All current, voltage, and power data are specified as RMS values. Connector type 8-pin multiple contact strip
Rated frequency frated 50 Hz, 60 Hz Differential current 4
input channels
16.7 Hz (for rail protection devices only)
Measuring range DC -24 mA to +24 mA
Protection-class Rated current Measuring Measuring
current transformers Irated range of the range of the Fault < 0.5 % of measuring range
modular non-modular Input impedance 140 Ω
devices devices Conversion principle Delta-sigma (16 bit)
5A 0 A to 500 A 0 A to 250 A Permissible potential DC 20 V
1A 0 A to 100 A 0 A to 50 A difference between
Instrument trans- 5A 0 A to 8 A 0 A to 8 A channels
formers Galvanic separation DC 700 V
1A 0 A to 1.6 A 0 A to 1.6 A
from ground/housing
Power consumption Approx. 0.1 VA
Permissible overload DC 100 mA continuously
per current circuit at
rated current Measurement repeti- 200 ms
tion
Thermal rating 500 A for 1 s
(protection and instru- 150 A for 10 s
Voltage Input
4.6 ment transformers) 20 A continuously
25 A for 3 min
All current, voltage, and power data are specified as RMS values.
30 A for 2 min
Rated frequency frated 50 Hz, 60 Hz
Dynamic load-carrying 1250 A one half wave
capacity 16.7 Hz (for rail-protection devices only)
Input and output IO202/IO208/IO211/ IO215
modules IO214
Measuring-Transducer Inputs (via Module ARC-CD-3FO)
Measuring range 0 V bis 200 V 0 V bis 7,07 V