Requirements:
Requirements:
C. Equipment Selection
1. Packaged Chiller
a. Estimated capacity of chiller (water cooled)
b. Chiller Data Selected
c. Chilled and cooling water flow in gpm
d. Schematic diagram showing the chiller, cooling tower, cooling & chilled water
pumps, flow rate in gpm, entering/leaving temperatures and pressure drops on the
chiller & condenser.
e. High-lighted selected data on the brochure
f. Specification of the chiller
1. Packaged Chiller
𝟗𝟖℉
𝟗𝟖℉
765 gpm
𝟖𝟖℉
∆𝑷𝒄𝒐𝒏𝒅𝒆𝒏𝒔𝒆𝒓 = 𝟐𝟎𝒇𝒕
CONDENSER
𝟓𝟒℉ 𝟓𝟒℉
𝟓𝟒℉
e. High-lighted selected data on the brochure
Interpolating:
90 − 88 262.7 − 𝑥
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦: = ⇒ 𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 = 264.42 𝑡𝑜𝑛𝑠
90 − 85 262.7 − 267
90 − 88 207 − 𝑥
𝐼𝑛𝑝𝑢𝑡 𝑘𝑊: = ⇒ 𝐼𝑛𝑝𝑢𝑡 𝑘𝑊 = 200.52 𝑘𝑊
90 − 85 207 − 190.8
90 − 88 629.9 − 𝑥
𝐶𝑜𝑜𝑙𝑒𝑟 𝐹𝑙𝑜𝑤 𝑅𝑎𝑡𝑒: = ⇒ 𝐶𝑜𝑜𝑙𝑒𝑟 𝐹𝑙𝑜𝑤 𝑅𝑎𝑡𝑒 = 634 𝑔𝑝𝑚
90 − 85 629.9 − 640
90 − 88 764.8 − 𝑥
𝐶𝑜𝑛𝑑𝑒𝑛𝑠𝑒𝑟 𝐹𝑙𝑜𝑤 𝑅𝑎𝑡𝑒: = ⇒ 𝐶𝑜𝑛𝑑𝑒𝑛𝑠𝑒𝑟 𝐹𝑙𝑜𝑤 𝑅𝑎𝑡𝑒 = 765 𝑔𝑝𝑚
90 − 85 764.8 − 764.2
18 ft wg
634 gpm
20 ft wg
765 gpm
f. Specification of the chiller
a. AHU Tabulated Data
ITEM AHU 1
LPC-AF-10-P-GH/
Unit Model/Size
Size 8
Fan CFM (with reference to Dehumidified CFM) 3962.714
FAN Type of Fan (Forward, Backward or Aerofoil curve
Forward
blades)
Selected Motor Brake Horsepower 2
Fan Revolution per Minute 1063.445 𝑅𝑃𝑀
Total Static Pressure (inch water gage) 2.3998142 in W.G
External Static Pressure
0.30 in W.G
(Air Distribution Losses in inch water gage)
Internal Static Pressure
2.0998142 in .W.G
TOTAL (Losses in the AHU in inch water gage)
STATIC a. Dampers (Face/Bypass Damper) 0.06906785 in W.G
PRESSURE b. Mixing Box 0.16720355 𝑖𝑛 𝑊. 𝐺
c. Flat Filter 0.5525428 𝑖𝑛 𝑊. 𝐺
d. Bag Type or high efficiency filters -
e. Cooling Coil (Air Side) 1.311 𝑖𝑛 𝑊. 𝐺
f. Unit Casing Losses -
Cooling Coil Model Size 8
𝐵𝑡𝑢
Cooling Coil Capacity in BTU per hour 182.28779280
ℎ𝑟
a. Face Area in Square Feet 7.5
Air b. Face Velocity in Feet per minute 531.966
Side c. Number of Rows per coil 8
d. Cooling Coil Entering Dry and Wet Bulb Air
80 / 67
Cooling Temperature in F
Coil e. Cooling Coil Leaving Dry and Wet Bulb Air
51.86 𝐹 / 51.76 𝐹
Temperature in F
Cooling Coil Chilled Water Flow in gallons per
21.648 𝐺𝑃𝑀
minute
Water Cooling Coil Entering and Leaving Chilled
44 / 54
Side Water Temperature in F
Cooling Coil Chilled Water Pressure Drop in
6.906785 𝑓𝑡. 𝐻2 𝑂
feet
c. Chilled and Cooling Water Flow in gpm
12,000 ∗ 𝑇𝑐 12,000 ∗ 9.02
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 = =
500 ∗ ∆𝑇 500(54 − 44)
𝑪𝒉𝒊𝒍𝒍𝒆𝒅 𝑾𝒂𝒕𝒆𝒓 𝑭𝒍𝒐𝒘 = 𝟐𝟏. 𝟔𝟒𝟖 𝒈𝒑𝒎
LDB = 51.86 F
LWB = 51.76 F
RETURN AIR
OUTSIDE
AIR
MIXING BOX
Pressure Coil = 6.906785 ft H2O
EDB = 80 F
EWB = 67 F
54 F
44 F 36.420 GPM
Internal Static Pressure = 2.0998142 in.
W.G. CHILLED
Mixing Box = 0.16720355 in. W.G. WATER PUMP
Flat Filter = 0.5525428 in. W.G.
Cooling Coil = 1.311 in. W.G.
Damper (Face) = 0.06906785 in. W.G.
e. Highlighted selected data of the brochure
𝐶𝐹𝑀 = 3962.714 𝐶𝐹𝑀
𝐶𝑜𝑖𝑙 𝐴𝑟𝑒𝑎 = 7.5 𝑓𝑡 2
𝐹𝑎𝑐𝑒 𝑉𝑒𝑙𝑜𝑐𝑖𝑡𝑦 = 531.966
𝐶𝑜𝑜𝑙𝑖𝑛𝑔 𝐶𝑜𝑖𝑙 𝑃𝑟𝑒𝑠𝑠𝑢𝑟𝑒 𝐷𝑟𝑜𝑝 = 1.311 𝑖𝑛. 𝑊𝐺.
𝐹𝑙𝑎𝑡 𝐹𝑖𝑙𝑡𝑒𝑟 𝑃𝑟𝑒𝑠𝑠𝑢𝑟𝑒 𝐷𝑟𝑜𝑝 = 0.37452 𝑖𝑛. 𝑊𝐺.
𝑀𝑖𝑥𝑖𝑛𝑔 𝑆𝑒𝑐𝑡𝑖𝑜𝑛 𝑃𝑟𝑒𝑠𝑠𝑢𝑟𝑒 𝐷𝑟𝑜𝑝 = 0.09272 𝑖𝑛. 𝑊𝐺.
𝐹𝑎𝑐𝑒 𝐷𝑎𝑚𝑝𝑒𝑟 𝑃𝑟𝑒𝑠𝑠𝑢𝑟𝑒 𝐷𝑟𝑜𝑝 = 0.0436 𝑖𝑛 𝑊𝐺.
Face filter pressure drop = 0.5525428
Mixing Section Pressure Drop = 0.16720355
Face Damper Pressure Drop = 0.06906785
2.0998142 in W.G.
Cost of Energy
P10.00 per kWh
kW
Equipment
Air-Cooled Water-Cooled
Total Energy Consumption in kWh 6,048.32 4,673.38
Monthly Energy Cost 1,814,494.53 1,402,014.28
Annual Energy Cost 21,773,934.35 16,824,171.38
Energy Cost Difference 4,949,762.97
Environmental Consideration
528 Ton Capacity
Equipment
Air-Cooled Water-Cooled
Total Energy Consumption in kWh 6,048.32 4,673.38
Annual Energy in kWh 2,207,635.01 1,705,784.04
Annual Greenhouse effect @ 8.47
18,698.67 14,447.99
Ton CO2/1000 kWh
Green House Difference in Ton
4,250.68
CO2