Book of Procedures

sidharaProduct FP – 60 Z AC UPS Procedure code FP60Z_0218_0-0


Consecutive no. 0218 Author A.GODIKAT
Procedure revision 0.0
Description Battery charging/discharging current scale factor calibration.
Special tools Multimeter, Clamp meter, laptop with PPVis Rev.2.0 (8738) and LAN cable.
PNU = parameter

Target of the Procedure


Charging discharging current scale factor calibration
This procedure should be used in case of ...
If deviation found between actual and display value. This test should be performed by certified engineer.

No. Step description Note


1 Starting point:
UPS in Normal Operation with load connected; External battery switch closed;
Connect the DC current clamp to the battery line;
Connect your notebook to the service port X9 and start PPVis Rev.2;
2 Select page : [7] “DIC1 Calibration“
3 Set “Access Level” to “Expert”: “PNU 51=3”;
4 Open Q3 in order to switch the unit on battery mode;
5 Read PNU 23.1 “Battery Charging/Discharging Current”;

6 Set PNU 731.13 in order to align the value “Battery current” on “Status Display PPVis” to
the measure read on the DC Current clamp

7 Let the batteries discharge, because you need the Charger in Current Limit when you will
close Q3;
8 Close Q3;
9 Set PNU 731.10 in order to align the measure read on the DC Current clamp 10% of AH
capacity.

10 Set “Access Level” back to “Normal Operation” (PNU 51=1). Restart the unit.
11 Procedure completed.

Bop Rev Error: Reference source Error: Reference source not found 10 September Page 1/ 1
not found 2015
PROCEDURE: Battery charging/discharging current scale factor calibration