Professional Documents
Culture Documents
TBA 09 Detailing of Clay Masonry
TBA 09 Detailing of Clay Masonry
TBA 09 Detailing of Clay Masonry
Detailing of
Clay Masonry
Manufacturer: Claypave
Brick collection: Dry Press - Red
Builder: Cru Collective
Contractor: TDM Constructions
Photography credit: Andy Macpherson
Studio
1 Introduction 7
2 Roof Anchorage 8
3 Wall Supports 10
4 Prevention of Dampness 13
4.6 Weepholes 15
5 Lintels 17
5.1 General 17
5.2 Definitions 17
5.5.1 General 26
5.5.2 Angle lintels 26
5.6.1 Notation 27
6 Movement Gaps 29
6.1.1 Thermal 29
6.2.1 General 30
7 References 37
Tables
1. Moment requirements for lintels
supporting non-loadbearing walls 19
Roof anchorages are required to For higher wind loads, a detail Figure 2. Roof - cavity wall (high
resist not only uplift from wind such as that shown in Figure wind)
forces, but also lateral shear 2 can be used. In this detail
from wind and earthquake the tie-down strap is attached
forces. Requirements vary directly to the rafter or truss
widely for different regions, and uses a steel bar embedded
depending on the level of wind in both leaves of masonry to
and earthquake risk. Where mobilise a greater weight of
the term high wind is used, it the wall. For very high wind
should not be taken to include loads such as in cyclonic regions 25 x 1 mm
gal.straps at
cyclonic wind conditions, but a continuous tie-down rod 1200 crs max.
600 mm min.
There are many different types Figure 9 shows an alternative Figure 10. Base of a cavity wall
of supports for walls, including detail for a cavity wall, supported with suspended floor
footings, slabs and shelf angles.
Requirements for residential slabs on a strip footing with a floor slab DPC
and footings are covered by AS founded on compacted fill. In this Weep holes at
2870. Typical details are shown case the flashing does not extend 1200 crs max.
here for cavity walls, veneer walls, across the cavity; proper drainage
single-skin walls, and internal is ensured by an outward-sloping 150 mm min. Ant cap if
min. required
walls, support of walls on slabs fill of mortar at the base of the
and supports for the tops of cavity. The damp-proof course in
internal walls. Some details for the outer leaf should be at least Mortar fill
the support of walls on nibs 150 mm above the finished ground Strip footing in cavity
and shelf angles are shown in level (if not paved) and the sub-
Section 6. floor membrane should extend
around the front of the slab and be
Weepholes (see Section 4.6) embedded beneath the inner leaf.
should be provided above all
flashings. Termite protection Figure 9. Base of a cavity wall on 3.2 Veneer walls
measures might also be required a strip footing with slab on fill
but are omitted here for clarity. For a veneer wall on a raft slab, as
shown in Figure 11, the step down
Sub-floor can be any convenient dimension
3.1 Cavity walls DPC membrane
Weep holes
wrapped around of at least 20 mm, but the flashing
slab edge
at 1200 crs must extend up at least 150 mm
The detail shown in Figure 8 is max. Compacted fill
above the base and be attached
for supporting a cavity masonry 150 mm min.
to the timber framing. The
wall on a raft slab. The step down
flashing also acts as a damp-
at the edge of the slab can be any
proof course for the masonry.
convenient height but must be Strip footing
The waterproofing membrane for
at least one course of brickwork Mortar fill in cavity
the slab must extend above the
to ensure adequate draining
finished ground level.
of the cavity. Usually, 86 mm is
the most convenient height.
The waterproofing membrane The detail shown in Figure 10 is
beneath the slab must extend for a cavity wall on a strip footing Figure 11. Base of a veneer wall on
above the finished ground level. with a suspended timber floor. The araft slab
Mortar should be packed behind important elements are similar to
the flashing to minimise the risk the previous detail. The ant cap,
of it being punctured. when required, can be combined
with the damp-proof course.
Timber frame
Ventilation required for the sub- Flashing/DPC
Figure 8. Base of a cavity wall on
floor area is not shown. Weep holes
a raft slab at 1200 crs
max. 150 mmm min.
20 mm
min.
Flashing/
DPC
Compacted fill
Waterproof
coating
Internal single-
Starter bar storey wall (brick
hooked into Slab or framed)
footing strengthening
Compacted fill
Membrane
Membrane
Flashing
Cornice fixed
to ceiling Trimmer fixed to top plate Ceiling joist
Allowance for with framing anchor
truss deflection
15 mm min.
Gap to
accommodate
3.7 Tops of internal walls movement
Framing anchor
to trimmer and Top plate fixed
joist with chemical
The tops of internal walls should anchors
always be supported so that the
wall has sufficient robustness
and resistance to incidental
loads caused by pressure Figure 18. Internal wall supported
differences within the building. In by a top plate
earthquake prone regions, there is
also a requirement for resistance
to lateral forces generated by
Framed roof ceiling joist
earthquakes. The details for
providing this support vary
depending on the level of loading
and local construction practices.
Typical details for low earthquake Top plate attached
risk areas, providing support to ceiling joist and
top of wall
Cornice attached
to top plate by
against nominal wind loads, are packing piece
shown in Figure 17 and Figure 18.
The most important requirement
for these details is provision for
movement between the different
materials at the wall-ceiling
junction.
Problems relating to water jointing or other poor bricklaying highly resistant to salt attack,
penetration into masonry practices. Defects in flashings can the provision of an additional
buildings happen all too often, also be a cause. DPC close to ground level is
but they can be prevented. recommended.
Construction methods exist which Cavity wall construction operates
if carefully followed, will ensure on the principle that the cavity Membrane-type DPCs must be
a durable and watertight building. provides a break between a wet laid across the full width of the
outside leaf and a dry inside leaf. wall or leaf and should be visible
Where dampness or deterioration This is usually an effective barrier on either side when the brickwork
due to water occurs in walls, it is to penetration of rainwater falling is completed to show that the
common to find that the cause on the face of the wall unless large operation of tooling the joint has
of failure is a poor architectural gaps allow water to enter and not provided a bridge of mortar
detail, unsuitable materials, bad either blow or splash across the across the membrane. If the
workmanship or a combination cavity. The effectiveness of the membrane is carried across the
of them all. Any of these causes cavity will be greatly reduced if it cavity to form a flashing, it should
might arise from a lack of is bridged by mortar droppings or incorporate a step-up of two
understanding of the properties of poorly designed or installed wall courses from the outside to the
the materials involved, although ties. Free drainage of the cavity inside leaf (see Section 3).
carelessness or building down to a must occur if water transmission
price will sometimes be the cause to the inner leaf is to be avoided. 4.3 Cavity flashings
of bad workmanship.
The porous nature of both In order to be effective, a
The NCC (Housing Provisions) bricks and mortar contributes wall cavity must act as an
includes various details of significantly to the water uninterrupted gap between
construction practice for flashings tightness of a wall. Their blotting a wet external leaf and a dry
and damp-proof courses that are paper action of soaking up free internal leaf. Whenever it is
deemed to be acceptable and water considerably reduces bridged or interrupted by
should be read in conjunction the load on flashings and other other parts of the building, for
with this manual. waterproofing elements and example by frames in openings
the water-holding capacity of or structural elements such as
4.1 Prevention of water brickwork is seldom exceeded by columns, beams, shelf angles or
penetration through walls the volume of water delivered to it haunches, special precautions
during a period of rain. are required to prevent the
Bricks and mortar both contain transfer of moisture across the
fine pores or capillaries of irregular 4.2 Damp-proof courses cavity. The flashing details given
shape and size extending for in Section 3 and Section 6.4 (for
various distances and directions. The correct locations for ground nibs and shelf angles) set out the
Water lodging on one surface of and floor-level damp-proof general principles applicable to
a wall made of these materials courses (DPCs) are shown in waterproofing of interruptions to
will be drawn into the pores by Section 3. In some regions in the the cavity.
capillary force. If sufficient water past, it has been the accepted
is present over a long enough practice to provide two DPCs Weep-holes are necessary to drain
time, it may eventually penetrate below timber floor level, but a any water that may be collected by
through the full thickness of the single membrane is now often the cavity flashings to the outside
wall to appear as dampness on recommended. The combination of the wall. Particular precautions
the inside. This is a possible cause of a DPC and a termite shield in are required in walls exposed to
of dampness in walls with no this location will be necessary high winds, because air pressure
cavity, but capillary action will not in many regions. Where there is on the external face can prevent
result in water running down the any risk that surrounding ground the water from escaping through
inside face of such a wall. Most may be waterlogged and the brick the weep holes. When there is
free water found in this location to be used below the floor level such a risk, the step across the
enters through gaps in the DPC is not of a type known to be cavity should be increased.
joints due to bed furrowing, tip
Detailing of Clay Masonry / 13
Squaring-up the flashing to have at least 5 mm clearance Figure 24. Window sill flashing –
Squaring-up the flashing to follow Windows installed into lower- Figure 24. Window sill flashing –
follow the horizontal and vertical between the underside of the metal window in a veneer wall
the horizontal and vertical surfaces storey brick veneer walls of houses metal window in a veneer wall
surfaces is preferred to the sill and the top of the sill brick to
is preferred to the common (using softwood framing) must
common practice of carrying the allow for shrinkage of the timber
practice of carrying the flashing have at least 5 mm clearance
flashing across the cavity in a frame. For second-storey windows
across the cavity in a straight between the underside of at
theleast
sill
straight diagonal slope. It is most the clearance should be
diagonal slope. Itthat
important is most
all joints in the and
10 the
mm.topThisofgap
the should
sill brickbetosealed Weather strip or
Weather strip or
important that alladequately
joints in thelapped sealant
flashing are allow
withfor shrinkage
a flexible of the timber
sealant. sealant
Clearance
flashing
andare adequately
sealed, lapped
particularly atand
corners. frame. For second-storey windows Clearance
(see text)
sealed, particularly at corners. (see text)
the clearance
Typical should details
sill flashing be at least
are Sill brick projects
10shown
mm. This gap should
in Figure 21 andbe sealed
Figure 22 10Sill
mm brick
min.projects Flashing to
4.4 Window flashings 10 mm min. extend at
Flashing to
4.4 Window flashings with a flexible sealant.
for timber-frame windows and least extend at
Weep holes at 100 mm
Figure 23 and Figure 24 for metal- 1200 crs max. least
Flashing
Flashing underunder
window window sills
sills should Weep holes at beyond100 mm
Typical
framesill flashing details are
windows. 1200 crs max. each jamb
beyond
extend should
acrossextend across
the cavity andthe becavity
and be embedded across shown in Figure 21 and Figure 22 each jamb
embedded across the full widththe of full 4.5 Roof and Parapet flashing
width of thethe
window intoonethe for timber-frame windows and
the window into bed joint
bed jointthe
one course Figure 23 and Figure 24 for
course below sill brick.below
The the The recommended uses of DPCs
sill can
brick. metal-frame windows.
flashing beThe flashingthrough
embedded can be in4.5 Parapet
parapets flashing
are shown in Figure 25
embedded through the full width
the full width of the outer leaf if Figure 22. Window sill flashing – and Figure 26. Because parapets,
of the outer leaf if this will not Figure 22. Window sill flashing –
this will not affect the structural timber window in a veneer wall The recommended
free-standing uses
walls and oflike
the DPCs in
affect the structural sufficiency, timber window in a veneer wall
sufficiency, otherwise it may be are so exposed
parapets to the weather,
are shown in Figure 25
otherwise it may be embedded 25 they
embedded 25 mm into the outer andare particularly
Figure prone
26. Because to
parapets,
mm into the outer leaf. Alternative damage from water
leaf. Alternative details, such as free-standing wallspenetration
and the like are
details, such as draping the and
draping the flashing
flashing in the cavity,
in the cavity, are not
Sealant so need protection
exposed by high shear
to the weather, they
are not recommended. The flashing Clearance strength DPCs at both
are particularly pronetop and
to damage
recommended. The flashing (see text) bottom.
should extend into the cavity
should extend into the cavity by by from water penetration and need
100 mm 100to mm200tomm
200beyond
mm beyond each each protection by high shear strength
Sill brick Figure 25. Parapet flashing – solid wall
window jamb.jamb.
window projects Flashing to DPCs at both top and bottom.
Mortar
10 mm min. extend at Particular attention must be paid
weathering
least 100 mm
Figure 21. Window sill flashing – beyond each to the stability of parapets and
Weep holes at jamb
timber window
Figure in a cavity
21. Window wall
still flashing- 1200 crs max. free-standing walls because a lack
Over-flashing
timber window in a cavity wall of restraint
DPC belowmakes themtoprone
gutter to
parapet cap
sliding or overturning where the
Figure 23.
Figure Window
23. Window sillsill
flashing ––
flashing bond is broken at the DPC.
metal window
metal window inin
a cavity
a cavity wall
wall DPC to
protect
Sealant The requirements
brickwork for the DPC
Flashing to
extend at resultbelow
from two factors: the
parapet
least membrane must be sufficiently
Sill brick
100 mm
projects robust to allow it to be placed in
beyond
10 mm min.
each jamb the wall
Sealant Flashing to Figure 26.without
Parapet risk of –
flashing
Weep holes at
1200 crs max.
extend at
Weather strip Flashing to perforation
cavity wall from angular particles
least DPC
Sill brick or sealant extend at intruding into the bed and it must
100 mm sandwiched
projects least
beyond Weather strip Flashing to not extrude from the joint under
in mortar
10 mm min. Sillor
brick projects 100 mm
each jamb sealant extend at under coping
Weep holes at 10 mm min. beyond
least load
Weepfrom
holes above. The application
each
100 jamb
1200 crs max. Sill brick projects mm of a skim of mortar to flush
at 1200 crs up the
Over-flashing
10 mm min.Weep holes at beyond max.
1200 crs max. each jamb bed before placing the membraneRoof membrane
The through-flashing
configuration can consist of Stepped flashings are made up of
a combination of straight sections, called trays, and detailed Figure 29. Stepped flashing to
flashings, stepped flashings as shown in Figure 29 and 30. Each masonry veneer wall (detailed view)
and soaker flashings. Where the tray shall:
wall/roof abutment is sloped,
• At minimum, be turned up
a stepped ‘cascade’ flashing is Weepholes
75 mm in the cavity and be
required. Acceptable flashing Tray flashing shall overlap the
fixed to the inner frame of tray below by 75mm min
configurations are shown in
the wall, and turned down Soaker flashing
Figures 27 and 28.
75 mm to the roof or soaker
flashing
Straight flashings are simple
configurations, as shown in • Be boxed up a minimum of
Figure 27a: 40 mm at the end to allow
for the passage of water to Soaker flashings are supplementary
• Be lapped at joints by a to the system and may not be
the tray below
minimum of 150 mm required, depending on the type of
• Overlap the tray below by a stepped flashings used - see Figure
• At minimum, be turned up 75
minimum of 75 mm 29.A detailing example for soaker
mm to the inner frame and
flashing are shown in Figure 30 and 31:
turned down 75 mm to the • Have weepholes nearby
roof or soaker flashing which are not concealed by • Be lapped at joints by a
the tray above minimum of 150 mm
• Have weepholes spaced
maximum 1.2 m apart • If a soaker flashing is • At minimum, be turned up
used, overlap the soaker 75 mm 40 behind overflashing
• If a soaker flashing is 40 min.
min.
by a minimum of 75 mm,7575min.
min. and turned out 150 mm onto
used, overlap the soaker 40 min.
otherwise turned out a the roof.
by a minimum of 75 mm, 75 min. 7575 min.
min.
minimum of 150 mm if no
otherwise turned out a Figure 30. Stepped flashing 75 min.
tray
soaker is used.
40 min.
minimum of 150 mm if no 75 min. options
Figure 28a. Stepped flashing for
40 min.
soaker is used. 75 min.
75 min.
Fan or lap
soaker
flashing at
ridge
A B C D
Open perpend (no Small weep holes Blind weep hole formed Combined weep
mortar on flashing) every 2 or 3 bricks by face tip joining holes every 3 or 4
bricks
5.1 General While the methods of design used 5.3 Using the design tables
in this note do not utilise the
Lintels are necessary to support moment capacity of brickwork, The design tables in Section
brickwork over door and window the ability of brickwork to form 5.4 can be used for openings
openings in walls. There are an arch over openings has been in internal, external and gable
many types of lintels and no one allowed for. The function of the walls. Reference need not be
type is best in all circumstances. lintel is to provide support for the made to Section 5.6 (Design by
Questions of performance, triangle of brickwork above the Calculation) unless verification
economy, appearance and opening, which does not form of the determined lintel size is
durability must be considered part of the arch, and it must be required. This manual considers
when specifying lintels. strong and stiff enough to prevent the support of single leaf walls
This section gives structural separation of the triangle from only; cavity walls should be
requirements that can be used to the adjoining brickwork. When treated as two single-leaf walls,
specify any type of commercially the height of brickwork over the each requiring support.
made lintel. The requirements opening is too small to form an
are given in tabular form for arch of adequate strength, the Point loads are not covered in
situations where clay brickwork is lintel must be able to carry all the design tables. For the design
to be supported over openings up of the loads acting above the of lintels to carry point loads,
to 4.2 m in span and the brickwork opening. reference should be made to
is either non-loadbearing or Section 5.6. It is also possible in
supports domestic floor or roof There is no need to create a some circumstances where wind
loads. The design assumptions high shear capacity in the loads are high and, for example, a
and methods of calculation are brickwork because all the forces light metal roof is used, that net
described. acting through the brickwork uplift forces will occur on a lintel.
are resolved into compressive Such cases are not provided for in
A full examination of the stresses. Any brick and mortar the tables.
structural behaviour of brickwork combination that is suitable for
supported by lintels is beyond the conditions can be used. The two most significant factors
the scope of this manual and affecting the choice of lintels are
a number of conservative 5.2 Definitions strength and stiffness. A lintel
assumptions have therefore must have both adequate strength
been used. Lintel manufacturers A number of terms used and stiffness and the factor
usually provide load tables for throughout this section have that imposes the more severe
their products, some of which been given specific meanings requirement controls the choice
assume composite action to simplify the determination of lintel size. Usually the stiffness
between the lintel and the and selection of lintels. For the requirement is the more severe.
masonry. This is a very efficient purposes of this section the terms
structural action, which uses the have the following meanings: To determine the required
brickwork and the lintel together strength and stiffness of a lintel
as a beam to resist the loads. This Stiffness (EI) – the stiffness of a the following data must be known
action cannot be achieved for lintel is expressed in terms of the
all materials and has not been Modulus of Elasticity (E) and the i. The clear span of the opening
assumed in the tables presented Moment of Inertia (I) for which (L);
here. When using manufacturers’ the unit is kN.m2.
tables it is essential to check ii. The height of the brickwork
that the underlying assumptions Strength (M) – the strength of above the lintel (h); and,
are compatible with the a lintel is expressed in terms of
circumstances of the particular bending moment capacity for iii. The type and magnitude of
building being designed. which the unit is kN.m. the loads acting upon the
lintel.
The tables provide the strength All tables have been prepared
and stiffness requirements for for limit states design using
the different lintel load types (see load factors from AS 1170.07. Type A Type B
Height of
Clear Span of opening. L (mm)
brickwork above
lintel, H (mm) 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 3.3 3.6 3.9 4.2
300 0.06 0.12 0.20 0.29 0.4 0.5 0.7 0.8 1.0 1.2 1.4 1.6
600 0.08 0.18 0.33 0.52 0.7 1.0 1.3 1.6 2.0 2.3 2.8 3.2
900 0.08 0.18 0.35 0.61 0.9 1.3 1.8 2.2 2.8 3.4 4.0 4.7
1200 0.08 0.18 0.35 0.61 1.0 1.4 2.0 2.7 3.4 4.2 5.0 5.9
1500 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.7 4.7 5.7 6.9
1800 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.1 7.5
2100 or more 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
Height of
Clear Span of opening. L (mm)
brickwork above
lintel, H (mm) 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 3.3 3.6 3.9 4.2
300 1.9 4.7 9.4 16.6 26.6 40 57 78 105 136 188 252
600 2.1 6.5 16.0 29.7 49.1 75 109 151 203 265 367 496
900 2.1 6.5 15.9 32.9 63.7 101 150 212 289 381 530 720
1200 2.1 6.5 15.9 32.9 61.0 104 177 256 355 475 670 917
1500 2.1 6.5 15.9 32.9 61.0 104 167 254 279 543 777 1076
1800 2.1 6.5 15.9 32.9 61.0 104 167 254 372 527 844 1188
2100 or more 2.1 6.5 15.9 32.9 61.0 104 167 254 372 527 786 1138
1.8 0.18 0.44 0.79 1.24 1.8 2.4 3.1 4.0 4.9 5.9 7.0 8.2
3.0 0.26 0.65 1.18 1.86 2.7 3.7 4.8 6.1 7.5 9.1 10.8 12.6
300 4.2 0.34 0.86 1.58 2.49 3.6 4.9 6.4 8.2 10.1 12.2 14.5 17.0
5.4 0.42 1.07 1.97 3.12 4.5 6.2 8.1 10.3 12.7 15.3 18.3 21.4
6.6 0.50 1.28 2.36 3.75 5.4 7.4 9.7 12.4 15.3 18.5 22.0 25.8
1.8 0.08 0.18 0.53 0.99 1.6 2.3 3.0 4.0 5.0 6.1 7.4 8.7
3.0 0.08 0.18 0.66 1.30 2.1 3.1 4.2 5.5 7.0 8.6 10.4 12.4
600 4.2 0.08 0.18 0.79 1.62 2.7 3.9 5.4 7.1 9.0 11.1 13.5 16.1
5.4 0.08 0.18 0.92 1.93 3.2 4.8 6.6 8.7 11.0 13.7 16.6 19.7
6.6 0.08 0.18 1.05 2.25 3.8 5.6 7.8 10.2 13.0 16.2 19.6 23.4
1.8 0.08 0.18 0.35 0.61 1.2 1.9 2.8 3.8 4.9 6.2 7.6 9.1
3.0 0.08 0.18 0.35 0.61 1.4 2.4 3.5 4.9 6.4 8.1 9.9 12.0
900 4.2 0.08 0.18 0.35 0.61 1.6 2.8 4.2 5.9 7.8 10.0 12.3 14.9
5.4 0.08 0.18 0.35 0.61 1.8 3.2 4.9 6.9 9.2 11.8 14.7 17.9
6.6 0.08 0.18 0.35 0.61 1.9 3.6 5.6 8.0 10.7 13.7 17.1 20.8
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.4 3.4 4.7 6.0 7.6 9.2
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.6 4.0 5.5 7.3 9.3 11.4
1200 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.8 4.5 6.4 8.6 11.0 13.6
5.4 0.08 0.18 0.35 0.61 1.0 1.4 3.1 5.0 7.3 9.8 12.7 15.8
6.6 0.08 0.18 0.35 0.61 1.0 1.4 3.3 5.5 8.1 11.1 14.4 18.0
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.1 5.6 7.3 9.1
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.4 6.3 8.3 10.6
1500 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.7 6.9 9.3 12.0
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 5.0 7.5 10.3 13.5
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 5.3 8.1 11.4 14.9
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.7 8.6
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 7.0 9.3
1800 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 7.3 10.1
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 7.7 10.8
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 8.0 11.5
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
2100 or 3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
more 5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
1.8 4.7 15 33 62 103 160 235 329 446 587 819 1112
3.0 6.6 21 49 92 155 240 353 496 673 888 1239 1686
300 4.2 8.4 28 64 122 206 321 472 663 901 1189 1660 2259
5.4 10.3 35 80 152 257 401 590 831 1128 1490 2081 2832
6.6 12.2 41 96 182 308 481 709 998 1356 1791 2502 3406
1.8 2.1 6.5 24 52 195 155 236 339 468 626 883 1212
3.0 2.1 6.5 29 67 126 209 320 464 645 867 1228 1690
600 4.2 2.1 6.5 34 82 157 262 405 590 822 1108 1572 2168
5.4 2.1 6.5 40 97 187 316 490 715 999 1348 1916 2646
6.6 2.1 6.5 45 112 218 369 574 841 1176 1589 2261 3123
1.8 2.1 6.5 15.9 33 79 141 227 338 478 651 932 1293
3.0 2.1 6.5 15.9 33 89 168 277 421 605 832 1200 1676
900 4.2 2.1 6.5 15.9 33 99 195 328 505 731 1012 1468 2058
5.4 2.1 6.5 15.9 33 110 222 379 588 857 1193 1735 2440
6.6 2.1 6.5 15.9 33 120 248 430 672 984 1373 2003 2822
1.8 2.1 6.5 15.9 33 61 104 202 319 469 656 957 1347
3.0 2.1 6.5 15.9 33 61 104 219 361 545 776 1148 1633
1200 4.2 2.1 6.5 15.9 33 61 104 236 403 621 897 1339 1920
5.4 2.1 6.5 15.9 33 61 104 253 445 697 1017 1530 2207
6.6 2.1 6.5 15.9 33 61 104 270 486 773 1137 1722 2493
1.8 2.1 6.5 15.9 33 61 104 167 254 435 633 949 1362
3.0 2.1 6.5 15.9 33 61 104 167 254 460 693 1064 1554
1500 4.2 2.1 6.5 15.9 33 61 104 167 254 486 753 1178 1745
5.4 2.1 6.5 15.9 33 61 104 167 254 511 814 1293 1936
6.6 2.1 6.5 15.9 33 61 104 167 254 536 874 1408 2127
1.8 2.1 6.5 15.9 33 61 104 167 254 372 527 901 1332
3.0 2.1 6.5 15.9 33 61 104 167 254 372 527 939 1427
1800 4.2 2.1 6.5 15.9 33 61 104 167 254 372 527 977 1523
5.4 2.1 6.5 15.9 33 61 104 167 254 372 527 1016 1618
6.6 2.1 6.5 15.9 33 61 104 167 254 372 527 1054 1714
1.8 2.1 6.5 15.9 33 61 104 167 254 372 527 786 1138
2100 or 3.0 2.1 6.5 15.9 33 61 104 167 254 372 527 786 1138
4.2 2.1 6.5 15.9 33 61 104 167 254 372 527 786 1138
more 5.4 2.1 6.5 15.9 33 61 104 167 254 372 527 786 1138
6.6 2.1 6.5 15.9 33 61 104 167 254 372 527 786 1138
1.8 0.13 0.30 0.54 0.83 1.2 1.6 2.1 2.6 3.2 3.9 4.6 5.4
3.0 0.18 0.42 0.76 1.19 1.7 2.3 3.0 3.8 4.7 5.7 6.8 7.9
300 4.2 0.22 0.54 0.98 1.55 2.2 3.0 4.0 5.0 6.2 7.5 8.9 10.4
5.4 0.27 0.66 1.21 1.91 2.8 3.8 4.9 6.2 7.7 9.3 11.0 12.9
6.6 0.31 0.78 1.43 2.27 3.3 4.5 5.9 7.4 9.1 11.1 13.2 15.5
1.8 0.08 0.18 0.44 0.79 1.2 1.7 2.3 2.9 3.7 4.5 5.4 6.4
3.0 0.08 0.18 0.52 0.97 1.5 2.2 3.0 3.8 4.8 5.9 7.1 8.5
600 4.2 0.08 0.18 0.59 1.15 1.8 2.7 3.6 4.7 6.0 7.4 8.9 10.5
5.4 0.08 0.18 0.67 1.33 2.2 3.1 4.3 5.6 7.1 8.8 10.6 12.6
6.6 0.08 0.18 0.74 1.51 2.5 3.6 5.0 6.5 8.3 10.2 12.4 14.7
1.8 0.08 0.18 0.35 0.61 1.1 1.7 2.4 3.1 4.0 5.0 6.0 7.2
3.0 0.08 0.18 0.35 0.61 1.2 1.9 2.8 3.7 4.8 6.0 7.4 8.9
900 4.2 0.08 0.18 0.35 0.61 1.3 2.2 3.2 4.3 5.6 7.1 8.7 10.5
5.4 0.08 0.18 0.35 0.61 1.4 2.4 3.6 4.9 6.5 8.2 10.1 12.2
6.6 0.08 0.18 0.35 0.61 1.5 2.6 4.0 5.5 7.3 9.3 11.5 13.9
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.2 3.1 4.1 5.2 6.5 7.8
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.4 3.4 4.6 5.9 7.4 9.1
1200 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.5 3.7 5.1 6.7 8.4 10.3
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.6 4.0 5.6 7.4 9.4 11.6
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.8 4.3 6.1 8.1 10.3 12.8
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.0 5.2 6.6 8.1
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.1 5.6 7.2 9.0
1500 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.3 5.9 7.8 9.8
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.4 6.3 8.4 10.6
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 4.6 6.7 8.9 11.5
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.4 8.1
3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.6 8.6
1800 4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.8 9.0
5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 7.0 9.4
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 7.2 9.8
1.8 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
2100 or 3.0 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
4.2 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
more 5.4 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
6.6 0.08 0.18 0.35 0.61 1.0 1.4 2.1 2.8 3.8 4.9 6.2 7.7
1.8 3.3 9.9 21.6 39.8 66 102 149 208 281 369 513 696
3.0 4.3 13.3 29.6 55.3 93 143 210 294 398 524 730 991
300 4.2 5.2 16.8 37.7 70.9 119 185 271 380 515 679 947 1287
5.4 6.2 20.2 45.8 86.4 145 226 332 466 632 834 1164 1583
6.6 7.2 23.7 53.9 101.9 172 267 393 552 750 989 1381 1878
1.8 2.1 6.5 20.1 41.3 73 117 174 248 340 451 633 865
3.0 2.1 6.5 22.8 49.1 89 144 218 313 431 575 811 1111
600 4.2 2.1 6.5 25.5 56.9 105 172 262 377 522 699 988 1358
5.4 2.1 6.5 28.1 64.6 120 199 305 442 613 824 1166 1604
6.6 2.1 6.5 30.8 72.4 136 227 349 507 705 948 1343 1850
1.8 2.1 6.5 15.9 32.9 72 122 190 277 386 520 737 1016
3.0 2.1 6.5 15.9 32.9 77 136 216 320 452 613 876 1213
900 4.2 2.1 6.5 15.9 32.9 82 150 242 363 517 706 1014 1410
5.4 2.1 6.5 15.9 32.9 87 163 268 406 582 799 1152 1607
6.6 2.1 6.5 15.9 32.9 93 177 294 449 647 892 1290 1804
1.8 2.1 6.5 15.9 32.9 61 104 190 289 414 568 818 1138
3.0 2.1 6.5 15.9 32.9 61 104 198 310 453 630 916 1286
1200 4.2 2.1 6.5 15.9 32.9 61 104 207 332 492 693 1015 1434
5.4 2.1 6.5 15.9 32.9 61 104 216 353 531 755 1113 1582
6.6 2.1 6.5 15.9 32.9 61 104 225 375 571 817 1212 1729
1.8 2.1 6.5 15.9 32.9 61 104 167 254 417 589 865 1224
3.0 2.1 6.5 15.9 32.9 61 104 167 254 430 620 925 1322
1500 4.2 2.1 6.5 15.9 32.9 61 104 167 254 443 651 984 1421
5.4 2.1 6.5 15.9 32.9 61 104 167 254 456 682 1043 1519
6.6 2.1 6.5 15.9 32.9 61 104 167 254 469 713 1102 1618
1.8 2.1 6.5 15.9 32.9 61 104 167 254 372 527 873 1262
3.0 2.1 6.5 15.9 32.9 61 104 167 254 372 527 893 1311
1800 4.2 2.1 6.5 15.9 32.9 61 104 167 254 372 527 913 1361
5.4 2.1 6.5 15.9 32.9 61 104 167 254 372 527 932 1410
6.6 2.1 6.5 15.9 32.9 61 104 167 254 372 527 952 1459
1.8 2.1 6.5 15.9 32.9 61 104 167 254 372 527 786 1138
2100 or 3.0 2.1 6.5 15.9 32.9 61 104 167 254 372 527 786 1138
4.2 2.1 6.5 15.9 32.9 61 104 167 254 372 527 786 1138
more 5.4 2.1 6.5 15.9 32.9 61 104 167 254 372 527 786 1138
6.6 2.1 6.5 15.9 32.9 61 104 167 254 372 527 786 1138
Load
Clear Span of opening. L (mm)
width
(m) 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 3.3 3.6 3.9 4.2
1.8 0.8 1.4 2.3 3.4 4.7 6.4 8.3 10 13 16 19 23
3.0 1.2 2.2 3.6 5.2 7.2 9.6 12.4 16 19 23 28 33
4.2 1.7 3.0 4.8 7.1 9.7 12.9 16.6 21 25 31 36 43
5.4 2.1 3.9 6.1 8.9 12.2 16.2 20.7 26 32 38 45 53
6.6 2.6 4.7 7.4 10.7 14.8 19.5 24.8 31 38 45 54 63
Table 8: Stiffness requirements (EI) for lintels supporting walls and timber floors
(Unit is kNm2)
Load
Clear Span of opening. L (mm)
width
(m) 0.9 1.2 1.5 1.8 2.1 2.4 2.7 3 3.3 3.6 3.9 4.2
1.8 14.2 35.3 72 130 215 334 495 704 971 1304 1857 2579
3.0 22.3 54.5 110 195 318 488 713 1004 1370 1823 2571 3540
4.2 30.4 73.7 147 260 421 642 932 1304 1770 2341 2385 4500
5.4 38.5 92.9 185 325 524 795 1151 1604 2169 2860 4000 5461
6.6 46.6 112.1 222 389 627 949 1370 1904 2568 3378 4714 6422
T a bl e 9: S tiff n e s s a n d m o m e n t c a p a ci ti e s of c o m m o n s t e el li n t el o p ti o n s
S t e el S e c ti o n ( m e a s u r e m e n t s
S tiff n e s s EI ( k N m 2 ) B e n di n g C a p a ci t y M ( k N m)
i n m m) sx
75 x 8 F MS
1 0 0 x1 0 F MS
90 x 90 x 6 EA
90 x 90 x 8 EA
1 0 0 x1 0 0 x 6 E A
1 0 0 x1 0 0 x 8 E A
15 0 x 9 0 x 8 U A
1 5 0 U B 1 4. 0
1 5 0 U B 1 8. 0
1 8 0 U B 2 2. 2 49
6 m m 8 m m
75x8 F MS
8 m m
75 m m
90x90x6 E A 90 m m 90x90x8 E A
90 m m
100x10 F MS
10 m m
6 m m 8 m m
100 m m 90 m m 90 m m
6 m m 8 m m 8 m m
100x100x6 E A
100 m m 100x100x8 E A
100 m m
150x90x8 U A
150 m m
6 m m 8 m m
100 m m 100 m m 8 m m
90 m m
1 5 0 U B 1 4. 0 1 5 0 U B 1 8. 0 1 8 0 U B 2 2. 2
7 m m 9. 5 m m 10 m m
155 m m
150 m m 5 m m 6 m m 179 m m 6 m m
7 m m 9. 5 m m 10 m m
75 m m 75 m m 90 m m
D et aili n g of Cl a y M a s o nr y / 2 5
5.5 Construction details 5.5.2 Angle lintels With reinforced brickwork
Because angles tend to twist lintels, the brickwork is part of
5.5.1 General
when loaded, they should be an integrated structural system
Arch bars and angle lintels
carefully built-in and mortar in which the brickwork becomes
are vulnerable to corrosion,
should be packed between the the lintel beam. A small quantity
which may cause cracking of
vertical leg and the masonry of steel is placed near the tensile
the brickwork and unsightly
(see Figure 29). No angle with a face and the brickwork carries the
staining. It is recommended that
bottom leg less than 70% of the compressive forces. The greater
all steel lintels be either stainless
width of the brick it supports the height of the brickwork, the
steel or hot dip galvanised after
should be used and the overhang larger is the bending strength of
fabrication, or receive equivalent
should not exceed 25 mm. the brickwork lintel.
protection before installation.
AS 3700 specifies requirements
Angles and arch-bars with a flange The structural advantages make
for corrosion protection of
thickness of 10 mm are difficult reinforced brickwork lintels
accessories, including lintels,
to build into a standard bed joint particularly suited to large spans
depending on the exposure
thickness and therefore it is or where large loads must be
conditions (see also TBA Manual
desirable to select members not supported. In addition, the steel
7: Design of Clay Masonry for
greater than 8 mm in thickness. components in reinforced lintels
Serviceability).
are not visible when installed.
There should be at least three
Figure 34. Packing of mortar The use of any brickwork
courses of masonry over any
behind angle lintel to prevent reinforcing system should be
lintel. Lintels should be built into
twisting based on the manufacturer’s
the masonry at each end for a
literature.
distance of not less than 100 mm
for spans up to 1000 mm and 150
mm for larger spans, for the loads 5.5.4 Other types of lintels
described in the tables above. For A number of proprietary lintels are
Pack gap made for brickwork in addition
larger loads the masonry should with
be assessed to ensure that it is not mortar to the common steel lintels.
locally overloaded. The masonry They include lightweight box-
supporting the lintels should section metal lintels, reinforced
be constructed in a mortar not concrete lintels, prestressed
weaker than 1 cement: 2 lime: 9 concrete lintels, prestressed
sand by volume. The heads of all fired clay lintels and brickwork
25 mm max.
openings in cavity brickwork must reinforcement systems. A full
be properly flashed. discussion of these products is
5.5.3 Reinforced brickwork beyond the scope of this manual;
To allow the full arching action lintels use of these lintels should be
to develop in the masonry, Lintels that act compositely with based on the manufacturers’
lintels should be propped during the brickwork they support, for literature.
construction until the masonry example reinforced brickwork
has hardened. lintels, are recommended for a
number of reasons. With most
steel and concrete lintels, the
brickwork sits on top of and
is separate from the lintel.
The greater the height of the
brickwork the larger the load on
the lintel and hence the larger and
more expensive the lintel must
become.
buted loads,
buted loads, be be estimated
estimated
6. Movement Gaps
All building materials change in 6.1.2 Short term wetting and depends upon the material from
size as their temperature varies, drying which they are made. It is now
or as they are loaded or unloaded. generally accepted that the rate of
Some materials (such as concrete All masonry units expand on expansion diminishes with time
and cement products) shrink as wetting and contract on drying, and can be accurately represented
they dry out after being placed but these changes are usually not by a linear relationship with the
in position in a building and sufficient to require consideration logarithm of time.
shrink further as they cure. Clay in clay brickwork.
bricks expand slowly over a long Experience shows that if control
period of time. When different gaps are provided, with widths
materials are used together, 6.1.3 Long term permanent calculated on the basis of the
their different responses to expansion coefficient of expansion of the
changing loads, temperatures Expansion of fired clay units particular brick used in the
and moisture contents will lead begins as soon as they have cooled structure, stresses due to the
to size differences between after firing and takes place in all restraint of further growth are
them. The resulting differential three directions. This expansion unlikely to cause distress during
movements must be taken is due to reaction with moisture the remaining practical life of the
into account if damage to the and is sometimes referred to as building.
structure is to be avoided and this ‘permanent moisture expansion’.
is achieved through the provision All fired clay products, including 6.1.4 Coefficient of expansion
of movement gaps between parts bricks, are subject to chemical The coefficient of expansion
of the structure. reactions between water and is an estimate of the bricks’
certain constituent minerals growth in the first fifteen years
6.1 Dimensional changes in clay that cause them to expand. The after they are made. Values are
masonry units reactions begin when bricks in generally lower than they were
the kiln cool below about 400ºC, in the past because of a better
There are a number of potential they are not hastened by wetting understanding of the factors
sources of dimensional change in and, for practical purposes, are influencing expansion and better
clay masonry. All except long-term irreversible. control over the manufacturing
expansion are cyclic, reversible processes, particularly the firing
changes. Any atmosphere in which people temperature. When it is required,
can live and breathe contains the coefficient of expansion for
sufficient water to cause clay particular units can be obtained
6.1.1 Thermal
brick expansion and neither from the manufacturer.
The thermal expansion of clay
the magnitude nor the rate
bricks varies slightly depending
of expansion is measurably Coefficient of expansion is now
upon their colour and the method
changed when bricks are used given the symbol em, but it was
of manufacture, but the value is
internally rather than externally. often formerly referred to simply
unlikely to be greater than 0.008
However, total movement is made as the ‘e’ value. The value is
mm/m/ºC. Thermal expansion
appreciably less by the absence of determined by subjecting a brick
can be taken into account by
significant temperature changes fresh from the kiln to saturated
calculating the spacings of
and gaps to accommodate steam at atmospheric pressure.
movement gaps in external
movements are often not required This expansion has been shown
brickwork (see later) but no
in internal walls. to correlate well with natural
particular consideration need be
given for thermal expansion in expansion over a longer period.
The magnitude of long-term The test procedure is given in the
most internal brickwork.
permanent change in the standard test procedures for clay
dimensions of clay bricks (growth) masonry units (AS 4456.11)8.
Sv /2 max.
1/3 to 1/5
wall height Sv Sv
Slip joint at
min. re-entrant
corner
Sv /2 max.
Gaps close to corner to
enable panels to be tied to
the supporting frame
Consideration should also be where 0.35 mm/m is the each of the full-height gaps.
given to the provision of control allowance for thermal movement
joints at wall openings and at in the wall. In many instances, it may be
changes in wall thickness (other convenient to locate gaps at
than for piers, buttresses or other If the closure is to be limited to 15 some line or lines occurring on
members that provide support). mm, then: the facade, for example behind
downpipes. Wider spacing than
In developing a method for that calculated might be adopted
calculating the spacing of vertical with more safety on south and
gaps, the following notation is east-facing walls where the
used: movement from temperature
changes will be less.
Sv = Maximum spacing of
vertical gaps in walls (in metres). A nearly invisible joint can be
A similar approach to parapets provided at a re-entrant angle by
Svp = Maximum spacing of vertical gives: the provision of a straight joint
gaps in parapets (in metres). that permits the long wall to slide
behind the shorter return (see
em = The coefficient of expansion Figure 31).
of the clay unit used in the
construction (mm/m). For example, consider a clay brick Vertical movement
where em = 1.6 mm/m. Horizontal gaps to control vertical
It has been recommended practice Then; movement are required only in
for many years to design spacings buildings where the external leaf
of vertical control gaps in walls of masonry is non-loadbearing
based on half the 5-year expansion and is supported by a frame or
value. It is known that expansion and; floor slabs. In these situations,
varies with the logarithm of time10 provision is required for the
and the 5-year expansion is about shortening of the supporting
70% of the 15-year expansion (em). frame or walls, for the growth of
The design movement for walls is the clay bricks and for movements
therefore; The first gap in the main wall associated with temperature
should be no more than 8 m from differences between the internal
the corner and, in the parapet, 5 supporting structure and the
m from the corner. However, it external brick cladding.
Double this amount is used for is probably best to put the first
parapets. gap close to the corner and run
it through both the wall and
If the spacing of vertical gaps is parapet. Then, for this example,
Sv, the total closure at each gap full-height gaps in the run of wall
would be: and parapet would be at around
16.5 m centres, with an extra gap
in the parapet half way between
0.81 to 1.2 19 12 13 8
Medium 1.21 to 1.6 16 10 11 6 6.4.2 Horizontal gaps
Any element that supports
1.61 to 2.0 14 8 9 5 masonry cladding should have a
High 2.01 to 2.4 12 7 8 4 movement control gap beneath it.
Typical details of gaps and suitable
methods of providing support for
Table 11: Maximum spacings for horizontal control the cladding are given in Figure 32
gaps in clay masonry (m) and Figure 33.
Design Manual
Windows and external door 3 text:Design Manual 3 text 13/12/12 11:55 AM Page 13
sealed. The timber should overlap Steel Gal. steel Gal. steel
Head
door angle lintel Terrazzo
flat lintels
the brickwork by approximately Gal. steel
flat lintel
frame
supports Boxed eave
threshold
Infillflashings
slab
or framed
when
dooreaves
13 mm. Where window or door clay brick
masonry do not
Change slab edge protect
openings are larger than 900 mm Clay pavers mortared Paver
at external doors door
head
x 900 mm, articulated joints are to slab as
step
and fixing of frames STEEL DOOR FRAME to slab as ALUMINIUM-FRAME SLIDING DOOR TIMBER DOOR FRAME
in all cases the opening is required step
to be adequately supported.
Gal. steel Mastic bead
Head
angle lintel Re-bars Plug
Built-in flashing
Figure 14. Built-in
lintel builtlug
intoon
and
required
Built-in screw
External
Figure 42:doors showing
Lintel and flashing
Boxed eave details
gal. wire and fixing of window
beddoor
joint
frames in when
or nail
from
framelintel there is
lintel and flashing details clip
cavityand brick
fixing of frames STEEL DOOR FRAME ALUMINIUM-FRAME SLIDING DOOR TIMBER DOOR FRAME
no eave
protection
Splayed cut Sill brick
brick sill projecting
6.5.2 Cavity Brick Splayed
Gal. steel
cut brick
with 10 mm
projection
10 mm
beyond Head
Re-bars
Because the brickwork in sill angle lintel
Brick- at lowBuilt-in
edge
lintel
Tile
builtsill
into
face of
clay brick
Timber
flashing
sill
required
on-edge bed joint
the loadbearing leaf has to Boxed eave sill from lintel
masonry when
there is
no eave
be laid around the opening, Alternative sill
Full-width protection
flashing position sill flashing
specific detailing is required. Recommended
forSplayed
exposedcut
brick sill
conditions/
Sill brick
projecting
sill flashingSplayed with 10 mm Built-in 10 mm
Particular attention must be position cut brick
high rainfall
projection lug on beyond
sill at low edge window face of Timber
given to the building in of Brick-
on-edgeFlashing
Tile sill
frame clay brick
Flashing
sill
sill 100 min. masonry
extra ties at unbonded cross- Figure 15.
100 min.
Flashing
walls intersections and at Lintel and flashing details 100 min.
Alternative sill
Full-width
sill flashing
and fixing of window frames flashing position
for exposed
discontinuities such as window Recommended conditions/
Built-in
sill flashing high rainfall
jambs and articulation joints or position lug on
window
Window opening
Medium-duty wall ties at 600 mm centres (maximum) in body of wall. Ties at 300 mm average
(400 mm maximum) centres at top edge around openings, at control gaps and at lateral supports
12
Detailing of Clay Masonry / 36
Figure 16.
Cavity wall tie positioning
7. References
2 Masonry Structures,
AS 3700–2018 Standards
Australia, Sydney, 2018
Think Brick Australia represents
3 Masonry Structures – Commentary,
AS 3700-2012 Supplement 1, Standards
Australia’s clay brick and paver
Australia, Sydney, 2012. manufacturers.
5 Residential Slabs and Footings – Some of our most popular FREE technical
Construction Commentary, AS 2870 manuals include:
Supp1-1996 Standards
Australia, Sydney, 1996 • The Brickwork Manual: A step-by-
step guide to installing clay bricks
6 Manual 7, Design of Clay Masonry
for Serviceability, Clay Brick and
• Manual 9: Detailing of Clay Masonry
Paver Institute, • Manual 5: Design of Clay Masonry
Sydney October 2018 Walls for Fire Resistance
7 Structural Design Actions Part 0:
General Principles, AS 1170.0–2002 • Manual 10: Construction Guidelines
Standards Australia, for Clay Masonry
Sydney, 2002
d 1
gle pages.ind
k-Manual-2019-sin
Manual20-Brickwor
Sarking
There should be
Flashing Plaster Board a MIN. of three
brick courses
above M.S. lintels.
Lintel Flashing
Allow
15mm
Space Timber Lintel Lintel flashing
is not required
Packing when eave depth
as shown is not
Moulding if 15mm space less than 3x’H’.
Sash Top Rail necessary
Reveals Eave Depth
Sealant Aluminium
Glass behind Frame M.S. Gal. Lintel Angle
Glass Sealant
Brick Flashing
Sill
Weep holes at
Weep every 4th perp.
Holes
Sarking
Flashing
Sill
Lintel Stud
wall
Packing Exterior Infill
Head Panel
Architraves Fiber-cement
infill panel
Head Reveal overlaps
window frames.
Sealant
Retain 15mm
space between
head reveal and
lintel. Don’t use
wedges or packing.
The head reveal is
straightened by the
architrave.
Fasten according
to the AWA
(Australian
Window
Association) Sealant
installation guide.
Flashing
Weep holes
at every 4th
perp.