Minimun Headroom Requeriments

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

PDVSA

ENGINEERING DESIGN MANUAL


VOLUME 18–STD

ENGINEERING SPECIFICATION

PDVSA N° TITLE

0602.1.341 MINIMUM HEADROOM REQUIREMENTS

2 JUN.92 GENERAL REVIEW 1 L.T. R.P. R.R.

1 DEC.89 GENERAL REVIEW 1 J.S. J.G. E.S.

0 DEC.85 FOR APPROVAL 1 J.S. J.G. E.S.

REV. DATE DESCRIPTION PAG. REV. APPD. APPD.

APPD.BY José Gilarranz DATE DEC.85 APPD.BY Eduardo Santamaria DATE DEC.85

E PDVSA, 1983 ESPECIALISTAS


ENGINEERING SPECIFICATION PDVSA 0602.1.341

PDVSA
REVISION FECHA
MINIMUM HEADROOM REQUIREMENTS
2 JUN.92
Página 1
.Menú Principal Indice manual Indice volumen Indice norma

NOTES:
1. The above heights are absolute minimum, and should be increased
wherever possible.
2. 2300 minimum headroom shall also apply to extensive obstructions such
as rack piping, beams, fixtures, etc., that effectively reduce the ceiling
height.
3. 2150 minimum headroom shall be maintained under floor beams, piping,
or other obstructions, provided that the occurrence of these obstructions
do not effectively reduce the ceiling height of 2150.
4. Headroom may be reduced to 2050 for isolated obstructions such as
lighting fixtures, sprinkler heads, valve stems, etc.
5. All dimension are in mm unless otherwise noted.

You might also like