Professional Documents
Culture Documents
CET Power - User Manual - Bravo - 7.4
CET Power - User Manual - Bravo - 7.4
CET Power - User Manual - Bravo - 7.4
AC BACKUP IN A DC ENVIRONMENT
Leverage your existing DC infrastructure
Table of content
1. Abbreviations............................................................................................................................................................. 5
2. Safety Instructions..................................................................................................................................................... 6
2.1 Disclaimer......................................................................................................................................................... 6
2.2 Technical care................................................................................................................................................... 6
2.3 Installation......................................................................................................................................................... 6
2.3.1 Handling................................................................................................................................................ 7
2.3.2 Surge and transients.............................................................................................................................. 7
2.3.3 Other..................................................................................................................................................... 7
2.4 Maintenance .. ................................................................................................................................................... 7
2.5 Replacement and Dismantling........................................................................................................................... 7
3. TSI TECHNOLOGY ...................................................................................................................................................... 8
3.1 On-line Mode..................................................................................................................................................... 8
3.2 Safe mode......................................................................................................................................................... 9
3.3 EPC-mode......................................................................................................................................................... 9
3.4 Mix Mode & Walk-in-mode................................................................................................................................ 9
4. Building Blocks.......................................................................................................................................................... 10
4.1 Inverter.............................................................................................................................................................. 10
4.2 Sub-rack........................................................................................................................................................... 10
4.3 Monitor unit T2S................................................................................................................................................ 11
5. Accessories............................................................................................................................................................... 12
5.1 Cabinet.............................................................................................................................................................. 12
5.2 Manual by-pass................................................................................................................................................. 12
5.3 AC distribution unit............................................................................................................................................ 13
5.3.1 Miniature circuit breakers...................................................................................................................... 13
5.3.2 MCCB.................................................................................................................................................... 13
6. Monitoring Accessories.............................................................................................................................................. 14
6.1 Can Dis shelf..................................................................................................................................................... 14
6.1.1 Display.................................................................................................................................................. 14
6.1.2 TCP/IP Agent.......................................................................................................................................... 14
7. System Design........................................................................................................................................................... 15
7.1 Pack / A la Carte................................................................................................................................................ 15
7.1.1 Pack ..................................................................................................................................................... 15
7.1.2 A la Carte............................................................................................................................................... 15
8. Installation of Bravo PACK or Single shelf/shelves...................................................................................................... 16
8.2 Electrical installation (Bravo PACK or single shelf).............................................................................................. 17
8.2.1 Pre requisites........................................................................................................................................ 17
8.2.2 Surge Suppression................................................................................................................................. 18
8.2.3 Terminations.......................................................................................................................................... 18
8.2.4 Grounding.............................................................................................................................................. 18
8.2.5 DC input................................................................................................................................................ 18
8.2.6 AC input................................................................................................................................................. 19
1. Abbreviations
TSI Twin Sine Innovation
EPC Enhanced Power Conversion
REG Regular
DSP Digital Signal Processor
AC Alternating current
DC Direct current
ESD Electro Static Discharge
MET Main Earth Terminal
MBP Manual By-pass
TCP/IP Transmission Control Protocol/Internet Protocol
USB Universal Serial Bus
PE Protective Earth
N Neutral
PCB Printed Circuit Board
TRS True Redundant Structure
MCB Miniature Circuit Breaker
MCCB Molded Case Circuit Breaker
CB Circuit Breaker
2. Safety Instructions*
2.1 Disclaimer
The manufacturer declines all responsibilities if equipment is not installed, used or operated according to instructions
herein by skilled technician according to local regulations.
Warranty does not apply if the product is not installed, used and handled according to the instructions in the manuals.
2.3 Installation
This product is intended to be installed only in restricted access areas as defined by UL60950 and in accordance with the
National Electric Code, ANSI/NFPA 70, or equivalent agencies.
Inverter System may contain output over current protection in the form of circuit breakers. In addition to these circuit
breakers, the user must observe the recommended UL listed upstream and downstream circuit breaker requirements as
defined in this manual.
Please use extreme caution when accessing circuits that may be at hazardous voltages or energy levels.
The modular inverter rack is a dual input power supply. The complete system shall be wired in a way that both input and
output leads can be made powerless.
REG systems and EPC systems that have no AC input wired and connected can be seen as independent power sources. To
comply with local and international safety standards N (output) and PE shall be bonded. The bonded connection between N
(output) and PE must be removed once the AC input is being connected.
AC and DC circuits shall be terminated with no voltage / power applied.
* These instructions are valid for most CE+T Products/Systems. Some points might however not be valid for the product described
in this manual.
6 – TSI BRAVO 230Vac– User manual – v7.4
Safety Instructions
The safety standard IEC/EN62040-1-1 requires that, in case of output short circuit, the inverter must disconnect in
maximum 5 seconds. Parameter can be adjusted on T2S; however, if the parameter is set at a value >5 seconds, an
external protection must be provided in order that the short circuit protection operates within 5 seconds. Default setting is
60s.
2.3.1 Handling
The cabinet shall not be lifted using lifting eyes.
Remove weight from the cabinet by unplugging the inverters. Mark inverters clearly with shelf and position for correct
rebuild. This is especially important in dual or three phase configurations.
Empty inverter positions must not be left open. Replace with module or cover.
2.3.3 Other
Isolation test (Hi-Pot) must not be performed without instructions from the manufacturer.
2.4 Maintenance
The modular inverter system/rack can reach hazardous leakage currents. Earthing must be carried out prior energizing the
system. Earthing shall be made according to local regulations.
Prior any work conducted to a system/unit make sure that AC input voltage and DC input voltage is disconnected.
Inverter modules and shelves comprise capacitors for filtering and energy storage. Prior to accessing to the system/
modules after power down, wait min 5 minutes to allow capacitors to discharge.
Some components and terminals carry high voltage during operation. Contact may result in fatal injury.
To download the latest documentation and software, please visit our website at www.cet-power.com.
3. TSI TECHNOLOGY 1
Inverter modules carrying the TSI logo and the EPC mark are triple port converters (AC in, DC in, AC out). Sinusoidal output is
converted from Mains or/and DC.
The block diagram here below gives an explicit description of the topology and operation.
BOOST
L L’
EMI EMI
FILTER FILTER
N N’
-
EMI
FILTER
+
User
T2S Interface
Redundant
Local Signaling DSP Commuication
Bus
1 | Information and data given in this chapter is intended to serve as an overview of the TSI Technology. Detailed features and parameters for each individual
module type of the range may differ and should be referred in the dedicated data sheet.
3.3 EPC-mode
Mains input (AC) is the primary source whilst DC works as backup.
The TSI is designed to operate on Mains on permanent basis and to deliver output voltage conditioned with low THD.
There is no physical difference on the output sine wave whether the source is AC (or) DC. If the Mains is out of tolerance or goes
down, the converter seamlessly switches to DC and the converter operates in “Back-up mode” (Switching time back and forth is
0ms).
As soon as the Mains returns in to valid range, the EPC mode is automatically resumed.
The EPC mode offers higher efficiency (up to 96% depending on the model) without compromising the purity of the output sine
wave.
4. Building Blocks
4.1 Inverter
Telecom / Datacom: +24VDC / 230Vac, 50/60Hz
-48VDC / 230VAC, 50/60Hz
-60VDC / 230VAC, 50/60Hz
Industrial / Transport: 110VDC / 230VAC, 50/60Hz
220VDC / 230VAC, 50/60Hz
4.2 Sub-rack
The BRAVO shelf shall be integrated in min 600mm deep cabinets, Inch/ETSI mounting.
The BRAVO shelf house max four (4) inverter modules and one (1) monitor unit.
The extension shelf house max four (4) inverter modules and one (1) monitor blank.
The BRAVO shelf is designed with individual DC input, Common AC input and Common AC output.
Optional rear cover for IP 20 in open rack
Max 10kVA (6kVA 2) per shelf
480 (D) x 19” (W) x 2U (H)
6 Kg empty
1 | +24VDC version
2 | +24VDC version
5. Accessories
5.1 Cabinet
Powder coated (RAL 7024), 19“ welded steel sheet cabinet with 600x600mm foot print. Cabinet designed for top cabling or
bottom cabling.
1100mm (600x600mm) 21U
1800mm (600x600mm) 37U
2100mm (600x600mm) 44U
The cabinet comes with a separable top cover to facilitate cabling. Tie strap support at cable entrance/exit.
Door optional accessory
WARNING
IF ATS (automatic transfer switch) IS INSTALLED UPSTREAM.
MAKE SURE THAT THE ATS SWITCH DOES NOT ALLOW
TRANSFER BETWEEN AC SOURCE OUT OF SYNC. THE MAXIMUM
ALLOWED PHASE SHIFT IS 10°.
Max current per AC DU is 200A, max current per terminal connector is 40A. Two adjacent terminal connectors shall be used for
63A breakers
If alarm is required for AC output breakers a held contact attached to each individual breaker is used (OF or SD). The alarm
function is common and use one of the digital input on the control unit. The help contact limits the breakers quantity.
5.3.2 MCCB
AC output distribution via MCCB in the range
up to 400A (1p, 2p or 3p)
Max two MCCB per inverter cabinet.
6. Monitoring Accessories
6.1 Can Dis shelf
The CanDis shelf has room for 1-3 display units and 1 TCP/IP agent.
6.1.1 Display
Backlit 2 line dot matrix
The display show two values simultaneous
7. System Design
7.1 Pack / A la Carte
The systems designed are divided in two topologies.
7.1.1 Pack
T2S
The PACK is a pre assembled and configured single phase inverter system comprising 19”
inverter sub rack, inverter modules, monitor device and AC output distribution breaker.
The PACK is normally mounted in a 19” rack. Mounting kit is included in the delivery.
The PACK is only available as single phase, -48VDC, EPC-mode.
A PACK comprises of max 6 inverter modules. Blank
TSI
TSI blank
AC Output
7.1.2 A la Carte
The A la Carte is pre assembled and configured as single phase or three phase systems. The system comprises cabinet, inverter
sub rack, inverter modules (+24VD to 220VDC), manual by-pass, monitor device and AC output distribution.
The A la Carte is available in EPC (Enhanced Power Conversion) or REG (Regular) mode.
The A la Carte (single phase) accommodates 1 to 32 modules, for max 80kVA (48kVA3)
The A la Carte (three phase) accommodates 3 to 30 modules, for max 75kVA (45kVA3)
Dual input (AC and DC) inverter modules (EPC)
96% efficiency4 at normal operation (EPC)
Always conditioned and filtered output voltage
Seamless transfer (0ms) between primary and secondary source of supply
No single point of failure
Flexible AC output distribution
Full modularity
Full redundancy
3 | +24V Version
4 | Bravo EPC -48VDC/230VAC
3
5
Finished
8.2.3 Terminations
All terminations are clearly marked.
8.2.4 Grounding
“PE CHASSIS GROUND”
PE Chassis ground shall be wired to MET or distributed earth bar connected to MET
According to local regulations.
8.2.5 DC input
8.2.6 AC input
8.2.7 AC output
8.2.8 Signalling
12
12
1 1
Common
12
NO Selectable*
11
NC
10
Common
9
Relay characteristics (Selectable, Major, Minor) NO Minor (NUA)
8
Switching power 60W NC
7
Rating 2A at 30VDC / 1A at 60VDC Common
6
Max wire size 1mm 2
NO
5 Major (UA)
NC
4
Digital input characteristics (Digital In 1 / 2) ln 1
3 Digital 1
Signal voltage +5VDC (galvanic insulated) Common
2
Max wire size 1mm 2
ln 2 Digital 2
1
Connect cables
9.4.1 Positioning
Phase 1
Phase 1
Phase 2 Inverter sub rack
Inverter modules
Phase 3
PLEASE ! Refer to the technical drawings received with
your cabinet for exact positioning!
9.4.2 Cabling
Note: Do not block the airflow through the top of the cabinet.
Cables are run through the top of the cabinet or the bottom.
The top cover is possible to split in three parts to facilitate cabling.
The top cover has support to strap the cables with nylon tie straps.
AC Output (X4)
9.4.3 Grounding
Ground terminal are located in the top rear left corner.
“PE CHASSIS GROUND”
PE Chassis ground shall be wired to MET or distributed earth bar (MET). Ground must be terminated even if commercial mains is
not available.
According to local regulations, Min 16mm2.
L1 L2 L3 N PE
9.4.5.2 2 DC Input
2x Common DC input per system.
Note: Screws and nuts are not included in the delivery.
M12 holes
Internal DC distribution with circuit breakers (Q01-Q32) per inverter module.
Max 3x240mm2 per pole(group0
9.4.5.3 3 DC Input
3x Common DC input per system.
Note: Screws and nuts are not included in the delivery.
M12 holes
Internal DC distribution with circuit breakers (Q01-Q32) per inverter module.
Max 2x240mm2 per pole(group)
9.4.13 Signalling
The illustration below shows the X3 relays contacts in a non-alarm state when the system is operational. In this case, the relays
are energized and as below.
When an alarm occurs, the X3 relays contacts are de-energized and switch.
10.Interface
10.1 Inverter module
=
AC out
~
=
DC in
=
~
AC in
=
10.2 T2S
Alarm indication on T2S (Urgent / Non Urgent / Configurable) Major Alarm
- Green: No alarm
- Red: Alarm Minor Alarm
- Flashing Exchanging information with inverters (only Configurable alarm)
User selectable Alarm
Outgoing alarm relay delay
- Urgent 60 seconds delay
- Non urgent 30 second delay
USB port
Parameter setting via Laptop.
Factory default according to list of set values, see Table of set values
11.System Set up
Parameter set up requires Hyper terminal installed on laptop
USB cable type A to B (not included)
T2S driver “CET_T2S.inf“installed on laptop.
Available for download:
- On my.CET for direct customers, in the “Document” section.
- At the following URL for everyone else:
http://www.cet-power.com/uploads/Driver_T2S/Driver_T2S_for_Windows_and_hyperterminal.zip
Read T2S manual for detailed setup
12.Inserting/removing/replacing modules
12.1 TSI Inverter
The TSI inverter is hot swappable.
When a new module is inserted in a live system it automatically adapt to working set of parameters.
When a new module is inserted in a live system it automatically assigns the next available address.
12.1.1 Removal
Notice: When one or several inverter modules is/are removed it gains access to live parts. Replace module with blinds without delay.
Inverter module is not switched off when opening the handle. The handle only fixes the module to the shelf.
Use a screw driver to release the latch of the handle
Open the handle
Pull the module out
Replace with new module or blind unit
A) Use screwdriver to release the latch B) open the cover completely C) Use the cover as a handle to remove
the module
12.1.2 Inserting
Check module compatibility (DC Voltage!)
Use a screw driver to release the latch of the handle
Open the handle
Push firmly until the unit is properly connected.
Close the cover and latch in position
A) Slide the module in B) Push firmly till the connection is C) Close the cover and latch the module
properly engaged in place if too hard redo step B
36 – TSI BRAVO 230Vac– User manual – v7.4
Inserting/removing/replacing modules
12.2 T2S
12.2.1 Removal
Use a small screw driver to release the latch keeping the T2S in position.
Pull the T2S out.
12.2.2 Inserting
Push the T2S firmly in place until the latch snaps in position.
13.2 MCCB
MCCBs are installed from factory.
A wide range of breakers is used. Breakers in picture may be different upon delivery.
1. Make sure that the breaker is in OFF position
2. Connect load cables to the terminal
3. Switch the breaker ON
14.Manual By-Pass
Manual By-Pass has to be operated by trained people only.
When system is in manual by-pass the load is subjected to mains voltage without active filtering.
Output alarm when system is in manual by-pass
The manual by-pass is not possible to operate remotely
15.Finishing
Make sure that the sub-rack/cabinet is properly fixed to the cabinet/floor
Make sure that the sub-rack/cabinet is connected to Ground.
Make sure that all DC and AC input breakers are switched OFF.
Make sure that all cables are according to recommendations and local regulations.
Make sure that all cables are strained relived.
Make sure that all breakers are according to recommendation and local regulations.
Make sure that DC polarity is according to marking.
Re tighten all electrical terminations.
Make sure that no inverter/controller positions are left open.
Cover empty inverter positions with blanks.
Make sure that the Remote ON/OFF is appropriately wired according to local regulations.
Make sure that the point of AC supply meets local regulations.
16.Commissioning
The DC breaker is a protection device. Modules are plugged in a system and DC breaker is then engaged. Please make sure the
corresponding DC breaker is engaged in the ON position. Failure to observe this rules will result not to have all module operating
when running on DC and have module failure when AC input recover from fault condition.
Installation and commissioning must be done and conducted by trained people fully authorized to act on installation.
It is prohibited to perform any isolation test without instruction from manufacturer.
Equipments are not covered by warranty if procedures are not respected.
18.Maintenance
Maintenance shall only be performed by properly trained people.
18.3 Optional
With an infrared camera check termination hot spots
- Tighten terminations
19.Defective modules
A repair request should follow the regular logistics chain:
End-user => Distributor => CE+T Power.
Before returning a defective product, a RMA number must be requested through the
http://my.cet-power.com extranet. Repair registering guidelines may be requested by
email at repair@cet-power.com.
The RMA number should be mentioned on all shipping documents related to the repair.
Be aware that products shipped back to CE+T Power without being registered first will
not be treated with high priority!(Label shown here is only for representation)
20. Appendix
20.1 Cabinet Footprint, layout
1 2 3 4 5 6 7 8 9 10 11
H
G
F
C
51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 21 22 23 24 49 50 51 52
DC DISTRIBUTION
49
B
(OPTIONAL)
50
THIS DOCUMENT REMAINS THE PROPERTY OF CE+T. IT SHALL NOT BE GIVEN TO A THIRD PARTY OR REPRODUCED WITHOUT CE+T's AUTHORIZATION.
(OPTIONAL)
DRAW BY APPROVED BY PART DESCRIPTION
Signature Signature
numérique de
Michel
numérique de
Michel REGNIER Joseph Joseph Bozzer
ID : cn=Joseph
A
Bozzer, o=ce+t,
ID : cn=Michel ou=INDUS, c=BE
M. REGNIER Bozzer
SYSTEM TSI BRAVO EPC 230VAC
Date :
REGNIER, o=CE+ La signature 2008.10.22
08:19:28 +02'00'
REGNIER
n'a pas été
T, ou=Dessin, c=BE vérifiée.
Date : 2008.10.21
21/10/2008 La signature
n'a pas été
vérifiée.
14:12:38 +02'00'
J. BOZZER
CHECKED BY APPROVED BY
3 à 8 RACKS MONO
Signature
numérique de
Sergio Sergio D'Angelo
ID : cn=Sergio
D'Angelo,
o=CET, c=BE
Nr MODIF. DATE S. D'ANGELO La signature
n'a pas été
vérifiée.
D'Angelo Date :
2008.10.21
14:16:42 +02'00'
DRAWING NUMBER
CONSTRUCTIONS ELECTRONIQUES Sheet Number
+ TELECOMMUNICATIONS
Rue du charbonnage nr.18 (Zoning Industriel)
B4020 WANDRE Tél: 04-3456700 Fax: 04-3456701
SEO32457
1 2 3 4 5 6
Released
7
by
8
CE+T 9 10 11
Appendix
1 2 3 4 5 6 7 8 9 10 11 12 13
I
H
(35)
(35)
G
TN - S (400/230VAC) L1
L1
L2
L2
L3
L3
N
PEN
N
PE
PE
TT (400/230VAC)
TN - C (400/230VAC)
L1
L1
L2
L2
L3
L3
N
PEN
TN - C - S (400/230VAC)
TN - S (400/230VAC)
L1
L1
L2
L2
L3
L3
N
N PEN
PE
PE
TN - C (400/230VAC) TT (400/230VAC)
L1
L1
L2
L2
L3
L3
PEN
N