0218 - Battery Charging Discharging Current Scale Factor Calibration - Rev.0
0218 - Battery Charging Discharging Current Scale Factor Calibration - Rev.0
0218 - Battery Charging Discharging Current Scale Factor Calibration - Rev.0
6 Set PNU 731.13 in order to align the value “Battery current” on “Status Display PPVis” to
the measure read on the DC Current clamp
7 Let the batteries discharge, because you need the Charger in Current Limit when you will
close Q3;
8 Close Q3;
9 Set PNU 731.10 in order to align the measure read on the DC Current clamp 10% of AH
capacity.
10 Set “Access Level” back to “Normal Operation” (PNU 51=1). Restart the unit.
11 Procedure completed.
Bop Rev Error: Reference source Error: Reference source not found 10 September Page 1/ 1
not found 2015
PROCEDURE: Battery charging/discharging current scale factor calibration