Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 37

NATIONAL BUILDING CODE

OF THE PHILIPPINES

National Building Code of the Philippines


REPUBLIC ACT NO. 6541 An Act to Ordain and Institute National Building Code of the Philippines

Chapter 1.01 GENERAL PROVISIONS


Title 1 ADMINISTRATIVE new buildings or structures. Alterations should preserve
SECTION 1.01.02: Declaration of Policy the aesthetic value of the building to be altered.

It is hereby declared to be the policy of the State SECTION: Application


to safeguard life, health, property, and public welfare, (a) This Code shall apply to all buildings and structures
consistent with the principles of environmental constructed and any change or repair made thereon after
management and control; and to this end, make it the the approval of said Code. Buildings or structures
purpose of this Code to provide for all buildings and constructed before the approval of this Code shall not be
structured, a framework of minimum standards and affected thereby; Except, where their continued use or
requirements by guiding, regulating, and controlling occupancy is dangerous to life or limb; or where
their location, siting, design, quality of materials, alterations, additions, conversions, or repairs are to be
construction, use, occupancy, and maintenance, made thereon, this Code shall apply only to such
including their environment, utilities, fixtures, portions of the buildings or structure which have to be
equipment, and mechanical electrical, and other systems altered in order to effect such damages or repairs.
and installations.
(b) This Code shall apply to chartered cities, poblaciones
SECTION: Scope of municipalities and municipal districts with a

(a) The provisions of this Code shall apply to the design, population of at least two thousand (2,000) inhabitants,

location, siting, construction, alteration, repair, and to barrios of urban areas with a population of at least

conversion, use, occupancy, maintenance, moving, and two thousand (2,000) inhabitants. This Code shall also

demolition of, and addition to, public and private apply to any area where there are fifty (50) or more

buildings and structures. families per hectare.

(b) Additions, alterations, repairs, and changes of use or (c) This Code shall likewise apply to any area proposed

occupancy in all buildings and structures shall comply for or being developed into a new town site, residential

with requirements for new buildings and structures subdivision, commercial or residential site, school site,

except as otherwise herein provided. Only such portion housing project, and similar construction projects where

or portions of the existing building or structure which five or more buildings not covered by paragraph (d) of

have to be altered to effect the addition, alteration, or this Section will be constructed even if the poblacion or

repair shall be made to conform to the requirements for barrio population is less than two thousand (2,000) or the
density of population is less than fifty (50) families per sanitary condition. All devices or safeguards, which are
hectare. required by this Code in a building or structure when
constructed, altered, or repaired, shall be maintained on
(d) The design and construction requirements of this good working order.
Code shall not apply to any traditional indigenous family
dwelling costing not more than five thousand pesos SECTION 1.01.07: Insanitary, Unsafe,
(P5,000.00) and intended for use and occupancy of the Hazardous, or Dangerous Sites
family of the owner only. The traditional type of family (a) The land or site upon which will be constructed any

dwellings are those that are constructed of native building or structure, or any ancillary or auxiliary facility

materials such as bamboo, nipa, logs, or lumber, wherein thereto, shall be sanitary, hygienic or safe. Where the

the distance between vertical supports or suportales does land or site is polluted, insanitary, unhygienic, unsafe, or

not exceed 3.00 meters (10 feet); and if masonry walls or hazardous, conditions contributing to or causing its being

socalos are used, such shall not be more than 1.00 meter polluted, insanitary, unhygienic, unsafe, or hazardous

(3 feet, 3 inches) from the ground: Provided, however, shall be reasonably improved or corrected, or proper

That such traditional indigenous family dwelling will not remedial measures shall be prescribed or incorporated in

constitute a danger to life or limb of its occupants or of the design or construction of the building or structure in

the public; will not be fire hazard or an eyesore to the accordance with the provisions of this Code.

community; and does not contravene any fire zoning


regulation of the city or municipality in which it is (b) The land or site upon which be constructed a building

located. of structure or any ancillary or accessory facility thereto,


for use of human habitation or abode, shall be at a safe
distance from streamers or bodies of water and/source of
SECTION 1.01.05 Building Use Affecting
Public Health and Safety air considered to be polluted, volcano or volcanic site,
(a) Any building or structure, or any ancillary or and building or structure considered to be a potential
accessory facility thereto, and any alteration or addition source of fire or explosion, such as ammunitions factory
to any building or structure already existing, shall or dump and storage place for highly inflammable
conform in all respects to the principles of safe material.
construction, shall be suited to the purpose for which the
building is designed, and shall, in no case contribute to
SECTION 1.01.08: Dangerous and Ruinous
making the community in which it is located at eyesore, Buildings or Structures
a slum, or a blighted area. Dangerous Buildings Defined. - Dangerous
buildings are those which are structurally unsafe or not
(b) Adequate environmental safeguards shall be provided with safe egrees, or which constitute a fire
observed in the design, construction, and use of any hazard, or are otherwise dangerous to human life, or
building or structure for the manufacture and production which in relation to existing use constitute a hazard to
of any kind of article or product which constitutes a safety or health or public welfare, by reason of
hazard or nuisance affecting public health and safety, inadequate maintenance, dilapidation, obsolescence, fire
such as explosives, gas, noxious chemicals, inflammable hazard, or abandonment; or which otherwise contribute
compounds, or the like. to the pollution of the site or the community to an
intolerable degree. Any building or structure which has
any or all of the conditions or defects hereinafter
SECTION: Maintenance
described, or conditions or defects similar thereto, shall
(a) All buildings or structures, both existing and new,
be deemed to be dangerous building: Provided, That
and all parts thereof shall be maintained in a safe and
such conditions or defect exists to the extent that the life,
health, property, or safety of the public or its occupant replacement cost of the building, it shall be repaired or
are endangered: demolished at the opinion of the owner;
(3) Where the dangerous building poses an immediate
Abatement of Dangerous Buildings threat to life, limb, or property, it shall be vacated

Abatement of Dangerous Buildings. In all cases immediately, then repaired or demolished in accordance

of dangerous buildings, except those covered by Article with subparagraphs (1) or (2) herein.

482 and 694 to 707 of the Civil Code of the Philippines,


the Building Official shall order their repair, vacation, or SECTION 1.01.10: Municipal and Provincial
demolition in accordance with the following procedure: Ordinances and Regulations
(a) Local ordinances should conform to the Code and
suppletory requirements hereto shall in no case diminish
(1) Where the dangerous building can reasonably be
minimum requirements embodied in this Code. The
repaired such that it will no longer be dangerous, it shall
Secretary of Public Works and Communications or, in
be ordered repaired;
the proper case, the Secretary of Justice shall take any
(2) Where the dangerous building is such that to repair it
and all appropriate steps in cases where local ordinances
would cost more than 50 per cent of the current to
conflict with the Code.

Chapter ENFORCEMENT
SECTION 1.02.03: Building permits (1) Group A traditional indigenous type of dwelling

(a) Any person, firm, or corporation, including any construction costing not more than three thousand pesos

department, office, bureau, agency of instrumentality of (P3,000.00); and

the government intending to construct, alter, repair, (2) Group J Division 1 Occupancy of Type 1

move, convert or demolish any building or structure, or conventional wood frame construction or of the

cause the same to be done, shall obtain a building permit traditional indigenous type of construction costing not

from the Building Official for whichever of such work is more than three thousand pesos (P3,000.00).

proposed to be undertaken for the building or structure,


before any such work is started. SECTION: Fees
(a) Regulations on building permit, inspection and other
(b) Appropriate rules and regulations shall be set by fees, and for compliance with the same shall be covered
the Secretary concerning:
by city and municipal ordinances: Provided, That
(1) Forms for application for building permits;
Traditional indigenous family dwellings under Section
(2) Procedures to be observed in securing such permits;
(d) shall be exempt from payment of building permit
(3) Procedures to be observed in the issuance,
fees.
suspension, and revocation of such building permits; and
(4) Type, nature, and scope of plans and specifications,
and other requisite documents, which shall be prepared SECTION 1.02.05: Inspection ad Certificates
of Occupancy
and designed by a licensed architect or engineer. (a) Inspection. The duly licensed architect or engineer
engaged by the owner to undertake inspection and
(c) When authorized by the Building Official in detailed supervision of the construction shall periodically
accordance with the provisions of this Code, plans certify that the construction conforms to the plans and
and specifications need not be submitted for the specifications submitted in the application for a building
following: permit. Upon submission of such periodic certifications
during the progress of construction, the Building Official
shall periodically issue the required authority to continue the Certificate should not be issued and shall indicate
with the subsequent phases of construction, without thereon the particular provisions of the Code violated or
prejudice to his right to conduct on his own initiative any the particular requirements not complied with. Within
inspection of the said construction. Upon completion of fifteen (15) days from receipt by the applicant of the
the construction, the said duly licensed architect or advice from Building Official or his Deputy authorized
engineer shall submit to the Building Official the final to issue the certificate why the certificate should not be
certification that the building conforms to the provisions issued, or why the certificate is suspended or revoked,
of the Code and with the detailed plans and the applicant may appeal the non-issuance, suspension,
specifications submitted. or revocation thereof, to the Mayor of the chartered city
or municipality, or the Governor of the province where
(b) Certificates of Occupancy. The proper Certificate of the building for which the certificate is being applied for
Occupancy shall be issued to the applicant within seven is located. Said appeal shall be decided within fifteen
(7) days from completion of the requirements for (15) days from receipts thereof, otherwise, the applicant
inspection and occupancy and payment of any and all may bring the matter to the proper Court of Justice for
fees therefor, unless the building Official or his Deputy final disposition. The building may be occupied only
issuing the Certificate shall show cause in writing why upon issuance of the Certificate of Occupancy.

Chapter REQUIREMENTS FOR FIRE ZONES


TITLE 2 - FIRE AND FIRE-RESISTIVE (c) Moved Building. Any building or structure moved
STANDARDS within or into any fire zone shall be made to comply
(a) Fire Zones Defined. Fire zones are areas within with all the requirements for buildings of that fire zone.
which only certain types of building are permitted to be
constructed based on their use, occupancy, type of (d) Temporary Buildings. Temporary buildings or
construction, and resistance to fire. structures conforming to the requirements of this Code,
used for the protection of the public around and in
(b) Building Located in More Than One Fire Zone. If a conjunction with construction work may be erected in
building or structure is located in more than one fire any of the fire zones: Provided, that such work is
zone and more than one-third of its total floor area is in a allowed by special permit from the Building Official and
more restricted fire zone, then the entire building shall such is used only for a limited period of time.
conform to the requirements for the more restricted area.

Chapter 2.02 - FIRE-RESISTIVE REQUIREMENTS AND STANDARDS FOR FIRE


PROTECTION
(a) Exterior bearing and nonbearing walls of Types II fire-resistive rating for partitions, and two-hour fire-
and III constructions shall have one-hour fire-resistive resistive rating for vertical openings, floors, and roofs.
rating; while those of types IV and V shall have four-
hour fire-resistive rating. (c) Structural frames of Types II and III constructions
shall have one-hour fire-resistive rating; those of Type
(b) Interior bearing walls, permanent partitions, floors, IV shall have two-hour fire-resistive rating; and those of
and roofs of Types II to IV constructions shall have one- Type V shall have three-hour fire-resistive rating.
hour fire-resistive rating; while those of Type V shall
have three-hour fire-resistive rating for walls, one-hour (d) Exterior doors and windows shall have three-fourths-
hour fire-resistive rating for all types of construction.
(1 inch) of plaster.(4) The following shall also have a
(b) One-Hour Fire-Resistive Time Period Rating one-hour fire-resistive rating; wood colums, 20
(1) The following walls and partitions shall have a one- centimeters (8 inches) or more in least dimension; and
hour fire-resistive rating: Solid masonry, 10 centimeters wood beams, 15 centimeters (6 inches) or more in least
(4 inches) thick; hollow unit masonry, 15 centimeters (6 dimension.
inches) thick; solid concrete, 10 centimeters (4 inches)
thick; stud walls covered on each side with 1.9 (c) Two-Hour Fire-Resistive Time Period Rating
centimeters (3/4 inch) lath and plaster, 1.6 centimeters (1) The following partitions, walls, and floors shall have
(5/8 inch) of vermiculite gypsum board, or 2.5 a two-hour fire-resistive rating: solid masonry, 15
centimeters (1 inch) of gypsum board; and 5 centimeters centimeters (6 inches) thick; hollow unit masonry, 20
(2 inches) nominal thickness tongue and groove wood, centimeters (8 inches) thick; and solid concrete, 127
or two layers of 1.9 centimeters (3/4 inch) tongue and centimeters (5 inches) thick.(2) The following
groove wood separated by sheet metal or asbestos paper protections for metal structural members shall have a
and treated on each side with a fire-retardant coating two-hour fire-resistive rating. 3.8 centimeters (1-1/2
having a flame-spread rating of 50 or less. Square-edged inches) of concrete; 5 centimeters (2 inches) of masonry;
boards may be used is the layers are laid at right angles and two layers of metal lath and plaster with 1.9
with each other. centimeters (3/4 inch) air space between and having a
total thickness of 6.3 centimeters (2-1/2 inches).
(2) The following floors shall have a one-hour fire-
resistive rating: masonry or concrete, 10 centimeters (4 (d) Three-Hour Fire-Resistive Time Period Rating
inches) thick; wood joists having two layers of flooring (1) The following partitions, walls, and floors shall have
above and a plaster or gypsum board ceiling, 1.9 a three-hour fire-resistive rating: solid masonry, 17.8
centimeters (3/4 inch) in thickness - the two layers of centimeters (7 inches) thick; hollow unit masonry, 25.4
flooring shall be separated by sheet metal or asbestos centimeters (10 inches) thick; and solid concrete, 15
building paper; 6.3 centimeters (2-1/2 inches) net centimeters (6 inches) thick.(2) The following protection
thickness tongue and grooved wood floors covered with for metal structural members shall have a three-hour fire
1.9 centimeters (3/4 inch) wood flooring laid at right resistive rating: centimeters (2 inches) of concrete; 7.6
angles thereto. The supporting beams for such floors centimeters (3 inches) of masonry.
shall be not less than 15 centimeters (6 inches) in
minimum dimension. (e) Four-Hour Fire-Resistive Time Period Rating
(1) The following partitions, walls, and floors shall have
(3) The following protections for metal structural a four-hour fire resistive rating: solid masonry walls, 20
members shall have one-hour fire-resistive rating: 2.5 centimeters (8 inches) thick; hollow unit masonry, 30
centimeters (1 inch) of concrete; 3.8 centimeters (1-1/2 centimeters (12 inches) thick; and solid concrete, 17.8
inches) of masonry; and metal lath and 2.5 centimeters centimeters (7 inches) thick.

Chapter CLASSIFICATION OF ALL BUILDINGS BYUSE OR OCCUPANCY AND


GENERAL REQUIREMENTS FOR ALL OCCUPANCIES
TITLE 3 - REQUIREMENTS BASED ON (a) Building proposed, for construction shall be
OCCUPANCY identified according to its use or the character of its
SECTION 3.01.01: Occupancy Classified occupancy and shall be classified as follows:
(1) Group A - Residential: Dwellings. Group A
Occupancies shall include dwellings.
use of highly flammable liquids; open parking garages
(2) Group B - Residential: Hotels and Apartments. - and heliports.
Group B Occupancies shall include boarding or lodging
houses, hotels, apartment houses, convents, and (6) Group F - Industrial. Group F Occupancies shall
monasteries (each accomodating more than 10 persons). include: Ice plants, power plants, pumping plants, cold
storage, and creameries; factories and workshops using
(3) Group C - Education and Recreation. Group C incombustible and non-explosive materials; and storage
Occupancies shall be any building used for school or day and sales rooms of incombustible and non-explosive
care purposes more than eight hours per week, involving materials.
assemblage for instruction, education, or recreation, and
not classed in Group I or in Divisions 1 and 2 of Group (7) Group G - Storage and Hazardous. Group G
H Occupancies. Occupancies shall include: Division 1 - Storage and
handling of hazardous and highly flammable or
(4) Group D - Institutional. Group D Occupancies shall explosive materials other than flammable liquids;
include: Division 1 - Mental hospitals, mental Division 2 - Storage and handling of flammable liquids;
sanitariums, jails, prisons, reformatories, and buildings dry cleaning plants using flammable liquids; paint stores
where personal liberties of inmates are similarly with bulk handling; paint shops and spray painting
restrained; Division 2 - Nurseries for full-time care of rooms, and shops; Division 3 - Wood working
children under kindergarten age, hospitals, sanitariums, establishments, planning mills and box factories, shops
nursing homes with non-ambulatory patients, and similar factories where loose, combustible fibers or dust are
buildings (each accommodating more than five persons); manufactured, processed or generated; warehouses
Division 3 - Nursing homes for ambulatory patients, where highly combustible material is stored; Division 4 -
homes for children of kindergarten age or over (each Repair garages; and Division 5 - Aircraft repair hangars.
accommodating more than five persons); Provided, That
Group D Occupancies shall not include buildings used 8) Group H - Assembly Other Than Group I. Group H
only for private residential purposes or for a family Occupancies shall include: Division 1 - Any assembly
group. building with a stage and an occupant load of less than
100 in the building; Division 2 - Any assembly building
(5) Group E - Business and Mercantile. Group E without a stage and having an occupant load of 300 or
Occupancies shall include: Division 1 - Gasoline filling more in the building; Division 3 - Any assembly
and service stations; storage garage and boat storage building without a stage and having an occupant load of
structures where no work is done except exchange of less than 300 in the building, including such buildings
parts and maintenance requiring no open flame, welding, used for school purposes less than eight hours per week;
or the use of highly flammable liquids; Division 2 - and Division 4 - Stadiums, reviewing stands, amusement
Wholesale and retail stores, office buildings, drinking park structures not included within Group I or Divisions
and dining establishments having an occupant load test 1, 2, and 3, Group H Occupancies.
than 100, printing plants, municipal police and fire
stations, factories and workshops using materials not (9) Group I - Assembly Occupant Load 1000 or More.
highly flammable or combustible, storage and sales room Group I Occupancies shall be any assembly building
for combustible goods, and paint stores without bulk with a stage and an occupant load of 1000 or more in the
handling, and Division 3 -Aircraft hangars where no building.
repair work is done except exchange of parts and
maintenance requiring no open flame, welding, or the
(10) Group J - Accessory. Group J Occupancies shall SECTION 3.01.04: Location on Property
include: Division 1 - Private garages, carports, sheds, (a) General. Buildings shall adjoin or have access to a
and agricultural buildings; Division 2 - Fences over 1.80 public space, yard, or street on not less than one side.
meters (6 feet) high, tanks, and towers. Required yards shall be permanently maintained. For the
purpose of this Section, the center line of an adjoining
SECTION: Change in Use street or alley shall be considered an adjacent property
(a) No change shall be made in the character of line. Eaves over required windows shall be not less than
occupancies or use of any building which would place 75 centimeters (30 inches) from the side and rear and
the building in a different division of the same group of rear property lines.
occupancy or in a different group of occupancies, unless
such buildings is made to comply with the requirements (b) Fire Resistance of Walls. Exterior walls shall have
for such division or group of occupancy: Except, That fire resistance and opening protection in accordance with
the character of occupancy of existing buildings may be requirements set by the Secretary. Projections beyond
changed subject to the approval of the Building Official the exterior wall shall not extend beyond a point one-
and the building may be occupied for purposes set forth third the distance to the property line from an exterior
in other Groups without conforming to all the wall; or a point one-third the distance from an assumed
requirements for those Groups, provided the new or vertical plane located where fire-resistive protection of
proposed use is less hazardous, based on life and fire openings is first required due to location on property,
risk, than the existing use. whichever is the least restrictive. Distance shall be
measured at right angles from the property line. When
SECTION 3.01.03: Mixed Occupancy openings in exterior walls are required to be protected

(a) General. When a building is used for more than one due to distance from property line, the sum of the area of

occupancy purposes, each part of the building such openings shall not exceed 50 per cent of the total

comprising a distinct "Occupancy" shall be separated area of the wall in each story.

from any other occupancy. When a building is used for


more than one occupancy purpose, it shall be subject to SECTION 3.01.05: Allowable Floor Areas
the most restrictive requirements for the occupancies Areas of One-Story Buildings and Building Over
concerned: Except, One Story. Allowable floor areas for one-story buildings
- (1) When a one-story building houses more than one and buildings over one story shall not exceed the limits
occupancy, each portion of the building shall conform to determined in accordance with occupancy groups and
the requirements for the occupancy housed therein, and types of construction.
the area of the building shall be such that the sum of the
actual areas divided by the allowable area for each SECTION 3.01.06: Allowable Area Increases
separate occupancy shall not exceed one; and The floor area hereinabove provided may be
increased in certain specific instances and under
(2) Where minor accessory uses do not occupy more appropriate conditions, based on the existence of public
than 10 per cent of the area of any floor of a building, space, streets, or yards extending along the adjoining two
nor more than 10 per cent of the basis are permitted in or more sides of the building or structure.
the occupancy requirements. The major use of the
building shall determine the occupancy classification SECTION 3.01.07: Maximum Height of
provided the uses are separated in accordance with
Buildings and Increases
requirements for occupancy separation.
The maximum height and number of stories of surface shall not exceed such maximum height by more
every building shall be dependent upon the character of than 3.00 meters (10 feet): Except, That towers, spires,
the occupancy and the type of construction, and shall not and steeples, erected as a part of a building and not used
exceed the limits determined by population density, for habitation or storage, are limited as to height only by
building bulk, widths of streets, and car parking structural design if completely of incombustible
requirements. The height shall be measured from the materials, or may extend not to exceed 6.00 meters (19
highest adjoining sidewalk or ground surface, provided feet, 8 inches) above the height limits for each
that the height measured from the lowest adjoining occupancy group if of combustible materials.
Chapter CLASSIFICATION OF ALL BUILDINGS BY TYPES OF CONSTRUCTION AND
GENERAL REQUIREMENTS
TITLE 4 - TYPES OF CONSTRUCTION nonbearing partitions of one-hour fire resistive
(a) The requirements of this Chapter are minimum for construction framing assembly.
the varying degrees of public safety and resistance to
fire. Every building proposed for construction shall be (5) Type V. Type V Buildings shall be fire-resistive.
identified according to the following: The structural elements shall be of steel, iron,
(1) Type I. Type I Buildings shall be of wood concrete, or masonry construction. Walls and
construction. The structural elements may be any of permanent partitions shall be incombustible fire-
the materials permitted by this Code. resistive construction.

(2) Type II. Type II Buildings shall be of wood SECTION 4.01.02: Change in Type
construction with protective fire-resistant materials
(a) No change shall be made in the type of
and one-hour fire-resistive throughout: Except, That
construction of any building which would place
permanent nonbearing partitions may use fire-
retardant treated wood within the framing assembly. the building in a different subtype or type of
construction unless such bidding is made to
(3) Type III. Type III Buildings shall be masonry and comply with the requirements for such subtype
wood construction, Structual elements may be any of or type of construction: Except, That the type of
the materials permitted by this Code: Provided, That
construction of existing buildings may be
the building shall be one-hour fire-resistive
changed subject to the approval of the Building
throughout. Exterior walls shall be of incombustible
fire-resistive construction. Official and the building may be constructed for
purposes set forth in other Types without
(4) Type IV. Type IV Building shall be of steel, iron, conforming to all the requirements for those
concrete, or masonry construction. Walls and Types, provided the new or proposed
permanent partitions shall be of incombustible fire-
construction is less hazardous, based on life and
resistive construction: Except, That permanent
fire risk, than the existing construction.

Chapter LIGHT AND VENTILATION


TITLE 5 - LIGHT, VENTILATION, AND (a) Subject to the provisions of the Civil Code on
SANITATION easement on light and view, and to provisions of this
SECTION: General Title, every building shall be so constructed, arranged,
and equipped as to provide adequate light and (8 feet) for the second story, and succeeding stories.
ventilation. Garages shall have an unobstructed headroom clearance
of not less than 2.10 meters (7 feet) above the finished
(b) All building erected shall face a street or public floor.
alley or private street which has been officially
approved. SECTION 5.01.06: Minimum Size of Rooms
(c) No building shall be altered nor arranged so as to and Their Least Dimensions
reduce the size of any room or the relative area of
(a) The minimum sizes of rooms and their least
windows to less than that provided for buildings under
horizontal dimensions shall be as follows: 6:00 square
this Code, or so as to create an additional room, unless
(65 square feet) with at least nominal dimension of 2.00
such additional room conforms to the requirements of
meters (6 feet 7 inches) for rooms for human habitation;
this Code.
3.00 square meters (32 square feet) with a least
horizontal dimension of 1.50 meters (5 feet) for
(d) No building shall be enlarged, so that the
kitchens; and 1.20 square meters (12 square feet) with a
dimensions of any required court yard would be less
least horizontal dimension of 0.90 meter (3 feet) for
than that prescribed for any such building.
bathrooms.

SECTION 5.01.09: Mezzanine Floor


SECTION 5.01.05: Ceiling Heights
(a) A Mezzanine floor is a partial, intermediate floor in
(a) Habitable rooms, bathrooms, toilet rooms, storage
any story or room of a building having an area not more
rooms, and utility rooms shall have a ceiling height of
than one-half of the area of the room or space in which
not less than 2.40 meters (8 feet), measured from the
it is constructed.
floor to the ceiling: Provided, That for buildings of
(b) A mezzanine floor shall be constructed with a clear
more than one story, the minimum ceiling height of the
ceiling height of not less than 1.90 meters (6 feet, 4
first story shall be 2.70 meters (9 feet) and 2.40 meters
inches) above and below.

Chapter SANITATION
SECTION: General conformity with the National Plumbing Code adopted

(a) All buildings hereafter erected for human habitation and promulgated by the National Master Plumbers

should be provided with plumbing facilities installed in Association of the Philippines pursuant to Republic Act
1378, otherwise known as the "Plumbing Law".

Chapter BUILDING PROJECTION OVERPUBLIC STREETS


TITLE 6 - REGULATIONS FOR USE OF PUBLIC (b) No projection shall be allowed on any
PROPERTY
national roads or public highway.
SECTION 6.01.02: Projection into Alleys and
Streets
(a) No part of any structure or its appendage (c) Footing located at least 2.40 meters (8 feet)
shall project into any alley or street except as below grade may project not more than 30
provided in this Code. centimeters (12 inches) beyond the property line.
(d) Foundation may be permitted to encroach SECTION 6.01.08: Corner Buildings with
into public sidewalk areas to a width not Chaflans
(a) Every corner building on a public street or alley less
exceeding 50 centimeters (1 foot, 8 inches):
than meters (12 feet) in width shall be made with a
Provided, That the top of the said foundations or chaflan or truncated angle at the corner. The face of the
footings does not reach beyond the level of a triangle so formed shall be at right angles to the bisector
plane 60 centimeters (2 feet) below the of the angle of intersection of the street lines; Provided,
That, in no case, shall the length of the chaflan be less
established grade; and Provided, further, That
than 4.00 meters (13 feet, 4 inches). In special cases, the
said projection does not obstruct any existing
Building Official shall determine the size and form of
utility such as power, communication, gas,
the chaflan
water, or sewer lines, unless the owner
concerned shall pay the corresponding entities (b) If the buildings is arcaded, no chaflan is required
for the re-routing of the parts affected. notwithstanding the width of the public street or alleys
less than meters (39 feet, 4 inches)

Chapter 6.02 - PROTECTION OR PEDESTRIANS DURING CONSTRUCTION OR


DEMOLITION
(a) No person shall use or occupy a street, alley, or SECTION 6.02.04: Mixing Mortar on Public
public sidewalk for the performance or work under a Property
(a) The mixing or handling of mortar, concrete, or
building permit except in accordance with the provisions
similar materials on public street shall not be allowed
of this Chapter.
except when the same are to be used on such streets or
any portion thereof such as curbs, gutters, manholes,
(b) No person shall perform any work on any work on
sidewalks, culverts and the like
any building or structure adjacent to a public way in
general use by the public for pedestrian travel, unless the
SECTION 6.02.07: Pedestrian protection
pedestrians are protected as specified in this Chapter
(a) Protection Required. Pedestrian traffic shall be

(c) Any material or structure temporarily occupying protected by a railing on the street side when the

public property, including fences, canopies, and walkway extends into the roadway, by a railing when

walkways, shall be adequately lighted between sunset adjacent to excavations, and by such other appropriate

and sunrise. portion such as set forth in Table 6.02-A: Type of


Protection Required for Pedestrian (Annex B).

SECTION 6.02.03: Storage on Public


(b) Railings. Railings shall be built substantially and
Property should be at least 1.00 meter (3 feet, 3 inches) in height.
(a) Materials and equipment necessary for work to be
done under a permit shall not be placed or stored on (c) Fence. Fences shall be built of an approved material,
public property so as to obstruct free and convenient not less than 2.40 meters (8 feet) in height above grade,
approach to and use of any fire hydrant, fire or police and to be placed on the side of the walkway nearest to
alarm box, utility box, catch basin, or manhole or so as the building site. Fences shall enclose entirely the
not to interfere with any drainage of any street or alley building site. Openings in such fences shall be provided
gutter. with doors which shall be kept closed at all times.
(d) Canopies. The protective canopy shall have a clear centimeters (1 foot) high and a railing not less than 1.00
height of 2.40 meters (8 feet) above the walkway, and meters (3 feet, 3 inches) high shall be provided. The
shall be constructed structurally safe. Every canopy shall entire structure shall be designed to carry the loads
have a solid fence built along its entire length on the imposed upon it: Provided, that the live load shall be not
construction side. If materials are stored or work is done less than 633 kilograms per square meter (150 pounds
on top of the canopy, the edge along the street shall be per square foot).
adopted by a tight curb board not less than 30

Chapter GENERAL DESIGN REQUIREMENTS


TITLE 7 - ENGINEERING REGULATIONS
SECTION: Scope SECTION 8.01.07: Stairs, Exits, and
(a) The design and construction of all buildings and Occupant Loads
Exit Requirements. Exit requirements of a building or
structures shall be in compliance with the provisions of
portion thereof used for different purposes shall be
the National Structural Code for Buildings, latest edition,
determined by the occupant load which gives the largest
adopted and promulgated by the Board of examiners of
number of persons. No obstruction shall be placed the
civil engineers pursuant to Republic Act Numbered 544,
required width of an exit except projections permitted by
as amended, otherwise known as the "Civil Engineering
this code. Number of Exits. Every building or usable
Law".
portion thereof shall have at least one exit. In all
occupancies, floors above the first story having an
TITLE 8 - DETAILED REGULATIONS
occupant load of more than 10 shall have not less than
SECTION 8.01.02: Excavations, Foundations,
two exits. Every story or portion thereof, having an
and Retaining Walls
Excavation or fills for any building structure and occupant load of 500 to 999 shall have not less than
excavations or fills accessory thereto shall be so three exits. Every story or portions thereof, having an
constructed or protected that they do not endanger life occupant load of 1000 or more shall have not less than
and property. Whenever or wherever there exists in the four exits.
site of the construction on abrupt change in the ground
levels or levels of the foundation such that instability of Width. The total width of exists in meters shall be not
the soil could result, retaining walls shall be provided less than the total occupant load served divided by 165
and such shall be of adequate design and type of (in feet, by 50). Such width of exits shall be divided
construction in accordance with generally accepted approximately equally among the separate exits.
standards and principles of engineering.

Chapter SIGNS
SECTION: General
(a) No signs or signboards shall be erected in such a manner as to confuse or obstruct the view or interpretation of any
official traffic sign signal or device. (b) No signboards shall be constructed as to unduly obstruct the natural view of
the landscape, distract or obstruct the view of the public as to constitute a traffic hazard, or otherwise defile, debase,
or NATIONAL STRUCTURAL CODE offend
the aesthetic
and cultural
OF THE PHILIPPINES
values and
traditions of the Filipino
people

INTRODUCTION
 ASEP recognizes the need for an up-to-date * Based on American standards, ASCE American Society
structural code addressing the design and of Civil Engineers 7-05
installation of building structural systems through * APO – Association of Professional Organization
requirements emphasizing performance, The new
National Structural Code of the Philippines CHANGES MID-DEVELOPMENTS
(NSCP) is designed to meet these needs through  In its drive to upgrade and update the NSCP, the
various model codes Regulations, generally from ASEP Codes and Standards Committee initially
the United States, to safeguard the public health warned to adopt the latest editions of American
and safety nationwide code counterparts. However, for cases where
available local data is limited to support the
 This updated Structural Code establishes minimum upgrade, then some provisions and procedures of
requirements for building structural systems using the NSCP 6th edition were retained.
prescriptive and performance-based provisions. It
is founded on broad-based principles that make INTERNATIONAL CODES AND REFERENCES
possible the possible use of new materials and new o Uniform Building Code UBC1997 (adopted for
building designs Earthquake loads)
o International Building Code IBC – 2009
 Also, this code, reflects the latest seismic design (referenced)
practice for earthquake resistant structures. o American Society of Civil Engineers ASCE 7-05
(adopted for Wind Loads)
*ASEP – Association of Structural Engineers of the o American Concrete Institute ACI318-O8M
Philippines
o American Institute for Steel Construction AISC-05 o Reinforced Masonry Engineering Handbook
WITH Supplementary Seismic Provisions America
o American Iron and Steel Institute AISIS100-2007 o Concrete Masonry Handbook, 6th edition

CHAPTER 1: PROVISIONS/GENERAL REQUIREMENTS


Significant Revisions Summarized
SECTION103 – Classification of Buildings

SECTION104 – Design Requirements


Defelcetion of any structural member uneder the Serviceablitty requirement deleted. For concrete and smcl materials
sec Chapter 4 and 5 respectively; new requirements are added to the design review section.

SECTION 105 – Posting and instrumentation


The provision of installed recording accelograph is adjusted

CHAPTER 2
SECTION 203 – Combination of Loads  Equations for the gust effect factors for both rigid
The load factor values on wind loads are adjusted and and flexible structures are introduced. These
together with the inclusion of loads include the gust effect factor for antennas,
transmission and latticed towers, poles/posts,
SECTION 205 – Live Loads masts and transmission lines based on ASCE
Additional loads are incorporated in the table foe Manual Practice no. 74 (Guidelines for Electrical
minimum uniform and concentrated loads Transmission Line Engineering Loading.
 New formulas are also introduced for the natural
SECTION 207 – Wind Loads frequency and damping ratio
Wind load provision, which KD were previously based SECTION 208 – Earthquake Loads
on ASCE 7-95, are updated by the introduction of the ASCE/SEI7-05 is recognized as alternative procedure in
Wind Directionality Factor, Kd, based on ASCE 7-05. the determination of earthquake loads.
The ANSI EIA/TIA-222-G is also referenced for winds
loads or antennas SECTION 210 and SECTION 211
New section on rain loads and flood loads are added

CHAPTER 3: SPECIFICATION FOR EXCAVATIONS AND GEOMATERIALS


 Provisions pertaining to the conduct and interpretation of foundation investigations for cases involving
liquefiable, expansive or questionable soils are adopted;
 The section on footings is amended to incorporate provisions for differential settlement, design loads and
vibratory loads
 The section on pile foundations is amended to incorporate new provisions on splicing of concrete piles; and
 The section on special foundations, slope stabilization and materials of construction are added
*geo materials example: coconut fiber, polymer materials

CHAPTER 4: STRUCTURAL CONCRETE


SECTION 401 - General Requirement: New requirements for headed shear stud reinforcement,
Design requirements for earthquake-resistant structures headed deformed bars, and stainless steel bars are given
are updated based on ACI 318-8M which mentions the with appropriate references to ASTM standards;
“Seismic Design Categories (SDCs)” of ASCE/SEI 7-
05. However, in the absence of Philvocs-issued spectral SECTION 404 – Durability Requirement:
acceleration maps for all areas in the Philippines, the Exposure categories and classes, requirements or
seismic loading procedures based on ASCE/SEI 7-05 is concrete by exposure class are adopted to replace the
adopted as an alternative procedure (see Section 208- many tables or durability requirements in Section 404,
11). Therefore, based on the Commentary of ACI 318- making it easier to clearly specific the intended
08, Seismic Zone 2 (UBC 97) was adopted in lieu of application;
SDC C (ASCE/SEI 7-05). Similarly, Seismic Zone 4 is
adopted in lieu of SDCs D, E, and F. SECTION 405 – Concrete Quality, Mixing, and
Placing:
SECTION 403- Materials: The use of three 100mm x 200 mm cylinders is adopted
as equivalent to the use of two 150 mm x 300 mm
cylinders for determining concrete compressive Provisions are added for the development length of
strength. Due to concern that material properties may headed deformed bars; splice length when splicing bars
change with time, a 12-month limit is set on historical with different sizes is addressed; and a coating factor of
data used to qualify mixture proportions and flexural 1.0 for galvanized reinforcement is added;
test performance criteria are added to qualify the use of
steel fiber – reinforced concrete as a replacement for SECTION 413 – Two –Way Slab Systems:
minimum shear reinforcement; Dimension limits are added for the use of shear caps;
and alternative corner reinforcement arrangement is
SECTION 407 – Details of Reinforcement: added for two-way slabs supported by edge beams or
To avoid the misconception that there is no minus walls;
tolerance on cover values given in the code, “minimum
cover” is replaced with “specified cover” throughput SECTION 414 – Walls
Section 407; Class B lap splices are now required for Design provisions for slender wall panels are modified
transverse reinforcement confining structural integrity to be more consistent with the methods used in design
reinforcement in perimeter beams are clarified; practice;

SECTION 409 – Strength and Serviceability SECTION 418 – Prestressed Concrete


Requirements: The allowable concrete compression stress immediately
Strength reduction factors for compression-controlled after prestress transfer is increased; and requirements
sections (other structural members) is reduced from for structural integrity steel in two-way unbounded
0.70 to 0.65, and shear and torsion for shear walls and post-tensioned slab systems are modified
frames in Seismic Zone 4 is reduced from 0.85 to 0.75
bearing on concrete (except for post-tensioning SECTION 420 – Strength Evaluation of Existing
anchorage zones) is reduced form 0,70 to 0.65. Strength Structures
reduction factors for strut-and-tie models, flexural Load factors for determining the required test load are
sections in pretensioned members, are also added; modified to reflect typical modern load combinations;

SECTION 410 – Flexure and Axial Loads: SECTION 421 – Earthquake-Resistant Structures
The section on slenderness effects is reorganized to This section presents the requirements for Seismic
recognized computer analysis techniques as the primary Resistant Design from ASCE?SEI 7-05, but instead of
method of evaluating second-order effects; using the Seismic Design categories of ASCE/SEI 7-05,
*Interaction Diagram the equivalent Seismic Zones as per UBC 1997 are
specified. Also, new design requirements are added for
such seismic zones; new detailing option is added for
diagonally reinforced coupling beams; design yield
strength for confinement reinforcement is raised to 690
MPa to help reduce the congestion; and boundary
SECTION 411 – Shear and Torsion:
element confinement requirements is relaxed;
Code requirements are added to permit the use of
headed stud assemblies as shear reinforcement for slabs
SECTION 423 – Anchoring to Concrete
and footings. The nominal shear strength is permitted to
Use of reinforcement in the vicinity anchors and
be larger for headed stud assemblies than for other
ductility requirements for anchors in seismic zones are
forms of slab and footing shear reinforcement; more
clarified
stringent limits are placed on the depths of beams that
are exempted from the requirement for minimum shear
SECTION 425 – Alternative Provisions for
reinforcement ; a new limit on the depth of hollow core
reinforced and Prestressed Concrete Flexural and
units for which minimum shear reinforcement could be
Compression Members
waived is established; steel fiber-reinforced concrete is
Revisions in Appendix B of ACI 318-08M is adopted;
added as an alternative to minimum shear
reinforcement; and the upper limit on shear friction
SECTION 426 – Alternative Load and Strength
strength is significantly increased for monolithically
Reduction factors;
placed concrete and concrete placed against
Revisions in Appendix C or ACI 318-08M is adopted;
intentionally roughened concrete;
and
SECTION 412 – Development and Splices of
Reinforcement:
SECTION 427 – Strut-and-tie Models
Appendix A of ACI 318-08M is adopted in its entirety

CHAPTER 5: STRUCTURAL STEEL


1. Adopted is an integrated treatment of the Allowable Stress Design (ASD) and the Load and Resistance factor
Design (LFRD) such that the earlier Specification that treated only the ASD method is retained;
2. IN lieu of the previous method of analysis, a new method (Direct Analysis Method is adopted; and
3. The cold formed steel design for building systems and structural members are included

CHAPTER 6: WOOD
The provisions in this chapter are refined to incorporate local practices and corrections in the previous version of the
code (NSCP 2001). Referrals are made to the NSCP 2010

Tables from the previous version of NSCP 2001 including the Table containing specified design information are
amended to incorporate the latest updated information/list of wood species as provided by the Forest Products
Research and Development Institute (FPRDI)
A provision that limit the use of wood shear walls and diaphragms is added; and
As section for Machine Graded Lumber (MGL) is included

CHAPTER 7: MASONRY
The provisions in this chapter are refined to include local practices and corrections from the previous version of the
code (NSCP 2001); referrals are made to the NSCP 201 Vol. III on Housing for relevant provisions concerning
single-family dwellings/low-cost housing;
Recycled aggregates are defined and provided;
A section for Seismic Design is added; and
Additional sections each for Masonry Fireplaces and Masonry Chimneys are included

CHAPTER 1 – GENERAL REQUIREMENT


SECTION 101 – Title, Purpose and Scope practice literature but shall refer to provisions of
o 101.1 Title. this code as a minimum wherever applicable.
These regulations shall be known as the National
Structural Code of the Philippines, Vol. 1, 6th For additions, alterations, maintenance, and
Edition 2015 and may be cites as such and will be change in use of buildings and structures, see
referred to herein as “this code” Section 108.

o 101.2 Purpose Where, in any specific case, different sections of


The purpose of this code is to provide minimum this code specify different materials, methods of
load requirements for the design of buildings, construction or other requirements, the most
towers, and other vertical structures, and restrictive provisions shall govern except in the
minimum standards and guideline to safeguard case of single family dwellings. Where there is a
life or limb, property and public welfare by conflict between a general requirement and a
regulating and controlling the design, specific requirement, the specific requirement
construction, quality of materials pertaining to the shall be applicable.
structural aspects of all building and structures
within this jurisdiction o 101.4 Alternative Systems
The provisions of this code are not intended to
o 101.3 Scope prevent the use of any material, alternate design or
The provisions of this code shall apply to the method of construction not specifically prescribed
construction, alteration, moving, demolition, by this code, provided any alternate has been
repair, maintenance and use of permitted and its use authorized by the Building
buildings, towers and other vertical structures Official (see Section 102).
within this jurisdiction.
o Sponsors of any system of design or construction
Special structures such as but not limited to single not within the scope of this code, the adequacy of
family dwellings, storage silos, liquid product which had been shown by successful use and by
tanks and hydraulic flood control analysis and test, shall have the right to present
structures, should be referred to special state of the data on which their design is based to the
Building Official or to a board of examiners
appointed by the Building Official or the project o 104.2. Serviceability Requirement
owner/developer. This board shall be composed
of competent structural engineers and shall have  104.2.1. Structural system and members
authority to investigate the data so submitted, to thereof shall be designed to have adequate
require tests if any, and to formulate rules stiffness to limit deflections, lateral drifts,
governing design and construction of such vibrations, or any other deformations that
systems to meet the intent of this code. These adversely affect the intended use and
rules, when approved and promulgated by the performance of buildings, towers and other
Building Official, shall be of the same force and vertical structures. The design shall also
effect as the provisions of this code consider durability, resistance to exposure to
weather or aggressive environment, crack
SECTION 102 – Definition of Terms control, and other conditions that affect the
intended use and performance of buildings,
SECTION 103 – Classification of Structures towers and other vertical structures.
Nature of Occupancy
Buildings and other structures shall be classified, based o 104.3. Analysis.
on the nature of occupancy, according to Table 103-1 for Any system or method of constructions to be used
purposes of applying wind and earthquake loads in shall be based on rational analysis in accordance
Chapter 2. Each building or other structures shall be with well-established principles of mechanics that
assigned to the highest applicable occupancy category or take in account equilibrium, general stability.
categories. Assignment of the same structure to multiple Geometric compatibility and both short term and
occupancy categories based on use and the type of long term material properties.
loading condition being evaluated (e.g wind or seismic)
shall be permissible Members that tend to accumulate residual
deformations under repeated service loads shall
When buildings or other structures have multiple uses have include in their analysis the added
(occupancies), the relationship between the uses of eccentricities expected to occur during their
various parts of the building or other structure and the service life. Such analysis shall result in a system
independence of the structural system for those various that provides a complete load path capable of
parts shall be examined. The classification for each transferring all loads and forces from their point
independent structure system of a multiple-use building of origin to the load-resisting elements. The
or other structure that is dependent on that basic analysis shall include, but not be limited to, the
structural system provisions of Section 104.3.1 through 104.3.3
 Essential facilities
 Hazardous facilities SECTION 105 – Posting and Instrumentation
 Special Occupancy Structures o 105.1 Posting of live loads
 Standard Occupancy Structures The live loads for which each floor or portion
 Miscellaneous Structures thereof a commercial or industrial building has
been designed shall have design live loads,
DESIGN METHOD conspicuously posted by the owner in that part of
 Strength Design each story in which they apply, using durable
 Load and Resistance Factor Design metal signs. It shall not be allowed to remove or
 Allowable Stress Design deface such notices. The occupant if the building
 Exception: shall be responsible for keeping the actual load
Unless otherwise required by the building below the allowable limits
official, buildings or portions thereof that are
constructed in accordance with the conventional o 105.2 Earthquake-Recording Instrumentation
light-framing requirements specified in Chapter 5  105.2.1 General
and the NSCP Volume III on Housing shall be Unless waived by the Building Official, every
deemed to meet the requirements of this section. building in Seismic Zone 4 over 50m in
height shall be provided with not less than
SECTION 104 – Design Requirements three approved Earthquake Recording
o 104.1. Buildings, towers and other vertical Instruments (ERI). The ERI shall be
structures and all portions thereof shall be interconnected for common start and
designed and constructed to sustain, within the common timing. Please refer to “ASEP
limitation specified in this code, all loads set forth Guidelines and Implementing Rules on
in Chapter 2 and elsewhere in this code, combined Earthquake Recording Instrumentation for
on accordance with the Section 203 Buildings (appendix 1-8)
 105.2.2 Location ink and shall be of sufficiently clarity to
The instrument shall be located in the indicate the location, nature and extent of the
basement, midportion, and near the top of the work proposed. The drawings hall show a
building. Each instrument shall be located so complete design with sizes, sections, relative
that access is maintained at all times and is locations and connection details of the
unobstructed by room contents. A sign various members. Floor levels, column
starting “MIANTAIN CLEAR ACCESS TO centers and offsets shall be dimensioned.
THIS INSTRUMENT” shall be posted in a Where available and feasible archive copies
conspicuous location. shall be maintained in durable medium such
as compact disc (CD) and digital versatile
SECTION 106 – Specifications, Drawings, and disc (DVD)
Calculations
o 106.1 General SECTION 107 – Structural Inspection, Tests and
Copies of design calculations, reports, plans, Structural Observations
specifications and inspection program for all o 107.1 General
constructions shall bear the signature and seal of All construction or work for which a permit is
the engineer-of-record required shall be subject to inspection throughout
the various work stages. One or more structure
o 106.2 Specifications inspectors who are registered civil engineers with
The specifications shall contain information experience in structural construction, who shall
covering the material and construction undertake competent inspection during
requirements. The materials and construction construction of the types of work listed under
requirements shall conform to the specifications Section 107.5 shall be employed by the owner or
referred in Chapter 1 to 7 of this Code the engineer-of-record acting as the owner’s
agent.
o 106.3. Design Drawings
 106.3.1 General Exception: The Building Official may waive the
The design drawings shall be drawn to scale requirement for the employment of a structural
on durable paper or cloth using permanent inspector if the construction is of a minor nature

BUILDING DESIGN MIDTERM NOTES


BUILDING DESIGN I
Architectural Documents elevations; floor to floor heights; door and window marks,
a. Architectural Plans/Drawings type of material and exterior finishes; adjoining existing
i. Vicinity Map/Location Plan within a 2.00 kilometer structure/s, if any, shown in single hatched lines.
radius for commercial, industrial, and institutional complex
and within a half-kilometer radius for residential buildings, vi. Sections, at least two (2), showing: gridlines; natural
at any convenient scale showing prominent landmarks or ground and finish levels; outline of cut and visible
major thoroughfares for easy reference. structural parts; doors and windows properly labeled
reflecting the direction of opening; partitions; built-in
ii. Site Development Plan showing technical description, cabinets, etc.; identification of rooms and functional spaces
boundaries, orientation and position of proposed cut by section lines.
building/structure in relation to the lot, existing or
proposed access road and driveways and existing public vii. Reflected ceiling plan showing: design, location,
utilities/services. Existing buildings within and adjoining finishes and specifications of materials, lighting fixtures,
the lot shall be hatched and distances between the proposed diffusers, decorations, air conditioning exhaust and return
and existing buildings shall be indicated. grills, sprinkler nozzles, if any, at scale of at least 1:100.

iii. Perspective drawn at a convenient scale and taken SIZES OF DRAWING SHEETS
from a vantage point (bird’s eye view or eye level). TYPE W*(mm) L*(mm)
A0 641 1189
iv. Floor Plans drawn to scale of not less than 1:100 A1 594 641
showing: gridlines, complete identification of rooms or A2 420 594
functional spaces. A3 297 420

v. Elevations, at least four (4), same scale as floor plans


showing: gridlines; natural ground to finish grade
TITLE BLOCK

STANDARD FORM (Type A0, A1, A2 and A3)


FOR BUILDING PLANS / CONSTRUCTION DRAWINGS

MODEL TITLE BLOCK


FOR BUILDING PLANS/CONSTRUCTION DRAWINGS

DETAILED IN THE FORM OF PLANS, (d) Accessible entrances, corridors and walkways
ELEVATIONS/SECTIONS (e) Accessible functional areas/comfort rooms
(a) Accessible ramps (f) Accessible switches, controls
(b) Accessible stairs (g) Accessible drinking fountains
(c) Accessible lifts/elevators (h) Accessible public telephone booths
(i) Accessible audio visual and automatic alarm system  Existing or proposed access road and driveways
(j) Accessible access symbols and directional signs and existing public utilities/services.
(k) Reserved parking for disabled persons  Existing buildings within and adjoining the lot
(l) Typical wall/bay sections from ground to roof shall be hatched and distances between the
(m) Stairs, interior and exterior proposed and existing buildings shall be
(n) Fire escapes/exits indicated.
(o) Built-in cabinets, counters and fixed furniture
(p) All types of partitions o STRUCTURAL PLANS
 Foundation Plans and Details at scale of not less
WORKING DRAWINGS OF CONSTRUCTION PLANS than 1:100.
 A graphical presentation on paper that enable the  Floor/Roof Framing Plans and Details at scale of
reader to visualize and understand how the building not less than 1:100.
would be constructed and how it functions  Details and Schedules of structural and civil
works elements including those for deep wells,
 STANDARD DRAWINGS INCLUDED IN THE water reservoir, pipe lines and sewer system.
CONSTRUCTION PLANS OR WORKING
DRAWINGS o FLOOR PLANS
1. Exterior perspective drawing of the building - Are drawings showing the outline and
2. Site Development Plan or Plot Plan arrangement of the rooms inside the building as
3. Vicinity Map or Location Map seen from a horizontal plane cutting thru the walls
4. Floor Plan/s about one meter above the floor line
5. Elevations
6. Transverse section and longitudinal Section o ELEVATION
7. Foundation Plan, details of posts/column, footings, - As used in design and construction, is a drawing
concrete hollow blocks. Reinforcement concrete representing the projection of any part of a structure
walls on a vertical plane directly facing it
8. Floor framing plan/s, details of beams, girders and Generally there are four elevation; FRONT, REAR,
RC slab/s RIGHT SIDE, LEFT SIDE
9. Roof framing plan, details of rafters and/or trusses
10. Plumbing plan, diagram and details of septic vault,  INFORMATION AND DETAILS FROM THE
catch basins, etc. ELEVATION PLANS
11. Electric plan/s, diagram/s and load computations,  Overall design and character of the building
etc.  Materials and finishes for the exterior
12. Mechanical Plan, where so required features of the building
 Heights of the building and its various levels
 THE FOLLOWING DRAWINGS SHOULD BE like: Ground line-to-first floor level; Floor
INCLUDED line-to-ceiling line; Level of basement, if any,
 Details of cabinets and closets from the first floor or ground line; heights of
 Details of stairs, including handrails other important parts of the building
 Details of windows and doors  Approximate or true profile on the building
 Interior designs and other notable building features site if not level
 Types and designs of exterior doors and
 DRAWINGS WHICH ARE SHOWCASED ON THE windows
FIRST SHEET OF THE CONSTRUCTION PLANS
ARE: o FOUNDATIONS PLAN
o PERSPECTIVE DRAWING - is to show the structural supports of the proposed
- The graphic presentation in 3 dimension style of structure at the ground level, and/or basement level
the project showing how it would appear when if the basement is incorporated in the building plan.
finished
 INFORMATION FROM THE FOUNDATION
o SITE DEVELOPMENT PLAN PLAN
- The outline and measurements of the proposed  Position of the column or posts, masonry
building and its placement on the property are walls and other building elements at the
designated. foundation level
 Showing technical description,  Necessary measurements to show the spatial
 boundaries, relationships between the building parts as
 Orientation and position of proposed non- well as for plotting their exact positions on
architectural horizontal structure such as: the ground during construction
sewerage treatment plan (STP), silos, elevated  Spaces for concrete slabs on fill and their
tanks, towers, fences, etc. building/structure in thickness: sizes and spacing of steel
relation to the lot, reinforcing or temperature bars, if required
 Foundation work required for other facilities
like driveways, outdoor terraces, patios, steps, *STANDARD HEIGHT OF WINDOW FROM
walkways and other related to the function of FLOOR IS 2.1M
the proposed building - Methods of presentation
* plan or top view * elevations
o SECTIONS * sections * perspective
– drawing reveals the innards of the structure. It
also shows the interior view, as projected on an  DETAILS AND SCHEDULES OF DOORS
imaginary vertical plane that passes through a given AND WINDOWS
axis of the building.  A mark placed near every door and window
- This includes the Longitudinal Sections, symbol to identify its detail including the
Transverse section materials or specification

 INFORMATION FROM THE FULL SECTION Lettering Styles


DRAWINGS * Old English style * Roman Letters * Gothic
 The height of the different levels as seen from
the inside of the building
 Interior elements of structure
 Contour of the building site if not level
 Profile of the ceiling lines and floor sections

o DETAIL DRAWING
- Enlarged drawings which focus only on selected
portions of a structure to show in greater detail
those parts of the constructions
- To reveal how certain building parts are Lettering Secrets
assembled, dimensions to be followed and kinds of * Guidelines * Form * Stability
materials to be used * Proportion * Density * Spacing
SYMBOLS

FLOOR PLANS
- A sectional drawing obtained by an imaginary cutting through the walls about 1m above the floor

SECTION 805. Ceiling Heights typical head-room clearance of not less than 2.10 meters above
1. Habitable rooms provided with artificial ventilation shall the finished floor.
have ceiling heights not less than 2.40 meters measured from Above-stated rooms with natural ventilation shall have ceiling
the floor to the ceiling; provided that for buildings of more heights of not less than 2.70 meters.
than one (1) storey, the minimum ceiling height of the first
storey shall be 2.70 meters and that for the second story 2.40 2. Mezzanine floors shall have a clear ceiling height not less
meters and the succeeding stories shall have an unobstructed than 1.80 meters above and below it.
SECTION 806. Sizes and Dimensions of Rooms  Circulation
1. Minimum sizes of rooms and their least horizontal  Furniture Grouping
dimensions shall be as follows:  Primary Grouping – chairs and sofa are grouped
a. Rooms for Human Habitations – 6.00 sq. meters with a around a fire place
least dimension of 2.00 meters;  Secondary Grouping – chairs and love seat are grouped
b. Kitchen – 3.00 sq. meters with a least dimension of 1.50 at end of the room or at the center
meters; and  Reading group – chair, ottoman, lamp shade, etc
c. Bath and toilet – 1.20 sq. meters with a least dimension of  Writing or study group – desk, lamp, on or two chair
900 millimeters. book cases
 Music group – piano bench, storage space
LIVING ROOM  Game group – game table and four chairs

 Planning Conisderations  90 cm for main traffic


 Through traffic should be separated from activity  150 cm in between TV seat and seating
center  45 minimum clearances for a single passage not a traffic
 Opening should be located so as to give enough wall lane
space for various furniture arrangement  100 cm minimum clearances for general traffic lane
 Provide a convenient access to the following  90 cm minimum tolerance for seating areas confined
* Doors windows * Electrical
outlets DINING ROOM
* Thermostat * Supply grills  It is room for consuming food
 For single passage between a low objects such as  Planning considerations
sofa, the pathway should be at a minimum of 40cm  Determine the number of persons to be seated
 For a single passage between tall objects – 60 cm  The required space occupied by the table
 For general traffic lane – 1.0m  The space for the chairs
 For a seating area which is permit one person to  The space required behind the chairs
passing at the back – 0.90m  The size and type of furniture
 Space for storage of china glassware, silverware and
Minimum clearance between furniture linen
 150 cm between facing seating
 50 cm where circulation occur between furniture Recommended Spacing
 75 cm for use of desk  Size of place setting – 0.50m
 For a place setting – 0.35m o For comfort seating 60cm on the table perimeter
 Table requirements per person  Size of table and dining area – minimum of 90cm width
o For crowded seating 50 cm to 55cm

FURNITURE ARRANGEMENT
& TRAFFIC PATTERNS

THREE (3) MAIN ZONES OF THE HOME


There are 3 main zones in every home: living, sleeping, and
service.
When laying out the floor plan, consider these zones and the
activities that take place in those zones. Quiet and private zones
should be separated from noisy and public zone

LIVING ZONES traffic; each person is allowed a minimum of 24 inches of


The living area of the home includes the living, dining, seating room at the table
family room, foyers, and specialty rooms such as those for
music, study, hobby, etc. SLEEPING ZONES
Primary conversation area: 8-12 foot diameter is ideal; The sleeping area of the home includes the bedrooms,
seating for at least 4-6 people; chairs seat 1, loveseats seat bathrooms, and dressing areas.
2, and sofas seat 3 Never place the side of a bed against a wall; you always
Secondary furniture grouping: seating for just 1-3 people allow room to walk on both sides
(piano, desk, etc.) Storage is a key factor in these rooms: personal items,
Traffic: the traffic pattern should flow TO the clothing, accessories, and bed and bath linens, medications
conversation area, but not THROUGH it Allow one nightstand per person sleeping in the room
Dining area: allow 3 feet from the table edge for the A chest of drawers is usually taller and has no mirror; a
person to be seated at the table and room behind them for dresser is usually shorter and does have a mirror
Twin/single beds are for 1 person; double, queen, and king  Work circulation includes how people move from the
can accommodate 2 kitchen to the dining areas, the kitchen triangle (a triangle
connecting the refrigerator, stove, & sink), and from the
SERVICE ZONES bedrooms to the utility room. No cross traffic should be
The service areas of the home include the kitchen, utility allowed to interfere with work circulation.
rooms, garage, and basements.
Storage is a key factor in these areas, for consumable  Family circulation includes traffic between bedrooms and
supplies (food, laundry soap, motor oil, furnace filters) and bathrooms, foyers and living rooms, foyers and bedroom
equipment areas, living rooms and patios, living rooms and dining
Traffic should flow to the area, but not through it rooms.
Utilities such as furnaces and hot water heaters need
clearances for ventilation and maintenance/repair  Guest circulation includes from the entry to the coat
Efficiency must be considered: efficiency is a desirable closet, from the entry to the living room, and from the
degree of energy expended to achieve effective or useful living room to the bathroom. Guests should not need to
output cross work or private family areas.
Safety must be considered: environmental (ice, lightening,
storms), mechanical (cars, furnaces, electrical, plumbing, TRAFFIC PATTERN CLEARANCES
tools) chemical (cleaners, windshield wiper fluid, bug Traffic areas need clearance for one or more people to walk
spray) sanitation (garbage, insect control) and for the people to accomplish a variety of tasks. There are
major and minor traffic patterns.
TRAFFIC PATTERNS  Major traffic patterns need 36”- 6’ clearance: hallways;
People move throughout the home every day, usually walking area in front of clothes closets, dressers, and chests of
in the shortest distance possible between two points. These drawers; any route where 2 people might pass each other;
walkways are referred to as traffic patterns, circulation, or area in front of stove, refrigerator, sink, washer, and dryer
traffic flow. areas; from the edge of a dining room table to a wall or
stationary object; side of bed you get in on;
best for stairways

 Minor traffic patterns need 18” – 4’ clearance: sides of


beds used only for making beds; space between sofas and
coffee tables; 30” in routes where only one person will
walk, such as in front of tubs or through doorways

Placement of doors and furniture influence the traffic patterns. Using a Furniture Template
In this apartment, the furniture arrangements are used to help You can either draw furniture using a ruler, or you can use an
direct the traffic. Traffic flows smoothly through the rooms. architect’s template. A template is simply a plastic pattern of
While walkway patterns take the people to the living and commonly used architectural symbols that is made to scale
work areas of the home, it doesn’t take them through those and can be easily traced. There are templates for fixtures and
areas unless they need to be there. furnishings.
When adding furniture to a room, you need to think about the
There are 4 types of traffic patterns: people that are living in that space. What are their needs?
 Service circulation includes how people move in and out How do they move about in the space?
of the house to make deliveries, maintain appliances, and
take out garbage.

Drawing fixtures and furnishings in bathrooms


Perfect Bathroom Arrangement
To be considered a “full bath”, the room must have a toilet, vanity with sink,
and bathtub. A ¾ bath has a shower instead of a tub. A half bath has only a
toilet and vanity. A water closet has only a toilet, with hand-washing facilities
in an adjoining area.
The FHA (Federal Housing Authority) recommends a minimum 5 x 7’ size for
a bathroom. A perfect arrangement, however, requires a bigger room. The tub
and a linen closet will be on one side of the door; the vanity and toilet will be
on the other. Try to position the toilet so it is not easily visible from the open
door. (Here it is partially concealed behind the vanity)

Avoid bathroom design problems…


The traffic pattern in a bathroom should be 30” wide. There should be at least
30” in front of the tub or shower, toilet, or sink.

Newer Bathroom Designs


Drawing fixtures and furnishings in bedrooms

Mechanical & Architectural Functions


Mechanical or architectural functions that
must be considered when placing furniture:
Air circulation vents, doors, windows,
electrical outlets, phone jacks, television
cables or antenna lines, fireplaces, and
stairs.

ROOF PLAN COMPONENTS


Roof Layout Plan
Roof is used as a shelter of the occupants
Roof Plan – commonly drawn to a scale of 1:100M Scale. It shows the shape of the roof, as well as roofing, materials,
underlayment and location of vents

ROOF FRAMING PLAN


- A roof framing plan shows size and direction of the construction
members that are required to frame a roof
* Includes the truss that supports the roofing system which
integrate the following: Ridge, rafter, and roofing surface of the
roof plan
* Use to prepare in the structural sheet
* You have to consider the structural framing that used to support
the roof surfaces/roof materials

Important element of the Roof


o Roof Slope - a description of the angle that the roof rafter makes with a horizontal reference. It compares the horizontal run
to the vertical rise. A 6:12 roof has a pitch of ½
TYPES OF ROOF
FLAT ROOF
On a flat roof, a slope of ¼ inch per foot is often uses to
prevent water from ponding on the roof. (2 percent slope)

The flat roof is a very common style in areas with


little rain or snow. In addition to being used in residential
construction, the flat roof is typically used on commercial
structures to provide a platform for heating and other
mechanical equipment. When used, it must be shown on the
roof plan
* Be aware of the minimum sizes of the reinforcement that we
provide on the slabs which conforms to the National structural
code
* Also define the water proofing system that we use; fiber,
flesi bond, tack cont,

*Live Loads: Those fixed or


moving weights, which are not
a structural part of the house. SHED ROOF
Examples include furniture, The only
occupants, snow on the roof, limiting factors
etc. of slope on a
shed roof are
* Dead Loads: Those static or the roofing
fixed weights of the structure material and
itself. Example of dead loads aesthetic
are the weights of roofing, considerations
foundation walls, siding, GABLE
joists, etc. ROOF
Define the term parapet as used in reference to a flat roof: It is *A Gable roof is
a false wall surrounding the perimeter of the roof the most common
type of roof used
in residential construction. It is the made up of two shed roofs slopes, the lower portion of the roof being a steeper slope than
that meet to form a ridge between the support walls the upper

DUTCH HIP ROOF


HIP ROOF A Dutch hip roof
*A Hip roof has is a combination
many similarities of a hip and gable
to a gable roof but roof
has a minimum of
four surfaces
instead of two

DORMER WINDOW
*Briefly describe a dormer: A dormer is an opening framed in
the roof to allow for window placement
The intersections of gable surfaces are called either hips or
valleys

The weight of the roofing material will


affect the size of framing members all
the way down to the foundation level
Example of skeleton of hip or valley gable

A-FRAME ROOF
An A-Frame
structure uses
A square is used to describe an area
rafters to form
of roofing that covers 100 square
its supporting
feet
walls

Built-up roofing of felt and asphalt is typically used on flat or


low slope roofs below a 3 in 12 slope

On a roof plan, the symbol


preceded by the letters
DN is called a slope
indicator

GAMBREL ROOF The standard shingle is a three tab


rectangular strip weighing 235 pounds per
square
A gambrel roof is
patterned
somewhat after
the gable roof but
has two separate
On shingle roofs most building codes require a minimum
slope of 4:12 with an underlayment of one layer of 15 pound A small gable built on the up-slope side of the chimney to
roofing felt. divert water away from the chimney is called a saddle

As the angle of the roof is increased, the size of the overhang


may need to be decreased so that the eave will not extend into
the line of sight from the window

Hips represent the intersection between two roof planes and


are represented by a line drawn at an angle that is one-half of
the angle formed between the two supporting walls

The attic area must be provided with vents that are covered
with 1/8 inch screen mesh
A skylight is connected to the
The attic access should have an opening that is 22 inches by ceiling by an enclosed area
30 inches with a minimum headroom clearance above the called a chase or well
access door of 30 inches.

Avoid placing the access in areas such as the garage; areas


with high moisture content, such as bathrooms and utility
rooms, or in bedrooms that will be used by young children.

Code requires that the access be located in a hallway or other


accessible location.
A roof plan requires very few dimensions. Typically only the
overhangs and openings are dimensioned. These may even be
specified in note form rather than with dimensions

When slopes on both sides of the roof are equal, the wider the
distance between the support walls the higher the roof ridge
will be.
TRUSSES
Trusses are designed so that the weight to be
supported is spread to the outer walls. This is done by
placing some members in tension and some in compression.
A member in compression is indicated by a plus sign, and FASCIA BOARD
one in tension is represented by a minus sign. A fascia is a trim board placed at the end of the rafter or truss
*Most trusses are spaced 24” O.C. tails and usually perpendicular to the building wall.
*The fascia can be make from either 1X or 2X material,
depending on the need to resist warping.

VENTS
*Vents may be placed in the gabled end walls near the ridge.
In some areas, a continuous vent is placed in the eaves, or a
vent may be placed in each third rafter space

ELEVATION
Objective:
To prepare working and IMPORTANT CONSIDERATIONS
architectural elevation plan of a 1. The required number of elevations
building 2. The type of elevations to be drawn
3. The scale of the elevations
ELEVATIONS – a drawing 4. Where the elevations will be placed
representing the projection of any 5. How the elevations will be identified
part of a structure on a vertical
plane directly facing it

COMMON METHOD OF ARRANGEMENT


COMMON PRACTICE IN DRAWING THE
IRREGULAR SHAPE

CATEGORIES TO INCLUDE
 Roofing
 Wall Coverings
 Doors
 Windows
ADDITIONAL ENHANCEMENT

WORKING ELEVATION
Working elevations contain less finish detail but still show the shape of a structure accurately
* Drawing the front elevation using finished-quality lines. Note that features in the background such as the chimney are often
omitted for clarity.

DIFFERENT ROOFING SYMBOLS


 Shingles
 Flat Tiles

 Curved or Spanish Tiles

LAYOUT

STABLISHING OF THE BOUNDARY LINES

ROOFING

DOORS AND WINDOWS


FINISHING

ANNOTATION

INTERIOR ELEVATION
* Is an elevation showing inside of the building * It used a right arrow showing the drawing number on which
* It is something included in working drawings only when the detail appears
there is some special interior construction to be illustrated * Sight arrow is used to interpret detail indicated in sight
* It is also drawn outside four elevation or sometimes drawn arrow
in a separate sheet

THUMBNAIL SKETCHES * Harmony * Shadows


To help decide the general exterior styling
It is simpler to draw than thumbnail sketches of the floor * PROPORTION
plan since dimensions, window, locations, and door locations Size and shape of areas and their relation to one another
may be transferred from the plan Rules of good proportion
The final choice may be influenced by the character of the 1. Avoid square areas or multiples of squared since a
neighborhood rectangular area that cannot be visually divided into
squares is more interesting and pleasing
PRELIMININARY SKETCHES 2. Balance areas so that they do not appear unstable
It is prepared using the thumbnail sketches as a guide to the 3. Areas should be either completely symmetrical or
general styling obviously unsymmetrical
It is done on graph paper 4. One leading area should dominate the entire design,
* Proportion * Fenestration with the other areas subordinate
5. Repetition of elements may be used to advantage or o Height of roof
disadvantage depending upon the circumstances o Depth of footings below grades
o Finished-floor-to-finished-floor heights
o Height of chimney above roof
o Height of other features
o Height of windows
* FENESTRATION
o Roof slope indication
Arrangements of windows in a wall
o Window schedules
Rules
o Titles and notes indicating materials and special
1. Arrange windows symmetrically in symmetrical
elevation but off center in unsymmetrical elevation details
2. Line up windows on different floors
3. Do not use a variety of types and sizes of window FINISHED SKETCHES
4. Arrange windows in groupings when possible * It can be omitted when preliminary sketches are done
carefully
* HARMONY * Window and door sizes
Feature  Window
Materials o Fixed
o Double – hung (slides vertically)
* SHADOWS o Sliding (slides horizontally)
Effect of solar orientation o Awning (hinged at top and swings outward)
Simple shadow lines are made more interesting by a o Hopper (hinged at bottom and swings inward)
variation in the surface casting the shadow or by varying o Casement (hinged outward and swings outward)
surface receiving the shadow o Pivoted (hinged at center)
o Jalousie (individually hinged panes)
DIMENSIONING
o Vertical dimensions

 Window and door representation * Rear elevation * east elevation


 Material representation * Right-side elevation * south elevation
 Footings and areawalls * Left – side elevation * west elevation
 Labeling views
* Front elevation * north elevation ELEVATION DRAWING
* Layout  Working plans:
* Details Materials to be used
o
 Roof fascia Symbols
o
 Roof beams Thickness
o
 Chimney, saddle and flashing  GI – sheet
 Window representation  Corrugated / rib type
 Thickness 0.03 – 0.05
 Grade lines
o Description
 Material representation
o Doors
 Darkened building outline
o Windows
 Glass
SECTION  Type (sliding or casement)
It shows the entire building construction  Window height 1.2m
* Structural section * Wall section  Window height from floor line 0.9 (2.1 – 1.2)
* Detail section o Annotations
ADDITIONAL NOTES  6mm and 3mm
 Golden ratio – 1.618  3mm for the notes and details
 Square – most efficient section  Minimum drop ceiling – 30
 Finished floor line – 0.1 m

You might also like