 99 47 108 52 119 62 143
150,000 23 52 27 62 32 73 37 84 43 99 49 113 54 123 59 137 73 167
200,000 25 56 29 67 35 80 40 91 48 110 54 123 59 136 65 150 79 181
Table 3 - Class L, A4BT Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 800 1000 1200 1600 2000
AMPERES irms lp irms lp irms lp irms lp irms lp
15,000 14 33 15 35 15 35 15 35 15 35
20,000 16 36 18 41 20 46 20 46 20 46
L
25,000 17 39 19 45 22 50 25 58 25 58
30,000 18 41 21 48 23 54 28 63 30 69
35,000 19 43 22 50 25 56 29 67 34 79
40,000 20 45 23 52 26 59 30 70 35 81
50,000 21 49 25 56 28 63 33 75 38 87
60,000 23 52 26 60 29 67 35 80 40 93
80,000 25 57 29 66 32 74 38 88 44 102
100,000 27 62 31 71 35 80 41 95 48 110
150,000 31 70 35 81 40 92 47 109 55 126
200,000 34 78 39 89 44 101 52 120 60 139
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 23
application information
Table 4 - Class RK1, A6K Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .63 1.4 1.4 3.2 2.0 4.6 3.2 7.4 4.6 11 5.0 11.5
10,000 .80 1.8 1.7 3.9 2.6 6.0 4.0 9.2 5.8 13 7.5 17
15,000 .91 2.1 2.0 4.6 2.9 6.7 4.6 11 6.7 15 8.6 20
20,000 1.0 2.3 2.2 5.1 3.2 7.4 5.0 12 7.4 17 9.5 22
25,000 1.1 2.5 2.4 5.5 3.5 8.1 5.4 12 7.9 18 10 23
30,000 1.2 2.6 2.5 5.8 3.7 8.5 5.8 13 8.4 19 11 25
35,000 1.2 2.8 2.6 6.0 3.9 9.0 6.1 14 8.9 20 11 26
40,000 1.3 2.9 2.8 6.4 4.1 9.4 6.3 14 9.3 21 12 27
50,000 1.4 3.1 3.0 6.9 4.4 10 6.8 16 10 23 13 30
60,000 1.4 3.3 3.2 7.4 4.7 11 7.3 17 11 24 14 32
80,000 1.6 3.7 3.5 8.1 5.1 12 8.0 18 12 27 15 35
100,000 1.7 3.9 3.7 8.5 5.5 13 8.6 20 13 29 16 37
150,000 2.0 4.5 4.4 9.9 6.3 14 9.9 23 14 33 19 43
200,000 2.2 4.9 4.7 11 7.0 16 11 25 16 37 20 47
Table 5 - Class RK1, A6D Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .80 1.8 1.5 3.5 2.0 4.6 3.5 8.0 5.0 12 - -
10,000 1.0 2.3 1.9 4.4 2.5 5.8 4.4 10.1 7.1 16.4 10 23
15,000 1.2 2.7 2.2 4.9 2.9 6.6 5.0 11.6 8.2 18.8 12 27
20,000 1.3 2.9 2.4 5.4 3.1 7.1 5.5 12 9.0 20.7 13 29
25,000 1.4 3.2 2.6 5.9 3.4 7.8 6.0 13.8 9.7 22.3 14 32
30,000 1.5 3.4 2.7 6.2 3.6 8.3 6.3 14.6 10.3 23.6 15 33
35,000 1.5 3.5 2.9 6.6 3.8 8.7 6.7 15.4 10.8 24.9 15 35
40,000 1.6 3.7 3.0 6.9 4.0 9.1 7.0 16.5 11.3 26 16 37
50,000 1.7 4.0 3.2 7.4 4.3 9.8 7.5 16.5 12.2 28 17 40
60,000 1.8 4.2 3.4 7.8 4.5 11 8.0 17 13 30 18 42
80,000 2.0 4.7 3.8 8.6 5.0 12 8.8 20.3 13 33 20 46
100,000 2.2 5.0 4.1 9.3 5.4 12 9.5 20 14 35 22 50
150,000 2.5 5.8 4.6 11 6.1 14 10.9 25 16 40 25 57
200,000 2.8 6.3 5.1 12 6.8 16 11 25 19 45 27 63
Table 6 - Class J, A4J Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .85 2.0 1.4 3.2 2.0 4.6 3.1 7.2 4.5 10 5.0 12
10,000 1.1 2.5 1.8 4.4 2.8 6.4 3.6 8.2 5.7 13 8.7 20
15,000 1.2 2.8 2.0 4.6 2.9 6.6 4.1 9.4 6.5 15 9.9 23
20,000 1.4 3.1 2.4 5.1 3.2 7.3 4.5 10 7.1 16 11 25
25,000 1.5 3.4 2.4 5.5 3.8 8.7 5.3 12 7.7 18 12 27
30,000 1.6 3.6 2.5 5.8 4.0 9.2 5.5 13 8.2 19 13 29
35,000 1.6 3.7 2.7 6.2 4.2 9.7 5.9 14 8.6 20 13 30
40,000 1.7 3.9 2.8 6.4 4.5 10 6.0 14 9.0 21 14 32
50,000 1.8 4.2 3.0 6.9 4.7 11 6.1 14 9.7 22 15 34
60,000 2.0 4.5 3.2 7.4 5.0 11 6.5 15 10 23 16 36
80,000 2.2 4.9 3.5 8.1 5.5 12 7.1 16 11 25 17 40
100,000 2.3 5.3 3.8 9.5 6.0 14 7.7 18 12 28 19 43
150,000 2.7 6.1 4.7 10.9 6.8 16 8.8 20 14 32 21 49
200,000 2.9 6.7 4.8 11 7.5 17 9.7 22 15 35 24 54
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 24
application information
DC CIRCUIT PROTECTION
Apparent RMS Symmetrical Let-Thru Current
Table 7 - Class J, AJT Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .79 1.8 1.2 2.8 1.8 4.0 3.1 7.0 4.8 11 5.0 12
10,000 1.0 2.3 1.6 3.6 2.2 5.1 3.8 8.8 6.0 14 8.3 19
15,000 1.2 2.6 1.8 4.1 2.5 5.8 4.4 10 6.9 16 9.5 22
20,000 1.3 2.9 2.0 4.5 2.8 6.4 4.8 11 7.6 18 11 24
25,000 1.4 3.1 2.1 4.8 3.0 6.9 5.2 12 8.2 19 11 26
30,000 1.4 3.3 2.2 5.1 3.2 7.4 5.5 13 8.7 20 12 28
35,000 1.5 3.5 2.4 5.4 3.4 7.7 5.8 13 9.1 21 13 29
40,000 1.6 3.7 2.5 5.6 3.5 8.1 6.1 14 9.6 22 13 30
50,000 1.7 3.9 2.7 6.1 3.8 8.7 6.6 15 10.3 24 14 33
60,000 1.8 4.2 2.8 6.4 4.0 9.2 7.0 16 11 25 15 35
80,000 2.0 4.6 3.1 7.1 4.4 10 7.7 18 12 28 17 38
100,000 2.2 4.9 3.3 7.6 4.8 11 8.3 19 13 30 18 41
150,000 2.5 5.7 3.8 8.7 5.4 12 9.5 22 15 34 21 47
200,000 2.7 6.2 4.2 9.7 6.0 14 10.4 24 16 37 23 59
Table 8 - Class T, A6T Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600 800
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp Irms Ip
5,000 .62 1.4 1.2 2.8 1.6 3.8 2.6 6.0 4.2 9.7 5.0 12 5.0 12
10,000 .78 1.8 1.5 3.5 2.1 4.8 3.3 7.5 5.3 12 8.2 19 10 22
15,000 .89 2.1 1.7 4.0 2.4 5.4 3.7 8.6 6.1 14 9.4 22 11 26
20,000 .98 2.3 1.9 4.4 2.6 6.0 4.1 9.5 6.7 15 10 24 12 28
25,000 1.1 2.4 2.0 4.8 2.8 6.5 4.4 10 7.2 17 11 26 13 31
30,000 1.1 2.6 2.2 5.0 3.0 6.9 4.7 11 7.7 18 12 27 14 32
35,000 1.2 2.7 2.3 5.3 3.1 7.2 5.0 11 8.1 19 12 29 15 34
40,000 1.2 2.9 2.4 5.6 3.3 7.5 5.2 12 8.5 19 13 30 16 36
50,000 1.3 3.1 2.6 6.0 3.5 8.1 5.6 13 9.1 21 14 32 17 38
60,000 1.4 3.3 2.8 6.4 3.8 8.6 5.9 14 9.7 22 15 34 18 41
80,000 1.6 3.6 3.0 7.0 4.1 9.5 6.5 15 11 25 16 38 20 45
100,000 1.7 3.9 3.2 7.5 4.5 10 7.0 16 11 26 18 40 21 48
150,000 1.9 4.4 3.8 8.6 5.1 12 8.1 19 13 30 20 46 24 55
200,000 2.1 4.9 4.1 9.5 5.6 13 8.9 20 14 33 22 51 27 61
Table 9 - Class T, A3T Fuses at 300 Volts AC, 15% Power Factor
Table 11 - Class RK1, A2D Fuses at 250 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .77 1.8 1.4 3.2 2.0 4.6 3.2 7.3 5.0 12 5.0 12
10,000 .97 2.2 1.8 4.0 2.5 5.8 4.0 9.2 6.4 15 8.0 18
15,000 1.1 2.6 2.0 4.6 2.9 6.6 4.6 11 7.3 17 9.2 21
20,000 1.2 2.8 2.2 5.1 3.2 7.3 5.0 12 8.1 19 10 23
25,000 1.3 3.0 2.4 5.5 3.4 7.9 5.4 12 8.7 20 11 25
30,000 1.4 3.2 2.5 5.8 3.6 8.3 5.8 13 9.2 21 12 27
35,000 1.5 3.4 2.7 6.1 3.8 8.8 6.1 14 9.7 22 12 28
40,000 1.5 3.5 2.8 5.7 4.0 9.2 6.4 15 10 23 13 29
50,000 1.7 3.8 3.0 6.9 4.3 9.9 6.8 16 11 25 14 32
60,000 1.8 4.0 3.2 7.3 4.6 11 7.3 17 12 27 15 34
80,000 1.9 4.5 3.5 8.1 5.0 12 8.0 18 13 29 16 37
100,000 2.1 4.8 3.8 8.7 5.4 12 8.6 20 14 32 17 40
150,000 2.4 5.5 4.3 9.9 6.2 14 9.9 23 16 36 20 46
200,000 2.6 6.0 4.8 11 6.8 16 11 25 17 40 22 50
Table 12 - Class RK5, TRS Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 1.7 3.9 3.2 7.4 3.4 7.8 5.0 12 - - - -
10,000 2.1 4.8 4.0 9.2 4.2 9.7 6.2 14 10 23 10 23
15,000 2.4 5.5 4.6 11 4.8 11 7.1 16 12 27 15 35
20,000 2.7 6.2 5.1 12 5.3 12 7.8 18 13 30 18 42
25,000 2.9 6.7 5.5 13 5.7 13 8.4 19 14 32 20 45
30,000 3.1 7.1 5.8 13 6.1 14 8.9 20 15 35 21 48
35,000 3.3 7.6 6.1 14 6.4 15 9.4 22 16 36 22 50
40,000 3.4 7.8 6.4 15 6.7 15 9.8 23 17 38 23 53
50,000 3.7 8.5 6.9 16 7.2 17 11 24 18 41 25 57
60,000 3.9 9.0 7.3 17 7.7 18 11 26 19 43 26 60
80,000 4.3 9.9 8.1 19 8.5 20 12 29 21 48 29 66
100,000 4.6 11 8.7 20 9.1 21 13 31 22 52 31 72
150,000 5.3 12 9.9 23 10 24 15 35 26 59 36 82
200,000 5.8 13 11 25 12 26 17 39 28 65 39 90
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 26
application information
BUS DUCT SHORT-CIRCUIT PROTECTION FEEDER & PLUG-IN MAXIMUM FERRAZ SHAWMUT FUSE
BUS DUCT FOR SHORT-CIRCUIT PROTECTION*
Bus duct listed to the UL 857 standard is labeled with a “short-
Short Circuit Peak Instantaneous
circuit current rating”. To earn this rating the bus duct must be
Current Rating Withstand Current 50,000A 100,000A 200,000A
capable of surviving its “short-circuit current rating” for 3 full
in Amperes in Amperes
cycles (60 Hz basis).
5000 8500 60A 60A 30A
The following table shows the potential short-circuit current rat - 7500 13,000 100A 100A 100A
ings for both feeder and plug-in bus duct. Also shown are the 10,000 17,000 200A 100A 100A
14,000 28,000 400A 400A 200A
peak instantaneous currents the bus duct must be capable of
withstanding to earn a given “short-circuit current rating”. 22,000 48,000 800A 600A 400A
25,000 55,000 1000A 600A 600A
Current-limiting fuses may be used to protect bus duct from 30,000 66,000 1200A 800A 600A
fault currents that exceed the bus duct “short-circuit current rat - 35,000 76,000 1600A 1000A 800A
ing”. The fuse will provide short-circuit protection if fuse peak
42,000 92,000 2500A 1600A 1000A
let-thru current does not exceed the bus duct peak instantaneous
50,000 110,000 3000A 2000A 1200A
withstand current. In addition, the fuse total clearing curve must 65,000 142,000 4000A 3000A 2500A
fall to the left of the bus duct short-circuit current rating at the 75,000 160,000 5000A 4000A 3000A
3 cycle (.05 sec.) point. The fuse ampere ratings shown in this
table satisfy both of these requirements. 85,000 180,000 5000A 5000A 4000A
Example:
In a 480V circuit with 100,000A available short-circuit current,
100,000
125,000
150,000
220,000
270,000
330,000
6000A
6000A
6000A
6000A
6000A
6000A
5000A
6000A
6000A
L
what maximum size fuse can be used to protect feeder bus duct * 30A to 600A fuses – Class J (time delay AJT)
which has a 42,000 short-circuit rating? Class RK1 (A2K/A6K or time delay A2D/A6D)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 27
application information
CAPACITOR PROTECTION
The primary responsibility of a capacitor fuse is to isolate a are available in a variety of voltage ratings and mounting con -
shorted capacitor before the capacitor can damage surrounding figurations. Refer to pages E 39 for specific data. Medium volt -
equipment or personnel. Typical capacitor failure occurs when age capacitor fuses are sized at 165% to 200% of the capacitor
the dielectric in the capacitor is no longer able to withstand current rating.
the applied voltage. A low impedance current path results. The
excessive heat generated builds pressure and can cause violent Capacitor fuses are selected for their ability to provide short
case rupture. A fuse will isolate the shorted capacitor before case circuit protection and to ride through capacitor inrush current.
rupture occurs. Inrush current is affected by the closing angle, capacitance,
resistance and inductance of the circuit, and varies from one
Fuse Placement application to another. Inrush lasts for less than 1/4 cycle and
The Code requires that an overcurrent device be placed in each is typically less than 25 times the capacitor’s current rating.
ungrounded conductor of each capacitor bank (see Figure 1).
The Code further requires that the rating or setting of the over- Steady state capacitor current is proportional to the applied
current device be as low as practicable. A separate overcurrent voltage and frequency. Since voltage and frequency are fixed in
device is not required if the capacitor is connected on the load power factor correction applications, the capacitor is not expect -
side of a motor-running overcurrent device. ed to be subjected to an overload. Therefore, capacitor fuses are
not selected to provide overload protectors for the capacitor.
Fusing per the Code provides reasonable protection if the
capacitors are the metalized film self-healing type. If not, each
capacitor should be individually fused as shown in Figure 2.
Ampere rating
How much overcurrent can a capacitor withstand? What
effects do neighboring capacitors have on the inrush of a given
capacitor? These and other questions influence fuse selection.
Circuit analysis can be very complex. It is best to consult the
capacitor manufacturer for specific recommendations.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 28
application information
CAPACITOR PROTECTION
KVAR vs. AMPS Example#2: What fuse would you recommend for a three
The capacitor’s current rating can be derived from its KVAR rat - phase capacitor rated 2400KV, 100kVAR?
ing by using the following formula:
Example#1: What fuse would you recommend for a three fuse size 24 x 1.65 = 39A
phase capacitor rated 100KVAR at 480 volts? 24 x 2.00 = 48A
100,000 volt-amps = 208 amps We suggest a 40 or 50 amp fuse rated at least 2400V
480 volts A250C50-XX, where XX is the type of mounting needed.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 29
application information
CABLE PROTECTION
Using Cable Protectors Placement of Cable Protectors
Cable Protectors are special purpose limiters which are used to In single phase applications where a single transformer supplies
protect service entrance and distribution cable runs. The National the service and there are only one or two conductors per phase,
Electrical Code (NEC) does not require using cable protectors. a single Cable Protector per cable may be used. The Cable
Protector should be located at the supply end of the cable. In
When unprotected cables are paralleled, a singe conductor faulting all other applications, Cable Protectors should be placed at
to ground can result in damage to and eventual loss of all parallel both ends of each cable. This allows a faulted cable to be iso -
conductors. The resultant cost of cable replacement, loss of lated from the source end and from a back feed at its load end.
service, and down time can be significant. This cost can be Isolation of a faulted cable is only possible if there are 3 or more
minimized by the use of Cable Protectors. parallel cables per phase.
When each phase consists of three or more parallel conductors, Cable Protector Ampacity
Cable Protectors are installed at each end of each conductor. Cable Protectors are not ampere rated. They are not intended to
Should one cable fault, the Cable Protectors at each end of the provide overload protection for the cable. Cable Protectors are
faulted cable will open and isolate the faulted cable. The unfaulted designed to open in case of a short circuit or after a cable has
cables will maintain service. faulted. Thus total system reliability is maximized. For these
reasons Cable Protectors are rated in terms of the cable mate -
Cable Protectors may be used as current limiters where there are rial (aluminum or copper) and the cable cable size (250kcmil,
less than three conductors in parallel, reducing potentially large 500kcmil, etc.)
fault currents down to manageable levels.
Selecting a Cable Protector
Terminations The following questions must be answered to choose the correct
In addition to improving system reliability, Cable Protectors Cable Protector:
provide a means of terminating cable, thus eliminating the need - Is the cable copper or aluminum?
for cable lugs. Cable Protectors are available with the following - What is the cable size?
configurations: - What termination type is desired?
- Is the Cable Protector to be insulated or protected with
a heat-shrink sleeve or a rubber boot?
Aluminum and copper cable require different terminations. Cable
Protectors intended for copper cable must not be used with Once these questions have been answered, the Cable Protector
aluminum cable. Cable Protectors intended for aluminum cable catalog number can be chosen from the listings.
include an oxide inhibitor.
Small Cable Sizes
Type 1 Class J fuses may be used for cable sizes smaller than 4/0.
Type 3 Since Class J blades are drilled for bolting, they may be attached
directly to bus. Cables must be prepared by installing lugs
Type 5 before bolting to the fuse. Cable-to-bus or cable-to-cable termi -
Type 6 nations are possible. The following ampere ratings are recom -
Type 8 mended, or each cable size.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 30
application information
WELDER PROTECTION
General Special Applications
Articles 630-12 and 630-32 of the National Electrical Code UL class fuses sized according to the Code may not be suitable
requires that electric welders and their supply conductors have in some welding applications. High ambient temperatures, high
overcurrent protection. The Code further requires that each cycle rates and high available fault currents may require the use
welder have a nameplate which provides information necessary of Ferraz Shawmut Welder Protectors.
for the selection of the appropriate supply conductors and
overcurrent protection devices. Welder Protectors (A4BX Type 150 or Type 150J) are special
purpose limiters which have been designed specifically for
While either circuit breakers or fuses may be used for overcur - welding applications to protect equipment in case of short
rent protection, the typically high available fault currents and the circuits. They have twice the thermal rating of UL Class fuses
need for overall system selective coordination favor the use of yet provide a low clearing I2t . This combination minimizes fuse
current-limiting fuses. fatigue and allows effective coordination with upstream devices.
Welder Protectors may be sized closer to welder primary ampere
Supply Conductor Protection rating than UL Class fuses, hence may allow the use of smaller
For AC transformer, DC rectifier and motor-generator arc welders disconnect switches.
the supply conductors should be fused at not more than 200% of
the conductor ampere rating. For resistance welders the Code allows Welder Protectors are intended for short circuit protection and
fusing at up to 300% of conductor ampere rating. In both appli - are not intended for overload protection. They should never be
cations a time delay RK5 fuse such as the Tri-onic® is generally used as the only protective device on any welder application.
recommended. Thermal overload protection must be provided in the welder by
some other device.
Welder Protection
To comply with the Code, AC transformer, DC rectifier and
motor-generator arc welders should be fused at not more than
200% of their primary current rating (shown on welder name -
plate). Resistance welders should be fused at not more than
300% of their primary current rating. As with supply conductors,
RK5 time delay fuses such as the Tri-onic® are recommended. It
should be noted that the Code states that a separate overcurrent
device is not required for the welder if the supply conductors are
protected by an overcurrent device which will satisfy the welder
overcurrent protection requirements.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 31
application information
Disconnect Switch
UL 98, UL 498
ESSENTIAL PARTS OF A MOTOR BRANCH CIRCUIT REQUIRED BY THE NATIONAL ELECTRICAL CODE:
➤ Disconnect means
➤ Branch-circuit short-circuit protective device
➤ Motor-controller
➤ Motor overload protective devices
DISCONNECT MEANS:
The Disconnect means can be a Manual Disconnect Switch according to UL 98 or UL 498.
A manual Motor Controller (according to UL 508) additionally marked “Suitable as Motor Disconnect” is only per-
mitted as a disconnecting means where installed between the final branch-circuit short-circuit and ground-fault
protective device and the motor (NEC 2005 Article 430.109).
BRANCH-CIRCUIT SHORT-CIRCUIT PROTECTIVE DEVICE:
The short-circuit protective device can be either a Fuse or an Inverse-time Circuit-breaker.
MOTOR-CONTROLLER:
Any switch or device that is normally used to start and stop a motor according to the National Electrical Code
article 430.81.
MOTOR OVERLOAD PROTECTIVE DEVICES:
The National Electrical Code permits fuses to be used as the sole means of overload protection for motor branch
circuits. This approach is often practical only with small single phase motors.
Most integral horsepower 3 phase motors are controlled by a motor starter which includes an overload relay. Since
the overload relay provides overload protection for the motor branch circuit, the fuses may be sized for short-circuit
protection.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 32
application information
DEFEATER
The defeat function allows qualified
personnel to by-pass the door
interlock when the switch is in the
ON position by means of a tool. POSITIVE OPENING OPERATION
This exclusive design is also available
in a NEMA 4 and 4X rating. 0-OFF
The positive opening operation
feature of our switches means that
I-ON
all the main contacts are ensured
to be in the open position when the
handle is in the “OFF” position.
0-OFF
I-ON
PADLOCKING
L
one off (open) and one on (closed)
position only.
2. Have an external operating means (e.g., handle).
3. Be provided with a permanent means permitting it to be locked in the off
(open) position only (e.g., by padlocks) independent of the door position. When
so locked, remote as well as local closing shall be prevented.
Handles can be padlocked in the OFF
4. Be operable, by qualified persons, independent of the door position without
position with up to 3 padlocks. Meets
the use of accessory tools or devices.
OSHA requirement for lockout/tagout.
For safety reasons, the door can not be However the closing of the disconnecting means while door is open is not
opened when the handle is padlocked. permitted unless an interlock is operated by deliberate action.
Flange and side operation:
Our side operated switches used with flange handles meet the requirements of
the NFPA 79 without any additional parts being added.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 33
application information
OFF
3F
ON
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 34
application information
1 3
Circuit breaker
Panel
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 35
application information
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 36
application information
These codes concern the auxiliary contacts and give the maximal load they can
make or break. The numerical suffix designates the maximum voltage design
values, which are to be 600, 300 and 150 volts for suffixes 600, 300 and 150
respectively. The table below gives some typical rating codes:
Example:
A contactor used at 600 VAC - 60 Hz has the following specifications:
Average consumption: - inrush 60 Hz: 1200 VA
- sealed 60 Hz: 120 VA
L
Thus a C600 rated auxiliary device is the minimum rating required.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 37
application information
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 38
application information
The degrees of protection are defined by two numbers and sometimes by an additional letter.
For example: IP 55 or IP xx B (x indicates: any value).
The numbers and additional letters are defined below:
ø 12.5 mm
Protected against water drops
Protected against solid bodies B Protected against
2 (1)
2 falling up to 15° from the verti-
greater than 12 mm access with finger
cal
ø 2.5 mm Protected against solid bodies Protected against water show- C Protected against
3 3
greater than 2.5 mm ers up to 60° from the vertical access with tool
15cm
mini
The first two numbers are defined by NF EN 60 529, IEC 529 and 1m Protected against total immer-
7
DIN 40 050 sion
Note:
(1) Fig. 2 is established by 2 tests:
• non penetration of a sphere with the diameter of 12.5 mm
• non accessibility of a test probe with a diameter of 12 mm.
(2) This additional letter only defines the access to dangerous components
Example: A device has an aperture allowing access with a finger. This will not be classified as IP 2x. However, if the components
which are accessible with a finger are not dangerous (electric shock, burns, etc.), the device will be classified as xx B.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 39
application information
AC22 DC22 Inductive and resistive mixed loads including Switches in secondary circuits or reactive circuits (capacitor
moderate overloads. banks, discharge lamps, shunt motors, etc.).
AC23 DC23 Loads made of motors or other highly Switches feeding one or several motors or inductive circuits
inductive loads. (electric carriers, brake magnet, series motor, etc.).
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 40
application information
SELECTIVITY BETWEEN 240, 480, OR 600 VOLT MAIN AND BRANCH FUSES
Definition if the downstream fuse opens while the upstream fuse remains
Coordination is defined as properly localizing a fault condition operable under all conditions of overcurrent. The term “dis -
to restrict outages to the equipment affected, accomplished by crimination” is synonymous with selectivity and is the preferred
choice of selective fault protective devices. international term for this definition.
Coordination (selectivity, discrimination) is desirable and often The word all is key. Fuse selectivity cannot be assured by com -
times mandatory. A lack of coordination can represent a hazard paring fuse time current curves alone. These curves stop at .01
to people and equipment. When designing for coordination, second. Fuse performance under high fault conditions must also
fuses provide distinct advantages over other types of overcurrent be evaluated. Fuse I2t is the best tool for assuring coordination
protective devices. under high fault current conditions. If the total clearing I2t of
the downstream fuse is less than the melting I2t of the main
To coordinate a circuit breaker protected system, it is generally upstream fuse, the fuses will be selective under high fault
necessary to intentionally delay the short circuit response of conditions.
upstream breakers. Though coordination may be achieved, short
circuit protection is compromised. The speed and consistency To simplify presenting weighty I2t data, selectivity information
of response of fuses allows coordination without compromising can simply be found in selectivity ratio tables.
component protection.
The ratios found in the following tables are conservative and are
The terms coordination and selectivity are often used inter - appropriate for all overcurrents up to 200,000 amperes RMS. In
changeably. The term coordination should be used to describe a some cases smaller ratios than shown may be used. Consult your
system as defined above, while two fuses are said to be selective Ferraz Shawmut representative for specific recommendations.
Fuse Selectivity Ratios - 600 and 480 Volt Applications Up to 200,000 RMS Symmetrical Amperes
RATIO (For fuses rated 61 – 600A)
BRANCH M A I N F U SE
FUSE A4BQ A4BY A4BT TRS A6K A6D A4J AJT A6T
A4BQ 2:1 2:1 2:1 - - - - - -
A4BY - 2.5:1 2:1 - - - - - -
A4BT 2.5:1 2.5:1 2:1 - - - - - -
TRS 4:1 4:1 3:1 2:1 4:1 4:1 4:1 3:1 4.5:1
A6K 2:1 2:1 1.5:1 1.5:1 2:1 2:1 3:1 2:1 3.5:1
A6D 2:1 2:1 1.5:1 1.5:1 2:1 2:1 3:1 2:1 3.5:1
A4J 2:1 2:1 1.5:1 1.5:1 2:1 2:1 2:1 2:1 3:1
AJT 2:1** 2:1** 2:1 1.5:1 2:1 2:1 2.5:1 2:1 3.5:1
A6T 3:1 2.5:1 2:1 1.5:1 2:1 2:1 2:1 2:1 2.5:1
Fuse Selectivity Ratios - 240 Volt Applications Up to 200,000 RMS Symmetrical Amperes
RATIO (For fuses rated 61 – 600A)
BRANCH M A I N F U SE
FUSE A4BQ A4BY A4BT TR A2K A2D A4J AJT A3T
A4BQ 2:1 2:1 2:1 - - - - - -
A4BY -
A4BT
TR
2.5:1
4:1
2.5:1
2.5:1
4:1
2:1 - - - - - -
2:1 - - - - - -
4:1 1.5:1 4:1 3:1 4:1 3:1 5:1
L
A2K 2:1 2:1 1.5:1 1.5:1 2:1 1.5:1 2:1 1.5:1 3:1
A2D 2.5:1 2.5:1 2:1 1.5:1 2:1 1:5:1 2:1 2:1 3:1
A4J 2:1 2:1 1.5:1 1.5:1 2:1 1.5:1 2:1 2:1 3:1
AJT 2:1 2:1 2:1 1.5:1 2.5:1 2:1 2.5:1 2:1 3:1
A3T 1.5:1 1.5:1 1.5:1 1.5:1 1.5:1 1.5:1 1.5:1 1.5:1 2:1
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 41
application information
Example 1:
What is the potential short circuit current at various points in a
480V, 3-phase system fed by a 1000KVA, 5.75%Z transformer?
(Assume primary short circuit power to be 500MVA.)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L
L 42
42
application information
3φ to 3φ
480V 208V
40,000A 14,500A
100kVA
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L
L 43
43
application information
A3- Factors for Single Phase Transformer in A3- Single Phase Transformer Factors
Three Phase System
FACTOR
Transformer connections must be known before factor can be TRANSFORMER 1 PHASE VOLTAGE
determined. See Figures A and B.
120V 240V 120V
KVA %Z FIG. A FIG. A FIG. B
1. Determine system factor at 1φ transformer primary, with 480V
pri., 120/240V sec. (Figure A) 15 2.5 34.6 48.0 24.0
25 2.5 20.7 28.8 14.4
Example: Isc @480V = 40,000A, 3φ. Factor is 3.00 (from
37.5 2.8 16.6 23.0 11.5
Scale 1).
50 3.0 12.5 17.3 8.65
75 3.0 8.28 11.5 5.75
1φ factor = 3φ factor = 3.00 = 3.46 100 3.0 6.22 8.64 4.32
.866 .866 150 2.5 3.46 4.80 2.40
167 2.5 3.10 4.31 2.16
2. Adjust factor in proportion to voltage ratio of 480/240V transformer. 225 2.5 2.30 3.20 1.60
Example: For 240V, 1φ factor is (240 ÷ 480) 3.46 = 1.73 300 3.0 2.07 2.88 1.44
500 4.5 1.86 2.59 1.30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 44
application information
L
350 8.60 7.40 3.70 3.00 7.49 6.50 3.07 2.45
400 8.30 7.20 3.60 2.90 6.87 5.95 2.98 2.38
500 7.40 6.40 3.20 2.60 6.12 5.31 2.66 2.13
600 7.20 6.20 3.10 2.44 5.30 4.59 2.29 1.83
750 6.50 5.60 2.80 2.22 4.85 4.20 2.10 1.69
Note: For parallel runs divide factor by number of conductors per phase.
Example: If factor for a single 500kcmil conductor is 2.49 then the factor for a run having 3-500kcmil per phase
is 2.49 ÷ 3 = .83 (Example from Table B, 480 volts)
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 45
application information
* These factors may be used with feeder duct manufactured by I-T-E, GE, Square D and Westinghouse. 55,000
50,000
2.5
D1- Factors for Plug-In** Bus Duct (Per 100’) 45,000
FACTOR
DUCT 3 PHASE VOLTAGE 3 40,000
AMPERE COPPER ALUMINUM
RATING 208 240 480 600 208 240 480 600 35,000
400 2.53 2.18 1.09 .89 3.88 3.34 1.67 1.36
600 2.53 2.18 1.09 .89 2.41 2.07 1.04 .84 4 30,000
800 1.87 1.61 .81 .66 2.41 2.07 1.04 .84
1000 1.87 1.61 .81 .66 1.69 1.45 .73 .59 25,000
5
1200 1.47 1.26 .63 .51 1.43 1.22 .61 .50
1350 1.26 1.08 .54 .44 1.30 1.12 .56 .45 6 20,000
1600 .91 .78 .39 .32 1.09 .94 .47 .38 7
2000 .79 .68 .34 .28 .89 .77 .38 .31 8 15,000
9
2500 .61 .52 .26 .21 .66 .57 .28 .23 10
3000 .48 .42 .21 .17 .59 .51 .25 .21 11
12 10,000
4000 .43 .37 .18 .15 .46 .40 .20 .16 9,000
14
5000 .38 .33 .16 .13 .35 .30 .15 .12 16 8,000
18 7,000
20 6,000
** These factors may be used with plug-in duct manufactured by GE, Square D and Westinghouse. 22
24 5,000
40 3,000
60 2,000
80 1,500
100
120 1,000
SCALE 1
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 46
application information
PROPERTIES OF MATERIALS*
FUSE BLOCKS, FUSE HOLDERS, POWER DISTRIBUTION BLOCKS, FUSES & ACCESSORIES
Tensile Strength psi D638 7,000 9,000 25,000 20,000 17,600 26,000 12,000
Compressive Strength psi D695 28,800 12,500 34,000 29,000 - - -
Water Absorption 24 hrs % D570 0.45 0.15 1.3 0.05 0.1 0.18 1.5
Hardness Rockwell D785 M-110 M-85 R-105 R-120 - - -
Dielectric Strength
60 hertz, 25ºC, s/t vpm - 300 425 435 460 500 460 432
60 hertz, 25ºC, s/s vpm - 250 425 - 355 - - -
Dielectric Constant
60 hertz–dry - D150 5.96 3.01 - 3.8 - - -
1 Mhertz–dry - D150 4.9 2.96 3.6 3.7 3.8 4.9 3.6
Volume Resistivity ohm-cm D257 50 x 10 6
>10 16
1016
>10 15
>10 16
3 x 10 16
>10 16
Heat Deflection ºF D648 320 270 410 435 330 523 167
(ºF @ 264 psi)
Flammability (UL 94) - - 94 V-0 94 V-0 94 V-0 94 V-0 94 V-0 94 V-0 94 V-0
Relative Thermal Index (RTI)
(UL746B)
Electrical ºC - 150 125 150 155 150 140 140
Mechanical without impact ºC - 150 125 140 155 150 130 110
61XXXX PDB USM GPM SHR AOS FSPDB
62XXXX DRM USCC FEB EI
64XXXX DFC US3J FEX
22XXXX 603XXX US6J IL
24XXXX 203XXX US14 TPMOV
26XX 206XXX US22 Surge Trap
Product Types P266 303XXX CC 1SC
and P243 306XXX MSC
L
Families 1MSC P243X NH
PS2OX127 703XX
FHXXX U705XX
U710XX
21XXXX
61XXXSJ
*Note: Above data represents approximate values and are for reference only.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 47
application information
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 48
application information
RULES FOR EQUIPMENT SHORT CIRCUIT RATING 11 REASONS FOR USING CURRENT-LIMITING FUSES
The National Electric Code (2002) states: ➤ ARC FLASH REDUCTION
Current limiting fuses, when applied within their current
110-9. Interrupting Rating limiting range, reduce personnel exposure to incident
“Equipment intended to interrupt current at fault levels shall have arc flash energy. Non fused systems may need extensive
an interrupting rating sufficient for the nominal circuit voltage re-engineering to reduce arc flash hazards, and improve
and the current that is available at the line terminals of the equip - personnel safety.
ment. Equipment intended to interrupt current at other than fault
levels shall have an interrupting rating at nominal circuit voltage ➤ SAFETY
sufficient for the current that must be interrupted.” Overcurrent protective devices which operate are often reset
without first investigating to find the cause of opening.
Enclosed fusible switches whether for individual wall mounting Electro-mechanical devices which have opened high level
or in equipment assemblies, are “equipment intended to faults may not have the reserve capacity to open a 2nd or 3rd
interrupt current”. With this in mind, both the switch and the fault safely. When a fuse opens it is replaced with a new fuse,
fuse must be adequately rated to satisfy code requirements. thus protection is not degraded by previous faults.
The fuse must have an interrupting rating greater than the short ➤ RELIABILITY
circuit current available at the line terminals of the switch. The No moving parts to wear or become contaminated by dust,
switch must have a short circuit current rating greater than the oil or corrosion.
short circuit current available at the line terminals of the switch.
➤ LONG LIFE
UL98 “Enclosed and Dead-Front Switches” requires that Listed The speed of response of a fuse will not change or slow
switches be tested with fuses to establish the short circuit cur - down as the fuse ages. In other words, the fuse’s ability to
rent withstand rating of the switch. The switch is then required to provide protection is not adversely affected by the passage
be marked with its withstand rating, the appropriate UL fuse class of time.
and maximum circuit voltage.
➤ MINIMAL MAINTENANCE
Fuses do not require periodic recalibration as do electro
mechanical overcurrent protective devices.
➤ COMPONENT PROTECTION
The current limiting action of a fuse minimizes or eliminates
component damage.
➤ SELECTIVITY
Fuses may be easily coordinated to provide selectivity under
both overload and short circuit conditions.
➤ COST EFFECTIVE
L
Fuses are generally the most cost effective means of
providing overcurrent protection. This is especially true
where high fault currents exist or where small components
need protection.
➤ EXTENDED PROTECTION
Devices with low interrupting ratings are often rendered
obsolete by service upgrades or increases in available fault
current. Non-fused systems may need expensive system
upgrades to maintain system safety.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 49
application information
2.0 Mains, Feeders and Branch Circuits F. Supplementary lighting and control circuits in the connected
combinations shown up to 600VAC and 24 amps shall be pro -
A. Circuits 601 to 6000 amperes shall be protected by current- tected by Ferraz Shawmut Amp-Trap 2000® Class CC time-delay
limiting Ferraz Shawmut Amp-Trap 2000® Class L time-delay ATQR or ATDR fuses, sized according to the fixture manufacturers
A4BQ fuses. Fuses shall be time-delay and shall hold 500% of recommendations.
rated current for a minimum of 4 seconds, clear 20 times rated
current in .01 second or less and be UL Listed and CSA Certified 3.0 Spares
with an interrupting rating of 200,000 amperes rms symmetrical. Spare fuses amounting to 10% (minimum three) of each type
and rating shall be supplied by the electrical contractor. These
B. Circuits 600 amperes or less shall be protected by current- shall be turned over to the owner upon project completion. Fuses
limiting Ferraz Shawmut Amp-Trap 2000® Class RK1 time-delay shall be contained and cataloged within the appropriate number
A2D (250V) or A6D (600V) or Class J time-delay AJT fuses. of spare fuse cabinets (no less than one). Spare fuse cabinets
Fuses shall hold 500% of rated current for a minimum of 10 shall be equipped with a key lock handle, be dedicated for storage
seconds (30A, 250V Class RK1 case size shall be a minimum of spare fuses and shall be GSFC, as supplied by Ferraz Shawmut.
of 8 seconds) and shall be UL Listed and CSA Certified with an
interrupting rating of 200,000 amperes rms symmetrical. 4.0 Execution
A. Fuses shall not be installed until equipment is to be energized.
C. Motor Protection All fuses shall be of the same manufacturer to assure selective
All individual motor circuits shall be protected by Ferraz coordination.
Shawmut Amp-Trap 2000® Class RK1, Class J or Class L time-
delay fuses as follows: B. As-installed drawings shall be submitted to the engineer after
completion of the job.
Circuits up to 480A: Class RK1 - A2D (250V) or A6D(600V)
Class J - AJT C. All fusible equipment rated 600 amperes or less shall be
equipped with fuse clips to accept Class RK1 or Class J fuses as
Circuits over 480A: Class L - A4BQ noted in the specifications.
Fuse sizes for motor protection shall be chosen from tables 5.0 Substitution
published by Ferraz Shawmut for the appropriate motor rating. Fuse sizes and types indicated on drawings are based on Ferraz
Heavy load and maximum fuse ratings are also shown for appli - Shawmut Amp-Trap 2000® fuse current-limiting performance
cations where typical ratings are not sufficient for the starting and selectivity ratios. Alternative submittals to furnish materials
current of the motor. other than those specified, shall be submitted to the engineer
in writing two weeks prior to bid date, along with a short circuit
D. Motor Controllers and selective coordination study.
Motor controllers shall be protected from short circuits by Ferraz
Shawmut Amp-Trap 2000® time-delay fuses. For Type 2 protec -
tion of motor controllers, fuses shall be chosen in accordance
with motor control manufacturers’ published recommendations,
based on Type 2 test results. The fuses shall be Class RK1
A2D (250V) or A6D (600V) or Class J AJT or Class CC ATDR
(600V).
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
L 50
Condensed Cross Reference
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
INDEX 1
Index of Products and Information
Part Number Description Page Part Number Description Page
A2Y Amp-Trap Form 600 Fuse,250V G23 CC 1500 CP DC Rated, special purpose round body fuse, G50
A300C Medium Voltage Capacitor Fuse, 3000V E39 gRC 20x190 1500V
A30QS Amp-Trap Form 101 Semicond. Fuse, 300V D7 CC 1500 CP DC Rated, special purpose round body fuse, G52
A3T Amp-Trap Class T Fuse, 300V B23 gRC 36x190 1500V
A430C Medium Voltage Capacitor Fuse, 4300V E39 CC 1500 CP gRD DC Rated, special purpose round body fuse, G48
A480R R-Rated 4.8kV Medium Voltage E26 1500V
A480T Potential Transformer Fuse, 4.8kV E36 CC 1551 CP gRB DC Rated, special purpose round body fuse, G48
A4BQ Amp-Trap 2000 Class L T-D Fuse,600V A5 1000V
A4BT Amp-Trap Class L Fuse, 600V B20 CC 1591 CP DC Rated, special purpose round body fuse, G50
A4BX Welder Protector, 600V G21 gRC 20x190 1500V
A4BY Amp-Trap Class L Fuse, 600V B17 CC 1591 CP DC Rated, special purpose round body fuse, G52
A4J Amp-Trap Class J Fuse, 600V B14 gRC 36x190 1500V
A500T Potential Transformer Fuse, 5.0kV E36 CC 20 SRC 120 QF DC Rated, special purpose square body fuse, G70
A50P Amp-Trap Form 101 Semicond. Fuse, 500V D16 2000V
A50QS Amp-Trap Form 101 Semicond. Fuse, 500V D12 CC 20 SRD 122 QF DC Rated, special purpose square body fuse, G72
A550C Medium Voltage Capacitor Fuse, 5500V E39 1800V, 2000V
A60Q Amp-Trap Form 101 Semicond. Fuse, 600V D18 CC 35 gRB 600 QF DC Rated, special purpose square body fuse, G74
A60X Amp-Trap Form 101 Semicond. Fuse, 600V D20 3500V
A6D Amp-Trap 2000 Class RK1 T-D Fuse, 600V A8 CC 40 gRB 600 QF DC Rated, special purpose square body fuse, G74
A6K Amp-Trap Class RK1 Fuse, 600V B27 4000V
A6T Amp-Trap Class T Fuse, 600V B23 CC 40 gRD 600 QF DC Rated, special purpose square body fuse, G74
A6Y Amp-Trap Form 600 Fuse,600V G23 4000V
A6Y-2B Amp-Trap Form 600 Midget Fuse, 600V C3 CC 4000 CP gRC DC Rated, special purpose round body fuse, G54
A70P Amp-Trap Form 101 Semicond. Fuse, 700V D36 4000V
A70Q Amp-Trap Form 101 Semicond. Fuse, 700V D38 CC 6,621 CP gRB DC Rated, special purpose round body fuse, 660V G40
A70QS-14F Amp-Trap Semicond. French. Cyl. Fuse, 700V D28 CC 6.6 gRB 123 DC Rated, special purpose square body fuse, 660V G62
A70QS-22F Amp-Trap Semicond. French. Cyl. Fuse, 700V D28 CC 6.6 gRB 2123 DC Rated, special purpose square body fuse, 660V G66
A70QS-4 Amp-Trap Form 101 Semicond. Fuse, 700V D32 CC 7,5 gRB 123 DC Rated, special purpose square body fuse, 750V G62
A720T Potential Transformer Fuse, 7.2kV E36 CC 7,5 gRB 2123 DC Rated, special purpose square body fuse, 750V G66
A825X 8.25kV CS-3 Medium Voltage Fuse E2 CC 7,5 gRC 120 DC Rated, special purpose square body fuse, G56
ACK Fork Lift Truck Fuse 1-400A, 125VAC G31 750V, 900V
ACL Fork Lift Truck Fuse 30-120A, 125VAC G31 CC 7,5 gRC 121 DC Rated, special purpose square body fuse, G58
AF Automotive Plastic Body/Silver-Plated Terminal C22 750V, 900V
Fuses CC 7,5 gRC 122 DC Rated, special purpose square body fuse, G60
AF2 Automotive Plastic Body/Silver-Plated C22 750V, 900V
Terminal Fuses CC 7,5 gRC 123 DC Rated, special purpose square body fuse, G62
AF2H Automotive Fuse Holders C23 750V, 900V
AF3 Automotive Plastic Body/Silver-Plated C22 CC 7,5 gRC 2122 DC Rated, special purpose square body fuse, G64
Terminal Fuses 700V, 900V
AF3H Automotive Fuse Holders C23 CC 7,5 gRC 2123 DC Rated, special purpose square body fuse, G66
AFH Automotive Fuse Holders C23 750V, 900V
AG Amp-Trap Class G Fuse, 480V B35 CC 7,5 gRD 2122 DC Rated, special purpose square body fuse, G64
AJT Amp-Trap 2000 Class J T-D Fuse,600V A2 700V, 900V
ALS Fork Lift Truck Fuse 100-500A, 125VAC G31 CC4.421 CP gLB DC Rated, special purpose round body fuse, 440V G38
AOS-S, AOS-Q Blown Fuse Indicators J7 CNL Fork Lift Truck Fuse 35-500A, 32V AC/DC G31
Application Info. Circuit Protection L2 CNN Fork Lift Truck Fuse 10-800A G31
ATDR Amp-Trap 2000 Class CC T-D Fuse, 600V A13 COU,COW,COX,COY Box Cover Units J2
ATM Amp-Trap Midget Fuse, 600V C4 COY-B, CSY-L, CSY-RL Box Cover Units J3
ATMR Amp-Trap Class CC Fuse, 600V B37 CP…A Amp-Trap Cable Protectors, 600V, Al Cable G11
ATQ Amp-Trap Midget Time Delay Fuse, 600V C2 CP…C Amp-Trap Cable Protectors, 600V, Cu Cable G11
ATQR Amp-Trap 2000 Class CC T-D Fuse, 600V A16 CRN & CRS Class H Canadian Fuses F40
C & CNS Class CA & CB Canadian Fuses F36 Cross Reference Competitor to Ferraz Shawmut XREF
C08915P-19P Fuse Clips for Ferrule type Fuses H65 CRU,CRW,CRX,CRY Box Cover Units J2
CC 1051 CP DC Rated, special purpose round body fuse, G44 CSU,CSW,CSX,CSY Box Cover Units J2
gRB 20x127 1000V CTY, CCY, CKA Box Cover Units J3
CC 1051 CP DC Rated, special purpose round body fuse, G46 DCT 1000V DC Ferrule Fuses G42
gRB 36x127 1000V DFC-1...DFC-9I Dead Front Fuse Covers H64
CC 12 SRG 72 QF DC Rated, special purpose square body fuse, G68 DFC3M, DFC3LP, DRM Dead Front Safety Pullers H66
1200V DS Series AC Disonnect Switch K56
CC 1500 CP gRB DC Rated, special purpose round body fuse, G48 EAFB.. Enclosed Disconnect Switch K42
1000V EALBS.. Enclosed Disconnect Switch K42
EASC.. Enclosed Disconnect Switch K42
EBFB.. Enclosed Disconnect Switch K42
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
INDEX 2
Index of Products and Information
Part Number Description Page Part Number Description Page
EBLBS.. Enclosed Disconnect Switch K42 MC .. PSC Microswitch J8
EBSC.. Enclosed Disconnect Switch K42 MC2R3E.. Protistor Microswitch J11
ECFB.. Enclosed Disconnect Switch K42 MC3E.. Protistor Microswitch J11
ECLBS.. Enclosed Disconnect Switch K42 MCR3E.. Protistor Microswitch J11
ECSC.. Enclosed Disconnect Switch K42 MRF, MRT Radial Lead Micro Fuses C20
EDLBS.. Enclosed Disconnect Switch K42 MS 4L.. PSC Microswitch J8
EFFB.. Enclosed Disconnect Switch K42 MS PA.. PSC Microswitch J8
EFLBS.. Enclosed Disconnect Switch K42 MS3V.. PSC Microswitch J8
EFSC.. Enclosed Disconnect Switch K42 MS7V.. PSC Microswitch J8
EGFB.. Enclosed Disconnect Switch K42 NIT & NS HRCII Canadian Fuses BS88 F37
EGSC.. Enclosed Disconnect Switch K42 NRN & NRS Class H Canadian Fuses F39
EHFB.. Enclosed Disconnect Switch K42 OT One-Time Fuse,Class K-5, 250V B39
EHLBS.. Enclosed Disconnect Switch K42 OTM One-Time Midget Fuse, 250V C8
ES Series Fusible Shunt Trip Engineered Disconnect Switch K53 OTN O-T Fuse, Class K-5, (Canadadian “P”) 250V B39
FBCC, FBJ, FBL Series Fusible Disconnect Switch K26 OTS One-Time Fuse,Class K-5, 600V B39
FEB, FEC, FEX, FEY In-Line Breakaway Fuse Holders H17 P243, P266, P292 Semiconductor Fuse Blocks H44
FES Canadian Class C Fuses F33 PCF PC Mount Fast-Acting Fuse C25
FESC Canadian Class C Fuses F33 PCS PC Mount Semiconductor Protection Fuse C26
FESF Canadian Class C Fuses F33 PCT PC Mount Time Delay Fuse C28
FSB1, FSB2 In-Line Fuse Holder Boot H17 PS 20x127 Fuse Holders & no-load disconnectors H48
FSFE Automotive SFE fuse C21 R132 - R642 Fuse Reducers Class RK1& RK5 J4
FSM Multi-Meter Fuse, 1000V C6 RF Renewable Fuse, 250V B42
FSPDB Finger-Safe Power Distribution Blocks I2 RFS Renewable Fuse, 600V B42
G Standard Plug Fuse-Non T-D CSA G37 RL Renewable Links, 250V, for RF Fuse B42
GAB 1/4” x 1” Ceramic Body Fuse C18 RLS Renewable Links, 600V, for RFS Fuse B42
GDG 5 mm x 20 mm Glass Body Fuse C16 SBS 1-3/8”x13/32” Fuses, 600V C12
GDG-V 5 mm x 20 mm Glass Body Fuse C16 SC Series Non-Fusible Disconnect Switch K11
GDL 1/4”x1-1/4” Glass Body Time Delay Fuse C13 SDC5,SCD6,SDC7 Fuse Clips for PC Board Mounting H67
GDL-V 1/4”x1-1/4” Glass Body Time Delay Fuse C13 SFRB In-Line Fuse Holder for FSFE fuse C21
GFN Midget Indicating Fuses C10 SFRG In-Line Fuse Holder for FSFE/2AG fuse C21
GGA 5 mm x 20 mm Glass Body Fuse C15 SFRT In-Line Fuse Holder for FSFE fuse C21
GGA-V 5 mm x 20 mm Glass Body Fuse C15 SHR In-Line Flourescent Light Fuse Holder for SLR/SMF G35
GGC 1/4”x1-1/4” Glass Body Time Delay Fuse C14 SLR In-Line Flourescent Light Fuse 1/2-15A G35
GGC-V 1/4”x1-1/4” Glass Body Time Delay Fuse C14 SMF In-Line Flourescent Light Fuse 3/10-10A G35
GGM 5 mm x 20 mm Glass Body Fuse C14 SMG 4 1/2”x14 1/2”mm Glass Body Fuse C19
GGM-V 5 mm x 20 mm Glass Body Fuse C14 SMG-V 4 1/2”x14 1/2”mm Glass Body Fuse C19
GGU Midget Glass/Ceramic Body Fuse C9 SS, SS200-4 Surge Switch, 200kA G8
GGX 1/4” x 1” Glass Body Fuse C18 ST Thermally Protected MOV, Din-Rail TVSS G2
GMS Alarm Indicating Telecommunications Fuse G30 STG 4 1/2”x14 1/2”mm Glass Body Fuse C19
GP Standard Plug Fuse “P” Type Non T-D CSA G37 STG-V 4 1/2”x14 1/2”mm Glass Body Fuse C19
GPM Panel Mount Fuse Holders H36 TA Blown Fuse Indicators J6
GSA 1/4”x1-1/4” Ceramic Body Time Delay Fuse C13 TD Standard Plug Fuse “D” Type Non T-D CSA G37
GSA-V 1/4”x1-1/4” Ceramic Body Time Delay Fuse C13 TGL Telecommunication Fuses 70-800A,170VDC G26
GSB 5 mm x 20 mm Glass Body Fuse C16 TGN Telecommunication Fuses 1-600A,170VDC G26
GSB-V 5 mm x 20 mm Glass Body Fuse C16 TGS Telecommunication Fuses 1-70A,170VDC G26
GSC 5 mm x 20 mm Glass/Ceramic Body Fuse C15 TI Blown Fuse Indicators J6
GSC-V 5 mm x 20 mm Glass/Ceramic Body Fuse C15 TPMOV Surge Suppression Fuses G4
GSD 5 mm x 20 mm Ceramic Body Fuse C17 TR Tri-onic Class RK5 Time Delay Fuse,250V B2
GSD-V 5 mm x 20 mm Ceramic Body Fuse C17 TRM Tri-onic Midget Time Delay Fuse, 250V C5
GSF 5 mm x 20 mm Ceramic Body Fuse C17 TRS Tri-onic Class RK5 Time Delay Fuse,600V B2
GSF-V 5 mm x 20 mm Ceramic Body Fuse C17 TRS-RDC Tri-onic DC Time Delay Fuse, 600V B7
GSL Standard Plug Fuse Rejection T-D UL G37 US14, US22 ULTRASAFE FuseHolders for 14x51 & 22x58 H8
GSR-V 7.1mm Plastic Body Fuse C18 Fuses
GT Standard Plug Fuse Low Temp T-D UL G37 US3J ULTRASAFE Fuseholders for Class J 30A H6
GTL Standard Plug Fuse T-D UL G37 US6J ULTRASAFE Fuseholders for Class J 60A H6
GW Standard Plug Fuse-Non T-D UL G37 USCC ULTRASAFE FuseHolders for Class CC fuses H2
HADSS200 Direct mount black handle G8 USCC-DC ULTRASAFE FuseHolders for Class CC fuses H2
HGPB, HGPR External handle for Surge Switch G8 DC rated
HGPB4, HGPR4 External handle for Surge Switch G8 USFM ULTRASAFE Fuse Module Compact 45mm width H4
HSJ High Speed / Class J B9 US-J-PAK ULTRASAFE Assembling Kits for Class J H7
HSRK High Speed Class RK1 Fuses B31 USM ULTRASAFE FuseHolders for Midget fuses H2
IL Indicator Blown Fuse Indicators J7 USM-DC ULTRASAFE FuseHolders for Midget fuses H2
Index App. Info Application Information L2 DC rated
Index of Products Products and Info INDEX1 USPTH2,3,4 ULTRASAFE Fuseholder Pin Tie Handles H2
J136-J646 Class J Fuse Reducers J4 VSP Surge Suppression Fuses G6
LBS Series Load Break Disconnect Switch K2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
INDEX 3
A relentless pursuit of protection for electrical
components, systems—and the people who use them.
Ferraz Shawmut is an international company manufacturing the widest range of circuit
protection solutions in the electrical industry. Drawing on a century of experience—and
an ongoing commitment to critical research in electrical safety—we provide industrial,
commercial, and OEM customers with innovative products and technical support teams
to increase effectiveness, simplify applications, and enhance productivity. Learn more
about our circuit protection solutions at us.ferrazshawmut.com.