Bureau Veritas (M) Sdn. Bhd.

EX DATABASE CLOSE-OUT REPORT

Malaysia Vietnam Offshore Terminal (L) Limited (MVOT)


Doc. Number: MLS 18-0377-RPT-ELE-Rev.0
EX DATABASE CLOSE-OUT REPORT
2
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 2 of 16
2020

Table of Contents

EXECUTIVE SUMMARY…………………………………………………………………4
1.0 PROJECT BACKGROUND……………………………………………………...5
1.1. SCOPE OF WORK………………………………………………………………..6
2.0 METHODOLOGY………………………………………………………………….7
3.0 EX DATABASE REVIEW WORKSHOP………………………………………..9
3.1. RESULT SUMMARY…………………………………………………………….10

APPENDIX 1 – EX DATABASE WORKSHOP SLIDES…………………………….11


APPENDIX 2 – EX DATABASE POST SITE VISIT………………………………….12
APPENDIX 3 – EX DATABASE POST WORKSHOP……………………………….13
APPENDIX 4 – EX DATABASE POST SITE VISIT SLIDES…………………….....14
APPENDIX 5 – EX DATABASE INSPECTION SAMPLING ACTIVITY…………...15
APPENDIX 6 – EX INSPECTION CHECKLIST………………………………………16
EX DATABASE CLOSE-OUT REPORT
32
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 3 of 16
2020

Abbreviations

AIR MS : Asset Integrity Reliability Management System


BVM : Bureau Veritas Malaysia
E&I : Electrical & Instrument
Ex : Product for an explosive environment
FSO : Floating Storage and Offloading
GA : General Arrangement
HAC : Hazardous Area Classification (HAC)
HSE : Health Safety & Environment
IEC : International Electrotechnical Commission
IP : International Protection
MVOT : Malaysia Vietnam Offshore Terminal
NA : Not Available
OPS : Operation Performance Standard
OSR MS : Offshore Self-Regulation Management System
PIMS : Pipeline Integrity Management System
PS : Performance Standard
P&ID : Piping & Instrumentations Diagram
SCE : Safety Critical Elements
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 4 of 16
2020

Executive Summary
The primary objective of the task is to establish Ex Database specifically tailored for
MVOT facilities, in which to improve the reliability and integrity performance of Ex
Equipment during operational mode while reducing the risk of hazards as minimum as
possible.

The completed Ex Database will details out the Ex Equipment’s properties such as its
tag number & description, manufacturer, Ex protection type, IP rating, temperature
class, gas type and location within the Hazardous Zone.

A proper-built Ex Database is the first step in creating an effective Ex Management


System which comprises of Ex Database, Ex Inspection, Ex Maintenance Plan and
Ex Rectification activities in accordance with IEC 60079 Part 17 that can be further
developed in the future.

For this project, the methodology consist of 3 Phase, Phase 1: Document Review,
Phase 2: Site Verification, Phase 3: Project Close-Out. Phase 1 is done 2 weeks prior
Phase 2 (18th November 2019 – 29th November 2019). Phase 2, Site Verification is
done 10 days (3rd December 2019 – 13th December 2019) at the FSO Orkid. Phase 3
is done on 7th January 2020 where 642 numbers of Ex equipment have been identify
in the Hazardous Area Classification (HAC).
.

1
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 5 of 16
2020

1.0 PROJECT BACKGROUND

Malaysia Vietnam Offshore Terminal (MVOT), has contracted Bureau Veritas Malaysia
(BVM) to perform scope below for FSO Orkid:

I. Safety Studies
II. Safety Critical Elements (SCE) and Operation Performance Standard (OPS)
development including Ex Equipment Database development.
III. Development of Asset Integrity Reliability Management System (AIR MS)
incorporating Pipeline Integrity Management System (PIMS) as per OSR MS
requirement

The detailed scope for this project are listed in Table 1 below.

Table 1: Detailed Scope of Project.

2
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 6 of 16
2020

1.2. Scope of Work

The scope implies establishing an Ex Database based on Asset Register List, P&ID,
Equipment Datasheet, GA Drawing, HAC Report and other relevant documents that
have been Finalized and Approved by client, for BVM reference.

Client have submitted the Equipment Datasheet and HAC Report prior to begin the
campaign as these are the main reference documents required. The drawings shall
consist of size/dimension of Ex Hatching, and the characteristic of the HAC (i.e. gas
group, temperature class and zoning).
EX DATABASE CLOSE-OUT REPORT
7
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 7 of 16
2020

2.0 METHODOLOGY

The work methodology can be described as per the Overview (Process Flowchart) and
methodology description in Figure 1 and 2 below:

Figure 1: Overview (Process Flowchart) of Establishing Ex Database

4
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 8 of 17
2020

Figure 2: Ex Database Establishment Methodology Description

5
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 9 of 16
2020

3.0 EX DATABASE REVIEW WORKSHOP

The Ex Database review workshop has been carried out at Bureau Veritas (M) Sdn.
Bhd. Offshore 2 meeting room, Level 11, Menara Dayabumi, Kuala Lumpur, Malaysia
on 7th January 2020.

MVOT’s HSE Engineer and OPS Superintendent with BVM represented by Project
Manager and E&I Lead Engineer were present for the workshop.

The workshop was facilitated and scribed by BVM. The Ex Database workshop
slides pack is attached in Appendix 1.

The Ex Database list post site visit and Ex Database post workshop is attached in
Appendix 2 & Appendix 3 respectively.

The slides presentation of site visit findings and Ex Inspection sampling activity
during site visit is attached in Appendix 4 & Appendix 5 respectively.

The Ex Inspection Checklist are attached in Appendix 6.

6
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 10 of 16
2020

3.1. Result Summary

The result summary from the site visit with the findings is reflected on Table 2. The Ex
Database with discipline summary is shown in Figure 3.

Table 2: Site Visit Findings Summary.

Figure 3: Ex Database with Discipline Summary

Full detail result per tag item is attached in Appendix 3-Ex Database post workshop.
7
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 11 of 16
2020

APPENDIX 1 – EX DATABASE WORKSHOP SLIDES


07 TH JAN 2020 MVOT FSO ORKID

MVOT FSO ORKID


EX DATABASE DEVELOPMENT
WORKSHOP
OUTLINE

02 Overview 03 Project

& Intro Methodology

01 04 Ex Database
Objective SV Findings
Ex DB Worksheet

05 Project
AOB
Slide / 2
01
OBJECTIVE

Slide / 3
To present Site Verification findings

To review Ex Database

OBJECTIVE

Slide / 4
02
PROJECT OVERVIEW
SCOPE OF WORK

No. Description Deliverables


Safety Critical Equipment (SCE)
1 1. SCE Identification Template
Identification
1. Specific PS Excel Files
2 Performance Standard Development
2. Assurance task target value template

3 Development of AIR MS 1. New or updated AIR MS Manual

1. Ex Equipment database
Ex Equipment register & inspection
2. Report on document review vs. site verification
4 checklist development as per
findings
IEC60079 Part 17
3. Inspection checklist
1. RBI Study report
Risk Based Inspection (RBI) study &
5 2. Mark up P&ID of corrosion loops
Flexible Pipe/Riser
3. Flexible Pipe/Riser Integrity Mgt Plan Report
WHY ?

Electrical installations inspection


and maintenance

Regulation
Ensure regulatory compliance of electrical installations in hazardous areas:

• make sure that equipment has an inspection and maintenance plan in accordance with
IEC 60079-17
• so that it continues to be safe to operate and
• this can be demonstrated to the satisfaction of the HSE
WHY ?
Challenges
Poor tracking system with regard to overhaul and maintenance of Ex equipment

Generalization of information leading to inaccuracies of area classification


schedule

Incomplete Hazardous Area Classification (HAC) drawings resulting to wrong


selection of equipment
Implications
Lack of competent Ex personnel Cost to install new Ex equipment if over-design

Cost to replace non-compliance equipment if inaccurate design

Safety to personnel onboard in dealing with non-compliance Ex equipment

Operational impact i.e. challenges to locate Ex spare parts and to perform repair/overhaul work
RESOLUTION
To fully implement Ex Management System which includes:

• Established interdisciplinary communication and review process

• Ex Training and awareness campaign for every personnel onboard

• Appointment and Authorization of Ex personnel

• Establishment of Ex Database

• Implementation of Ex IMG Visual, Close and Detailed Inspection as per


IEC60079 Part 14 & 17

• Implementation of Ex Rectification Campaign for repair, overhaul and re-


certification of Ex equipment as per IEC60079 Part 19

• Management of Change (MOC) for Ex Assessment and Ex Documentation


03
METHODOLOGY

Slide / 10
METHODOLOGY

Phase 1 Documentation Review

• Data gathering from Asset Register, P&ID, HAC, Equipment


Dossier, GA Drawing, Plant Layout etc. for creating initial Ex
Database.

Phase 2 Site Verification

• Physical asset verification via photo taking and record findings.


Certificate number of Ex equipment is the most crucial
information required.
• Any discrepancies found e.g. limited access, missing nameplate
and document, live equipment status will be remarked in the
database.

Phase 3 Project Close-Out

• Establish Ex Database.
• Establish generic Inspection & Maintenance Task for Ex
equipment as per IEC60079 Part 17.
Slide / 11
04
SITE VERIFICATION
FINDINGS

Slide / 12
FINDINGS SUMMARY

TAG EX DATABASE LIST


No. FINDINGS
NOS 642 (171 – no Ex Data)

1 122 NO TAG AT SITE


ELECTRICAL INSTRUMENT TELECOM
239 (27) 342 (142) 61 (2)

2 75 PLATE FADED

3 80 NO PLATE AT SITE

4 32 NO EX INFO

5 19 NO TAG & PLATE AT SITE


FINDINGS

NO TAG AT SITE
(141)

CONTROL VALVE AND PRESSURE TRANSMITTER


(BOILER)

LEVEL SWITCH (GAS SPEAKER AND DETECTOR


SCRUBBER AREA) (PAGA & FIRE AND GAS)
FINDINGS

PLATE FADED
(75)

JUNCTION BOX(TURRET AREA)

JUNCTION BOX LEVEL TRANSMITTER AND MCP


(BOILER) (INSTRUMENT & FIRE AND GAS)
FINDINGS

NO PLATE AT SITE
(80)

ISOLATOR
(GAS SCRUBBER)

BEACON & RADIO REAPEATER GAS DETECTOR AND LIGHTING


(TELECOM) (FIRE & GAS, ELECTRICAL)
FINDINGS

NO EX INFO
(32)

GAS DETECTOR (PUMP ROOM)

LIMIT SWITCH
(BOILER)
PRESURE SWITCH (BOILER AND SCRUBBER)
FINDINGS

OTHERS

CABLE GLAND LOOSE


NO EARTHING
(GAS SCRUBBER) CABLE TEAR
(GAS SCRUBBER)
SAMPLING INSPECTION

Detailed Inspection

SAMPLING TAG NO EQUIPMENT DESCRIPTION

#001 No Tag at Site Pressure Transmitter

#002 ELT-U-EX13 Emergency Lighting


05
AOB
Deliverables
Project Close Out
DELIVERABLES

Phase 3 Project Close-Out

• Establish Ex Database.
• Establish generic Inspection & Maintenance Task for Ex
equipment as per IEC60079 Part 17.

Slide / 21
SHAPING
A WORLD
OF TRUST
W W W. B U R E AU V E R I TA S . C O M
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 12 of 16
2020

APPENDIX 2 – EX DATABASE POST SITE VISIT


SITE VERIFICATION REPORT
FOR EX DATABASE
Date
Prepared by Page
December
Bureau Veritas (M) Sdn Bhd 3 of 82
2019

Attachment: Attachment A Ex Asset Verification List

FINDINGS SUMMARY

TOTAL EQUIPMENT LIST = 642

No. TAG NOS DISCIPLINE

1 239 ELECTRICAL

2 342 INSTRUMENT

3 61 TELECOM

FINDINGS (other details to be referred in Ex Database Worksheet attached)

No. TAG NOS FINDINGS

1 122 NO TAG AT SITE

2 75 PLATE FADED

3 80 NO PLATE AT SITE

4 32 NO EX INFO

5 19 NO TAG & PLATE AT SITE


SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 4 of 82

Attachment A: Ex Asset Verification List

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

PA070
NAV BRIDGE LIGHTING LIGHTING
1. ZONE 2 ELT-NAV-EX5 ELECTRICAL GLAMOX 81500 nA II T4 67
DECK FIXTURE SYSTEM
4

NAV BRIDGE LIGHTING LIGHTING AQUAL


2. ZONE 2 LT-NAV-EX6 ELECTRICAL NO PLATE AT SITE
DECK FIXTURE SYSTEM SIGNAL

NAV BRIDGE LIGHTING LIGHTING AQUAL


3. ZONE 2 LT-NAV-EX7 ELECTRICAL NO PLATE AT SITE
DECK FIXTURE SYSTEM SIGNAL

PA070
NAV BRIDGE LIGHTING LIGHTING
4. ZONE 2 ELT-NAV-EX8 ELECTRICAL GLAMOX 81500 nA II T4 67
DECK FIXTURE SYSTEM
4

DAEYANG
D DECK (BAT. LIGHTING LIGHTING
5. ZONE 2 LT-D-BR ELECTRICAL ELECTRIC NO PLATE AT SITE
ROOM) FIXTURE SYSTEM
CO. LTD

D DECK PA070
LIGHTING LIGHTING
6. (OUTSIDE BAT. ZONE 2 ELT-D-EX6 ELECTRICAL GLAMOX 81500 nA II T4 67
FIXTURE SYSTEM
ROOM) 4

D DECK PA070
LIGHTING LIGHTING
7. (OUTSIDE BAT. ZONE 2 ELT-D-EX7 ELECTRICAL GLAMOX 81500 nA II T4 67
FIXTURE SYSTEM
ROOM) 4

PA070
LIGHTING LIGHTING
8. UPPER DECK ZONE 2 ELT-U-EX8 ELECTRICAL GLAMOX 81500 nA II T4 67
FIXTURE SYSTEM
4
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 5 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

PA070
LIGHTING LIGHTING
9. UPPER DECK ZONE 2 ELT-U-EX9 ELECTRICAL GLAMOX 81500 nA II T4 67
FIXTURE SYSTEM
4

PA070
LIGHTING LIGHTING
10. UPPER DECK ZONE 2 ELT-U-EX10 ELECTRICAL GLAMOX 81500 nA II T4 67
FIXTURE SYSTEM
4

PA070
LIGHTING LIGHTING
11. UPPER DECK ZONE 2 ELT-U-EX11 ELECTRICAL GLAMOX 81500 nA II T4 67
FIXTURE SYSTEM
4

PA070
LIGHTING LIGHTING
12. UPPER DECK ZONE 2 ELT-U-EX12 ELECTRICAL GLAMOX 81500 nA II T4 67
FIXTURE SYSTEM
4

PA070
LIGHTING LIGHTING
13. UPPER DECK ZONE 2 ELT-U-EX13 ELECTRICAL GLAMOX 81500 nA II T4 67
FIXTURE SYSTEM
4

UPPER DECK PA070


LIGHTING LIGHTING
14. (AFT OFF. ZONE 2 ELT-U-EX15 ELECTRICAL GLAMOX 81500 nA II T4 67
FIXTURE SYSTEM
AREA) 4

UPPER DECK PA070


LIGHTING LIGHTING
15. (AFT OFF. ZONE 2 ELT-U-EX16 ELECTRICAL GLAMOX 81500 nA II T4 67
FIXTURE SYSTEM
AREA) 4

GTX
UPPER DECK LIGHTING LIGHTING GLAMOX
16. ZONE 1 ELT-U-PUM1 ELECTRICAL 24046 d IIC T6 67
(PUMP ROOM) FIXTURE SYSTEM ASA
9
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 6 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK ELT-PUM- LIGHTING LIGHTING Tenchor EVF-


17. ZONE 1 ELECTRICAL d IIC T4 66
(PUMP ROOM) NE1 FIXTURE SYSTEM Iitalsmea P236

GTX
UPPER DECK LIGHTING LIGHTING GLAMOX
18. ZONE 1 LT-PUM-EX1 ELECTRICAL 24046 d IIC T6 67
(PUMP ROOM) FIXTURE SYSTEM ASA
9

UPPER DECK ELLK


LIGHTING LIGHTING
19. (METERING ZONE 1 LT-U-MS1 ELECTRICAL CEAG 92036/ d IIC T4 66
FIXTURE SYSTEM
SKID) 36

UPPER DECK ELLK


LIGHTING LIGHTING de Mb
20. (METERING ZONE 1 ELT-U-MS2 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
SKID) 36NIB

UPPER DECK ELLK


LIGHTING LIGHTING
21. (METERING ZONE 1 LT-U-MS3 ELECTRICAL CEAG 92036/ d IIC T4 66
FIXTURE SYSTEM
SKID) 36

UPPER DECK ELLK


LIGHTING LIGHTING de Mb
22. (METERING ZONE 1 ELT-U-MS4 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
SKID) 36NIB

UPPER DECK ELLK


LIGHTING LIGHTING
23. (METERING ZONE 1 LT-U-MS5 ELECTRICAL CEAG 92036/ d IIC T4 66
FIXTURE SYSTEM
SKID) 36

2ND DECK ELT-2DK- LIGHTING LIGHTING GTX2


24. ZONE 1 ELECTRICAL GLAMOX d IIC T6 67
(PUMP ROOM) PUM2 FIXTURE SYSTEM 40469

2ND DECK LIGHTING LIGHTING KOKOSHA


25. ZONE 1 LT-COC-EX1 ELECTRICAL NO PLATE AT SITE
(PUMP ROOM) FIXTURE SYSTEM CO. LTD
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 7 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

2ND DECK LIGHTING LIGHTING Technor EVF-P


26. ZONE 1 LT-PUM-NE2 ELECTRICAL de IIC T4 66
(PUMP ROOM) FIXTURE SYSTEM italsmea 236

2ND DECK LIGHTING LIGHTING KOKOSHA


27. ZONE 1 LT-COC-EX2 ELECTRICAL NO PLATE AT SITE
(PUMP ROOM) FIXTURE SYSTEM CO. LTD

3RD DECK LIGHTING LIGHTING Technor EVF-P


28. ZONE 1 LT-PUM-NE3 ELECTRICAL de IIC T4 66
(PUMP ROOM) FIXTURE SYSTEM italsmea 236

3RD DECK LIGHTING LIGHTING Technor EVF-P


29. ZONE 1 LT-PUM-NE4 ELECTRICAL de IIC T4 66
(PUMP ROOM) FIXTURE SYSTEM italsmea 236

3RD DECK LIGHTING LIGHTING KOKOSHA


30. ZONE 1 LT-COC-EX3 ELECTRICAL NO PLATE AT SITE
(PUMP ROOM) FIXTURE SYSTEM CO. LTD

3RD DECK ELT-3DK- LIGHTING LIGHTING EVF-P


31. ZONE 1 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) PUM3 FIXTURE SYSTEM 218

3RD DECK ELT-PUM- LIGHTING LIGHTING Technor EVF-P


32. ZONE 1 ELECTRICAL de IIC T4 66
(PUMP ROOM) NE5 FIXTURE SYSTEM italsmea 236

3RD DECK LIGHTING LIGHTING GTX2


33. ZONE 1 LT-PUM-EX2 ELECTRICAL GLAMOX d IIC T6 67
(PUMP ROOM) FIXTURE SYSTEM 40469

3RD DECK LIGHTING LIGHTING Technor EVF-P


34. ZONE 1 LT-PUM-NE6 ELECTRICAL de IIC T4 66
(PUMP ROOM) FIXTURE SYSTEM italsmea 236

4TH DECK LIGHTING LIGHTING KOKOSHA


35. ZONE 1 LT-COC-EX7 ELECTRICAL NO PLATE AT SITE
(PUMP ROOM) FIXTURE SYSTEM CO. LTD

4TH DECK ELT-4DK- LIGHTING LIGHTING GTX2


36. ZONE 1 ELECTRICAL GLAMOX d IIC T6 67
(PUMP ROOM) PUM6 FIXTURE SYSTEM 40469

4TH DECK LIGHTING LIGHTING EVF-P


37. ZONE 1 LT-PUM-EX9 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) FIXTURE SYSTEM 236
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 8 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

4TH DECK LIGHTING LIGHTING EVF-P


38. ZONE 1 LT-PUM-NE9 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) FIXTURE SYSTEM 236

4TH DECK LIGHTING LIGHTING EVF-P


39. ZONE 1 LT-PUM-EX8 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) FIXTURE SYSTEM 218

4TH DECK ELT-PUM- LIGHTING LIGHTING Technor EVF-P


40. ZONE 1 ELECTRICAL de IIC T4 66
(PUMP ROOM) NE8 FIXTURE SYSTEM italsmea 236

4TH DECK LIGHTING LIGHTING EVF-P


41. ZONE 1 LT-PUM-EX5 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) FIXTURE SYSTEM 218

4TH DECK LIGHTING LIGHTING EVF-P


42. ZONE 1 LT-PUM-EX7 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) FIXTURE SYSTEM 218

4TH DECK LT-PUM- LIGHTING LIGHTING Technor EVF-P


43. ZONE 1 ELECTRICAL de IIC T4 66
(PUMP ROOM) NE10 FIXTURE SYSTEM italsmea 236

4TH DECK LIGHTING LIGHTING EVF-P


44. ZONE 1 LT-PUM-EX6 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) FIXTURE SYSTEM 236

4TH DECK ELT-4DK- LIGHTING LIGHTING Technor EVF-P


45. ZONE 1 ELECTRICAL de IIC T4 66
(PUMP ROOM) PUM5 FIXTURE SYSTEM italsmea 236

4TH DECK LIGHTING LIGHTING KOKOSHA


46. ZONE 1 LT-COC-EX6 ELECTRICAL NO PLATE AT SITE
(PUMP ROOM) FIXTURE SYSTEM CO. LTD

TURBINE FLAT LIGHTING LIGHTING EVF-P


47. ZONE 1 LT-PUM-EX3 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) FIXTURE SYSTEM 218

TURBINE FLAT ELT-4DK- LIGHTING LIGHTING EVF-P


48. ZONE 1 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) PUM4 FIXTURE SYSTEM 218

TURBINE FLAT LIGHTING LIGHTING EVF-P


49. ZONE 1 LT-PUM-NE7 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) FIXTURE SYSTEM 236
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 9 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

TURBINE FLAT LIGHTING LIGHTING KOKOSHA


50. ZONE 1 LT-COC-EX4 ELECTRICAL NO PLATE AT SITE
(PUMP ROOM) FIXTURE SYSTEM CO. LTD

TURBINE FLAT LIGHTING LIGHTING KOKOSHA


51. ZONE 1 LT-COC-EX5 ELECTRICAL NO PLATE AT SITE
(PUMP ROOM) FIXTURE SYSTEM CO. LTD

TURBINE FLAT LIGHTING LIGHTING EVF-P


52. ZONE 1 LT-PUM-EX4 ELECTRICAL italsmea d IIC T6 66
(PUMP ROOM) FIXTURE SYSTEM 236

4TH DECK LIGHTING LIGHTING


53. ZONE 1 JB-EB-15 ELECTRICAL WALSALL e II T6 66
(PUMP ROOM) JUNCTION BOX SYSTEM

UPPER DECK
STARTER PANEL
54. (METERING ZONE 2 DB-001 METERING SKID ELECTRICAL d
(DENSITY PUMP)
SKID)

UPPER DECK
DISTRIBUTION
55. (METERING ZONE 2 DB-002 METERING SKID ELECTRICAL d SAME TAG AT SITE
BOARD
SKID)

UPPER DECK
DISTRIBUTION
56. (METERING ZONE 2 DB-002 METERING SKID ELECTRICAL d SAME TAG AT SITE
BOARD
SKID)

UPPER DECK
DISTRIBUTION
57. (METERING ZONE 2 DB-003 METERING SKID ELECTRICAL d
BOARD
SKID)

UPPER DECK DISTRIBUTION


58. (METERING ZONE 2 DB-004 BOARD (HEAT METERING SKID ELECTRICAL d
SKID) TRACING)
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 10 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK DISTRIBUTION


59. (METERING ZONE 2 DB-005 BOARD (SKID METERING SKID ELECTRICAL d
SKID) LIGHTING)

UPPER DECK
43941- SG165
60. (METERING ZONE 2 MOV-6511A MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
1 30-108
SKID)

UPPER DECK
43941- SG165
61. (METERING ZONE 2 MOV-6511B MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
1 30-109
SKID)

UPPER DECK
43941- SG165
62. (METERING ZONE 2 MOV-6511C MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
1 30-105
SKID)

UPPER DECK
43941- SG165
63. (METERING ZONE 2 MOV-6512A MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
1 30-102
SKID)

UPPER DECK
43941- SG165
64. (METERING ZONE 2 MOV-6512B MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
1 30-101
SKID)

UPPER DECK
43941- SG165
65. (METERING ZONE 2 MOV-6512C MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
1 30-110
SKID)

UPPER DECK
43941- SG165
66. (METERING ZONE 2 MOV-6513A MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
1 30-106
SKID)
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 11 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK
43941- SG165
67. (METERING ZONE 2 MOV-6513B MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
1 30-103
SKID)

UPPER DECK
43941- SG165
68. (METERING ZONE 2 MOV-6513C MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
1 30-104
SKID)

UPPER DECK
43941- SG165
69. (METERING ZONE 2 MOV-6510A MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
1 30-107
SKID)

UPPER DECK
50365
70. (METERING ZONE 2 MOV-6510B MOV METERING SKID ELECTRICAL ROTORK PLATE FADED
EP-2
SKID)

UPPER DECK
NTD9
71. (METERING ZONE 2 PM-6510 MOTOR METERING SKID ELECTRICAL CMG d IIB T4 66
0524-4
SKID)

DISTRIBUTION THE EX EJB-


72. TURRET ZONE 2 410-DB-4002 HEATER ELECTRICAL d IIB T5 66
BOARD ZONE LTD 5B

DISTRIBUTION LIGHTING THE EX EJB-


73. TURRET ZONE 2 410-DB-4003 ELECTRICAL d IIB T5 66
BOARD SYSTEM ZONE LTD 5B

THE EX EJB-
74. TURRET ZONE 2 455-HT-4202 JUNCTION BOX HEATER ELECTRICAL d IIB T5 66
ZONE LTD 5B

455-TFXR- DISTRIBUTION THE EX EJB-


75. TURRET ZONE 2 HEATER ELECTRICAL d IIB T4 66
4004 BOARD ZONE LTD 5B
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 12 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

455-TFXR- DISTRIBUTION LIGHTING THE EX EJB-


76. TURRET ZONE 2 ELECTRICAL d IIB T4 66
4005 BOARD SYSTEM ZONE LTD 5B

455-TFXR- DISTRIBUTION THE EX EJB-


77. TURRET ZONE 2 HEATER ELECTRICAL d IIB T4 66
4006 BOARD ZONE LTD 5B

LIGHTING GTX2
78. TURRET ZONE 2 415-L-4015 FLOODLIGHT ELECTRICAL CLAMOX d IIC T5 67
SYSTEM 20368

LIGHTING GTX2
79. TURRET ZONE 2 415-L-4016 FLOODLIGHT ELECTRICAL CLAMOX d IIC T5 67
SYSTEM 20368

LIGHTING GTX2
80. TURRET ZONE 2 415-L-4017 FLOODLIGHT ELECTRICAL CLAMOX d IIC T5 67
SYSTEM 20368

LIGHTING GTX2
81. TURRET ZONE 2 415-L-4018 FLOODLIGHT ELECTRICAL CLAMOX d IIC T5 67
SYSTEM 20368

LIGHTING GTX2
82. TURRET ZONE 2 415-L-4019 FLOODLIGHT ELECTRICAL CLAMOX d IIC T5 67
SYSTEM 20368

eLLK
LIGHTING LIGHTING
83. TURRET ZONE 2 415-L-4011 ELECTRICAL CEAG 92036/ de IIC T4 66
FIXTURE SYSTEM
36

eLLK
LIGHTING LIGHTING
84. TURRET ZONE 2 415-L-4012 ELECTRICAL CEAG 92036/ de IIC T4 66
FIXTURE SYSTEM
36

eLLK
LIGHTING LIGHTING
85. TURRET ZONE 2 415-L-4013 ELECTRICAL CEAG 92036/ de IIC T4 66
FIXTURE SYSTEM
36
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 13 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

eLLK
LIGHTING LIGHTING
86. TURRET ZONE 2 415-L-4131 ELECTRICAL CEAG 92036/ de IIC T4 66
FIXTURE SYSTEM
36

eLLK
LIGHTING LIGHTING
87. TURRET ZONE 2 415-L-4132 ELECTRICAL CEAG 92036/ de IIC T4 66
FIXTURE SYSTEM
36

eLLK
LIGHTING LIGHTING
88. TURRET ZONE 2 415-L-4133 ELECTRICAL CEAG 92036/ de IIC T4 66
FIXTURE SYSTEM
36

eLLK
LIGHTING LIGHTING
89. TURRET ZONE 2 415-L-4136 ELECTRICAL CEAG 92036/ de IIC T4 66
FIXTURE SYSTEM
36

eLLK
LIGHTING LIGHTING
90. TURRET ZONE 2 415-L-4137 ELECTRICAL CEAG 92036/ de IIC T4 66
FIXTURE SYSTEM
36

eLLK
LIGHTING LIGHTING demb
91. TURRET ZONE 2 415-EL-4157 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
36NIB

eLLK
LIGHTING LIGHTING demb
92. TURRET ZONE 2 415-EL-4160 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
36NIB

eLLK
LIGHTING LIGHTING demb
93. TURRET ZONE 2 415-EL-4177 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
36NIB
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 14 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

eLLK
LIGHTING LIGHTING demb
94. TURRET ZONE 2 415-EL-4178 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
36NIB

eLLK
LIGHTING LIGHTING demb
95. TURRET ZONE 2 415-EL-4183 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
36NIB

eLLK
LIGHTING LIGHTING demb
96. TURRET ZONE 2 415-EL-4184 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
36NIB

JBM-
455-HTJB-
97. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66
4202-01
EP

JBM-
455-HTJB-
98. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-02
EP

JBM-
455-HTJB-
99. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-03
EP

JBM-
455-HTJB-
100. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-04-A
EP

JBM-
455-HTJB-
101. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-04-B
EP
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 15 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

JBM-
455-HTJB-
102. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-04-C
EP

JBM-
455-HTJB-
103. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-05-A
EP

JBM-
455-HTJB-
104. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-05-B
EP

JBM-
455-HTJB-
105. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-05-C
EP

JBM-
455-HTJB-
106. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-06
EP

JBM-
455-HTJB-
107. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-07
EP

JBM-
455-HTJB-
108. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66 PLATE FADED
4202-08
EP

415-EJB- LIGHTING LIGHTING


109. TURRET ZONE 2 ELECTRICAL Weidmuller e IIC T6
4154A JUNCTION BOX SYSTEM
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 16 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

415-EJB- LIGHTING LIGHTING


110. TURRET ZONE 2 ELECTRICAL Weidmuller e IIC T6
4158A JUNCTION BOX SYSTEM

LIGHTING LIGHTING
111. TURRET ZONE 2 415-EJB-4161 ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

415-EJB- LIGHTING LIGHTING


112. TURRET ZONE 2 ELECTRICAL Weidmuller e IIC T6
4175A JUNCTION BOX SYSTEM

415-EJB- LIGHTING LIGHTING


113. TURRET ZONE 2 ELECTRICAL Weidmuller e IIC T6
4178A JUNCTION BOX SYSTEM

415-EJB- LIGHTING LIGHTING


114. TURRET ZONE 2 ELECTRICAL Weidmuller e IIC T6
4178B JUNCTION BOX SYSTEM

LIGHTING LIGHTING
115. TURRET ZONE 2 415-EJB-4184 ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

LIGHTING LIGHTING
116. TURRET ZONE 2 415-JB-4010B ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

LIGHTING LIGHTING
117. TURRET ZONE 2 415-JB-4010C ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

LIGHTING LIGHTING
118. TURRET ZONE 2 415-JB-4010D ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

LIGHTING LIGHTING
119. TURRET ZONE 2 415-JB-4100 ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

LIGHTING LIGHTING
120. TURRET ZONE 2 415-JB-4130 ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

LIGHTING LIGHTING
121. TURRET ZONE 2 415-JB-4134 ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 17 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

LIGHTING LIGHTING
122. TURRET ZONE 2 415-JB-4138A ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

LIGHTING LIGHTING
123. TURRET ZONE 2 415-JB-4140A ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

LIGHTING LIGHTING
124. TURRET ZONE 2 415-JB-4141A ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

LIGHTING LIGHTING
125. TURRET ZONE 2 415-JB-4120 ELECTRICAL Weidmuller e IIC T6
JUNCTION BOX SYSTEM

Ellk
LIGHTING LIGHTING
126. TURRET ZONE 2 415-L-4102 ELECTRICAL CEAG 92036/ ed IIC T4 66
FIXTURE SYSTEM
36

Ellk
LIGHTING LIGHTING
127. TURRET ZONE 2 415-L-4103 ELECTRICAL CEAG 92036/ ed IIC T4 66
FIXTURE SYSTEM
36

eLLK
LIGHTING LIGHTING ed m
128. TURRET ZONE 2 415-EL-4155 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
129. TURRET ZONE 2 415-EL-4156 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
130. TURRET ZONE 2 415-EL-4158 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 18 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

eLLK
LIGHTING LIGHTING ed m
131. TURRET ZONE 2 415-EL-4159 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
132. TURRET ZONE 2 415-EL-4161 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
133. TURRET ZONE 2 415-EL-4162 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
134. TURRET ZONE 2 415-EL-4163 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
135. TURRET ZONE 2 415-EL-4175 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
136. TURRET ZONE 2 415-EL-4176 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
137. TURRET ZONE 2 415-EL-4179 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
138. TURRET ZONE 2 415-EL-4180 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 19 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

eLLK
LIGHTING LIGHTING ed m
139. TURRET ZONE 2 415-EL-4181 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
140. TURRET ZONE 2 415-EL-4182 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
141. TURRET ZONE 2 415-EL-4185 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
142. TURRET ZONE 2 415-EL-4186 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
143. TURRET ZONE 2 415-EL-4187 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
144. TURRET ZONE 2 415-EL-4188 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

eLLK
LIGHTING LIGHTING ed m
145. TURRET ZONE 2 415-L-4101 ELECTRICAL CEAG 92036/ IIC T4 66
FIXTURE SYSTEM ib
18NIB

LIGHTING LIGHTING VEERSTEEG


146. TURRET ZONE 2 415-L-4135 ELECTRICAL emb II T4 66
FIXTURE SYSTEM 17
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 20 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

LIGHTING LIGHTING VEERSTEEG


147. TURRET ZONE 2 415-L-4138 ELECTRICAL emb II T4 66
FIXTURE SYSTEM 17

LIGHTING VEERSTEEG
148. TURRET ZONE 2 415-L-4014 FLOODLIGHT ELECTRICAL me II T4 66
SYSTEM 17

OBSTRUCTION LIGHTING EQUIPMENT


149. TURRET ZONE 2 415-L-4139 ELECTRICAL
LIGHT SYSTEM BEYOND REACH

Ellk
LIGHTING LIGHTING
150. TURRET ZONE 2 415-L-4141 ELECTRICAL CEAG 92036/ ed IIC T4 66
FIXTURE SYSTEM
36

Ellk
LIGHTING LIGHTING
151. TURRET ZONE 2 415-L-4142 ELECTRICAL CEAG 92036/ ed IIC T4 66
FIXTURE SYSTEM
36

Ellk
LIGHTING LIGHTING
152. TURRET ZONE 2 415-L-4143 ELECTRICAL CEAG 92036/ ed IIC T4 66
FIXTURE SYSTEM
36

Ellk
LIGHTING LIGHTING
153. TURRET ZONE 2 415-L-4144 ELECTRICAL CEAG 92036/ ed IIC T4 66
FIXTURE SYSTEM
36

Ellk
LIGHTING LIGHTING
154. TURRET ZONE 2 415-L-4145 ELECTRICAL CEAG 92036/ ed IIC T4 66
FIXTURE SYSTEM
36

Ellk
LIGHTING LIGHTING
155. TURRET ZONE 2 415-L-4146 ELECTRICAL CEAG 92036/ ed IIC T4 66
FIXTURE SYSTEM
36
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 21 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

Ellk
LIGHTING LIGHTING
156. TURRET ZONE 2 415-L-4121 ELECTRICAL CEAG 92018/ ed IIC T4 66
FIXTURE SYSTEM
18

Ellk
LIGHTING LIGHTING
157. TURRET ZONE 2 415-L-4122 ELECTRICAL CEAG 92036/ ed IIC T4 66
FIXTURE SYSTEM
36

Ellk
LIGHTING LIGHTING
158. TURRET ZONE 2 415-L-4123 ELECTRICAL CEAG 92036/ ed IIC T4 66
FIXTURE SYSTEM
36

JBM-
455-HTJB-
159. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66
4201-04
EP

JBM-
455-HTJB-
160. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66
4201-05
EP

JBM-
455-HTJB-
161. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66
4201-03-A
EP

JBM-
455-HTJB-
162. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66
4201-03-B
EP

JBM-
455-HTJB-
163. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66
4201-01
EP
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 22 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

JBM-
455-HTJB-
164. TURRET ZONE 2 JUNCTION BOX HEATER ELECTRICAL Raychem 100- e IIC T6 66
4010-D
EP

UPPER DECK TERMI


165. (METERING ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON NATO e II T4 66 NO TAG AT SITE
SKID) R ZP

UPPER DECK TERMI


166. (METERING ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON NATO e II T4 66 NO TAG AT SITE
SKID) R ZP

UPPER DECK TERMI


167. (METERING ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON NATO e II T4 66 NO TAG AT SITE
SKID) R ZP

UPPER DECK TERMI


168. (METERING ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON NATO e II T4 66 NO TAG AT SITE

SKID) R ZP

UPPER DECK TERMI


169. (METERING ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON NATO e II T4 66 NO TAG AT SITE
SKID) R ZP

UPPER DECK TERMI


170. (METERING ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON NATO e II T4 66 NO TAG AT SITE
SKID) R ZP

UPPER DECK TERMI


171. (METERING ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON NATO e II T4 66 NO TAG AT SITE
SKID) R ZP
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 23 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK TERMI


172. (METERING ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON NATO e II T4 66 NO TAG AT SITE
SKID) R ZP

UPPER DECK TERMI


173. (METERING ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON NATO e II T4 66 NO TAG AT SITE
SKID) R ZP

UPPER DECK TERMI


174. (METERING ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON NATO e II T4 66 NO TAG AT SITE
SKID) R ZP

UPPER
ELLK
DE+B175:B185C LIGHTING LIGHTING
175. ZONE 2 LT-U-MS4 ELECTRICAL CEAG 92036/ d IIC T4 66 NO TAG AT SITE
K (METERING FIXTURE SYSTEM
36
SKID)

UPPER DECK ELLK


LIGHTING LIGHTING
176. (METERING ZONE 2 LT-U-MS5 ELECTRICAL CEAG 92036/ d IIC T4 66 NO TAG AT SITE
FIXTURE SYSTEM
SKID) 36

UPPER DECK ELLK


LIGHTING LIGHTING
177. (METERING ZONE 2 LT-U-MS6 ELECTRICAL CEAG 92036/ d IIC T4 66 NO TAG AT SITE
FIXTURE SYSTEM
SKID) 36

UPPER DECK ELLK


LIGHTING LIGHTING
178. (METERING ZONE 2 LT-U-MS7 ELECTRICAL CEAG 92036/ d IIC T4 66 NO TAG AT SITE
FIXTURE SYSTEM
SKID) 36
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 24 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK ELLK


LIGHTING LIGHTING
179. (METERING ZONE 2 LT-U-MS8 ELECTRICAL CEAG 92036/ d IIC T4 66 NO TAG AT SITE
FIXTURE SYSTEM
SKID) 36

UPPER DECK ELLK


LIGHTING LIGHTING de Mb
180. (METERING ZONE 2 ELT-U-MS3 ELECTRICAL CEAG 92036/ IIC T4 66 NO TAG AT SITE
FIXTURE SYSTEM ib
SKID) 36NIB

UPPER DECK ELLK


LIGHTING LIGHTING de Mb
181. (METERING ZONE 2 ELT-U-MS4 ELECTRICAL CEAG 92036/ IIC T4 66 NO TAG AT SITE
FIXTURE SYSTEM ib
SKID) 36NIB

UPPER DECK ELLK


LIGHTING LIGHTING de Mb
182. (METERING ZONE 2 ELT-U-MS5 ELECTRICAL CEAG 92036/ IIC T4 66 NO TAG AT SITE
FIXTURE SYSTEM ib
SKID) 36NIB

UPPER DECK ELLK


LIGHTING LIGHTING de Mb
183. (METERING ZONE 2 ELT-U-MS6 ELECTRICAL CEAG 92036/ IIC T4 66 NO TAG AT SITE
FIXTURE SYSTEM ib
SKID) 36NIB

UPPER DECK ELLK


LIGHTING LIGHTING de Mb
184. (METERING ZONE 2 ELT-U-MS7 ELECTRICAL CEAG 92036/ IIC T4 66 NO TAG AT SITE
FIXTURE SYSTEM ib
SKID) 36NIB

WALSALL

FLOODLIGHT LIGHTING LTD WEST TYPE


185. UPPER DECK ZONE 1 JB-FL-01 ELECTRICAL e II T6 66 NO TAG AT SITE
JUNCTION BOX SYSTEM BROMWICH GL501
U.K

FLOODLIGHT LIGHTING WALSALL TYPE


186. UPPER DECK ZONE 1 JB-FL-02 ELECTRICAL e II T6 66 NO TAG AT SITE
JUNCTION BOX SYSTEM LTD WEST GL501
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 25 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

BROMWICH
U.K

WALSALL
FLOODLIGHT LIGHTING LTD WEST TYPE
187. UPPER DECK ZONE 1 JB-FL-03 ELECTRICAL e II T6 66 NO TAG AT SITE
JUNCTION BOX SYSTEM BROMWICH GL501
U.K

WALSALL
FLOODLIGHT LIGHTING LTD WEST TYPE
188. UPPER DECK ZONE 1 JB-FL-04 ELECTRICAL e II T6 66 NO TAG AT SITE
JUNCTION BOX SYSTEM BROMWICH GL501
U.K

ISOLATOR
189. UPPER DECK ZONE 1 GAS SCRUBBER ELECTRICAL STAHL e II T6 66 NO TAG AT SITE
HEATER

FATI-
ELECTRICAL
190. UPPER DECK ZONE 1 GAS SCRUBBER ELECTRICAL CUSAGO (MI) d IIB T3 66 NO TAG AT SITE
HEATER BUNDLE
ITALY

FATI-
JUNCTION BOX,
191. UPPER DECK ZONE 1 GAS SCRUBBER ELECTRICAL CUSAGO (MI) d IIB T3 66 NO TAG AT SITE
HEATER
ITALY

WALSALL
UPPER DECK
FLOODLIGHT LIGHTING LTD WEST TYPE
192. (SKID OILY ZONE 1 JB-FL-01 ELECTRICAL e II T6 66 NO TAG AT SITE
JUNCTION BOX SYSTEM BROMWICH GL501
WATER)
U.K

ELECTRICAL ELECTRICAL OILY


193. UPPER DECK ZONE 1 ELECTRICAL Weidmuller e IIC T6 NO TAG AT SITE
JB JUNCTION BOX SEPARATOR
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 26 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

SMALL POWER
NO TAG & PLATE AT
194. TURRET ZONE 2 415-M4150 SOCKET OUTLET DISTRIBUTION ELECTRICAL
SITE
SYSTEM
195. TURRET ZONE 2 840-JB-2001 JUNCTION BOX HPU ELECTRICAL d NO PLATE AT SITE
196. TURRET ZONE 2 840-M-2001 JUNCTION BOX HPU ELECTRICAL e NO PLATE AT SITE
197. TURRET ZONE 2 840-JB-2002 JUNCTION BOX HPU ELECTRICAL e NO PLATE AT SITE
198. TURRET ZONE 2 840-JB-2003 JUNCTION BOX HPU ELECTRICAL e NO PLATE AT SITE
199. TURRET ZONE 2 325-PM-1091 PUMP MOTOR HPU ELECTRICAL NO PLATE AT SITE
200. TURRET ZONE 2 840-PM-2091 PUMP MOTOR HPU ELECTRICAL NO PLATE AT SITE
201. TURRET ZONE 2 840-PM-2092 PUMP MOTOR HPU ELECTRICAL NO PLATE AT SITE

PRGN
/236/B

C DECK LIGHTING LIGHTING Chalmit I-


202. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B

I/EM

PRGN
/236/B

C DECK LIGHTING LIGHTING Chalmit I-


203. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

C DECK LIGHTING LIGHTING Chalmit PRGN


204. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting /236/B
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 27 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

I-
PRGN
/236/B
I/EM

PRGN
/236/B
C DECK LIGHTING LIGHTING Chalmit I-
205. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
/236/B

C DECK LIGHTING LIGHTING Chalmit I-


206. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B

I/EM

PRGN
/236/B

C DECK LIGHTING LIGHTING Chalmit I-


207. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B

I/EM

PRGN
C DECK LIGHTING LIGHTING Chalmit
208. ZONE 2 ELECTRICAL /236/B nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting
I-
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 28 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

PRGN
/236/B
I/EM

PRGN
/236/B
C DECK LIGHTING LIGHTING Chalmit I-
209. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
/236/B
C DECK LIGHTING LIGHTING Chalmit I-
210. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
/236/B
C DECK LIGHTING LIGHTING Chalmit I-
211. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
C DECK LIGHTING LIGHTING Chalmit /236/B
212. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting I-
PRGN
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 29 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

/236/B
I/EM

PRGN
/236/B
C DECK LIGHTING LIGHTING Chalmit I-
213. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
/236/B
C DECK LIGHTING LIGHTING Chalmit I-
214. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
/236/B
B & C DECK LIGHTING LIGHTING Chalmit I-
215. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
B & C DECK LIGHTING LIGHTING Chalmit /236/B
216. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting I-
PRGN
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 30 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

/236/B
I/EM

PRGN
/236/B
B & C DECK LIGHTING LIGHTING Chalmit I-
217. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
/236/B
B & C DECK LIGHTING LIGHTING Chalmit I-
218. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
/236/B
B & C DECK LIGHTING LIGHTING Chalmit I-
219. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
B & C DECK LIGHTING LIGHTING Chalmit /236/B
220. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting I-
PRGN
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 31 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

/236/B
I/EM

PRGN
/236/B
B & C DECK LIGHTING LIGHTING Chalmit I-
221. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
/236/B
B & C DECK LIGHTING LIGHTING Chalmit I-
222. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
223. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
B DECK LIGHTING LIGHTING Chalmit /236/B
224. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting I-
PRGN
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 32 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
225. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
226. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
227. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
B DECK LIGHTING LIGHTING Chalmit /236/B
228. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting I-
PRGN
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 33 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
229. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
230. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
231. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
B DECK LIGHTING LIGHTING Chalmit /236/B
232. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting I-
PRGN
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 34 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
233. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
234. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
235. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

PRGN
B DECK LIGHTING LIGHTING Chalmit /236/B
236. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting I-
PRGN
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 35 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
237. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN
/236/B
I/EM

PRGN
/236/B
B DECK LIGHTING LIGHTING Chalmit I-
238. ZONE 2 ELECTRICAL nA II T4 66 NO TAG AT SITE
(BOILER AREA) FIXTURE SYSTEM Lighting PRGN

/236/B
I/EM

UPPER DECK
LIGHTING AQUAL 10760
239. (METERING ZONE 2 NLT-MS-FL32 FLOODLIGHT ELECTRICAL 67 NO EX INFO.
SYSTEM SIGNAL 30000
SKID)

CROWCON Xguar
FIRE & GAS W107
NAV BRIDGE DETECTION d
240. ZONE 2 GD-001 GAS DETECTOR DETECTION INSTRUMENT 40210 d IIC T4 66
DECK INSTRUMEN (Type3
SYSTEM 1-10
T )

CROWCON Xguar
FIRE & GAS
DETECTION d
241. D DECK ZONE 2 GD-003 GAS DETECTOR DETECTION INSTRUMENT d IIC T4 66 PLATE FADED
INSTRUMEN (Type3
SYSTEM
T )
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 36 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

CROWCON Xguar
FIRE & GAS W106
DETECTION d
242. D DECK ZONE 2 GD-004 GAS DETECTOR DETECTION INSTRUMENT 855/01 d IIC T4 66
INSTRUMEN (Type3
SYSTEM -10
T )

FIRE & GAS


SMOKE
243. D DECK ZONE 2 A015 DETECTION INSTRUMENT TYCO ia IIC T5
DETECTOR
SYSTEM

CROWCON
FIRE & GAS
DETECTION Nimbu
244. C DECK ZONE 2 GD-028 GAS DETECTOR DETECTION INSTRUMENT 8675 d IIB+H2 T6
INSTRUMEN s
SYSTEM
T

CROWCON
FIRE & GAS
DETECTION Nimbu
245. C DECK ZONE 2 GD-029 GAS DETECTOR DETECTION INSTRUMENT 8007 d IIB+H2 T6
INSTRUMEN s
SYSTEM
T

CROWCON Xguar
FIRE & GAS
DETECTION d
246. C DECK ZONE 2 GD-010 GAS DETECTOR DETECTION INSTRUMENT d IIC T4 66
INSTRUMEN (Type3
SYSTEM
T )

CROWCON Xguar
FIRE & GAS
DETECTION d
247. C DECK ZONE 2 GD-011 GAS DETECTOR DETECTION INSTRUMENT d IIC T4 66
INSTRUMEN (Type3
SYSTEM
T )
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 37 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

CROWCON Xguar
FIRE & GAS
DETECTION d
248. A DECK ZONE 2 GD-019 GAS DETECTOR DETECTION INSTRUMENT d IIC T4 66
INSTRUMEN (Type3
SYSTEM
T )

CROWCON
FIRE & GAS
UPPER DECK DETECTION Nimbu EQUIPMENT
249. ZONE 2 GD-024 GAS DETECTOR DETECTION INSTRUMENT d IIB+H2 T6 66
(OFF LOADING) INSTRUMEN s BEYOND REACH
SYSTEM
T

FIRE & GAS


UPPER DECK MANUAL CALL THORN CP840
250. ZONE 2 C047 DETECTION INSTRUMENT ia IIC T5 PLATE FADED
(OFF LOADING) POINT SECURITY Ex
SYSTEM

FIRE & GAS


SMOKE
251. UPPER DECK ZONE 1 C040 DETECTION INSTRUMENT TYCO ia IIC T5
DETECTOR
SYSTEM

FIRE & GAS


SMOKE
252. UPPER DECK ZONE 1 C041 DETECTION INSTRUMENT TYCO ia IIC T5
DETECTOR
SYSTEM

FIRE & GAS


MANUAL CALL THORN CP840
253. UPPER DECK ZONE 1 C039 DETECTION INSTRUMENT ia IIC T5
POINT SECURITY Ex
SYSTEM

FIRE & GAS


MANUAL CALL THORN CP840
254. UPPER DECK ZONE 1 C042 DETECTION INSTRUMENT ia IIC T5
POINT SECURITY Ex
SYSTEM
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 38 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

CROWCON
FIRE & GAS
UPPER DECK DETECTION Nimbu
255. ZONE 1 GD-021 GAS DETECTOR DETECTION INSTRUMENT d IIB+H2 T6
(FR55-FR61) INSTRUMEN s
SYSTEM
T

CROWCON
FIRE & GAS
UPPER DECK DETECTION Nimbu
256. ZONE 1 GD-022 GAS DETECTOR DETECTION INSTRUMENT d IIB+H2 T6
(FR55-FR61) INSTRUMEN s
SYSTEM
T

CROWCON
FIRE & GAS
UPPER DECK DETECTION Nimbu
257. ZONE 1 GD-023 GAS DETECTOR DETECTION INSTRUMENT d IIB+H2 T6
(FR55-FR61) INSTRUMEN s
SYSTEM
T

CROWCON
FIRE & GAS
UPPER DECK DETECTION Nimbu
258. ZONE 1 GAS DETECTOR DETECTION INSTRUMENT d IIB+H2 T6 NO TAG AT SITE
(FR55-FR61) INSTRUMEN s
SYSTEM
T

UPPER FIRE & GAS


MANUAL CALL THORN CP840
259. DECK(FR55- ZONE 1 C048 DETECTION INSTRUMENT ia IIC T5 PLATE FADED
POINT SECURITY Ex
FR61) SYSTEM

CROWCON
FIRE & GAS
UPPER DECK DETECTION Nimbu
260. ZONE 1 GD-034 GAS DETECTOR DETECTION INSTRUMENT d IIB+H2 T6
(CRANE) INSTRUMEN s
SYSTEM
T
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 39 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER FIRE & GAS


SMOKE EQUIPMENT
261. DECK(CRANE ZONE 1 C056 DETECTION INSTRUMENT TYCO
DETECTOR BEYOND REACH
OP ROOM) SYSTEM

CROWCON
FIRE & GAS
UPPER DECK DETECTION Nimbu
262. ZONE 1 GD-025 GAS DETECTOR DETECTION INSTRUMENT d IIB+H2 T6
(FR69-FR77) INSTRUMEN s
SYSTEM
T

UPPER FIRE & GAS


SMOKE
263. DECK(FR69- ZONE 1 C050 DETECTION INSTRUMENT TYCO ia IIC T5
DETECTOR
FR77) SYSTEM

UPPER FIRE & GAS


SMOKE
264. DECK(FR69- ZONE 1 C057 DETECTION INSTRUMENT TYCO ia IIC T5 NO PLATE AT SITE
DETECTOR
FR77) SYSTEM

UPPER FIRE & GAS


SMOKE
265. DECK(FR69- ZONE 1 C052 DETECTION INSTRUMENT TYCO ia IIC T5
DETECTOR
FR77) SYSTEM

UPPER FIRE & GAS


SMOKE
266. DECK(FR69- ZONE 1 C058 DETECTION INSTRUMENT TYCO ia IIC T5 PLATE FADED
DETECTOR
FR77) SYSTEM

UPPER FIRE & GAS


MANUAL CALL THORN CP840
267. DECK(FR69- ZONE 1 C049 DETECTION INSTRUMENT ia IIC T5
POINT SECURITY Ex
FR77) SYSTEM
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 40 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER FIRE & GAS


MANUAL CALL THORN CP840
268. DECK(FR69- ZONE 1 C051 DETECTION INSTRUMENT ia IIC T5 PLATE FADED
POINT SECURITY Ex
FR77) SYSTEM

AA-
FIRE & GAS
UPPER DECK AC-
269. ZONE 1 GD-030 GAS DETECTOR DETECTION INSTRUMENT IRMAX NO PLATE AT SITE
(FR75-FR85) 011-
SYSTEM
AC-01

CROWCON
FIRE & GAS
UPPER DECK DETECTION Nimbu 90144
270. ZONE 1 GD-031 GAS DETECTOR DETECTION INSTRUMENT d IIB+H2 T6 66
(FR75-FR85) INSTRUMEN s 7
SYSTEM
T

CROWCON
FIRE & GAS
DETECTION Nimbu
271. TURRET ZONE 2 GD-032 GAS DETECTOR DETECTION INSTRUMENT 12373 d IIB+H2 T6 66
INSTRUMEN s
SYSTEM
T

CROWCON
FIRE & GAS
DETECTION Nimbu EQUIPMENT
272. TURRET ZONE 2 GD-033 GAS DETECTOR DETECTION INSTRUMENT d IIB+H2 T6 66
INSTRUMEN s BEYOND REACH
SYSTEM
T

CROWCON
FIRE & GAS
FLAME DETECTION EQUIPMENT
273. TURRET ZONE 2 C064 DETECTION INSTRUMENT
DETECTOR INSTRUMEN BEYOND REACH
SYSTEM
T
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 41 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

CROWCON
FIRE & GAS
FLAME DETECTION EQUIPMENT
274. TURRET ZONE 2 C065 DETECTION INSTRUMENT
DETECTOR INSTRUMEN BEYOND REACH
SYSTEM
T

FIRE & GAS


MANUAL CALL THORN CP840
275. TURRET ZONE 2 C054 DETECTION INSTRUMENT ia IIC T5 66
POINT SECURITY Ex
SYSTEM

FIRE & GAS


MANUAL CALL THORN M800
276. TURRET ZONE 2 C055 DETECTION INSTRUMENT ia IIC T5 66
POINT SECURITY Ex
SYSTEM

AA-
FIRE & GAS
AC-
277. TURRET ZONE 2 GD-026 GAS DETECTOR DETECTION INSTRUMENT IRMAX NO PLATE AT SITE
011-
SYSTEM
AC-01

FIRE & GAS


BOSUN STORE MANUAL CALL THORN CP840
278. ZONE 1 C053 DETECTION INSTRUMENT ia IIC T5 66
FLAT POINT SECURITY Ex
SYSTEM

CROWCON
FIRE & GAS
BOSUN STORE DETECTION Nimbu
279. ZONE 1 GD-027 GAS DETECTOR DETECTION INSTRUMENT d IIB+H2 T6 66
FLAT INSTRUMEN s
SYSTEM
T

FIRE & GAS


4TH DECK SMOKE EQUIPMENT
280. ZONE 1 C043 DETECTION INSTRUMENT TYCO ia IIC T5
(PUMP ROOM) DETECTOR BEYOND REACH
SYSTEM
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 42 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

FIRE & GAS


4TH DECK SMOKE EQUIPMENT
281. ZONE 1 C044 DETECTION INSTRUMENT TYCO ia IIC T5
(PUMP ROOM) DETECTOR BEYOND REACH
SYSTEM

FIRE & GAS


4TH DECK SMOKE EQUIPMENT
282. ZONE 1 C045 DETECTION INSTRUMENT TYCO ia IIC T5
(PUMP ROOM) DETECTOR BEYOND REACH
SYSTEM

FIRE & GAS


4TH DECK SMOKE EQUIPMENT
283. ZONE 1 C046 DETECTION INSTRUMENT TYCO ia IIC T5
(PUMP ROOM) DETECTOR BEYOND REACH
SYSTEM

FIRE & GAS


3RD DECK GAS HUBBLE HFC
284. ZONE 1 NO.1 DETECTION INSTRUMENT NO EX INFO.
(PUMP ROOM) DETECTOR,CH4 KILLARK 1108
SYSTEM

FIRE & GAS


4TH DECK GAS HUBBLE HFC
285. ZONE 1 NO.2 DETECTION INSTRUMENT NO EX INFO.
(PUMP ROOM) DETECTOR,CH4 KILLARK 1108
SYSTEM

FIRE & GAS


4TH DECK GAS HUBBLE HFC
286. ZONE 1 NO.3 DETECTION INSTRUMENT NO EX INFO.
(PUMP ROOM) DETECTOR,H2S KILLARK 1108
SYSTEM

FIRE & GAS


4TH DECK GAS HUBBLE HFC
287. ZONE 1 NO.4 DETECTION INSTRUMENT NO EX INFO.
(PUMP ROOM) DETECTOR,H2S KILLARK 1108
SYSTEM

FIRE & GAS


4TH DECK GAS HUBBLE HFC
288. ZONE 1 NO.5 DETECTION INSTRUMENT NO EX INFO.
(PUMP ROOM) DETECTOR,CH4 KILLARK 1108
SYSTEM
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 43 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK
JUNCTION BOX
289. (METERING ZONE 2 DJB-001 METERING SKID INSTRUMENT eia II T6 66 NO PLATE AT SITE
(DIGITAL)
SKID)

UPPER DECK
JUNCTION BOX
290. (METERING ZONE 2 DJB-002 METERING SKID INSTRUMENT Weidmuller e II T6 66/67
(DIGITAL)
SKID)

UPPER DECK
JUNCTION BOX
291. (METERING ZONE 2 DJB-003 METERING SKID INSTRUMENT Weidmuller e II T6 66/67
(DIGITAL)
SKID)

UPPER DECK
JUNCTION BOX
292. (METERING ZONE 2 DJB-004 METERING SKID INSTRUMENT Weidmuller e II T6 66/67
(DIGITAL)
SKID)

UPPER DECK
JUNCTION BOX
293. (METERING ZONE 2 DJB-005 METERING SKID INSTRUMENT Weidmuller e II T6 66/67
(FGS)
SKID)

UPPER DECK
JUNCTION BOX
294. (METERING ZONE 2 AJB-001 METERING SKID INSTRUMENT eia II T6 66
(ANALOGUE)
SKID)

UPPER DECK
JUNCTION BOX
295. (METERING ZONE 2 AJB-002 METERING SKID INSTRUMENT Weidmuller e II T6 66/67
(ANALOGUE)
SKID)

UPPER DECK
AUTO SAMPLING
296. (METERING ZONE 2 SP-001 METERING SKID INSTRUMENT JICKOOT NO PLATE AT SITE
PANEL
SKID)
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 44 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK 7835B


MICRO- 35660
297. (METERING ZONE 2 DT-6510A DENSITY METER METERING SKID INSTRUMENT AASA ia IIC T6
MOTION 3
SKID) JTAAX

UPPER DECK 7835B


MICRO- 35660
298. (METERING ZONE 2 DT-6510B DENSITY METER METERING SKID INSTRUMENT AASA ia IIC T6
MOTION 2
SKID) JTAAX

UPPER DECK
FAURE BP201
299. (METERING ZONE 2 FT-6511A FLOW METER METERING SKID INSTRUMENT ia IIC T6 66
HERMAN 54
SKID)

UPPER DECK
FAURE BP201
300. (METERING ZONE 2 FT-6511B FLOW METER METERING SKID INSTRUMENT ia IIC T6 66
HERMAN 54
SKID)

UPPER DECK
FAURE BP201
301. (METERING ZONE 2 FT-6512A FLOW METER METERING SKID INSTRUMENT ia IIC T6 66
HERMAN 54
SKID)

UPPER DECK
FAURE BP201
302. (METERING ZONE 2 FT-6512B FLOW METER METERING SKID INSTRUMENT ia IIC T6 66
HERMAN 54
SKID)

UPPER DECK
FAURE BP201
303. (METERING ZONE 2 FT-6513A FLOW METER METERING SKID INSTRUMENT ia IIC T6 66
HERMAN 54
SKID)

UPPER DECK
FAURE BP201
304. (METERING ZONE 2 FT-6513B FLOW METER METERING SKID INSTRUMENT ia IIC T6 66
HERMAN 54
SKID)
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 45 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK
TEMPERATURE YTA11
305. (METERING ZONE 2 TT-6511 METERING SKID INSTRUMENT YOKOGAWA ia IIC T5 67
TRANSMITTER 0
SKID)

UPPER DECK
TEMPERATURE YTA11
306. (METERING ZONE 2 TT-6512 METERING SKID INSTRUMENT YOKOGAWA ia IIC T5 67
TRANSMITTER 0
SKID)

UPPER DECK
TEMPERATURE YTA11
307. (METERING ZONE 2 TT-6513 METERING SKID INSTRUMENT YOKOGAWA ia IIC T5 67
TRANSMITTER 0
SKID)

UPPER DECK
TEMPERATURE YTA11
308. (METERING ZONE 2 TT-6510A METERING SKID INSTRUMENT YOKOGAWA ia IIC T5 67
TRANSMITTER 0
SKID)

UPPER DECK
TEMPERATURE YTA11
309. (METERING ZONE 2 TT-6510B METERING SKID INSTRUMENT YOKOGAWA ia IIC T5 67
TRANSMITTER 0
SKID)

UPPER DECK
TEMPERATURE YTA11
310. (METERING ZONE 2 TT-6510C METERING SKID INSTRUMENT YOKOGAWA ia IIC T5 67
TRANSMITTER 0
SKID)

UPPER DECK
PRESSURE EXJ53
311. (METERING ZONE 2 PT-6511 METERING SKID INSTRUMENT YOKOGAWA ia IIC T4 67
TRANSMITTER 0A
SKID)

UPPER DECK
PRESSURE EXJ53
312. (METERING ZONE 2 PT-6512 METERING SKID INSTRUMENT YOKOGAWA ia IIC T4 67
TRANSMITTER 0A
SKID)
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 46 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK
PRESSURE EXJ53
313. (METERING ZONE 2 PT-6513 METERING SKID INSTRUMENT YOKOGAWA ia IIC T4 67
TRANSMITTER 0A
SKID)

UPPER DECK
PRESSURE EXJ53
314. (METERING ZONE 2 PT-6510A METERING SKID INSTRUMENT YOKOGAWA ia IIC T4 67
TRANSMITTER 0A
SKID)

UPPER DECK
PRESSURE EXJ53
315. (METERING ZONE 2 PT-6510B METERING SKID INSTRUMENT YOKOGAWA ia IIC T4 67
TRANSMITTER 0A
SKID)

UPPER DECK
PRESSURE EXJ53
316. (METERING ZONE 2 PT-6510C METERING SKID INSTRUMENT YOKOGAWA ia IIC T4 67
TRANSMITTER 0A
SKID)

UPPER DECK
DP EJX11
317. (METERING ZONE 2 PDT-6511 METERING SKID INSTRUMENT YOKOGAWA ia IIC T4 67
TRANSMITTER 0A
SKID)

UPPER DECK
DP EJX11
318. (METERING ZONE 2 PDT-6512 METERING SKID INSTRUMENT YOKOGAWA ia IIC T4 67
TRANSMITTER 0A
SKID)

UPPER DECK
DP EJX11
319. (METERING ZONE 2 PDT-6513 METERING SKID INSTRUMENT YOKOGAWA ia IIC T4 67
TRANSMITTER 0A
SKID)

UPPER DECK
CONTROL VALVE SP014
320. (METERING ZONE 2 FY-6511 METERING SKID INSTRUMENT ROTORK ia IIC T4 66
POSITIONER 2
SKID)
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 47 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK
CONTROL VALVE SP014
321. (METERING ZONE 2 FY-6512 METERING SKID INSTRUMENT ROTORK ia IIC T4 66
POSITIONER 2
SKID)

UPPER DECK
CONTROL VALVE SP014
322. (METERING ZONE 2 FY-6513 METERING SKID INSTRUMENT ROTORK ia IIC T4 66
POSITIONER 2
SKID)

UPPER DECK
CONTROL VALVE SP014
323. (METERING ZONE 2 FY-6510A METERING SKID INSTRUMENT ROTORK ia IIC T4 66
POSITIONER 2
SKID)

UPPER DECK
10364
324. (METERING ZONE 2 AT-6510 ANALYZER METERING SKID INSTRUMENT THERMO 4200 NO PLATE AT SITE
292-1
SKID)

UPPER DECK
325. (METERING ZONE 2 ZS-6510A LIMIT SWITCH METERING SKID INSTRUMENT PLATE FADED

SKID)

UPPER DECK
326. (METERING ZONE 2 ZS-6510B LIMIT SWITCH METERING SKID INSTRUMENT PLATE FADED
SKID)

UPPER DECK
327. (METERING ZONE 2 ZS-6510C LIMIT SWITCH METERING SKID INSTRUMENT PLATE FADED
SKID)

UPPER DECK
328. (METERING ZONE 2 ZS-6510D LIMIT SWITCH METERING SKID INSTRUMENT PLATE FADED
SKID)
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 48 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK
PRESSURE
329. (METERING ZONE 2 PSH-6510 METERING SKID INSTRUMENT PLATE FADED
SWITCH
SKID)

UPPER DECK
330. (METERING ZONE 2 RO-6510 FLOW SWITCH METERING SKID INSTRUMENT KROHNE H250 ia IIC T6
SKID)

UPPER DECK SOLENOID VALVE


EQUIPMENT INSIDE
331. (METERING ZONE 2 (AUTO METERING SKID INSTRUMENT
PANEL SP001
SKID) SAMPLING)

UPPER DECK SOLENOID VALVE


EQUIPMENT INSIDE
332. (METERING ZONE 2 (AUTO METERING SKID INSTRUMENT
PANEL SP001
SKID) SAMPLING)

CRUDE OIL PIG


333. TURRET ZONE 2 ZI0102 LIMIT SWITCH INSTRUMENT NO PLATE AT SITE
RECEIVER

TEMPERATURE CRUDE OIL PIG 02170


334. TURRET ZONE 2 TI020B INSTRUMENT ROSEMOUNT 3144P ia IIC T6 66
INDICATOR RECEIVER 058

FIRE & GAS


335. TURRET ZONE 2 840-JB-0323 JUNCTION BOX DETECTION INSTRUMENT Weidmuller TB10 NO PLATE AT SITE
SYSTEM

PRESSURE HEAT TRACING


336. TURRET ZONE 2 PT-0204 INSTRUMENT ROSEMOUNT NO PLATE AT SITE
TRANSMITTER PIPING

HEAT TRACING EQUIPMENT


337. TURRET ZONE 2 ZI-0202 LIMIT SWITCH INSTRUMENT
PIPING BEYOND REACH
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 49 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

LEVEL HEAT TRACING


338. TURRET ZONE 2 LT-1004 INSTRUMENT ROSEMOUNT ia IIC T5 Plate faded
TRANSMITTER PIPING

LEVEL HEAT TRACING


339. TURRET ZONE 2 LI-1004 INSTRUMENT ROSEMOUNT ia IIC T5 Plate faded
TRANSMITTER PIPING

PRESSURE HEAT TRACING


340. TURRET ZONE 2 PT-0104 INSTRUMENT ROSEMOUNT NO PLATE AT SITE
TRANSMITTER PIPING

PRESSURE HEAT TRACING


341. TURRET ZONE 2 TT-0107 INSTRUMENT ROSEMOUNT Plate faded
TRANSMITTER PIPING

EMERGENCY GHG4
342. UPPER DECK ZONE 1 PUSH BUTTON INSTRUMENT CEAG de IIC T6 NO TAG AT SITE
SHUTDOWN 11

EMERGENCY GHG4
343. UPPER DECK ZONE 1 PUSH BUTTON INSTRUMENT CEAG de IIC T6 NO TAG AT SITE
SHUTDOWN 11

EMERSON X
AD117
ANALYZER PROCESS STRE
344. UPPER DECK ZONE 1 GAS SCRUBBER INSTRUMENT 18680 de IIB+H2 T4 66 NO TAG AT SITE
PANEL MANAGEME AM
42
NT FD-1R

EMERSON X
AD117
ANALYZER PROCESS STRE
345. UPPER DECK ZONE 1 GAS SCRUBBER INSTRUMENT 18680 de IIB+H2 T4 66 NO TAG AT SITE
PANEL MANAGEME AM
41
NT FD-1R
346. UPPER DECK ZONE 1 FG-ZHS-008 LIMIT SWITCH GAS SCRUBBER INSTRUMENT NO PLATE AT SITE
347. UPPER DECK ZONE 1 DS-JB001 JUNCTION BOX GAS SCRUBBER INSTRUMENT NO PLATE AT SITE
348. UPPER DECK ZONE 1 DS-JB001 JUNCTION BOX GAS SCRUBBER INSTRUMENT NO PLATE AT SITE
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 50 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

FLOW CONTROL INVEN 83/038


349. UPPER DECK ZONE 1 FG-FCV-001 GAS SCRUBBER INSTRUMENT ECKARDT ia IIB T6
VALVE SYS 640

LEVEL
350. UPPER DECK ZONE 1 GAS SCRUBBER INSTRUMENT ROSEMOUNT ia IIC T4 66 NO TAG AT SITE
TRANSMITTER

LEVEL SWITCH D6943


351. UPPER DECK ZONE 1 GAS SCRUBBER INSTRUMENT KSR KUBLER ia IIC T6 NO TAG AT SITE
HIGH 9

LEVEL SWITCH D6943


352. UPPER DECK ZONE 1 GAS SCRUBBER INSTRUMENT KSR KUBLER ia IIC T6 NO TAG AT SITE
LOW 9

ESO-
100
12025
M1A0.
353. UPPER DECK ZONE 1 FG-ZSL-002 LIMIT SWITCH GAS SCRUBBER INSTRUMENT EL-O-MATIC 7090/0 NO PLATE AT SITE
A.00N
8
0 11 2
GD

5PM-
A5-
PRESSURE M2-
354. UPPER DECK ZONE 1 IA-PSL-001 GAS SCRUBBER INSTRUMENT SOR PLATE FADED
SWITCH LOW C2A-
P/PPS
PA1

5PM-
PRESSURE A5-
355. UPPER DECK ZONE 1 FG-PSL-003 GAS SCRUBBER INSTRUMENT SOR PLATE FADED
SWITCH LOW M2-
C2A-
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 51 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

P/PPS
PA1

PRESSURE
356. UPPER DECK ZONE 1 DIFFRENCE GAS SCRUBBER INSTRUMENT ROSEMOUNT 3051 ia IIC T5 66 NO TAG AT SITE
TRANSMITTER

PRESSURE FIELD
357. UPPER DECK ZONE 1 FG-PCV-001 GAS SCRUBBER INSTRUMENT FISHER NO PLATE AT SITE
CONTROL VALVE VUE

PRESSURE
358. UPPER DECK ZONE 1 GAS SCRUBBER INSTRUMENT ROSEMOUNT d IIC T5 66 NO TAG AT SITE
TRANSMITTER

644SA
TEMPERATURE
359. UPPER DECK ZONE 1 FG-TIT-003 GAS SCRUBBER INSTRUMENT ROSEMOUNT I1XAM ia IIC T5
TRANSMITTER
5Q4

5PM-
A5-
PRESSURE M2-
360. UPPER DECK ZONE 1 FG-PS-004 GAS SCRUBBER INSTRUMENT SOR PLATE FADED
SWITCH LOW C2A-
P/PPS
PA1

UNITED
HIGH OPERATING
OILY ELECTRIC
361. UPPER DECK ZONE 1 HPS PRESSURE INSTRUMENT e IIC T6 66 NO TAG AT SITE
SEPARATOR CONTROLS
SWITCH
CO
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 52 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UNITED
LOW AIR
OILY ELECTRIC
362. UPPER DECK ZONE 1 LPS PRESSURE INSTRUMENT e IIC T6 66 NO TAG AT SITE
SEPARATOR CONTROLS
SWITCH
CO

CONTROL OILY 27500-


363. UPPER DECK ZONE 1 CONTROL PANEL INSTRUMENT ADALET d IIB 66 NO TAG AT SITE
PANEL SEPARATOR J509

LS320
N-
1.00-
LS
CONTROL OIL SENSING OILY S6-
364. UPPER DECK ZONE 1 INSTRUMENT DELTA 70450- d IIC T4 NO TAG AT SITE
PANEL PROBE SEPARATOR 2.00-
2
220-

LE-00-
S

LIMIT SWITCH OILY Velba ( Body NO TAG & PLATE AT


365. UPPER DECK ZONE 1 AOV 1 INSTRUMENT
VALVE SEPARATOR valve) SITE

LIMIT SWITCH OILY Velba ( Body NO TAG & PLATE AT


366. UPPER DECK ZONE 1 AOV 2 INSTRUMENT
VALVE SEPARATOR valve) SITE

LIMIT SWITCH OILY Velba ( Body NO TAG & PLATE AT


367. UPPER DECK ZONE 1 AOV 3 INSTRUMENT
VALVE SEPARATOR valve) SITE

OILY NO TAG & PLATE AT


368. UPPER DECK ZONE 1 AOV 1 SOLENOID JB INSTRUMENT
SEPARATOR SITE

OILY NO TAG & PLATE AT


369. UPPER DECK ZONE 1 AOV 2 SOLENOID JB INSTRUMENT
SEPARATOR SITE
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 53 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

OILY NO TAG & PLATE AT


370. UPPER DECK ZONE 1 AOV 3 SOLENOID JB INSTRUMENT
SEPARATOR SITE
371. TURRET ZONE 2 325-LS-1091 LEVEL SWITCH HPU INSTRUMENT NO PLATE AT SITE
372. TURRET ZONE 2 325-LS-2091 LEVEL SWITCH HPU INSTRUMENT NO PLATE AT SITE

PRESSURE
373. TURRET ZONE 2 840-PS-2093 HPU INSTRUMENT NO PLATE AT SITE
SWITCH

PRESSURE
374. TURRET ZONE 2 840-PS-2094 HPU INSTRUMENT NO PLATE AT SITE
SWITCH

PRESSURE
375. TURRET ZONE 2 840-PS-2095 HPU INSTRUMENT NO PLATE AT SITE
SWITCH

CORTEM SX-
376. TURRET ZONE 2 325-LS-2093 LEVEL SWITCH HPU INSTRUMENT d IIC T6 66
GROUP 26.1N

CORTEM SX-
377. TURRET ZONE 2 325-LS-2093 LEVEL SWITCH HPU INSTRUMENT d IIC T6 66
GROUP 26.1N

PRESSURE
378. TURRET ZONE 2 325-PT-1094 HPU INSTRUMENT NO PLATE AT SITE
TRANSMITTER

FLUID
379. TURRET ZONE 2 325-SV-0101 SOLENOID VLAVE HPU INSTRUMENT BIFOLD POWE d 66

FLUID
380. TURRET ZONE 2 325-SV-0201 SOLENOID VLAVE HPU INSTRUMENT BIFOLD POWE d 66
R

3RD DECK PRESSURE FM9,PUMP UNITED JI20-


381. ZONE 1 FM-3RDPC-4 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM ELECTRIC 704
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 54 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

CONTROLS
CO

UNITED
3RD DECK PRESSURE FM8,PUMP ELECTRIC JI20-
382. ZONE 1 FM-3RDPC-3 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704
CO

UNITED
3RD DECK PRESSURE FM7,PUMP ELECTRIC JI20-
383. ZONE 1 FM-3RDPC-2 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704
CO

UNITED
3RD DECK PRESSURE FM6,PUMP ELECTRIC JI20-
384. ZONE 1 FM-3RDPC-1 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704
CO

UNITED
2ND DECK PRESSURE FM2,PUMP ELECTRIC JI20-
385. ZONE 1 FM-2NDPC-1 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704

CO

UNITED
2ND DECK PRESSURE FM3,PUMP ELECTRIC JI20-
386. ZONE 1 FM-2NDPC-2 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704
CO

2ND DECK PRESSURE FM4,PUMP UNITED JI20-


387. ZONE 1 FM-2NDPC-3 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM ELECTRIC 704
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 55 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

CONTROLS
CO

UNITED
2ND DECK PRESSURE FM5,PUMP ELECTRIC JI20-
388. ZONE 1 FM-2NDPC-4 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704
CO

UNITED
1ST DECK PRESSURE FM1,PUMP ELECTRIC JI20-
389. ZONE 1 FM-UDPC-1 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704
CO

UNITED
1ST DECK PRESSURE FM1,PUMP ELECTRIC JI20-
390. ZONE 1 FM-UDPC-2 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704
CO

UNITED
4TH DECK PRESSURE FM10,PUMP ELECTRIC JI20-
391. ZONE 1 FM-4RDPC-1 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704

CO

UNITED
4TH DECK PRESSURE FM11,PUMP ELECTRIC JI20-
392. ZONE 1 FM-4RDPC-2 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704
CO

4TH DECK PRESSURE FM11,PUMP UNITED JI20-


393. ZONE 1 FM-4RDPC-3 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM ELECTRIC 704
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 56 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

CONTROLS
CO

UNITED
4TH DECK PRESSURE FM13,PUMP ELECTRIC JI20-
394. ZONE 1 FM-4RDPC-4 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704
CO

UNITED
4TH DECK PRESSURE FM13,PUMP ELECTRIC JI20-
395. ZONE 1 FM-4RDPC-5 INSTRUMENT d IIC T6 66
(PUMP ROOM) SWITCH LOW ROOM CONTROLS 704
CO

JUNCTION BOX,
4TH DECK JUNCTION BOX,
396. ZONE 1 TEMPERATURE INSTRUMENT e NO TAG AT SITE
(PUMP ROOM) INSTRUMENT
SENSOR

JUNCTION BOX,
4TH DECK JUNCTION BOX,
397. ZONE 1 TEMPERATURE INSTRUMENT e NO TAG AT SITE
(PUMP ROOM) INSTRUMENT
SENSOR

JUNCTION BOX,
4TH DECK JUNCTION BOX,
398. ZONE 1 TEMPERATURE INSTRUMENT e NO TAG AT SITE
(PUMP ROOM) INSTRUMENT
SENSOR

JUNCTION BOX,
4TH DECK JUNCTION BOX,
399. ZONE 1 TEMPERATURE INSTRUMENT e NO TAG AT SITE
(PUMP ROOM) INSTRUMENT
SENSOR
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 57 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

JUNCTION BOX,
4TH DECK JUNCTION BOX,
400. ZONE 1 TEMPERATURE INSTRUMENT e NO TAG AT SITE
(PUMP ROOM) INSTRUMENT
SENSOR

SBB-
B DECK
401. ZONE 2 CA-ZSHL-003 LIMIT SWITCH BOILER INSTRUMENT SWITCHBOX 77M82 ia IIC T6 67
(BOILER AREA)
/4

SBB-
B DECK
402. ZONE 2 CA-ZSHL-005 LIMIT SWITCH BOILER INSTRUMENT SWITCHBOX 77M82 ia IIC T6 67
(BOILER AREA)
/4

PRESSURE
B DECK 3051/3
403. ZONE 2 PS-PDT-202 DIFFRENCE BOILER INSTRUMENT ROSEMOUNT ia IIC t5 65
(BOILER AREA) 001
TRANSMITTER

B DECK JUNCTION BOX, 21031


404. ZONE 2 1H2-SBV-PS BOILER INSTRUMENT ABRECH 518 e II T6 67
(BOILER AREA) INSTRUMENT 9

B DECK
405. ZONE 2 CONTROL VALVE BOILER INSTRUMENT AIR TORQUE ia IIC T6 67 NO TAG AT SITE
(BOILER AREA)

B DECK
406. ZONE 2 H2-SBV-SOL SOLENOID VALVE BOILER INSTRUMENT NORGEN NO PLATE AT SITE
(BOILER AREA)

B DECK JUNCTION BOX, 21031


407. ZONE 2 2H2-SBV-PS BOILER INSTRUMENT ABRECH 518 e II T6 67
(BOILER AREA) INSTRUMENT 9

B DECK
408. ZONE 2 CONTROL VALVE BOILER INSTRUMENT AIR TORQUE ia IIC T6 67 NO TAG AT SITE
(BOILER AREA)

B DECK NO TAG & PLATE AT


409. ZONE 2 SOLENOID VALVE BOILER INSTRUMENT NORGEN
(BOILER AREA) SITE
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 58 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

SBB-
B DECK
410. ZONE 2 CA-SHL-006 LIMIT SWITCH BOILER INSTRUMENT SWITCHBOX 77M82 ia IIC T6 67
(BOILER AREA)
/4

B DECK FEED WATER SIPAR


411. ZONE 2 BOILER 1 INSTRUMENT SIMENS ia/ib IIC T6 66 NO TAG AT SITE
(BOILER AREA) CONTROL VALVE T/PS2

B DECK FEED WATER SIPAR


412. ZONE 2 BOILER 2 INSTRUMENT SIMENS ia/ib IIC T6 66 NO TAG AT SITE
(BOILER AREA) CONTROL VALVE T/PS2

B DECK LEVEL SITRA


413. ZONE 2 FW-PDT-103 BOILER 1 INSTRUMENT SIMENS NO PLATE AT SITE
(BOILER AREA) TRANSMITTER NS P

B DECK LEVEL SITRA


414. ZONE 2 FW-PDT-104 BOILER 1 INSTRUMENT SIMENS NO PLATE AT SITE
(BOILER AREA) TRANSMITTER NS P

B DECK LEVEL SITRA


415. ZONE 2 FW-PDT-203 BOILER 2 INSTRUMENT SIMENS NO PLATE AT SITE
(BOILER AREA) TRANSMITTER NS P

B DECK LEVEL SITRA


416. ZONE 2 FW-PDT-204 BOILER 2 INSTRUMENT SIMENS NO PLATE AT SITE
(BOILER AREA) TRANSMITTER NS P

BOILER NO.1
C DECK 8125/5
417. ZONE 2 LCP-1 LOCAL CONTROL BOILER 1 INSTRUMENT STHAL de IIC T6 66 PLATE FADED
(BOILER AREA) 09
PANEL

C DECK PRESSURE
418. ZONE 2 CA-PSHH-109 BOILER 1 INSTRUMENT PLATE FADED
(BOILER AREA) SWITCH

C DECK PRESSURE 1950- CL 1


419. ZONE 2 CA-PSLL-101 BOILER 1 INSTRUMENT DWYER T5 PLATE FADED
(BOILER AREA) SWITCH 0-6X Div. 1
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 59 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

PRESSURE
C DECK 3051/3
420. ZONE 2 CA-DPT-101 DIFFERENTIAL BOILER 1 INSTRUMENT ROSEMOUNT ia IIC T5 66
(BOILER AREA) 001
TRANSMITTER

5PM-
A5-
C DECK PRESSURE M2-
421. ZONE 2 PS-PSHH-108 BOILER 1 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH C2A-
P/PPS
PA1

C DECK PRESSURE 3051/3


422. ZONE 2 PS-PT-102 BOILER 1 INSTRUMENT ROSEMOUNT ia IIC T5 66
(BOILER AREA) TRANSMITTER 001

5PM-
A5-
C DECK PRESSURE M2-
423. ZONE 2 ASL-PSL-104 BOILER 1 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH C2A-
P/PPS
PA1

C DECK COTSWORLD ES-


424. ZONE 2 ASL-ZSL-107 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


425. ZONE 2 ASL-ZSL-108 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


426. ZONE 2 ASL-ZSL-109 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 60 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK COTSWORLD ES-


427. ZONE 2 ASL-ZSL-110 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
428. ZONE 2 FO-SV-107 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6 PLATE FADED
(BOILER AREA) /ia

C DECK EP000
429. ZONE 2 FO-SV-108 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6 PLATE FADED
(BOILER AREA) /ia

C DECK EP000
430. ZONE 2 FO-SV-109 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6 PLATE FADED
(BOILER AREA) /ia

C DECK EP000
431. ZONE 2 FO-SV-110 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6 PLATE FADED
(BOILER AREA) /ia

C DECK COTSWORLD ES-


432. ZONE 2 FG-ZSL-119 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
433. ZONE 2 FO-SV-119 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6 PLATE FADED
(BOILER AREA) /ia

5PM-
A5-
C DECK PRESSURE M2-
434. ZONE 2 FG-PSLL-101 BOILER 1 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH C2A-
P/PPS

PA1

C DECK FLOW CONTROL FIELD


435. ZONE 2 FG-FCV-151 BOILER 1 INSTRUMENT FISHER NO PLATE AT SITE
(BOILER AREA) VALVE VUE

C DECK 15081
436. ZONE 2 FG-SV-151 SOLENOID VALVE BOILER 1 INSTRUMENT ROSE ia IIC T6 66
(BOILER AREA) 806
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 61 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK PRESSURE 3051/3


437. ZONE 2 FG-PT-101 BOILER 1 INSTRUMENT ROSEMOUNT ia IIC T5 66
(BOILER AREA) TRANSMITTER 001

C DECK PRESSURE 3051/3


438. ZONE 2 FG-PSHH-102 BOILER 1 INSTRUMENT ROSEMOUNT ia IIC T5 66 PLATE FADED
(BOILER AREA) SWITCH 001

C DECK JUNCTION BOX, 8125/2


439. ZONE 2 B1-FG-JB101 BOILER 1 INSTRUMENT STHAL e(a/ib) II T6 66 PLATE FADED
(BOILER AREA) INSTRUMENT 088

CRL
C DECK JUNCTION BOX, HUBBLE
440. ZONE 2 B1-CH-JB101 BOILER 1 INSTRUMENT MOD d IIC T6 66
(BOILER AREA) INSTRUMENT KILLARK
CEN

C DECK
441. ZONE 2 FG-ZSL-115 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK
442. ZONE 2 FG-ZSH-115 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK EP000
443. ZONE 2 CA-SV-115 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK
444. ZONE 2 FG-ZSL-117 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK
445. ZONE 2 FG-ZSH-117 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK EP000
446. ZONE 2 CA-SV-117 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK
447. ZONE 2 FG-ZS-116 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 62 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK NO TAG & PLATE AT


448. ZONE 2 FG-ZSL-XXX LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT
(BOILER AREA) SITE

C DECK NO TAG & PLATE AT


449. ZONE 2 FG-ZSH-XXX LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT
(BOILER AREA) SITE

C DECK EP000
450. ZONE 2 CA-SV-XXX SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6 NO TAG AT SITE
(BOILER AREA) /ia

C DECK
451. ZONE 2 FG-ZSL-120 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK
452. ZONE 2 FG-ZSH-120 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK EP000
453. ZONE 2 CA-SV-120 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK NO TAG & PLATE AT


454. ZONE 2 FG-ZS-XXX LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT
(BOILER AREA) SITE

C DECK FLAME SCANNER


455. ZONE 2 BOILER 1 INSTRUMENT ia IIC T4 NO TAG AT SITE
(BOILER AREA) 1, BURNER 1

C DECK FLAME SCANNER


456. ZONE 2 BOILER 1 INSTRUMENT ia IIC T4 NO TAG AT SITE
(BOILER AREA) 2, BURNER 1

C DECK FLAME SCANNER


457. ZONE 2 BOILER 1 INSTRUMENT ia IIC T4 NO TAG AT SITE
(BOILER AREA) 1, BURNER 2

C DECK FLAME SCANNER


458. ZONE 2 BOILER 1 INSTRUMENT ia IIC T4 NO TAG AT SITE
(BOILER AREA) 2, BURNER 2

C DECK EP000
459. ZONE 2 FG-SV-120 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 63 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK COTSWORLD ES-


460. ZONE 2 FG-ZSHL-120 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
461. ZONE 2 FG-SV-103 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


462. ZONE 2 FG-ZSHL-103 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
463. ZONE 2 FG-SV-101 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


464. ZONE 2 FG-ZSHL-101 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
465. ZONE 2 FG-SV-104 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


466. ZONE 2 FG-ZSHL-104 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
467. ZONE 2 FG-SV-106 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


468. ZONE 2 FG-ZSHL-106 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
469. ZONE 2 FG-SV-102 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


470. ZONE 2 FG-ZSHL-102 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
471. ZONE 2 FG-SV-105 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 64 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK COTSWORLD ES-


472. ZONE 2 FG-ZSHL-105 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

CRL
C DECK JUNCTION BOX, HUBBLE
473. ZONE 2 B1-CH-JB102 BOILER 1 INSTRUMENT MOD d IIC T6 66
(BOILER AREA) INSTRUMENT KILLARK
CEN

C DECK FLOW ENDRESS PROM


474. ZONE 2 FO-FT-101 BOILER 1 INSTRUMENT de(ia) IIC T6 67
(BOILER AREA) TRANSMITTER HAUSER AS40

C DECK FLOW CONTROL FIELD NO TAG & PLATE AT


475. ZONE 2 FG-FCV-152 BOILER 1 INSTRUMENT FISHER
(BOILER AREA) VALVE VUE SITE

C DECK 15081
476. ZONE 2 FG-SV-152 SOLENOID VALVE BOILER 1 INSTRUMENT ROSE ia IIC T6 66
(BOILER AREA) 806

5PM-
A5-
C DECK PRESSURE M2-
477. ZONE 2 FO-PSL-103 BOILER 1 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH C2A-
P/PPS
PA1

5PM-
A5-

C DECK PRESSURE M2-


478. ZONE 2 IA-PSL-106 BOILER 1 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH C2A-
P/PPS
PA1
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 65 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK COTSWORLD ES-


479. ZONE 2 FO-ZSL-111 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


480. ZONE 2 FO-ZSL-112 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


481. ZONE 2 AS-ZSL-113 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


482. ZONE 2 AS-ZSL-114 LIMIT SWITCH BOILER 1 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
483. ZONE 2 FO-SV-111 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK EP000
484. ZONE 2 FO-SV-112 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK EP000
485. ZONE 2 AS-SV-113 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK EP000
486. ZONE 2 AS-SV-114 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

5PM-
A5-

C DECK PRESSURE M2-


487. ZONE 2 AS-PSL-105 BOILER 1 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH C2A-
P/PPS
PA1

C DECK TEMPERATURE NO TAG & PLATE AT


488. ZONE 2 BOILER 1 INSTRUMENT ROSEMOUNT
(BOILER AREA) TRANSMITTER SITE
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 66 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

DXYM
ITTER
C DECK 400-
489. ZONE 2 BIP-DXY-001 ANALYZER BOILER 1 INSTRUMENT ROSEMOUNT d IIC+H2 T6 66
(BOILER AREA) MOC-
QXT4
C

C DECK TEMPERATURE NO TAG & PLATE AT


490. ZONE 2 C8A BOILER 1 INSTRUMENT ROSEMOUNT
(BOILER AREA) TRANSMITTER SITE

C DECK JUNCTION BOX,


491. ZONE 2 B1-CA-JB101 BOILER 1 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) INSTRUMENT

C DECK JUNCTION BOX,


492. ZONE 2 B1-SW-JB101 BOILER 1 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) INSTRUMENT

C DECK JUNCTION BOX,


493. ZONE 2 B1-BUI-JB101 BOILER 1 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) INSTRUMENT

C DECK B1-BS-FL- JUNCTION BOX,


494. ZONE 2 BOILER 1 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) JB101 INSTRUMENT

C DECK B1-FW-FL- JUNCTION BOX,


495. ZONE 2 BOILER 1 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) JB101 INSTRUMENT

C DECK JUNCTION BOX,


496. ZONE 2 B1-FO-JB101 BOILER 1 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) INSTRUMENT

C DECK JUNCTION BOX,


497. ZONE 2 CA-JB001 BOILER 1 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) INSTRUMENT

C DECK B1-BU2- JUNCTION BOX,


498. ZONE 2 BOILER 1 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) JB101 INSTRUMENT
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 67 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK B2-BS-FL- JUNCTION BOX,


499. ZONE 2 BOILER 1 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) JB201 INSTRUMENT

BOILER NO.1
C DECK 8125/5
500. ZONE 2 LCP-2 LOCAL CONTROL BOILER 2 INSTRUMENT STHAL de IIC T6 66 PLATE FADED
(BOILER AREA) 09
PANEL

C DECK PRESSURE
501. ZONE 2 CA-PSHH-209 BOILER 2 INSTRUMENT PLATE FADED
(BOILER AREA) SWITCH

C DECK PRESSURE 1950- CL 1


502. ZONE 2 CA-PSLL-201 BOILER 2 INSTRUMENT DWYER T5 PLATE FADED
(BOILER AREA) SWITCH 0-6X Div. 1

PRESSURE
C DECK 3051/3
503. ZONE 2 CA-DPT-201 DIFFERENTIAL BOILER 2 INSTRUMENT ROSEMOUNT ia IIC T5 66
(BOILER AREA) 001
TRANSMITTER

5PM-
A5-
C DECK PRESSURE M2-
504. ZONE 2 PS-PSHH-208 BOILER 2 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH C2A-
P/PPS
PA1

C DECK PRESSURE 3051/3


505. ZONE 2 PS-PT-202 BOILER 2 INSTRUMENT ROSEMOUNT ia IIC T5 66
(BOILER AREA) TRANSMITTER 001

5PM-
C DECK PRESSURE A5-
506. ZONE 2 ASL-PSL-204 BOILER 2 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH M2-
C2A-
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 68 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

P/PPS
PA1

C DECK COTSWORLD ES-


507. ZONE 2 ASL-ZSL-207 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


508. ZONE 2 ASL-ZSL-208 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


509. ZONE 2 ASL-ZSL-209 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


510. ZONE 2 ASL-ZSL-210 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
511. ZONE 2 FO-SV-207 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6 PLATE FADED
(BOILER AREA) /ia

C DECK EP000
512. ZONE 2 FO-SV-208 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6 PLATE FADED
(BOILER AREA) /ia

C DECK EP000
513. ZONE 2 FO-SV-209 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6 PLATE FADED
(BOILER AREA) /ia

C DECK EP000
514. ZONE 2 FO-SV-210 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6 PLATE FADED
(BOILER AREA) /ia

C DECK COTSWORLD ES-


515. ZONE 2 FG-ZSL-219 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
516. ZONE 2 FO-SV-219 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6 PLATE FADED
(BOILER AREA) /ia

C DECK PRESSURE 5PM-


517. ZONE 2 FG-PSLL-201 BOILER 2 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH A5-
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 69 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

M2-
C2A-
P/PPS
PA1

C DECK FLOW CONTROL FIELD


518. ZONE 2 FG-FCV-251 BOILER 2 INSTRUMENT FISHER NO PLATE AT SITE
(BOILER AREA) VALVE VUE

C DECK 15081
519. ZONE 2 FG-SV-251 SOLENOID VALVE BOILER 2 INSTRUMENT ROSE ia IIC T6 66
(BOILER AREA) 806

C DECK PRESSURE 3051/3


520. ZONE 2 FG-PT-201 BOILER 2 INSTRUMENT ROSEMOUNT ia IIC T5 66
(BOILER AREA) TRANSMITTER 001

C DECK PRESSURE 3051/3


521. ZONE 2 FG-PSHH-202 BOILER 2 INSTRUMENT ROSEMOUNT ia IIC T5 66 PLATE FADED
(BOILER AREA) SWITCH 001

C DECK JUNCTION BOX, 8125/2


522. ZONE 2 B2-FG-JB201 BOILER 2 INSTRUMENT STHAL e(a/ib) II T6 66 PLATE FADED
(BOILER AREA) INSTRUMENT 088

CRL
C DECK JUNCTION BOX, HUBBLE
523. ZONE 2 B2-CH-JB201 BOILER 2 INSTRUMENT MOD d IIC T6 66
(BOILER AREA) INSTRUMENT KILLARK
CEN

C DECK
524. ZONE 2 FG-ZSL-215 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK
525. ZONE 2 FG-ZSH-215 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK EP000
526. ZONE 2 CA-SV-215 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 70 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK
527. ZONE 2 FG-ZSL-217 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK
528. ZONE 2 FG-ZSH-217 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK EP000
529. ZONE 2 CA-SV-217 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK
530. ZONE 2 FG-ZS-216 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK NO TAG & PLATE AT


531. ZONE 2 FG-ZSL-XXX LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT
(BOILER AREA) SITE

C DECK NO TAG & PLATE AT


532. ZONE 2 FG-ZSH-XXX LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT
(BOILER AREA) SITE

C DECK EP000
533. ZONE 2 CA-SV-XXX SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6 NO TAG AT SITE
(BOILER AREA) /ia

C DECK
534. ZONE 2 FG-ZSL-220 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK
535. ZONE 2 FG-ZSH-220 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
(BOILER AREA)

C DECK EP000
536. ZONE 2 CA-SV-220 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK NO TAG & PLATE AT


537. ZONE 2 FG-ZS-XXX LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT
(BOILER AREA) SITE

C DECK FLAME SCANNER


538. ZONE 2 BOILER 2 INSTRUMENT ia IIC T4 NO TAG AT SITE
(BOILER AREA) 1, BURNER 1
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 71 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK FLAME SCANNER


539. ZONE 2 BOILER 2 INSTRUMENT ia IIC T4 NO TAG AT SITE
(BOILER AREA) 2, BURNER 1

C DECK FLAME SCANNER


540. ZONE 2 BOILER 2 INSTRUMENT ia IIC T4 NO TAG AT SITE
(BOILER AREA) 1, BURNER 2

C DECK FLAME SCANNER


541. ZONE 2 BOILER 2 INSTRUMENT ia IIC T4 NO TAG AT SITE
(BOILER AREA) 2, BURNER 2

C DECK EP000
542. ZONE 2 FG-SV-220 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


543. ZONE 2 FG-ZSHL-220 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
544. ZONE 2 FG-SV-203 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


545. ZONE 2 FG-ZSHL-203 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
546. ZONE 2 FG-SV-201 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


547. ZONE 2 FG-ZSHL-201 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
548. ZONE 2 FG-SV-204 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


549. ZONE 2 FG-ZSHL-204 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
550. ZONE 2 FG-SV-206 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 72 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK COTSWORLD ES-


551. ZONE 2 FG-ZSHL-206 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
552. ZONE 2 FG-SV-202 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


553. ZONE 2 FG-ZSHL-202 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
554. ZONE 2 FG-SV-205 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK COTSWORLD ES-


555. ZONE 2 FG-ZSHL-205 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

CRL
C DECK JUNCTION BOX, HUBBLE
556. ZONE 2 B2-CH-JB202 BOILER 2 INSTRUMENT MOD d IIC T6 66
(BOILER AREA) INSTRUMENT KILLARK
CEN

C DECK FLOW ENDRESS PROM


557. ZONE 2 FO-FT-201 BOILER 2 INSTRUMENT de(ia) IIC T6 67
(BOILER AREA) TRANSMITTER HAUSER AS40

C DECK FLOW CONTROL FIELD


558. ZONE 2 FG-FCV-252 BOILER 2 INSTRUMENT FISHER NO PLATE AT SITE
(BOILER AREA) VALVE VUE

C DECK 15081
559. ZONE 2 FG-SV-252 SOLENOID VALVE BOILER 2 INSTRUMENT ROSE ia IIC T6 66
(BOILER AREA) 806

5PM-
C DECK PRESSURE A5-
560. ZONE 2 FO-PSL-203 BOILER 2 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH M2-
C2A-
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 73 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

P/PPS
PA1

5PM-
A5-
C DECK PRESSURE M2-
561. ZONE 2 IA-PSL-206 BOILER 2 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH C2A-
P/PPS
PA1

C DECK COTSWORLD ES-


562. ZONE 2 FO-ZSL-211 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


563. ZONE 2 FO-ZSL-212 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


564. ZONE 2 AS-ZSL-213 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK COTSWORLD ES-


565. ZONE 2 AS-ZSL-214 LIMIT SWITCH BOILER 2 INSTRUMENT NO PLATE AT SITE
(BOILER AREA) VALVE 0025

C DECK EP000
566. ZONE 2 FO-SV-211 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK EP000
567. ZONE 2 FO-SV-212 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK EP000
568. ZONE 2 AS-SV-213 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia

C DECK EP000
569. ZONE 2 AS-SV-214 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. ia IIC T6
(BOILER AREA) /ia
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 74 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

5PM-
A5-
C DECK PRESSURE M2-
570. ZONE 2 AS-PSL-205 BOILER 2 INSTRUMENT SOR NO EX INFO.
(BOILER AREA) SWITCH C2A-
P/PPS
PA1

C DECK TEMPERATURE NO TAG & PLATE AT


571. ZONE 2 BOILER 2 INSTRUMENT ROSEMOUNT
(BOILER AREA) TRANSMITTER SITE

DXYM
ITTER
C DECK 400-
572. ZONE 2 BIP-DXY-001 ANALYZER BOILER 2 INSTRUMENT ROSEMOUNT d IIC+H2 T6 66
(BOILER AREA) MOC-

QXT4
C

C DECK TEMPERATURE NO TAG & PLATE AT


573. ZONE 2 C8A BOILER 2 INSTRUMENT ROSEMOUNT
(BOILER AREA) TRANSMITTER SITE

C DECK JUNCTION BOX,


574. ZONE 2 B2-CA-JB201 BOILER 2 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) INSTRUMENT

C DECK JUNCTION BOX,


575. ZONE 2 B2-SW-JB201 BOILER 2 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) INSTRUMENT

C DECK JUNCTION BOX,


576. ZONE 2 B2-BUI-JB201 BOILER 2 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) INSTRUMENT

C DECK B2-BS-FL- JUNCTION BOX,


577. ZONE 2 BOILER 2 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) JB201 INSTRUMENT
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 75 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

C DECK B2-FW-FL- JUNCTION BOX,


578. ZONE 2 BOILER 2 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) JB201 INSTRUMENT

C DECK JUNCTION BOX,


579. ZONE 2 B2-FO-JB201 BOILER 2 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) INSTRUMENT

C DECK B2-BU2- JUNCTION BOX,


580. ZONE 2 BOILER 2 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) JB201 INSTRUMENT

C DECK B2-BS-FL- JUNCTION BOX,


581. ZONE 2 BOILER 2 INSTRUMENT STAHL PLATE FADED
(BOILER AREA) JB202 INSTRUMENT
582. TURRET ZONE 2 840-JB-5012 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
583. TURRET ZONE 2 840-JB-5032 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
584. TURRET ZONE 2 840-JB-0325 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
585. TURRET ZONE 2 840-JB-5013 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
586. TURRET ZONE 2 840-JB-5033 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6

DNH
DSP-
587. TURRET ZONE 2 PA-A5A/12 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
15
NORWAY

DNH
DSP-
588. TURRET ZONE 2 PA-B5A/11 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
15
NORWAY

DNH
HP-
589. TURRET ZONE 2 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 56 NO TAG AT SITE
15(T)
NORWAY
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 76 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

DNH
DSP-
590. TURRET ZONE 2 PA-B5A/10 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67 NO TAG AT SITE
15
NORWAY

DNH
DSP-
591. TURRET ZONE 2 PA-A5A/11 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67 NO TAG AT SITE
15
NORWAY
592. TURRET ZONE 2 840-JB-0303 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
593. TURRET ZONE 2 840-JB-0304 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
594. TURRET ZONE 2 840-JB-1004 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6

UPPER DECK DNH


DSP- NO TAG AT SITE,
595. (STORE LAB ZONE 1 PA-B5A/4 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
15 STORE ROOM LAB
PORT SIDE) NORWAY

DNH
UPPER DECK DSP- NO TAG AT SITE,
596. ZONE 1 PA-A4A/15 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(PAINT ROOM) 15 PAINT STORE
NORWAY

DNH
UPPER DECK DSP- NO TAG AT SITE,
597. ZONE 1 PA-B4A/15 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(PAINT ROOM) 15 PAINT STORE
NORWAY

DNH
UPPER DECK DSP- NO TAG AT SITE,
598. ZONE 1 PA-B4A/15 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(STORE ROOM) 15 STORE ROOM
NORWAY

DNH
UPPER DECK DSP- NO TAG AT SITE,
599. ZONE 1 PA-A4A/14 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(STORE ROOM) 15 STORE ROOM
NORWAY
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 77 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

UPPER DECK DNH


DSP-
600. (OILY WATER ZONE 1 PA-A4A/10 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
15
SAPERATOR) NORWAY

UPPER DECK DNH


DSP-
601. (OILY WATER ZONE 1 PA-B4A/11 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
15
SAPERATOR) NORWAY

DNH
UPPER DECK DSP- NO TAG AT SITE,
602. ZONE 1 PA-A4A/11 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(STAR BOARD) 15 STAR BOARD
NORWAY

DNH
UPPER DECK DSP- NO TAG AT SITE,
603. ZONE 1 PA-B4A/13 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(STAR BOARD) 15 STAR BOARD
NORWAY

DNH
UPPER DECK DSP-
604. ZONE 1 PA-A4A/13 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(STAR BOARD) 15
NORWAY

DNH
UPPER DECK DSP-
605. ZONE 1 PA-B4A/14 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(STAR BOARD) 15
NORWAY

DNH
UPPER DECK DSP-
606. ZONE 1 PA-A4A/17 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(STAR BOARD) 15
NORWAY

DNH
UPPER DECK DSP-
607. ZONE 1 PA-B4A/18 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(STAR BOARD) 15
NORWAY
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 78 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

DNH
UPPER DECK DSP- NO TAG AT SITE,
608. ZONE 1 PA-B4A/17 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(STAR BOARD) 15 STAR BOARD
NORWAY

DNH
UPPER DECK DSP- NO TAG AT SITE,
609. ZONE 1 PA-A4A/16 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(STAR BOARD) 15 STAR BOARD
NORWAY

DNH
UPPER DECK DSP- NO TAG AT SITE,
610. ZONE 1 PA-B5A/7 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(PORT SIDE) 15 PORT SITE
NORWAY

DNH
UPPER DECK DSP- NO TAG AT SITE,
611. ZONE 1 PA-A5A/8 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(PORT SIDE) 15 PORT SITE
NORWAY

UPPER DECK DNH


DSP- NO TAG AT SITE,
612. (STORE LAB ZONE 1 PA-A5A/5 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
15 STORE ROOM LAB
PORT SIDE) NORWAY

DNH
UPPER DECK DSP-
613. ZONE 1 PA-B5A/6 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(PORT SIDE) 15
NORWAY

DNH
UPPER DECK DSP- NO TAG AT SITE,
614. ZONE 1 PA-A5A/3 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(PORT SIDE) 15 PORT SITE
NORWAY

DNH
UPPER DECK DSP-
615. ZONE 1 PA-B5A/3 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(PORT SIDE) 15
NORWAY
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 79 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

DNH
UPPER DECK DSP- NO TAG AT SITE,
616. ZONE 1 PA-A5A/7 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(PORT SIDE) 15 PORT SITE
NORWAY

UPPER DECK DNH


DSP- NO TAG AT SITE,
617. (METERING ZONE 1 PA-A5A/2 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
15 METERING SKID
SKID) NORWAY

UPPER DECK DNH


DSP-
618. (METERING ZONE 1 PA-B5A/2 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
15
SKID) NORWAY

DNH NO TAG AT SITE,


UPPER DECK DSP-
619. ZONE 2 PA-A5A/1 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67 INFRONT PUMP
(PORT SIDE) 15
NORWAY ROOM, PORT SITE

DNH NO TAG AT SITE,


UPPER DECK HP-
620. ZONE 2 PA-B3A/4 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 56 INFRONT PUMP
(PORT SIDE) 15(T)
NORWAY ROOM, PORT SITE

DNH
UPPER DECK DSP-
621. ZONE 2 PA-B4A/10 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(BEHIND GYM) 15
NORWAY

DNH
UPPER DECK HP-
622. ZONE 2 PA-A4A/9 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 56
(STAR BOARD) 15(T)
NORWAY

PELCO EHX8 EQUIPMENT


623. TURRET ZONE 2 CAM-01 CCTV CAMERA CCTV SYSTEM TELECOM EXD IIB - IP66
WORLDWIDE E BEYOND REACH
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 80 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

PELCO EHX8 EQUIPMENT


624. TURRET ZONE 2 CAM-01 CCTV CAMERA CCTV SYSTEM TELECOM EXD IIB - IP66
WORLDWIDE E BEYOND REACH

4TH DECK PELCO EHX8


625. ZONE 1 CAM-03 CCTV CAMERA CCTV SYSTEM TELECOM EXD IIB - IP66
(PUMP ROOM) WORLDWIDE E

4TH DECK PELCO EHX8


626. ZONE 1 CAM-04 CCTV CAMERA CCTV SYSTEM TELECOM EXD IIB - IP66
(PUMP ROOM) WORLDWIDE E

UPPER DECK, PELCO EHX8 EQUIPMENT


627. ZONE 2 CAM-05 CCTV CAMERA CCTV SYSTEM TELECOM EXD IIB - IP66
OFFLOADING WORLDWIDE E BEYOND REACH

FIRE & GAS 31295


4TH DECK NG16
628. ZONE 1 PA-BBA/1 BEACON DETECTION TELECOM MEDC 73200 d IIC T5
(PUMP ROOM) 6JF
SYSTEM 8

DNH
4TH DECK DSP-
629. ZONE 1 PA-A6B/1 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67 NO TAG AT SITE
(PUMP ROOM) 15
NORWAY

DNH
4TH DECK DSP-
630. ZONE 1 PA-B6B/1 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67 NO TAG AT SITE
(PUMP ROOM) 15
NORWAY

RADIO
4TH DECK
631. ZONE 1 LPA-5 REPEATER, PUMP ROOM TELECOM NO PLATE AT SITE
(PUMP ROOM)
WALKIE TALKIE

FIRE & GAS 31295


4TH DECK NG16
632. ZONE 1 PA-ABA/1 BEACON DETECTION TELECOM MEDC 73200 d IIC T5
(PUMP ROOM) 6JF
SYSTEM 8
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 81 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

FIRE & GAS 31295


4TH DECK NG16
633. ZONE 1 PA-ABA/1 BEACON DETECTION TELECOM MEDC 73200 d IIC T5
(PUMP ROOM) 6JF
SYSTEM 8

FIRE & GAS


4TH DECK CORTEM
634. ZONE 1 BEACON DETECTION TELECOM 200 d IIC T1 66 NO TAG AT SITE
(PUMP ROOM) GROUP
SYSTEM

DNH
B DECK DSP-
635. ZONE 2 PA-B4A/6 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(BOILER AREA) 15
NORWAY

FIRE & GAS 31295


B DECK NG16
636. ZONE 2 PA-BBB/1 BEACON DETECTION TELECOM MEDC 73200 d IIC T5
(BOILER AREA) 6JF
SYSTEM 1

DNH
B DECK DSP-
637. ZONE 2 PA-A4A/4 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(BOILER AREA) 15
NORWAY

DNH
C DECK DSP-
638. ZONE 2 PA-B4A/8 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(BOILER AREA) 15
NORWAY

FIRE & GAS 31295


C DECK NG16
639. ZONE 2 PA-BBB/2 BEACON DETECTION TELECOM MEDC 73200 d IIC T5
(BOILER AREA) 6JF
SYSTEM 1

DNH
C DECK DSP-
640. ZONE 2 PA-B4A/6 SPEAKER PA SPEAKER TELECOM KRAGER de IIB+H2 T5 67
(BOILER AREA) 15
NORWAY
SITE VERIFICATION REPORT
FOR EX DATABASE
Prepared by Date Page
Bureau Veritas (M) Sdn Bhd December 2019 82 of 82

Deck/Process Package/System Serial Ex Gas Temp IP


No. Zone Tag No. Equipment Name Discipline Manufacturer Model Remarks
Area Description No Class Group Class Rating

FIRE & GAS 31295


B DECK NG16
641. ZONE 2 PA-ABB/2 BEACON DETECTION TELECOM MEDC 73200 d IIC T5 NO PLATE AT SITE
(BOILER AREA) 6JF
SYSTEM 1

UPPER DECK FIRE & GAS


EQUIPMENT
642. (METERING ZONE 2 BEACON DETECTION TELECOM
BEYOND REACH
SKID) SYSTEM
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 13 of 16
2020

APPENDIX 3 – EX DATABASE POST WORKSHOP


EX Database

Equipment
ID Deck/Process Area Zone Tag Availability (Yes/No) Equipment Name Package/System Description Discipline Manufacturer Model Serial No Ex Class Gas Group Temp Class IP Rating Remarks
Protection Level
1 1ST DECK (PUMP ROOM) ZONE 1 FM-UDPC-1 PRESSURE SWITCH LOW FM1,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
2 1ST DECK (PUMP ROOM) ZONE 1 FM-UDPC-2 PRESSURE SWITCH LOW FM1,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
3 2ND DECK (PUMP ROOM) ZONE 1 ELT-2DK-PUM2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX GTX240469 d IIC T6 67
4 2ND DECK (PUMP ROOM) ZONE 1 LT-COC-EX1 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL KOKOSHA CO. LTD NO PLATE AT SITE
5 2ND DECK (PUMP ROOM) ZONE 1 LT-PUM-NE2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Technor italsmea EVF-P 236 de IIC T4 66 Gb
6 2ND DECK (PUMP ROOM) ZONE 1 LT-COC-EX2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL KOKOSHA CO. LTD NO PLATE AT SITE
7 2ND DECK (PUMP ROOM) ZONE 1 FM-2NDPC-1 PRESSURE SWITCH LOW FM2,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
8 2ND DECK (PUMP ROOM) ZONE 1 FM-2NDPC-2 PRESSURE SWITCH LOW FM3,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
9 2ND DECK (PUMP ROOM) ZONE 1 FM-2NDPC-3 PRESSURE SWITCH LOW FM4,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
10 2ND DECK (PUMP ROOM) ZONE 1 FM-2NDPC-4 PRESSURE SWITCH LOW FM5,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
11 3RD DECK (PUMP ROOM) ZONE 1 LT-PUM-NE3 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Technor italsmea EVF-P 236 de IIC T4 66 Gb
12 3RD DECK (PUMP ROOM) ZONE 1 LT-PUM-NE4 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Technor italsmea EVF-P 236 de IIC T4 66 Gb
13 3RD DECK (PUMP ROOM) ZONE 1 LT-COC-EX3 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL KOKOSHA CO. LTD NO PLATE AT SITE
14 3RD DECK (PUMP ROOM) ZONE 1 ELT-3DK-PUM3 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 218 d IIC T6 66
15 3RD DECK (PUMP ROOM) ZONE 1 ELT-PUM-NE5 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Technor italsmea EVF-P 236 de IIC T4 66 Gb
16 3RD DECK (PUMP ROOM) ZONE 1 LT-PUM-EX2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX GTX240469 d IIC T6 67
17 3RD DECK (PUMP ROOM) ZONE 1 LT-PUM-NE6 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Technor italsmea EVF-P 236 de IIC T4 66 Gb
18 3RD DECK (PUMP ROOM) ZONE 1 NO.1 GAS DETECTOR,CH4 FIRE & GAS DETECTION SYSTEM INSTRUMENT HUBBLE KILLARK HFC 1108 NO EX INFO.
19 3RD DECK (PUMP ROOM) ZONE 1 FM-3RDPC-4 PRESSURE SWITCH LOW FM9,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
20 3RD DECK (PUMP ROOM) ZONE 1 FM-3RDPC-3 PRESSURE SWITCH LOW FM8,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
21 3RD DECK (PUMP ROOM) ZONE 1 FM-3RDPC-2 PRESSURE SWITCH LOW FM7,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
22 3RD DECK (PUMP ROOM) ZONE 1 FM-3RDPC-1 PRESSURE SWITCH LOW FM6,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
23 4TH DECK (PUMP ROOM) ZONE 1 LT-COC-EX7 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL KOKOSHA CO. LTD NO PLATE AT SITE
24 4TH DECK (PUMP ROOM) ZONE 1 ELT-4DK-PUM6 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX GTX240469 d IIC T6 67
25 4TH DECK (PUMP ROOM) ZONE 1 LT-PUM-EX9 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 236 d IIC T6 66
26 4TH DECK (PUMP ROOM) ZONE 1 LT-PUM-NE9 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 236 d IIC T6 66
27 4TH DECK (PUMP ROOM) ZONE 1 LT-PUM-EX8 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 218 d IIC T6 66
28 4TH DECK (PUMP ROOM) ZONE 1 ELT-PUM-NE8 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Technor italsmea EVF-P 236 de IIC T4 66 Gb
29 4TH DECK (PUMP ROOM) ZONE 1 LT-PUM-EX5 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 218 d IIC T6 66
30 4TH DECK (PUMP ROOM) ZONE 1 LT-PUM-EX7 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 218 d IIC T6 66
31 4TH DECK (PUMP ROOM) ZONE 1 LT-PUM-NE10 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Technor italsmea EVF-P 236 de IIC T4 66 Gb
32 4TH DECK (PUMP ROOM) ZONE 1 LT-PUM-EX6 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 236 d IIC T6 66
33 4TH DECK (PUMP ROOM) ZONE 1 ELT-4DK-PUM5 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Technor italsmea EVF-P 236 de IIC T4 66 Gb
34 4TH DECK (PUMP ROOM) ZONE 1 LT-COC-EX6 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL KOKOSHA CO. LTD NO PLATE AT SITE
35 4TH DECK (PUMP ROOM) ZONE 1 JB-EB-15 LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL WALSALL e II T6 66
36 4TH DECK (PUMP ROOM) ZONE 1 C043 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5 EQUIPMENT BEYOND REACH
37 4TH DECK (PUMP ROOM) ZONE 1 C044 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5 EQUIPMENT BEYOND REACH
38 4TH DECK (PUMP ROOM) ZONE 1 C045 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5 EQUIPMENT BEYOND REACH
39 4TH DECK (PUMP ROOM) ZONE 1 C046 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5 EQUIPMENT BEYOND REACH
40 4TH DECK (PUMP ROOM) ZONE 1 NO.2 GAS DETECTOR,CH4 FIRE & GAS DETECTION SYSTEM INSTRUMENT HUBBLE KILLARK HFC 1108 NO EX INFO.
41 4TH DECK (PUMP ROOM) ZONE 1 NO.3 GAS DETECTOR,H2S FIRE & GAS DETECTION SYSTEM INSTRUMENT HUBBLE KILLARK HFC 1108 NO EX INFO.
42 4TH DECK (PUMP ROOM) ZONE 1 NO.4 GAS DETECTOR,H2S FIRE & GAS DETECTION SYSTEM INSTRUMENT HUBBLE KILLARK HFC 1108 NO EX INFO.
43 4TH DECK (PUMP ROOM) ZONE 1 NO.5 GAS DETECTOR,CH4 FIRE & GAS DETECTION SYSTEM INSTRUMENT HUBBLE KILLARK HFC 1108 NO EX INFO.
44 4TH DECK (PUMP ROOM) ZONE 1 FM-4RDPC-1 PRESSURE SWITCH LOW FM10,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
45 4TH DECK (PUMP ROOM) ZONE 1 FM-4RDPC-2 PRESSURE SWITCH LOW FM11,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
46 4TH DECK (PUMP ROOM) ZONE 1 FM-4RDPC-3 PRESSURE SWITCH LOW FM11,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
47 4TH DECK (PUMP ROOM) ZONE 1 FM-4RDPC-4 PRESSURE SWITCH LOW FM13,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
48 4TH DECK (PUMP ROOM) ZONE 1 FM-4RDPC-5 PRESSURE SWITCH LOW FM13,PUMP ROOM INSTRUMENT UNITED ELECTRIC CONTROLS CO JI20-704 d IIC T6 66
49 4TH DECK (PUMP ROOM) ZONE 1 JUNCTION BOX, TEMPERATURE SENSOR JUNCTION BOX, INSTRUMENT INSTRUMENT e NO TAG AT SITE
50 4TH DECK (PUMP ROOM) ZONE 1 JUNCTION BOX, TEMPERATURE SENSOR JUNCTION BOX, INSTRUMENT INSTRUMENT e NO TAG AT SITE
51 4TH DECK (PUMP ROOM) ZONE 1 JUNCTION BOX, TEMPERATURE SENSOR JUNCTION BOX, INSTRUMENT INSTRUMENT e NO TAG AT SITE
52 4TH DECK (PUMP ROOM) ZONE 1 JUNCTION BOX, TEMPERATURE SENSOR JUNCTION BOX, INSTRUMENT INSTRUMENT e NO TAG AT SITE
53 4TH DECK (PUMP ROOM) ZONE 1 JUNCTION BOX, TEMPERATURE SENSOR JUNCTION BOX, INSTRUMENT INSTRUMENT e NO TAG AT SITE
54 4TH DECK (PUMP ROOM) ZONE 1 CAM-03 CCTV CAMERA CCTV SYSTEM TELECOM PELCO WORLDWIDE EHX8E EXD IIB - IP66 -
55 4TH DECK (PUMP ROOM) ZONE 1 CAM-04 CCTV CAMERA CCTV SYSTEM TELECOM PELCO WORLDWIDE EHX8E EXD IIB - IP66 -
56 4TH DECK (PUMP ROOM) ZONE 1 PA-BBA/1 BEACON FIRE & GAS DETECTION SYSTEM TELECOM MEDC NG166JF 31295732008 d IIC T5
57 4TH DECK (PUMP ROOM) ZONE 1 PA-A6B/1 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE
58 4TH DECK (PUMP ROOM) ZONE 1 PA-B6B/1 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE
59 4TH DECK (PUMP ROOM) ZONE 1 LPA-5 RADIO REPEATER, WALKIE TALKIE PUMP ROOM TELECOM NO PLATE AT SITE
60 4TH DECK (PUMP ROOM) ZONE 1 PA-ABA/1 BEACON FIRE & GAS DETECTION SYSTEM TELECOM MEDC NG166JF 31295732008 d IIC T5
61 4TH DECK (PUMP ROOM) ZONE 1 PA-ABA/1 BEACON FIRE & GAS DETECTION SYSTEM TELECOM MEDC NG166JF 31295732008 d IIC T5
62 4TH DECK (PUMP ROOM) ZONE 1 BEACON FIRE & GAS DETECTION SYSTEM TELECOM CORTEM GROUP 200 d IIC T1 66 NO TAG AT SITE
63 A DECK ZONE 2 GD-019 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Xguard (Type3) d IIC T4 66
64 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
65 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
66 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
67 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
68 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
69 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
70 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
71 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
72 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
73 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
74 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
75 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
76 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
77 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
78 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
79 B DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE

Page 1 of 9
EX Database

Equipment
ID Deck/Process Area Zone Tag Availability (Yes/No) Equipment Name Package/System Description Discipline Manufacturer Model Serial No Ex Class Gas Group Temp Class IP Rating Remarks
Protection Level
80 B DECK (BOILER AREA) ZONE 2 CA-ZSHL-003 LIMIT SWITCH BOILER INSTRUMENT SWITCHBOX SBB-77M82/4 ia IIC T6 67
81 B DECK (BOILER AREA) ZONE 2 CA-ZSHL-005 LIMIT SWITCH BOILER INSTRUMENT SWITCHBOX SBB-77M82/4 ia IIC T6 67
82 B DECK (BOILER AREA) ZONE 2 PS-PDT-202 PRESSURE DIFFRENCE TRANSMITTER BOILER INSTRUMENT ROSEMOUNT 3051/3001 ia IIC t5 65
83 B DECK (BOILER AREA) ZONE 2 1H2-SBV-PS JUNCTION BOX, INSTRUMENT BOILER INSTRUMENT ABRECH 518 210319 e II T6 67
84 B DECK (BOILER AREA) ZONE 2 CONTROL VALVE BOILER INSTRUMENT AIR TORQUE ia IIC T6 67 NO TAG AT SITE
85 B DECK (BOILER AREA) ZONE 2 H2-SBV-SOL SOLENOID VALVE BOILER INSTRUMENT NORGEN NO PLATE AT SITE
86 B DECK (BOILER AREA) ZONE 2 2H2-SBV-PS JUNCTION BOX, INSTRUMENT BOILER INSTRUMENT ABRECH 518 210319 e II T6 67
87 B DECK (BOILER AREA) ZONE 2 CONTROL VALVE BOILER INSTRUMENT AIR TORQUE ia IIC T6 67 NO TAG AT SITE
88 B DECK (BOILER AREA) ZONE 2 SOLENOID VALVE BOILER INSTRUMENT NORGEN NO TAG & PLATE AT SITE
89 B DECK (BOILER AREA) ZONE 2 CA-SHL-006 LIMIT SWITCH BOILER INSTRUMENT SWITCHBOX SBB-77M82/4 ia IIC T6 67
90 B DECK (BOILER AREA) ZONE 2 FEED WATER CONTROL VALVE BOILER 1 INSTRUMENT SIMENS SIPART/PS2 ia/ib IIC T6 66 NO TAG AT SITE
91 B DECK (BOILER AREA) ZONE 2 FEED WATER CONTROL VALVE BOILER 2 INSTRUMENT SIMENS SIPART/PS2 ia/ib IIC T6 66 NO TAG AT SITE
92 B DECK (BOILER AREA) ZONE 2 FW-PDT-103 LEVEL TRANSMITTER BOILER 1 INSTRUMENT SIMENS SITRANS P NO PLATE AT SITE
93 B DECK (BOILER AREA) ZONE 2 FW-PDT-104 LEVEL TRANSMITTER BOILER 1 INSTRUMENT SIMENS SITRANS P NO PLATE AT SITE
94 B DECK (BOILER AREA) ZONE 2 FW-PDT-203 LEVEL TRANSMITTER BOILER 2 INSTRUMENT SIMENS SITRANS P NO PLATE AT SITE
95 B DECK (BOILER AREA) ZONE 2 FW-PDT-204 LEVEL TRANSMITTER BOILER 2 INSTRUMENT SIMENS SITRANS P NO PLATE AT SITE
96 B DECK (BOILER AREA) ZONE 2 PA-B4A/6 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
97 B DECK (BOILER AREA) ZONE 2 PA-BBB/1 BEACON FIRE & GAS DETECTION SYSTEM TELECOM MEDC NG166JF 31295732001 d IIC T5
98 B DECK (BOILER AREA) ZONE 2 PA-A4A/4 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
99 B DECK (BOILER AREA) ZONE 2 PA-ABB/2 BEACON FIRE & GAS DETECTION SYSTEM TELECOM MEDC NG166JF 31295732001 d IIC T5 NO PLATE AT SITE
100 B & C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
101 B & C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
102 B & C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
103 B & C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
104 B & C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
105 B & C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
106 B & C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
107 B & C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
108 BOSUN STORE FLAT ZONE 1 C053 MANUAL CALL POINT FIRE & GAS DETECTION SYSTEM INSTRUMENT THORN SECURITY CP840Ex ia IIC T5 66
109 BOSUN STORE FLAT ZONE 1 GD-027 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus d IIB+H2 T6 66
110 C DECK ZONE 2 GD-028 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus 8675 d IIB+H2 T6
111 C DECK ZONE 2 GD-029 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus 8007 d IIB+H2 T6
112 C DECK ZONE 2 GD-010 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Xguard (Type3) d IIC T4 66
113 C DECK ZONE 2 GD-011 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Xguard (Type3) d IIC T4 66
114 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
115 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
116 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
117 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
118 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
119 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
120 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
121 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
122 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
123 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
124 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
125 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
126 C DECK (BOILER AREA) ZONE 2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Chalmit Lighting PRGN/236/BI - PRGN/236/BI/EM nA II T4 66 NO TAG AT SITE
127 C DECK (BOILER AREA) ZONE 2 LCP-1 BOILER NO.1 LOCAL CONTROL PANEL BOILER 1 INSTRUMENT STHAL 8125/509 de IIC T6 66 PLATE FADED
128 C DECK (BOILER AREA) ZONE 2 CA-PSHH-109 PRESSURE SWITCH BOILER 1 INSTRUMENT PLATE FADED
129 C DECK (BOILER AREA) ZONE 2 CA-PSLL-101 PRESSURE SWITCH BOILER 1 INSTRUMENT DWYER 1950-0-6X CL 1 Div. 1 T5 PLATE FADED
130 C DECK (BOILER AREA) ZONE 2 CA-DPT-101 PRESSURE DIFFERENTIAL TRANSMITTER BOILER 1 INSTRUMENT ROSEMOUNT 3051/3001 ia IIC T5 66
131 C DECK (BOILER AREA) ZONE 2 PS-PSHH-108 PRESSURE SWITCH BOILER 1 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
132 C DECK (BOILER AREA) ZONE 2 PS-PT-102 PRESSURE TRANSMITTER BOILER 1 INSTRUMENT ROSEMOUNT 3051/3001 ia IIC T5 66
133 C DECK (BOILER AREA) ZONE 2 ASL-PSL-104 PRESSURE SWITCH BOILER 1 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
134 C DECK (BOILER AREA) ZONE 2 ASL-ZSL-107 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
135 C DECK (BOILER AREA) ZONE 2 ASL-ZSL-108 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
136 C DECK (BOILER AREA) ZONE 2 ASL-ZSL-109 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
137 C DECK (BOILER AREA) ZONE 2 ASL-ZSL-110 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
138 C DECK (BOILER AREA) ZONE 2 FO-SV-107 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 PLATE FADED
139 C DECK (BOILER AREA) ZONE 2 FO-SV-108 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 PLATE FADED
140 C DECK (BOILER AREA) ZONE 2 FO-SV-109 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 PLATE FADED
141 C DECK (BOILER AREA) ZONE 2 FO-SV-110 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 PLATE FADED
142 C DECK (BOILER AREA) ZONE 2 FG-ZSL-119 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
143 C DECK (BOILER AREA) ZONE 2 FO-SV-119 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 PLATE FADED
144 C DECK (BOILER AREA) ZONE 2 FG-PSLL-101 PRESSURE SWITCH BOILER 1 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
145 C DECK (BOILER AREA) ZONE 2 FG-FCV-151 FLOW CONTROL VALVE BOILER 1 INSTRUMENT FISHER FIELDVUE NO PLATE AT SITE
146 C DECK (BOILER AREA) ZONE 2 FG-SV-151 SOLENOID VALVE BOILER 1 INSTRUMENT ROSE 15081806 ia IIC T6 66
147 C DECK (BOILER AREA) ZONE 2 FG-PT-101 PRESSURE TRANSMITTER BOILER 1 INSTRUMENT ROSEMOUNT 3051/3001 ia IIC T5 66
148 C DECK (BOILER AREA) ZONE 2 FG-PSHH-102 PRESSURE SWITCH BOILER 1 INSTRUMENT ROSEMOUNT 3051/3001 ia IIC T5 66 PLATE FADED
149 C DECK (BOILER AREA) ZONE 2 B1-FG-JB101 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT STHAL 8125/2088 e(a/ib) II T6 66 PLATE FADED
150 C DECK (BOILER AREA) ZONE 2 B1-CH-JB101 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT HUBBLE KILLARK CRL MOD CEN d IIC T6 66
151 C DECK (BOILER AREA) ZONE 2 FG-ZSL-115 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
152 C DECK (BOILER AREA) ZONE 2 FG-ZSH-115 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
153 C DECK (BOILER AREA) ZONE 2 CA-SV-115 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
154 C DECK (BOILER AREA) ZONE 2 FG-ZSL-117 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
155 C DECK (BOILER AREA) ZONE 2 FG-ZSH-117 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
156 C DECK (BOILER AREA) ZONE 2 CA-SV-117 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
157 C DECK (BOILER AREA) ZONE 2 FG-ZS-116 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
158 C DECK (BOILER AREA) ZONE 2 FG-ZSL-XXX LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO TAG & PLATE AT SITE

Page 2 of 9
EX Database

Equipment
ID Deck/Process Area Zone Tag Availability (Yes/No) Equipment Name Package/System Description Discipline Manufacturer Model Serial No Ex Class Gas Group Temp Class IP Rating Remarks
Protection Level
159 C DECK (BOILER AREA) ZONE 2 FG-ZSH-XXX LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO TAG & PLATE AT SITE
160 C DECK (BOILER AREA) ZONE 2 CA-SV-XXX SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 NO TAG AT SITE
161 C DECK (BOILER AREA) ZONE 2 FG-ZSL-120 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
162 C DECK (BOILER AREA) ZONE 2 FG-ZSH-120 LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO EX INFO.
163 C DECK (BOILER AREA) ZONE 2 CA-SV-120 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
164 C DECK (BOILER AREA) ZONE 2 FG-ZS-XXX LIMIT SWITCH BOILER 1 INSTRUMENT VARICONT NO TAG & PLATE AT SITE
165 C DECK (BOILER AREA) ZONE 2 FLAME SCANNER 1, BURNER 1 BOILER 1 INSTRUMENT ia IIC T4 NO TAG AT SITE
166 C DECK (BOILER AREA) ZONE 2 FLAME SCANNER 2, BURNER 1 BOILER 1 INSTRUMENT ia IIC T4 NO TAG AT SITE
167 C DECK (BOILER AREA) ZONE 2 FLAME SCANNER 1, BURNER 2 BOILER 1 INSTRUMENT ia IIC T4 NO TAG AT SITE
168 C DECK (BOILER AREA) ZONE 2 FLAME SCANNER 2, BURNER 2 BOILER 1 INSTRUMENT ia IIC T4 NO TAG AT SITE
169 C DECK (BOILER AREA) ZONE 2 FG-SV-120 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
170 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-120 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
171 C DECK (BOILER AREA) ZONE 2 FG-SV-103 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
172 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-103 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
173 C DECK (BOILER AREA) ZONE 2 FG-SV-101 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
174 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-101 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
175 C DECK (BOILER AREA) ZONE 2 FG-SV-104 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
176 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-104 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
177 C DECK (BOILER AREA) ZONE 2 FG-SV-106 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
178 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-106 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
179 C DECK (BOILER AREA) ZONE 2 FG-SV-102 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
180 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-102 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
181 C DECK (BOILER AREA) ZONE 2 FG-SV-105 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
182 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-105 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
183 C DECK (BOILER AREA) ZONE 2 B1-CH-JB102 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT HUBBLE KILLARK CRL MOD CEN d IIC T6 66
184 C DECK (BOILER AREA) ZONE 2 FO-FT-101 FLOW TRANSMITTER BOILER 1 INSTRUMENT ENDRESS HAUSER PROMAS40 de(ia) IIC T6 67
185 C DECK (BOILER AREA) ZONE 2 FG-FCV-152 FLOW CONTROL VALVE BOILER 1 INSTRUMENT FISHER FIELDVUE NO TAG & PLATE AT SITE
186 C DECK (BOILER AREA) ZONE 2 FG-SV-152 SOLENOID VALVE BOILER 1 INSTRUMENT ROSE 15081806 ia IIC T6 66
187 C DECK (BOILER AREA) ZONE 2 FO-PSL-103 PRESSURE SWITCH BOILER 1 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
188 C DECK (BOILER AREA) ZONE 2 IA-PSL-106 PRESSURE SWITCH BOILER 1 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
189 C DECK (BOILER AREA) ZONE 2 FO-ZSL-111 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
190 C DECK (BOILER AREA) ZONE 2 FO-ZSL-112 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
191 C DECK (BOILER AREA) ZONE 2 AS-ZSL-113 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
192 C DECK (BOILER AREA) ZONE 2 AS-ZSL-114 LIMIT SWITCH BOILER 1 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
193 C DECK (BOILER AREA) ZONE 2 FO-SV-111 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
194 C DECK (BOILER AREA) ZONE 2 FO-SV-112 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
195 C DECK (BOILER AREA) ZONE 2 AS-SV-113 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
196 C DECK (BOILER AREA) ZONE 2 AS-SV-114 SOLENOID VALVE BOILER 1 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
197 C DECK (BOILER AREA) ZONE 2 AS-PSL-105 PRESSURE SWITCH BOILER 1 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
198 C DECK (BOILER AREA) ZONE 2 TEMPERATURE TRANSMITTER BOILER 1 INSTRUMENT ROSEMOUNT NO TAG & PLATE AT SITE
199 C DECK (BOILER AREA) ZONE 2 BIP-DXY-001 ANALYZER BOILER 1 INSTRUMENT ROSEMOUNT DXYMITTER 400-MOC-QXT4C d IIC+H2 T6 66
200 C DECK (BOILER AREA) ZONE 2 C8A TEMPERATURE TRANSMITTER BOILER 1 INSTRUMENT ROSEMOUNT NO TAG & PLATE AT SITE
201 C DECK (BOILER AREA) ZONE 2 B1-CA-JB101 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT STAHL PLATE FADED
202 C DECK (BOILER AREA) ZONE 2 B1-SW-JB101 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT STAHL PLATE FADED
203 C DECK (BOILER AREA) ZONE 2 B1-BUI-JB101 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT STAHL PLATE FADED
204 C DECK (BOILER AREA) ZONE 2 B1-BS-FL-JB101 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT STAHL PLATE FADED
205 C DECK (BOILER AREA) ZONE 2 B1-FW-FL-JB101 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT STAHL PLATE FADED
206 C DECK (BOILER AREA) ZONE 2 B1-FO-JB101 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT STAHL PLATE FADED
207 C DECK (BOILER AREA) ZONE 2 CA-JB001 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT STAHL PLATE FADED
208 C DECK (BOILER AREA) ZONE 2 B1-BU2-JB101 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT STAHL PLATE FADED
209 C DECK (BOILER AREA) ZONE 2 B2-BS-FL-JB201 JUNCTION BOX, INSTRUMENT BOILER 1 INSTRUMENT STAHL PLATE FADED
210 C DECK (BOILER AREA) ZONE 2 LCP-2 BOILER NO.1 LOCAL CONTROL PANEL BOILER 2 INSTRUMENT STHAL 8125/509 de IIC T6 66 PLATE FADED
211 C DECK (BOILER AREA) ZONE 2 CA-PSHH-209 PRESSURE SWITCH BOILER 2 INSTRUMENT PLATE FADED
212 C DECK (BOILER AREA) ZONE 2 CA-PSLL-201 PRESSURE SWITCH BOILER 2 INSTRUMENT DWYER 1950-0-6X CL 1 Div. 1 T5 PLATE FADED
213 C DECK (BOILER AREA) ZONE 2 CA-DPT-201 PRESSURE DIFFERENTIAL TRANSMITTER BOILER 2 INSTRUMENT ROSEMOUNT 3051/3001 ia IIC T5 66
214 C DECK (BOILER AREA) ZONE 2 PS-PSHH-208 PRESSURE SWITCH BOILER 2 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
215 C DECK (BOILER AREA) ZONE 2 PS-PT-202 PRESSURE TRANSMITTER BOILER 2 INSTRUMENT ROSEMOUNT 3051/3001 ia IIC T5 66
216 C DECK (BOILER AREA) ZONE 2 ASL-PSL-204 PRESSURE SWITCH BOILER 2 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
217 C DECK (BOILER AREA) ZONE 2 ASL-ZSL-207 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
218 C DECK (BOILER AREA) ZONE 2 ASL-ZSL-208 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
219 C DECK (BOILER AREA) ZONE 2 ASL-ZSL-209 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
220 C DECK (BOILER AREA) ZONE 2 ASL-ZSL-210 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
221 C DECK (BOILER AREA) ZONE 2 FO-SV-207 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 PLATE FADED
222 C DECK (BOILER AREA) ZONE 2 FO-SV-208 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 PLATE FADED
223 C DECK (BOILER AREA) ZONE 2 FO-SV-209 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 PLATE FADED
224 C DECK (BOILER AREA) ZONE 2 FO-SV-210 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 PLATE FADED
225 C DECK (BOILER AREA) ZONE 2 FG-ZSL-219 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
226 C DECK (BOILER AREA) ZONE 2 FO-SV-219 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 PLATE FADED
227 C DECK (BOILER AREA) ZONE 2 FG-PSLL-201 PRESSURE SWITCH BOILER 2 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
228 C DECK (BOILER AREA) ZONE 2 FG-FCV-251 FLOW CONTROL VALVE BOILER 2 INSTRUMENT FISHER FIELDVUE NO PLATE AT SITE
229 C DECK (BOILER AREA) ZONE 2 FG-SV-251 SOLENOID VALVE BOILER 2 INSTRUMENT ROSE 15081806 ia IIC T6 66
230 C DECK (BOILER AREA) ZONE 2 FG-PT-201 PRESSURE TRANSMITTER BOILER 2 INSTRUMENT ROSEMOUNT 3051/3001 ia IIC T5 66
231 C DECK (BOILER AREA) ZONE 2 FG-PSHH-202 PRESSURE SWITCH BOILER 2 INSTRUMENT ROSEMOUNT 3051/3001 ia IIC T5 66 PLATE FADED
232 C DECK (BOILER AREA) ZONE 2 B2-FG-JB201 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT STHAL 8125/2088 e(a/ib) II T6 66 PLATE FADED
233 C DECK (BOILER AREA) ZONE 2 B2-CH-JB201 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT HUBBLE KILLARK CRL MOD CEN d IIC T6 66
234 C DECK (BOILER AREA) ZONE 2 FG-ZSL-215 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
235 C DECK (BOILER AREA) ZONE 2 FG-ZSH-215 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
236 C DECK (BOILER AREA) ZONE 2 CA-SV-215 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
237 C DECK (BOILER AREA) ZONE 2 FG-ZSL-217 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.

Page 3 of 9
EX Database

Equipment
ID Deck/Process Area Zone Tag Availability (Yes/No) Equipment Name Package/System Description Discipline Manufacturer Model Serial No Ex Class Gas Group Temp Class IP Rating Remarks
Protection Level
238 C DECK (BOILER AREA) ZONE 2 FG-ZSH-217 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
239 C DECK (BOILER AREA) ZONE 2 CA-SV-217 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
240 C DECK (BOILER AREA) ZONE 2 FG-ZS-216 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
241 C DECK (BOILER AREA) ZONE 2 FG-ZSL-XXX LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO TAG & PLATE AT SITE
242 C DECK (BOILER AREA) ZONE 2 FG-ZSH-XXX LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO TAG & PLATE AT SITE
243 C DECK (BOILER AREA) ZONE 2 CA-SV-XXX SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6 NO TAG AT SITE
244 C DECK (BOILER AREA) ZONE 2 FG-ZSL-220 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
245 C DECK (BOILER AREA) ZONE 2 FG-ZSH-220 LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO EX INFO.
246 C DECK (BOILER AREA) ZONE 2 CA-SV-220 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
247 C DECK (BOILER AREA) ZONE 2 FG-ZS-XXX LIMIT SWITCH BOILER 2 INSTRUMENT VARICONT NO TAG & PLATE AT SITE
248 C DECK (BOILER AREA) ZONE 2 FLAME SCANNER 1, BURNER 1 BOILER 2 INSTRUMENT ia IIC T4 NO TAG AT SITE
249 C DECK (BOILER AREA) ZONE 2 FLAME SCANNER 2, BURNER 1 BOILER 2 INSTRUMENT ia IIC T4 NO TAG AT SITE
250 C DECK (BOILER AREA) ZONE 2 FLAME SCANNER 1, BURNER 2 BOILER 2 INSTRUMENT ia IIC T4 NO TAG AT SITE
251 C DECK (BOILER AREA) ZONE 2 FLAME SCANNER 2, BURNER 2 BOILER 2 INSTRUMENT ia IIC T4 NO TAG AT SITE
252 C DECK (BOILER AREA) ZONE 2 FG-SV-220 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
253 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-220 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
254 C DECK (BOILER AREA) ZONE 2 FG-SV-203 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
255 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-203 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
256 C DECK (BOILER AREA) ZONE 2 FG-SV-201 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
257 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-201 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
258 C DECK (BOILER AREA) ZONE 2 FG-SV-204 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
259 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-204 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
260 C DECK (BOILER AREA) ZONE 2 FG-SV-206 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
261 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-206 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
262 C DECK (BOILER AREA) ZONE 2 FG-SV-202 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
263 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-202 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
264 C DECK (BOILER AREA) ZONE 2 FG-SV-205 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
265 C DECK (BOILER AREA) ZONE 2 FG-ZSHL-205 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
266 C DECK (BOILER AREA) ZONE 2 B2-CH-JB202 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT HUBBLE KILLARK CRL MOD CEN d IIC T6 66
267 C DECK (BOILER AREA) ZONE 2 FO-FT-201 FLOW TRANSMITTER BOILER 2 INSTRUMENT ENDRESS HAUSER PROMAS40 de(ia) IIC T6 67
268 C DECK (BOILER AREA) ZONE 2 FG-FCV-252 FLOW CONTROL VALVE BOILER 2 INSTRUMENT FISHER FIELDVUE NO PLATE AT SITE
269 C DECK (BOILER AREA) ZONE 2 FG-SV-252 SOLENOID VALVE BOILER 2 INSTRUMENT ROSE 15081806 ia IIC T6 66
270 C DECK (BOILER AREA) ZONE 2 FO-PSL-203 PRESSURE SWITCH BOILER 2 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
271 C DECK (BOILER AREA) ZONE 2 IA-PSL-206 PRESSURE SWITCH BOILER 2 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
272 C DECK (BOILER AREA) ZONE 2 FO-ZSL-211 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
273 C DECK (BOILER AREA) ZONE 2 FO-ZSL-212 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
274 C DECK (BOILER AREA) ZONE 2 AS-ZSL-213 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
275 C DECK (BOILER AREA) ZONE 2 AS-ZSL-214 LIMIT SWITCH BOILER 2 INSTRUMENT COTSWORLD VALVE ES-0025 NO PLATE AT SITE
276 C DECK (BOILER AREA) ZONE 2 FO-SV-211 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
277 C DECK (BOILER AREA) ZONE 2 FO-SV-212 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
278 C DECK (BOILER AREA) ZONE 2 AS-SV-213 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
279 C DECK (BOILER AREA) ZONE 2 AS-SV-214 SOLENOID VALVE BOILER 2 INSTRUMENT RGS LTD. EP000/ia ia IIC T6
280 C DECK (BOILER AREA) ZONE 2 AS-PSL-205 PRESSURE SWITCH BOILER 2 INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 NO EX INFO.
281 C DECK (BOILER AREA) ZONE 2 TEMPERATURE TRANSMITTER BOILER 2 INSTRUMENT ROSEMOUNT NO TAG & PLATE AT SITE
282 C DECK (BOILER AREA) ZONE 2 BIP-DXY-001 ANALYZER BOILER 2 INSTRUMENT ROSEMOUNT DXYMITTER 400-MOC-QXT4C d IIC+H2 T6 66
283 C DECK (BOILER AREA) ZONE 2 C8A TEMPERATURE TRANSMITTER BOILER 2 INSTRUMENT ROSEMOUNT NO TAG & PLATE AT SITE
284 C DECK (BOILER AREA) ZONE 2 B2-CA-JB201 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT STAHL PLATE FADED
285 C DECK (BOILER AREA) ZONE 2 B2-SW-JB201 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT STAHL PLATE FADED
286 C DECK (BOILER AREA) ZONE 2 B2-BUI-JB201 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT STAHL PLATE FADED
287 C DECK (BOILER AREA) ZONE 2 B2-BS-FL-JB201 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT STAHL PLATE FADED
288 C DECK (BOILER AREA) ZONE 2 B2-FW-FL-JB201 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT STAHL PLATE FADED
289 C DECK (BOILER AREA) ZONE 2 B2-FO-JB201 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT STAHL PLATE FADED
290 C DECK (BOILER AREA) ZONE 2 B2-BU2-JB201 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT STAHL PLATE FADED
291 C DECK (BOILER AREA) ZONE 2 B2-BS-FL-JB202 JUNCTION BOX, INSTRUMENT BOILER 2 INSTRUMENT STAHL PLATE FADED
292 C DECK (BOILER AREA) ZONE 2 PA-B4A/8 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
293 C DECK (BOILER AREA) ZONE 2 PA-BBB/2 BEACON FIRE & GAS DETECTION SYSTEM TELECOM MEDC NG166JF 31295732001 d IIC T5
294 C DECK (BOILER AREA) ZONE 2 PA-B4A/6 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
295 D DECK ZONE 2 GD-003 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Xguard (Type3) d IIC T4 66 PLATE FADED
296 D DECK ZONE 2 GD-004 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Xguard (Type3) W106855/01-10 d IIC T4 66
297 D DECK ZONE 2 A015 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5
298 D DECK (BAT. ROOM) ZONE 2 LT-D-BR LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL DAEYANG ELECTRIC CO. LTD NO PLATE AT SITE
299 D DECK (OUTSIDE BAT. ROOM) ZONE 2 ELT-D-EX6 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
300 D DECK (OUTSIDE BAT. ROOM) ZONE 2 ELT-D-EX7 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
301 NAV BRIDGE DECK ZONE 2 ELT-NAV-EX5 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
302 NAV BRIDGE DECK ZONE 2 LT-NAV-EX6 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL AQUAL SIGNAL NO PLATE AT SITE
303 NAV BRIDGE DECK ZONE 2 LT-NAV-EX7 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL AQUAL SIGNAL NO PLATE AT SITE
304 NAV BRIDGE DECK ZONE 2 ELT-NAV-EX8 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
305 NAV BRIDGE DECK ZONE 2 GD-001 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Xguard (Type3) W107402101-10 d IIC T4 66
306 TURBINE FLAT (PUMP ROOM) ZONE 1 LT-PUM-EX3 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 218 d IIC T6 66
307 TURBINE FLAT (PUMP ROOM) ZONE 1 ELT-4DK-PUM4 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 218 d IIC T6 66
308 TURBINE FLAT (PUMP ROOM) ZONE 1 LT-PUM-NE7 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 236 d IIC T6 66
309 TURBINE FLAT (PUMP ROOM) ZONE 1 LT-COC-EX4 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL KOKOSHA CO. LTD NO PLATE AT SITE
310 TURBINE FLAT (PUMP ROOM) ZONE 1 LT-COC-EX5 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL KOKOSHA CO. LTD NO PLATE AT SITE
311 TURBINE FLAT (PUMP ROOM) ZONE 1 LT-PUM-EX4 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL italsmea EVF-P 236 d IIC T6 66
312 TURRET ZONE 2 410-DB-4002 DISTRIBUTION BOARD HEATER ELECTRICAL THE EX ZONE LTD EJB-5B d IIB T5 66
313 TURRET ZONE 2 410-DB-4003 DISTRIBUTION BOARD LIGHTING SYSTEM ELECTRICAL THE EX ZONE LTD EJB-5B d IIB T5 66
314 TURRET ZONE 2 455-HT-4202 JUNCTION BOX HEATER ELECTRICAL THE EX ZONE LTD EJB-5B d IIB T5 66
315 TURRET ZONE 2 455-TFXR-4004 DISTRIBUTION BOARD HEATER ELECTRICAL THE EX ZONE LTD EJB-5B d IIB T4 66
316 TURRET ZONE 2 455-TFXR-4005 DISTRIBUTION BOARD LIGHTING SYSTEM ELECTRICAL THE EX ZONE LTD EJB-5B d IIB T4 66

Page 4 of 9
EX Database

Equipment
ID Deck/Process Area Zone Tag Availability (Yes/No) Equipment Name Package/System Description Discipline Manufacturer Model Serial No Ex Class Gas Group Temp Class IP Rating Remarks
Protection Level
317 TURRET ZONE 2 455-TFXR-4006 DISTRIBUTION BOARD HEATER ELECTRICAL THE EX ZONE LTD EJB-5B d IIB T4 66
318 TURRET ZONE 2 415-L-4015 FLOODLIGHT LIGHTING SYSTEM ELECTRICAL CLAMOX GTX220368 d IIC T5 67
319 TURRET ZONE 2 415-L-4016 FLOODLIGHT LIGHTING SYSTEM ELECTRICAL CLAMOX GTX220368 d IIC T5 67
320 TURRET ZONE 2 415-L-4017 FLOODLIGHT LIGHTING SYSTEM ELECTRICAL CLAMOX GTX220368 d IIC T5 67
321 TURRET ZONE 2 415-L-4018 FLOODLIGHT LIGHTING SYSTEM ELECTRICAL CLAMOX GTX220368 d IIC T5 67
322 TURRET ZONE 2 415-L-4019 FLOODLIGHT LIGHTING SYSTEM ELECTRICAL CLAMOX GTX220368 d IIC T5 67
323 TURRET ZONE 2 415-L-4011 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36 de IIC T4 66 Gb
324 TURRET ZONE 2 415-L-4012 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36 de IIC T4 66 Gb
325 TURRET ZONE 2 415-L-4013 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36 de IIC T4 66 Gb
326 TURRET ZONE 2 415-L-4131 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36 de IIC T4 66
327 TURRET ZONE 2 415-L-4132 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36 de IIC T4 66
328 TURRET ZONE 2 415-L-4133 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36 de IIC T4 66
329 TURRET ZONE 2 415-L-4136 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36 de IIC T4 66
330 TURRET ZONE 2 415-L-4137 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36 de IIC T4 66
331 TURRET ZONE 2 415-EL-4157 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36NIB demb ib IIC T4 66
332 TURRET ZONE 2 415-EL-4160 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36NIB demb ib IIC T4 66
333 TURRET ZONE 2 415-EL-4177 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36NIB demb ib IIC T4 66
334 TURRET ZONE 2 415-EL-4178 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36NIB demb ib IIC T4 66
335 TURRET ZONE 2 415-EL-4183 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36NIB demb ib IIC T4 66
336 TURRET ZONE 2 415-EL-4184 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/36NIB demb ib IIC T4 66
337 TURRET ZONE 2 455-HTJB-4202-01 JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66
338 TURRET ZONE 2 455-HTJB-4202-02 JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
339 TURRET ZONE 2 455-HTJB-4202-03 JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
340 TURRET ZONE 2 455-HTJB-4202-04-A JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
341 TURRET ZONE 2 455-HTJB-4202-04-B JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
342 TURRET ZONE 2 455-HTJB-4202-04-C JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
343 TURRET ZONE 2 455-HTJB-4202-05-A JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
344 TURRET ZONE 2 455-HTJB-4202-05-B JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
345 TURRET ZONE 2 455-HTJB-4202-05-C JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
346 TURRET ZONE 2 455-HTJB-4202-06 JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
347 TURRET ZONE 2 455-HTJB-4202-07 JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
348 TURRET ZONE 2 455-HTJB-4202-08 JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66 PLATE FADED
349 TURRET ZONE 2 415-EJB-4154A LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
350 TURRET ZONE 2 415-EJB-4158A LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
351 TURRET ZONE 2 415-EJB-4161 LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
352 TURRET ZONE 2 415-EJB-4175A LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
353 TURRET ZONE 2 415-EJB-4178A LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
354 TURRET ZONE 2 415-EJB-4178B LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
355 TURRET ZONE 2 415-EJB-4184 LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
356 TURRET ZONE 2 415-JB-4010B LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
357 TURRET ZONE 2 415-JB-4010C LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
358 TURRET ZONE 2 415-JB-4010D LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
359 TURRET ZONE 2 415-JB-4100 LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
360 TURRET ZONE 2 415-JB-4130 LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
361 TURRET ZONE 2 415-JB-4134 LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
362 TURRET ZONE 2 415-JB-4138A LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
363 TURRET ZONE 2 415-JB-4140A LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
364 TURRET ZONE 2 415-JB-4141A LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
365 TURRET ZONE 2 415-JB-4120 LIGHTING JUNCTION BOX LIGHTING SYSTEM ELECTRICAL Weidmuller e IIC T6
366 TURRET ZONE 2 415-L-4102 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92036/36 ed IIC T4 66
367 TURRET ZONE 2 415-L-4103 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92036/36 ed IIC T4 66
368 TURRET ZONE 2 415-EL-4155 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
369 TURRET ZONE 2 415-EL-4156 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
370 TURRET ZONE 2 415-EL-4158 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
371 TURRET ZONE 2 415-EL-4159 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
372 TURRET ZONE 2 415-EL-4161 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
373 TURRET ZONE 2 415-EL-4162 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
374 TURRET ZONE 2 415-EL-4163 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
375 TURRET ZONE 2 415-EL-4175 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
376 TURRET ZONE 2 415-EL-4176 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
377 TURRET ZONE 2 415-EL-4179 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
378 TURRET ZONE 2 415-EL-4180 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
379 TURRET ZONE 2 415-EL-4181 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
380 TURRET ZONE 2 415-EL-4182 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
381 TURRET ZONE 2 415-EL-4185 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
382 TURRET ZONE 2 415-EL-4186 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
383 TURRET ZONE 2 415-EL-4187 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
384 TURRET ZONE 2 415-EL-4188 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
385 TURRET ZONE 2 415-L-4101 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG eLLK 92036/18NIB ed m ib IIC T4 66
386 TURRET ZONE 2 415-L-4135 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL VEERSTEEG 17 emb II T4 66
387 TURRET ZONE 2 415-L-4138 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL VEERSTEEG 17 emb II T4 66
388 TURRET ZONE 2 415-L-4014 FLOODLIGHT LIGHTING SYSTEM ELECTRICAL VEERSTEEG 17 me II T4 66
389 TURRET ZONE 2 415-L-4139 OBSTRUCTION LIGHT LIGHTING SYSTEM ELECTRICAL EQUIPMENT BEYOND REACH
390 TURRET ZONE 2 415-L-4141 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92036/36 ed IIC T4 66
391 TURRET ZONE 2 415-L-4142 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92036/36 ed IIC T4 66
392 TURRET ZONE 2 415-L-4143 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92036/36 ed IIC T4 66
393 TURRET ZONE 2 415-L-4144 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92036/36 ed IIC T4 66
394 TURRET ZONE 2 415-L-4145 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92036/36 ed IIC T4 66
395 TURRET ZONE 2 415-L-4146 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92036/36 ed IIC T4 66

Page 5 of 9
EX Database

Equipment
ID Deck/Process Area Zone Tag Availability (Yes/No) Equipment Name Package/System Description Discipline Manufacturer Model Serial No Ex Class Gas Group Temp Class IP Rating Remarks
Protection Level
396 TURRET ZONE 2 415-L-4121 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92018/18 ed IIC T4 66
397 TURRET ZONE 2 415-L-4122 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92036/36 ed IIC T4 66
398 TURRET ZONE 2 415-L-4123 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG Ellk 92036/36 ed IIC T4 66
399 TURRET ZONE 2 455-HTJB-4201-04 JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66
400 TURRET ZONE 2 455-HTJB-4201-05 JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66
401 TURRET ZONE 2 455-HTJB-4201-03-A JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66
402 TURRET ZONE 2 455-HTJB-4201-03-B JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66
403 TURRET ZONE 2 455-HTJB-4201-01 JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66
404 TURRET ZONE 2 455-HTJB-4010-D JUNCTION BOX HEATER ELECTRICAL Raychem JBM-100-EP e IIC T6 66
405 TURRET ZONE 2 415-M4150 SOCKET OUTLET SMALL POWER DISTRIBUTION SYSTEM ELECTRICAL NO TAG & PLATE AT SITE
406 TURRET ZONE 2 840-JB-2001 JUNCTION BOX HPU ELECTRICAL d NO PLATE AT SITE
407 TURRET ZONE 2 840-M-2001 JUNCTION BOX HPU ELECTRICAL e NO PLATE AT SITE
408 TURRET ZONE 2 840-JB-2002 JUNCTION BOX HPU ELECTRICAL e NO PLATE AT SITE
409 TURRET ZONE 2 840-JB-2003 JUNCTION BOX HPU ELECTRICAL e NO PLATE AT SITE
410 TURRET ZONE 2 325-PM-1091 PUMP MOTOR HPU ELECTRICAL NO PLATE AT SITE
411 TURRET ZONE 2 840-PM-2091 PUMP MOTOR HPU ELECTRICAL NO PLATE AT SITE
412 TURRET ZONE 2 840-PM-2092 PUMP MOTOR HPU ELECTRICAL NO PLATE AT SITE
413 TURRET ZONE 2 GD-032 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus 12373 d IIB+H2 T6 66
414 TURRET ZONE 2 GD-033 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus d IIB+H2 T6 66 EQUIPMENT BEYOND REACH
415 TURRET ZONE 2 C064 FLAME DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT EQUIPMENT BEYOND REACH
416 TURRET ZONE 2 C065 FLAME DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT EQUIPMENT BEYOND REACH
417 TURRET ZONE 2 C054 MANUAL CALL POINT FIRE & GAS DETECTION SYSTEM INSTRUMENT THORN SECURITY CP840Ex ia IIC T5 66
418 TURRET ZONE 2 C055 MANUAL CALL POINT FIRE & GAS DETECTION SYSTEM INSTRUMENT THORN SECURITY M800Ex ia IIC T5 66
419 TURRET ZONE 2 GD-026 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT IRMAX AA-AC-011-AC-01 NO PLATE AT SITE
420 TURRET ZONE 2 ZI0102 LIMIT SWITCH CRUDE OIL PIG RECEIVER INSTRUMENT NO PLATE AT SITE
421 TURRET ZONE 2 TI020B TEMPERATURE INDICATOR CRUDE OIL PIG RECEIVER INSTRUMENT ROSEMOUNT 3144P 02170058 ia IIC T6 66
422 TURRET ZONE 2 840-JB-0323 JUNCTION BOX FIRE & GAS DETECTION SYSTEM INSTRUMENT Weidmuller TB10 NO PLATE AT SITE
423 TURRET ZONE 2 PT-0204 PRESSURE TRANSMITTER HEAT TRACING PIPING INSTRUMENT ROSEMOUNT NO PLATE AT SITE
424 TURRET ZONE 2 ZI-0202 LIMIT SWITCH HEAT TRACING PIPING INSTRUMENT EQUIPMENT BEYOND REACH
425 TURRET ZONE 2 LT-1004 LEVEL TRANSMITTER HEAT TRACING PIPING INSTRUMENT ROSEMOUNT ia IIC T5 Plate faded
426 TURRET ZONE 2 LI-1004 LEVEL TRANSMITTER HEAT TRACING PIPING INSTRUMENT ROSEMOUNT ia IIC T5 Plate faded
427 TURRET ZONE 2 PT-0104 PRESSURE TRANSMITTER HEAT TRACING PIPING INSTRUMENT ROSEMOUNT NO PLATE AT SITE
428 TURRET ZONE 2 TT-0107 PRESSURE TRANSMITTER HEAT TRACING PIPING INSTRUMENT ROSEMOUNT Plate faded
429 TURRET ZONE 2 325-LS-1091 LEVEL SWITCH HPU INSTRUMENT NO PLATE AT SITE
430 TURRET ZONE 2 325-LS-2091 LEVEL SWITCH HPU INSTRUMENT NO PLATE AT SITE
431 TURRET ZONE 2 840-PS-2093 PRESSURE SWITCH HPU INSTRUMENT NO PLATE AT SITE
432 TURRET ZONE 2 840-PS-2094 PRESSURE SWITCH HPU INSTRUMENT NO PLATE AT SITE
433 TURRET ZONE 2 840-PS-2095 PRESSURE SWITCH HPU INSTRUMENT NO PLATE AT SITE
434 TURRET ZONE 2 325-LS-2093 LEVEL SWITCH HPU INSTRUMENT CORTEM GROUP SX-26.1N d IIC T6 66
435 TURRET ZONE 2 325-LS-2093 LEVEL SWITCH HPU INSTRUMENT CORTEM GROUP SX-26.1N d IIC T6 66
436 TURRET ZONE 2 325-PT-1094 PRESSURE TRANSMITTER HPU INSTRUMENT NO PLATE AT SITE
437 TURRET ZONE 2 325-SV-0101 SOLENOID VLAVE HPU INSTRUMENT BIFOLD FLUID POWER d 66
438 TURRET ZONE 2 325-SV-0201 SOLENOID VLAVE HPU INSTRUMENT BIFOLD FLUID POWER d 66
439 TURRET ZONE 2 840-JB-5012 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
440 TURRET ZONE 2 840-JB-5032 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
441 TURRET ZONE 2 840-JB-0325 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
442 TURRET ZONE 2 840-JB-5013 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
443 TURRET ZONE 2 840-JB-5033 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
444 TURRET ZONE 2 PA-A5A/12 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
445 TURRET ZONE 2 PA-B5A/11 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
446 TURRET ZONE 2 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY HP-15(T) de IIB+H2 T5 56 NO TAG AT SITE
447 TURRET ZONE 2 PA-B5A/10 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE
448 TURRET ZONE 2 PA-A5A/11 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE
449 TURRET ZONE 2 840-JB-0303 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
450 TURRET ZONE 2 840-JB-0304 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
451 TURRET ZONE 2 840-JB-1004 JUNCTION BOX PA SPEAKER TELECOM Weidmuller TB10 ia IIC T6
452 TURRET ZONE 2 CAM-01 CCTV CAMERA CCTV SYSTEM TELECOM PELCO WORLDWIDE EHX8E EXD IIB - IP66 - EQUIPMENT BEYOND REACH
453 TURRET ZONE 2 CAM-01 CCTV CAMERA CCTV SYSTEM TELECOM PELCO WORLDWIDE EHX8E EXD IIB - IP66 - EQUIPMENT BEYOND REACH
454 UPPER DE+B175:B185CK (METERING SKID) ZONE 2 LT-U-MS4 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36 d IIC T4 66 NO TAG AT SITE
455 UPPER DECK ZONE 2 ELT-U-EX8 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
456 UPPER DECK ZONE 2 ELT-U-EX9 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
457 UPPER DECK ZONE 2 ELT-U-EX10 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
458 UPPER DECK ZONE 2 ELT-U-EX11 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
459 UPPER DECK ZONE 2 ELT-U-EX12 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
460 UPPER DECK ZONE 2 ELT-U-EX13 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
461 UPPER DECK ZONE 1 JB-FL-01 FLOODLIGHT JUNCTION BOX LIGHTING SYSTEM ELECTRICAL WALSALL LTD WEST BROMWICH U.K TYPE GL501 e II T6 66 NO TAG AT SITE
462 UPPER DECK ZONE 1 JB-FL-02 FLOODLIGHT JUNCTION BOX LIGHTING SYSTEM ELECTRICAL WALSALL LTD WEST BROMWICH U.K TYPE GL501 e II T6 66 NO TAG AT SITE
463 UPPER DECK ZONE 1 JB-FL-03 FLOODLIGHT JUNCTION BOX LIGHTING SYSTEM ELECTRICAL WALSALL LTD WEST BROMWICH U.K TYPE GL501 e II T6 66 NO TAG AT SITE
464 UPPER DECK ZONE 1 JB-FL-04 FLOODLIGHT JUNCTION BOX LIGHTING SYSTEM ELECTRICAL WALSALL LTD WEST BROMWICH U.K TYPE GL501 e II T6 66 NO TAG AT SITE
465 UPPER DECK ZONE 1 ISOLATOR HEATER GAS SCRUBBER ELECTRICAL STAHL e II T6 66 NO TAG AT SITE
466 UPPER DECK ZONE 1 ELECTRICAL HEATER BUNDLE GAS SCRUBBER ELECTRICAL FATI-CUSAGO (MI) ITALY d IIB T3 66 NO TAG AT SITE
467 UPPER DECK ZONE 1 JUNCTION BOX, HEATER GAS SCRUBBER ELECTRICAL FATI-CUSAGO (MI) ITALY d IIB T3 66 NO TAG AT SITE
468 UPPER DECK ZONE 1 ELECTRICAL JB ELECTRICAL JUNCTION BOX OILY SEPARATOR ELECTRICAL Weidmuller e IIC T6 NO TAG AT SITE
469 UPPER DECK ZONE 1 C040 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5
470 UPPER DECK ZONE 1 C041 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5
471 UPPER DECK ZONE 1 C039 MANUAL CALL POINT FIRE & GAS DETECTION SYSTEM INSTRUMENT THORN SECURITY CP840Ex ia IIC T5
472 UPPER DECK ZONE 1 C042 MANUAL CALL POINT FIRE & GAS DETECTION SYSTEM INSTRUMENT THORN SECURITY CP840Ex ia IIC T5
473 UPPER DECK ZONE 1 PUSH BUTTON EMERGENCY SHUTDOWN INSTRUMENT CEAG GHG411 de IIC T6 NO TAG AT SITE
474 UPPER DECK ZONE 1 PUSH BUTTON EMERGENCY SHUTDOWN INSTRUMENT CEAG GHG411 de IIC T6 NO TAG AT SITE

Page 6 of 9
EX Database

Equipment
ID Deck/Process Area Zone Tag Availability (Yes/No) Equipment Name Package/System Description Discipline Manufacturer Model Serial No Ex Class Gas Group Temp Class IP Rating Remarks
Protection Level
475 UPPER DECK ZONE 1 ANALYZER PANEL GAS SCRUBBER INSTRUMENT EMERSON PROCESS MANAGEMENT X STREAM FD-1R AD1171868042 de IIB+H2 T4 66 NO TAG AT SITE
476 UPPER DECK ZONE 1 ANALYZER PANEL GAS SCRUBBER INSTRUMENT EMERSON PROCESS MANAGEMENT X STREAM FD-1R AD1171868041 de IIB+H2 T4 66 NO TAG AT SITE
477 UPPER DECK ZONE 1 FG-ZHS-008 LIMIT SWITCH GAS SCRUBBER INSTRUMENT NO PLATE AT SITE
478 UPPER DECK ZONE 1 DS-JB001 JUNCTION BOX GAS SCRUBBER INSTRUMENT NO PLATE AT SITE
479 UPPER DECK ZONE 1 DS-JB001 JUNCTION BOX GAS SCRUBBER INSTRUMENT NO PLATE AT SITE
480 UPPER DECK ZONE 1 FG-FCV-001 FLOW CONTROL VALVE GAS SCRUBBER INSTRUMENT ECKARDT INVENSYS 83/038640 ia IIB T6
481 UPPER DECK ZONE 1 LEVEL TRANSMITTER GAS SCRUBBER INSTRUMENT ROSEMOUNT ia IIC T4 66 NO TAG AT SITE
482 UPPER DECK ZONE 1 LEVEL SWITCH HIGH GAS SCRUBBER INSTRUMENT KSR KUBLER D69439 ia IIC T6 NO TAG AT SITE
483 UPPER DECK ZONE 1 LEVEL SWITCH LOW GAS SCRUBBER INSTRUMENT KSR KUBLER D69439 ia IIC T6 NO TAG AT SITE
484 UPPER DECK ZONE 1 FG-ZSL-002 LIMIT SWITCH GAS SCRUBBER INSTRUMENT EL-O-MATIC ESO-100 M1A0.A.00N0 11 2 GD 120257090/08 NO PLATE AT SITE
485 UPPER DECK ZONE 1 IA-PSL-001 PRESSURE SWITCH LOW GAS SCRUBBER INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 PLATE FADED
486 UPPER DECK ZONE 1 FG-PSL-003 PRESSURE SWITCH LOW GAS SCRUBBER INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 PLATE FADED
487 UPPER DECK ZONE 1 PRESSURE DIFFRENCE TRANSMITTER GAS SCRUBBER INSTRUMENT ROSEMOUNT 3051 ia IIC T5 66 NO TAG AT SITE
488 UPPER DECK ZONE 1 FG-PCV-001 PRESSURE CONTROL VALVE GAS SCRUBBER INSTRUMENT FISHER FIELD VUE NO PLATE AT SITE
489 UPPER DECK ZONE 1 PRESSURE TRANSMITTER GAS SCRUBBER INSTRUMENT ROSEMOUNT d IIC T5 66 NO TAG AT SITE
490 UPPER DECK ZONE 1 FG-TIT-003 TEMPERATURE TRANSMITTER GAS SCRUBBER INSTRUMENT ROSEMOUNT 644SAI1XAM5Q4 ia IIC T5
491 UPPER DECK ZONE 1 FG-PS-004 PRESSURE SWITCH LOW GAS SCRUBBER INSTRUMENT SOR 5PM-A5-M2-C2A-P/PPSPA1 PLATE FADED
492 UPPER DECK ZONE 1 HPS HIGH OPERATING PRESSURE SWITCH OILY SEPARATOR INSTRUMENT UNITED ELECTRIC CONTROLS CO e IIC T6 66 Gb NO TAG AT SITE
493 UPPER DECK ZONE 1 LPS LOW AIR PRESSURE SWITCH OILY SEPARATOR INSTRUMENT UNITED ELECTRIC CONTROLS CO e IIC T6 66 Gb NO TAG AT SITE
494 UPPER DECK ZONE 1 CONTROL PANEL CONTROL PANEL OILY SEPARATOR INSTRUMENT ADALET 27500-J509 d IIB 66 NO TAG AT SITE
495 UPPER DECK ZONE 1 CONTROL PANEL OIL SENSING PROBE OILY SEPARATOR INSTRUMENT DELTA LS320N-1.00-S6-2.00-220-LE-00-S LS 70450-2 d IIC T4 NO TAG AT SITE
496 UPPER DECK ZONE 1 AOV 1 LIMIT SWITCH VALVE OILY SEPARATOR INSTRUMENT Velba ( Body valve) NO TAG & PLATE AT SITE
497 UPPER DECK ZONE 1 AOV 2 LIMIT SWITCH VALVE OILY SEPARATOR INSTRUMENT Velba ( Body valve) NO TAG & PLATE AT SITE
498 UPPER DECK ZONE 1 AOV 3 LIMIT SWITCH VALVE OILY SEPARATOR INSTRUMENT Velba ( Body valve) NO TAG & PLATE AT SITE
499 UPPER DECK ZONE 1 AOV 1 SOLENOID JB OILY SEPARATOR INSTRUMENT NO TAG & PLATE AT SITE
500 UPPER DECK ZONE 1 AOV 2 SOLENOID JB OILY SEPARATOR INSTRUMENT NO TAG & PLATE AT SITE
501 UPPER DECK ZONE 1 AOV 3 SOLENOID JB OILY SEPARATOR INSTRUMENT NO TAG & PLATE AT SITE
502 UPPER DECK (AFT OFF. AREA) ZONE 2 ELT-U-EX15 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
503 UPPER DECK (AFT OFF. AREA) ZONE 2 ELT-U-EX16 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX PA070815004 nA II T4 67
504 UPPER DECK (BEHIND GYM) ZONE 2 PA-B4A/10 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
505 UPPER DECK (CRANE) ZONE 1 GD-034 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus d IIB+H2 T6
506 UPPER DECK (FR55-FR61) ZONE 1 GD-021 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus d IIB+H2 T6
507 UPPER DECK (FR55-FR61) ZONE 1 GD-022 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus d IIB+H2 T6
508 UPPER DECK (FR55-FR61) ZONE 1 GD-023 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus d IIB+H2 T6
509 UPPER DECK (FR55-FR61) ZONE 1 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus d IIB+H2 T6 NO TAG AT SITE
510 UPPER DECK (FR69-FR77) ZONE 1 GD-025 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus d IIB+H2 T6
511 UPPER DECK (FR75-FR85) ZONE 1 GD-030 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT IRMAX AA-AC-011-AC-01 NO PLATE AT SITE
512 UPPER DECK (FR75-FR85) ZONE 1 GD-031 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus 901447 d IIB+H2 T6 66
513 UPPER DECK (METERING SKID) ZONE 1 LT-U-MS1 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36 d IIC T4 66
514 UPPER DECK (METERING SKID) ZONE 1 ELT-U-MS2 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36NIB de Mb ib IIC T4 66
515 UPPER DECK (METERING SKID) ZONE 1 LT-U-MS3 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36 d IIC T4 66
516 UPPER DECK (METERING SKID) ZONE 1 ELT-U-MS4 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36NIB de Mb ib IIC T4 66
517 UPPER DECK (METERING SKID) ZONE 1 LT-U-MS5 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36 d IIC T4 66
518 UPPER DECK (METERING SKID) ZONE 2 DB-001 STARTER PANEL (DENSITY PUMP) METERING SKID ELECTRICAL d
519 UPPER DECK (METERING SKID) ZONE 2 DB-002 DISTRIBUTION BOARD METERING SKID ELECTRICAL d SAME TAG AT SITE
520 UPPER DECK (METERING SKID) ZONE 2 DB-002 DISTRIBUTION BOARD METERING SKID ELECTRICAL d SAME TAG AT SITE
521 UPPER DECK (METERING SKID) ZONE 2 DB-003 DISTRIBUTION BOARD METERING SKID ELECTRICAL d
522 UPPER DECK (METERING SKID) ZONE 2 DB-004 DISTRIBUTION BOARD (HEAT TRACING) METERING SKID ELECTRICAL d
523 UPPER DECK (METERING SKID) ZONE 2 DB-005 DISTRIBUTION BOARD (SKID LIGHTING) METERING SKID ELECTRICAL d
524 UPPER DECK (METERING SKID) ZONE 2 MOV-6511A MOV METERING SKID ELECTRICAL ROTORK 43941-1 SG16530-108 PLATE FADED
525 UPPER DECK (METERING SKID) ZONE 2 MOV-6511B MOV METERING SKID ELECTRICAL ROTORK 43941-1 SG16530-109 PLATE FADED
526 UPPER DECK (METERING SKID) ZONE 2 MOV-6511C MOV METERING SKID ELECTRICAL ROTORK 43941-1 SG16530-105 PLATE FADED
527 UPPER DECK (METERING SKID) ZONE 2 MOV-6512A MOV METERING SKID ELECTRICAL ROTORK 43941-1 SG16530-102 PLATE FADED
528 UPPER DECK (METERING SKID) ZONE 2 MOV-6512B MOV METERING SKID ELECTRICAL ROTORK 43941-1 SG16530-101 PLATE FADED
529 UPPER DECK (METERING SKID) ZONE 2 MOV-6512C MOV METERING SKID ELECTRICAL ROTORK 43941-1 SG16530-110 PLATE FADED
530 UPPER DECK (METERING SKID) ZONE 2 MOV-6513A MOV METERING SKID ELECTRICAL ROTORK 43941-1 SG16530-106 PLATE FADED
531 UPPER DECK (METERING SKID) ZONE 2 MOV-6513B MOV METERING SKID ELECTRICAL ROTORK 43941-1 SG16530-103 PLATE FADED
532 UPPER DECK (METERING SKID) ZONE 2 MOV-6513C MOV METERING SKID ELECTRICAL ROTORK 43941-1 SG16530-104 PLATE FADED
533 UPPER DECK (METERING SKID) ZONE 2 MOV-6510A MOV METERING SKID ELECTRICAL ROTORK 43941-1 SG16530-107 PLATE FADED
534 UPPER DECK (METERING SKID) ZONE 2 MOV-6510B MOV METERING SKID ELECTRICAL ROTORK 50365EP-2 PLATE FADED
535 UPPER DECK (METERING SKID) ZONE 2 PM-6510 MOTOR METERING SKID ELECTRICAL CMG NTD90524-4 d IIB T4 66 Gb
536 UPPER DECK (METERING SKID) ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON TERMINATOR ZP e II T4 66 NO TAG AT SITE
537 UPPER DECK (METERING SKID) ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON TERMINATOR ZP e II T4 66 NO TAG AT SITE
538 UPPER DECK (METERING SKID) ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON TERMINATOR ZP e II T4 66 NO TAG AT SITE
539 UPPER DECK (METERING SKID) ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON TERMINATOR ZP e II T4 66 NO TAG AT SITE
540 UPPER DECK (METERING SKID) ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON TERMINATOR ZP e II T4 66 NO TAG AT SITE
541 UPPER DECK (METERING SKID) ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON TERMINATOR ZP e II T4 66 NO TAG AT SITE
542 UPPER DECK (METERING SKID) ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON TERMINATOR ZP e II T4 66 NO TAG AT SITE
543 UPPER DECK (METERING SKID) ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON TERMINATOR ZP e II T4 66 NO TAG AT SITE
544 UPPER DECK (METERING SKID) ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON TERMINATOR ZP e II T4 66 NO TAG AT SITE
545 UPPER DECK (METERING SKID) ZONE 1 JUNCTION BOX METERING SKID ELECTRICAL THERMON TERMINATOR ZP e II T4 66 NO TAG AT SITE
546 UPPER DECK (METERING SKID) ZONE 2 LT-U-MS5 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36 d IIC T4 66 NO TAG AT SITE
547 UPPER DECK (METERING SKID) ZONE 2 LT-U-MS6 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36 d IIC T4 66 NO TAG AT SITE
548 UPPER DECK (METERING SKID) ZONE 2 LT-U-MS7 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36 d IIC T4 66 NO TAG AT SITE
549 UPPER DECK (METERING SKID) ZONE 2 LT-U-MS8 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36 d IIC T4 66 NO TAG AT SITE
550 UPPER DECK (METERING SKID) ZONE 2 ELT-U-MS3 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36NIB de Mb ib IIC T4 66 NO TAG AT SITE
551 UPPER DECK (METERING SKID) ZONE 2 ELT-U-MS4 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36NIB de Mb ib IIC T4 66 NO TAG AT SITE
552 UPPER DECK (METERING SKID) ZONE 2 ELT-U-MS5 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36NIB de Mb ib IIC T4 66 NO TAG AT SITE
553 UPPER DECK (METERING SKID) ZONE 2 ELT-U-MS6 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36NIB de Mb ib IIC T4 66 NO TAG AT SITE

Page 7 of 9
EX Database

Equipment
ID Deck/Process Area Zone Tag Availability (Yes/No) Equipment Name Package/System Description Discipline Manufacturer Model Serial No Ex Class Gas Group Temp Class IP Rating Remarks
Protection Level
554 UPPER DECK (METERING SKID) ZONE 2 ELT-U-MS7 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL CEAG ELLK 92036/36NIB de Mb ib IIC T4 66 NO TAG AT SITE
555 UPPER DECK (METERING SKID) ZONE 2 NLT-MS-FL32 FLOODLIGHT LIGHTING SYSTEM ELECTRICAL AQUAL SIGNAL 1076030000 67 NO EX INFO.
556 UPPER DECK (METERING SKID) ZONE 2 DJB-001 JUNCTION BOX (DIGITAL) METERING SKID INSTRUMENT eia II T6 66 NO PLATE AT SITE
557 UPPER DECK (METERING SKID) ZONE 2 DJB-002 JUNCTION BOX (DIGITAL) METERING SKID INSTRUMENT Weidmuller e II T6 66/67
558 UPPER DECK (METERING SKID) ZONE 2 DJB-003 JUNCTION BOX (DIGITAL) METERING SKID INSTRUMENT Weidmuller e II T6 66/67
559 UPPER DECK (METERING SKID) ZONE 2 DJB-004 JUNCTION BOX (DIGITAL) METERING SKID INSTRUMENT Weidmuller e II T6 66/67
560 UPPER DECK (METERING SKID) ZONE 2 DJB-005 JUNCTION BOX (FGS) METERING SKID INSTRUMENT Weidmuller e II T6 66/67
561 UPPER DECK (METERING SKID) ZONE 2 AJB-001 JUNCTION BOX (ANALOGUE) METERING SKID INSTRUMENT eia II T6 66
562 UPPER DECK (METERING SKID) ZONE 2 AJB-002 JUNCTION BOX (ANALOGUE) METERING SKID INSTRUMENT Weidmuller e II T6 66/67
563 UPPER DECK (METERING SKID) ZONE 2 SP-001 AUTO SAMPLING PANEL METERING SKID INSTRUMENT JICKOOT NO PLATE AT SITE
564 UPPER DECK (METERING SKID) ZONE 2 DT-6510A DENSITY METER METERING SKID INSTRUMENT MICRO-MOTION 7835BAASAJTAAX 356603 ia IIC T6
565 UPPER DECK (METERING SKID) ZONE 2 DT-6510B DENSITY METER METERING SKID INSTRUMENT MICRO-MOTION 7835BAASAJTAAX 356602 ia IIC T6
566 UPPER DECK (METERING SKID) ZONE 2 FT-6511A FLOW METER METERING SKID INSTRUMENT FAURE HERMAN BP20154 ia IIC T6 66
567 UPPER DECK (METERING SKID) ZONE 2 FT-6511B FLOW METER METERING SKID INSTRUMENT FAURE HERMAN BP20154 ia IIC T6 66
568 UPPER DECK (METERING SKID) ZONE 2 FT-6512A FLOW METER METERING SKID INSTRUMENT FAURE HERMAN BP20154 ia IIC T6 66
569 UPPER DECK (METERING SKID) ZONE 2 FT-6512B FLOW METER METERING SKID INSTRUMENT FAURE HERMAN BP20154 ia IIC T6 66
570 UPPER DECK (METERING SKID) ZONE 2 FT-6513A FLOW METER METERING SKID INSTRUMENT FAURE HERMAN BP20154 ia IIC T6 66
571 UPPER DECK (METERING SKID) ZONE 2 FT-6513B FLOW METER METERING SKID INSTRUMENT FAURE HERMAN BP20154 ia IIC T6 66
572 UPPER DECK (METERING SKID) ZONE 2 TT-6511 TEMPERATURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA YTA110 ia IIC T5 67
573 UPPER DECK (METERING SKID) ZONE 2 TT-6512 TEMPERATURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA YTA110 ia IIC T5 67
574 UPPER DECK (METERING SKID) ZONE 2 TT-6513 TEMPERATURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA YTA110 ia IIC T5 67
575 UPPER DECK (METERING SKID) ZONE 2 TT-6510A TEMPERATURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA YTA110 ia IIC T5 67
576 UPPER DECK (METERING SKID) ZONE 2 TT-6510B TEMPERATURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA YTA110 ia IIC T5 67
577 UPPER DECK (METERING SKID) ZONE 2 TT-6510C TEMPERATURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA YTA110 ia IIC T5 67
578 UPPER DECK (METERING SKID) ZONE 2 PT-6511 PRESSURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA EXJ530A ia IIC T4 67
579 UPPER DECK (METERING SKID) ZONE 2 PT-6512 PRESSURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA EXJ530A ia IIC T4 67
580 UPPER DECK (METERING SKID) ZONE 2 PT-6513 PRESSURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA EXJ530A ia IIC T4 67
581 UPPER DECK (METERING SKID) ZONE 2 PT-6510A PRESSURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA EXJ530A ia IIC T4 67
582 UPPER DECK (METERING SKID) ZONE 2 PT-6510B PRESSURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA EXJ530A ia IIC T4 67
583 UPPER DECK (METERING SKID) ZONE 2 PT-6510C PRESSURE TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA EXJ530A ia IIC T4 67
584 UPPER DECK (METERING SKID) ZONE 2 PDT-6511 DP TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA EJX110A ia IIC T4 67
585 UPPER DECK (METERING SKID) ZONE 2 PDT-6512 DP TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA EJX110A ia IIC T4 67
586 UPPER DECK (METERING SKID) ZONE 2 PDT-6513 DP TRANSMITTER METERING SKID INSTRUMENT YOKOGAWA EJX110A ia IIC T4 67
587 UPPER DECK (METERING SKID) ZONE 2 FY-6511 CONTROL VALVE POSITIONER METERING SKID INSTRUMENT ROTORK SP0142 ia IIC T4 66
588 UPPER DECK (METERING SKID) ZONE 2 FY-6512 CONTROL VALVE POSITIONER METERING SKID INSTRUMENT ROTORK SP0142 ia IIC T4 66
589 UPPER DECK (METERING SKID) ZONE 2 FY-6513 CONTROL VALVE POSITIONER METERING SKID INSTRUMENT ROTORK SP0142 ia IIC T4 66
590 UPPER DECK (METERING SKID) ZONE 2 FY-6510A CONTROL VALVE POSITIONER METERING SKID INSTRUMENT ROTORK SP0142 ia IIC T4 66
591 UPPER DECK (METERING SKID) ZONE 2 AT-6510 ANALYZER METERING SKID INSTRUMENT THERMO 4200 10364292-1 NO PLATE AT SITE
592 UPPER DECK (METERING SKID) ZONE 2 ZS-6510A LIMIT SWITCH METERING SKID INSTRUMENT PLATE FADED
593 UPPER DECK (METERING SKID) ZONE 2 ZS-6510B LIMIT SWITCH METERING SKID INSTRUMENT PLATE FADED
594 UPPER DECK (METERING SKID) ZONE 2 ZS-6510C LIMIT SWITCH METERING SKID INSTRUMENT PLATE FADED
595 UPPER DECK (METERING SKID) ZONE 2 ZS-6510D LIMIT SWITCH METERING SKID INSTRUMENT PLATE FADED
596 UPPER DECK (METERING SKID) ZONE 2 PSH-6510 PRESSURE SWITCH METERING SKID INSTRUMENT PLATE FADED
597 UPPER DECK (METERING SKID) ZONE 2 RO-6510 FLOW SWITCH METERING SKID INSTRUMENT KROHNE H250 ia IIC T6
598 UPPER DECK (METERING SKID) ZONE 2 SOLENOID VALVE (AUTO SAMPLING) METERING SKID INSTRUMENT EQUIPMENT INSIDE PANEL SP001
599 UPPER DECK (METERING SKID) ZONE 2 SOLENOID VALVE (AUTO SAMPLING) METERING SKID INSTRUMENT EQUIPMENT INSIDE PANEL SP001
600 UPPER DECK (METERING SKID) ZONE 1 PA-A5A/2 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, METERING SKID
601 UPPER DECK (METERING SKID) ZONE 1 PA-B5A/2 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
602 UPPER DECK (METERING SKID) ZONE 2 BEACON FIRE & GAS DETECTION SYSTEM TELECOM EQUIPMENT BEYOND REACH
603 UPPER DECK (OFF LOADING) ZONE 2 GD-024 GAS DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT CROWCON DETECTION INSTRUMENT Nimbus d IIB+H2 T6 66 EQUIPMENT BEYOND REACH
604 UPPER DECK (OFF LOADING) ZONE 2 C047 MANUAL CALL POINT FIRE & GAS DETECTION SYSTEM INSTRUMENT THORN SECURITY CP840Ex ia IIC T5 PLATE FADED
605 UPPER DECK (OILY WATER SAPERATOR) ZONE 1 PA-A4A/10 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
606 UPPER DECK (OILY WATER SAPERATOR) ZONE 1 PA-B4A/11 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
607 UPPER DECK (PAINT ROOM) ZONE 1 PA-A4A/15 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, PAINT STORE
608 UPPER DECK (PAINT ROOM) ZONE 1 PA-B4A/15 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, PAINT STORE
609 UPPER DECK (PORT SIDE) ZONE 1 PA-B5A/7 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, PORT SITE
610 UPPER DECK (PORT SIDE) ZONE 1 PA-A5A/8 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, PORT SITE
611 UPPER DECK (PORT SIDE) ZONE 1 PA-B5A/6 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
612 UPPER DECK (PORT SIDE) ZONE 1 PA-A5A/3 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, PORT SITE
613 UPPER DECK (PORT SIDE) ZONE 1 PA-B5A/3 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
614 UPPER DECK (PORT SIDE) ZONE 1 PA-A5A/7 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, PORT SITE
615 UPPER DECK (PORT SIDE) ZONE 2 PA-A5A/1 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, INFRONT PUMP ROOM, PORT SITE
616 UPPER DECK (PORT SIDE) ZONE 2 PA-B3A/4 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY HP-15(T) de IIB+H2 T5 56 NO TAG AT SITE, INFRONT PUMP ROOM, PORT SITE
617 UPPER DECK (PUMP ROOM) ZONE 1 ELT-U-PUM1 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX ASA GTX 240469 d IIC T6 67
618 UPPER DECK (PUMP ROOM) ZONE 1 ELT-PUM-NE1 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL Tenchor Iitalsmea EVF-P236 d IIC T4 66
619 UPPER DECK (PUMP ROOM) ZONE 1 LT-PUM-EX1 LIGHTING FIXTURE LIGHTING SYSTEM ELECTRICAL GLAMOX ASA GTX 240469 d IIC T6 67
620 UPPER DECK (SKID OILY WATER) ZONE 1 JB-FL-01 FLOODLIGHT JUNCTION BOX LIGHTING SYSTEM ELECTRICAL WALSALL LTD WEST BROMWICH U.K TYPE GL501 e II T6 66 NO TAG AT SITE
621 UPPER DECK (STAR BOARD) ZONE 1 PA-A4A/11 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, STAR BOARD
622 UPPER DECK (STAR BOARD) ZONE 1 PA-B4A/13 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, STAR BOARD
623 UPPER DECK (STAR BOARD) ZONE 1 PA-A4A/13 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
624 UPPER DECK (STAR BOARD) ZONE 1 PA-B4A/14 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
625 UPPER DECK (STAR BOARD) ZONE 1 PA-A4A/17 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
626 UPPER DECK (STAR BOARD) ZONE 1 PA-B4A/18 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67
627 UPPER DECK (STAR BOARD) ZONE 1 PA-B4A/17 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, STAR BOARD
628 UPPER DECK (STAR BOARD) ZONE 1 PA-A4A/16 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, STAR BOARD
629 UPPER DECK (STAR BOARD) ZONE 2 PA-A4A/9 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY HP-15(T) de IIB+H2 T5 56
630 UPPER DECK (STORE LAB PORT SIDE) ZONE 1 PA-B5A/4 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, STORE ROOM LAB
631 UPPER DECK (STORE LAB PORT SIDE) ZONE 1 PA-A5A/5 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, STORE ROOM LAB
632 UPPER DECK (STORE ROOM) ZONE 1 PA-B4A/15 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, STORE ROOM

Page 8 of 9
EX Database

Equipment
ID Deck/Process Area Zone Tag Availability (Yes/No) Equipment Name Package/System Description Discipline Manufacturer Model Serial No Ex Class Gas Group Temp Class IP Rating Remarks
Protection Level
633 UPPER DECK (STORE ROOM) ZONE 1 PA-A4A/14 SPEAKER PA SPEAKER TELECOM DNH KRAGER NORWAY DSP-15 de IIB+H2 T5 67 NO TAG AT SITE, STORE ROOM
634 UPPER DECK(CRANE OP ROOM) ZONE 1 C056 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO EQUIPMENT BEYOND REACH
635 UPPER DECK(FR55-FR61) ZONE 1 C048 MANUAL CALL POINT FIRE & GAS DETECTION SYSTEM INSTRUMENT THORN SECURITY CP840Ex ia IIC T5 PLATE FADED
636 UPPER DECK(FR69-FR77) ZONE 1 C050 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5
637 UPPER DECK(FR69-FR77) ZONE 1 C057 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5 NO PLATE AT SITE
638 UPPER DECK(FR69-FR77) ZONE 1 C052 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5
639 UPPER DECK(FR69-FR77) ZONE 1 C058 SMOKE DETECTOR FIRE & GAS DETECTION SYSTEM INSTRUMENT TYCO ia IIC T5 PLATE FADED
640 UPPER DECK(FR69-FR77) ZONE 1 C049 MANUAL CALL POINT FIRE & GAS DETECTION SYSTEM INSTRUMENT THORN SECURITY CP840Ex ia IIC T5
641 UPPER DECK(FR69-FR77) ZONE 1 C051 MANUAL CALL POINT FIRE & GAS DETECTION SYSTEM INSTRUMENT THORN SECURITY CP840Ex ia IIC T5 PLATE FADED
642 UPPER DECK, OFFLOADING ZONE 2 CAM-05 CCTV CAMERA CCTV SYSTEM TELECOM PELCO WORLDWIDE EHX8E EXD IIB - IP66 - EQUIPMENT BEYOND REACH

Page 9 of 9
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 14 of 16
2020

APPENDIX 4 – EX DATABASE POST SITE VISIT SLIDES


04 TH DEC 2019 MVOT FSO ORKID

MVOT FSO ORKID


EX DATABASE DEVELOPMENT
SITE VERIFICATION CLOSING
OUTLINE

02 Overview 03 Project
Site Visit Summary

01 04 Project
Objective Site Visit Findings Result

05 Project
AOB
Slide / 2
01
OBJECTIVE

Slide / 3
To brief site visit findings & result.

1. To present FSO Orkid Field Ex Asset Verification


Results

2. To validate findings (Signing-Ofl) with Operation Rep.


and FSO Master.

OBJECTIVE

Slide / 4
02
PROJECT OVERVIEW
SCOPE OF WORK

No. Description Deliverables


Safety Critical Equipment (SCE)
1 1. SCE Identification Template
Identification
1. Specific PS Excel Files
2 Performance Standard Development
2. Assurance task target value template

3 Development of AIR MS 1. New or updated AIR MS Manual

1. Ex Equipment database
Ex Equipment register & inspection
2. Report on document review vs. site verification
4 checklist development as per
findings
IEC60079 Part 17
3. Inspection checklist.
1. RBI Study report
Risk Based Inspection (RBI) study &
5 2. Mark up P&ID of corrosion loops
Flexible Pipe/Riser
3. Flexible Pipe/Riser Integrity Mgt Plan Report
03
SITE VISIT SUMMARY

Slide / 7
SUMMARY
Ex LlST
642 EQUIPMENT IN THE HAZARDOUS ELECTRICAL Ex
239
INSTRUMENT Ex
342
TELECOM Ex
61
AREA CLASSIFICATION
No TAG
FINDINGS
. NOS

1 122 NO TAG AT SITE

2 75 PLATE FADED

3 80 NO PLATE AT SITE Ex LlST


171 EQUIPMENT NOT HAVING
4 32 NO EX INFO EX DATA
ELECTRICAL INSTRUMENT TELECOM
5 19 NO TAG & PLATE AT SITE 27 142 2
04
SITE VISIT FINDINGS
RESULT

Slide / 9
FINDINGS

NO TAG
AT SITE
CONTROL VALVE AND PRESSURE TRANSMITTER
(141) (BOILER)

LEVEL SWITCH (GAS SPEAKER AND DETECTOR


SCRUBBER AREA) (PAGA & FIRE AND GAS)
FINDINGS

PLATE
FADED
JUNCTION BOX(TURRET AREA)
(75)

LEVEL TRANSMITTER AND MCP


JUNCTION BOX (BOILER)
(INSTRUMENT & FIRE AND GAS)
FINDINGS

NO
PLATE
AT SITE ISOLATOR (GAS SCRUBBER)
(80)

BEACON & RADIO REAPEATER GAS DETECTOR AND LIGHTING (FIRE & GAS,
(TELECOM) ELECTRICAL)
FINDINGS

NO EX
INFO (32)
GAS DETECTOR (PUMP ROOM)

LIMIT SWITCH
(BOILER)
PRESURE SWITCH (BOILER AND SCRUBBER)
FINDINGS

OTHERS

CABLE GLAND LOOSE


NO EARTHING (GAS SCRUBBER)

CABLE TEAR (GAS SCRUBBER)


05
AOB
SHAPING
A WORLD
OF TRUST
W W W. B U R E AU V E R I TA S . C O M
EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 15 of 16
2020

APPENDIX 5 – EX DATABASE INSPECTION SAMPLING ACTIVITY


EX DATABASE CLOSE-OUT REPORT
Date
Prepared by Page
January
Bureau Veritas (M) Sdn Bhd 16 of 16
2020

APPENDIX 6 – EX INSPECTION CHECKLIST


Ex'd Visual Site Inspection Checklist
Date:

Project

Inspected Location

HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type

Equipment S/Number

EX Certificate Number

EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:

Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 1)
2.1 General
2.1.1 Equipment is appropriate to the EPL/Zone requirements
of the location
2.1.2 Degree of protection (IP grade) of equipment is
appropriate for the level of protection/group/conductivity

2.1.3 Equipment circuit identification is available


2.1.4 Enclosure, glass parts and glass-to-metal sealing
gaskets and/or compounds are satisfactory
2.1.5 There is no evidence of unauthorized modifications
2.1.6 Bolts, cable entry devices (direct and indirect) and
blanking elements are of the correct type and are
complete and tight–Visual check
2.1.7 Threaded covers on enclosures are of the correct type,
are tight and secured–visual check
2.1.8 Equipment Specific (Lighting)
2.1.8.1 HID lamps are not indicating EOL effects
2.1.9 Equipment Specific (Motor)
2.1.9.1 Motor fans have sufficient clearance to the enclosure
and/or covers, cooling systems are undamaged, motor
foundations have no indentations or cracks.

2.1.9.2 The ventilation airflow is not impeded


2.2 Installation - General
2.2.1 There is no obvious damage to cables
2.2.2 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.2.3 Earthing connections, including any supplementary
earthing bonding connections are satisfactory (for
example connections are tight and conductors are of
sufficient cross-section) – visual check

2.2.4 Obstructions adjacent to flameproof flanged joints are in


accordance with IEC 60079-14
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors

2.3.2 No undue accumulation of dust and dirt


3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

1/4
Ex'e Visual Site Inspection Checklist
Date:

Project

Inspected Location

HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type

Equipment S/Number

EX Certificate Number

EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:

Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 1)
2.1 General
2.1.1 Equipment is appropriate to the EPL/Zone requirements
of the location
2.1.2 Degree of protection (IP grade) of equipment is
appropriate for the level of protection/group/conductivity

2.1.3 Equipment circuit identification is available


2.1.4 Enclosure, glass parts and glass-to-metal sealing
gaskets and/or compounds are satisfactory
2.1.5 There is no evidence of unauthorized modifications
2.1.6 Bolts, cable entry devices (direct and indirect) and
blanking elements are of the correct type and are
complete and tight–Visual check
2.1.7 Equipment Specific (Lighting)
2.1.7.1 Fluorescent lamps are not indicating EOL effects
2.1.7.2 HID lamps are not indicating EOL effects
2.1.8 Equipment Specific (Motor)
2.1.8.1 Motor fans have sufficient clearance to the enclosure
and/or covers, cooling systems are undamaged, motor
foundations have no indentations or cracks.
2.1.8.2 The ventilation airflow is not impeded
2.2 Installation - General
2.2.1 There is no obvious damage to cables
2.2.2 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.2.3 Earthing connections, including any supplementary
earthing bonding connections are satisfactory (for
example connections are tight and conductors are of
sufficient cross-section) – visual check
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors
2.3.2 No undue accumulation of dust and dirt
3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

2/4
Ex'n Visual Site Inspection Checklist
Date:

Project

Inspected Location

HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type

Equipment S/Number

EX Certificate Number

EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:

Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 1)
2.1 General
2.1.1 Equipment is appropriate to the EPL/Zone requirements
of the location
2.1.2 Degree of protection (IP grade) of equipment is
appropriate for the level of protection/group/conductivity

2.1.3 Equipment circuit identification is available


2.1.4 Enclosure, glass parts and glass-to-metal sealing
gaskets and/or compounds are satisfactory
2.1.5 There is no evidence of unauthorized modifications
2.1.6 Bolts, cable entry devices (direct and indirect) and
blanking elements are of the correct type and are
complete and tight–Visual check
2.1.7 Equipment Specific (Lighting)
2.1.7.1 Fluorescent lamps are not indicating EOL effects
2.1.7.2 HID lamps are not indicating EOL effects
2.1.8 Equipment Specific (Motor)
2.1.8.1 Motor fans have sufficient clearance to the enclosure
and/or covers, cooling systems are undamaged, motor
foundations have no indentations or cracks.

2.1.8.2 The ventilation airflow is not impeded


2.2 Installation - General
2.2.1 There is no obvious damage to cables
2.2.2 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.2.3 Earthing connections, including any supplementary
earthing bonding connections are satisfactory (for
example connections are tight and conductors are of
sufficient cross-section) – visual check
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors

2.3.2 No undue accumulation of dust and dirt


3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

3/4
Ex'i Visual Site Inspection Checklist
Date:

Project

Inspected Location

HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type

Equipment S/Number

EX Certificate Number

EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:

Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 2 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 2)
2.1 General
2.1.1 Circuit and/or equipment documentation is appropriate
to the EPL/Zone
2.1.2 Cable glands and blanking elements are the correct
type, complete and tight
– physical check
– visual check
2.1.3 There is no evidence of unauthorized modifications
2.1.4 Diode safety barriers, galvanic isolators, relays and
other energy limiting devices are of the approved type,
installed in accordance with the certification
requirements and securely earthed where required
2.2 Installation - General
2.2.1 There is no obvious damage to cables
2.2.2 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors
2.3.2 No undue external accumulation of dust and dirt
3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

4/4
Ex'd Close Site Inspection Checklist
Date:

Project

Inspected Location

HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type

Equipment S/Number

EX Certificate Number

EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:

Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 1)
2.1 General
2.1.1 Equipment is appropriate to the EPL/Zone
requirements of the location
2.1.2 Equipment group is correct
2.1.3 Equipment temperature class is correct
2.1.4 Degree of protection (IP grade) of equipment is
appropriate for the level of protection/group/conductivity
2.1.5 Equipment circuit identification is available
2.1.6 Enclosure, glass parts and glass-to-metal sealing
gaskets and/or compounds are satisfactory
2.1.7 There is no evidence of unauthorized modifications
2.1.8 Bolts, cable entry devices (direct and indirect) and
blanking elements are of the correct type and are
complete and tight– physical check
2.1.9 Threaded covers on enclosures are of the correct type,
are tight and secured– physical check
2.1.10 Breathing and draining devices are satisfactory
2.1.11 Equipment Specific (Lighting)
2.1.11.1 HID lamps are not indicating EOL effects
2.1.12 Equipment Specific (Motor)
2.1.12.1 Motor fans have sufficient clearance to the enclosure
and/or covers, cooling systems are undamaged, motor
foundations have no indentations or cracks.
2.1.12.2 The ventilation airflow is not impeded
2.2 Installation - General
2.2.1 There is no obvious damage to cables
2.2.2 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.2.3 Earthing connections, including any supplementary
earthing bonding connections are satisfactory (for
example connections are tight and conductors are of
sufficient cross-section) – visual check
2.2.4 Obstructions adjacent to flameproof flanged joints are
in accordance with IEC 60079-14
2.2.5 Variable voltage/frequency installation complies with
documentation
2.2.6 Installation - Heating Systems
2.2.6.1 The setting of the safety cut off is sealed
2.2.6.2 Reset of a heating system safety cut off possible with
tool only
2.2.6.3 Auto-reset is not possible
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors
2.3.2 No undue accumulation of dust and dirt
3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

1/4
Ex'e Close Site Inspection Checklist
Date:

Project

Inspected Location

HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type

Equipment S/Number

EX Certificate Number

EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:

Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 1)
2.1 General
2.1.1 Equipment is appropriate to the EPL/Zone
requirements of the location
2.1.2 Equipment group is correct
2.1.3 Equipment temperature class is correct
2.1.4 Degree of protection (IP grade) of equipment is
appropriate for the level of protection/group/conductivity
2.1.5 Equipment circuit identification is available
2.1.6 Enclosure, glass parts and glass-to-metal sealing
gaskets and/or compounds are satisfactory
2.1.7 There is no evidence of unauthorized modifications
2.1.8 Bolts, cable entry devices (direct and indirect) and
blanking elements are of the correct type and are
complete and tight– physical check
2.1.9 Breathing and draining devices are satisfactory
2.1.10 Equipment Specific (Lighting)
2.1.10.1 Fluorescent lamps are not indicating EOL effects
2.1.10.2 HID lamps are not indicating EOL effects
2.1.11 Equipment Specific (Motor)
2.1.11.1 Motor fans have sufficient clearance to the enclosure
and/or covers, cooling systems are undamaged, motor
foundations have no indentations or cracks.
2.1.11.2 The ventilation airflow is not impeded
2.2 Installation - General
2.2.1 There is no obvious damage to cables
2.2.2 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.2.3 Earthing connections, including any supplementary
earthing bonding connections are satisfactory (for
example connections are tight and conductors are of
sufficient cross-section) – visual check
2.2.4 Variable voltage/frequency installation complies with
documentation
2.2.5 Installation - Heating Systems
2.2.5.1 The setting of the safety cut off is sealed
2.2.5.2 Reset of a heating system safety cut off possible with
tool only
2.2.5.3 Auto-reset is not possible
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors
2.3.2 No undue accumulation of dust and dirt
3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

2/4
Ex'n Close Site Inspection Checklist
Date:

Project

Inspected Location

HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type

Equipment S/Number

EX Certificate Number

EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:

Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 1)
2.1 General
2.1.1 Equipment is appropriate to the EPL/Zone
requirements of the location
2.1.2 Equipment group is correct
2.1.3 Equipment temperature class is correct
2.1.4 Degree of protection (IP grade) of equipment is
appropriate for the level of protection/group/conductivity
2.1.5 Equipment circuit identification is available
2.1.6 Enclosure, glass parts and glass-to-metal sealing
gaskets and/or compounds are satisfactory
2.1.7 There is no evidence of unauthorized modifications
2.1.8 Bolts, cable entry devices (direct and indirect) and
blanking elements are of the correct type and are
complete and tight– physical check
2.1.9 Breathing and draining devices are satisfactory
2.1.10 Equipment Specific (Lighting)
2.1.10.1 Fluorescent lamps are not indicating EOL effects
2.1.10.2 HID lamps are not indicating EOL effects
2.1.11 Equipment Specific (Motor)
2.1.11.1 Motor fans have sufficient clearance to the enclosure
and/or covers, cooling systems are undamaged, motor
foundations have no indentations or cracks.
2.1.11.2 The ventilation airflow is not impeded
2.2 Installation - General
2.2.1 There is no obvious damage to cables
2.2.2 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.2.3 Earthing connections, including any supplementary
earthing bonding connections are satisfactory (for
example connections are tight and conductors are of
sufficient cross-section) – visual check
2.2.4 Variable voltage/frequency installation complies with
documentation
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors
2.3.2 No undue accumulation of dust and dirt
3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

3/4
Ex'i Close Site Inspection Checklist
Date:

Project

Inspected Location

HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type

Equipment S/Number

EX Certificate Number

EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:

Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 2 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 2)
2.1 General
2.1.1 Circuit and/or equipment documentation is appropriate
to the EPL/Zone
2.1.2 Equipment installed is that specified in the
documentation
2.1.3 Circuit and/or equipment category and group correct
2.1.4 IP rating of equipment is appropriate to the Group III
material present
2.1.5 Equipment temperature class is correct
2.1.6 Ambient temperature range of the apparatus is correct
for the installation
2.1.7 Service temperature range of the apparatus is correct
for the installation
2.1.8 Installation is clearly labelled
2.1.9 Cable glands and blanking elements are the correct
type, complete and tight
– physical check
– visual check
2.1.10 There is no evidence of unauthorized modifications
2.1.11 Diode safety barriers, galvanic isolators, relays and
other energy limiting devices are of the approved type,
installed in accordance with the certification
requirements and securely earthed where required
2.1.12 The maximum voltage Um of the associated apparatus
is not exceeded
2.2 Installation - General
2.2.1 There is no obvious damage to cables
2.2.2 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors
2.3.2 No undue external accumulation of dust and dirt
3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

4/4
Ex'd Detailed Site Inspection Checklist
Date:
Project
Inspected Location
HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type
Equipment S/Number
EX Certificate Number
EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:
Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 1)
2.1 General
2.1.1 Equipment is appropriate to the EPL/Zone
requirements of the location
2.1.2 Equipment group is correct
2.1.3 Equipment temperature class is correct
2.1.4 Degree of protection (IP grade) of equipment is
appropriate for the level of
protection/group/conductivity
2.1.5 Equipment circuit identification is correct
2.1.6 Equipment circuit identification is available
2.1.7 Enclosure, glass parts and glass-to-metal sealing
gaskets and/or compounds are satisfactory
2.1.8 There is no damage or unauthorized modifications
2.1.9 Bolts, cable entry devices (direct and indirect) and
blanking elements are of the correct type and are
complete and tight– physical check
2.1.10 Threaded covers on enclosures are of the correct
type, are tight and secured– physical check
2.1.11 Joint surfaces are clean and undamaged and
gaskets, if any, are satisfactory and positioned
2.1.12 correctly
Condition of enclosure gaskets is satisfactory
2.1.13 There is no evidence of ingress of water or dust in the
enclosure in accordance with the IP rating
2.1.14 Dimensions of flanged joint gaps are:
– within the limits in accordance with manufacturer’s
documentation or
– within maximum values permitted by relevant
construction standard at time of installation or
– within maximum values permitted by site
documentation
2.1.15 Breathing operation is satisfactory– ( type “nR” only)
2.1.16 Breathing and draining devices are satisfactory
2.1.17 Equipment Specific (Lighting)
2.1.17.1 HID lamps are not indicating EOL effects
2.1.17.2 Lamp type, rating, pin configuration and position are
correct
2.1.18 Equipment Specific (Motor)
2.1.18.1 Motor fans have sufficient clearance to the enclosure
and/or covers, cooling systems are undamaged,
motor foundations have no indentations or cracks.

2.1.18.2 The ventilation airflow is not impeded


2.1.18.3 Insulation resistance (IR) of the motor windings is
satisfactory
2.2 Installation - General
2.2.1 Type of cable is appropriate
2.2.2 There is no obvious damage to cables
2.2.3 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.2.4 Stopping boxes and cable boxes are correctly filled
2.2.5 Integrity of conduit system and interface with mixed
system maintained
2.2.6 Earthing connections, including any supplementary
earthing bonding connections are satisfactory (for
example connections are tight and conductors are of
sufficient cross-section) – physical check
2.2.7 Fault loop impedance (TN systems) or earthing
resistance (IT systems) is satisfactory
2.2.8 Automatic electrical protective devices are set
correctly (auto-reset not possible)
2.2.9 Automatic electrical protective devices operate within
permitted limits

1/8
Ex'd Detailed Site Inspection Checklist
Date:
Project
Inspected Location
HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type
Equipment S/Number
EX Certificate Number
EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:
Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
2.2.10 Specific conditions of use (if applicable) are complied
with
2.2.11 Cables not in use are correctly terminated
2.2.12 Obstructions adjacent to flameproof flanged joints are
in accordance with IEC 60079-14
2.2.13 Variable voltage/frequency installation complies with
documentation
2.2.14 Installation - Heating Systems
2.2.14.1 Temperature sensors function according to
manufacturer’s documents
2.2.14.2 Safety cut off devices function according to
manufacturer’s documents
2.2.14.3 The setting of the safety cut off is sealed
2.2.14.4 Reset of a heating system safety cut off possible with
tool only
2.2.14.5 Auto-reset is not possible
2.2.14.6 Reset of a safety cut off under fault conditions is
prevented
2.2.14.7 Safety cut off independent from control system
2.2.14.8 Level switch is installed and correctly set, if required
2.2.14.9 Flow switch is installed and correctly set, if required
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors
2.3.2 No undue accumulation of dust and dirt
3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

2/8
Ex'e Detailed Site Inspection Checklist
Date:
Project
Inspected Location
HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type
Equipment S/Number
EX Certificate Number
EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:
Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 1)
2.1 General
2.1.1 Equipment is appropriate to the EPL/Zone
requirements of the location
2.1.2 Equipment group is correct
2.1.3 Equipment temperature class is correct
2.1.4 Degree of protection (IP grade) of equipment is
appropriate for the level of
2.1.5 protection/group/conductivity
Equipment circuit identification is correct
2.1.6 Equipment circuit identification is available
2.1.7 Enclosure, glass parts and glass-to-metal sealing
gaskets and/or compounds are satisfactory
2.1.8 There is no damage or unauthorized modifications
2.1.9 Bolts, cable entry devices (direct and indirect) and
blanking elements are of the correct type and are
complete and tight– physical check
2.1.10 Condition of enclosure gaskets is satisfactory
2.1.11 There is no evidence of ingress of water or dust in the
enclosure in accordance with the IP rating
2.1.12 Electrical connections are tight
2.1.13 Unused terminals are tightened
2.1.14 Encapsulated components are undamaged
2.1.15 Flameproof components are undamaged
2.1.16 Breathing operation is satisfactory– ( type “nR” only)
2.1.17 Breathing and draining devices are satisfactory
2.1.18 Equipment Specific (Lighting)
2.1.18.1 Fluorescent lamps are not indicating EOL effects
2.1.18.2 HID lamps are not indicating EOL effects
2.1.18.3 Lamp type, rating, pin configuration and position are
correct
2.1.19 Equipment Specific (Motor)
2.1.19.1 Motor fans have sufficient clearance to the enclosure
and/or covers, cooling systems are undamaged,
motor foundations have no indentations or cracks.
2.1.19.2 The ventilation airflow is not impeded
2.1.19.3 Insulation resistance (IR) of the motor windings is
satisfactory
2.2 Installation - General
2.2.1 Type of cable is appropriate
2.2.2 There is no obvious damage to cables
2.2.3 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.2.4 Integrity of conduit system and interface with mixed
system maintained
2.2.5 Earthing connections, including any supplementary
earthing bonding connections are satisfactory (for
example connections are tight and conductors are of
sufficient cross-section) – physical check
2.2.6 Fault loop impedance (TN systems) or earthing
resistance (IT systems) is satisfactory
2.2.7 Automatic electrical protective devices are set
correctly (auto-reset not possible)
2.2.8 Automatic electrical protective devices operate within
permitted limits
2.2.9 Specific conditions of use (if applicable) are complied
with
2.2.10 Cables not in use are correctly terminated
2.2.11 Variable voltage/frequency installation complies with
documentation
2.2.12 Installation - Heating Systems
2.2.12.1 Temperature sensors function according to
manufacturer’s documents
2.2.12.2 Safety cut off devices function according to
manufacturer’s documents

3/8
Ex'e Detailed Site Inspection Checklist
Date:
Project
Inspected Location
HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type
Equipment S/Number
EX Certificate Number
EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:
Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
2.2.12.3 The setting of the safety cut off is sealed
2.2.12.4 Reset of a heating system safety cut off possible with
tool only
2.2.12.5 Auto-reset is not possible
2.2.12.6 Reset of a safety cut off under fault conditions is
prevented
2.2.12.7 Safety cut off independent from control system
2.2.12.8 Level switch is installed and correctly set, if required
2.2.12.9 Flow switch is installed and correctly set, if required
2.2.13 Installation - Motors
2.2.13.1 Motor protection devices operate within the permitted
tE or tA time limits.
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors

2.3.2 No undue accumulation of dust and dirt


2.3.3 Electrical Insulation is clean and dry
3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

4/8
Ex'n Detailed Site Inspection Checklist
Date:
Project
Inspected Location
HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type
Equipment S/Number
EX Certificate Number
EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:
Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 1)
2.1 General
2.1.1 Equipment is appropriate to the EPL/Zone
requirements of the location
2.1.2 Equipment group is correct
2.1.3 Equipment temperature class is correct
2.1.4 Degree of protection (IP grade) of equipment is
appropriate for the level of
protection/group/conductivity
2.1.5 Equipment circuit identification is correct
2.1.6 Equipment circuit identification is available
2.1.7 Enclosure, glass parts and glass-to-metal sealing
gaskets and/or compounds are satisfactory
2.1.8 There is no damage or unauthorized modifications
2.1.9 Bolts, cable entry devices (direct and indirect) and
blanking elements are of the correct type and are
complete and tight– physical check
2.1.10 Condition of enclosure gaskets is satisfactory
2.1.11 There is no evidence of ingress of water or dust in the
enclosure in accordance with the IP rating
2.1.12 Electrical connections are tight
2.1.13 Unused terminals are tightened
2.1.14 Enclosed-break and hermetically sealed devices are
undamaged
2.1.15 Encapsulated components are undamaged
2.1.16 Flameproof components are undamaged
2.1.17 Restricted breathing enclosure is satisfactory – ( type
“nR” only)
2.1.18 Test port, if fitted, is functional– ( type “nR” only)
2.1.19 Breathing operation is satisfactory– ( type “nR” only)
2.1.20 Breathing and draining devices are satisfactory
2.1.21 Equipment Specific (Lighting)
2.1.21.1 Fluorescent lamps are not indicating EOL effects
2.1.21.2 HID lamps are not indicating EOL effects
2.1.21.3 Lamp type, rating, pin configuration and position are
correct
2.1.22 Equipment Specific (Motor)
2.1.22.1 Motor fans have sufficient clearance to the enclosure
and/or covers, cooling systems are undamaged,
motor foundations have no indentations or cracks.
2.1.22.2 The ventilation airflow is not impeded
2.1.22.3 Insulation resistance (IR) of the motor windings is
satisfactory
2.2 Installation - General
2.2.1 Type of cable is appropriate
2.2.2 There is no obvious damage to cables
2.2.3 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.2.4 Integrity of conduit system and interface with mixed
system maintained
2.2.5 Earthing connections, including any supplementary
earthing bonding connections are satisfactory (for
example connections are tight and conductors are of
sufficient cross-section) – physical check
2.2.6 Fault loop impedance (TN systems) or earthing
resistance (IT systems) is satisfactory
2.2.7 Automatic electrical protective devices are set
correctly (auto-reset not possible)
2.2.8 Automatic electrical protective devices operate within
permitted limits
2.2.9 Specific conditions of use (if applicable) are complied
with
2.2.10 Cables not in use are correctly terminated

5/8
Ex'n Detailed Site Inspection Checklist
Date:
Project
Inspected Location
HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type
Equipment S/Number
EX Certificate Number
EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:
Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 1 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
2.2.11 Variable voltage/frequency installation complies with
documentation
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors

2.3.2 No undue accumulation of dust and dirt


2.3.3 Electrical Insulation is clean and dry
3.0 Overall Inspection Remarks

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

6/8
Ex'i Detailed Site Inspection Checklist
Date:
Project
Inspected Location
HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type
Equipment S/Number
EX Certificate Number
EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:
Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 2 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A
1.0 Prior to Site
1.0.1 HAC Layout is available
1.0.2 IECEx Certificate is available
Checked?
No. Description Findings/ Remarks
Y N N/A
2.0 Site Verification (IEC 60079-17: 2013 Clause 6 Table 2)
2.1 General
2.1.1 Circuit and/or equipment documentation is appropriate
to the EPL/Zone
2.1.2 Equipment installed is that specified in the
documentation
2.1.3 Circuit and/or equipment category and group correct
2.1.4 IP rating of equipment is appropriate to the Group III
material present
2.1.5 Equipment temperature class is correct
2.1.6 Ambient temperature range of the apparatus is correct
for the installation
2.1.7 Service temperature range of the apparatus is correct
for the installation
2.1.8 Installation is clearly labelled
2.1.9 Enclosure, glass parts and glass-to-metal sealing
gaskets and/or compounds are satisfactory
2.1.10 Cable glands and blanking elements are the correct
type, complete and tight
– physical check
– visual check
2.1.11 There are no unauthorized modifications
2.1.13 Diode safety barriers, galvanic isolators, relays and
other energy limiting devices are of the approved type,
installed in accordance with the certification
requirements and securelyearthed where required
2.1.14 Condition of enclosure gaskets is satisfactory
2.1.15 Electrical connections are tight
2.1.16 Printed circuit boards are clean and undamaged
2.1.17 The maximum voltage Um of the associated apparatus
is not exceeded
2.2 Installation - General
2.2.1 Cables are installed in accordance with the
documentation
2.2.2 Cable screens are earthed in accordance with the
documentation
2.2.3 There is no obvious damage to cables
2.2.4 Sealing of trunking, ducts, pipes and/or conduits is
satisfactory
2.2.5 Point-to-point connections are all correct (initial
inspection only)
2.2.6 Earth continuity is satisfactory (e.g. connections are
tight, conductors are of sufficient cross- section) for
non-galvanically isolated circuits
2.2.7 Earth connections maintain the integrity of the type of
protection
2.2.8 Intrinsically safe circuit earthing is satisfactory
2.2.9 Insulation resistance is satisfactory
2.2.10 Separation is maintained between intrinsically safe and
non-intrinsically safe circuits in common distribution
boxes or relay cubicles
2.2.11 Short-circuit protection of the power supply is in
accordance with the documentation
2.2.12 Specific conditions of use (if applicable) are complied
with
2.2.13 Cables not in use are correctly terminated
2.3 Environment
2.3.1 Equipment is adequately protected against corrosion,
weather, vibration and other adverse factors
2.3.2 No undue external accumulation of dust and dirt
3.0 Overall Inspection Remarks

7/8
Ex'i Detailed Site Inspection Checklist
Date:
Project
Inspected Location
HAC Zone Marking Hazardous Area Zone:________________ Temp Class: ________________ Gas Group _________
Equipment, Model/Type
Equipment S/Number
EX Certificate Number
EX Certificate Marking Equipment Protection Level:________________ Temp Class: ________________ Gas Group _________ IP Rating __________
Drawing/ Document Ref:
Code/ Standard Ref: IEC 60079-17: 2013 Clause 6 Table 2 (Main reference)
Checked?
No. Description Findings/ Remarks
Y N N/A

NAME SIGNATURE DATE


Inspected By (BV):
Verified By (Client):

8/8