323A 138T1733 C Shaftline Foundation Interface
323A 138T1733 C Shaftline Foundation Interface
323A 138T1733 C Shaftline Foundation Interface
Revision History
Date
Rev Description Approved
(YYYY-MM-DD)
C LEGEND 2022-03-21 BASHA
1) UPDATED DIMENSION LABEL IN SH3 AND SH4.
ROBERT, SEBASTIEN
GENERATOR
PEDESTAL
GAS TURBINE
FORWARD SUPPORT
PEDESTAL
GAS TURBINE
AFT SUPPORT
PEDESTAL
GAS TURBINE
EXHAUST SUPPORT
PEDESTAL
GAS TURBINE
EXHAUST
DIFFUSER SUPPORT
ISOMETRIC VIEW
For Information Only
GENERAL NOTES:
5. THE TOP OF CONCRETE IS GIVEN AS REFERENCE. TOC SHALL USUALLY BE LOWER THAN TOP OF BASE PLATE
LEVEL IN ORDER TO ENSURE THAT BASE PLATES ARE OUT OF WATER. REFER TO EQUIPMENT DETAILED DRAWING
FOR BASE PLATE REFERENCE LEVELS.
6. THE GROUT POCKET DEPTH SHALL BE DETERMINED BASED ON THE HEIGHT OF THE LEVELING
DEVICE, THE INITIAL GROUT POUR REQUIRED TO HOLD THE LEVELING DEVICE IN PLACE,
AND THE THICKNESS OF THE BASE PLATE. THE FOUNDATION DESIGNER SHOULD CONSULT WITH
THE INSTALLER TO CONFIRM THAT THE SPECIFIED GROUT POCKET SIZES ARE SUITABLE FOR
ALL SITE SPECIFIC INSTALLATION CONSIDERATIONS.
7. THE FOUNDATION DESIGNER SHALL BE RESPONSIBLE FOR THE DESIGN OF THE GROUT POCKET TO
ENSURE LOCAL SLOPE AWAY FROM LEVELING DEVICE, SO AS TO PROVIDE ADEQUATE RUN OFF.
GROUT POCKET EDGE DISTANCES SHALL BE DESIGNED TO PROVIDE A MINIMUM OF 100MM (150MM FOR
LARGE PLATES) BETWEEN THE FOUNDATION PLATE EDGE AND THE GROUT POCKET EDGE TO ALLOW FOR
ADEQUATE ACCESS TO THE LEVELING DEVICE ADJUSTMENT NUT. ELSEWHERE THE DISTANCE BETWEEN
THE FOUNDATION PLATE EDGE AND THE GROUT POCKET EDGE SHOULD BE 50MM MINIMUM.
THE GOAL IS TO PROVIDE SUFFICIENT WRENCH ACCESS AND INSTALLATION DEPTH FOR THE LEVELING DEVICES.
8. FOR FOUNDATION DESIGN DATA INCLUDING FOUNDATION LOADS, MISALIGNMENT TOLERANCE MATRIX AND
SUPPLEMENTARY DRAWINGS, SEE LOAD DESIGN DATA DOCUMENT.
9. FOR THE POWERTRAIN FOUNDATION, THE MAXIMUM TOTAL VERTICAL DISPLACEMENT DUE TO LONG-TERM,
TIME-DEPENDENT EFFECT AFTER INTERCONNECTING SYSTEMS ARE COMPLETE AND THE UNIT IS PLACED IN
OPERATION SHALL NOT EXCEED 25 MM (1 INCH) OVER THE SERVICE LIFE OF THE PLANT. THIS MAXIMUM NEED
NOT INCLUDE ANY IMMEDIATE, ELASTIC SETTLEMENT DUE TO ONLY THE DEAD WEIGHT OF THE FOUNDATION AND EQUIPMENT.
10. MAXIMUM LONG-TERM DIFFERENTIAL SETTLEMENTS OF ADJACENT FOUNDATIONS WITH RESPECT TO EACH OTHER AFTER
INTER-CONNECTING PIPING SYSTEMS AND DUCTING EXPANSION JOINTS ARE INSTALLED SHOULD NOT EXCEED 12 MM (0.5 INCH)
OR 0.002L, WHICHEVER IS GREATER WHERE L IS THE DISTANCE BETWEEN SUPPORTS OF INTERCONNECTING SYSTEMS.
FOR REQUIREMENT REGARDING ALLOWABLE SETTLEMENT, SEE DOCUMENT 384A2911
12. THE GROUT REQUIREMENT SHALL TAKE INTO ACCOUNT THE DEPTH OF THE POCKET.
14. PRIOR TO LANDING THE TURBINE, THE FIXATORS ON THE GAS TURBINE FORWARD AND AFT SUPPORT TO BE SET AND ALIGNED IN
ACCORDANCE WITH GE SPECIFICATION 355A8842.
15. THE MINIMUM COMPRESSIVE STRENGTH OF CONCRETE FOR THE FOUNDATION, MEASURED AT 28 DAYS, SHALL NOT BE LESS
THAN 30 MPa (4350 psi) BASED ON STANDARD CONCRETE SPECIMENS (e.g. ASTM C39)
16. THE GROUD SYPHONS SHALL BE INSTALLED IN THE FOUNDATION TO DRAIN WATER MIST FIRE FIGHTING SYSTEM. UNDERGROUND
PIPING DESIGN IN THE FOUNDATION BY CIVIL ENGINEER / PLANT DESIGNER. DUE TO THE NEGATIVE AIR PRESSURE IN THE
GAS TURBINE ENCLOSURE A WATER PRESSURE EQUIVALENT TO 50 MILLIMETER OF WATER (MMH2O) IS REQUIRED FOR THIS
DRAIN PIPING IN ORDER TO AVOID SUCKING IN AIR.
REFERENCE DRAWINGS
SYSTEM MLI DRAWING NUMBER DRAWING TITLE
GENERATOR A1B0 137T3738 ASSEMBLY PLAN GENERATOR
GENERATOR B7G0 137T3750 GEN FOUNDATION PLATE ARRANGEMENT
GAS TURBINE 1603 119T8351 FOUNDATION BOLTING ARRANGEMENT
GAS TURBINE / GENERATOR 323C 136T0869 FOUNDATION INTERFACE PIPING 9AH.02 PIPING SINGLE SHAFT
INLET PLENUM 1612 127T4835 INLET PLENUM FOUNDATION INTERFACE
TURBINE GENERATOR FOUNDATION INTERFACE DETAILING.
GEK 106957
DESIGN AND INSTALLATION RECOMMENDATIONS
323A 355A8842 LEVELING DEVICE INSTALLATION INSTRUCTIONS
MINIMUM REQUIREMENTS FOR TECHNICAL CONTENTS FOR
323A 384A2911
GEOTECHNICAL REPORTS
STATIC DEFLECTION CRITERIA
323B 354A2868 STATIC DEFLECTION CRITERIA FOR GTG FOUNDATION
FOR GTG FOUNDATION
GAS TURBINE / GENERATOR 323B 138T1919 FOUNDATION INTERFACE LOAD TABLES
EXHAUST DIFFUSER A042 121T9341 EXHAUST DIFFUSER FOUNDATION INTERFACE
EXHAUST FRAME COOLING A132 136T5826 OUTLINE DRAWING 9HA.02 88TK CF
EXHAUST ENCLOSURE
1643 136T6841 OUTLINE DRAWING 88 EF 9HA.01 PP
VENTILATION FANS 88 EF
9HA.02 GAS ONLY AM10 FUEL GAS CONTROL MODULE -
GAS FUEL CONTROL MODULE AM10 131T1368
MECHANICAL OUTLINE ARRANGEMENT For Information Only
AIR EXTRACTION LOWER MODULE AM40 121T1592 MODULE, AIR EXTRACTION LOWER - AM40
GT DRAINS MODULE AM50 128T3986 MODULE ARRGT, GT DRAINS - AM50
19. THE DIMENSIONS TO THE FACE OF CONCRETE AT THE LOCATIONS REFERENCING THIS NOTE ARE DEFINED TO AVOID INTERFERENCE
WITH MLI 1627 INLET PLENUM BARRIER WALL FLASHING. THESE DIMENSIONS HAVE A POSITIVE 12,7 [0.50] TOLERANCE BUT
CANNOT ANY LESS THAN WHAT IS DIMENSIONED ON THE DRAWING.
ARRANGEMENT
OUTLINE FOUNDATION
NLR INTERFACE GAS TURB / GEN PKG
2020-2022
2020-11-30 138T1733 C 2 of 5
GE Non-Public- Class II - (Non Critical) NLR
Doc Name : 138T1733 Rev C Released Date : 2022/03/23 Page 3 of 5
C1
2X 14287,8 562.51
2X 17275,9 680.15
2X 19967,9 786.14
EXPANSION JOINT
8741,0 344.13
SEE NOTE 19
SEE NOTE 19
+12,7 .50
+12,7 .50
2X 3783,0 148.94
SEE NOTE 16
2X 3490,0 137.40
2X 1738,4 68.44
,0 .00
UNIT
.50
SEE NOTE 19
4X 2900,0 2 X +12,7 4X
114.17 .50
SEE NOTE 19
GEN GT GT GT
MLI A1B0 MLI 1612 MLI 1603 MLI A042
,0 .00
PLAN VIEW
ARRANGEMENT
OUTLINE FOUNDATION
NLR INTERFACE GAS TURB / GEN PKG
2020-2022
2020-11-30 138T1733 C 3 of 5
GE Non-Public- Class II - (Non Critical) NLR
Doc Name : 138T1733 Rev C Released Date : 2022/03/23 Page 4 of 5
C1
BRG 4
BRG 3
1300,0 +12,7 [0.50]
SEE NOTE 19 1000,0 +12,7 [0.50] 2860,5 2860,5 2886,7 4822,7
51.18
SEE NOTE 19
39.37 112.62 112.62 113.65 189.87
TOP OF
CONCRETE AT TOP OF TOP OF TOP OF TOP OF TO TOP OF
ST FRONT CONCRETE CONCRETE CONCRETE CONCRETE DIFFUSER
STANDARD GENERATOR GAS TURBINE GAS TURBINE GAS TURBINE SUPPORT CL UNIT
3241,5
127.62
5500,0
216.53
EQUIPMENT
BASELINE
(BOTTOM OF
GE EQUIPMENT)
SEE NOTE 17
ARRANGEMENT
OUTLINE FOUNDATION
NLR INTERFACE GAS TURB / GEN PKG
2020-2022
2020-11-30 138T1733 C 4 of 5
GE Non-Public- Class II - (Non Critical) NLR
Doc Name : 138T1733 Rev C Released Date : 2022/03/23 Page 5 of 5
GENERATOR FOUNDATION
FOR DETAILS REFER TO GENERATOR MLI B7G0
For Information Only
ARRANGEMENT
OUTLINE FOUNDATION
NLR INTERFACE GAS TURB / GEN PKG
2020-2022
2020-11-30 138T1733 C 5 of 5