System Record
System Record
System Record
2023
2019
V1.00
43 60
220 V AC - 230 V AC 02 Amp
Circuit Breaker 10 Amp
Switch Board 1
2 X (12V DC 12 AH)
Inside of Fire Alarm Control Panel
24 Hour 5 min
A
A
A
B
N/A
30
N/A
N/A
N/A
01
N/A
PA System Control 01
Exhaust Fan Control 09
Fire Pump, Lift, Ex-Fan, Fire Door, PA System, Flow Switch, Temper Switch
05-10-2023
Md. Abdur Rahman
Md. Abdur Rahman
05.10.23
2019
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
43
Yes
N/A
N/A
N/A
N/A
N/A
N/A N/A
05.10.2023
Generator Room
Generator Room Diesel
24 Hours 05
N/A N/A
N/A N/A
N/A
N/A
N/A
N/A N/A
8 to 33 VDC 8 Amp
Circuit Breaker 6 Amp
Ground Floor Panel Room
24 Hours 5 Min
05.10.2023
Control Module All Building Exit Fire Door Interface with Fire Door
Monitor Module Pump Room & Riser Interface with Flow Switch
Monitor Module Pump Room & Riser Interface With Gate Valve
Site Installer
V1.00
N/A
N/A N/A
24 Hours 05
ok ok
ok ok
ok ok
ok ok
ok ok
ok ok
ok ok
ok ok
ok
75
95
NFPA-72 100%
05-10-2023 05-10-2023
ok
Exhaust Fan Shut Down All DB Board
Fire Door All Building Fire Door ok
Flow Switch & Gate Valve. All Riser & Pump Room ok
PA System
Building-1 Office Room ok
Lift Lift Room ok
NAC-Extender Panel Room ok
05-10-2023
2019
376
12
06
43 Horn With Strobe
62