Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Arabian Journal for Science and Engineering (2022) 47:14695–14710

https://doi.org/10.1007/s13369-022-06774-w

RESEARCH ARTICLE-ELECTRICAL ENGINEERING

The Impact of Electrical Traction Drives on Power System Quality


under Different Loading Conditions
Ammar Mishal Elagab1 · Ibrahim M. El-Amin1

Received: 14 July 2021 / Accepted: 1 March 2022 / Published online: 9 June 2022
© King Fahd University of Petroleum & Minerals 2022

Abstract
Modern societies and cities require a fast and reliable transportations system. Electrical tractions or trains are now the
predominant mass transportation throughout the world. However, they impose several power quality problems on the utility
grid. This paper is dedicated to quantifying and assessing the impact of electrical traction on power quality. MATLAB/Simulink
is used to design a dynamic model of the traction system. The model has considered the different dynamic modes, which are
acceleration, cruising and deceleration modes. In order to assess the impact of the electrical traction system on the power
system, two different loading conditions of the train (light and heavy load) are considered. The results showed that the electric
train has affected the power system negatively. This is manifested during the acceleration and deceleration stages of the train’s
journey. The total harmonic distortions of the voltage (THDv) and current (THDi) during these two modes were 8.35% and
9.64%, respectively, and the THDv has not been affected with the loading condition. However, the THDi has been increased
to 21.33%. The THDv and THDi increase as the voltage level decreases. Thus, the maximum distortions in the voltage and
current waves occur at the load (1.06 kV) side which are 15.14% and 32%, respectively, while they reach their minimum
values at the utility grid (110 kV) side to be 8.31% and 21.33%, respectively. These are the values when the train is heavily
loaded. However, both THDv and THDi have the same trend in the light load condition. A corrective action is taken by
designing an active power filter. The individual and total harmonic distortion (THD) is reduced significantly, the power factor
(Pf) has been improved from 0.75 to 0.95, and thereby, the total reactive power consumption and the absorbed current from
the utility side have been reduced by 30% as well. To validate the model, real data for metro system are implemented for the
same model. The results were consistent with the previous ones.

Keywords Electric train · Power quality · Negative sequence components · Harmonics · Dynamic model · Active power filter

1 Introduction is used for short distances, while the AC train is used for long
distances. In the past, in order to maintain a constant voltage
Electric transportation has acquired and maintained a strong level throughout the railway track, substations were located
presence in modern transportation societies. It is the preferred every three or four kilometers. However, nowadays the volt-
option due to the high performance, low maintenance cost age is transmitted at high values and then stepped down to
and lack of greenhouse gas emissions [1]. There are two types low rating. Substations could thus be laid every 20 km [5–10].
of electric trains: AC and DC. Usually, high-speed electric Electric trains are playing an important role in people’s
trains are fed by AC power supply, while underground trains life. However, they may have a negative impact on the power
are operated with DC supply [2–4]. Generally, the DC train system. They may cause problems in the public utility grid
such as injecting a large negative sequence components
Life Senior Member, IEEE. (NSCs), generating undesirable harmonics, reducing the Pf,
causing additional system losses, causing malfunction of pro-
B Ammar Mishal Elagab
ammar.elagab@kfupm.edu.sa tection relays and measuring instruments and overheating the
Ibrahim M. El-Amin
rotating machine [11, 12]. The situation is aggravated fur-
imelamin@kfupm.edu.sa ther if DC series motors are used in the electric locomotives.
Series DC motors draw a large amount of current at start-
1 Electrical Engineering Department King Fahd, University of ing. This is magnified when several locomotives run from
Petroleum & Minerals, Dhahran 31261, Saudi Arabia

123
14696 Arabian Journal for Science and Engineering (2022) 47:14695–14710

the same section of the overhead system at the same time important part, which the dynamic features of the traction
[13–17]. In addition, the electric train is a dynamic load as it system. This is essential part and has severe negative impact
moves at different speeds and changes its position continu- on power system quality.
ously. The power demands for the electric train vary with the
time, and it is influenced by the operating conditions, such
as accelerating, running with a constant speed and braking 2 Modeling of the Traction System
when it becomes close to the station. It is also a function of the
railroad profile due to ascent and descent grades, curvature In this paper, SIMULINK/MATLAB software is used to
radius and rolling resistance, as well as the weight of the train model the dynamic load of an electric train including all
[18–22]. Moreover, the train travels with different speeds in components and control accessories. The model has taken
every section in order to stay within the railway’s tracks. into consideration all the stages for a real electrical train
Thus, the supply current varies continuously with the time movement, which are accelerating, cruising and decelerat-
[23, 24]. Harmonics is the one of the most severe problems ing modes. The model of the train is built based on the basic
that appear in the power system due to integrating an electri- dynamic equations of movement.
cal traction load with a utility grid. The level of harmonics
is getting more with the change of the train’s speed during 2.1 Formulation of the Mathematical Description
the journey. In addition, harmonics could be increased due to of the Mechanical System
the friction at the contact point between the pantograph col-
lector and OCS [25–28]. This paper is dedicated to quantify The planetary gear block represents a set of carrier, ring,
and assess the impact of electrical traction on power quality. planet and sun gear wheels. A planetary gear set is developed
In addition, due to the nonlinearity nature of the electrical from planet–planet and ring–planet gears. The ring and sun
traction load, a large amount of reactive power is consumed coronate with a fixed gear ratio and in opposite directions
and dissipated in particular in the AC traction systems. This with respect to the carrier. To model the planet’s rotational
occurs because they are equipped with induction motors. inertia, the inertia block has been integrated with a planet
In addition to that, modern adjustable speed drives (ASDs) connector port.
absorb a considerable level of reactive power [29–32]. More- The planetary gear block imposes two geometric and two
over, the existence of asymmetrical load in the three-phase kinetic constraints on the three connected axes and the fourth,
network causes excessive reactive power consumption [33]. internal wheel (planet) as described in Eqs. (1) and (2).
The general objective of this paper is to study the impact
of electrical traction on power system through modeling and rc ωc = rs ωs + r p ω p , rc = rs + r p (1)
simulation. The specific objectives can be summarized as
follows:
r R ω R = rc ωc + r p ω p , r R = rc + r p (2)
• Develop a model for the dynamic load of an electrical
where rc The teeth number of carrier gear, r R The teeth num-
traction including all components and control accessories.
ber of the ring gear, r S The teeth number of the sun gear, r p
The model must take into consideration accelerating time,
The teeth number of planet gear, ωc The speed of carrier gear,
cruising time and deceleration time.
ω R The speed of ring gear, ω S The speed of sun gear, ω p The
• Simulate and study the operation of the electrical traction
speed of planet gear.
by using the developed model on a power network under
In terms of the ring-to-sun gear ratio, g R S = rrRs , the key
different operating conditions of light and heavy load.
effective kinematic constraint is given by Eq. (3).
• Adding an active filter scheme to reduce the negative
impact of the electric train and thereby improving power
(1 + g R S )ωc = ωs + g R S .ω R (3)
system quality.
• Test the model with real system data.
The four degrees of freedom are reduced to two indepen-
dent degrees of freedom. The gear ratio is also the ratio of
The paper is different from the previous ones because most
the number of teeth on each gear and the ratio of the torques
of the simulation models for the traction systems have not
in each axis. Equations ((4) to (11)) describe the dynamics
considered all the expected conditions of the train. These con-
of the electric train.
ditions are the acceleration, cruising and deceleration modes.
They have discussed the power quality issues related to the NR TR
power electronics elements. They also discussed the volt- gRS = = (4)
NS TS
age unbalance problem, which caused by the single-phase
traction motors. Nevertheless, they have neglected the most where

123
Arabian Journal for Science and Engineering (2022) 47:14695–14710 14697

g R S The gear ratio, N R The speed of the ring gear, Ns The


speed of the sun gear, TR The torque of the ring gear, TR The
torque of the sun gear.

J R ω̇w = G r Tm − TL (5)

where J R Rotary inertia moment around the wheel axis,


ω̇w Driving wheel angular acceleration, Tm Mechanical gear
ratio, TL Load torque.

TL
M V̇T = − Fext (6)
r

where M Translational body mass per one axle, V̇T Longi- Fig. 1 Simulink model of the electrical train
tudinal traction acceleration, r The radius of a gearbox, Fext
The radius of a gearbox.

V22 + V32 + V42 + V52 + · · · + Vn2
vs = r ω̇w − vb (7) T H Dv = (13)
V1
where vs Slip speed, ω̇w Driving angular acceleration, VT 
Longitudinal train speed. I22 + I32 + I42 + I52 + . . . +I 2n
T H Di = . (14)
I1
1
JR = MRr 2 (8)
4 An accelerator signal has been used to control the time of
the train movement starting with acceleration mode, cruising
where M R Equivalent translational inertia.
mode and deceleration mode.
J = Mr 2 (9)
2.2 Simulink Model
where M Translational body mass.
The MATLAB/Simulink model consists of four main parts as
    shown in Fig. 1. Each part has been represented by a separate
1 JR jR
a= G r Tm − 1 + TL + r Fext . (10) block. Each block has a subsystem.
JR J J
The power management system includes two parts: the
The speed at any time is given by Eq. (11) power supply and the battery systems. It is designed to coor-
dinate the power flow between the source, the traction load
VT (t) = V0 + a ∗ T (11) and the battery system. This can be achieved by specifying
the maximum and minimum values for the power that will
where VT Train speed in km/h, V0 The initial speed is equal be stored in the batteries. In addition, a specific amount of
to zero in the, acceleration mode and has the same, value in torque and speed are determined to the point that the battery
the cruising and the deceleration, mode in km/h, a Acceler- will start to charge and discharge. The relationship between
ation rate in km/h which has, appositive a positive value in the train speed and the torque is controlled by determining
the, accelerating mode and has a negative, value in the decel- the maximum speed and torque of the train.
eration mode, but, equals zero in the cruising mode, T Time The control system block controls the dynamic of the
in an hour. train movement, the train starts by acceleration mode, then it
The traction system is analyzed based on Eqs. (1) to (11). moves with a constant speed, and then it decelerates to a com-
The equations are represented in MATLAB/Simulink. Then, plete stop. This process is accomplished through a group of
the train is connected to a three-phase power supply through gearboxes that are working together to regulate the speed of
two units of a three-phase step-down transformer and DC/DC the train and transfer smoothly between the different dynamic
converter. Equations ((12) to (14)) are used to analyze the modes of the train.
voltage and current waveforms. The converter system block is represented by a three-
phase, 12-pulse, IGBT-based multi-level converter. It is used

3 2 to convert the AC current into DC current to feed the
Vdc = Vr .m.s (12) train. Using a three-phase converter helped to overcome the
π

123
14698 Arabian Journal for Science and Engineering (2022) 47:14695–14710

unbalanced problem, which appeared in the case of using a


single-phase converter.
The control system is designed to control the power flow
between the utility grid and the train. It coordinates the torque
of the train with its speed; this is accomplished by connect-
ing a speed governor. The train runs at a variable speed that
can be controlled with a Simulink throttle signal. The throt-
tle signal directly controls the output torque that the motor
generates and indirectly controls the speed at which the train
runs. If the speed of the train exceeded the specified maxi-
mum speed, the motor does not generate any torque and vice
versa. If the speed decreases below the specified rated speed,
the motor will generate more torque. The throttle signal spec-
ifies the motor torque as a fraction of the maximum torque
possible in a steady state at a fixed motor speed and should lie
between 0 and 1. To prevent the engine’s power and torque Fig. 2 Single-line diagram of the electrical train connected to 110 kV
from becoming negative, the block imposes an upper limit substation
on the maximum train speed itself.
Some physical factors have been ignored in the modeling,
which are the friction between the train and the rail and wind 1.06 kV. A DC/DC converter provides the appropriate voltage
resistance. In addition, I assumed that no curves or slopes in of the brushless DC (BLDC) motor.
the rail and the train are launching in a straight line.

3.1 Light Load Case


3 Simulation Results
In this case, the train is assumed to be loaded by few numbers
After developing the model of the train, it has been connected of passengers. The voltage and current are measured at the
to a power supply system to assess the impact of the train utility grid side at 110 kV and 11 kV and at the AC side of
on the power system quality. The train is supplied from the the traction load, which is 1.06 kV side. The ratings of the
utility grid side through two-step down transformers. Both proposed system components are shown in Table 1.
transformers are connected delta to delta to avoid zero-phase The total period of the journey is 10 min. The train starts
sequence components that might be generated. The output of accelerating at a constant rate for 2 min. Then, the train con-
the second transformers is connected to a multi-level IGBT- tinues moving with a constant speed. This stage takes 6 min.
based rectifier; the train is connected to this rectifier through In the last stage, which is taking 2 min, the train decreases
a DC/DC converter. its speed gradually until zero. The speed of the train varies
Figure 2 shows a single-line diagram of the traction system with time. Figure 3 shows the train speed in km/h versus the
connected to a 110 kV bus system. The power supply system time in seconds.
is represented by 110 kV bus, and two transformers are used For the DC side, the output voltage of the secondary side
to step down the voltage from 110 to 11 kV and from 11 kV to of the transformer (11/1.06) KV is connected to a 24-pulse,

Table 1 the ratings of traction


system components Component Rated voltage Q (MVAR) S (MVA) P (MW) Current
(KV) (A)

Transformer (1) 110/11 – 100 – –


Transformer (2) 11/1.06 – 100 – –
IGBT-based rectifier 1.06 – – – 68,000
system
DC/DC Converter 1.43/11 – – 75 I/P
system 50,000
O/P
6555
BLDC motor 11 – – 72 –

123
Arabian Journal for Science and Engineering (2022) 47:14695–14710 14699

For the light load case, the BLDC motors are working by
50% of their full load values. Therefore, the total absorbed
current from the power supply is approximately half of the
full load current.
In order to assess the impact of electrical traction drives
on power quality, FFT is used to analyze voltage and cur-
rent waves at different locations in the system. The analysis
considered three different dynamic modes for the train: accel-
eration, cruising and deceleration modes.
Before analyzing the voltage and current waves, the IEEE
standard distortion limits are determined. The short-circuit
Fig. 3 Speed of the train in km/h versus the Time in Seconds
MVA values at 110 kV, 11 kV and 1.06 kV buses are obtained
from [34]. The short-circuit current can be calculated using
Eq. (15).

M V As/c
Is/c (K A) = √ (15)
3 ∗ V (K V )

where M V As/c Short-circuit MVA at the specific bus in


MVA, V The line–line voltage at the specific bus in KV,
The fundamental frequency is 60 HZ in all cases.
The load current at the PCC when the train is lightly loaded
is measured. It was about 266 A; according to this value, the
Fig. 4 Applied DC voltage on the train in the light load case maximum limits of the THD in the voltage and current wave-
forms at 110 kV, 11 kV and 1.06 kV sides can be determined
according to the IEEE standard distortion limits.
three-phase, IGBT-based AC/DC converter. The output volt- Table 2 shows the short-circuit data and load current
age of this converter is connected to a DC/DC converter in according to values of the IEEE 519 standard distortion lim-
order to increase the DC voltage to be compatible with the its.
rating of the traction load. The FFT has been used to analyze voltage and current
The traction load is represented by 12 brushless DC waveforms at 110 kV side, which is representing the PCC in
(BLDC) motors connected in parallel. The rated voltage for this case. These waves are analyzed based on the dynamic
these motors is 11 kV DC, with power ratings of 6 MW for operation mode of the train, and the total interval is divided
each motor at full load. Thus, the total power rating of the into three periods, accelerating, cruising and decelerating
traction system at the full load is 72 MW. period. A snapshot of the current wave when the train accel-
The output DC voltage of the rectifier is amplified from erates is shown in Fig. 5.
1430 V to 11 kV to be compatible with the rating of the BLDC The THD of the voltage and current waves can be calcu-
motors. This is accomplished by using a DC/DC converter. lated from Eqs. (13) and (14). In this case, the THD values
Figure 4 shows the converter output DC voltage. are obtained from the FFT analysis directly.
The total DC current absorbed by the train increases with Figure 6 shows the harmonic spectrum and the total har-
the speed. The current starts from zero. Then, it increases as monic distortion (THD)(THD) of the current waveform at
the speed increases. When the train moves with a constant 110 kV side when the train operates in the acceleration mode.
speed, the current remains constant. Finally, it starts declining It is clear that the dominant harmonics in the current wave-
when the train starts decelerating. form at 110 kV side are the 11th and 13th orders. These

Is/c
Table 2 Short-circuit data and
the distortion limits for the light Voltage level MVA s/c I cs (K A) I L (A) IL IEEE standard limit (%)
load case according to the IEEE
standard 519 110 kV 6955 36.5 266 137.2 7.5
11 kV 4000 210 2660 78.9 12.0
1.06 kV 2750 1500 27,603 54.3 12.0

123
14700 Arabian Journal for Science and Engineering (2022) 47:14695–14710

Fig. 5 Small section of the current wave at 110 kV side in the acceler-
Fig. 8 Harmonic spectrum and THD index of the current wave at 110 kV
ation mode when the train is lightly loaded
side in the cruising mode when the train is lightly loaded

Fig. 6 Harmonic spectrum and THD index of the current wave at 110 kV Fig. 9 The voltage wave at 110 kV in the deceleration mode when the
side in the acceleration mode when the train is lightly loaded train is lightly loaded

Fig. 7 The current wave at 110 kV side in the cruising mode when the Fig.10 Harmonic spectrum and THD index of the current wave at
train is lightly loaded 110 kV side when the train is decelerating with a light load

harmonics are almost representing 10% of the fundamental


harmonic, which exceeds the IEEE standard.
When the speed of the train reaches 100 km/h, the train
starts moving with a constant speed. In this mode, the train
absorbs constant current from the utility side. Figures 7 and
8 show a snapshot of the current waveform at 110 kV side
and the harmonics spectrum, respectively, when the train is
moving with a constant speed.
Fig.11 Small section of the voltage at 110 kV side in the acceleration
Since the THD, in this case, is less than 7.5%, it is within mode when the train is lightly loaded
the IEEE standard distortion limits.
In the last two minutes, the train starts decreasing its speed
gradually, and the current that absorbed from the source Generally, a large amount of harmonics is injected into
decreases accordingly. Figures 9 and 10 show snapshot of the PCC during the acceleration and deceleration modes,
the current at 110 kV side and the harmonics spectrum at whereas few of them are injected when the train is moving
this stage, respectively. with a constant speed.
In the deceleration mode, the THD in the current wave is The voltage of the supply system does not change with
high compared to the THD in the acceleration and cruising time. It always maintains constant magnitude during the three
modes. The 13th harmonic is the dominant one; it is about dynamic modes of the train. Figure 11 shows a small section
16% of the fundamental harmonic. of the voltage in the acceleration mode at the 110 kV side.

123
Arabian Journal for Science and Engineering (2022) 47:14695–14710 14701

Table 3 THD index in the


voltage and Current waves over Voltage level T H D v % of IEEE standard limit T H D i % of IEEE standard
the full period at the different ( kV) fundamental of T H D v (%) fundamental limit of T H D i
buses when the train is lightly (%)
loaded
110 6.05 2.5 21.21 7.5
11 11.41 5.0 29.01 12.0
1.06 14.09 5.0 32.04 12.0

Table 4 THD index in the voltage wave at the PCC (110 kV side) in the
three dynamic modes of the train with a light load

Dynamic mode T H D v % of T H D i % of
fundamental fundamental

Acceleration 8.35 18.32


Cruising 3.21 7.25
Deceleration 9.64 23.16
Fig. 12 The current at 110 kV side when the traction is heavily loaded
IEEE standard Limit 2.5% 7.50%

The voltage wave at 110 kV side is analyzed with the


FFT. Table 3 shows the THD index in the voltage and current
waves over the full period at 110 kV, 11 kV and 1.06 kV sides,
respectively. The THD values at all buses have exceeded the
IEEE standard limits adversely.
THD in the voltage wave at 110 kV side in the acceleration,
cruising and deceleration modes, when the train operates with Fig. 13 Harmonic spectrum and THD index of the current wave at
light load, is summarized in Table 4. 110 kV side when the traction is heavily loaded
High amount of harmonics are injected to the PCC when
the train operates in the acceleration and deceleration modes,
whereas low THD occurred when the train moves with a
constant speed.

3.2 Heavy Load Case

In the heavy load condition, the train is assumed to carry large


numbers of passengers. The train has the same dynamic of Fig. 14 Harmonic spectrum and THD index of the current wave at
the light load case. The total power of the traction system is 110 kV side when the train is accelerating with a heavy load
72 MW. The absorbed DC current by the traction load when
it is heavily loaded has the same trend of the current in the
light load case. However, the absorbed current by the traction The harmonic spectrum for this wave is shown in Fig. 13.
load, in this case, is very high compared to the previous case, The THD is 21.35% which is much higher than IEEE stan-
approximately twice the current in the light load case. The dard limits.
load current at 110 kV side when the train is heavily loaded is Figures 14, 15 and 16 show the harmonic spectrum of the
measured. It reaches up to 525 A; according to this value, the current wave at 110 kV side in the acceleration, cruising and
maximum limit of the THD in the voltage and current wave- deceleration modes, respectively.
forms at 110 kV, 11 kV and 1.06 kV sides can be determined It is clear that the THD in the current wave at the PCC is
according to the IEEE standard distortion limits. very high in the deceleration mode. It has a low value when
Figure 12 shows the current wave over the full period at the train is moving with a constant speed, THD values in the
110 kV, which represents the PCC of the system. acceleration and deceleration mode are 18.39% and 29.34%,

123
14702 Arabian Journal for Science and Engineering (2022) 47:14695–14710

Fig. 15 Harmonic spectrum and THD index of the current wave at


110 kV side when the train is cruising with a heavy load
Fig. 18 Harmonic spectrum and THD index of the current wave at 11 kV
side when the traction is heavily loaded

Fig. 16 Harmonic spectrum and THD index of the current wave at


110 kV side when the train is decelerating with a heavy load
Fig. 19 The current at 1.06 kV side when the traction is heavily loaded

Fig. 17 The current at 11 kV side when the traction is heavily loaded

Fig. 20 Harmonic spectrum and THD index of the current wave at


respectively, which are very much higher than the limits spec- 1.06 kV side when the traction is heavily loaded
ified by IEEE standards, and the percentage of the individual
current harmonics 11th and 13th is also around 12% in the
acceleration mode and around 16% in the deceleration mode
which are also very much higher than the IEEE standards
limits. These harmonics are less than 6.0% in the cruising
mode.
The current wave at 11 kV side and the harmonic spectrum
for this wave are shown in Figs. 17 and 18, respectively.
From Fig. 18, it is very clear that the 11th, 25th and 37th
harmonics are the dominant, they are almost equal 16%, 14%
Fig. 21 The reactive power consumed by the traction load measured at
and 10% of the fundamental harmonic, respectively. The 110 kV side
13th, 23rd and 35th harmonics are around 10% of the funda-
mental harmonic. Figure 19 shows the current at 1.06 kV side,
and the harmonic spectrum and the THD index are shown in amount of harmonics that are transferred from the traction
Fig. 20. load side to 1.06 kV side and 11 kV side. The voltage waves
From Figs. 18 and 20, the current waveforms at 1.06 kV at the PCC and at the other buses are analyzed at the differ-
side and 11 kV side are highly distorted compared with the ent operating conditions to assess the impact of the traction
current at the PCC in Fig. 13. This occurs due to the high dynamic on power system. Figures 21 and 22 show the active

123
Arabian Journal for Science and Engineering (2022) 47:14695–14710 14703

Fig. 22 The reactive power consumed by the traction load measured at


110 kV side

and reactive power that consumed by the traction system in


Fig. 23 Active Filter model in MATLA\Simulink
the heavy load case.
In all dynamic mode and at all busses, it is observed that
the 11th, 13th, 23rd and 25th are the dominant among the Table 5 Ratings of the active filter components
other inter harmonics, and there is absence of the trebled Component Voltage (KV) P (MW) Current
harmonics due to the use of delta–delta transformers which (A)
enables an internal track for these harmonics.
Voltage source 1.5 15 –
Inverter 1.5 (DC)/1.06 (AC) – 10,000
3.3 Active Filter Scheme (DC)

The existence of harmonics in power systems and their effects


have led to opulent issues of electric power quality [34]. The Many researcher have discussed the optimization of filters
presence of these harmonics could not be ignored because it based on different methods and techniques such as C-type
causes many problems in power system at different voltage filters based on minimization of voltage harmonic and dis-
levels. It is considered one of the most significant sources tortion for nonlinear load which is discussed in detailed in
of power quality issues, and if it is not reduced, it most [37].
likely causes many problems such as malfunctioning of pro- In this paper, a PI controller is adopted to control the
tective equipment, measurement errors of revenue meters PWM operation. The output current of the inverter is deter-
and the possibility of occurrence of series and parallel reso- mined according to a predetermined reference value. The
nance at some harmonic frequencies and other problems [35]. main aim of this controller is to compare the actual current
These harmonics appear with high level with the existence of that absorbed from the utility side with the reference value in
advance power electronic devices and nonlinear loads such the PI controller. ‘P’ is represented by the proportion part, and
as the traction and electric drives [36]. In order to reduce the ‘I’ is represented by an integral part. In proportional, part ‘P’
harmonic penetration in to the system, an active power filter reduces the error, whereas integral part ‘I’ reduces the offset.
is installed. Active power filter (APF) system is developed ‘P’ is a contingent in present error, whereas ‘I’ is contingent
in MATLAB/Simulink in order to reduce the harmonics and in past error. Therefore, active filter parameters can be set
thereby improve the power quality. It consists of a DC volt- controlled to the desired value by using a PI controller. In
age source connected to an IGBT-based converter. Figure 23 order to get the values of the PI parameters, particle swarm
shows the filter model in MATLAB/Simulink. optimization (PSO) technique is adopted and the constrained
The active filter parameters are selected based on the optimization problem is formulated to find the optimal filter
ratings of the power system components. A trigonometric design that can enhance the power quality performance of the
carrier wave is used as an input to the PWM to control the system [36, 37]. Our objective is to reduce the individual har-
output voltage of the DC source. The frequency of the carrier monic distortion to the minimum level, and thereby the THD
wave is 500 kHz. This value is specified base on the voltage will be reduced accordingly. Based on that, the THD of the
level. From the literature, the frequency of the carrier wave voltage and current equations were considered as the objec-
usually takes a value between 300 to 700 kHz when it con- tive functions. A sinusoidal wave with the same magnitude
nected to a voltage above 10 kV [30]. of the fundamental load current wave and with a frequency
The ratings of the voltage source and the VSI are shown of the fundamental harmonic (60 HZ) is used as a reference
in Table 5. signal. This signal will be compared with the actual current

123
14704 Arabian Journal for Science and Engineering (2022) 47:14695–14710

Fig. 25 Harmonic spectrum of the voltage wave at 110 kV side in the


acceleration mode after connecting the filter

Fig. 24 Block diagram of the traction system


Fig. 26 Harmonic spectrum of the voltage wave at 110 kV side in the
cruising mode after connecting the filter
wave that absorbed from the utility side by the traction load.
Then, according to the difference between them, an error sig-
nal will be generated. The generated error signal will be used
as an input to the PWM after multiplying by a carrier wave,
which is a trigonometric wave with high frequency. Since
the heavy loading condition is the most common operating
condition for the traction system, the APF scheme is con-
nected to the traction system when it is heavily loaded. This
is the worst case of the operating condition. The filter has
been placed at different buses in order to identify the best
location for the filter. Finally, it is found the best location is Fig. 27 Harmonic spectrum of the voltage wave at 110 kV side in the
to be placed at the load side. deceleration mode after connecting the filter
Figure 24 shows a block diagram for the active filter when
it is connected at 1.06 kV side.
The block diagram in Fig. 24 is implemented in MAT- and this means the power factor has improved from 0.75 to
LAB/Simulink. The voltage and current waves are measured be 0.95. Thus, the reactive power consumption has reduced
and analyzed using FFT to evaluate the performance of the accordingly.
filter when it is connected at the load side. The voltage Figures 28 and 29 show the active and reactive power
waves at the PCC are analyzed in the three dynamic modes consumption after connecting the APF at the load side.
after connecting the filter at the load side. The THD index From Figs. 28 and 29, the active power that consumed by
has suppressed significantly at the acceleration, cursing and the traction load has the same profile after connecting the fil-
deceleration modes as shown in Figs. 25, 26 and 27, respec- ter. However, the reactive power has decreased significantly.
tively. It has reduced from 71 MVAR to 24.5 MW only. This means
THD in the current waves has also been reduced less than less amount of reactive power is needed after connecting the
the maximum limits of the IEEE distortion limits. active filter. This has resulted in improving 91 Pf from 0.70 to
Tables 6 and 7 show the THD indexes in the voltage and 0.94. According to that, the total current absorbed by the trac-
current waves at the three buses, respectively. The THD ratios tion system from the utility side has decreased significantly
are reduced below the allowed limits according to the IEEE from 525 to 390 A only.
standards.
Before connecting the filter, the power factor at the PCC 4 Model Validation
was 0.75. After installing the filter at the PCC, the total cur-
rent absorbed from the utility side has been decreased by In order to validate the developed electric train model and for
30% and the active power remains constant without change, having a more realistic overview of the impact of electrical

123
Arabian Journal for Science and Engineering (2022) 47:14695–14710 14705

Table 6 THD index in the voltage wave at different buses when the train
is heavily loaded

Voltage level T H D v (%inthe f undamental) IEEE


(kV) standard
limit (%)

Before adding After adding the


the filter filter

110 8.31 1.31 2.5 Fig. 29 The reactive power absorbed from the utility grid after connect-
11 12.21 2.84 5.0 ing the active filter at the load side
1.06 15.14 3.01 5.0

Table 7 THD index in the current waves at different buses when the
train is heavily loaded

Voltage level T H D i (%inthe f undamental) IEEE


(kV) standard
limit (%)

Before adding After adding the


the filter filter

110 21.33 3.36 7.5


11 29.65 5.65 12.0
1.06 32.0 7.18 12.0

Fig. 30 Block diagram of the real Middle East metro system connected
to a utility grid

The metro has been operating with a heavy load to assess


its impact on the utility side. The total load current load at
the 380 kV side is 456 A.
Based on Table X and by using Eq. (15), the model of the
power system is simulated in MATLAB/Simulink. The train
is operating with a heavy load. Voltage and current waves are
Fig. 28 The active power consumed by the traction load after connecting measured at 380 kV and 33 kV side and thereby subjected
the active filter at the load side
for FFT analysis to evaluate the impact of this train on the
utility network that might occur.
traction drives on the power system, real data for a metro Figures 32 and 33 show a snapshot of the current wave at
in the Middle East are used. The electric utility provided 380 kV side and its harmonic spectrum, respectively, when
some data on the electrical power system where the train the train is in the acceleration mode.
will be connected. However, the electric train data have not From Fig. 33, the THD is 14.13%, which is much higher
provided. Thus, the proposed electric train model that has than the IEEE standard limit. Therefore, corrective action is
been developed in the previous section is used. The real data needed to reduce the THD for minimum value. Based on the
of this metro will be tested with the heavy load condition. case of this metro, the active filter will be connected at 33 kV
Corrective action will be suggested to improve the power side. This is shown in Fig. 34; the DC voltage source, in this
quality of the systems if required. Figure 30 represents a case, is 33 kV DC.
block diagram of the metro system. The ratings of the active filter components are shown in
The BLDC motors specification is shown in Table 8. Table 10.
Figure 31 shows a single-line diagram of the power system After connecting the filter at 33 kV bus, the total harmonic
that supplies the metro. distortion decreased significantly from 14.13 to 2.98% only.
Table 9 shows the data of 380 kV bus and 33 kV bus. This is shown in Fig. 35.

123
14706 Arabian Journal for Science and Engineering (2022) 47:14695–14710

Table 8 Ratings of Riyadh metro


components Component Rated voltage Q (MVAR) S (MVA) P (MW) Current
(KV) (A)

Transformers (1, 2, 3) 380/33 – 100 – –


IGBT-based rectifier 11 – – – 6550
system
BLDC motor 11 – – 72 –

Fig. 32 Small section of the current wave at 380 kV side in the accel-
eration mode

Fig. 31 Single-line diagram of the metro connection to the utility grid

Fig. 33 Harmonic spectrum and THD index of the current wave at


380 kV side in the acceleration mode

Figure 36 shows a small section of the voltage wave at


380 kV side for the invariable speed mode. After connecting the active filter, the THD has decreased
The harmonic spectrum and THD index for this wave are below the IEEE standard distortion limits from 16.13 to
shown in Fig. 37. 3.14% only, as shown in Fig. 41.
After connecting the active filter, the THD index has The THD at 380 kV side in the acceleration mode, cruising
decreased from 8.21% to 1.65% as shown in Fig. 38. mode and the deceleration mode before and after connecting
The last stage of traveling is the deceleration mode. In the active filter is summarized in Table 11.
this stage, the train decelerates its speed until it reaches zero The THD ratios in the voltage and current waveforms
speed. Figure 39 shows a snapshot of the current wave in the before and after connecting the active filter at 380 kV side
deceleration mode. are shown in Table 12.
The current wave is highly distorted. The THD index is From Tables 11 and 12, it is clear that the THD has
16.13% as shown in Fig. 40. decreased significantly in the voltage and current waves at the

Table 9 metro power supply


system data Bus No Bus name Voltage (kV) Three-phase SC One-phase SC

(kA) X/R (kA) X/R

9051 Metro—380 380 43.6 23.9 42.9 12.9


90,511 Metro—33 33 20.7 54 20.7 49.8

123
Arabian Journal for Science and Engineering (2022) 47:14695–14710 14707

Fig. 36 The voltage wave at 380 kV side in the cruising mode

Fig. 34 Block diagram of Riyadh metro when the active filter is con-
nected at 33 kV side

Table 10 The ratings of the active filter components

Component Voltage (KV) P (MW) Current (A)


Fig. 37 Harmonic spectrum and THD index of the current wave at
Voltage source 35 kV 60 – 380 kV in the cruising mode
Inverter 35 (DC)/33 (AC) – 1700 (DC)

Fig. 38 Harmonic spectrum of the voltage wave at 380 kV side in the


Fig. 35 Harmonic spectrum of the current wave at 380 kV side in the cruising mode after connecting the active filter
acceleration mode after connecting the active filter

PCC and at the load side as well. Also, the individual har-
monics have reduced below the IEEE standards distortion
limits.

5 Conclusion and Future Work

A dynamic load of electric train has been developed in Fig. 39 The current wave at 380 kV side in the deceleration mode
MATLAB/Simulink software. This model includes all com-
ponents and control accessories. The developed model of the
train model is built by using brushless DC motors (BLDC) impact of the traction on the power system. However, in the
which have become the most suitable due to its valuable heavy load case, a higher current will be absorbed from the
advantage over the conventional DC motors. The developed utility grid. FFT tool in MATLAB has been used to analyze
model of the train is connected to a power system to study voltage and current waves at different buses in the system. It
the impact of such kind of tractions on the utility grids. The has been found that the current and voltage waves at the train
study shows that the loading has not a significant effect in the side are highly affected compared to the voltage and current

123
14708 Arabian Journal for Science and Engineering (2022) 47:14695–14710

into the PCC when the train was operating in the acceleration
and deceleration mode. However, THD was very low when
the train moves with invariable speed. Thus, the minimum
ratio of the THD occurred during the cruising mode.
To enhance the power system quality, an active filter has
been designed and integrated with the system at the load side.
The active filter has been controlled by using a PI controller.
The output current of the filter is determined according to the
Fig. 40 Harmonic spectrum and THD index of the current wave at output signal from a PWM. A negative feedback technique
380 kV side in the decelerating mode has been used to control the active power filter operation.
Installing static VAR compensator (SVC) or damped filter
might be more suitable instead of using active power filter,
especially with the high ratings of power system parameters
(P, V and I). I think this is a possible scenario should be
considered in future. Then, a comparison between the output
results that will be obtained from the SVC or damped filter
and the current results could be conducted at different voltage
level and power ratings to determine which is better based
on these different ratings.
A real case of a Middle Eastern metro system has been
considered to validate the proposed model. The train was
Fig. 41 Harmonic spectrum of the current wave at 380 kV side in the
assumed to be working with a heavy load. The output results
deceleration mode after connecting the active filter for this metro were consistent with the achieved ones of the
proposed train model. The active filter has been connected to
the Riyadh metro system at the load side. The active filter has
waves at the PCC. The total harmonic distortion (THD) has absorbed the undesirable harmonics, and therefore, individ-
the highest value at 1.06 kV side, which is the nearest point ual and total harmonic distortions have been suppressed and
to the traction load, whereas it was relatively low at the PCC. reduced significantly to be within the allowed IEEE standard
In addition, voltage and current waves have been analyzed in limits.
the acceleration, cruising and deceleration modes separately.
It has been found that a large amount of harmonics is injected

Table 11 THD index in the


voltage waves at the PCC Dynamic mode T H D v (% of the fundamental) T H D i (% of the fundamental)
(380 kV side) in the three
Before adding filter After adding filter Before adding filter After adding
dynamic modes of the train with
filter
a heavy load

Acceleration 9.31 0.92 14.13 2.98


Cruising 4.61 0.89 8.21 1.65
Deceleration 10.32 1.21 16.13 3.14
IEEE standard 1.5 3.75
limits

Table 12 THD index in the


voltage and current waves at the V (KV) T H D v (%V1 ) IEEE limits of T H D i (%I1 ) IEEE limits
different buses when the train is T H D v (%) of T H D I
Before After Before After (%)
heavily loaded
adding adding adding adding
filter filter filter filter

380 5.31 1.01 1.5 13.41 2.43 3.75


33 17.31 2.01 5.0 29.64 3.12 5.0

123
Arabian Journal for Science and Engineering (2022) 47:14695–14710 14709

Acknowledgements The authors would like to acknowledge the sup- 16. Shu, Z.; Xie, S.; Lu, K.; Zhao, Y.; Nan, X.; Qiu, D.; Zhou, F.;
port and help that have been provided by King Fahd University of Gao, S.; Li, Q.: Digital detection, control, and distribution system
Petroleum and Minerals, Dhahran, Saudi Arabia. for co-phase traction power supply application. IEEE Trans. Ind.
Electron. 60(5), 1831–1839 (2019)
17. Kejian, S.; Konstantinou, G.; Jing, L.; Mingli, W.; Agelidis,
V.G.: High-performance control strategy for single-phase three-
References level neutral-point-clamped traction four-quadrant converters. IET
Power Electron. 10(8), 884–893 (2018)
1. Vasquez, J.C.: Reactive power sharing and voltage harmonic dis- 18. Perin, I (2015) Application of power electronics in improving
tortion compensation of droop controlled single phase islanded power quality and supply efficiency of AC traction networks. Kol-
microgrids. IEEE J. 5(3), 1149–1158 (2014) lam, Kerala, India no., pp. 1086–1094
2. Quesada, I.; Lazaro, A.; Martinez, C.; Barrado, A.; Sanz, M.; Fer- 19. Ghassemi, A.; Maghsoud, I.; Farshad, S.; Fazel, S.S.: Dynamic dc
nandez, C.; Vazquez, R.; Gonzalez, I.: Modulation technique for voltage regulation of split-capacitor DSTATCOM for power qual-
low-frequency harmonic cancellation in auxiliary railway power ity improvement. IET Gener. Transm. Distrib. 11(17), 4373–4383
supplies. IEEE Trans. Ind. Electron. 58(9), 3976–3987 (2011) (2017)
3. Mohammad, S.; Gazafrudi, M.; Langerudy, A.T.; Fuchs, E.F.; 20. Ke, X.; Sankman, J.; Chen, Y.; He, L.; Ma, D.B.: A tri-slope gate
Al-Haddad, K.: power quality issues in railway electrification : driving GaN DC-DC converter with spurious noise compression
a comprehensive perspective. IEEE Trans. Ind. Electron. 62(5), and ringing suppression for automotive applications. IEEE J. Solid-
3081–3090 (2015) State Circuits 53(1), 247–260 (2017)
4. Abramov, E.Y.; Shchurov, N. I.; Rozhkova, M. V.: Energy effi- 21. Frasca, R.; Andreozzi, F.; Cascone, B.; Della Valle, D.; Fratelli,
ciency matching of electric traction network with double and L.; Giannini, G.; Improta, V.; Nappo, C.; Porzio, M.: Supercapac-
single-way circuits. In: 18th International Conference of Young itors system for balancing power-supply gap in railway electric
Specialists on Micro/Nanotechnologies and Electron Devices vehicles. In: SPEEDAM 2012-2012 International Symposium on
(EDM), Erlagol, Russia, pp 547–550, (2017). Power Electronics, Electrical Drives, Automation and Motion,
5. Hayashiya, H.; Masuda, M.; Noda, Y.; Suzuki, K.; Suzuki, T. (2017) pp. 754–758, (2018)
Reliability analysis of DC traction power supply system for electric 22. Jinhao, W.; Lei, X.; Yuzhuo, L.; Mengzan, L.; Leilei, P.; Shuying,
railway keywords. In: 19th European Conference on Power Elec- L.; Shuzhong, W.; Yingying, L.: The interaction research between
tronics and Applications (EPE’17 ECCE Europe), Warsaw, Poland, public grid and traction power supply system. In: Electricity Dis-
1–14 Sept. 2017 pp. 1–6 tribution, 2008, CICED 2008, China International Conference,
6. Wu, C.; Luo, A.; Shen, J.; Ma, F.J.; Peng, S.: A negative sequence pp. 1–8, China, (2008).
compensation method based on a two-phase three-wire converter 23. Rygg, A.; Molinas, M.; Zhang, C.; Cai, X.: A modified sequence-
for a high-speed railway traction power supply system. IEEE Trans domain impedance definition and its equivalence to the DQ-domain
Power Electron 27(2), 706–717 (2018) impedance definition for the stability analysis of AC power elec-
7. Chirinos, C.M.; Lorenavelásquez, V.; Soto, H. A.: Power consump- tronic systems. IEEE J. 4(4), 1383–1396 (2016)
tion reduction of an electric shower using a PWM based power 24. Xu, X.: Research of electrified railway harmonic suppression based
supply. In: 2016 IEEE Central America and Panama Student Con- on H-infinity control. J. Comput. 7(12), 3075–3081 (2012)
ference (CONESCAPAN), pp. 1–3, Guatemala City, Guatemala, 25. Saleh, M.; Member, S.; Dutta, O.; Member, S.; Esa, Y.: Quantitative
27–30 (Sept. 2016) analysis of regenerative energy in electric rail traction systems. In:
8. Maghsoud, I.; Farshad, S.; Ghassemi, A.; Fazel, S.S.: Comprehen- 2017 IEEE Industry Applications Society Annual Meeting, pp. 1–7,
sive study on the power rating of a railway power conditioner using Cincinnati, OH, USA, (2017)
thyristor switched capacitor. IET Electr. Syst. Transp. 4(4), 97–106 26. Chin, C.S.H.; Lin, C.: Electronic combined transformer for
(2014) power-quality measurements in high-voltage systems. IEEE Trans.
9. Ashok, S.: Harmonic filter for electric traction system. Innov. Smart Instrum. Meas. 60(6), 2007–2019 (2019)
Grid Technol. - India (ISGT India), IEEE PES, pp. 282–286, (2018) 27. Hu, H.; Shi, Q.; He, Z.; He, J.; Gao, S.: Potential harmonic reso-
10. Bellan, D.; Spadacini, G.; Fedeli, E.; Pignari, S.A.: Space- nance impacts of PV inverter [27]s on distribution systems. IEEE
frequency analysis and experimental measurement of magnetic Trans. Sustain. Energy 6(1), 151–161 (2015)
field emissions radiated by high-speed railway systems. IEEE 28. Jeschke, S.; Tsiapenko, S.; Hirsch, H.: Investigations on the shaft
Trans. Electromag. Compat 55(6), 1031–1042 (2019) currents of an electric vehicle traction system in dynamic operation.
11. Shu, Z.; Xie, S.; Lu, K.; Zhao, Y.; Nan, X.; Qiu, D.; Zhou, F.; In: IEEE International Symposium on Electromagnetic Compati-
Gao, S.; Li, Q.: Digital detection, control, and distribution system bility, vol. 2015–Sept, pp. 696–701, Dresden, Germany, (2015)
for co-phase traction power supply application. IEEE Trans. Ind. 29. Zupan, A.; Teklic, A.; Filipovic-Grcic, B.: Modeling of 25 kV elec-
Electron. 60(5), 1831–1839 (2013) tric railway system for power quality studies. In: Eurocon, IEEE
12. Liu H (2017) Towards urban electric taxi systems in smart cities: trans. July, pp. 844–849, (2019)
the battery swapping challenge. IEEE Trans, pp. 1–6, issue: 99 30. Hu, H.; He, Z.; Li, X.; Wang, K.; Gao, S.: Power-quality impact
13. Kylymchuk A (2017) Impact of linear regulator, installed in the assessment for high-speed railway associated with high-speed
electric grid of energy supply company, on power losses. In: trains using train timetable—part I: methodology and modeling.
First Ukraine Conference on Electrical and Computer Engineer- IEEE Trans. Power Deliv., vol. 8977, no. c, pp. 1–1, (2015)
ing (UKRCON), pp. 411–416, Kiev, Ukraine 31. Song, W.; Wang, S.; Xiong, C.; Ge, X.; Feng, X.: Single-phase
14. Xie, B.; Li, Y.; Zhang, Z.; Hu, S.; Zhang, Z.; Luo, L.; Cao, Y.; Zhou, three-level space vector pulse width modulation algorithm for grid-
F.; Luo, R.; Long, L.: A compensation system for Co phase high- side railway traction converter and its relationship of carrier-based
speed electric railways by reactive power generation of SHC&SAC. pulse width modulation. IET Electr. Syst. Transp. 4(3), 78–87
IEEE Trans. Ind. Electron. 65(4), 2956–2966 (2017) (2014)
15. Chen, T.; Yang, W.; Hsu, Y.: A systematic approach to evaluating 32. Shu-Ming, L.; Dong-Xin, C.; Qiong-Lin, L.; Xiao-Dong, Z.; Xiao-
the overall impact of the electric traction demands of a high-speed Peng, Y.: The Impact of 350km/h high-speed railway to grid power
railroad on a power system. IEEE Trans. Veh. Technol. 47(4), quality. International Conference on Electric Utility Deregulation
1378–1384 (1998)

123
14710 Arabian Journal for Science and Engineering (2022) 47:14695–14710

and Restructuring and Power Technologies (DRPT) vol. 1, pp. 0–3, 36. Aleema, S.H.E.A.; Zobaa, A.F.; Balci, M.E.: Optimal resonance-
Weihai, Shandong, China, (2012) free third-order high-pass filters based on minimization of the total
33. Chymera, M.Z.; Renfrew, A.C.; Barnes, M.; Holden, J.: Model- cost of the filters using Crow Search Algorithm. Electric Power
ing electrified transit systems. IEEE Trans. Veh. Technol. 59(6), Syst. Res. 151, 381–394 (2017)
2748–2756 (2019) 37. Chymera, M.Z.; Renfrew, A.C.; Barnes, M.; Holden, J.: Optimal
34. Zobaa, A.F.; Abdel Aziz, M.M.; Abdel Aleem, S.H.E.: Compari- C-type passive filter based on minimization of the voltage harmonic
son of shunt-passive and series-passive filters for DC drive loads. distortion for nonlinear loads. IEEE Trans. Industr. Electron. 59,
Electric Power Compon. Syst. 38(3), 275–291 (2010) 281–289 (2011)
35. Aleem, S.H.E.A.; Zobaa, A.F.; Balci, M.E.; Ismael, S.M.: Har-
monic overloading minimization of frequency-dependent com-
ponents in harmonics polluted distribution systems using Harris
hawks optimization algorithm. IEEE Access 7, 100824–100837
(2019)

123

You might also like