Monitoring Relays

Pump alternating
Type DLA71
• Pump alternating relay for 2 or 3 pumps
• Output: 2 x 5 A SPST relay or 3 x 5 A SPST
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• 35.5 mm DIN-rail housing
• LED indication for relay and power supply ON
• Galvanically separated power supply
• Built-in delay for the second or third pump in case of
simultaneous activation is required
• Built-in function for automatic rotation of the pumps

Product Description Ordering Key DLA 71 T B23 3P


DLA71 is relay made to avoid big inrush current. Housing
alternate 2 or 3 pumps in a Function
multiple pump system. In The LED indicates the state Type
case of need (i.e.: overflow) of the alarm and the output Item number
the second, or even the third relay. Output
pump can be activated Power supply
together with the first one. 35.5 mm wide housing suit- Number of pumps
In case more than one pump able both for back and front
is required to start at the panel mounting.
same time, the pumps start
10 s after the previous to

Type Selection
Mounting Output Function Supply: 24/48 VAC Supply: 115/230 VAC

DIN-rail 2 x SPST For two pumps DLA 71 D B48 2P DLA 71 D B23 2P


DIN-rail 3 x SPST For three pumps DLA 71 T B48 3P DLA 71 T B23 3P

Input Specifications Output Specifications


Contact input Terminals Output DLA71...2P 2 x SPST NO relay
DLA71...3P 3 x SPST NO relay
DLA71...2P (normal mode) Rated insulation voltage 250 VAC
ON/OFF 1 pump C, S1 Contact ratings (AgSnO2) µ
ON/OFF 2 pumps C, S2 Resistive loads AC 1 5 A @ 250 VAC
DC 12 5 A @ 24 VDC
DLA71...2P (differential mode) Small inductive loads AC 15 1.5 A @ 250 VAC
first pump starts C, S1 DC 13 1.5 A @ 24 VDC
first pump stops C, S3
second pump start C, S2 Mechanical life ≥ 30 x 106 operations
second pump stop C, S4 Electrical life ≥ 105 operations
(at 5 A, 250 V, cos ϕ = 1)
DLA71...3P (normal mode) Operating frequency ≤ 7200 operations/h
ON/OFF 1 pump C, S1 Dielectric strength
ON/OFF 2 pumps C, S2 Dielectric voltage 2 kVAC (rms)
ON/OFF 3 pumps C, S3 Rated impulse withstand volt. 4 kV (1.2/50 µs)
DLA71...3P (full mode)
ON 1 pump C, S1
ON 2 pumps C, S2
ON 3 pumps C, S3
OFF all pumps C, S4

Disabled > 10 kΩ
Enabled < 1 kΩ
Voltage < 25 V
Current < 2 mA

Empting mode N.O. contacts


Filling mode N.C. contacts

Specifications are subject to change without notice (03.06.10) 1


DLA71

Supply Specifications General Specifications (cont.)


Power supply Overvoltage cat. III Indication for
Rated operational voltage (IEC 60664, IEC 60038) Power supply ON LED, green, steady
through terminals: One Pump ON as above, flashing 1 Hz
A1, A2 or A3, A2 Two Pumps ON as above, flashing 2 Hz
B48: 24/48 VAC ± 15% Three Pumps ON(DLA71...3P) as above, flashing 3 Hz
45 to 65 Hz, insulated Note: if more than one pump
B23: 115/230 VAC ± 15% is active, the indication refers
45 to 65 Hz, insulated to the pump started last.
Dielectric voltage First pump activated after Random
Supply to input 4 kV (1.2/50 µs) power up
Supply to output 4 kV (1.2/50 µs) Environment (EN 60529)
Input to output 4 kV (1.2/50 µs) Degree of protection IP 20
Rated operational power Pollution degree 3
AC 3 VA Operating temperature -20 to 60°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing
Dimensions 35.5 x 81 x 67.2 mm
Material PA66 or Noryl
General Specifications Weight Approx. 135 g
Reaction time Screw terminals
Closing input < 100 ms Tightening torque Max. 0.5 Nm
Opening input < 100 ms acc. to IEC 60947
Minimum delay to activate Product standard EN 60255-6
the rescue pumps 10 s Approvals UL, CSA
Continous working time to CE Marking L.V. Directive 2006/95/EC
activate the rotation pumps 6 h ± 10% EMC Directive 2004/108/EC
EMC
Immunity According to EN 60255-26
According to EN 61000-6-2
Emissions According to EN 60255-26
According to EN 61000-6-3

Mode of Operation
DLA71 is made for pumping Example 2 described in example 1 Note (3-pump system)
systems where 2 or 3 pumps (emptying a basin, 2-pump except that if switch S3 is If the system is continuously
are in parallel. It lets the system, differential mode) reached three pumps work working with only one pump,
pumps work alternatively, In this case the pumps are at the same time. When they after working for 6 hours,
allowing more pumps to separately started and switch back the pumps are DLA71 stops the pump and
work togheter in case of stopped by the two pairs of turned off in sequence start- the second one automatical-
need. switches S1, S2 and S3, S4. ing from the one running ly starts. If also the second
Appropriate positioning longer. pump works continuously
Example 1 allows the pumps to work alone for 6 hours, it is
(emptying a basin, 2-pump together in case of need. Example 4 stopped and the third pump
system) (emptying a basin, 3-pump is then started.
As soon as the liquid reach- Note (2-pump system) system, full mode) If a couple of pumps is con-
es switch S1 one pump If the system is continuously As soon as the liquid reach- tinuously working for 6
starts. As soon as S1 working with only one pump, es switch S1 one pump hours, the one running for
switches back the pump after working for 6 hours, starts. When it drops below more time stops and the free
stops. When switch S1 is DLA71 stops the pump and switch S4 it stops. If switch one starts.
activated again the other the second one automatical- S1 is triggered again another This rotation is repeated
pump starts allowing uni- ly starts. pump starts. If switch S2 is every 6 hours of continuative
form wear and tear of all the This rotation is repeated activated a second pump work of a pump or a couple
pumps. If switch S2 is acti- every 6 hours of single and starts (rescue function). If of pumps.
vated both pumps start (2 continuative work of a switch S3 is activated all the
pumps running at the same pump. pumps operate. The only Note (2 and 3-pump sys-
time). When S2 switches switch to stop all the pumps tems)
back the pump running Example 3 active at a certain time is S4. In case the task is to fill a
since most time stops. (emptying a basin, 3-pump basin, all the switches are
system, normal mode) reversed in the basin itself.
The system works exactly as

2 Specifications are subject to change without notice (03.06.10)


DLA71

Operation Diagrams
Example 1 (empting mode) Power supply
L m m

S4 A1 A3 18 28 S1
S3

S2
S2
S1 C A2 15

S3
N

S4

15 -18
S2
15 -28

S1

PUMP 2

PUMP 1
Automatic
rotation function 6h 6h 6h 6h Working time

Example 2 (empting mode)


L m m Power supply

S4 A1 A3 18 28
S3 S1

S2 S2
S1 C A2 15

S3
N

S4

15 -18

15 -28
S2

S4

S1

PUMP 2
S3

PUMP 1
Automatic
rotation function 6h 6h 6h 6h Working time

Example 3 (empting mode)


L m m m Power supply

S4 A1 A3 18 28 38
S3 S1

S2 S2
S1 C A2 15

S3
N

S4

15 -18

15 -28
S3
15 -38

S2

S1
PUMP
PUMP 3
3

PUMP 2
PUMP 2

PUMP11
PUMP
Automatic
rotation function 6h 6h 6h 6h Working time

Specifications are subject to change without notice (03.06.10) 3


DLA71

Operation Diagrams (cont.)

Example 4 (empting mode)


Power supply
L m m m

S4 A1 A3 18 28 38 S1
S3

S2
S2
S1 C A2 15
S3

N
S4

15 -18

15 -28

15 -38
S3

S2

PUMP 3
PUMP 3
S1

S4 PUMP
PUMP 2
2

PUMP
PUMP 1
Automatic
1

rotation function 6h 6h 6h 6h Working time

Example 5 (filling mode)


Power supply

S1

L m m
S2
S4 A1 A3 18 28
S3
S3

S2
S1 C A2 15 S4

N 15 -18

15 -28

S3

S1

S4
Automatic
S2
rotation function 6h 6h 6h 6h Working time

Wiring Diagrams
DLA71...2P DLA71...3P

48/230 VAC 24/115 VAC 48/230 VAC 24/115 VAC

L m m L m m m

S4 A1 A3 18 28 S4 A1 A3 18 28 38
S3 S3

S2 S2
S1 C A2 15 S1 C A2 15

N N

4 Specifications are subject to change without notice (03.06.10)


Dimensions

35.5 67.2

18.7
81

45
2

Specifications are subject to change without notice (03.06.10) 5