Professional Documents
Culture Documents
Technical Spec - 33kV SWGR - EDF Final
Technical Spec - 33kV SWGR - EDF Final
Document Control
SIGN OFF
DOCUMENT CONTROL
Schedule of Requirements for Circuit Breaker for Solar Farms, Wind Farms, and Battery Energy
Document Title
Storage Systems
1 INTENT OF SPECIFICATION................................................................................................................
2 SCOPE OF WORK...............................................................................................................................
3 GENERAL REQUIREMENTS................................................................................................................
4 NOTES.............................................................................................................................................
5 TECHNICAL COMPLIANCE...............................................................................................................
6 TESTING..........................................................................................................................................
7 QUANTITY.......................................................................................................................................
8 DOCUMENTATION..........................................................................................................................
10 LIST OF SUPPLIERS..........................................................................................................................
11 APPENDIX B - DRAWING.................................................................................................................
12 SCHEDULE A....................................................................................................................................
13 SCHEDULE B....................................................................................................................................
1 INTENT OF SPECIFICATION
This specification is intended to cover the design, manufacture, assembly, testing at manufacturer's works, supply
& delivery, properly packed for transport to site of 400 KV CIRCUIT BREAKERS, complete with all materials and
accessories for efficient and trouble-free operation in a manner acceptable to Owner.
In the event of any discrepancy with listed documents, the stipulation of this specification shall govern.
The specification shall be read and construed in conjunction with other sections of bidding document.
2 SCOPE OF WORK
2.1 Scope of Supply
Type, rating, connections, etc. of the equipment shall be as detailed in the drawings and annexures. The
equipment shall be furnished in strict compliance with the same.
2.1.1 Each circuit breaker shall be furnished complete with:
a) Fittings and accessories.
b) Auxiliary equipment.
2.1.2 Spares
2.1.3 All relevant drawings, data and instruction manuals.
3 GENERAL REQUIREMENTS
3.1 Codes and Standards
Equipment is to be NG type registered in line with the requirements of:
Standards
BS 381C Specification for Colours for Identification, Coding and Special Purposes
ENA TS 41-37 Switchgear for use on 66kV to 132kV distribution systems*
IEC 62271-100 High-voltage switchgear and Control gear - Part 100: Alternating current
circuit-breakers
IEC 62271-1 High-voltage Switchgear and Control gear: Part 1: Common Specification
IEC 62271-110 High voltage Switchgear and Control gear : Part 110 – inductive load
switching
IEC 60507 Artificial Pollution Tests On High-Voltage Ceramic and Glass Insulators To
Be Used On A.C. Systems.
IEC 60815-1 Selection And Dimensioning Of High-Voltage Insulators Intended For Use
In Polluted Conditions - Part 1: Definitions, Information and General
Principles
IEC 60815-2 Selection And Dimensioning Of High-Voltage Insulators Intended For Use
In Polluted Conditions - Part 2: Ceramic and Glass Insulators For A.C.
Systems
IEC 60815-3 Selection And Dimensioning Of High-Voltage Insulators Intended For Use
In Polluted Conditions - Part 3: Polymer Insulators For A.C. Systems
IEC 61936-1 Power Installation Exceeding 1kV a.c. Part 1: Common Rules
IEC 62271-302 High-Voltage Switchgear And Control gear - Part 302: Alternating Current
Circuit-Breakers With Intentionally Non-Simultaneous Pole Operation
6. Altitude m ≤1000
-Switching Impulse Withstand (Across Open Switching Device) 900 (+345) kV Peak
230V AC
36. Isolation White Links in Closing and Tripping Circuits required Yes
37. Wiring Type LSZH
38. Terminals Type According to ENA- TS
39. Density Switch Two Stages
40. Pressure Gauge dial marking mPA / bar
41. Operational Counter Non-resettable
42. SF6 Filling Point Yes
43. Breaker Status Indication Symbol ‘I’ / ’O’
44. Local Control Cabinet enclosure rating IP55
45. Local Control Cabinet colour (shall be project specific) See Note 4 (4)
46. Steel Support Structure Required
47. “Local/Remote” Selector Switch (Lockable) required Yes
48. “Open/Neutral/Close” Control Switch (Spring return to Neutral)
Yes
required
49. Key Solenoid Lock Required No
50. Harting plug to be fitted by factory on Both cable ends / or One end
Both Ends
only
51. Phase spacing minimum (shall be project specific) 5m
52. Cable Length- Local Control Cabinet to Pole A Mech. Box See Figure 1
53. Cable Length-Local Control Cabinet to Pole B Mech. Box See Figure 1
54. Cable Length- Local Control Cabinet to Pole C Mech. Box See Figure 1
4 NOTES
1. All the design & installation works shall comply with UK safety & CDM regulations
4. The corrosive environment of the equipment shall be classified as: ISO 12944, outdoor
C3-High Durability.
5. 1. Steel items shall be hot-dip galvanised to a zinc coverage of not less than 100 µm
whenever applicable, or stainless steel AISI 316.
The finish shall be suitable for the lifetime of the installation with more than 15 years to
first major maintenance.
6. All document/drawing numbers and tags will be supplied at later stage. Supplier shall
incorporate the same in the drawings/documents/equipments.
5 TECHNICAL COMPLIANCE
The attached appendix ‘A’ technical compliance check sheet is to be provided as part of the clarified
quotation.
Yes No
Yes No
Yes No
Yes (____________) No
6 TESTING
Supplier to comply Clause no 3 TEST REQUIREMENTS of NGTS TS 3.02.01, Issue 5
7 QUANTITY
Please refer to BOQ in ITT
8 DOCUMENTATION
All documentation to be issued through the agreed management system. Supplier shall be trained as
required.
Standard document / drawing templates with the numbering as per agreed system.
4. 3D model in Autodesk Revit (.rvt) or Autocad Inventor (.iam) or step (.stp/step) format. (Only
outer peripheral geometry required; generally less than 10MB.)
4 3D model in Autodesk Revit (.rvt) or Autocad Inventor (.iam) or step (.stp/step) format. (Only
outer peripheral geometry required; generally less than 10MB.)
6 Detailed General arrangement drawing for Operating boxes & Control Cubicle
7 Schematics drawings
9 Quality Plan
10 Project Plan
1 Circuit Breaker 3
2 Fixed contacts 3
3 Moving contacts 3
4 Closing coil 6
5 Tripping coil 6
10 LIST OF SUPPLIERS
1 Hitachi
2 Siemens
3 GE
11 APPENDIX B - DRAWING
Figure 1
MK
LA LB LC
CU
CABLE TRENCH
CU – Control Unit
LA – CU = 12.5m
LB – CU = 2m
12 SCHEDULE A
A1.1 MANUFACTURER -
Circuit Breaker Designation (GIS or OT self-blast puffer
A1.2 -
etc)
A1.3 Circuit Breaker Type Reference: -
Year production
(month/year)
commenced
Year production ceased
(NGC use only)
A1.4 CIRCUIT BREAKER RATING
Rated Voltage kV
Rated Normal Current A
Rated short circuit current kA.rms
Rated short circuit making current kA.pk
Rated short circuit peak break current kA.pk
First-Pole-to-Clear Factor kpp
RRRV on 100% duty kV/μS /
D.C Component at contact separation (following 10ms
%
relay time and open time as A3 Cl 3.9)
X/R Test Ratio
Capacitive Current Switching Ability - Bank A
Voltage Factor for OHL Capacitive Current Duty p.u.
Non mandatory Shunt Reactor Switching Ability A
Non mandatory Series Reactor Switching Ability kA
RRRV on Series Reactor Duty - 3 phase kV/μS /
Out of Phase Switching Ability kA
RRRV Out of Phase Duty kV/μS /
Dielectric Withstand: -
(i) Lightning Impulse (1/50) kVp
(ii) Switching Impulse (250/2500) kVp
(iii) Power Frequency (wet and dry) kVrms
Mechanical Endurance Class
Bending Moment at base of support porcelian kN-m
A1.5 DRAWINGS -
3-phase arrangement drawing No -
Single-phase arrangement drawing No -
Control schematic drawing No -
13 SCHEDULE B
Product Description
Product Type
Test Duty or Test Document Test Object (offered Remarks Compliance (yes, no, n/a)
Requirement Reference or equivalent)
Item Procedure Witness
(1) (2) (3)
10% terminal fault
30% terminal fault
60% terminal fault
100% symmetrical
terminal fault
100% asymmetrical
terminal fault
90% short line fault
75% short line fault
peak making ability
out of phase
switching
short time current
withstand
peak current
withstand
capacitive line
switching
capacitive bank
switching
shunt reactor
switching (IEC 62271-
110)
series reactor
switching
continuous current
temperature rise
lightning impulse
switching impulse
power frequency
withstand
RIV
mechanical
endurance
High and Low
Temperature tests
Verification of IP
coding
Tightness test
EMC tests
Test Duty or Test Document Test Object (offered Remarks Compliance (yes, no, n/a)
Requirement Reference or equivalent)
Item Procedure Witness
(1) (2) (3)
Test to prove the
operation under
severe ice conditions
Static terminal load
test
impulse noise level
grading capacitor test
data
insulator shed
shape/pollution
performance
operating manual(s)
routine test
specification
commissioning
schedule
outline drawings
(1) - Supplier to confirm item tested is identical to the item offered. Differences should be identified in the non-
conformance schedule
(2) - Suppler to confirm item has been tested in full compliance with the reference test specification. Differences
should be identified in the non-conformance schedule
(3) - Supplier to confirm tests have been independently witnessed