Schedule of Requirements

400kV OUTDOOR DISCONNECTOR


DOCUMENT REFERENCE: XXXXXXXXXXX
Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Document Control
SIGN OFF
Name (Role) Signature Date

DOCUMENT CONTROL

Document
DMS document refer added here
Number

Schedule of Requirements for Outdoor Disconnector for Solar Farms, Wind Farms, and
Document Title
Battery Energy Storage Systems
Rev. Date Description Prepared Checked Approved
[dd mmm yyyy]

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 2 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

1 INTENT OF SPECIFICATION
This specification is intended to cover the design, manufacture, assembly, testing at manufacturer's works, supply
& delivery, properly packed for transport to site of 400 KV disconnectors, complete with all materials and
accessories for efficient and trouble-free operation in a manner acceptable to Owner.
In the event of any discrepancy with listed documents, the stipulation of this specification shall govern.
The specification shall be read and construed in conjunction with other sections of bidding document.

2 SCOPE OF WORK
2.1 Scope of Supply
Type, rating, connections, etc. of the equipment shall be as detailed in the drawings and annexures. The
equipment shall be furnished in strict compliance with the same.
2.1.1 Each disconnector shall be furnished complete with:
a) Fittings and accessories.

b) Auxiliary equipment.

c) First filling of SF6 gas plus 20% spare.

2.1.2 Spares
2.1.3 All relevant drawings, data and instruction manuals.

3 GENERAL REQUIREMENTS
3.1 Codes and Standards
Equipment is to be NG type registered in line with the requirements of:

NG Specifications / Title Date / Issue


Policies
TS 1 Ratings & Requirements for Plant Issue 7
TS 2.01 Substations Issue 5 and
Addendum
TS 2.02 Switchgear Issue 5
nnnnnn Disconnector Issue 5
(All associated standards within these documents are to be taken into consideration)

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 3 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

3.2 General Details

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 4 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Disconnector UNIT DATA


EDF Required Offered

General Information

3.2.1 MANUFACTURER'S NAME AND COUNTRY OF By Bidder


MANUFACTURE
3.2.2 MANUFACTURER'S TYPE AND DESIGNATION By Bidder

3.2.3 APPLICATION Outdoor

3.2.4 QUANTITY As per Layout / BOQ

a) WITH ONE EARTH SWITCH As per Layout / BOQ


b) WITHOUT EARTH SWITCH As per Layout / BOQ
C) WITH TWO EARTH SWITCH As per Layout / BOQ
3.2.5 APPLICABLE STANDARD Refer to Clause 3.1

3.2.6 TYPE & ENDURANCE CLASS OF DISCONNECTOR AND Double Break, M2


MOUNTING Endurance class
(10,000 operations)
3.2.7 Endurance class of Earth Switch M0 class (1,000
operations)
3.2.8 EXECUTION OF POLES (GANG OPERATED THREE Three individual
PHASES/ THREE INDIVIDUAL PHASES) phases
3.2.9 RATED VOLTAGE AND FREQUENCY kV & Hz 420kV & 50 Hz

3.2.10 POWER FREQUENCY WITHSTAND VOLTAGE kV (rms) Ph-E & Between


phases 520kV rms
and 610 kV rms
(Across isolating
distance)
3.2.11 LIGHTNING IMPULSE WITHSTAND VOLTAGE kVp Ph-E & Between
phases 1425kVp and
1425 (+240) kVp
(Across isolating
distance)
3.2.12 SWITCHING IMPULSE WITHSTAND VOLTAGE kVp 1050kVp (For Ph-E &
Across open
switching device)
1575 kVp (For Ph-Ph)
900(+345) kVp
(Across isolating
distance)
3.2.13 RATED CURRENT UNDER SITE CONDITIONS (A) AT 50°C A 2000/3150

3.2.14 SHORT TIME WITHSTAND CURRENT AND DURATION kA & sec. 63,1

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 5 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Disconnector UNIT DATA


EDF Required Offered
3.2.15 RATED SHORT TIME CURRENT OF ISOLATOR FOR 1S(kA) kA (rms), 50, 125
AND DYNAMIC CURRENT (kAP) kAp
3.2.16 PEAK WITHSTAND CURRENT kAp 157.5

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 6 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Disconnector UNIT DATA


EDF Required Offered

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 7 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

3.2.17 SHORT CIRCUIT MAKING CURRENT OF EARTHING kA 157.5


SWITCH
3.2.18 BREAKING CAPACITY OF LINE CHARGING CURRENT A/pf 0.7A at 0.15pf

3.2.19 BREAKING CAPACITY OF MAGNETISING CURRENT A 0.7A at 0.15pf

3.2.20 OPERATING MECHANISM

3.2.21 OPERATING DEVICE

3.2.22 MAIN DISCONNECTOR Motor Operated

3.2.23 EARTH SWITCH Manual

3.2.24 EMERGENCY OPERATION

3.2.25 MAIN DISCONNECTOR Manual operated

3.2.26 EARTH SWITCH Manual operated

3.2.27 OPENING TIME OF ISOLATOR AND EARTH SWITCH By Bidder

3.2.28 CLOSING TIME OF ISOLATOR AND EARTH SWITCH By Bidder

3.2.29 MAXIMUM TEMPERATURE RISE OF CURRENT °C As per IEC-62271-1


CARRYING PARTS WHEN CARRYING RATED CURRENT Table-3
CONTINUOUSLY OVER AMBIENT TEMPERATURE
3.2.30 DIELECTRIC WITHSTAND CAPACITY OF COMPLETELY By Bidder
ASSEMBLED ISOLATOR/ EARTH SWITCH
3.2.31 CONTACTS AND MATERIAL OF CURRENT CARRYING
PARTS
a) TYPE OF MAIN AND ARCING CONTACTS Jaw contacts
b) MATERIAL OF CONTACTS
i) MAIN Silver faced copper
ii) ARCING By Bidder
d) CONTACT PRESSURE kg/cm2
e) WHETHER CONTACTS ARE SILVER COATED Yes/No Yes
f) MATERIAL USED FOR CURRENT CARRYING PARTS Copper
3.2.32 MAXIMUM CURRENT DENSITY UNDER NORMAL IEC BS EN 62271-
CURRENT CARRYING CAPACITY (A/mm2) 1:2017+A1:2021/IEC
62271-
102:2018+A1:2022
3.2.33 THICKNESS OF SILVER PLATING µm 25

3.2.34 Note: All current carrying part shall be high


conductivity electrolytic copper material
3.3 CLEARANCE
a) BETWEEN POLES mm Refer Layouts

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 8 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

b) BETWEEN LIVE PARTS AND EARTH (MINIMUM) mm 3500


c) BETWEEN LIVE PARTS WHEN THE SWITCH IS OPEN
i) ON THE SAME POLE mm 4200
ii) BETWEEN ADJACENT POLES mm 4200
3.3.1 TORQUE REQUIRED TO OPERATE THE GANG OPERATED Nm NA
DISCONNECTOR
3.4 INSULATOR DATA (FOR COMPLETE STACK)
a) MANUFACTURER'S NAME AND COUNTRY By bidder

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 9 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Disconnector UNIT DATA


EDF Required Offered
b) TYPE PORCELAIN
c) NUMBER OF UNITS By Bidder
d) NUMBER OF INSULATOR STACKS/PHASE Three
e) HEIGHT OF THE STACK mm By Bidder
f) BOLT CIRCLE DIAMETER mm By Bidder
g) TORSIONAL STRENGTH Nm BY BIDDER - SUBJECT
TO APPROVAL OF
PURCHASER
g) CANTILEVER STRENGTH kG 1000
h) VISUAL DISCHARGE VOLTAGE kV By Bidder
i) DRY ARCING DISTANCE mm By Bidder
j) POWER FREQUENCY PUNCTURE VOLTAGE kV By Bidder
3.5 SWITCH DESIGN
a) ROTATING/TILTING/LIFTING ETC. Horizontal Double
Break
b) HORIZONTAL/VERTICAL ETC. Horizontal Double
Break
c) SINGLE BREAK/DOUBLE BREAK ETC. Double Break
RATED OUTPUT OF MOTOR kw By Bidder
3.6 TERMINAL STUD
a) WHETHER HORIZONTAL OR VERTICAL As per requirement
in layout and BOQ
b) DIAMETER mm By Bidder
c) LENGTH mm By Bidder
3.7 CLAMPS/CONNECTORS
a) CLAMP MATERIAL Copper/ Aluminium
alloy
b) BOLT MATERIAL By Bidder
c) RANGE OF DIAMETER OF CONDUCTORS THAT CAN As per requirement
BE RECEIVED in layout and BOQ
d) MAXIMUM TEMPERATURE RISE WHEN CARRYING °C As per IEC 62271-
RATED CURRENT OVER SPECIFIED AMBIENT 1:2017+A1:2021
TEMPERATURE
e) WEIGHT OF EACH TYPE OF CLAMP kg By Bidder
f) WHETHER HORIZONTAL/VERTICAL TAKE-OFF As per requirement
in layout and BOQ
g) FLEXIBLE/RIGID As per requirement
in layout and BOQ
3.8 SUPPORTING STRUCTURES
3.8.1 MATERIAL OF SUPPORTING STRUCTURES RCC/STEEL Steel

3.8.2 WHETHER CALCULATIONS FOR THE DESIGN OF Yes/No NA


SUPPORTING STRUCTURES ENCLOSED

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 10 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Disconnector UNIT DATA


EDF Required Offered

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 11 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

3.8.3 WHETHER STRUCTURAL DRAWINGS ENCLOSED Yes/No NA

3.8.4 TOTAL WEIGHT OF DISCONNECTOR (3 PHASE/1PHASE) Kg By Bidder

3.8.5 VISUAL DISCHARGE VOLTAGE FOR COMPLETE kV 320kV RMS


DISCONNECTOR WITH FITTINGS (FOR 132 kV AND
ABOVE)
3.8.6 RIV FOR COMPLETE DISCONNECTOR WITH FITTINGS µV less than 1000µV
(FOR 132 kV AND ABOVE)
3.8.7 WHETHER GENERAL ARRANGEMENT DRAWING Yes/No Yes to be provided by
ENCLOSED Bidder
3.8.8 WHETHER ALL TYPE TEST REPORTS ARE ENCLOSED Yes/No Yes to be provided by
Bidder
3.8.9 WHETHER DEVIATIONS IN DATA SHEET 'A' ARE Yes/No By Bidder
FURNISHED
3.8.10 CORONA EXTINCTION VOLTAGE kV (rms) 320 kV rms (phase to
earth)
3.8.11 MAX. RADIO INTERFERENCE LEVEL AT 1.1 UR ∀3 AT 1.0 LESS THAN 1000 AT
MHz (MICROVOLTS) 266kV(rms) in all
positions
3.8.12 TOTAL CREEPAGE DISTANCE TO GROUND mm

3.8.13

3.8.14 NO. OF NO & NC AUX. CONTACTS FOR PURCHASER'S


USE
a) MAIN SWITCH Nos. 10 NO + 10 NC
b) EARTH SWITCH Nos. 5 NO + 5 NC
3.8.15 POLE DISCREPANCY CIRCUIT REQUIRED Yes/No Yes

3.8.16 PURCHASER'S EARTHING CONDUCTOR (MATERIAL & mm x mm 75 x 10 GI


SIZE)
3.8.17 AUXILIARY SUPPLY

3.8.18 FOR MOTOR 415/230V VAC

3.8.19 FOR CONTROL 220V DC

3.8.20 RATED AUX. SUPPLY CONTINUOUS CURRENT A 10

3.8.21 RATED DC BREAKING CURRENT WITH 20ms TIME A 2


CONSTAND (A)
3.8.22 INTERLOCKS WITH CIRCUIT BREAKER Electrical
(ELECTRICAL/MECHANICAL)
3.8.23 INTERLOCKS POWER CONSUMPTION W

3.8.24 POWER CONSUMPTION OF CONTROL COILS W

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 12 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

3.8.25 NO. OF POLES 3

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 13 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Disconnector UNIT DATA


EDF Required Offered
3.8.26 RATED MECHANICAL TERMINAL LOAD As per table III of IEC-
IEC 62271-
102:2018+A1:2022 or
as per value
calculated in Chapter-
GTR whichever is
higher.
3.8.27 THERMAL RATING OF AUXILIARY DC CONTACTS 10 A at 220 V

3.8.28 BREAKING CAPACITY OF AUXILIARY CONTACTS 2 A DC with circuit


time constant less
than 20
3.8.29 Confirm whether in line with specifications Yes/ No Yes

3.8.30 Factory Acceptance Test – Routine Tests As per NGTS


According to BS EN IEC 62271-102:2018+A1:2022 and
accompanying specification
3.8.31 Factory Acceptance Test – Type Tests As per NGTS
According to BS EN IEC 62271-102:2018+A1:2022 and
accompanying specification
3.8.32 Factory Acceptance Test – Special Tests As per NGTS
According to BS EN standard 61869-5:2011 and
accompanying specification

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 14 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

4 TECHNICAL COMPLIANCE
The attached appendix ‘A’ technical compliance check sheet is to be provided as part of the clarified quotation.

Appendix ‘A’ Technical compliance

Fully complying with this Technical specification requirements

Yes No

Fully complying with relevant NG specifications mentioned in section 3 above

Yes No

Documents including revisions are as listed in Clause 5 and 6:

Yes No

Equipment type registered:

Yes (____________) No

If ‘No’ please provide the details below in brief:

Table for Deviations.

Clause Equipment Deviation

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 15 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

5 TO BE SUBMITTED WITH THE BID


 Typical general arrangement drawings of the equipment.

 Technical leaflets on equipment explaining construction features, principle of operation, special features etc.

 Type test certificate on similar equipment.

6 TO BE SUBMITTED FOR APPROVAL AND DISTRIBUTION


 Technical Data and Type Test evidence (Schedule A and B) Refer to Annexure A and B

 Dimensional general arrangement drawing showing disposition of various fittings.

 Transport/shipping dimensions with weights.

 Foundation plan and loading.

 Assembly drawing for erection at site with part numbers and schedule of materials.

 Control schematic and wiring diagram.

 Any other relevant drawing or data necessary for satisfactory installation, operation and maintenance.

 Instruction manuals on disconnectors and its accessories.

 The manual shall clearly indicate method of installation, check ups and tests to be carried out before
commissioning of the equipment.

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 16 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

7 SCHEDULE OF RECOMMENDED SPARES

Sl. No. Description Quantity

1. Complete Pole with Arm Quantity (For each type


of mechanism & current
rating)
a) With Earth Switch 3

b) b) Without Earth Switch 3

2. Copper Contact Finger for Female Contact 3

3. Relay, Power Contractor and Switch Fuse for Electrical Control 1 Set
Circuit

4. Support Insulators for One Pole 1 Set

5. Bearing 2 Sets

6. Hinge Pin 2

7. Terminal Pad 2

8. Auxiliary Switch (6 NO + 6 NC) 2 Sets

9. Limit Switch 2 Sets

10. Terminal, Connector of each type 6

11. Motor 2

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 17 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

8 LIST OF SUPPLIERS

Sl. No. Description

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 18 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

9 SCHEDULE A

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 19 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

SCHEDULE OF TYPE TESTS (EARTH SWITCHES)

SCHEDULE OF GENERAL AND TECHNICAL DETAILS (DISCONNECTORS)


GENERAL DETAILS
1 MANUFACTURER
2 MANUFACTURER'S TYPE / MODEL
3 YEAR PRODUCTION COMMENCED (month/year)
4 DRAWINGS
4.01 Three Phase Arrangement Drawing No. / Rev
4.02 Control Schematic Drawing No. / Rev
4.03 Base Fixing (Foundation) Drawing No. / Rev
4.04 Base Loading (Foundation) Drawing No. / Rev

TECHNICAL DETAILS
NO. DESCRIPTION UNIT VALUE
5 NUMBER OF POLES
6 DESIGN TYPE (REP, RCP, VERT, REPTAN, RCPTAN. TAN=TANDEM)
7 DISCONNECTOR RATINGS DETAILS
7.01 Rated Design Voltage (eg 420kV) kV
7.02 Rated Design Current A
7.03 Rated Short-time Withstand Current kA
7.04 Duration of Rated Short-time Withstand Current seconds
7.05 Rated Peak Withstand Current kA
7.06 Bus Transfer Duty to IEC 62271-102 Yes/No
7.07 Bus-transfer Voltage V
7.08 Bus-transfer Current A
7.09 Capacitive Current Switching Capability A
7.10 Inductive Current Switching Capability A
7.11 Load Make or Break Capability Yes/No

8 METHOD OF OPERATION (eg M=MOTORIZED, H=HAND)


9 Mechanism Type Reference
10 Mechanism Manufacturer if different to above
11 METHOD OF OPERATION - Motorized
11.01 Motor rating Voltage

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 20 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

SCHEDULE OF GENERAL AND TECHNICAL DETAILS (DISCONNECTORS)


11.02 Watts
11.03 Motor operating time Close - seconds
11.04 Open - seconds
11.05 Motor protection operating time (stalled) seconds
12 METHOD OF OPERATION - Manual (Hand)
12.01 Maximum torque required to operate Close - N
12.02 Open - N
13 METHOD OF OPERATION - OTHER
13.01 Specify and provide relevant data

14 Number and Type of Auxiliary Switches Type (i)


Type (ii)
Type (iii)
Type (iv)
Type (v)
Type (vi)
Type (vii)
Type (viii)

15 INSULATION
15.01 Manufacturer of Support Insulation
15.02 Support Insulation Type Reference
15.03 Manufacturer of Drive Insulation
15.04 Drive Insulation Type Reference
15.05 Support insulator deflection under 70% load mm

16 RATED CONTACT ZONE (as defined in IEC 62271-102 clause 4.102)


16.1 x mm
16.2 y mm
16.3 z (or z1 if applicable) mm
16.4 z2 (if applicable) mm

17 STATIC MECHANICAL TERMINAL LOADS (as defined in IEC 62271-102 clause


4.103)

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 21 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

SCHEDULE OF GENERAL AND TECHNICAL DETAILS (DISCONNECTORS)


17.01 Fa1 (and Fa2) N
17.02 Fb1 (and Fb2) N
17.03 Fc N

18 WEIGHTS OF DISCONNECTOR COMPONENTS


18.01 Moving contact(s) assembly (complete with arm) kg
18.02 Fixed contact assembly (single pole) kg
18.03 Support insulator for fixed contact kg
18.04 Support insulator for moving contact kg
18.05 Drive insulator (if not as above) kg
18.06 Base unit without mechanism kg
18.07 Mechanism (state whether for 3-pole or 1-pole) kg

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 22 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

SCHEDULE OF GENERAL AND TECHNICAL DETAILS (EARTH SWITCHES)

GENERAL DETAILS
1 MANUFACTURER
2 MANUFACTURER'S TYPE / MODEL
3 YEAR PRODUCTION COMMENCED (month/year)
4 DRAWINGS
4.01 Three Phase Arrangement Drawing No. / Rev
4.02 Control Schematic Drawing No. / Rev
4.03 Base Fixing (Foundation) Drawing No. / Rev
4.04 Base Loading (Foundation) Drawing No. / Rev

TECHNICAL DETAILS
NO. DESCRIPTION UNIT VALUE
5 NUMBER OF POLES
6 DESIGN TYPE
7 EARTH SWITCH MOUNTED WITH (PART OF) Yes/No
DISCONNECTOR

8 EARTH SWITCH SEPARATELY MOUNTED Yes/No


9 EARTH SWITCH RATINGS DETAILS
9.01 Rated Design Voltage (eg 420kV) kV
9.02 Rated Design Current A
9.03 Rated Short-time Withstand Current kA
9.04 Duration of Rated Short-time Withstand Current seconds
9.05 Rated Peak Withstand Current kA
9.06 Induced Current Switching Duty to IEC 62271-102 Yes/No
9.07 Induced Current Switching Class to IEC 62271-102 (eg. A or B)
9.08 Inductive Current Switching Capability A
9.09 Capacitive Current Switching Capability A
9.10 Fault Making / Ferroresonance Quenching Yes/No

10 METHOD OF OPERATION (eg M=MOTORIZED, H=HAND)


11 Mechanism Type Reference
12 Mechanism Manufacturer if different to above
13 METHOD OF OPERATION - Motorized
13.01 Motor rating Voltage

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 23 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

GENERAL DETAILS
13.02 Watts
13.03 Motor operating time Close - seconds
13.04 Open - seconds
13.05 Motor protection operating time (stalled) seconds
14 METHOD OF OPERATION - Manual (Hand)
14.01 Maximum torque required to operate Close - N
14.02 Open - N
15 METHOD OF OPERATION - OTHER
15.01 Specify and provide relevant data

16 Number and Type of Auxiliary Switches Type (i)


Type (ii)
Type (iii)
Type (iv)
Type (v)
Type (vi)
Type (vii)
Type (viii)

17 INSULATION
17.01 Manufacturer of Support Insulation
17.02 Support Insulation Type Reference
17.03 Support insulator deflection under 70% load mm

18 RATED CONTACT ZONE (as defined in IEC 62271-102 clause 4.102)


18.1 x mm
18.2 y mm
18.3 z (or z1 if applicable) mm
18.4 z2 (if applicable) mm

19 STATIC MECHANICAL TERMINAL LOADS (as defined in IEC 62271-102 clause


4.103)
19.01 Fa1 (and Fa2) N
19.02 Fb1 (and Fb2) N

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 24 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

GENERAL DETAILS
19.03 Fc N

20 WEIGHTS OF EARTH SWITCH COMPONENTS


20.01 Moving contact(s) assembly (complete with arm) kg
20.02 Fixed contact assembly (single pole) kg
20.03 Support insulator for fixed contact kg
20.04 Support insulator for moving contact kg
20.05 Base unit without mechanism kg
20.06 Mechanism (state whether for 3-pole or 1-pole) kg

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 25 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

10 SCHEDULE B

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 26 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

SCHEDULE OF TYPE TESTS (DISCONNECTORS)

Product Description Disconnector (with optional Bus Transfer Contacts)


Product Type

Test Reference Test Test Date Compliance (yes, no, n/a)


Report
No. Item Procedure Witness
(1) (2) (3)
Dielectric Tests IEC 62271-102

Salt Fog Pollution tests NGT TS 1


Heavy Wetting tests NGT TS 1
Radio Interference Voltage (riv) IEC 62271-102
test
Resistance of Main Circuit IEC 62271-102
Temperature Rise test IEC 62271-102
Short-time withstand current test IEC 62271-102

Operational & Mechanical IEC 62271-102


Endurance
Severe Ice Conditions IEC 62271-102

Operation at Temperature Limits IEC 62271-102

Bus Transfer Current Switching IEC 62271-102


tests
Duty for Bus-charging Current IEC 62271-102
tests

(1) - Supplier to confirm item tested is identical to the item offered for type registration. Differences should be
identified in the non-conformance schedule
(2) - Suppler to confirm item has been tested in full compliance with the reference test specification. Differences
should be identified in the non-conformance schedule
(3) - Supplier to confirm tests have been independently witnessed

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 27 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

Product Description Disconnector and Earth Switch Operating Mechanism

Product Type

Test Reference Test Report Test Date


No. Compliance (yes, no, n/a)
Item Procedure Witness
(1) (2) (3)

Verification of Protection (IP Test) IEC 62271-102

Operational & Mechanical Endurance IEC 62271-102

Severe Ice Conditions IEC 62271-102

Operation at Temperature Limits IEC 62271-102

Reliable Position-Indicating Device IEC 62271-102

(1) - Supplier to confirm item tested is identical to the item offered for type registration. Differences should be identified in
the non-conformance schedule
(2) - Suppler to confirm item has been tested in full compliance with the reference test specification. Differences should be
identified in the non-conformance schedule
(3) - Supplier to confirm tests have been independently witnessed

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 28 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

SCHEDULE OF TYPE TESTS (EARTH SWITCHES)

Earth Switch (with optional Induced current switching duty and/or


Product Description
Ferreoresonance Quenching duty)

Product Type

Test Reference Test Report Test Date


No. Compliance (yes, no, n/a)
Item Procedure Witness
(1) (2) (3)
IEC 62271-
Dielectric Tests
102
Salt Fog Pollution
NGT TS 1
tests

Heavy Wetting tests NGT TS 1

Radio Interference IEC 62271-


Voltage (riv) test 102
Resistance of Main IEC 62271-
Circuit 102
Short-time withstand IEC 62271-
current test 102
Operational &
IEC 62271-
Mechanical
102
Endurance
IEC 62271-
Severe Ice Conditions
102
Operation at IEC 62271-
Temperature Limits 102
Induced Current IEC 62271-
Switching Tests 102
Ferroresonance NGT TS
Quenching 3.2.2

(1) - Supplier to confirm item tested is identical to the item offered for type registration. Differences
should be identified in the non-conformance schedule
(2) - Suppler to confirm item has been tested in full compliance with the reference test specification.
Differences should be identified in the non-conformance schedule
(3) - Supplier to confirm tests have been independently witnessed

SoR Template Reference: ER-ENG-TEM-0043v1.0 Information Security Classification: C0 - Public PAGE 29 OF 30


Schedule of Requirements - Disconnectors for Wind Farms,
Solar Farms, and Battery Energy Storage Systems
EDF RENEWABLES - BMS DOCUMENT REF : XXXXXXXX VERSION: 1.0

SCHEDULE OF TYPE TESTS (MECHANISM)

Product Description Disconnector and Earth Switch Operating Mechanism

Product Type

Test Reference Test Test Date Compliance (yes, no, n/a)


Report
No. Item Procedure Witness
(1) (2) (3)

Verification of Protection (IP IEC 62271-


Test) 102

Operational & Mechanical IEC 62271-


Endurance 102

IEC 62271-
Severe Ice Conditions
102

IEC 62271-
Operation at Temperature Limits
102

Reliable Position-Indicating IEC 62271-


Device 102

(3) - Supplier to confirm tests have been independently witnessed


(2) - Suppler to confirm item has been tested in full compliance with the reference test specification. Differences
should be identified in the non-conformance schedule
(3) - Supplier to confirm tests have been independently witnessed.