Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Appendix SIEMENS FMS 7KE85

Technical data – Current Inputs

Current Inputs Measuring-Transducer Inputs (via Module ANAI-CA-4EL)

All current, voltage, and power data are specified as RMS values. Connector type 8-pin multiple contact strip
Rated frequency frated 50 Hz, 60 Hz Differential current 4
input channels
16.7 Hz (for rail protection devices only)
Measuring range DC -24 mA to +24 mA
Protection-class Rated current Measuring Measuring
current transformers Irated range of the range of the Fault < 0.5 % of measuring range
modular non-modular Input impedance 140 Ω
devices devices Conversion principle Delta-sigma (16 bit)
5A 0 A to 500 A 0 A to 250 A Permissible potential DC 20 V
1A 0 A to 100 A 0 A to 50 A difference between
Instrument trans- 5A 0 A to 8 A 0 A to 8 A channels
formers Galvanic separation DC 700 V
1A 0 A to 1.6 A 0 A to 1.6 A
from ground/housing
Power consumption Approx. 0.1 VA
Permissible overload DC 100 mA continuously
per current circuit at
rated current Measurement repeti- 200 ms
tion
Thermal rating 500 A for 1 s
(protection and instru- 150 A for 10 s
Voltage Input
4.6 ment transformers) 20 A continuously
25 A for 3 min
All current, voltage, and power data are specified as RMS values.
30 A for 2 min
Rated frequency frated 50 Hz, 60 Hz
Dynamic load-carrying 1250 A one half wave
capacity 16.7 Hz (for rail-protection devices only)
Input and output IO202/IO208/IO211/ IO215
modules IO214
Measuring-Transducer Inputs (via Module ARC-CD-3FO)
Measuring range 0 V bis 200 V 0 V bis 7,07 V

Connector type AVAGO AFBR-4526Z Input impedance 200 kΩ 7 kΩ

Number of trans- 3 Thermal rating 230 V continuously 20 V continuously


ceivers
Fiber type Polymer Optical Fiber (POF) 1 mm Integrated Power Supply
Receiver For modular devices, the following printed circuit-board assemblies
have a power supply:
Maximum -10 dBm ± 2 dBm
Minimum -40 dBm ± 2 dBm PS201 – Power supply of the base module and of the 1st device row
Spectrum 400 nm to 1100 nm PS203 – Voltage supply of 2nd device row
Attenuation In the case of plastic optical fibers, you can CB202 – Plug in module assembly with integrated power supply, for
expect a path attenuation of 0.2 dB/m Addi- example, to accommodate communication modules
tional attenuation comes from the plug and Permissible DC 19 V DC 48 V to DC 300 V
sensor head. voltage ranges to DC 60 V
AC 80 V to AC 265 V, 50 Hz/60 Hz
Optical budget 1 Minimal 25 dB
(PS201, PS203,
Analog sampling rate 16 kHz CB202)
ADC type 10-bit successive approximation Auxiliary rated DC 24 V/DC 48 V DC 60 V/DC 110 V/DC 125 V/
Transmitter voltage VH DC 220 V/
Type LED (PS201, PS203, DC 250 V or
Wavelength λ = 650 nm CB202) AC 100 V/AC 115 V/AC 230 V,
Transmit power Minimum 0 dBm 50 Hz/60 Hz
Maximum 2 dBm Permissible DC 19 V DC 48 V to 150 DC 88 V
Numerical aperture 0.5 2 voltage ranges to DC 60 V V to DC 300 V
(PS101)
Signal rate connection 1 pulse per second AC 80 V to
test AC 265 V, 50 Hz/
60 Hz
Pulse duration connec- 11 μs
tion test
Comment:
1 All values in combination with sensors approved by Siemens.
2 Numerical aperture (NA = sin θ (launch angle))

4.6/1 SIPROTEC 5 ⋅ Devices Protection, Automation and Monitoring ⋅ Siemens SIPROTEC 5.01 - Edition 4