Introduction
■ Introduction
In this section the wide range of CEWE INSTRUMENT
BLUE MODULE Transducers is described - these are
suitable for DIN-rail mounting.
Owing to their excellent performance and high reliability
(e.g. a MTBF of 40 years for current transducers) CEWE
INSTRUMENT transducers are now used by power
utilities and industry in over 20 European countries as
well as in other parts of the world.
The output from our transducers are, within certain
limits, independent of load. The load limits are given on
the data sheets. The load impendence is obtained by
feedback of the output signal to the input of the
amplifier. ■ Linearity
These transducer characteristics give great advantages
among which the most important are:- A transducer is linear when the output is proportional to
the input. A deviation from a linear function is called a
■ Measuring unit can be measured over relatively long non-linearity error and is expressed as a percentage of a
distances. range in our data sheets.
32.5 114 75
M5
CASE 1
M4
73 77 *With terminal CASE 3 73 M4, M5
60 50
protection
60
DRILLING PLAN CASE 3
Casing 3 and 4 100
M5
85
DRILLING PLAN CASE 4
17
ELECTRICAL TRANSDUCERS
Introduction
18
TRANSDUCERS
For A.C. Voltage
Type DU01, 02, 03, 04 and DU11
■ Output
■ Information required with Order
Nominal accuracy: 0,2
Accuracy class: 0.5 Type: DU 01
Non-linearity: <0.2% Measuring range: 0 - 4 kV
Load dependence: <0.05% (within load limits) Transf. ratio: 3300/110V
Response time: <300ms Frequency: 50Hz
Aux. supply dependence: <0.05% for Uaux. ±20% Output: 0 - 10mA
Temperature coefficient: <0.1% 10°C Auxiliary supply: 230V~
Max. open circuit output
voltage: 20V
Adjustable output: ±10%/OPTION
DU 01, 02
■ Input ■ Connections
Input voltage: 0 - 60...600V
Burden: <1.1 mA x Uin
Uaux. SUPPLY
■ Auxiliary suppy Uaux. SUPPLY
AC voltage: 110V~, 230V~
Burden: <2.5VA OUTPUT + - OUTPUT
CASE
CASE SIZE 3
Output Config. page 17 Load resistance RL Type SIZE 1
For measuring voltages 300VAC and greater units will be supplied in case size 3.
19
TRANSDUCERS
For A.C. Voltage
Type DU01, 02, 03, 04 and DU11
DU 03 ■ Connections
■ Input Uaux. SUPPLY
Input voltage: 0-60...600V
Burden: <1.1mA x Uin Uaux. SUPPLY
Measuring range: ±10% - ±27% Uin OUTPUT + - OUTPUT
■ Auxiliary suppy + -
14 15 16 15 16 13 14
AC voltage: 110V~, 230V~
Burden: <2.5VA
DC Voltage: 24V, 48V, 60V, 110V, 125V, 220V CASE
CASE SIZE 3
Burden: <1.5W SIZE 1
DU 04 ■ Connections
■ Input
Uaux. SUPPLY
Input voltage: 0-10...600V
Burden: <0,6mA x Uin + - OUTPUT
Measuring range: ±10% - ±27% Uin
15 16 13 14
■ Auxiliary suppy
AC voltage: 110V~, 230V~
CASE SIZE 3
Burden: <2,0VA
DC Voltage: 24V, 48V, 60V, 110V, 125V, 220V
Burden: <1.5W
2 5
Output Config. page 17 Load resistance RL Type
1) Other input voltages on request. For measuring voltages 300VAC and greater units will be supplied in case size 3.
2) Other output ranges between 0-1mA and 0-20mA on request.
DU 11 ■ Connections
■ Input
OUTPUT
Input voltage: 0 - 60...525V + -
Burden: <1.2 VA
15 16
■ Auxiliary suppy
Does not require auxiliary supply CASE
SIZE 1
Output Config. page 17 Load resistance RL Type
0 - 1mA A 0 - 15kΩ DU 11 2 5
0 - 5mA A 0-3Ω DU 11
0 - 10mA A 0 -1.5 Ω DU 11
0 - 20mA A 0 - 750 Ω DU 11 U~
INPUT
1) Other input voltages on request.
20
TRANSDUCERS
For A.C. Current
Type DI01, 02 and DI11
DI 01, 02 ■ Connections
■ Input
Input current: 1, 2, 5A Uaux. SUPPLY
Burden: <0,2VA
OUTPUT Uaux. SUPPLY
■ Auxiliary suppy OUTPUT + -
AC voltage: 110V~, 230V~ + -
Burden: <2.5VA 14 15 16 15 16 13 14
DC voltage: 24V, 48V, 60V, 110V, 125V, 220V.
Burden: <1.5W
CASE
CASE SIZE 3
SIZE 1
Output Config. page 17 Load resistance RL Type
D.C. AUX. VOLT SUPPLY
0 - 10mA A 0 - 1.5kΩ DI 01 1 3 13 1 3
0 - 20mA A 0 - 750 Ω DI 01
4 - 20mA C 0 - 750 Ω DI 02 I~
0 - 10V A min 2K Ω DI 01 INPUT I~
INPUT
1) Other output ranges between 0-1mA and 0-20mA on request.
2) Other input currents on request.
DI 11 ■ Connections
■ Input
Input current: 1, 1.2, 5, 6A OUTPUT
Burden: <1.7 VA + -
■ Auxiliary suppy 15 16
Does not require an auxiliary supply.
CASE
Output Config. page 17 Load resistance RL Type SIZE 1
0 - 5mA A 0-3Ω DI 11
0 - 10mA A 0 - 1.5 Ω DI 11 1 3
0 - 20mA A 0 - 750kΩ DI 11
I~
1) Other input currents on request.
INPUT
2) Other output ranges between 0-1mA and 0-20mA on request.
21
TRANSDUCERS
For D.C. Voltage and D.C. Current
Type DU61, 62, 63 and DI61, 62, 63
■ Auxiliary suppy
A.C. voltage: 110V~, 230V~ 15 16 13 14
Burden: <2.5VA
DC voltage: 24V, 48V, 60V, 110V, 125V, 220V
Burden: <2W CASE SIZE 3
■ Measuring range DU 63
Suppressed input version. 2 5
Suppression max 72% of full nominal input signal.
22
TRANSDUCERS
For power, Active and Reactive
Type DP and DQ
Transducers types DP and DQ transform active and Function temp. range: -20 - + 65°C
reactive AC power to a proportionally load Working temp. range: -10 - + 55°C
independent analogue DC signal. The measuring Storage temp. range: -65 - + 80°C
principle for multiplication of current and voltage is Test voltage: 2kV, 50Hz. 4kV as option
based on the TDM-method (Time-Division- Overload: 1.2 x Uin continuously, 2 x Uin
Multiplication). Input voltage and input current can during 5 s, 4 x Uin during 0.5 s
be connected either directly or via transformers. 2 x Iin continuously, 10 x Iin
Scale factor normally lies between 0.5 - 1.3 and is during 10 s, 40 x Iin during 1 s.
defined: Weight: 0.42-0.55kg
■ Connections
DP 01, 02 (Active power single phase)
■ Input Uaux. SUPPLY
■ Auxiliary suppy
1 2 3 11
AC voltage: 110V~, 230V~
Burden: <2.5VA
DC voltage: 24V, 48V, 60V, 110V, 125V, 220V L1
Burden: <1.9W N
Uaux. SUPPLY
+ - OUTPUT
Output Config. page 17 Load resistance RL Type
0 - ±10mA A, D 0 - 1.5kΩ DP 01 15 16 13 14
0 - ±20mA A, D 0 - 750Ω DP 01
4 - 20mA C, E, F 0 - 750Ω DP 02 CASE SIZE 3
0 - ±10V A, D min 2kΩ DP 01
1 2 3 11
1) Other input voltages on request.
2) Other output ranges between 0-±1mA and 0-±20mA on request.
L1
N
23
TRANSDUCERS
For power, Active and Reactive
Type DP and DQ
DP 11, 12 ■ Connections
(Active power 3phase 4 wire balanced) Uaux. SUPPLY
+ - OUTPUT
■ Input 15 16 13 14
Burden: <0.2VA
L1
L2
■ Auxiliary suppy L3
AC voltage: 110V~, 230V~ N
Burden: <2.5VA Uaux. SUPPLY
DC Voltage: 24V, 48V, 60V, 110V, 125V, 220V + - OUTPUT
Burden: <1.9W
15 16 13 14
0 - ±10mA A, D 0 - 1.5KΩ DP 11
0 - ±20MA A, D 0 - 750 Ω DP 11 1 2 3 11
4 - 20mA C, E, F 0 - 750 Ω DP 12
0 - ±10V A, D min 2KΩ DP 11 L1
L2
L3
1) Other input voltages on request. N
2) Other output ranges between 0-±1mA and 0-±20mA on request.
■ Connections
DP 13, 14
(Active power 3 phase 3 wire balanced) + - OUTPUT
Uaux. SUPPLY
15 16 1 3 13 14
■ Input
Input voltage: 110...500V CASE SIZE 3
Burden: <0.2VA
L1
■ Auxiliary suppy L2
L3
AC voltage: 110V~, 230V~
Burden: <2,5VA
Uaux. SUPPLY
DC Voltage: 24V, 48V, 60V, 110V, 125V, 220V + - OUTPUT
Burden: <1.9W
15 16 1 3 13 14
24
TRANSDUCERS
For power, Active and Reactive
Type DP and DQ
DP 23, 24 ■ Connections
(Active power 3 phase 3 wire unbalanced)
Uaux. SUPPLY
+ -
■ Input OUTPUT
■ Auxiliary suppy L1
AC voltage: 110V~, 230V~ L2
Burden: <2.8VA L3
0 - ±10mA A, D 0 - 1.5KΩ DP 23
0 - ±20MA A, D 0 - 750 Ω DP 23 CASE SIZE 3
4 - 20mA C, E, F 0 - 750 Ω DP 24
1 2 3 5 8
0 - ±10V A, D min 2KΩ DP 23
■ Connections
DP 33, 34
(Active power 3 phase 4 wire unbalanced)
Uaux. SUPPLY
OUTPUT + -
■ Input 15 16 7 9 13 14
0 - ±10mA A, D 0 - 1.5kΩ DP 33
0 - ±20mA A, D 0 - 750Ω DP 33
4 - 20mA C, E, F, 0 - 750Ω DP 34
0 - ±10V A, D min 2kΩ DP 33
L1
1) Other input voltages on request. L2
L3
2) Other output ranges between 0-±1mA and 0-±20mA on request. N
25
TRANSDUCERS
For power, Active and Reactive
Type DP and DQ
DQ 13, 14 ■ Connections
(Reactive power 3 phase 3 wire balanced) Uaux. SUPPLY
+ - OUTPUT
■ Input 15 16 13 14
Burden: <1.9W
15 16 13 14
0 - ±10mA A, D 0 - 1.5KΩ DQ 13
0 - ±20MA A, D 0 - 750 Ω DQ 13 1 3 5 8
4 - 20mA C, E, F 0 - 750 Ω DQ 14
0 - ±10V A, D min 2KΩ DQ 13 L1
L2
L3
1) Other inputs voltages on request.
2) Other output ranges between 0-±1mA and 0-±20mA on request.
DQ 23, 24 ■ Connections
(Reactive power 3 phase 3 wire unbalanced)
Uaux. SUPPLY
■ Input OUTPUT + -
■ Auxiliary suppy L1
AC voltage: 110V~, 230V~ L2
L3
Burden: <2.8VA
DC Voltage: 24V, 48V, 60V, 110V, 125V, 220V
Burden: <2.2W Uaux. SUPPLY
OUTPUT + -
Output Config. page 17 Load resistance RL Type 15 16 7 9 13 14
0 - ±10mA A, D 0 - 1.5KΩ DQ 23
0 - ±20MA A, D 0 - 750 Ω DQ 23 CASE SIZE 3
4 - 20mA C, E, F 0 - 750 Ω DQ 24
1 2 3 5 8
0 - ±10V A, D min 2KΩ DQ 23
26
TRANSDUCERS
For power, Active and Reactive
Type DP and DQ
DQ 33, 34 ■ Connections
(Reactive power 3 phase 4 wire unbalanced)
Uaux. SUPPLY
OUTPUT + -
■ Input 15 16 7 9 13 14
■ Auxiliary suppy L3
N
CASE SIZE 4
27
TRANSDUCERS
Combined Active and Reactive Power
Type DPQ
■ Input OUTPUT + - + -
17 18 15 16 7 9 13 14
Input voltage: 60..500V
Burden: <1mA per phase CASE SIZE 4
Input current: 1A, 2A, 5A
Burden: <0.1VA per phase 2 1 3 5 8
■ Auxiliary suppy L1
AC voltage: 110V~, 230V~ L2
L3
Burden: <4.0VA
DC Voltage: 24V, 48V, 60V, 110V, 125V, 220V
Burden: <3.0W
Q P Uaux. SUPPLY
OUTPUT + - + -
Output Config. page 17 Load resistance RL Type
17 18 15 16 7 9 13 14
■ Connections
DPQ 23, 24
(Combined unit 3 phase 3 wire unbalanced)
Q P Uaux. SUPPLY
OUTPUT + - + -
■ Input
17 18 15 16 13 14
Input voltage: 60..500V
Burden: <1mA per phase CASE SIZE 4
■ Auxiliary suppy L1
L2
AC voltage: 110V~, 230V~ L3
Burden: <4.0VA
Q P
DC Voltage: 24V, 48V, 60V, 110V, 125V, 220V Uaux. SUPPLY
OUTPUT + - + -
Burden: <3.0W
17 18 15 16 13 14
28
TRANSDUCERS
For AC Voltage Frequency
Type DF
Transducers type DF are used for the measurement Function temp. range: -20 - + 65°C
of the frequency of an AC voltage and transforms it Working temp. range: -10 - + 55°C
into a proportionally load independent DC Storage temp. range: -65 - + 80°C
analogue signal. The input can be connected Test voltage: 2kV, 50Hz. 4kV as option
directly or via a voltage transformer. Overload: 1.2 x Uin continuously, 2 x Uin
during 5 s, 4 x Uin during 0.5 s
Weight: 0.45kg
■ Output
■ Information required with Order
Accuracy class: 0.1
Non-linearity: <0.05%
Load dependence: <0.05% (within load limits) Type: DF 03
Response time: <300ms Measuring range: 48 - 52Hz
Aux. supply dependence: <0.05% for Uaux ±20% Voltage: 110V
Temperature coefficient: <0.2% / 10°C Output: 0 - 10mA
Max. open circuit output Auxiliary supply: 230V~
voltage: 20V
DF 03, 04 ■ Connections
■ Input
Input voltage: 0 - 60...500V (40 - 120%) Uaux. SUPPLY
OUTPUT
Burden: <0.2VA x Uin
+ -
■ Auxiliary suppy 15 16 13 14
0 - 10mA B 0 - 1.5kΩ DF 03
0 - 20mA B 0 - 750Ω DF 03
4 - 20mA C 0 - 750Ω DF 04
0 - 10V B min 2kΩ DF 03
29
TRANSDUCERS
For Power Factor
Type DPF
Transducers type DPF are connected to 3-phase, Function temp. range: -20 - + 65°C
3-wire symmetric load for the measurement of Working temp. range: -10 - + 55°C
power factor, which value is transformed to a Storage temp. range: -65 - + 80°C
proportionally load independent DC analogue
output signal. Test voltage: 2kV, 50Hz.
Overload: 1.2 x Uin continuously, 2 x Uin
Input voltage and input current can be connected
either directly or via transformers. during 5 s, 4 x Uin during 0.5 s
2 x Iin continuously, 10 x Iin
The transducer type DPF requires a separate during 10 s, 40 x Iin during 1 s.
auxiliary supply. If required, the measuring voltage
can also be used as an auxiliary supply under Weight: 0.45kg
condition that this lies within the given tolerance.
■ Information required with Order
■ Output
Accuracy class: 0.5 Type: DPF 13
Non-linearity: <0.1% Measuring range: 0.5 - 1 - 0.5 cos
Load dependence: <0.05% (within load limits) Voltage: 110V
Response time: <300ms Current: 5A
Aux. supply dependence: <0.05% for Uaux ±20% Frequency: 50Hz
Temperature coefficient: <0.2% / 10°C Output: 10 - 0 - 10mA
Max. open circuit output
Auxiliary supply: 230V~
voltage: 20V
■ Connections
DPF 13, 14
■ Input
Input voltage: 110...500V (40 -120%) Uaux. SUPPLY
Burden: <0.6mA per phase x Uin
Input current: 1A, 2A, 5A (10 -130%)
+ - OUTPUT
30
TRANSDUCERS
DC Analogue Signals to Relay Pulse Output
Type DIF
■ Description ■ Relays
Contacts: 0.75A / 350V max. 50VA
Transducers type DIF converts an analogue DC Life expectancy: 108 operations
input signal to a proportional pulse frequency
output. The output signal is obtained by a relay
with two pairs of mercury wetted contacts. The
input signal can be either uni-polar or bi-polar. The ■ General data
relay pulses can of course also be transmitted to an
integrator in a computer. Function temp. range: -20 - + 65°C
Working temp. range: -10 - + 55°C
■ Output
Storage temp. range: -65 - + 80°C
Accuracy class: 0.2 Test voltage: 2kV, 50Hz.
Non-linearity: <0.1% Weight: 0.51kg
Pulse frequency: 0 - 0.0001Hz (min)
Pulse time: 0 - 10Hz, max.
Pulse time, 40ms, 80ms, 160ms
as standard (specify which one)
Aux. supply dependence: <0.5% for Uaux ±20%
Temperature coefficient: <0.1% / 10°C
DIF 01, 02
■ Input
Input ranges: 0 -5mA DIF 01 ■ Connections
0 -10mA DIF 01
0 -20mA DIF 01
4 -20mA DIF 01 + - INPUT Uaux. SUPPLY
0 -10V DIF 01
0 - ± 5mA DIF 02
0 - ± 10mA DIF 02
1 2 3 4 13 14
0 - ± 20mA DIF 02
DC-TO PULSE RATE CONVERTER
4 - 12 - 20mA DIF 02 DIF 01
0 - ± 10V DIF 02 CASE SIZE 3
RELAY
OUTPUT
■ Auxiliary suppy
+ - INPUT Uaux. SUPPLY
■ Note 6 7 8 9
31