8DJH en Catalog
8DJH en Catalog
siemens.com/8DJH
Application
Typical uses
R-HA40-111.tif
R-HA40-112.tif
Application
in public
and industrial
energy systems
R_HA40-150a tif
R_HA40_160 tif
R-HA40-157 tif
R-HA40-110.tif
2 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Contents
Requirements
Distribution Systems Features, safety, technology, classification 6 to 8
Components
Three-position switch-disconnector 24 to 26
Vacuum circuit-breaker 27 to 29
Busbar extension, modularity 30
HV HRC fuse assembly 31
Allocation of HV HRC fuses
and transformer ratings 32 to 36
Current and voltage transformers 37 to 41
Current and voltage sensors 42 and 43
Cable connections, cable plugs 44 to 50
Interlocks, locking devices 51
Indicating and measuring equipment 52 to 60
Transformer monitor system,
time-fuse-link protection system 61
Intelligent transformer substation 62 and 63
Protection systems 64
Low-voltage compartment, low-voltage niche 65
Dimensions
Room planning, switchgear installation 66 to 68
Individual panels and modules,
panel combinations 69 to 81
Outdoor enclosure 82
Floor openings and fixing points 83 to 86
Installation
The products and systems described in this catalog Shipping data, transport 87 and 88
are manufactured and sold according to a certified
management system (acc. to ISO 9001, ISO 14001
Standards
and BS OHSAS 18001).
Standards, specifications, guidelines 89 to 91
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 3
Application
Types
R-HA40-150a.eps
R-HA40-149b tif
R-HA40-156.eps
4 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Application
Typical uses, ratings, approvals
8DJH switchgear is a factory-assembled, type-tested, Electrical data (maximum values) and dimensions
3-pole metal-enclosed single-busbar switchgear for indoor Rated voltage kV 7.2 12 15 17.5 24
installation. Rated frequency Hz 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
8DJH switchgear is used in public and industrial energy Rated short-duration kV 20 1) 28 2) 36 38 50
systems of the secondary distribution level, e.g. in power-frequency
withstand voltage
• Local ring-main units, customer transfer substations and Rated lightning impulse kV 60 1) 75 2) 95 95 125
switching substations of power supply and public utilities withstand voltage
• Wind power and solar plants, hydroelectric power plants Rated peak kA 63 / 65 63 / 65 63 / 65 63 / 65 50 / 55
• Water and sewage treatment plants withstand current
Rated short-circuit kA 63 / 65 63 / 65 63 / 65 63 / 65 50 / 55
• Airports, railway stations, underground railway stations
making current
• Open-cast mining facilities
Rated short-time kA 20 / 21 20 / 21 20 / 21 20 / 21 20 / 21
• High-rise buildings. withstand current 3 s
Rated short-time kA 25 25 25 25 20 / 21
withstand current 1 s
Rated normal current A 630 630 630 630 630
of the busbar
Rated normal current A 200 / 250 / 400 / 630 3)
of feeders
Width (feeders) mm 310 / 430 / 500 3)
Depth
– without pressure
relief duct mm 775 775 775 775 775
– with pressure
relief duct mm 890 890 890 890 890
Height
without low-voltage
compartment and
pressure relief duct mm optionally 1040 / 1200 / 1400 / 1700
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 5
Requirements
Features Safety
6 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Requirements
Technology
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 7
Requirements
Classification
8 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Technical Data
Electrical data of the switchgear
1) Design option
2) The rated normal currents apply to ambient air temperatures of max. 40 °C.
The 24-hour mean value is max. 35 °C (according to IEC / EN 62271-1 / VDE 0671-1)
3) Depending on HV HRC fuse-link
4) Minimum and maximum permissible ambient air temperature depending on the secondary equipment used
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 9
Technical Data
Switching capacity and classification of switching devices
Three-position switch-disconnector
Switching capacity for general-purpose switches according to IEC / EN 62271-103 (former: IEC / EN 60265-1 / VDE 0670-301)
Rated voltage Ur kV 7.2 12 15 17.5 24
Test duty Rated mainly active load 100 operations Iload [I1] A 630
TDload breaking current Iload 20 operations 0.05 Iload [I1] A 31.5
Test duty Rated closed-loop breaking current Iloop [I2a] A 630
TDloop
Test duty Rated cable-charging breaking current Icc [I4a] A 68
TDcc
Test duty Rated line-charging breaking current Ilc [I4b] A 68
TDlc
Test duty Rated short-circuit making current Ima 50 Hz up to kA 63 63 63 63 50/52.5 1)
TDma 60 Hz up to kA 65 65 65 65 52/55 1)
Test duty Rated earth-fault breaking current Ief1 [I6a] A 200
TDef1
Test duty Rated cable-charging breaking current and line-charging breaking
TDef2 current under earth-fault conditionsIef2 [I6b (√3 · I4a) or I6b (√3 · I4b)] A 115
Number of operating cycles, mechanical / Classification n 1000/M1
Number of operating cycles, electrical with Iload / Classification n 100/E3
Number of short-circuit making operations with Ima / Classification n 5 / E3 5 / E3 5 / E3 5 / E3 5 / E3
C-classification for general-purpose switches (no restrikes, TD: Icc, Ilc) C2 C2 C2 C2 C2
Switching capacity for make-proof earthing switch according to IEC / EN 62271-102 / VDE 0671-102
Rated short-circuit making current Ima 50 Hz up to kA 63 63 63 63 50/52.5 1)
60 Hz up to kA 65 65 65 65 52/55 1)
Number of operating cycles, mechanical / Classification n 1000/M0
Number of short-circuit making operations n 5
Classification E2
Switching capacity for make-proof earthing switch, feeder side, in transformer feeder with HV HRC fuses
Rated short-circuit making current Ima 50 Hz kA 6.3
60 Hz kA 6.5
Rated short-time withstand current Ik with t k = 1 s kA 2.5
1) Design option
2) Depending on HV HRC fuse-link
10 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Technical Data
Switching capacity and classification of switching devices
Vacuum circuit-breaker
Switching capacity according to IEC / EN 62271-100 / VDE 0671-100
Type 1.1 with three-position disconnector
Rated voltage Ur kV 7.2 12 15 17.5 24
Rated normal current of feeders Ir A 630
50 Hz Rated short-time for switchgear with t k = 1 s up to kA 25 25 25 25 20/21 1)
withstand current Ik for switchgear with t k = 3 s up to kA 20/21 1)
Rated peak withstand current Ip up to kA 63 63 63 63 50/52.5 1)
Rated short-circuit breaking current Isc up to kA 25 25 25 25 20/21 1)
Rated short-circuit making current Ima up to kA 63 63 63 63 50/52.5 1)
60 Hz Rated short-time for switchgear with t k = 1 s up to kA 25 25 25 25 20/21 1)
withstand current Ik for switchgear with t k = 3 s up to kA 20/21 1)
Rated peak withstand current Ip up to kA 65 65 65 65 52/55 1)
Rated short-circuit breaking current Isc up to kA 25 25 25 25 20/21 1)
Rated short-circuit making current Ima up to kA 65 65 65 65 52/55 1)
Number of mechanical operating cycles for disconnector n 1000
Number of mechanical operating cycles for earthing switch n 1000
Number of mechanical operating cycles for circuit-breaker n 10,000
Classification of circuit-breaker M2, E2, C2, S2
Classification of disconnector M0
Classification of make-proof earthing switch E2
Rated operating sequence O – 0.3 s – CO – 3 min – CO
O – 0.3 s – CO – 15 s – CO on request
Number of short-circuit breaking operations n 25 or 50
1) Design option
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 11
Product Range
Individual panels and modules – freely configurable for up to 4 functions in the block
HA40-2291 eps
HA40-2125a eps
Three-position
switch-disconnector
Three-position
disconnector
Capacitive voltage
detecting system
HV HRC fuse
Ring-main feeder Circuit-breaker feeder
Type R Type L
HA40-2124a eps
HA40-2127a eps
Cable connection
with outside cone
(not included in the
scope of supply)
Surge arrester
or limiter
Make-proof
earthing switch
Transformer feeder
Type T
HA40-2126a eps
430 mm wide
1)
12 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Product Range
Individual panels
HA40-2129a eps
circuit-breaker
430 mm wide 430 mm wide
Three-position
switch-disconnector
Three-position
disconnector
Capacitive voltage
detecting system
Bus sectionalizer panel with switch-disconnector
Type S(620) Type S(500)
HA40-2130 eps
HA40-2131c eps
Current transformer
Plug-in voltage
transformer 4MT3
HA40-2133b eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 13
Product Range
Individual panels
HA40-2135b eps
Type R(500) Type L(500) Vacuum
500 mm wide with circuit- circuit-breaker
1) 1)
breaker
type 1.1 or
4MT3 4MT3
type 2)
500 mm wide
Three-position
switch-disconnector
*) *)
Three-position
disconnector
Capacitive voltage
detecting system
4MT8 4MT8
*)
Three-phase
current transformer
Cable connection
with outside cone
(not included in the
scope of supply)
Surge arrester
or limiter
4MT3 4MT3
Plug-in voltage
transformer
Busbar earthing panel Busbar earthing panel
Type E
HA40-2138a eps
HA40-2136a eps
Type E(500)
310 mm wide 500 mm wide
1) 1)
4MT3
14 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Product Range
Air-insulated billing metering panels type M, 840 mm wide
Voltage transformer,
P1 P2 cast-resin insulated
P1 P2
P2 P1
P2 P1
Capacitive voltage
detecting system
Fixed earthing
points for
busbar earthing
Billing metering panels with cable connection on the right P1 and P2
are terminal
HA40-2140a eps
designations of
the current
transformer
P1 P2
P1 P2
P2 P1
P2 P1
P1 P2 P2 P1 P1 P2 P2 P1
P1 P2
P1 P2
P2 P1
P2 P1
HA40-2142a eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 15
Product Range
Product range overview of panel blocks (excerpt)
Panel blocks with transformer feeders, Panel blocks with circuit-breaker feeders,
optionally with busbar extension optionally with busbar extension
KT 1 transformer feeder, KL 1 circuit-breaker feeder,
K Radial cable 1 radial cable connection K Radial cable 1 radial cable connection
HA40-2108b eps
HA40-2113a eps
connection as connection as
incoming 740 775 1200 incoming 740 775 1200
feeder 1400 feeder 1400
1700 1700
HA40-2219a eps
1400 1400
1700 1700
HA40-2114a eps
HA40-2116a eps
HA40-2117a eps
16 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Product Range
Product range overview of panel blocks (excerpt)
Panel blocks with ring-main feeders, Panel blocks with transformer feeders,
optionally with busbar extension optionally with busbar extension
RR 2 ring-main feeders TT 2 transformer feeders
HA40-2121b eps
HA40-2118a eps
HA40-2122b eps
HA40-2119a eps
RRT-R
HA40-2361a eps
RRT-RRT
HA40-2362a eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 17
Design
Panel design (examples)
HA40-2144e eps
HA40-2143c eps
2 2
6 6
1 1
7 7
3 3
8 9
4 4
11
9
12
13
10
10
Circuit-breaker feeder
Type L Section
5 1 Control board (for details, see page 23)
HA40-2145e eps
2 2 Busbar arrangement
6 3 Three-position switch-disconnector
1 1 4 Pressure relief device
15 5 Wiring duct, removable, for protection
14 and / or bus wires
10 14 Vacuum circuit-breaker
15 Circuit-breaker operating mechanism,
Type 1.1 Type 2 operating mechanism for three-position
disconnector
18 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Design
Panel design (examples)
Circuit-breaker feeder
Type L(500) Section
1 Control board (for details, see page 23)
HA40-2146d eps
5 10
11
12
Type 2 Section
13 Low-voltage compartment (standard)
HA40-2263c eps
3
7
1
8
4
9
5 10
11
17
18
12
Type 1.1
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 19
Design
Panel design (examples)
3
8
4
9a
1 9b
10
12
Section
7 1 Sockets for voltage detecting system
HA40-2149e eps
2 Busbar connection
3 Busbar vessel, filled with gas
6 4 Pressure relief device
8
5 Current transformer type 4MA7
1
6 Voltage transformer type 4MR
7 Wiring duct, removable, for protection and /
10
or bus wires
12
20 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Design
Panel design (examples)
Panel block
Type 8DJH Compact RRT Section
HA40-2363 eps
6
3
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 21
Design
Outdoor enclosure
R-HA40-8DJH-179.tif
• For outdoor applications on company grounds
• Enclosure attached to standard indoor panels
• Enclosure with three different heights, for 1200 mm
switchgear height (optionally with low-voltage compart-
ment as a 200 mm, 400 mm or 600 mm high version), or
1400 mm switchgear height (optionally with low-voltage
compartment as a 200 mm or 400 mm high version)
• Enclosure with four different widths for freely configu-
rable, non-extendable switchgear rows up to a switch-
gear width of 2000 mm (for dimensions, see page 82)
• Internal arc classification IAC A FL or FLR to 21 kA / 1 s
according to IEC 62271-200
• Degree of protection IP 54.
R-HA40-8DJH-178.tif
22 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Design
Operation (examples)
HA40-2265b eps
as well as locking devices and local-remote switches are
arranged according to the panel type and version. The ready-
for-service indicator and rating plates are fitted in accor-
dance with the panel blocks. 4
Operation is identical for transformer and circuit-breaker 5
feeders. First, the operating mechanism must be charged;
then, closing / opening is done through separate pushbut-
6
tons. The condition of the energy store is indicated.
All actuating openings are functionally interlocked against
each other, and are optionally lockable. Separate operating 7
levers for the disconnecting and earthing function are
optionally available.
HA40-2266b eps
R-HA40-114.tif
HA40-2264a eps
12
11
1 4
10
5 9
2 6
8
3
3
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 23
Components
Three-position switch-disconnector
Features
• Switch positions: Three-position switch-disconnector
CLOSED – OPEN – EARTHED
• Switching functions as general-purpose switch- Busbar
disconnector (class E3) according to CLOSED
– IEC / EN 62271-103 / VDE 0671-103
– IEC / EN 62271-102 / VDE 0671-102 OPEN
• Designed as a three-position switch with the functions
– Switch-disconnector and
– Make-proof earthing switch
• Operation via rotary bushing welded gas-tight into the EARTHED
front of the switchgear vessel
• Climate-independent contact in the gas-filled switchgear
HA40-2150b eps
vessel
• Maintenance-free for indoor installation according to
IEC / EN 62271-1 / VDE 0671-1
Feeder
• Individual secondary equipment.
Mode of operation
The operating shaft forms one unit together with the
three contact blades. Due to the arrangement of the fixed
contacts (earth – busbar), it is not necessary to interlock the
CLOSE and EARTHING functions. OPEN / CLOSE
Closing operation
During the closing operation, the operating shaft with the
moving contact blades changes from the “OPEN” to the
“CLOSED” position. OPEN / EARTH
The force of the spring-operated mechanism ensures a
high operator-independent closing speed and a reliable
connection of the main circuit.
Opening operation
CLOSED OPEN
During the opening operation, the arc is caused to rotate by
the arc-suppression system. This rotation movement pre-
A40-2273 eps
24 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Operating mechanisms for the three-position switch
Legend:
R = Ring-main feeder
S = Bus sectionalizer panel with switch-disconnector
L = Circuit-breaker feeder
T = Transformer feeder
H = Bus sectionalizer panel with switch-fuse combination
V = Bus sectionalizer panel with circuit-breaker
M(430) / M(500) = Busbar voltage metering panel
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 25
Components
Operating mechanisms for the three-position switch, equipment (optional)
Abbreviations:
NO = Normally open contact
NC = Normally closed contact
26 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Vacuum circuit-breaker
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 27
Components
Vacuum circuit-breaker
HA40-2271a_en eps
HA40-2270a_en eps
10,000 10,000
Permissible operating cycles
2000 2000
1000 1000
500 500
200 200
1 2 1 2
100 100
50 50
25 25
10 10
0.1 0.2 0.5 1 2 5 10 20 kA 50 0.1 0.2 0.5 1 2 5 10 25 kA 50
Breaking current (r.m.s. value) Breaking current (r.m.s. value)
HA40-2268a_en eps
10,000 10,000
5000 5000
Permissible operating cycles
2000 2000
1000 1000
500 500
200 200
100 100
50 50
3 4 3 4
20 20
10 10
6 6
2 2
1 1
0.1 0.2 0.5 1 2 5 10 16 kA 50 0.1 0.2 0.5 1 2 5 10 20 kA 50
Breaking current (r.m.s. value) Breaking current (r.m.s. value)
Max. number of
short-circuit breaking operations
➀ n = 25 ➂ n=6
➁ n = 50 ➃ n = 20
28 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Secondary equipment of the vacuum circuit-breakers
= standard Abbreviations:
= option NO = Normally open contact
1) Depending on the secondary components selected o.r. = on request NC = Normally closed contact
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 29
Components
Busbar extension, modularity
Features
• Busbar extension possible on all individual panels and Interconnecting the panels
panel blocks (ordering option) 4 1 2
• Plug-in unit consisting of contact coupling and screened
silicone coupling
• Insensitive to pollution and condensation
• Switchgear installation, extension or panel replacement
is possible without gas work
• Busbar connections to metering panels are possible.
Every panel block and every individual panel is optionally
available with busbar extension on the right, on the left or
on both sides. This offers a high fl exibility for the creation
of switchgear configurations whose functional units can
be lined up in any order. Local installation and lining up is
HA40-2152a eps
done without gas work.
Lining up takes place as follows:
• By the busbar couplings on the medium-voltage side. 3
Tolerances between adjacent panels are compensated
by spherical fixed contacts and the movable contact
coupling with degrees of freedom in all axis directions.
• By safe dielectric sealing with screened silicone couplings
that are externally earthed and adjustable to tolerances.
These silicone couplings are pressed on with a defined
pressure when the panels are interconnected.
Surge-proof termination
• On free busbar ends, screened dummy plugs are
inserted, each of which is pressed on through a metal 5
cover. A common protective cover with a warning is
fixed over all three covers.
• By centering bolts for easier switchgear installation
and fixing of adjacent panels.
• By bolted panel joints with defined stops for the distances
between adjacent panels and the associated pressure for
contact pieces and silicone couplings.
Switchgear installation, extension or replacement of one
or more functional units requires a lateral wall distance
≥ 200 mm.
HA40-2215 eps
6 7
1 Contact piece
2 Silicone coupling
3 Tension spring for earthing
4 Centering bolt
5 Silicone dummy plug with insertable sleeve
6 Clamping cover for dummy plugs
7 Busbar termination cover
30 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
HV HRC fuse assembly
Features
• Application in switch-disconnector / fuse combination in HV HRC fuse assembly
– Transformer feeders (T)
HA40-2153c eps
– Bus sectionalizer with switch-fuse combination (H) 1 2 3
• HV HRC fuse-links according to DIN 43625
(main dimensions) with striker; “medium“ version
according to IEC / EN 60282-1/ VDE 0670-4
– As short-circuit protection for transformers
– With selectivity – depending on correct selection –
to upstream and downstream connected equipment
– 1-pole insulated
• Requirements according to IEC/EN 62271-105/VDE 0671-105
fulfilled in high-voltage switch-fuse combinations 9 8 5 7 6 5 4
• Climate-independent and maintenance-free
• Fuse assembly connected to the three-position
switch-disconnector via welded-in bushings and con- 1 Fuse box
necting bars
2 Fuse slide
• Arrangement of fuse assembly below the switchgear vessel
3 Tripping pin for spring-operated / stored-energy mechanism
• Fuses can only be replaced if feeder is earthed
4 Sealing cover with seal
• Fuse slide for reference dimension 292 mm and 442 mm
5 Locking cap
Option with three-position switch-disconnector
6 HV HRC fuse
• Shunt release (f-release)
7 Cable connection
• “Tripped signal” of the transformer switch for remote
8 Bushing
electrical indication with 1 normally open contact.
9 Switchgear vessel
Mode of operation
Schematic sketches for fuse tripping
In the event that an HV HRC fuse-link has tripped, the
switch-disconnector is tripped via an articulation which is
HA35-2523 eps
Fuse link in
integrated into the cover of the fuse box (see figure). service condition
In the event that the fuse tripping fails, e.g. if the fuse
has been inserted incorrectly, the fuse box is protected by
thermal protection. The overpressure generated by over- Fuse tripping
heating trips the switch via the diaphragm in the cover of through striker
the fuse box and via an articulation. This prevents the fuse
box from incurring irreparable damage.
Fuse tripping through
This thermal protection works independently of the type
overpressure, e.g. if
and design of the HV HRC fuse used. Like the fuse itself, HV HRC fuse-link has
it is maintenance-free and independent of any outside been inserted incorrectly
climatic effects.
Furthermore, the HV HRC fuses (e.g. make SIBA) release
Note to HV HRC fuse-links
the striker depending on the temperature and trip the
switch-disconnector as early as in the fuse overload range. According to IEC 60282-1 (2009) Clause 6.6, the breaking
Impermissible heating of the fuse box can be avoided in capacity of HV HRC fuses is tested within the scope of
this way. the type test at 87 % of their rated voltage. In three-phase
systems with resonance-earthed or isolated neutral, under
Replacement of HV HRC fuse-links double earth fault and other conditions, the full phase-to-
(without tools) phase voltage may be available at the HV HRC fuse during
• Isolate and earth the transformer feeder breaking. Depending on the size of the operating voltage
• Open the cover of the fuse access of such a system, this applied voltage may then exceed
• Replace the HV HRC fuse-link. 87 % of the rated voltage. It must therefore already be
ensured during configuration of the switching devices
and selection of the HV HRC fuse that only such fuse-links
are used, which either satisfy the above operating
conditions, or whose breaking capacity was tested at least
with the maximum system voltage. In case of doubt, a
suitable HV HRC fuse must be selected together with the
fuse manufacturer.
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 31
Components
Allocation of HV HRC fuses and transformer ratings
32 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Allocation of HV HRC fuses and transformer ratings
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 33
Components
Allocation of HV HRC fuses and transformer ratings
34 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Allocation of HV HRC fuses and transformer ratings
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 35
Components
Allocation of HV HRC fuses and transformer ratings
36 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Cable-type current transformers 4MC7033 and 4MC7031
Features
• According to Cable-type current transformer Cable-type current transformer
IEC / EN 61869-1 and -2 / 4MC7033, 4 overall heights 4MC7031
VDE 0414-9-1 and -2
• Designed as ring-core
R-HA41-024a.eps
R-HA41-025.eps
current transformers, 1-pole
H
• Free of dielectrically
stressed cast-resin parts
H
(due to design)
• Insulation class E
• Inductive type
• Secondary connection by
means of a terminal strip
in the panel.
Installation
The mounting location is out-
side the switchgear vessel,
around the cable at the panel
connection; installation on
the cable on site.
Note: Installation inside or Technical data Technical data
underneath the panel depend- Cable-type current transformer 4MC7033 Cable-type current transformer 4MC7031
ing on the panel type and Primary data Primary data
the overall transformer
Highest voltage 0.72 kV Highest voltage 0.72 kV
height. for equipment Um for equipment Um
Rated current IN 20 A to 600 A Rated current IN 50 A to 600 A
Rated short-duration 3 kV Rated short-duration 3 kV
power-frequency withstand power-frequency withstand
voltage (winding test) voltage (winding test)
Rated short-time up to 25 kA / 1 s Rated short-time up to 25 kA / 1 s
thermal current Ith or 20 kA / 3 s thermal current Ith or 14.5 kA / 3 s
Rated continuous 1.2 × IN Rated continuous 1.2 × IN
thermal current ID thermal current ID
Transient overload 1.5 × ID / 1 h or Transient overload 1.5 × ID / 1 h or
current 2 × ID / 0.5 h current 2 × ID / 0.5 h
Rated dynamic 2.5 × Ith Rated dynamic 2.5 × Ith
current Idyn current Idyn
Dimensions Dimensions
Overall height H, mm 65 110 170 285 Overall height H 89 mm
depending on
core data
Outside diameter 150 mm Width × depth 85 mm × 114 mm
Inside diameter 55 mm Inside diameter 40 mm
For cable diameter 50 mm For cable diameter 36 mm
Other values on request Other values on request
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 37
Components
Three-phase current transformer 4MC63
Features
• According to Three-phase current transformer
IEC / EN 61869-1 and -2 / 4MC63
VDE 0414-9-1 and -2
R-HA41-022.eps
• Designed as ring-core
current transformer, 3-pole
• Free of dielectrically
stressed cast-resin parts
(due to design)
• Insulation class E
• Inductive type
• Climate-independent
• Secondary connection by Technical data Technical data
means of a terminal strip Three-phase current transformer 4MC6310 Three-phase current transformer 4MC6311
in the panel. for IN ≤ 150 A and ID = 630 A for IN ≤ 400 A and ID = 630 A
38 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Bus / cable-type current transformer 4MC7032
Features
• According to Bus / cable-type current transformer
IEC / EN 61869-1 and -2 / 4MC7032
VDE 0414-9-1 and -2
R-HA41-027.eps
• Designed as ring-core
current transformer, 1-pole
• Free of dielectrically
stressed cast-resin parts B
(due to design)
• Insulation class E
• Inductive type
• Secondary connection by
means of a terminal strip
in the panel. Technical data Panel section type V
Bus / cable-type current transformer 4MC7032
Installation
Primary data
• Mounting location:
HA40-2154a eps
Highest voltage 0.72 kV
– Arranged outside the
for equipment Um
switchgear vessel on the
Rated current IN 200 A to 600 A
screened busbar section
in bus sectionalizer panels Rated short-duration 3 kV
power-frequency withstand
with switch-disconnector
voltage (winding test)
type S and bus sectionalizer
Rated short-time up to 25 kA / 1 s
panels with circuit-breaker
thermal current Ith or 20 kA / 3 s
type V with the option of
Rated continuous 1.2 × IN
busbar current transformers
thermal current ID
– Arranged outside the
switchgear vessel around Transient overload 1.5 × ID / 1 h or
current 2 × ID / 0.5 h
the cable at the panel
connection for 310 mm Rated dynamic 2.5 × Ith
current Idyn
panel width (cable feeders
type R and K), transformers Secondary data
mounted on a supporting Rated current 1 A (option: 5 A) 1
plate at the factory; Measur- Class 0.2 0.5 1
final assembly around the ing Overcurrent with- FS5 FS10
cables on site. core factor out 130 130
Note: Depending on
Rating 2.5 VA to 10 VA
the transformer overall
Protec- Class 10 P 5 P *)
height: Installation inside
tion Overcurrent 10 10
or underneath the panel. core factor
Rating 2.5 VA to 15 VA
Dimensions
Overall width B, 80 mm / 150 mm 1 Bus / cable-type current transformer
depending on core data 4MC7032
and mounting location
Outside diameter 125 mm
Inside diameter 55 mm
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 39
Components
Plug-in voltage transformers 4MT3 and 4MT8
Common features
• According to Plug-in Plug-in
IEC / EN 61869-1 and -3 / voltage transformer 4MT3 voltage transformer 4MT8
VDE 0414-9-1 and -3
• 1-pole, plug-in design
• Inductive type
• Connection with
plug-in contact
R-HA41-020.eps
• Safe-to-touch due
to metal cover
R-HA35-120.eps
• Secondary connection by
means of plugs inside the
panel.
Installation
Technical data
• Mounting location:
for types 4MT3 and 4MT8
– Arranged above the
switchgear vessel in Primary data Secondary data
individual panels type Highest voltage for equipment 1.2 × Un Rated voltage 1st winding 100 / √3
L(500), M(430), V and E Rated voltage (8 h) = 1.9 × Un 110 / √3
(optional) Rated voltage Ur Operating voltage Un Auxiliary winding 100 / 3
– Arranged in front of the (option) 110 / 3
kV kV / √3
switchgear vessel in indivi- 3.6 3.3 for 4MT3
dual panel type M(500)
7.2 3.6 Rated long-time current (8 h) 6 A Class
– Direct connection to the
4.2 Rating in VA up to 20 0.2
busbar.
4.8 60 0.5
Features of type 4MT8 5.0 120 1.0
• Metal-enclosed 6.0
for 4MT8
• For connection to the cable 6.3
Rated long-time current (8 h) 6 A Class
plug-in unit (screened). 1) 6.6
Rating in VA up to 25 0.2
12 7.2
Installation 75 0.5
10.0
• Mounting location: 120 1.0
11.0
– Arranged in the cable
11.6
compartment of indivi-
dual panels type L(500) 17.5 12.8
and R(500) (optional). 13.2
13.8
15.0
16.0
24 17.5
20.0
22.0
23.0
40 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Current transformers 4MA7 and voltage transformers 4MR for air-insulated billing metering panels
Features
Current transformer 4MA7 Current transformer 4MA7 Voltage transformer 4MR
• According to
R-HA41-030.eps
R-HA41-029.eps
IEC / EN 61869-1 and -2 /
VDE 0414-9-1 and -2
• Dimensions according to
DIN 42600-8 (small design)
• Designed as indoor support-
type current transformer,
1-pole
• Cast-resin insulated
• Insulation class E
• Secondary connection by
means of screw-type
terminals. Technical data Technical data
Voltage transformer 4MR Current transformer 4MA7, 1-pole Voltage transformer 4MR, 1-pole
• According to Primary data Primary data
IEC / EN 61869-1 and -3 /
Highest voltage up to 24 kV Highest voltage for equipment 1.2 × Un
VDE 0414-9-1 and -3 for equipment Um Rated voltage (8 h) = 1.9 × Un
• Dimensions according to Rated short-duration up to 50 kV Rated voltage Ur Operating voltage Un
DIN 42600-9 (small design) power-frequency
kV kV / √3
• Designed as indoor voltage withstand voltage Ud
transformer: 3.6 3.3
Rated lightning impulse up to 125 kV
– Type 4MR, 1-pole withstand voltage Up 7.2 3.6
– Option: Type 4MR, 2-pole Rated current IN 20 A to 600 A 4.2
• Cast-resin insulated Rated short-time up to 25 kA / 1 s 4.8
• Insulation class E thermal current Ith 5.0
Secondary data
Rated voltage 1st winding 100 / √3
in V 110 / √3
120 / √3
Auxiliary 100 / 3
winding 110 / 3
(option) 120 / 3
Rating Class
in VA up to 20 0.2
60 0.5
100 1.0
Other values on request Other values on request
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 41
Components
Current sensors
Common features
• According to
IEC 60044-8
R-HA40-152.tif
R-HA40-147.tif
(low-power current trans-
formers)
• Example for available
secondary devices that can Ring-core current sensor Ring-core current sensor
be connected: SMCS-JW 1001 SMCS / T-JW 1002, divisible
– SICAM FCM
– 7SJ81
R-HA40-151.tif
(make Zelisko)
The current sensors are
inductive current transfor-
mers whose secondary Three-phase ring-core current sensor Ring-core current sensor
winding delivers a voltage SMCS3-JW1004 with integrated GAE120 / SENS-JW 1003 for
signal through a precision earth-fault detection sensor earth-fault detection, divisible
shunt. At the rated primary
current, this is 225 mV.
Depending on their version,
the sensors have a dual
accuracy class; the output
signal can be equally used for Technical data
measuring, protection and, SMCS-JW1001 SMCS/ GAE120/ SMCS3-
if required, earth-fault detec- T-JW1002 SENS-JW1003 JW1004
tion. The outgoing leads of
Primary data
the sensors are directly
Highest voltage
connected to the secondary 0.72 / 3 kV 0.72 / 3 kV 0.72 / 3 kV 0.72 / 3 kV
for equipment Un
device (SICAM FCM, 7SJ81).
Rated current IN 300 A 1) 300 A 1) 60 A 300 A 1)
Rated short-time
25 kA 1 s 25 kA 1 s 25 kA 1 s 25 kA 1 s
thermal current Ith
Secondary data
Output signal 225 mV 225 mV 225 mV 225 mV
Class 0.5; 1; 3 1; 3 – 0.5; 1; 3
Measuring
Overcurrent factor – – – –
Class 5P 5P – 5P
Protection
Overcurrent factor 10 20 10; 20 – 10
Class – – 1 1
Earth-fault Angle error – – ± 120' ± 120'
detection Composite ≤ 10 % (at 0.4 A) ≤ 10 %
– –
error e ≤ 20 % (at 200 A) (at 0.4 A)
Rated burden ≥ 20 kOhm ≥ 20 kOhm ≥ 20 kOhm ≥ 20 kOhm
1) Usable up to 2 × I n = 600 A (output signal 2 × 225 mV) at constant accuracy class and
half overcurrent factor
2) Mounting location at the bushings around the screened cable plug
42 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Voltage sensors
Common features
• According to
IEC 60044-7
R-HA3541-194 tif
(low-power voltage trans-
R-HA40-153.tif
formers)
• Example for available
secondary devices that can
be connected: Voltage sensor Voltage sensor
– SICAM FCM SMVS-UW 1001 SMVS-UW 1002
– 7SJ81
Voltage sensors
(make Zelisko)
The voltage sensors are
resistor dividers which
provide an output signal Technical data
of 3.25 V / √3 at the rated SMVS-UW1001 SMVS-UW1002
primary voltage. The out-
going leads of the sensors are Primary data
directly connected to the Highest voltage
secondary device for equipment Um 1.2 × Un 1.2 × Un
(SICAM FCM, 7SJ81). Rated voltage (8 h) 1.9 × Un 1.9 × Un
Rated voltage Ur 12 kV 24 kV 12 kV 24 kV
Operating voltage Un 10 kV 20 kV 10 kV 20 kV
Secondary data
Rated voltage 3.25 V / √3 3.25 V / √3
Class 0.5; 1; 3 0.5; 1; 3
Rated burden 200 kOhm ± 1 % 200 kOhm ± 1 %
Installation
Mounting location On the screened cable plugs On the screened cable plugs
make Nexans type 440TB, K440TB; make TE Connectivity type RSTI-58,
other types and makes on request RSTI-CC58xx,
make nkt cables type CB-24 and
CC-24; other types and makes
on request
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 43
Components
Cable connection with interface type C
Features
• Access to the cable compart- Cable compartment
ment only if the feeder has
HA40-2156b eps
HA40-2155a eps
HA40-2157b eps
been disconnected and
earthed
• Bushings according to
DIN EN 50181 with outside
cone and bolted connection
C
B
M16 as interface type C. L1 L2 L3 L1 L2 L3 L1 L2 L3
Connection of 60 95 95 60 85 130 130 85 100 150 150 100
• Cable elbow plugs or cable
T-plugs with bolted contact
M16 for 630 A Panel width 310 mm Panel width 430 mm Panel width 500 mm
• Paper-insulated mass-
impregnated cables via
customary adapters
• Thermoplastic-insulated
cables (1-core and 3-core
Switchgear height 1040 2) 1200 1400 without 1400 with
cables).
without low-voltage absorber base absorber base,
Option compartment 1) or 1700
• Mounted cable clamps on Typical K, R 500 660 860 1160
cable bracket. Panel width 310 mm A
Typical R (8DJH Compact) – – 200 500
Cable plugs Panel width 430 mm Typical K(E), L B – 660 860 1160
Panel width 500 mm Typical R(500), L(500) C – 510 710 1010
• As screened (semi-conduc-
tive) design independent of 1) Option: With low-voltage compartment
the site altitude, 2) Only for panel blocks RR, RRR, RT, RRT and RTR
or
as unscreened (insulated)
design, but then dependent
Connection options
on the site altitude.
185 260 290 298
Surge arresters
• Pluggable on cable T-plug,
cable elbow plug or T-adapter
• The switchgear depth can be 1 2 1 3
380
HA40-2163a eps
44 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Cable connection with interface type C
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 45
Components
Cable connection with interface type C
HA40-2164c eps
HA40-2277a eps
deep cable compartment covers can be ordered optionally
(not for 8DJH Compact). The assignment to selected types
of cable plugs and cable plug / surge arrester combinations 300 a 480
is given in the following tables.
64 b 64 b
775 775
775 + (a+10)
46 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Cable connection with interface type C
Cable plugs for single and double cable connection with surge arresters
Cable plugs for single and double cable connection with Connection combination Deep cable compartment cover 1)
surge arresters
Make Se- Cable plug / Design 2) Arrangement Mounting Deeper by a 3)
rial surge arrester (type) depth (mm)
no. (mm)
Nexans 1 (K)430TB / G + 300SA, Screened K+Ü 290 –
(K)480TB / G + 800SA,
(K)484TB / G + 800SA
2 (K)400TB / G + 400PB-...SA Screened K+Ü 410 250
3 (K)430TB / G + (K)300PB / G + 300SA Screened K+K+Ü 395 105
4 (K)480TB / G + (K)800PB / G + 800SA, Screened K+K+Ü 400 250
(K)484TB / G + (K)804PB / G + 800SA
Südkabel 5 SET (12 / 24) + MUT (13 / 23) Screened K+Ü 302 105
6 SEHDT 23.1 + MUT 23 Screened K+Ü 302 105
7 2× SET (12 / 24) + MUT (13 / 23) Screened K+K+Ü 476 250
with coupling unit KU 23.2 / 23
8 2× SEHDT 23.1 + MUT 23 Screened K+K+Ü 476 250
with coupling unit KU 23.2 / 23
9 SEHDT (13 / 23) + MUT 33 Screened K+Ü 540 250
nkt cables 10 CB 24-630 + CSA 24... Screened K+Ü 290 –
11 AB 24-630 + ASA 24... Insulated K+Ü 290 105
12 CB 36-630 (1250) + CSA... Screened K+Ü 290 –
TE Connectivity 13 RICS 5139 + RDA... Insulated K+Ü 275 –
14 RSTI-58xx + RSTI-CC-58SAxx Screened K+Ü 285 –
15 RSTI-58xx + RSTI-CC-68SAxx Screened K+Ü 292 –
16 RSTI-x9xx + RSTI-CC-58SAxx Screened K+Ü 295 –
17 RSTI-x9xx + RSTI-CC-68SAxx Screened K+Ü 302 105
3M 18 2× 93-EE705-6 / xxx + MUT 23 Screened K+K+Ü 476 250
with coupling unit KU 23.2
Cable plugs for single cable connection and 4MT8 voltage transformers
The 4MT8 voltage transformers can be installed in ring-main Before a dielectric test on the cables (supplied by site with
and circuit-breaker feeders (500 mm panel width). A deep max. 80 % Ud) can be carried out, the voltage transformers
cable compartment cover is not necessary. To connect must be demounted.
them, symmetrical cable T-plugs (see table) are required.
1) Applies to panels of 310- and 430-mm. For individual panels of 500 mm, no deep cable compartment cover
and fl oor opening are required – except for serial no. 9 with cable compartment cover deeper by 105 mm (a)
2) Use of current transformers and sensors in combination with insulated systems on request
3) See drawing on page 46.
K = Cable plug Ü = Surge arrester
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 47
Components
Cable connection for transformer feeders with interface type A
Features
• Access to the cable compartment only if the feeder has Cable compartment
been disconnected and earthed
• Bushings according to DIN EN 50181 with outside cone
and plug-in contact as interface type A.
HA40-2165a eps
Connection of
• Cable elbow plugs or straight cable plugs
• Connection cross-sections up to 120 mm2.
B1
B2
Option
• Mounted cable clamps on cable bracket L1 L2 L3
A
• Bushings according to DIN EN 50181 with outside cone
HA40-2364 eps
and bolted contact as interface type C for cable routing 80 135 135 80
downwards.
300
For 8DJH Compact design with bushing arrangement:
HA40-2365 eps
210
• At the top with cable elbow plug: To the rear (standard)
HA40-2166a eps
Cable plugs
Cable routing downwards Cable routing to the rear
• As screened (semi-conductive) design independent of with cable elbow plug with cable elbow plug
the site altitude,
or
as unscreened (insulated) design, but then dependent
on the site altitude.
310
1040 2) 1200
HA40-2167a eps
48 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Cable connection for transformer feeders with interface type A
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 49
Components
Cable connections
Cable testing
• For cable, ring-main cable and circuit-breaker feeders Cable testing
• Disassembly of the switchgear cables not necessary
• Measuring bolts can be connected following the removal
of the protective cap and / or the end stopper of the cable
plug 2 1
• The switchgear is suitable for the following cable test
voltages:
HA40-2035d eps
Rated voltage of Cable test voltage 1)
switchgear
Ur Uct (DC) Uct (AC) VLF 0.1 Hz 2)
kV kV kV kV
7.2 22 11 11
12 38 19 19
Cable testing at the
15 52 28 28 cable T-plug (example)
17.5 52 28 28
24 72 38 38
Test duration 15 min 60 min 60 min
1 Insulating cap
– In the cable and cable plug manufacturer information.
2 Measuring bolt
50 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Interlocks, locking devices
Standard interlocks
• Three-position switch: Disconnecting function against Interlocking of three-position switch
earthing function (option: locking device)
• Circuit-breaker feeder: Circuit-breaker against three-
position disconnector
• Access to cable compartment is generally only possible if
– the feeder is isolated
HA40-2225b eps
and
– the feeder is earthed (“EARTHED” position).
For ring-main and circuit-breaker feeders
• Option: Closing lockout
Prevents switching the three-position switch-disconnec-
tor from “OPEN” position to “CLOSED” position when the
cable compartment cover is removed.
For transformer feeders Initial situation
• The three-position switch-disconnector cannot be
switched from “EARTHED” to “OPEN” position when the
cable com- partment cover / the HV HRC fuse compart-
ment is open.
HA40-2226b eps
Locking device for padlock
• Shackle diameter 12 mm
• Standard for transformer and circuit-breaker feeders
(stored-energy mechanisms)
• Option for ring-main feeders (spring-operated mecha-
nisms)
• Three-position switch-disconnector lockable at the
operating mechanism in any desired switch position. Release for disconnector operation
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 51
Components
Indicating and measuring equipment
Ready-for-service indicator
Features Gas monitoring
• Self-monitoring; easy to read
• Independent of temperature and pressure variations
• Independent of the site altitude Indicator on control board:
• Only responds to changes in gas density 1 1 Indication:
green: ready for service
• Option: Alarm switch “1NO + 1NC” for remote electrical red: not ready for service
indication.
HA40-2216a eps
2 Measurement box
Mode of operation
3 Magnetic coupling
For the ready-for-service indicator, a gas-tight measure-
ment box is installed inside the switchgear vessel.
A coupling magnet, which is fitted to the bottom end of
the measurement box, transmits its position to an outside
armature through the non-magnetizable switchgear vessel. Principle of operation
This armature moves the ready-for-service indicator of the of gas monitoring with ready-for-service indicator
switchgear.
HA40-2217a eps
While changes in the gas density during the loss of gas, 2
which are decisive for the dielectric strength, are
displayed, temperature-dependent changes in the gas 3
pressure are not. The gas in the measurement box has the
same temperature as that in the switchgear vessel.
The temperature effect is compensated via the same
pressure change in both gas volumes.
Stainless-steel vessel Ready-for-service
filled with SF6 gas indicator
52 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Indicating and measuring equipment
R-HA40-103 psd
A0
in indicator Plug-in
• LRM detecting systems with integrated voltage
indicator A1
indicator type VOIS+, VOIS R+,
CAPDIS-S1+, CAPDIS-S2+, WEGA 1.2 C, per phase at
the panel front A2
WEGA 2.2 C or WEGA 3.
Plug-in voltage indicator A3
• Verification of safe isolation from
supply phase by phase A4
• Indicator suitable for continuous
R-HA41-VOIS tif
operation A5
• Measuring system and voltage indicator
can be tested, repeat test according to A6
local specifications and standards
A7
HA35-2579c eps
• Voltage indicator flashes if high voltage
is present. Integrated voltage indicator
VOIS+, VOIS R+ A8
VOIS+, VOIS R+
• Without auxiliary power
CAPDIS S2+: The red and green LEDs show the
• Display indication “A1” to “A3” state of the relay contacts
(see legend)
R-HA41-CAPDIS-S1.tif
L2
• Without auxiliary power
L3
• Display indication “A1” to “A7” C1
(see legend)
• Without ready-for-service monitoring U LE C2 U2
• Without signaling relay
(without auxiliary contacts). Voltage indica- CAPDIS-Sx+ / VOIS+
CAPDIS-S2+ tor plugged in installed
(HR, LRM)
• Display indication “A0” to “A8”
(see legend) Voltage indication
• Only by pressing the “Test” pushbutton: via capacitive voltage divider (principle)
“ERROR” indication (A8), e.g. in case of
missing auxiliary voltage – C1 Capacitance integrated into bushing
• With ready-for-service monitoring – C2 Capacitance of the connection leads and the voltage indicator to earth
(auxiliary power required) ULE = UN / 3 during rated operation in the three-phase system
• With integrated signaling relay for U2 = UA = Voltage at the capacitive interface of the switchgear or at the voltage indicator
signals (auxiliary power required).
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 53
Components
Indicating and measuring equipment
WEGA 3
• Display indication “A1” to “A5”
R-HA41-WEGA-3.tif
Symbols shown
• Integrated repeat test of the
interface (self-monitoring) WEGA 3 WEGA 1.2 C WEGA 2.2 C
HA35-2845a eps
WEGA 1.2 C
• With integrated 3-phase LRM
test socket for phase compar- A7
R-HA41-WEGA-2-2-C.tif
ison.
LC display gray: not illuminated
LC display white: illuminated
WEGA 2.2 C WEGA 2.2 C: The red and green LEDs show the
• Display indication “A0” to state of the relay contacts
“A7” (see legend) LED doesn´t light up
LED lights up
• Integrated repeat test of the
Integrated voltage indicator U = Operating voltage
interface (self-monitoring)
WEGA 2.2 C A0 For WEGA 2.2 C:
• With integrated function test Operating voltage not present, auxiliary
(without auxiliary power) by power present, LCD illuminated
pressing the “Display Test” A1 Operating voltage present
button For WEGA 2.2 C: Auxiliary power
• With integrated 3-phase LRM present, LCD illuminated
A2 Operating voltage not present
test socket for phase com-
For WEGA 2.2 C: Auxiliary power not
parison present, LCD not illuminated
• With two integrated signal- A3 Failure in phase L1,
ing relays (auxiliary power operating voltage at L2 and L3
required *) ). For WEGA 2.2 C: Auxiliary power
present, LCD illuminated
A4 Voltage present,
L1 current monitoring of coupling
HA35-2537a eps
54 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Indicating and measuring equipment
Verification of correct
terminal-phase connections Phase comparison test units according to IEC 61243-5 or VDE 0682-415
• Verification of correct termi-
R-HA41-EPV.eps
R-HA41-ORION-3-1.tif
nal-phase connections possible
by means of a phase comparison
test unit (can be ordered
separately)
• Safe-to-touch handling of
the phase comparison test unit
by inserting it into the capaci-
tive taps (socket pairs) of the
switchgear.
R-HA41-ORION-M-1.tif
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 55
Components
Indicating and measuring equipment
R-HA41-EARTH-ZERO.psd
be equipped with short-circuit or earth-fault indicators in
different designs. The equipment features are shown in the
table on page 57.
Short-circuit and earth-fault indicators reduce the
downtimes of a power system by delimiting the fault
locations in medium-voltage systems.
R-HA40-146.tif
EARTH ZERO
R-HA41-ALPHA-E.psd
Ring-main unit
Short-circuit indicator has picked up
Short-circuit indicator has not picked up
Response of protection device with tripping
ALPHA E
Short-circuit/earth-fault indicators can be used in all kinds of
power systems. In impedance-earthed and solidly earthed
systems, as well as in isolated and compensated (resonant-
earthed) systems, earth-fault detection is also possible.
R-HA41-SIGMA-2.psd
56 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Indicating and measuring equipment
ComPass Bs 2.0
Short-circuit /
ComPass A 2.0
ComPass B 2.0
EarthZeroFlag
SIGMA F+E 2.0
earth-fault indicators
SIGMA D++
Earth Zero-
SIGMA 2.0
SIGMA D+
Horstmann
ALPHA M
SIGMA D
ALPHA E
Function
Short circuit / earth fault / / / / / / / / / / –/
Direction indication – – – – – –
Monitoring: U, I, f, P, Q, S, E, cos ϕ,
– – – – – – – –
load flow direction
Control of a CB or SD – – – – – – – – – –
Logic – – – – – – – – – –
Applicable for the following neutral treatments
Impedance earthed
Solidly earthed
Isolated –
Compensated –
Short-circuit pickup values
400, 600, 200, 300, 400, 600, DIP: 200, 300, 400, 600, 800,
I>> Short-circuit current 800, 800, 1000, 2000 A, 2000 A, self-adjustment 20 – 2000 A –
1000 A self-adjustment Software (SW): 50 – 2000 A
40, 80, 200, DIP: 40, 80 ms, –
tI>> Pickup delay 100 ms 40, 80 ms 40 ms – 60 s
300 ms Software (SW): 40 ms – 60 s
Reset
Manually / from remote / – (M)
/ / / / / / / / / /–
/ (E)
Auto. time reset (E)
Current / voltage recovery – – – /– / / / /– / / –/
Test
Manually / from remote /– / / / / / / / /–
Communication
Relay contact 1 1 2 3 4 4 4 4 4 4 1
Maintained/passing contact adjustable adjustable adjustable adjustable adjustable
RS485 / MODBUS-RTU – – – – – – – –
USB connection – – – –
Parameterizing
Manually / from remote /– /– /– /– /– /– /– / / / /–
Supply
Lithium cell, ≥ 20 years (E) /Capacitor (AC / DC)
Current-transformer operated (not IET>) – – –
External auxiliary voltage 24 – 230 V
24 V AC, 24 – 230 V
24 – 230 V AC / DC AC / DC 24 – 230 V
– – 24 – 60 V DC AC / DC –
(only AC / DC versions) (SIGMA F+E3 AC / DC
(possible) (for IET>)
2.0 optional)
Binary inputs
Number 2 2 2 2 2 2 2 2 2 6 –
Current inputs
Phase current 3 3 3 3 3 3 3 3 3 or 2 0
Summation current 0 0 0 0 0 0 or 1 0 or 1 0 0 or 1 1
Voltage inputs
Capacitive – – – – – –
Resistive – – – – – – – – –
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 57
Components
Indicating and measuring equipment
R-HA41-IKI-20.tif
be equipped with short-circuit or earth-fault indicators in
different designs. The equipment features are shown in
the table on page 59.
The three most common types of faults in medium-voltage
systems are earth faults in cables and switchgear, faults and
overloads of distribution transformers, as well as short
circuits in cables and switchgear. For fast fault location and
minimization of downtimes, electronic fault indicators are IKI-20
used:
• Selective fault detection, and thus minimization of
downtimes
• Reliable fault detection through electronic measured-
R-HA41-IKI-20CPULS.tif
value acquisition
• Remote indication of fault events and measured values.
Short-circuit and short-circuit-to-earth indicator IKI-20
– Universally adjustable
– Current-transformer supported battery version or
auxiliary voltage versions available
– Extended commissioning and testing functions. IKI-20CPULS
Short-circuit and earth-fault indicator IKI-20PULS
– Short-circuit detection same as IKI-20
– Earth-fault detection via pulse location in compensated
R-HA41-IKI-22.tif
systems.
Short-circuit and earth-fault indicator IKI-20C(PULS)
– Current-transformer operated (No battery, no auxiliary
voltage)
– Optionally with pulse location for earth-fault detection
in compensated systems.
Directional short-circuit and earth-fault indicator IKI-22 IKI-22
– Directional fault detection for all system types
– Directional detection combined with the voltage
detecting system CAPDIS-Sx+.
Grid-Inspector IKI-50
R-HA41-IKI-50.tif
flow total
– Directional detection combined with resistor dividers
(accuracy 1.0 %)
– Early fault detection and detection of intermittent
earth faults
– Telecontrol interface according to IEC 60870-5-104.
Short-circuit-to-earth indicator IKI-10light
– Earth-fault detection in systems with impedance- IKI-10light
earthed neutral or temporarily impedance-earthed
neutral
– Adjustable.
58 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Indicating and measuring equipment
IKI-10-light-P
IKI-20CPULS
50_2F_EW_
50_1F_EW_
IKI-20PULS
IKI-50_2F
IKI-50_1F
IKI-20U
IKI-20C
IKI-20B
Short-circuit /
IKI-20T
IKI-22
PULS
PULS
IKI-
IKI-
earth-fault indicators
Kries
Function
Short-circuit indication
Earth-fault indication
Short-circuit-to-earth
indication 5)
Direction indication
Solid
Isolated
Compensated
Pickup current
Short-circuit current 100, 200, 400, 600, 800, 400, 600, 100, 200, 300, 400, 100 ... 1000 A (steps of 100 A)
1000, 2000 A 800, 1000 A 600, 800, 1000, 2000 A
Earth-fault current Transient fault detection 4 ... 30 A (steps of 1 A)
Short-circuit-to-earth 20, 40,
40, 80, 100, 150 A 40, 80, 100, 200 A 40 ... 200 A (steps of 10 A)
current 5) 60, 80 A
Pulse location
Pickup time
Short-circuit current 60, 80, 150, 200 ms 100 ms 60, 80, 150, 200 ms 60 – 1600 ms
Short-circuit-to-earth 70,
60, 80, 150, 200 ms 100 ms 60, 80, 150, 200 ms 60 – 1600 ms
current 5) 250 ms
Earth-fault current Pulse Pulse
Transient fault detection 400 – 3000 ms
location location
Reset
Manual
Automatic
From remote
Remote indication
Passing contact adjustable adjustable
Maintained contact adjustable adjustable
Interface
RS485 / MODBUS
Power supply
Lithium battery
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 59
Components
On request: Indicating and measuring equipment
R-HA41-SICAM-FCM.tif
Earth-fault indication
Earth-fault function
(impedance-earthed system)
Indication of direction,
–
short-circuit / earth-fault
Undervoltage and
– SICAM FCM
overvoltage indication
Applicable for the following neutral earthing options
Impedance
Solid SICAM FCM
Isolated The short-circuit and earth-fault indicator SICAM FCM
Compensated (Feeder Condition Monitor) with direction indication
Pickup current enables fast and precise fault location, thus reducing
Type 1: 200 – 1200 A, the downtimes in the power system. The possibility to
50 … 2000 A
Short-circuit current Type 2: 200 – 800 A determine and telecommunicate the values U, I, f, P, Q, S,
(steps of 1 A)
(in 7 steps each) E, cos ϕ and load flow direction supports efficient opera-
Type 1: 10 – 100 A, tional management and network planning.
1 … 1000 A
Earth-fault current Type 2: 40 – 300 A
(steps of 1 A)
(in 7 steps each)
• Usable in earthed, isolated and resonance-earthed systems
Pulse location – – • Directional short-circuit and earth-fault detection
Pickup time • Selective fault information with direction indication as a
40 ms basis for “self-healing” applications
Short-circuit current < 500 ms adjustable
< t < 60 s • Usable with current and voltage sensors according to
40 ms IEC 60044 for precise measurement without calibration
Earth-fault current < 500 ms adjustable
< t < 60 s
and adjustment to the primary values
Reset
Manual
• Alternatively usable with an integrated capacitive
Automatic
voltage detecting system
From remote • Flexible earth-current detection as from 0.4 A
Remote indication • Integrated MODBUS-RTU interface:
Passing contact adjustable – • Remote parameterization via SICAM A8000 and MODBUS
Maintained contact adjustable 2 binary outputs • Self-test function of the communication connection.
Interface
RS485 / MODBUS – SICAM FPI (Fault Passage Indicator)
Power supply • Detection of short circuits and earth faults
Lithium battery • Indication of phase and earth faults via 4 separate LEDs
External auxiliary voltage – • Enhanced diagnostics, self and sensor cable diagnostics
Current inputs is supported
Phase current 3 (2) 1) 3 optical
• Configurable binary outputs, for remote indication to
Summation current 0 (1) 1) 1 optical
SCADA via RTU for faults and for diagnostics.
Voltage inputs
Via resistor divider 3 –
Relay outputs
Potential-free 2 2) 2
Binary inputs
Number 1 –
SICAM FPI
60 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Transformer monitor system, time-fuse-link protection system
/ / /
– Externally undelayed instantaneous tripping 7ULSSLQJFRLO
• Self-test function
• Indication
– LED indication for tripping (single flash: starting;
double flash: tripping)
a
– Reset after 2 h or automatically (after return of power) a
%8/
²
)XVH
)XVH
/
/
/
6 6 6
• Input
– Remote tripping signal
– Instantaneous tripping.
Circuit diagram of the time fuse link
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 61
Components
Intelligent transformer substation
5
R-HA40-151a.psd
62 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Intelligent transformer substation
Components Function
1
Uninterruptible power supply (UPS) The task of the UPS is to continue to
Depending on the requested bridging time ensure the communication and / or the
in case of power failures, an uninterrupt- possibility to telecontrol the transformer
ible power supply based on battery or substation in case of power failure.
capacitor modules is used.
4
Current sensors The current signal serves to detect
Current sensors with low-power trans- short-circuits and ground faults, and can
former technology are available as closed be used as a measured value for load flow
or divisible ring cores. control or for optimal utilization of the
grid capacity.
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 63
Components
Protection systems
LSP 2339-afp.tif
– Siemens SIPROTEC 7SJ46
• Instrument transformer as
– Cable-type current transformer (standard)
– Three-phase current transformer as option for
8DJH switchgear panels L(500). SIPROTEC 7SJ45
Mounting location
• In 200-mm-high top low-voltage unit (option) of the
circuit-breaker feeder.
Application of simple protection systems
Operating Transformer rating (kVA)
voltage (kV) 7SJ45 / 7SJ46 WIC 1-2P
6 ≥ 160 ≥ 160
10 ≥ 200 ≥ 250
13.8 ≥ 250 ≥ 400
15 ≥ 315 ≥ 400
20 ≥ 400 ≥ 500
LSP 2874-afp.eps
64 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Components
Low-voltage compartment, low-voltage niche
Features
• Overall heights Low-voltage compartment (example 500 × 600 mm)
– 200 mm, 400 mm, 600 mm, 900 mm
– Option: Cover
R-HA40-128.eps
• Partitioned safe-to-touch from the high-voltage part
of the panel
• Installation on the panel:
– Possible per feeder
– Standard for circuit-breaker panels type L (1.1) and
bus sectionalizer panels with circuit-breaker type V (1.1)
– Option for all other panel types, depending on the
scope of the secondary equipment
• Customer-specific equipment
For accommodation of protection, control, measuring
and metering equipment
• Separate wiring duct on the switchgear beside the
low-voltage compartment (option)
• Door with hinge on the left (standard for heights
Open low-voltage compartment
of 400, 600 and 900 mm). with built-in equipment (option)
Low-voltage cables
• Control cables of the panel to the low-voltage compart-
ment via multi-pole, coded module plug connectors
• Option: Plug-in bus wires from panel to panel in the
separate wiring duct on the panel.
Low-voltage niche
• Only inside billing metering panels type M Low-voltage niche
• For accommodation of options, e.g.:
– Voltage transformer m.c.b.s
– Small distribution fuse-box and fuse-links type Diazed
or Neozed. 1
2
R-HA41-042a.eps
1 Low-voltage niche
2 Built-in equipment (option)
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 65
Dimensions
Room planning
Switchgear installation
³15
HA40-2101a eps
Wall-standing arrangement
– 1 row
775
– 2 rows (for face-to-face arrangement)
Option: Free-standing arrangement.
Pressure relief ³50 ³200*
³800**
The type of pressure relief selected has an effect on the
switchgear depth, and places requirements on the size of the
cable basement and / or the room height. In case of pressure
relief upwards, the room heights reproduced in the type
test are decisive for the internal arc classification acc. to
IEC / EN 62271-200 / VDE 0671-200 (see table on page 67). Top view: Switchgear without pressure relief duct at the rear
Door dimensions
*) For lined up switchgear
The door dimensions have an influence on the size of the
**) Depending on national requirements
transport units (see page 87) and the factory assembly of For extension or panel replacement, a control aisle
panel groups, low-voltage compartments and pressure of at least 1000 mm is recommended
absorber systems. If required, this installation work can
also be performed on site by the customer.
³15
HA40-2107 eps
Switchgear fixing
• For floor openings and fixing points of the switchgear,
see pages 83 to 86
890
775
• Foundations:
– Steel girder construction
– Reinforced-concrete floor. ³50 ³200*
Panel dimensions
See illustrations on pages 69 to 86.
Top view: Switchgear with pressure relief duct at the rear
Weight
For data, see page 88.
Local regulations and guidelines
HA40-2171a eps
HA40-2170a eps
HA40-2169a eps
2600
2300
2300
2100
2000
1900
1800
1700
1600
1400
1400
1200
66 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Dimensions
Room planning
The following type-tested versions of the pressure relief • Upwards through rear pressure relief duct (for extend-
system are available for 8DJH switchgear: able and non-extendable panel blocks, internal arc classi-
• Downwards into the cable basement (for individual panels fication up to IAC A FL 16 kA /1 s, minimum room heights
and panel blocks, internal arc classification up to according to the table below), with pressure absorber
IAC A FL 21 kA /1 s or IAC A FLR 21 kA /1 s, minimum system
cross-section of the cable basement according to the • Upwards through base and rear pressure relief duct (for
illustration below) individual panels and panel blocks, internal arc classifi -
• To the rear (for non-extendable panel blocks with 1400 cation up to IAC A FL 21 kA / 1 s and IAC A FLR 21 kA / 1 s,
or 1700 mm switchgear height, internal arc classifi cation minimum room heights according to the table below),
up to IAC A FL 21 kA / 1 s, a rear pressure relief outlet with pressure absorber system.
with a minimum cross-section of 1 m2 is required in the
switchgear room and must be supplied by the site)
HA40-2103b eps
1 4
Room heights for switchgear
installation with pressure relief duct
1 at the rear (design with or without base)
600É8001)
3
Side view Switchgear height Room height
2 1400 mm ≥ 2000 mm
1700, 1800 mm ≥ 2200 mm
2300 mm ≥ 2400 mm
600 É 8001) 2600 mm ≥ 2600 mm
Side view
Switchgear installation with rear pressure Switchgear installation with base and rear pressure
relief duct (option) for panel block relief duct (option) for panel block
with IAC A FL or FLR up to 16 kA / 1 s with IAC A FL or FLR up to 21 kA / 1 s
HA40-2104b eps
HA40-2276a eps
HA40-2106d eps
2 2 2
2300
1400
1800
1700
4 5 5
4 4
775 1
³15 880
775 1 775 1
Side view ³15 890 ³15 890
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 67
Dimensions
Room planning
For 8DJH Compact, the following types of pressure relief For 8DJH with outdoor enclosure (option), the direction of
can be selected: the pressure relief can be selected as follows:
• Downwards into the cable basement for all feeders • Downwards into the cable basement (internal arc
(internal arc classification up to IAC A FL or FLR 21 kA /1 s) classification up to IAC A FL or FLR 21 kA /1 s, minimum
• Downwards into the cable basement for the ring-main cross-section of the cable basement according to the
feeders, and to the rear for the transformer feeders illustration below)
(internal arc classification up to IAC A F 21 kA /1 s). • To the rear (internal arc classification up to
The dimensions for wall distances, control aisles and cable IAC A FL 21 kA /1 s; for wall-standing arrangement, a rear
basements correspond to those of the 8DJH Standard pressure relief outlet with a minimum cross-section of
design. The pressure relief to the rear was tested with a 1 m2 is required and must be supplied by the site)
rear wall distance of ≥ 3 m. This design is recommended • Upwards through rear pressure relief duct (internal arc
for application in prefabricated substations without control classification up to IAC A FL or FLR 21 kA / 1 s, free space
aisle, with internal arcing test according to IEC 62271-202. above the switchgear 600 mm as a minimum).
The dimensions for wall distances, control aisles and cable
basements correspond to those of the 8DJH Standard de-
sign. The outdoor enclosure is conceived for application on
company ground.
Switchgear installation for 8DJH Compact Switchgear installation for 8DJH Compact with
with pressure relief downwards for all feeders pressure relief downwards for the ring-main
(standard) feeders, and to the rear for the transformer
feeders (option)
HA40-2368 eps
HA40-2369 eps
1700
600É8001)
600É8001)
Switchgear installation for outdoor enclosure Switchgear installation for outdoor enclosure
with pressure relief downwards with pressure relief to the rear or upwards
through rear duct
HA40-2370 eps
HA40-2371 eps
2
HA40-2372a eps
1 Floor opening 6 5
2 Direction of pressure relief 2
1
500
3
4 Floor cover (divided plate for 1 1
2 comfortable working at the
cable connection)
5 Pressure absorber system
with pressure relief duct
600 É 8001)
68 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Dimensions
Feeder panels (310 mm)
HA40-2173b eps
C1)
C1)
60
60
B1)
B1)
A
554
A
D 554
D
E
E
3002)
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 69
Dimensions
Feeder panels (430 mm)
HA40-2174c eps
HA40-2186c eps
C1)
C1)
60
60
B1)
B1)
A
434
A
554 D
D
E
E
3002)
3002)
C1)
60
B1)
554
D
E
3002)
430 775
1) Option: With low-voltage compartment 3) Only for panel blocks RR, RRR, RT, RRT and RTR
2) Base for switchgear height of 1700 mm, or
absorber --> cable connection height = D + 300 mm
70 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Dimensions
Feeder panels (500 mm)
HA40-2176f eps
HA40-2187e eps
C1)
C1)
60
60
B1)
B1)
A
A
369 369
D
D
E
E
3002)
3002)
60
HA40-2179c eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 71
Dimensions
Bus sectionalizer panels with switch-disconnector
HA40-2373 eps
HA40-2180c eps
C1)
C1)
60
60
B1)
B1)
A
A
E
E
3002)
3002)
C1)
C1)
60
60
B1)
B1)
A
A
E
E
3002)
3002)
72 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Dimensions
Bus sectionalizer panel with circuit-breaker
C1)
60
B1)
E
3002)
500 775
Design options
with busbar voltage transformer and / or
busbar current transformer
1)
C
60
HA40-2183c eps
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 73
Dimensions
Busbar earthing panels and busbar voltage metering panels
HA40-2185d eps
HA40-2184c eps
C1)
C1)
60
60
B1)
B1)
A
E
E
3002)
HA40-2275b eps
C1)
C1)
60
60
B1)
B1)
A
A
D
E
E
3002)
3002)
74 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Dimensions
Billing metering panel as individual panel, air-insulated
HA40-2209e eps
HA40-2208d eps
C1)
C1)
60
60
B1)
B1)
A
A
D
250 250 250 250
840 775 840 775
Connection: busbar – busbar Connection: busbar on the left – cable on the right
HA40-2210f eps
HA40-2211e eps
C1)
C1)
60
60
B1)
B1)
A
A
D
Connection: cable – cable Connection: cable on the left – busbar on the right
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 75
Dimensions
Panel blocks (preferred versions)
HA40-2190 eps
HA40-2188 eps
HA40-2193 eps
R R T R R R T T R R T
310 310 430 310 310 310 430 430 310 310 430
76 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Dimensions
Panel blocks (preferred versions)
HA40-2214b eps
HA40-2195 eps
HA40-2194 eps
K L K (E) L R L
HA40-2198 eps
HA40-2196 eps
R R L R R R L L R R L
310 310 430 310 310 310 430 430 310 310 430
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 77
Dimensions
Panel blocks (preferred versions)
Further versions
HA40-2201 eps
HA40-2200 eps
HA40-2199 eps
R R R R R R R R R
620 860
HA40-2203 eps
HA40-2202 eps
R K T T
78 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Dimensions
Panel blocks (8DJH Compact)
HA40-2374 eps
A1
D2
D3
A1
A1
A2
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 79
Dimensions
Panel blocks (freely configuarable)
Examples
1480 1050
HA40-2204a eps
HA40-2272 eps
R R L L L R R
1480 1050
HA40-2206a eps
HA40-2207 eps
R T T R R T R
80 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Dimensions
Panel combinations with billing metering panels (examples)
2320
HA40-2220b eps
R R S M T
2390
HA40-2221b eps
R R V M T
2320
HA40-2222b eps
R R L M T
Transfer with circuit-breaker in the panel block and cable connection (RRL-M-T...)
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 81
Dimensions
Outdoor enclosure
HA40-2378 eps
E
955
HA40-2377 eps
HA40-2196 eps
HA40-2196 eps
HA40-2196 eps
C
B
A
D
667
1070 821
1380
1740 Outdoor enclosure with pressure relief
2020 downwards or to the rear
HA40-2379 eps
downwards or to the rear E
75 955
C
B
D
667
821
871
82 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Dimensions
Floor openings and fixing points
Individual panels
310
40 230 64
610
465 10
HA40-2228a eps
653
699
155
291
19
430
40 350
64
610
10
• For bus sectionalizer panel type S with switch-disconnector
465
• For bus sectionalizer panel type H
HA40-2229b eps
653
699 with switch-disconnector / fuse combination
• For busbar voltage metering panel type M(430)
19
215
411
500
40 420
64
610
653
699 • For busbar voltage metering panel type M(500)
19
250
481
840
40 760
420
³ 15
64
610
465
653
HA40-2231 eps
699
155
19
364
476
685
821
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 83
Dimensions
Floor openings and fixing points
1050 1240
620 Panel Width 930 Panel Width
40 540 block mm 40 850 block mm
64
64
type type
36 36
102 RR 102 RRR 930
223 RK 620 223 RRRR 1240
319 319
714
714
610
610
KR
465 10 465 10
RRT
HA40-2232b eps
1050
HA40-2234a eps
653 653
699 RRL 699
1031
19
155
292
465
602
835
1221
1085
19
155
292
465
602
775
912
1050
740 Panel Width 1360
40 660 block mm 40 1280 Panel Width
64
type
64
block mm
36 36 type
102 RT 102
223 RL 740 223 RRRT
1360
319 319
714
714
610
RRRL
610
KT
465 10 465 10
KL
HA40-2235b eps
HA40-2233b eps
653 653
699 RTR 1050 699
RLR
1031
19
155
292
525
722
895
1341
1145
19
155
292
465
602
775
912
1480
1050 Panel block Width
740 type mm
40 660
TK
64
740
36 LK
102
TR
223
319 LR
714
610
465 10 TRRT
1480
HA40-2237b eps
653 LRRL
699
1461
1265
1032
19
215
412
585
722
895
1720
1290 Panel block Width
860 type mm
40 780
K(E)T
64
36 K(E)L
102 860
TT
223
319 LL
714
610
465 10 TTT
1290
HA40-2236b eps
653 LLL
699
TTTT
1720
1701
1272
1505
1075
19
215
412
645
842
LLLL
84 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Dimensions
Floor openings and fixing points
Panel blocks 8DJH Compact (design option with pressure relief downwards)
52
52
52
33 33 33
99 99 99
220 220 220
315 315 315
734
734
734
642
642
642
462 462 462
10 10 10
650 650 650
HA40-2382a eps
HA40-2380a eps
HA40-2381a eps
99
235
372
545
682
719
855
991
1165
1301
99
235
372
545
682
99
235
372
545
682
719
855
991
Panel block RRT Compact Panel block RRT-R Compact Panel block RRT-RRT Compact
64
64
64
36 36 36
102 102 102
223 223 223
610 / 635*
819
715
860
964
10 10 10
HA40-2280d eps
19 19 752
804
19 19 902
949
19 19
Example:
Position of floor openings and fixing points for double cable connection
for panel blocks
1050 1050
40 970 40 970
64
64
36 36
102 102
223 223
319 319
714
714
610
610
819
964
465 465
10 10
653 653
752 752
HA40-2246a eps
804
HA40-2247b eps
902
949
1031
19
155
292
330
465
602
835
1031
19
155
292
330
465
602
835
* 610 mm for single cable connection; 635 mm for double cable connection with coupling T-plug
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 85
Dimensions
Floor openings and fixing points
Versions in connection with base and rear pressure relief duct for switchgear
with IAC A FL or FLR up to 21 kA / 1 s and deep cable compartment covers**
115
115
151 151 151
type R
217 217 217
• For cable panel type K
550
550
550
934
with make-proof
1079
580 580 580
(225)*
10 10
HA40-2284c eps
200
10 earthing switch
305
HA40-2285c eps
768
450
768 768
814 • For circuit-breaker panel
867 867
HA40-2286c eps
19 19 919 type L
19 19 1017
1064
19 19
Deep cable compartment cover:
Without With base extension
(floor opening depending on selected cable connection / arrester)
Deeper by 105 mm Deeper by 250 mm
430
40 310 / 430 / 500
40
• For transformer panel • For panels
115
115
151
430
434 338
829
434
320
580 10
HA40-2251c eps
580
HA40-2290b eps
768
814 768
19 19 814
19 19
500 500
40 40
115
365
217 217
338 338
829
434 434
934
385
580 580
490
HA40-2287c eps
HA40-2288c eps
768 768
814
19 19 919
19 19
840
40 760
151
217
210
550
338
829
434
425
580
200
HA40-2289c eps
768
814
19
155
364
476
685
821
* 200 mm for single cable connection; 225 mm for double cable connection with coupling T-plug
** In versions with rear pressure relief duct for panel block with IAC A FL or FLR
up to 16 kA / 1 s, the depth is reduced by 10 mm.
For wall-standing arrangement, a wall distance of ≥15 mm must be provided.
86 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Installation
Shipping data, transport
HA40-2238 eps
with wooden base
Pallet
Type: Seaworthy crate (for open-top container)
Welded PE protective foil, with closed wooden crate,
with desiccant bag Crane transport with Pallet
Airfreight Type: Open
PE protective foil pulled over the switchgear,
with wooden base and lattice or cardboard cover Crane hook
HA40-2239 eps
• Transport dimensions and weights
• Size of door openings in building
• Switchgear with low-voltage compartment: Please ob-
serve other transport dimensions and weights. Crane transport with rod
Transport dimensions
HA40-2011b eps
TE
B
(top view)
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 87
Installation
Shipping data, transport
Transport weights Panel block Width Gross weight for switchgear height
The transport weight results from the switchgear weight per without LV compartment
transport unit and the packing weight. The packing weight 1200 mm 1400 mm 1700 mm
results from the transport dimensions and the type of trans- mm approx. kg approx. kg approx. kg
port. 2 panels
88 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Standards
Standards, specifications, guidelines
HA40-2037c en eps
the altitude cor- m=1
gear with rated values of short-duration power-frequency
Altitude correction factor
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 89
Standards
Standards, specifications, guidelines
90 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Standards
Standards, specifications, guidelines
IP 6 5
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017 91
Published by
Siemens AG 2017
Energy Management
Medium Voltage & Systems
Mozartstraße 31 C
91052 Erlangen, Germany
For further information please contact
our Customer Support Center
Phone: +49 180 524 70 00
Fax: +49 180 524 24 71
E-mail: support.energy@siemens.com
siemens.com / medium-voltage-switchgear
siemens.com / 8DJH
Article No. EMMS-K1440-A211-A6-7600
Printed in Germany
Dispo 40401
PU 002806 KG 07.17 1.0
Subject to changes and errors. The information
given in this document only contains general
descriptions and/or performance features which
may not always specifically reflect those described,
or which may undergo modification in the course
of further development of the products.
The requested performance features are binding
only when they are expressly agreed upon in the
concluded contract.