Commissioning Summary:
1. Device Information
Category No. Name Information Record
1.1 Device model UPS5000E
1.2 Device SN N022B1047198
Device
1.3 UPS rack capacity (kVA) 120
information
1.4 Capacity of a single module (kVA) Others
1.5 Cabling mode Top cabling
Ensure that the PDC is free of metal scraps and dust and is
2.6
sealed in a standard manner.
UPS mains 2.9 Cable for each phase (L1, L2, and L3) of mains input (mm2) 25
input 2.10 Mains input N cable (mm2) Same as the live wire
Page 1 of 13
UPS output
2.15 Output N cable (mm2) Same as the live wire
Page 2 of 13
2.35 Ambient environment
Installation
photo
Page 3 of 13
2.42 Power module surface
3. Parameter Configuration
Category No. Parameter Configuration
3.1.1 Single UPS/Parallel UPSs Single
Basic number of racks connected in parallel (not involved in the
3.1.2 1
single
Number UPS scenario) racks connected in parallel (not involved in
of redundant
3.1.3
System settings the single UPS scenario)
3.1.4 Working mode Normal mode
3.1.5 BSC mode Non-BSC mode
3.1.6 Altitude (m) (derated when the altitude exceeds 1000 m) ≤ 1000
3.2.1 Battery string sharing Disable
3.2.2 Battery type Lead-acid battery
3.2.3 Single battery voltage (lead-acid battery) (V) 12
Battery settings 3.2.4 Single battery capacity (lead-acid battery) (Ah) 40
3.2.5 Battery quantity in a string (lead-acid battery) 40
3.2.6 Battery string quantity (lead-acid battery) 1
3.2.7 Charging current limiting coefficient (C)
3.3.1 MUE05A connection Enable
3.3.2 Battery ground fault [BTG] Disable
3.3.3 Genset connection [GEN] Disable
3.3.4 BCB connection [OL] (If the battery switch box or BIB board is Disable
3.3.5 installed, set this
Battery circuit parameter
breaker statusto[STA]
Enable.)
(If the battery switch box or Disable
Dry contact 3.3.6 BIB
EPOboard is installed,
detection [EPO] set this parameter to Enable.) Disable
settings
3.3.7 PDF output switch [OUT] Disable
3.3.8 PDF maintenance switch [MT] Disable
3.3.9 PDF bypass input switch [BP] Disable
3.3.10 SPD status [SPD] Disable
3.3.11 MUE06A connection Disable
4. Function Test
Category No. Test Item Test Result
4.1.1 Single inverter startup Pass
4.1.2 Mains inverter-to-battery mode Pass
Single UPS 4.1.3 Battery-to-mains inverter mode Pass
functions 4.1.4 Single inverter shutdown to bypass mode Pass
4.1.5 Maintenance bypass Pass
4.1.6 Lead-acid battery switch tripping Pass
Parallel UPS 4.2.1 Parallel inverter startup N/A
functions 4.2.2 Parallel inverter shutdown to bypass mode N/A
Page 4 of 13
5. Running Parameters
Category No. Parameter Parameter Record (Photo)
Running
5.1 Running software version
parameter
Fire Fighting and 6.1 UPS equipment room fire extinguishing system
Emergency
Response
7. Maintenance Suggestions
Maintenance 1. Ensure that the equipment room door is normally closed, the air conditioners keep running properly, and the
suggestions equipment room temperature is within a required range.
2. Keep the equipment room clean and regularly clean or replace the equipment dust filter.
.
8. Commissioning Conclusion
Commissioning
Pass
conclusion
Customer
signature
Remarks
Welcome to Huawei Digital Power service hotline. If you have any questions or need help, please contact us via the
following ways:
(1) Service hotline: 400-822-99992
(2) Inquiry email: dpcaisd@huawei.com
(3) Search for and follow the Huawei Digital Power Service official account in WeChat, and leave a message.
You can also use the intelligent Q&A to search for what you want to know. Please stay tuned for future updates.
Page 5 of 13
UPS5000 Commissioning
and Acceptance Report
${contract}
Contract No. :
Delivery
Organization : ${buOrgName}
Commissioning
Engineer : ${docCreateName}
Commissioning
Date : ${docCreateDate}
Commissioning and acceptance items: total: 87; normal: 87; abnormal: 0
Parameter configu r at io n F un ct io n t e st
check c he ck
Main tenance Su gg e st io ns /
Commission ing Co nc lusi on