DCS Thyristor Power Converters

for DC drive systems


25 to 5150 A

Instructions for Software


DCS 600 MultiDrive

Instructions for Software Version 15.208 CON-2


15.610 AMC-DC
DCS 600_E MultiDrive

ABB Automation
This unit is equipped with software
15.208 CON-2
15.610 AMC-DC
DCS600_E MultiDrive

This software can directly replace


• All pre-releases of 15.610 and 15.208
• All software releases 15.607, 15.608, 15.609 and 15.205, 15.206, 15.207

Solved problem
• Emergency STOP supervision for long ramp times
• Main contactor off time delay of 3-phase field exciter units
• Start synchronization outside the limits 49.5...61 Hz
• LED panel parameter selection (18.1) is lost after power down
• F33 for field currents above 165 A

This software is released for:


• DCS 600 armature converter modules and DCA 600 enclosed
• DCF 600 Field supplies and DCA 620 enclosed for motor field application
• Operation with FEX-1, FEX-2, DCF 503, DCF 504, DCF 506
• Communcation to APC (YPQ 112) and Advant (AC70, AC80, FCI)
• 12-Pulse parallel, serial and sequential configuration
• DCR 600 Rebuild kits
• Fieldbus communication with Profibus V2.2; Modbus Plus V1.3; CS31 V1.5
• AC80 Modulebus link: OK; Drivebus link:maximum two datasets per ACS RX
block

This software is also released for beta tests

• Rebuild with converter fan monitoring PW 1002 / PW 1003


• External zero current detection CZD-01 (MG SET field exciter)

The Download function for


AMC board use Hardware (NISA03..)
CON-2 board use Hardware (SNAT608.. and COM-1 or COM-5, NPCU-02)
see also Flash-PROM problem hint for a certain batch of boards

Documentation and software

AMC-DC Software 15.603 15.604 15.605 15.606 15.608 15.609 15.610


Software description
3 ADW 0000 076 R0301 Rev C û û û
MultiDrive

3 ADW 0000 076 R0401 Rev D û


3 ADW 0000 076 R0501 Rev E û û
3 ADW 0000 076 R0601 Rev F û
Operating instructions
3 ADW 0000 080 R0201 Rev B û û û
3 ADW 0000 080 R0301 Rev C û
3 ADW 0000 080 R0401 Rev D û û
3 ADW 0000 080 R0501 Rev E û
CON-2 Software 15.203 û û û
CON-2 Software 15.204 û
CON-2 Software 15.207 û û
CON-2 Software 15.208 û û

Revision History
The difference between 15.609 to 15.610 is:
• a new control input for DC Break trip (current rise detection)
• a new alarm * for missing Acknowledge, DC Breaker, Dynamic Brake
• Temperature Alarm Level 5°C below Fault Level
* in the combination 15.208/15.609, the alarm displays a <undefined Alarm> (9.05 bit 15)
Cross reference list
Changed Signals and Parameters
(in relation to the previous software release)

THIS release: '&

previous release(s): DC 15.607 / 15.609



Release 

Reasons for changes  

1 Compatibility to ACS600 Reason Index Name Scaling / Limits Index Name Scaling / Limits
2 Added function 2 70.21 CH0 HW CONNECTION
3 Clean-up 2 20.18 CURRENT RISE MAX
2 17.06 INDX SQUARE WAVE
2 42.14 CONV TEMP DELAY
2 4.23 CON SW PRERELEASE 4.23 CON SW SUBRELEASE
2 4.24 AMC SW PRERELEASE 4.24 AMC SW SUBRELEASE
2 8.08 DRIVE STATE
2 42.06 NOM SUPPLY VOLT int. minimum 50 V 42.06 NOM SUPPLY VOLT int. minimum 40 V
; check parameter files
< check application
3ADW 000 119 R0701 REV G

ABB Automation Products GmbH


Postfach 1180
D-68619 Lampertheim
Telefon +49(0) 62 06 5 03-0
Telefax +49(0) 62 06 5 03-6 09
12_00

www.abb.com/motors&drives

*119R0701A0490000*
*119R0701A0490000*