EXHAUST BACKPRESSURE CALCULATOR - RESULTS

CALCULATIONS MADE 11/25/2021

INPUT DATA
Input By

Customer: Chinchina Job Name: Colegios Job Number:

Engine Data Piping Data Silencer Data


Manufacturer: Clarke Pipe Size: 65mm Manufacturer: Clarke UK
Engine Model: KA4H-UFKA24 Number 90° elbows: 2 Pipe Size: 65mm
Engine RPM: 2800 Number 45° elbows: 0 Model: 0U061042
Engine HP: 33.5 KW Straight Pipe (M): 10 Application: Industrial
Connection: Clamped

OUTPUT DATA
Exh Flow ( m³/sec ): 0.18

Temperature ( °C ): 635.0

Max Backpressure ( mm water ): 889

Min Backpressure ( mm water ): 0

EXHAUST PIPE RECOMMENDATIONS


BACKPRESSURE CALCULATIONS ( MM WATER )

460.4 Pipe
+ 103.3 Silencer (see note 1)
563.7 Total
889.0 Maximum Allowable Backpressure
Result: Total backpressure is within limits

1) CAUTION: Silencer Backpressure is based upon a Clarke UK provided Silencer. Actual Silencer Backpressure will vary depending
upon the actual Silencer used (manufacturer, size, type and model). If the total Backpressure from the pipe, Silencer and orifice plate (if
required) is close to the engine Maximum Allowed Backpressure, it is highly recommended you obtain the actual Backpressure (for the
engine exhaust flow given above) on the Silencer being used and then confirm that the total Backpressure is still under the Maximum
Allowed Backpressure.
2) Schedule 40 pipe used in calculations
3) All pipe sizes and lengths are in millimeters and meters.

COPYRIGHT © 2021 CLARKE®, ALL RIGHTS RESERVED