Compressor Installation Guide 25

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

24 Guidelines for cooling water

requirements
Knowing your total cooling water requirement 50% of the water flow should be by-passed
and its allowed temperature increase you can around the compressor and be mixed with the
calculate the heat amount that has cooled away warm compressor water before entering the
in the cooling tower. cooling tower.
t v
D X Q in kcal/second You'll need to balance and adjust the by-passed
water flow in accordance with your actual
t o
where D is increase of cooling water temp. in C compressor running conditions.
v
Q is cooling water flow in litres/second.
You can cool the water in a cooling tower to a
o
Calculate with a cooling water temperature temperature approximately 5 C above the wet
o
increase of 15 C. Should a lower temperature bulb temperature. If you still need better cooling
o
increase than 15 C be required, please contact you will have to make a large increase in the size
your Atlas Copco Engineer for advice. of your cooling tower.

The water pressure in G or Z compressor must Even, in the warmest countries, wet bulb temper-
o
not exceed 5 bar. You must therefore limit the ature seldom exceeds 28 C. This fact makes
o
water pressure drop through the compressor to cooling water temperature of 33 C possible &
o
approximately 2 bar. If you install a cooling 35 C practical.
water pump close to and before the compressor,
the pump must overcome the following You must regularly check you cooling water
resistance: quality. Cooling water should be soft, clean and
free from mineral salts. Your cooling tower must
Compressor 2.0 bar have a chemical dosage system to prevent algae
Static water height 0.3 bar growth, line crustation and corrosion.
Cooling tower nozzle 0.4 bar
Pipes, bends and valves 0.3 bar A cooling tower always uses up a certain amount
Totally 3.0 bar of water. The three main reasons are:

In countries with a temperate climate you can Evaporation Splashing Dilution


o
reduce water temperature by 15 C in a cooling
tower. You can use a simple single-circuit You can work out the water amount lost by
cooling system with this water flow: evaporation with this formula:

Heat quantity kcal/hour water loss in


Pump Compressor Cooling Tower = liters/hour
580

580 is evaporation coefficient for water


In tropical countries with high temperature and Splash losses are negligible
high humidity it is difficult to obtain a better
o
temperature reduction than 10 C in a cooling
You need to add water dilution to avoid
tower. To get this you will need a double-circuit
increased concentration of mineral salts. The
cooling system with two water pumps, a
amount of water to be added is approximately
separate water basin, and individual water
50% of the evaporation without chemical dosage
circuits for tower and compressor. This gives a
at favourable conditions.
sophisticated and efficient solution but
investment needed is high. The alternative is
If you have a chemical dosage system, then your
to use a modified single-circuit system. Your
dilution needs can be reduced to 25% of the
investment costs will be lower. But you must
evaporation.
dimension your cooling tower for a water flow
50% higher than the flow through the
The total water amount you need to add equals
compressor.
evaporation amount plus 25% or 50%.

You might also like