Professional Documents
Culture Documents
AC Loco Refresher-SCR-1
AC Loco Refresher-SCR-1
for
Loco Pilots (Refresher)
CONTACTORS
Contactor is a device, which is used to close or open the high tension circuit and
remotely operated from Loco Pilots desk. No contactor should be operated manually, without
taking necessary precautions.
C. Cam Contactors:
CGR-1, CGR-2 & CGR-3.
D. Drum Contactors:
J1, J2, CTF1, CTF2 & CTF3.
General Instructions
1. Try to clear the block section by coasting or with lower notches or stop the train at
convenient place.
2. Build up maximum air pressure in
MR & RS, if possible.
3. Trip DJ, lower pantograph, keep
HBA on ‘0’.
4. Check flexibility of contactor and
ensure that the flexible shunts are
intact and fixed properly.
5. Check the surface of the fixed and
mobile contacts for any pit or
burnt mark or globules or welding
mark. If necessary, remove the arc
chutes for checking.
6. If any abnormality mentioned
above is noticed, try to clean the
contacts with a cloth or smooth
emery sheet.
7. Wedge the contactor with suitable wedge.
8. After wedging ensure all three contacts closed fully.
ETTC/BZA Page 1
Course Material for Loco Pilot refresher 201.Contactors and Relays
Note: Do not wedge more than two contactors at a time. Inform to TLC and enter in loco
logbook.
PRECAUTIONS
A. After wedging C101, C102 or C103:
1) Energise the loco. Check and ensure proper working of SS2.
2) After reaching pressure to 9.5 kg/cm2 in MR, create sufficient leakage by opening
CDC drain cock to maintain between 8 to 9.5 kg/cm2.
Note: If isolating switch is not placed in '3' position, operate Q118 manually for every
closing of DJ.
ETTC/BZA Page 2
Course Material for Loco Pilot refresher 201.Contactors and Relays
RELAYS:
Relay is a device, which conveys the information regarding proper working of apparatus
to the operator or may cut off the supply if any abnormality in power circuit.
ETTC/BZA Page 3
Course Material for Loco Pilot refresher 201.Contactors and Relays
relay will energises and initiates protective action. In Electric Traction locomotive there
are two types of current relays. They are:
i. Over current relays
ii. Differential current relays
In our locomotive, over current relays are: QLM, QLA, QRSI 1, QRSI 2, QE, QF1 &
QF2.
QLM: It is an over current relay to protect Feeding power circuit from over current.
If over current flows in Feeding Power Circuit, QLM energises and trips DJ.
Note: Setting of QLM: WAG 7 & WAP 4 – 450 Amps. and WAG 5 & WAM 4 - 325 amps.
When QLM is energized, check the following items for any smell/ smoke / fire / oil
splashes.
1. TFILM 1. Oil splashes in HT compartment
2. Roof bushing bar / HT cable 2. GR Safety valves
3. Transformer oil level 3. AO, A33 terminals
4. Transformer explosion door 4. CGR contactors / arc chutes
5. Transformer Silica gel 5. RGR & RPGR
6. GR oil level 6. Oil splashes at under frame
7. GR breather & silica gel valves 7. Transformer oil trap indicator
If there is any abnormality, should not re-set the relay, ask for relief loco. If there
is no abnormality, reset the relay; keep Asst. Loco pilot in the corridor to observe for
abnormality while closing DJ. If there is any abnormality while closing DJ, Asst. Loco
pilot should shout to trip the DJ by Loco pilot. If no abnormality is found, work the
train further duly checking the Feeding Power Circuit equipment for every 15 minutes.
If QLM is energized second time, contact TLC though there is no abnormality and ask
for relief loco.
If QLM energised along with other relays, check the items belonging to
other relay also. If QLM energised along with other relays second time, contact TLC
and ask for relief loco. Note down the readings of meters, time, place etc. Make clear
remarks in logbook and rough journal.
QLA: It is an over current relay to protect Auxiliary power circuit from over current. If
over current flows in Auxiliary Power Circuit, this relay energises and trips DJ. Setting
of QLA in WAG7 & WAP4 is 2000 Amps and in WAG5 & WAM4 is 1400 Amps.
ETTC/BZA Page 4
Course Material for Loco Pilot refresher 201.Contactors and Relays
QRSI1/QRSI2: These are over current relays to protect RSI Blocks 1 & 2 respectively
from over current. If over current comes because of short circuit in Traction Power
Circuit, this relay energises and trips DJ. Setting of QRSI in WAG 7 & WAP 4 is 4000
Amps and in WAG 5 & WAM 4 is 3600 Amps.
QE: It is an over current relay to ATFEX. During RB, if excitation current exceeds
900Amps to ATFEX, this relay energises and causes auto regression of GR.
QF 1&2: These are over current relays for RFs. During RB, if TM output current
exceeds 700Amps, relay QF energises and causes auto regression of GR.
Q20: It is an over voltage relay provided in TPC1. Q20 will energise when the TPC-1
voltage exceeds 865V and Auto regression of GR, Sounding of SON and LSOV lamp
(If provided). If Q 20 is energising at less voltage, work the train by using MPS. If still
losing time, inform to TLC.
ETTC/BZA Page 5
Course Material for Loco Pilot refresher 201.Contactors and Relays
A. Pressure Relays:
QPH: It is a pressure relay provided on the delivery pipeline of MPH. When the oil
pressure is sufficient in the system this relay will be in energised position. Due to any
reason if this relay is not energised, it causes tripping of DJ in operation-B part 1.
B. Circulation Relays:
QVSI1, QVSI2, QVSL1, QVSL2, QVRH, QVMT1, QVMT2 & QVRF: These are air
circulation relays provided to concerned motor air circulation system. If air circulation
is sufficient, concerned relay energises. Otherwise, Loco pilot will experience tripping
failure according to the relay.
Q118:
1. Stop the train at convenient place.
2. Secure the train as per procedure to avoid roll back.
3. Break the seal and open the relay cover.
4. Keep BLDJ & BLVMT in closed condition.
5. Ensure C118 opened fully.
6. Ensure Battery voltage is above 90 volts
7. Ensure MR or RS pressure is above 6.5 kg/cm2.
8. Keep ZPT on ‘1’ and ensure panto raised and touching to contact wire.
9. Press Q118 pallet first then press BP2DJ.
10. Release BP2DJ after extinguishing of LSCHBA and release Q118 after 30 seconds.
Q45:
1. Ensure BLDJ closed, ZPT on 1 and GR on ‘0’.
2. Ensure Battery voltage is above 90 volts.
3. Ensure MR or RS pressure is above 6.5 kg/cm2.
4. Press Q45 pallet manually.
5. Release Q45 after extinguishing of LSCHBA.
Q44:
1. Ensure C118 open fully, BLDJ closed ZPT-1, GR-0 battery voltage and MR/RS
pressure is sufficient.
2. Ensure Q118 energised.
3. Depute Asst. loco pilot to watch RGR from corridor.
4. Press BP2DJ and then press Q44 pallet manually.
ETTC/BZA Page 6
Course Material for Loco Pilot refresher 201.Contactors and Relays
Procedure of Wedging:
BBC TYPE:
Energise wedging: press the both stems and insert the wooden wedge in rear of the
outer bracket. Ensure interlocks are closed / opened properly then release the stems.
De-energise wedging: Ensure that both stems have come out, fully. Insert the wooden
wedge in front of the outer bracket. Ensure interlocks are closed / opened properly then
release the stems.
EEC TYPE:
Energise wedging: Insert the wooden wedge, in front of the pallet.
De-energise wedging: Insert the wooden wedge, in rear of the pallet.
WOAMA TYPE:
To wedge the relay in energise condition. Press the pallet towards the coil and insert
suitable wooden wedge in the other side. In few locos, a latch provided for this
purpose. Few locos are having miniature toggle switch for Q51 relay for wedging in
de-energise position.(Toggle switch in wedge side will make the relay in de-energise
position).
COMAT TYPE:
Release the lock and rotate the lever provided for wedging the relay.
Note: Time lag/Time delay relays are provided with Red and green Lamps. Glowing
of Red Lamp indicates Relay in De-energise position. Glowing of GREEN LAMP
indicates relay in energise position.
ETTC/BZA Page 7
Course Material for Loco Pilot refresher 201.Contactors and Relays
QRS 2:
1. Ensure BP pressure is 5 kg/cm2.
2. When BP pressure reduced, keep MP on ‘0’ and ascertain the cause.
Q50:
Before Wedging After Wedging
1. Ensure J1, J2 are in proper direction 1. Do not operate MPJ.
according to MPJ. 2. Do not perform shunting. If it is required to
2. Ensure CTF 1, 2 & 3 are in Traction perform shunting, operate MPJ ensure J1 &
side. J2 set properly for every movement.
3. Ensure C145 opened fully. 3. Bring MP to ‘0’ when DJ tripped on
notches.
4. Do not use RB.
Q51:
1. Obtain permission from TLC.
2. GR will not regress through Q20/Q48/QRS2/PR2. Hence, ensure correct current rating,
observe LSP and observe BP.
3. Check the relay frequently. If becomes over heat, remove the wedge and contact TLC.
Q118:
Before Wedging After Wedging
1. Ensure C118 opened fully. 1. Ensure C118 open fully.
2. Ensure C107, C105 & C106 opened 2. Ensure proper working of MVRH, MVMT1,
fully. MVMT2, MPH, MVSL1, MVSL2 & ARNO
3. Ensure HVRH, HVMT1, HVMT2, frequently.
HPH, HVSL1, HVSL2, and HQCVAR 3. Ensure transformer oil level is normal.
in ‘1’ position. 4. Avoid quick regression of GR.
5. Observe restricted current rating of 920/500
Amps.
Q44:
Before Wedging After Closing DJ
1. Obtain permission from TLC. 1. Ensure C118 is opened fully and no
2. Conduct GR efficiency test and ensure abnormality in RGR.
GR is moving in 11 to 13 seconds for 2. Ensure OHE supply is above 17.5 KV and
progression 0-32 notches and avoid manual operation of GR.
regression 32-0 notches. 3. Ensure proper working of auxiliaries
3. Ensure GR drum is on ‘0’. provided on Q118 & Q44 branches.
4. Ensure Q118 is normal. 4. Ensure Q118 in energised position and
5. Ensure C118 open fully. avoid quick regression of GR.
6. Ensure HVSI 1 & 2 are in ‘1’ position.
7. Note down transformer oil level.
ETTC/BZA Page 8
Course Material for Loco Pilot refresher 201.Contactors and Relays
Q45:
Before Wedging After Closing DJ
1. Whenever loco is having ‘A’ ending 1. Ensure OHE supply is more than 17.5KV
trouble should not wedge Q45. and proper working of VSI1 & VSI2.
2. Ensure BLDJ open, GR is on ‘0’, ZPT 2. If DJ required to be open for a longer
on ‘1’ and pantograph raised. period remove wedge of Q45 or keep HBA
3. Ensure Q118 & Q44 working normal. on ‘o’ to avoid chattering of Q44 & Q118.
4. Close BLDJ for closing of DJ. 3. If DJ tripped with any reason, open BLDJ
immediately to avoid DJ chattering.
Q45:
Note: After wedging Q45, relays Q118 & Q44 will chatter until such time DJ is closed.
So, close DJ without any delay.
201.12 The following relays may be wedged in energized condition and work with
precautions:
Q44, Q100, Q118, Q45, QRS2, Q50, QTD101, QTD105, QTD106, QSVM, QCON.
201.13 The following relays may be wedged in de-energized condition and work with
precautions : Q52.
PANTOGRAPH
201.14 PANTOGRAPH
Pantograph is collapsible equipment mounted on loco roof to receive the OHE supply
smoothly and spark less at all speeds. Pantograph electrical control circuit is protected by CCPT
(16 AMPS) fuse. Pantograph is raised by ZPT key. ZPT key is having three positions (0,1&2).
When ZPT is operated, concerned pantograph raise/lowers in three stages with the throttle valve
action.
201.14.1 Trouble shooting for pantograph not rising Electrical:
1. Ensure HBA is on ‘1’ position..
2. Battery voltage is above 90 Volts
3. Ensure CCBA & CCPT are in good condition.
4. Ensure ZPT is in ‘1’ or ’2’ position and ZPT wires are intact.
5. Ensure electrical terminals of VEPT are intact and VEPT is energised.
6. Ensure BPEMS Switch is not in pressed condition.
Pneumatic:
1. Ensure MR / RS pressure is above 6.5 Kg/cm2 and RAL is in open position.
2. Ensure PT 1 & 2 cocks are opened.
3. Tap Throttle valve gently.
4. Ensure there is no pneumatic leakages in the pipe lines and VEPT’S.
Mechanical:
No mechanical irregularities in panto mechanism.
ETTC/BZA Page 9
Course Material for Loco Pilot refresher 201.Contactors and Relays
ETTC/BZA Page 10
Course Material for Loco Pilot refresher 201.Contactors and Relays
ETTC/BZA Page 11
Course Material for LP Refresher Course 202. DJ Control Circuit
➢ Close BLDJ, press BLRDJ and observe the LSDJ, UA needle, Auxiliaries sound
& LSCHBA.
➢ After extinguishing of LSCHBA, release BLRDJ. If LSCHBA not extinguishes,
release after re glowing of LSDJ.
➢ Pick up the correct abnormal sign as following manner.
SL INDICATION / ABNORMAL
PROBABLE REASONS
No OPERATION SIGN
On closing BLDJ and ICDJ a. Less air pressure in MR or RS
pressing BLRDJ, LSDJ b. Less battery voltage below 90 V
1 remains glowing c. Q118/ Q45/ Q44/ C118/ EFDJ may not be
energised.
d. Check A conk for any slackness.
Close BLDJ, press BLRDJ. NO TENSION a. Derailment/ Accident (reducing of BP level
LSDJ extinguished, UA in loco)
needle not deviated, no b. Defect in Feeding Power Circuit.
auxiliaries sound, LSCHBA c. Defect in OHE/ track/ formation
2
not extinguished and after d. Cut in Feeding Power circuit.
5.6 seconds LSDJ re-glows e. Foreign body on loco roof.
then release BLRDJ. f. No supply on OHE
g. Panto not touching to contact wire.
ETTC/BZA Page 12
Course Material for LP Refresher Course 202. DJ Control Circuit
Close BLDJ and press BLRDJ , ‘A’ BEGINNING a. Less air pressure or QPDJ defective
LSDJ lamp extinguished and b. Check QOA/ QLA/ QLM for
3 re- glows immediately, then energisation.
release BLRDJ. (ie. LSDJ c. Cut in MTDJ branch or defective MTDJ
FLICKERING) coil
Close BLDJ and press BLRDJ. ‘A’ ENDING a. Defective ARNO
LSDJ extinguished, UA b. Defective QCVAR
needle deviated, auxiliary
4
sound may heard LSCHBA
not extinguished after 5.6
seconds LSDJ re glows.
Close BLDJ and press BLRDJ. OPERATION ‘B’ Defect in
LSDJ extinguished, UA PART-I a. MVSL1/VSL1/ QVSL1
needle deviated, Auxiliary b. MVSL2/VSL2/ QVSL2
5 sound heard, LSCHBA also c. MPH/PH/QPH
extinguished, after releasing d. QCVAR N/O I/L on Q118 branch.
BLRDJ, while counting
15seconds LSDJ re-glows.
Close BLDJ and press BLRDJ. OPERATION ‘B’ Defective Q30
LSDJ extinguished, UA PART-II
needle deviated, auxiliary
6 sound heard, LSCHBA also
extinguished, on releasing
BLRDJ, LSDJ re glows
immediately
Close DJ, close BLVMT, OPERATION ‘O’ Defect in
while counting 30 seconds a. MVRH/VRH/QVRH.
7
LSDJ re-glows. b. MVMT1/VMT1/QVMT1
c. MVMT2/VMT2/QVMT2
Close DJ, close BLVMT and OPERATION ‘I’ Defect in
take one traction notch LSDJ a. MVSI1/VSI1/QVSI1
8
re-glows IMMEDIATELY. b. MVSI2/VSI2/QVSI2 or
c. Sluggish operation of GR.
Close DJ, close BLVMT and OPERATION ‘II’ a. All contactors not closed
take six traction notches. b. Any one of C107 / C105 /C106 not
9 While counting 15 seconds closed
LSDJ re-glows. c. C107, C105 & C106 closed but N/O I/Ls
defective.
DJ trips in various occasions TWAC a. Defective QPDJ
other than above b. Slackness of CCDJ /CCPT/CCA
indications. c. Moisture in system
10 d. Defective SMGR
e. Defective ZPT I/L
f. Momentary defect of any I/L in the DJ
control circuit.
ETTC/BZA Page 13
Course Material for LP Refresher Course 202. DJ Control Circuit
Preparation:
1. Keep MP on zero.
2. Open all top row BL switches.
3. Ensure LSGR is glowing.
4. Safety relays are normal.
5. Ensure C107,C105,C106 open fully.
6. MR / RS pressure above 6.5 Kg/cm2.
7. Battery voltage is above 90 volts.
8. Ensure pantograph is raised fully and touches to OHE.
➢ Close BLDJ, press BLRDJ and observe the LSDJ, UA needle, Auxiliaries sound &
LSCHBA.
➢ After extinguishing of LSCHBA, release BLRDJ. If LSCHBA not extinguishes, release
after re glowing of LSDJ.
➢ Pick up the correct abnormal sign in the following manner.
SL Abnormal
Indication/Operation Probable Reasons
No Sign
1 On closing BLDJ and ICDJ a. Less air pressure in RS or MR
pressing BLRDJ, LSDJ b. Less battery voltage below 90
remains glowing V
c. Less air pressure in VCB unit
d. Q118/ Q45/ Q44/ C118/ MTDJ
not energised.
e. Defective C118 N/O I/L on
MTDJ branch.
f. Check for any slackness of A
conk
2 Close BLDJ, press BLRDJ. NO TENSION a. Derailment/ Accident
LSDJ extinguished, UA (reducing of Vacuum / BP
needle not deviated, no levels in loco)
auxiliaries sound, LSCHBA b. Cut/defect in Feeding
not extinguished and after 5.6 Power Circuit.
seconds LSDJ re-glows then c. Cut/Defect in Auxiliary
release BLRDJ. power circuit.
d. Defect in OHE/ track/
formation
e. Foreign body on loco roof.
f. No supply on OHE.
3 Close BLDJ and press ‘A’ a. Less air pressure or QPDJ
BLRDJ LSDJ lamp BEGINNING defective
extinguished and re- glows b. Check QOA/ QLA/ QLM for
immediately, and then energisation.
release BLRDJ.
(ie. LSDJ FLICKERING)
4 Close BLDJ and press ‘A’ ENDING a. Defective ARNO
BLRDJ. LSDJ extinguished, b. Defective QCVAR
UA needle deviated,
ETTC/BZA Page 14
Course Material for LP Refresher Course 202. DJ Control Circuit
9 Close DJ, close BLVMT and OPERATION a. All contactors not clo
take six traction notches. ‘II’ b. Any one of C107 / C105 /C106
While counting 15 seconds not closed
LSDJ re-glows. c. C107,C105&C106 closed but
N/O I/Ls defective.
d. If CCA melts or Q100
defective.
10 DJ trips in various occasions TWAC a. Defective QPDJ
other than above indications. b. Slackness of CCDJ
/CCPT/CCA
c. Moisture in system
d. Defective SMGR
e. Defective ZPT I/L
f. Momentary defect of any
I/L in the DJ control circuit.
ETTC/BZA Page 15
Course Material for LP Refresher Course 202. DJ Control Circuit
Precautions:
1. TLC permission is compulsory.
2. GR efficiency test shall be conducted.
3. Check working of MVSI1&2,MVSL1&2,MVMT1&2,MVRH.
4. Ensure OHE voltage is above 17.5KV.
NO TENSION:
1. Ensure BP level is intact, if dropped, put on FL stop the train and check the formation.
2. Check track, formation, OHE for any abnormality
3. If everything is normal, try once again
4. Change ZPT and try
5. If still unsuccessful, lower both pantographs, contact TPC, act accordingly
6. If could not contact with TPC and meanwhile if supply is restored, work the train further
with speed restriction of 60/30 Kmph up to next station, inform to SM and act
accordingly
‘A’ BEGINNING:
1. Check for dropping of QOA/QLA/QLM, if any relay energised, act accordingly.
2. Create maximum pressure in RS and try.
3. Tap QOA, QLA&QLM, operate re-setting knobs and try.
4. Keep HQOA in ‘0’ and try
If still unsuccessful, ask for relief engine.
‘A’ ENDING:
1. Check ARNO, any abnormality is noticed, ask for relief engine
2. If ARNO is good, keep HQCVAR in ‘0’, work further with necessary precautions
Note: While closing DJ, after deviation of UA needle count 4 seconds and then release BLRDJ
(LSCHBA will not extinguish).
‘A’ ENDING-PART 2:
Loop wire Nos. 733 – 739 with necessary precautions and work further.
Precautions:
1. Check in LT and ensure C 118 is opening and closing properly
2. After closing DJ ensure C 118 opened.
OPERATION B PART 1:
1. Keep HVSL1& HVSL 2 IN ‘3’, HPH & HQCVAR IN ‘0’, duly checking motors
working clear the section find out where the trouble is by normalising the switches. If
relay is defective, Keep concerned switch in ‘3’, position and work further with
precautions. If any motor is not working, isolate the motor and work with precaution.
OPERATION B PART 2:
1. Wedge Q45 in energised position and work with precautions,i.e. check working of
MVSI1,MVSI2 and ensure OHE voltage is above 17.5KV.
OPERATION ‘0’:
1. Keep HVRH, HVMT 1 & HVMT 2 IN ‘3’, duly checking motor’s working clear the
section and find out where the trouble is by normalising the switches. If relay is
defective, Keep concerned switch in ‘3’, and work further with precautions. If any motor
is not working, isolate the motor and work with precautions.
ETTC/BZA Page 17
Course Material for LP Refresher Course 202. DJ Control Circuit
OPERATION ‘1’:
1. Keep HVSI 1, HVSI 2 IN ‘3’ and close DJ. If still trouble is existing, trouble shoot for
sluggish operation of GR
2. If DJ not tripped, clear the section by duly checking motor’s working and find out where
the trouble is by normalising the switches one by one. If relay is defective, Keep
concerned switch in ‘3’ and work further with precautions. If motor not working, isolate
motor and work with precaution.
3. For sluggish operation of GR, increase SMGR pressure or clear section with manual
operation of GR.
OPERATION ‘2’:
1. All contactors not closed
2. Any one of the contactors of C107/ C105/ C106 not closed
3. C107, C105 & C106 closed but their I/Ls defective.
If NO EM CONTACTOR is closed:
a. Check CCA fuse.
b. Check for energisation of Q100.
c. Ensure C118 chronometric I/L is good otherwise, loop wire Nos. 089 –100
d. If still Q100 not energised, wedge it in energise condition and work with precaution.
TWAC:
1. Renew CCPT, CCDJ, CCA and try
2. Work the train with maximum pressure, always
3. Change ZPT position and try
4. Keep HQOP 1 & HQOP 2 in ‘OFF’ and HQOA in ‘0’ and try.
5. Increase SMGR pressure for 0.5Kg/cm2 and try
6. Wedge Q118 in energise position and try
7. Wedge Q44 in energise position and try
8. Change the cab and try
9. Operate GR manually and try
If still unsuccessful, contact TLC
ETTC/BZA Page 18
Course Material for LP Refresher Course 203. Traction Power Circuit
QE:
It is an over excitation current relay to ATFEX. During RB, if current exceeds 900Amps to
ATFEX, this relay energises and causes auto regression of GR by deenergising Q50.
QF 1&2:
These are over current relays for RFs. During RB, if TM Armature output current exceeds 700
Amps, relay QF energises and causes auto regression of GR by deenergising Q50.
ATFEX:
It is an Autotransformer for field excitation. It will come in to the service during RB. It is
located in HT 1 compartment (WAG 7: HT 3- BA 4) it is connected to TPC 1 in WAG 5 and
TPC 2 in WAG 7 locos.
QRSI1/QRSI2:
These are over current relays to protect RSI Blocks 1 & 2 respectively from over current. If over
current flows in Traction Power Circuit, this relay energises and trips DJ. Setting of QRSI in
WAG 7 & WAP 4 is 4000 Amps and in WAG 5 & WAM 4 is 3600 Amps.
ETTC/BZA Page 19
Course Material for LP Refresher Course 203. Traction Power Circuit
ETTC/BZA Page 20
Course Material for LP Refresher Course 203. Traction Power Circuit
RSI 1 & RSI 2: These are rectifier blocks, used to convert AC to DC through diodes. If diode is
punctured, LSRSI will glow on Loco Pilots desk.
RSI1 supplies DC current to TMs 1,2,3 through SL1 and L1,L2,L3. RSI2 supplies DC
current to TMs 4,5,6 through SL2 and L4,L5,L6. MVSI1 & MVSI 2 are provided to cool the
RSI 1 & 2 blocks, respectively
LINE CONTACTORS:
There are six line contactors L1 to L6 to give supply for TMs 1 to 6 respectively. These Line
Contactors are controlled by switches HMCS1, HMCS2, HVSI1, HVSI 2, HVMT1 & HVMT2.
RPS:
It is a permanent resistance connected across magnetic field to absorb left over AC pulses in
the supply Current of TMs. These are located in cowl box and cooled by MVRH.
J1 & J2:
These are Drum Contactors operated by MPJ. J1 controls direction of flow of current in TMs
1,2&3 field coils. J2 controls direction of flow of current in TMs 4,5&6 field coils. If cab-1 is
leading, both J1 & J2 operating handles should be in UP direction and for cab-2 leading DOWN
direction.
Q20:
It is an over voltage relay in traction power circuit. Due to any reason if circuit fed more than
865 volts, this relay will energise and causes auto regression of GR. This is connected across
+ve and -ve levels of RSI 1 output. When Q 20 energises, causes auto regression of GR and
sounding of SON in both cabs. (In some Locos LSOV also will glow).
If Q 20 is energising at less voltage, work the train by using MPS. If still losing time,
inform to TLC.
Note: Q20 setting is 865 volts. However, TM voltage is limited to 750 volts.
Modified setting: 790 V -700 V.
QD:
QD1 connected across TMs 2&3 and QD2 connected across TMs 4&5. Whenever there is
difference of current between these two traction motors exceeds 160 Amps, this relay will
energise and causes auto regression of GR, auto sanding and glowing of LSP. When QD
energised, Locopilot should ascertain the cause and trouble shoot accordingly.
When QD energised, Loco pilot should ascertain the reason of the above and take necessary
action.
Note: when Traction Motor is isolated, Loco pilot should ensure that correct Traction Motor
only isolated by observing Ammeters & Voltmeters.
Meter connections
Cab1 Cab2
U1 U2 A3 A4 U5 U6
TM TM
TM2 TM3 TM4 TM6
1 5
ETTC/BZA Page 22
Course Material for LP Refresher Course 203. Traction Power Circuit
3 HMCS 1 IN 4 J1–6
4 HMCS 2 IN 2 J2–6
5 HMCS 2 IN 3 J 2 –10
6 HMCS 2 IN 4 J2–8
a. Check for any smoke, burning smell, fire or any abnormality in TFR terminals (a5, a6
for 3900 KVA transformer locos, a3, a4 for 5400 KVA transformer locos) , RSI-1, J1,
CTF-1, 2, 3, SL-1, L1, L2, L3, traction motors 1, 2, 3, RU1, RU2 & AM3 shunt , Q20,
RQ20, QD1, , SJ 1,2,3 . If everything is normal reset the relay target and accelerate
gradually, duly watching ammeters (if anything is found abnormal use fire
extinguishers, try to isolate the same, otherwise contact TLC for further instructions).
b. If QRSI-1 is dropping after long interval, check the equipment mentioned above, if
everything is normal, reset the target and resume traction.
c. if QRSI-1 dropping frequently, check the equipments mentioned above. If there is no
abnormality, change HMCS-1 to 2,3 &4 positions one by one and try. if QRSI-1 is not
dropping in a particular position of HMCS-1, isolate that traction motor work with
5/6th of maximum permissible load
d. If QRSI-1 is dropping in all position of HMCS-1, isolate truck no.1 by placing HVSI-1
HVMT-1 and HVSL-1 on ‘0’. Resume traction if road and load permits otherwise work
with 50% of the maximum permissible load.
e. If load and road does not permit ask for assisting loco.
a. Check for any smoke, burning smell or any abnormality in TFR terminals (a3, a4 for
3900 KVA transformer locos, a5, a6 for 5400 KVA transformer locos) , RSI-2 , J2 ,
CTF-1, 2, 3, SL 2, L4 , L5, L6, traction motors 4, 5, 6, AM4 shunt, RU5, RU6 , QD-2
and SJs 4,5,6 .If everything is normal, reset the relay target and accelerate gradually
duly watching ammeters (If anything is found abnormal, use fire extinguishers, try to
isolate the same. Otherwise contact TLC for further instructions).
b. If QRSI-2 is dropping after long interval, check the equipments mentioned above, if
everything is normal, reset the target and resume traction.
c. If QRSI-2 dropping frequently, check the equipments mentioned above. If there is no
abnormality, change HMCS-2 to 2, 3 & 4 positions one by one and try. If QRSI-2 not
dropping in a particular position of HMCS-2, isolate that traction motor and work with
5/6th of maximum permissible load.
d. If QRSI-2 is dropping in all positions of HMCS-2, isolate truck no.2 by placing HVSI-2,
HVMT-2, and HVSL-2 on ‘0’. Resume traction if road and load permits otherwise work
with 50% of the maximum permissible load.
e. If load and road does not permit as for assisting loco.
ETTC/BZA Page 23
Course Material for LP Refresher Course 203. Traction Power Circuit
a. Check for any abnormality in a5, a6 (in WAG5A & WAM4) a3, a4 (in WAG7 &
WAP4), RSI-1, SL-1, L1, L2, L3, traction motors 1, 2,3, J1, Q20, RQ20 QD-1, RC
damping panel, CTF-1, 2, 3, ATFEX, C145, shunting contactors and their resistances,
RU1, RU2 & AM3 shunt , SJ 1,2,3 , RB equipment & MVRF.
b. If anything is found abnormal use fire extinguishers, isolate the concerned equipment or
circuit and resume traction if possible.
c. If everything is normal, try to reset the relay target and resume traction.
d. If QOP-1 drops further after a long interval, every time check the equipment mentioned
above. If no abnormality, reset the target and resume traction.
e. If QOP-1 drops frequently, isolate TMs one by one +ve side, -ve side and try. If QOP-1
not dropping after isolating particular TM, work if the load is less than 5/6th of
maximum permissible load.
f. If QOP-1 drops in all the positions of HMCS-1, check the equipments mentioned above
thoroughly and if no abnormality is noticed, after confirming that there is no BANDING
FAILURE, place HQOP-1 in OFF position. Reset the relay target and clear section duly
watching the power circuit equipments for any abnormality and contact TLC.
ETTC/BZA Page 24
Course Material for LP Refresher Course 203. Traction Power Circuit
d. If the relay target does not reset, keep HQOP-1 in OFF position and clear section with
precautions. After clearing section trip DJ, keep MPJ in Neutral. Take safety measures,
and enter into the HT compartment.
e. Normalize HQOP-1 to ON and keep reverser J1 in neutral position.
f. Try to reset the relay target.
g. If the target does not reset (the fault is not with the traction motor), contact TLC for
advice.
h. If the target is reset, conclude the fault is with the traction motors (1, 2, 3).
i. Keep the reverser J1 in the appropriate direction. Find out the defective traction motor
by packing the reverser bit as follows.
g. If the target does not reset (the fault is not with the traction motor), contact TLC for
advice.
h. If the target is reset, conclude the fault is with the traction motors (4, 5, 6).
i. Keep the reverser J2 in the appropriate direction. Find out the defective traction motor
by packing the reverser bit as follows.
Projection of poly-glass material from traction motor vent mesh is treated as ‘banding
failure’. when it occurs, isolate particular tm both +ve and –ve sides and clear the section with
speed restriction of 15 kmph, contact TLC. If banding failure is noticed at station then
immediately inform to TLC.
Note: Ignoring of banding failure leads to locked axle.
ETTC/BZA Page 26
Course Material for LP Refresher Course 203. Traction Power Circuit
Procedure
1. Should not bring MP to ‘0’.
2. Note down the readings of Ammeters, Voltmeters, Line voltage, Notch position,
MPS position, Speed and Gradient.
3. Now, bring MP to ‘0’.
4. Take necessary precautions and check the projection of tell-tale fuses.
5. If two fuses are projected in same RSI block, isolate concerned block and work
further.
6. If one fuse is projected in a block (or in each block), remove the same with
precautions so as to get the again glowing of LSRSI if another fuse melts and work
further duly not reaching the earlier current ratings.
7. In modified locos RED LED’S are provided. If one red LED glows in any one RSI
block (change the miniature toggle switch position if provided so as to get the again
glowing of another fuse melts ) not to exceed the previous current ratings work the
train further duly informing to TLC.
8. If two red LEDS are glowing in any RSI block then isolate concerned RSI block by
keeping HVSI,HVMT,HVSL on 0 position and work the train with 50% tractive
effort if load and road permits otherwise inform to TLC and ask for assistance or
banker loco.
Make entry in loco logbook and inform to TLC if necessary.
ETTC/BZA Page 27
Course Material for LP Refresher Course 203. Traction Power Circuit
ETTC/BZA Page 28
Course Material for LP Refresher Course 203. Traction Power Circuit
Abnormal Sign
When MP is moved from ‘O’ to ‘N’ then to ‘+’ LSB is glowing, LSGR not extinguished, NR
not deviated,
Trouble shooting :
Then check the following:
1. Operate MPJ handle for 2 to 3 times. Forward and Reverse finally keep it in required
direction.
2. Take necessary precautions and check the proper setting of J1 & J2 according to the cab
leading i.e., both J1 & J2 manual operating handles should be in upwards for cab1
leading and downwards for cab 2. Gently tap the handles.
3. Ensure CTF1,2,3 manual operating handles are in upwards (traction side) and tap the
handles.
4. Ensure C145 is opened fully and LSC145 is extinguished.
5. Clean the interlocks of Q50 and operate BL 2 or 3 times and try.
6. If still un-successful, wedge Q50 in energised position.
Precautions:
a. MPJ should not be operated up to destination.
b. Shunting is prohibited. If required in emergency personally ensure proper setting of
reversers for every operation of MPJ.
c. Don’t use RB.
d. When DJ is tripped on notches, keep MP on ‘O’ to bring GR to ‘O’.
Write remarks in loco log-book & Inform to TLC at first opportunity.
Trouble Shooting :
Check the following.
1. Try by EEC operation.
2. Operate ZSMS for 2 or 3 times and try
3. Check Q52. It should be in de-energise position. If Q52 is in energised position, wedge
in de-energised position. Don’t keep MP in ‘+’ for longer period, otherwise quick
progression of GR will takes place.
4. Check Q51. It should be in de-energise position. If it is energised,
ETTC/BZA Page 29
Course Material for LP Refresher Course 203. Traction Power Circuit
Trouble Shooting :
Operate BL for 2 / 3 times.
1. Clean the interlocks of Q50 and try.
2. Ensure CTF 1,2&3 are in traction side, tap the handles gently duly taking necessary
precautions.
3. Ensure HVSI1&2,HVMT1&2 are on 1 position.
4. Keep HVSI1, HVMT1, HVSI2, HVMT2 switches in ‘3’ and try.
5. Ensure MR pressure is above 5 Kg/cm2.
6. Ensure EP 1&2 COC(s) are open and no leakage. And also ensure EP drain cock is in
close position.
7. Operate GR manually for few notches and try.
8. Change cab and try.
• If still unsuccessful, contact TLC for advice.
Abnormal Sign : When MP is moved from ‘0’ to ‘N’ then to ‘+’ LSGR extinguished, , GR
came to ‘0’ with LSP glowing.
Reason : Due to QD action
Trouble shooting :
1. Isolate TM 2 or 3 or TM 4 or TM 5 basing on the Volt and ammeters deviation.
2. Work the train with 5/6 of maximum sectional load.
3. Check and ensure for correct isolation of TM by observing Ammeters & Voltmeters.
4. Check BP, brake binding & abnormality on train.
5. Apply sand and press ZQWC and try.
ETTC/BZA Page 30
Course Material for LP Refresher Course 203. Traction Power Circuit
Trouble Shooting :
1. Isolate TM 1 or TM 6 duly observing concerned voltmeters.
2. Work the train with 5/6 of maximum sectional load.
3. Check and ensure for correct isolation of TM by observing Ammeters & Voltmeters.
Write remarks in loco log-book and inform to TLC.
4. PLTE with half traction: Ensure HVSI1&2,HVMT1&2 are on 1 position and EP1 And
EP2 coc’s are in open position.
5. One truck may be in isolated without remark.
Trouble Shooting :
1. Check HVSI 1 or HVSI 2 may be in 0/2 and HVMT1 or HVMT 2 may be in 0/2
position.
2. Change the switch position if no trouble in Motors.
Trouble shooting :
1. Operate rear cab BL for 2 / 3 times and try.
2. Clean the I/Ls of Q50 and try.
3. If still unsuccessful pack Q46 in de-energise position and work with EEC operation to
avoid DJ tripping through rear cab BL,MP ‘0’ I/L while on notches.
4. If ZSMS is modified work from rear cab or by manual operation of GR (EEC operation
is not possible from leading cab).
5. In VCD provided locos check QVCD, if it energized wedge in de- energized condition
and also keep HVCD on 0 position and remove the cables connected to VCD main unit.
6. Write remarks in loco log-book.
Inform to TLC at first opportunity.
4. Contact TLC.
Note: Ignoring of banding failure leads to locked axle.
ETTC/BZA Page 32
Course Material for LP Refresher Course 203. Traction Power Circuit
ETTC/BZA Page 33
Course Material for LP Refresher Course 204.Auxiiliary Power & Control Circuit
ETTC/BZA Page 34
Course Material for LP Refresher Course 204. Auxiliary Power & Control Circuit
i. If QOA drops while closing DJ, check ARNO, MVSI-1, MVSI-2, MVSL-
1, MVSL-2, MPH, CHBA, a0, a1 terminals, cab heaters, cab fans, capacitor
bank of ARNO , TFVT, C118, R118, Q30,RQ30, UA1, UA2, HVSI-1, HVSI-
2, HPH, HVSL-1, HVSL-2 for any abnormality.
ii. If QOA drops while closing BLCP, check MCPs and C101, C102, C103 for
any abnormality.
iii. If QOA drops while closing BLVMT, check MVRH MVMT-1, MVMT-2 and
contactors C105, C106, C107 for any abnormality.
Note: If any abnormality is noticed in the above equipment, try to isolate the
defective equipment and resume traction. Otherwise contact TLC for advice.
ETTC/BZA Page 35
Course Material for LP Refresher Course 204. Auxiliary Power & Control Circuit
MVSL: When MVSL is defective isolate concerned RSI block by keeping respective
switches HVSI, HVMT & HVSL in ‘0’ and work the train with normal current ratings and
50% of the maximum permissible sectional load.
1. When MVSL is not working-operation B part-I is experienced.
2. Earth fault in MVSL-QOA energises.
3. Short circuit in MVSL-QLA energises.
MVSI: When MVSI is defective isolate concerned RSI block by keeping respective
switches HVSI, HVMT & HVSL in ‘0’ and work the train with normal current ratings and
50% of the max permissible sectional load.
1. When MVSI is not working-operation -I is experienced.
2. Earth fault in MVSI-QOA energises.
3. Short circuit in MVSI-QLA energises.
MCP: If any one CP failed, isolate the same by HCP and work the train by the help of
other CPs. Earth fault in any MCP causes tripping of DJ through QOA. Over current to any
MCP causes tripping of DJ through QLA. In both cases, isolate the defective MCP with
HCP and ensure concerned contactor is opened, otherwise disconnect terminals at terminal
box of Compressor.
ETTC/BZA Page 36
Course Material for LP Refresher Course 204. Auxiliary Power & Control Circuit
MVRH: Isolate MVRH by keeping HVRH in '0' and ensure C107 opened, otherwise
disconnect terminals at terminal box of MVRH. If MVRH is isolated maintain the restricted
current rating of 920/500 Amps and check Transformer oil level frequently for any
abnormal raise. Wedge Q 118 in energise position or work with in 5 notches if load and
road permits.
1. When MVRH is not working-operation -O is experienced.
2. Earth fault in MVRH-QOA energises.
3. Short circuit in MVRH-QLA energises.
MVMT: If MVMT is failed, it leads to OPERATION ‘O’. Earth fault in MVMT1 causes
tripping of DJ through QOA. Over current in MVMT1 causes tripping of DJ through QLA.
In both cases, isolate MVMT1 by keeping HVMT1 in '0' and ensure C105 opened,
otherwise disconnect terminals at terminal box of MVMT1. If MVMT1/MVMT2 is isolated,
isolate concerned RSI block and work the train with 50% of the maximum permissible
sectional load.
1. When MVMT is not working-operation -O is experienced.
2. Earth fault in MVMT-QOA energises.
3. Short circuit in MVMT-QLA energises.
REPLACEMENT OF BULB
1. Open the back cover from inside the cab, identify the defective bulb.
2. Pull out the wire loom by holding 3way nylon connector.
3. Press the bulb holder a little inwards and rotate in anti clockwise direction.
4. The spring loaded holder will come out. Remove the defective bulb.
5. Take the new bulb from the box fitted on the back cover of headlight unit.
6. The new bulb is to be placed properly in the reflector, matching the notch & small
raised portion on the bulb.
ETTC/BZA Page 37
Course Material for LP Refresher Course 204. Auxiliary Power & Control Circuit
7. Fix the spring loaded holder and connect back the wire loom.
Caution: The glass portion of the Halogen lamp should not be touched by hand, which may
cause for cracking during operation. The Bulb to be handled from metallic portion only.
Make an entry in loco logbook.
b) If CHBA is failed,
1. Check MCBs on CHBA whether tripped. If tripped reset same. If fuses are
provided check the fuses. If fused renew them with 16 A spare fuse.
2. Still CHBA not working, work the train as follows.
3. Give information to TLC
4. Keep HCHBA on ‘O’.
5. Minimize the use of cab lights, corridor lights, MP, MPJ,MPS, PSA and PVEF etc.
6. With BA voltage day time can work 6 hours and night time can work 4 hours duly
watching BA voltage which should not drop below 90 V.
7. Make a remark in log book.
TFVT: If TFVT defective, cab fans will not work. Then check CCVT. Earth fault in TFVT
causes tripping of DJ through QOA. If so, isolate TFVT by removing fuse CCVT, if still
QOA not resetting, disconnect the cables at TFVT. In modified locos (SIV Locos), put off
defective cab fans by keeping HRAVT in 3 position to isolate CAB Fans.
RA1&2: If cab heaters are not working, check fuses CCRA1&2, according to cab. Earth
fault in cab heaters leads to tripping of DJ through QOA. At that time isolate cab heaters by
removing fuses CCRA1&2. In modified locos (SIV Locos), put off defective heaters by
keeping HRAVT in 2 position according to the cab. If still QOA not re-setting, disconnect
cables at Heaters.
ETTC/BZA Page 38
Course Material for LP Refresher Course 204. Auxiliary Power & Control Circuit
ETTC/BZA Page 39
Course Material for LP Refresher Course 204. Auxiliary Power & Control Circuit
Earth fault in the control circuit causes melting of CCA, which in turn causes OPERATION 2.
1. Keep HOBA in OFF, renew the fuse and work the train further.
2. If CCA fuses even HOBA in OFF, work the train by wedging of minimum contactors, in
the following manner.
ETTC/BZA Page 40
Course Material for LP Refresher Course 204. Auxiliary Power & Control Circuit
c) If CCA melts, trouble may be in Q100 /Q119/ VEULs. Find out the defective one and
disconnect the concerned positive cable.
d) f CCA does not melt, close BLCP. If CCA melts defect may be in
BLCP/RGCP/VEAD/HCP/C101/C102/C103. Wedge concerned contactor and do not
close BLCP & BLCPD.
e) If CCA does not melt, close BLVMT. If CCA melts defect may be in
BLVMT/HVRH/C107/ QTD105/HVMT1/C105/QTD106/ HVMT2 /C106. Find out the
defective one and disconnect the positive cable.
Note:
1. If Q100 wire disconnected, work the train by wedging Q100 in energise
condition.
2. If any Contactor coil wire is disconnected, wedge the same.
3. If BLCP defective, work with BLCPD. If BLVMT is defective, take one traction
notch, ensure starting of blowers.
4. If HCP is defective, change the position.
5. If HVRH/HVMT1/HVMT2 is defective change to ‘3’ position.
If still pilot lams are not working, work the train by observing audible & visible indications
as follows.
LSDJ: while closing DJ, close BLDJ, press BLRDJ, and release it after 4 seconds. Observe
UA needle. While on run, observe UA needle frequently, if UA needle drops to ‘0’, conclude
DJ is tripped, open BLDJ.
LSCHBA: while closing DJ, close BLDJ, press BLRDJ, and release it after 4 seconds of
deviating UA needle. While on run: Ensure CHBA is working properly, observe auxiliaries
sound frequently, if sound reduced, trip the DJ immediately
LSGR: Before closing DJ ensure GR is on ‘0’ by observing at GR drum. While on run:
observe Ammeters and Notch Repeater.
LSRSI: While on run: observe trigger fuses of RSI blocks, frequently. If any fuse is
projected, take precautions as if LSRSI glowing on run.
LSB: When initially MPJ operated, ensure proper setting of J1 & J2 according to cab, CTFs
are in Traction side and C145 opened fully. While on run do not disturb the position of MPJ,
do not perform shunting. If emergency, for every movement ensure proper setting of J1 & J2.
Do not use RB.
LSP: While on run, do not allow for wheel slipping, observe ammeters, NR, Speedometer
and also listen for wheel slipping (spinning) noise from wheels.
ETTC/BZA Page 41
Course Material for LP Refresher Course 204. Auxiliary Power & Control Circuit
ETTC/BZA Page 42
Course Material for LP Refresher Course 205. Brake System
205.BRAKE SYSTEM
ETTC/BZA Page 43
Course Material for LP Refresher Course 205. Brake System
a) Check the MR pressure between 8.0kg/cm2 to 9.5kg/cm2 and also ensure MR4COC is
open.
b) Check and ensure MU2B in LEAD position, A9 handle is in release in both cabs. L &
T cock (A8) is open, A9 inlet and out let Cocks are opened in working cab and closed
in non-working cab. Check BP angle COCs are closed properly on either side of the
loco, ALP emergency valves in closed condition in both cabs. If anything is found
abnormal, normalize the same, charge the BP pressure and resume traction.
c) If everything is normal, check for any air leakage from BP pipeline and IP valve. If any
leakage is found, rectify and resume traction.
d) If there is no air leakage, operate MU2B from 'LEAD' to 'TRAIL' and back to 'LEAD'
2 or 3 times and try.
e) If unsuccessful, tap the C2A relay valve (BP charging) gently and try.
f) Ensure, additional BP COCs on both sides open condition.
g) g) If unsuccessful, build up MR pressure above 9.5 kg/cm2 and keep A9 handle in
release position. Adjust the A9 feed valve; raise the BP pressure to 5kg/cm2 and
resume traction.
h) If unsuccessful, try to work from rear cab, otherwise contact TLC and act as per his
instructions.
i) Still not success, de energise the loco, drain out complete MR and energise the loco
and try.
ETTC/BZA Page 44
Course Material for LP Refresher Course 205. Brake System
BP Leakage test:
1. Ensure MR pressure is 9.5 Kg/cm2
2. Ensure BP pressure is 5 Kg/cm2
3. Apply A9 to bring BP pressure to 4.0Kg/cm2
4. Close A8 and wait for 30 seconds to settle the gauge needle and note the reading.
5. Wait for another five minutes and note down the BP pressure reading
6. Difference of pressure should not be more than
For loco: 0.7Kg/cm2 within 5 minutes (0.2Kg/cm2 for one minute)
For formation : 1.25Kg/cm2 for 5 min (0.25Kg/cm2 for 1 minute)
ETTC/BZA Page 45
Course Material for LP Refresher Course 205. Brake System
FP Leakage test
1. Ensure MR pressure is 9.5 Kg/cm2
2. FP pressure is 6 Kg/cm2
3. Open FP angle cock slightly to reach FP pressure to 5 Kg/cm2
4. Close feed valve COC, FP angular cock and wait for one minute to note down the FP
pressure reading.
5. Wait for another 5 minutes, note down the reading
6. Difference of pressure should not be more than
For loco: 0.7Kg/cm2 within 5 minutes (0.2Kg/cm2 for one minute)
For formation: 1.25Kg/cm2 for 5 minutes (0.25Kg/cm2 for 1 minute)
ETTC/BZA Page 46
Course Material for LP Refresher Course 205. Brake System
ETTC/BZA Page 47
Course Material for LP Refresher Course 205. Brake System
Procedure:
1. This test to be conducted with the cooperation of Guard.
2. Create 9.5 kg/cm2 of MR pressure and 5.0 kg/cm2 of BP in the locomotive.
3. Ensure 4.8 / 4.7 kg/cm2 of BP pressure in the BV according to the no of wagons.
4. Apply A9 automatic brake valve and reduce BP pressure by 1. kg/cm2 without
pause.
5. Confirm from the guard for corresponding reduction of BP should be in between 3.6
to 4.0 kg/cm2in the BV .
6. Physically ensure brake application in formation.
7. Loco pilot has to close A8 Cock ( E70 Cock/Mode switch TEST In case of 3 phase
locos and ignore fault message).
8. Now immediately Guard shall open the BV emergency valve and the Guard shall
observe the drop of BP pressure to zero and close.
9. If the BV is not the last vehicle, Guard shall open the BP angle cock in the rear side
of last vehicle and close after complete exhaust.
10. Loco pilot to ensure dropping of BP pressure completely to “0” and should not
raise.
11. Guard has to close the BV emergency valve.
12. Now the Loco pilot release A-9 ,open A8 coc and Ensure recreation of 5.0 kg/cm2
of BP in the locomotive and4.8 / 4.7 kg/cm2 of BP pressure in the BV.
13. For originating trains after turn around examination (where SSE/SE- C&W is
posted): continuity test will be done by the loco-pilot and guard in the presence of
SSE/SE-C&W who shall make endorsement on the reverse of the original BPC.
14. Where SSE/SE-C&W is not posted: loco-pilot and guard will check the continuity
and make endorsement on the reverse of original BPC.
1. The Loco Pilot must charge the BP to 5 Kg/Cm2 and FP to 6Kg/Cm2 must confirm
from the Guard that minimum BP 4.8 Kg/Cm2 and FP 5.8 Kg/Cm2 in BV
2. The LP must move the A9 automatic brake valve to reduce BP pressure to 4.0
Kg/Cm2 and must confirm from the Guard that BP pressure in brake van is reduced
by 1.0 Kg/Cm2 (in the range of 3.6 to 4.0). In this condition, train brakes must also
apply.
3. If BP pressure in BV does not show reduction in BP pressure in the range of 3.6 to
4.0 Kg/Cm2, it indicates discontinuity in brake pipe, which must be looked into be
TXR staff.
4. After that, the LP must move A9 automatic brake valve to ‘running’ position and
check that 5 Kg/Cm2 BP pressure is registered in BP gauge in loco and must confirm
from the Guard that minimum 4.8 Kg/Cm2 in BV.
5. After the BP pressure has stabilized in the locomotive, air supply for the BP should
be cut off by closing A-8 COC or E-70 COC OR Mode switch to TEST (Ignore the
message appeared in 3-φ locos).
6. Then, the Guard shall immediately open the Emergency brake valve to vent out the
BP drop up to3.6 Kg/Cm2 and close. LP should observe that the pressure in the BP
gauge in the locomotive is within in the range of 3.6 to 4.0 Kg/Cm2, otherwise it
indicates discontinuity in brake pipe, which must be looked into by TXR staff for
rectification.
7. After confirmation of continuity, open the A-8 COC/E-70 COC/MODE switch to
lead and restore the BP pressure in the loco/SLR.
ETTC/BZA Page 48
Course Material for LP Refresher Course 205. Brake System
ETTC/BZA Page 49
Course Material for LP Refresher Course 205. Brake System
ETTC/BZA Page 50
Course Material for LP Refresher Course 205. Brake System
ETTC/BZA Page 51
Course Material for LP Refresher Course 205. Brake System
ETTC/BZA Page 52
Course Material for LP Refresher Course 205. Brake System
Trouble shooting in case of BP-FP angle failure on the last Coach (LHB coach FIAT
Bogie).
1. Loosen the check nut fitted on ‘T’ joint and affected angle cock pipe.
2. Disconnect the affected pipe from ‘T’ joint by loosening holding clips.
3. Tighten the Dummy plug to that end.
Trouble shooting in case of BP-FP angle failure on the last coach (Hybrid coach).
MS Dummy Plate (98x65x2 mm)
1. Loosen and remove the both bolts.
2. Make gap between block and affected angle cock pipe.
3. Insert Dummy plate between block and affected pipe flange.
4. Insert and tighten both bolts. Dummy Plug Bore
1. Place the loco pilot’s automatic brake valve handle in emergency position.
2. In case of WAG5 electric locomotive start the compressors for building up of main
reservoir pressure.
3. Allow the main reservoir pressure to build up of the maximum stipulated limit.
4. Close the angle cock for the brake pipe. Couple 7.5 mm diameter leak hole special test
coupling fabricated to RDSO design SKDP 2691 with the brake pipe coupling of the
locomotive. In case of MU consist test coupling should be fitted on the rear most
locomotive of consist.
5. Move the loco pilot’s automatic brake valve handle from emergency position to release
position to charge the brake pipe to 5 Kg/cm2.
6. Open the angle cock for the brake pipe. The brake pipe pressure should fall from
5Kg/cm2.
7. Check the brake pipe pressure with help of gauge fitted in the locomotive which should
not fall below 4 Kg/cm2 within 60 seconds.
8. The test shall be carried out with the number of compressor s considered adequate by the
loco pilot for operating the train.
ETTC/BZA Page 53
Course Material for LP Refresher Course 205. Brake System
Introduction:
For MU operation, 3 electrical jumpers (One set) are connected between two Locos
besides connecting the pneumatic hosepipes. Due to connection of electrical jumpers, the
control circuit feed of one Loco reaches to another Loco therefore same control circuit operation
takes place in both the Locos, though operation is done from leading Loco. In MU operation,
almost all the feed of control circuits of the leading Loco reaches to the trailing Loco but Q118,
Q44 and Q100 get the control supply from its own Loco. Therefore for closing DJ, HBA should
be on '1' position in both Locos. A switch BLSN is provided on the BL box, which controls the
feed to VEPT and MTDJ of trailing Loco. Its normal position is 'up' (close). On pressing it
down, the supply to trailing Loco VEPT and MTDJ cuts off and the DJ of trailing Loco gets
opened and Panto also lowers. It is important to know that from leading Loco closing of DJ can
be done for both Locos together or separately. Similarly tripping of DJ can be done for both
Locos together or of the rear Loco only. However, DJ of the leading Loco alone cannot be
tripped from leading Loco. It should be kept in mind that if required, DJ can be closed of
trailing Loco by pressing BP2DJ of trailing Loco, but cannot be opened by BP1DJ of the
ETTC/BZA Page 54
Course Material for LP Refresher Course 205. Brake System
trailing Loco. In case of emergency the DJ of trailing Loco can be opened by removing CCPT
of trailing Loco, but normally it is to be avoided.
Preparing of MU Locos:
Checking of Locos
1. Examine the Locos separately and prepare them individually.
2. After complete checking de-energise the Locos. Attach them one to the other,
preferably with cab 2 on either ends with CBC & pin.
3. Keep HBA of both Locos in '0' position.
4. On one side attach B C D couplers of one Loco to other. On other Loco side Loco B C
D couplers will be kept as spare.
5. Couple up MR and BC equalising hose pipes and open their angular cocks.
6. Couple BP &FP air hoses and open their angle cocks. If necessary connect vacuum
hose pipe also.
7. Keep A9 I/L & O/L cocks of working cab open condition and remaining cabs should
be in closed position.
8. Keep SA9 supply & apply cocks of working cab open condition and remaining cabs
should be in closed position.
9. Keep A8 COC Open in leading Loco Close in Trailing Loco.
10. MU2B of leading Loco in LEAD position and in Trailing Loco should be kept in
TRAIL/DEAD position.
11. Keep ZPT, MPJ & BL keys of trailing Loco in the side locker.
12. HBA should be kept on '1' in both the Locos.
13. Start MCPA of both the Locos and ensure RS pressure raises up to 6.5 kg/cm2.
Note: If CPA of any Loco is defective, then first energise the MU Locos from the Loco
in which CPA is working.
Energising Of MU Locos
1. Unlock the BL in working cab of leading Loco and ensure four pilot lamps LSDJ,
LSCHBA, LSGR, & LSB glowing.
2. Place ZPT ON '1' and ensure rear pantos of both the Locos are raised and touched to
OHE.
3. Place BLSN switch at 'ON' position and ensure trailing Loco panto is lowered.
4. Close BLDJ and press BLRDJ. After UA needle is deviated release BLRDJ exactly
after 4 seconds. LSDJ, LSCHBA, LSGR & LSB will not extinguish.
5. Normalize the switch BLSN (i.e., 'OFF' position) and ensure trailing Loco rear panto is
raised and touching to OHE.
6. Now press BLRDJ again and release it after LSDJ & LSCHBA lamps extinguishes.
7. Close BLCP and ensure CPs working according to HCP switch position of each Loco.
8. Close BLVMT and ensure three blower motors are working in both Locos.
9. Keep MPJ on 'F' or 'R' as required and ensure LSB is extinguished.
10. Move MP from 'N' to '+' and ensure LSGR is extinguished. NR shows one notch and
ammeters are deviating. Then bring back mp to '0'.
Now MU Locos are ready to work a train
ETTC/BZA Page 55
Course Material for LP Refresher Course 205. Brake System
The concerned pilot lamp indicating the fault will also glow in both the Locos along
with LSGROUP/LSOL. Until the fault is rectified, the pilot lamp will continue to glow in both
the Locos.
Therefore, on seeing LSGROUP (along with pilot lamps), we can locate the defective
Loco. If LSGROUP is glowing in leading Loco, then leading Loco is defective and if LSOL
glows in leading Loco then it means that defect is in trailing Loco (ensure LSGROUP is in
working order).
ETTC/BZA Page 56
Course Material for LP Refresher Course 205. Brake System
ETTC/BZA Page 57
Course Material for LP Refresher Course 205. Brake System
ETTC/BZA Page 58
Course Material for LP Refresher Course 205. Brake System
11. Now trailing loco will respond to the operations done in leading Loco.
12. Clear the section duly watching the BA voltage.
Working the train from trailing loco when leading loco fails:
1. In case leading loco (other than CCPT) fuse melting, do not change any COC position
and work from leading loco (Close panto COCs and observe BA voltage is above 90 v)
carefully to clear section.
2. If not possible, make the leading loco dead and work from the trailing loco.
3. Resume traction from trailing loco and clear section without exceeding the speed limit
of 15 KMPH and contact TLC.
4. If the load and road permits, request TLC for re-marshalling of the loco (changing
trailing loco as leading loco) and work onwards with single loco.
5. If load and road does not permit, contact TLC.
Working the train from leading loco when trailing loco fails:
1. Put BLSN ‘DOWN’ to de-energize the rear loco and work with the leading loco. If
trouble persists remove the electrical jumpers between the locos and secure them on
clamps. Keep HBA on ‘0’, close IP COC of rear loco and work the train from leading
loco.
2. Put ZLS on ‘0’ in trailing loco and ensure GR on ‘0’.
3. Don’t change any COC position.
4. Clear section and contact TLC.
5. If the load and road permits, work onwards with single loco. Otherwise contact TLC for
advice.
Procedure to charge the loco Batteries in case of Run down or less BA voltage in MU
locos.
I.
1. Stop the train and secure as per the procedure.
2. Get the extra ZPT key and insert in defect loco and keep in any PT raise position.
3. Enersige the Good loco.
II.
1. Get extra BL key and unlock in defective loco BL box.
2. Energise Good loco.
ETTC/BZA Page 59
Course Material for LP Refresher Course 206. Modifications to Locos
206.MODIFICATIONS TO LOCOS
Loco pilot/Asst Loco pilot have to do the following operations for every 60 sec
1. Progression by MP or EEC.
2. Regression by MP or EEC.
3. Application of Sanders.
4. Operation of foot pedal switch.
5. Operation of MPS (1st notch)
If VCD is not acknowledged within 60 sec, VCD warning yellow lamp flickers for next 8
sec, if still not acknowledge, VCD warning yellow lamp and buzzer will come for next 8 sec. If
still not acknowledge VCD action takes place. BP drops and GR comes to ‘0’.
Resetting of VCD:
1. Keep MP on ‘0’.
2. Apply SA-9
3. Keep A9 on emergency to avoid MR dropping.
4. Wait for 32 sec, then press VCD reset button.
5. Keep A9 on release for charging of BP.
ETTC/BZA Page 60
Course Material for LP Refresher Course 206. Modifications to Locos
If VCD malfunction:
1. A bypass switch is provided in the main unit, in case of any mal functioning of VCD,
Loco Pilot has to isolate the unit by keeping the bypass switch in OFF position duly
entering in the log book.
2. If still not success, HBA off and try.
3. If still not success, disconnect VCD main unit four cables and try.
206.3 Provision of 16th regression on SMGR in locos provided with roof mounted DBR:
To improve the effectiveness of dynamic braking QF setting and auto regression of GR have
revised as:
✓ QF setting-850 amps & Auto regression-16th notch
The above changes are to be applied in WAP1 and WAP4 locos provided with naturally cooled
roof mounted DBR.
206.4 Reduction of brake cylinder pressure on diesel and electrical conventional locos from
1.8 kg/cm2 to 1.4 kg/cm2 in proportional working for the locos provided with
composite brake blocks.
Direct Brake cylinder pressure: Reduced to 3.0 Kg/Cm2 from 3.5 Kg/Cm2.
ETTC/BZA Page 61
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 62
Course Material for LP Refresher Course 206. Modifications to Locos
This is provided for switching on Flasher light automatically during any emergency
situation such as ACP, Bp pressure dropping or during derailment, etc,. It does not take any
responsibility of Loco pilot in abnormal situation like train parting, etc,. as given in G&SR.
Loco pilot should keep the manual push button switch BPSW 1/2 pressed during brake release/
initial charging.
When BP pressure drops below 4.4 kg/cm2, automatically P2 I/L will close and Buzzer
and Flasher light will work through P2, PR1, SW & QFL I/Ls. same time LED indication will
also come in the cab. By energising PR2 relay, circuit will maintain through PR2 I/L and it's I/L
will close on Q51 branch and auto regression of GR will takes place. Loco pilot can isolate
Flasher light and Buzzer by pressing SW1/2 provided in the cab, if required. LEDs will
extinguish only after BP pressure recharged to 4.7 kg/cm2.
Relay PR1 is provided for avoiding AFL when loco pilot applying brake through A9.
When control pressure drops through A9, P1 will actuate at 4.5 kg/cm2 and PR1 Relay will
energise and it's I/L will open on AFL branch and action of P2 will nullify. When Loco pilot
again keeping A9 in release position, control pipeline pressure will create immediately and PR1
will de energise after 60 seconds. Due time lag I/L of PR1, flasher light will not work even
though BP pressure is not creating up to 4.7 kg/cm2 within 60 seconds.
TESTING:
Preparation:
1. Keep SA 9 in application position.
2. Ensure BC gauge reads 3.5 Kg/cm2
3. Personally ensure that all brake cylinders are applied and brake blocks are touching to
the wheels.
4. Keep HVSI 1&2 and HVMT 1&2 on '0'
5. Keep MPJ in required direction.
6. Power MODE switch on FL unit must be in Auto/OFF side.
A. WITH TSAFL:
a. Take few notches.
b. By pressing TSAFL, Flasher light will glow, GR will come to ‘0’, Buzzer
will sound, LSAFL & LEDs will glow.
B. WITH A9:
a. Take few notches.
b. Apply A9 to full service, there will not be any actions of AFL except
dropping of BP pressure.
c. When A9 brought to emergency, only GR will come to ‘0’.
C. WITH RS:
a. Take few notches.
b. Open RS. On dropping of BP pressure below 4.4 Kg/CM2 Flasher light
will glow, GR will come to ‘0’, Buzzer will sound, LSAFL & LEDs will
glow (On opening of BP angle COC also same actions will come).
206.9 BOGIES
Introduction:
Bogies in locomotive are provided to permit long length of locomotive body to negotiate
the curves. A small length of bogie is desirable. The length of bogies is decided by the distance
between the centre of extreme wheels of bogie is known as bogie wheelbase. Bogie wheelbase
shall be well proportioned to permit the bogie negotiating the curve and jerking. The bogie has
two a more bogies on which the body is mounted. The distance between the centers of extreme
wheels is known as the total wheelbase.
ETTC/BZA Page 64
Course Material for LP Refresher Course 206. Modifications to Locos
Bogies Components:
The bogie of a locomotive is an assembly of following components.
Bogies Frame
Wheels
Axles
Springs
Axle Boxes
Supports For Traction Motors
Supports For Brake Rigging & Brake Cylinder
Friction Dampers / Snubbers.
ETTC/BZA Page 65
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 66
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 67
Course Material for LP Refresher Course 206. Modifications to Locos
20. Safety chain is provided between bogie frame and loco body and provided at centre
axle.
Static Converter is provided in place of ARNO to give constant 415 Volts ±5%, 50 Hz, 3Ø AC
supply to all auxiliary motors, to charge the batteries and to give 415 volts 1Ø AC to non-motor
loads (static devices). At present static converters are designed by SIEMENS, AAL, MEDHA,
HIRECT, Stesalite and ABB companies. Nowadays most of the locos are provided with Static
converters.
Equipment removed:
ARNO, C118, R118, QCVAR, HQCVAR, QOA, HQOA, QLA, Q100, HCHBA, QTD 105
&QTD 106.
Indications on SIV panel: Most of the SIV inverters having following indications
a) OHE out of range lamp (red colour).
b) Internal fault lamp (red colour).
c) External fault lamp (red colour).
d) SIV ON lamp (green colour).
e) Battery charger ON lamp (green colour).
f) ELD bypass switch.
g) ELD by pass LEDs.
ETTC/BZA Page 68
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 69
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 70
Course Material for LP Refresher Course 206. Modifications to Locos
S
Indication / operation Ab. sign Probable reasons
No
1 On closing BLDJ and pressing ICDJ a. Less air pressure in RS or MR.
BLRDJ, LSDJ remains glowing b. Less BA voltage.
c. Q118/ Q45/ Q44/MTDJ not
energized.
d. Less VCB unit pressure.
e. A conk defective.
f. QSIT may energised
2 Close BLDJ, press BLRDJ. No a. Derailment/ Accident(
LSDJ extinguished, UA needle Tension reduction of BP levels in loco)
not deviated, no auxiliaries b. Defect in Feeding Power
sound, DJ trips immediately Circuit.
after releasing BLRDJ. c. Defect in OHE/ track/
formation
d. Defect in A0 / A33.
e. Cut in TFWA.
f. Insufficient rising of panto.
g. Foreign body on loco roof.
h. Cut in roof bars towards raised
panto or touching to loco roof.
3 Close BLDJ and press BLRDJ ‘A’ a. QSIT may be defective
LSDJ extinguishes and comes Beginning b. QPDJ may be defective
back immediately. c. Leakage in VCB unit
d. MTDJ coil may be defective
4 Close BLDJ and press BLRDJ. ‘A’ Ending
LSDJ extinguished, UA meter SIV not picking up
needle deviated, Release
BLRDJ. LSCHBA glows
continuously and DJ maintains
till MR/RS pressure available.
ETTC/BZA Page 71
Course Material for LP Refresher Course 206. Modifications to Locos
A. ICDJ (On closing BLDJ and pressing BLRDJ, LSDJ remains glowing):
Trouble shooting:
➢ If Q118, Q45, Q44 are not energized, trouble shooting is same like
conventional loco.For Q118 clean QCON N/C I/Ls also.
➢ If unsuccessful, place HOBA in OFF and try,
➢ Switch OFF & ON battery, and try.
Note: If QSIT is energized, troubleshoot for SIV tripping and other troubleshooting for EFDJ is
same as conventional loco.
If unsuccessful contact TLC for advice.
ETTC/BZA Page 72
Course Material for LP Refresher Course 206. Modifications to Locos
B. NO TENSION: (While closing DJ, LSDJ extinguishes, UA meter does not deviate, and
DJ trips immediately on releasing BLRDJ).
Trouble shoot for “NO TENSION” is same as conventional loco.
C. ‘A’ beginning: (Close BLDJ and press BLRDJ LSDJ extinguishes and comes back
immediately.)
Trouble shooting: If QLM is energized trouble shoot as conventional loco for QLM
energisation. Raise RS pressure and try and operate relay targets once and try.
D. ‘A’ Ending:
(Close BLDJ and press BLRDJ. LSDJ extinguished, UA meter needle deviated, Release
BLRDJ. LSCHBA glowing continuously and DJ maintains till MR/RS pressure
available.)
Trouble shooting: Trouble shoot as follows for SIV not picking up
➢ Check CCINV, If melts renew. Still melting keep HOBA in ‘OFF’.
➢ If CCINV good condition, Close BLVMT and try.
➢ Still SIV not starting, Check whether QSVM is energised
➢ If QSVM is not energized, Check CCA
➢ If CCA melts renew, still melting keep HOBA in ‘OFF’ & Try.
➢ If CCA good, Wedge QSVM.
➢ Still SIV not starting, clean QV60 N/C I/L,
➢ Still SIV not starting
➢ Keep HBA “OFF” & try
Precaution: If QSVM is wedged close BLVMT before closing DJ to ensure soft start.
ETTC/BZA Page 73
Course Material for LP Refresher Course 206. Modifications to Locos
➢ Put HVMT 1 & 2 and HVRH on 3 and close BLVMT and close DJ.
➢ Ensure the working MVMT-1, MVMT-2 and MVRH. If any one of the blowers
are not working isolate the same and work with precautions.
➢ If all the 3 blowers are working normally with HVRH, HVMT-1 and HVMT-2
on 3 position , clear the block section, trip DJ, place HVRH on '1' close BLVMT
and close DJ, and wait for 15 seconds after extinguishing of LSCHBA. If DJ
trips, QVRH is defective, place HVRH on '3' and other two switches on '1', work
further duly watching MVRH blower working.
➢ If DJ holds with HVRH on '1', trip DJ, place HVMT-1 on '1', close BLVMT and
close DJ, and wait for 15 seconds after extinguishing of LSCHBA. If DJ trips,
QVMT-1 is defective, place HVMT-1 on '3' and HVMT-2 on '1' and work
further duly watching working of MVMT1 frequently.
➢ If DJ holds with HVMT-1 on '1', it indicates QVMT-2 is defective, so keep
HVMT-2 on '3' and work further duly watching working of MVMT-2 frequently.
I. OPERATION ‘2’: (DJ trips after taking 6th notch, after 5.6 seconds)
Troubleshoot:
Same as conventional loco for any Contactor not closing.
➢ If C107 alone is not closing, tap CTF 1.
➢ If contactors closed and N/O I/Ls are defective, trouble shoot same as
conventional loco.
Note: Wedging of contactors are not permitted.
➢ If any internal or external fault occurs SIV stops and restarts for 2 to 3 times
normally.
➢ If trouble is not rectified, DJ trips through relay QSIT and LSSIT lamp glows on
Loco Pilot’s desk.
➢ Check fault lamp (External/Internal) on SIV panel and trouble shoot accordingly.
ETTC/BZA Page 74
Course Material for LP Refresher Course 206. Modifications to Locos
Now close BLCP, if external fault lamp glows, trouble with one of MCPs. Find out
defective one, isolate and work normal.
After closing BLCP, if lamp is not glowing, close BLVMT, if lamp glows, trouble with
one of MVMT 1, MVMT2 and MVRH. Find out defective one, isolate and work
accordingly. If load and road do not permit, contact TLC.
Action to be taken:
1. Press Reset button, if lamp extinguishes work further.
2. If lamp is not extinguishing, contact TPC/TLC and confirm whether OHE is within
range.
ETTC/BZA Page 75
Course Material for LP Refresher Course 206. Modifications to Locos
3. If OHE is normal, trip DJ & keep HBA in OFF and ON & try.
4. Still not successful ask for relief engine.
Note: If there is no information and OHE is restored after 5 min. observe G&SR rules.
Note: Normally for faults related to OHE voltage (under voltage or over voltage), static
converter does not lock but restarts as soon as voltage resumes within permissible range.
Other instructions:
➢ Avoid simultaneous closing of BLCP and BLVMT when QTD101 is wedged.
➢ Close BLVMT before closing DJ whenever QSVM is wedged.
➢ DJ trips with LSSIT lamp glowing/QSIT target dropping, troubleshoot for SIV.
➢ DJ trips and LSSIT lamp not glown/QSIT target not dropped, troubleshoot for tripping
failures.
➢ BA on load test is not possible in SIV locos since HCHBA is not provided.
ETTC/BZA Page 76
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 77
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 78
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 79
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 80
Course Material for LP Refresher Course 206. Modifications to Locos
IMPORTANT INSTRUCTIONS
1. If there is any fault in loco, the fault message will come on display unit along with
buzzer sound. Based on the fault message, troubleshoot according to TSD. After
troubleshooting, press ACK/CLR FLT button provided on display unit. Message will
clear from the screen and it will be recorded in memory, buzzer sound stops.
➢ If message not cleared keep HOBA in OFF and try.
➢ If still unsuccessful, keep HBA on ‘0’, wait for 3 min., again energise the loco
and try.
➢ If there is a message working with one ‘CPU’ Then press ‘ACK’ button and
work the train and inform TLC at appropriate place.
2. BPQD is provided on locopilot desk of each cab. This switch should be pressed (up to
10th notch only) if locopilot experiences auto regression via wheel slipping. After
releasing BPQD, If still auto-regression experiences, it may be due to any Traction
Motor defect, troubleshoot according to TSD.
3. In case of any safety relay acted, troubleshoot according to TSD.
ETTC/BZA Page 81
Course Material for LP Refresher Course 206. Modifications to Locos
4. In case of any E.M contactor not closing, troubleshoot according to TSD, If unsuccessful
keep HOBA in OFF and try. Still unsuccessful in case of ARNO provided locos wedge
the contactor and work onwards.
5. In case of tripping through Airflow relays, locopilot can isolate relay/Blower through
Programme switch like conventional loco.
6. It is not necessary change the position of ZSMS, during EEC operation.
7. Do not change the position of any switch while the loco is in energised condition.
8. If anyone display unit not working:
By observing other cab display unit messages work onwards duly making necessary
remarks in logbook.
9. If both display units not working
Keep HBA on `O' and keep in `1' after 10 sec. If still not displays.
If Loco is in energised condition work up to destination, duly informing to TLC and
make necessary remarks in log book.
If any fault occurs, identify the same with the help of pilot lamps and troubleshoot as per
TSD
10. If main unit is not working, pilot lamps will not work and no message will be displayed.
Ensure battery voltage is above 90 V.
Check Add. CCBA, CCBA, CCPT and CCCPU. If any fuse melted, renew the same. If
again melts keep HOBA in OFF and renew the fuse.
If still unsuccessful, keep HBA on ‘0’ and wait for 3 minutes and again try to close DJ.
ETTC/BZA Page 82
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 83
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 84
Course Material for LP Refresher Course 206. Modifications to Locos
33. All Loco Pilots should have good road knowledge and self confidence to
operate/handle loco & train.
34. Switch on flasher light when BP is dropped other than A9.
35. Do not pack luggage or box while approaching signals at ON.
36. Do not talk on VHF sets while approaching signals at ON.
37. Do not write memo book or log book while approaching signals at ON.
ETTC/BZA Page 85
Course Material for LP Refresher Course 206. Modifications to Locos
ETTC/BZA Page 86
Course Material for LP Refresher Course 206. Modifications to Locos
6. All brake rigging; brake block, brake shoe, sleeve rod, assembly hanger arrangement
are OK.
7. Wheels are not skidded.
8. Return current bush are connected properly.
9. Parking brakes cylinders are provided with manual releaser hook.
10. Traction link is fitted properly and their all 6+6 bolts are tightened with safety slings.
11. Oil level in CP is above min mark; also ensure that CP foundation bolts are tightened.
12. Bogie brake -1 COC is in open condition.
13. Battery box cover is locked.
14. Safety chain is intact.
15. BP and FP additional COC are in open condition.
16. Ensure MCP’s, traction links and traction motors are properly secured with safety
slings.
D. In Cab
1. Cab and look out glasses are clean.
2. All switches are normal, ZBAN-OFF, BLCP-AUTO
3. Emergency exhaust Cocks are normal.
4. Water is filled up in windshield washer unit.
5. Spare hoses, wooden wedges are provided in side locker.
6. Fixed and handy both fire extinguisher are in good condition and filled with gas.
7. Ensure that emergency push button is released.
E. In Machine Room
1. Control and power Circuit breakers in cubicle SB-1 / SB-2 , HB-1 and HB-2 are
normal
2. Switches provided in SB-1 are at normal position.
3. Oil level of conv-1/2 and transformer-1/2 are above min mark.
4. All fittings and connections are normal.
5. Outer cover of any power equipment is not opened.
6.
ETTC/BZA Page 87
Course Material for LP Refresher Course 206. Modifications to Locos
Energisation Of Loco
1. Check the machine room and cubicle HB1/2,SB1/2 and pneumatic panel and ensure
that all Circuit breakers, rotating switches and Cock at Pneumatic Panel are at Normal
position and ensure that key ‘IG-38’ is provided on pneumatic panel. Also ensure that
panto selector switch is at normal position.
2. Switch ON compartment light, it ensures closing of main circuitry breaker 112 of
battery.
3. Put battery additional circuit breaker No.112.1 to ‘ON’ position in cubicle SB-2.
Ensure that CHBA circuit breaker No. 110 (SB-2) is at ON position and also CHBA
input MCB 100(HB-2) is at ON position.
4. Go in operating cab.
5. Insert A-9 handles at ‘Neutral’ position and keep it in ’RUN’ position by lifting lock.
6. Insert ‘BL’ key at ‘OFF’ position and turn it to ‘D’ position
a. Light of screen (panel-C) and Memotel will get ON.
b. MCPA will start (if pressure is less).
c. UBA will deviate to 110 volts.
d. LSDJ will glow.
All above indications indicates that Control Electronics is get ‘ON’.
7. The message “Loco is in configuration, please wait” will appear on the screen and self
testing is done for 10 seconds.
8. During testing, all pilot lamps will glow and extinguish, Bogies-1 & 2 meter will
deviate both in TE/BE mode and come to -0
9. After testing FLG No. 504, will be displayed on the screen, Now press ‘ZPT’ in ‘UP’
mode for raising of pantograph and confirm the touching of panto with contact wire
by seeing physically also U-meter will deviate and indicate the value of OHE voltage.
10. No.550 will display on the screen- now press BLDJ for closing VCB and check
‘LSDJ’ is extinguished.
11. Now DJ will close, loco will energize and all the auxiliary motors will start
automatically.
12. Ensure that BLCP is at AUTO position.
13. No.570 will appear on the screen.
14. After building of MR pressure to 6.4 kg/cm2, set Reverser to F/R as per requirement.
(FLG 590 will show on the screen.)
15. Note: If the reverser is set without confirming the MR pressure above 6.4
kg/cm2, P 1 message will be there on screen- indicating wrong operation.
16. Apply loco brakes, now release the parking brakes, ensure BP pressure is 5 kg/cm2,
ensure AFI is at Zero.
17. Now operate throttle in TE direction.
18. TE /BE meter will deviate in TE side indicating that traction is available. No. “596”
will appear on the screen.
19. Check the loco brake power. Release loco brake.
ETTC/BZA Page 88
Course Material for LP Refresher Course 206. Modifications to Locos
PROCEDURE
1. Stop the train and secure the loco by applying SA-9.
2. Open the VCB and lower the pantograph
3. (Ensure FLG-504 on the screen).
4. Operate BL-key from ‘D’ to ‘Off’ (wait for 2 sec.) ensure LSDJ off, UBA indicates
‘0’ and parking brake gauge needle ‘0’.
5. Operate BL-key from ‘Off’ to ‘C’ ,LSDJ,UBA indication comes back and wait (wait
for 6 to 10 sec) until display screen, SPM display screen, LSDJ, and UBA goes off.
6. It indicates that CE goes’ OFF’ and now rotate it from ‘C’ to ‘OFF’ for removing the
BL Key or Going to other Mode. Ensure BP pressure drops to ‘0’.
Note:
a. CE gets automatically ‘off’ after 10 minutes if BL-key is rotate from ’D’
to‘OFF’ (as explained in self hold mode).
b. C.E. will get ‘off’ automatically after 10 minutes in driving mode also, if panto is
remained in lowered position for more than 10 minutes.
c. If the key switch is moved from “D” to “Off” without opening VCB and
lowering panto graph, results in automatic shutdown of the loco.
d. Loco will go into shut down mode if more than one cab activated for more than
10 minutes.
ETTC/BZA Page 89
Course Material for LP Refresher Course 206. Modifications to Locos
NOTE:
a. After 10/15 min if LSCE lamp does not extinguished then normalize and energise
loco as per procedure and in Driving mode check for availability of TE, if TE is
available then ignore LSCE lamp work further duly informing TLC and make a
remark in the loco log book.
b. During Cooling Mode observe UBA meter frequently. If battery voltage drops to
92V, stop cooling mode and energise the loco in driving mode to charge the batteries
(CHBA will not work in cooling mode).
c. During cooling mode ,if VCB trips ensure no OCR action.
d. If CE is switch off it may not possible to reenergize the control electronics if LSCE
glowing continuously. Now press 126 and 218 Contactors in SB-1 for CE to get ON.
1. Stop the train at convenient place and apply loco brakes by SA-9.
2. Ensure that brake cylinders showing 3.5 kg / cm2.
3. Release parking brakes and release A-9.
4. Keep the screen on SIMULATION MODE.
5. Operate reverser to forward.
6. Move throttle in traction and loco should not move up to 150KN (WAG9/WAP7) and
100KN (WAP5).
7. If the loco is moving with in the KN it indicates that loco brake power is poor.
8. Inform to TLC, make a remark in loco LOG BOOK.
ETTC/BZA Page 90
Course Material for LP Refresher Course 206. Modifications to Locos
Note:
a. If BL key is taken ‘OFF’ without opening DJ and lowering panto, loco will be
shutdown as emergency shutdown will initiate on loco.
b. During normal driving if BL key is kept ‘OFF’, emergency brakes will get applied as
emergency shutdown will initiate on loco.
c. After moving the key switch ‘BL’ to position ‘O’, the MCE remains active for 10
minutes. The cab changing should take place during this time.
d. Apply Loco brakes when BL key is in Driving mode only since SA9 and A9
becomes deactivates in BL key in OFF position.
Multiple unit
1. Move key switch ‘BL’ on master locomotive into position ‘Off’ and remove the key.
2. Set automatic brake controller to position ‘Neutral’
3. Release direct brake .
4. Close 136 Cock.
5. Insert key in Loco pilot’s cab of previous slave loco.
6. Open 136 cock.
7. Move key switch “BL” into position “D”
Note: The change of Loco pilot’s cab has to take place within this 10 minutes
period otherwise the MCE has to be restarted.
Banking Mode
When it is required to use loco as a banker i.e use of TE / BE without charging BP, at that time
loco should be operate in banking mode.
Procedure:
1. Couple the loco with formation. Do not open the BP and FP angle cocks.
2. Trip the VCB and Set switch “ZBAN” “to position “ON” (Panel A).
3. BP pressure will be drop to ‘0’.
4. In E-70 Loco: Close 70 & 136 cocks provided on pneumatic panel.
5. In CCB locos: Close 136 cock and keep Mode switch in HLPR.
6. Set up the loco in the normal manner.A-9 will not active except emergency position.
7. Loco pilot receives a priority-2 message F1001 P2 that banking mode is active.
8. Open BP and FP angle cocks, BP and FP pressures will rush into this loco which will
be seen in the gauges.
9. Loco is ready for banking operation.
10. On completion of banking mode operation, switch off ZBAN, Open the cocks/change
mode switch to lead for Normal working.
ETTC/BZA Page 91
Course Material for LP Refresher Course 206. Modifications to Locos
Loco Grounding
Loco should be grounded only while climbing loco roof to attend any trouble on loco body like
removing foreign body, securing damaged pantograph etc.
PROCEDURE:
1. Stop the train at convenient place and secure the train.
2. Open VCB and lower pantograph.
3. Rotate IG-38 in anti clockwise direction and extract key.
4. Insert the key in empty socket of HOM box and rotate in clock wise direction.
5. Operate HOM handle by 180 degrees by taking it out from latch.
6. Rotate yellow KABA key in clock wise direction and extract the key and keep in
personal custody.
1.
DO’s and DON’Ts for Loco Pilots
DO’s
1. Acknowledge VCD always within every 60 sec.
2. Do maximum use of regenerative braking, it not only control the train but participate
in generating the power.
3. In case of any trouble, as a last step, switch off the CE for 5 minutes.
4. In panto down condition and in CE off condition, to switch on the flasher, use cooling
mode.
5. In case of heavy airflow, instead of attending the screen, do the protection of train and
adjacent track.
6. In case of emergency use emergency stop push button.
7. While deactiving the CSC , check the position of throttle , it should not be opposite to
the force.
8. Use throttle gradually.
9. Before regenerative braking, bunch the load.
10. While working dead loco, ensure conjunction working in dead loco.
11. While working dead loco ensure releasing of parking brakes and pneumatic brakes in
dead loco.
ETTC/BZA Page 92
Course Material for LP Refresher Course 206. Modifications to Locos
12. First note down the fault message and then acknowledge the fault.
13. During failure mode operation, use throttle carefully.
14. Before resetting MCB, first rotate the knob provided on it.
15. Keep the SA-9 handle of rear loco at release.
16. Apply parking brakes when stationary.
17. 17.Instead of continuous operation of sanders, use frequently.
DON’Ts
1. Don’t operate BL when loco is in motion.
2. Don’t believe on U-meter, ensure the panto physically.
3. Don’t press PSA continuously.
4. Don’t allow any unauthorized person in rear cab, as some functions are remains active
in rear cab.
5. Don’t declare the loco FAIL, without switching OFF and ON the control electronics.
6. Don’t lower the panto for more than 10 minutes otherwise CE will switch off.
7. Don’t forget to acknowledge the fault message.
8. Don’t use CSC in undulating area.
9. Don’t isolate VCD unnecessarily.
10. Don’t switch off CE in running train.
11. Don’t smoke in the loco.
12. Don’t use quick release position of A-9 frequently and unnecessarily.
13. If MR pressure is less than 6.4 kg/cm2, don’t operate MPJ.
14.
MAKING LOCO DEAD
When loco can’t be worked further due to trouble, make the loco dead. Following
procedure to be followed for making dead.
ETTC/BZA Page 93
Course Material for LP Refresher Course 206. Modifications to Locos
1. Open VCB and lower the pantograph of the loco to be sent as dead. Isolate the
pantograph through panel isolating cock on pneumatic panel.
2. Switch off the control electronics as per procedure.
3. Take out BL key from ‘OFF’ position.
4. Keep auto brake handle (A9) in ‘Neutral’ position in both the cabs of dead loco and
take out handle. Keep the auto brake handle (A9), BL key & loco log book in safe
custody.
5. Switch OFF the MCB No.112.1 and 110 in SB2 panel. Switch OFF all corridor and
cab lights.
6. Couple the dead loco in rear of the working loco and lock the CBC coupling with lock
pins of both locos.
7. In the dead locomotive, ensure isolating cocks position in the pneumatic panel is as
follows. (Towed dead):
47 74 70
136
Cock (Dead (Emergency/ (E-70 Brake
(Feed Pipe)
Loco) Vigilance) Pipe)
Position Open Closed Closed Closed
8.
1. Connect BP pipe of the dead loco to the BP pipe of working loco and open BP angle
cocks of both the locos. Check the BP pressure gauge in the cab of dead loco. It
should show the same pressure as that of the live locomotive
2. In case of locos are to be attached on a train having twin pipe i.e., both BP and FP of
both the locos should also be connected and its angle cocks should be opened.
3. Connect MR equalising and DB equalising pipes in between locos and open their
angle cocks (if possible). When MR equalising pipe is connected, auxiliary reservoir
of dead loco is charged with leading loco MR pressure. If MR equalising & BC
equalising are coupled, direct loco brake application is possible by direct brake (SA-9)
in leading and dead loco.
4. When MR equalising pipe is not connected, the auxiliary reservoir of dead locomotive
will get charged from BP supply of the working locomotive through cut out cock No.
47. The auxiliary reservoir pressure is used for proportional and parking brake. Direct
loco brake application is not possible in dead loco by leading loco direct brake (SA-9)
if MR equalising & BC equalising are not coupled.
5. Keep the direct brake handle (SA9) in ‘release’ position in both cabs of dead
locomotive.
6. Drain out complete pressure from MR-1 & MR-2 of dead locomotive. After draining
out, close the drain cocks of MR-1 & MR-2.
7. If dead loco brakes are not released, pull the QRV of distributor valve. If still not
releasing, close both bogies isolating cocks and after releasing of the BC pressure
normalize the both bogie isolating cocks.
8. Lock the parking brakes in applied condition. This procedure is safe to avoid brake
binding and condensation of moisture in the parking brake cylinder. It is as under
a) Apply the parking brakes of dead loco by apply push button (left plunger) of
solenoid vale and lock the parking brakes in applied condition.
b) Release the parking brake of the dead loco by manual releasing of individual
parking brake cylinders. For manual releasing, first turn the release handles
slightly clockwise and then pull till a sound of locking mechanism is heard. As
parking brakes are locked in applied condition PB gauge will show 0 Kg/Cm2.
c) The parking brake units are fitted to the following wheels.
ETTC/BZA Page 94
Course Material for LP Refresher Course 206. Modifications to Locos
8. Connect BP pipe of the dead loco to the BP pipe of working loco and open BP angle
cocks of both the locos. Check the BP pressure gauge in the cab of dead loco. It
should show the same pressure as that of the live locomotive
9. In case of locos are to be attached on a train having twin pipe i.e., both BP and FP of
both the locos should also be connected and its angle cocks should be opened.
10. The auxiliary reservoir of dead locomotive will get charged from BP supply of the
working locomotive through cut out cock No. 47. The auxiliary reservoir pressure is
used for proportional and parking brake.
11. Keep the direct brake handle (SA9) in ‘release’ position in both cabs of dead
locomotive.
12. Drain out complete pressure from MR-1 & MR-2 of dead locomotive. After draining
out, close the drain cocks of MR-1 & MR-2.
13. If dead loco brakes are not released, pull the QRV of distributor valve. If still not
releasing, close both bogies isolating cocks and after releasing of the BC pressure
normalize the both bogie isolating cocks.
14. Lock the parking brakes in applied condition. This procedure is safe to avoid brake
binding and condensation of moisture in the parking brake cylinder. It is as under
a. Apply the parking brakes of dead loco by apply push button (left plunger) of
solenoid vale and lock the parking brakes in applied condition.
b. Release the parking brake of the dead loco by manual releasing of individual
parking brake cylinders. For manual releasing, first turn the release handles
slightly clockwise and then pull till a sound of locking mechanism is heard. As
parking brakes are locked in applied condition PB gauge will show 0 Kg/Cm2.
c. The parking brake units are fitted to the following wheels.
LOCO TYPE WHEEL POSITION OF PARKING BRAKE UNITS
WAP 5 1 4 5 8
WAP 7 &
2 6 7 11
WAG 9
d. If parking brake handles are defective and if it is not possible to release
manually, then release the parking brake by ‘release’ Push button (right
plunger) of the latched solenoid valve No.30/22 in the pneumatic panel of the
dead locomotive.
15. Double check the release of parking brakes of dead loco by moving the parking brake
unit by hand.
16. Apply auto brakes (A9) in the working locomotive and check that loco brakes on both
the locomotives are getting applied. Then release the auto brake in the working loco
and check that loco brakes are getting released on both the locomotives. Rear
locomotive (WAG-9 / WAP-5 / WAP7 dead) takes about 60 seconds to release.
17. As a final check, run the train for about 500 meters and feel for any abnormal rise in
temperature of wheels of dead loco and ensure no brake binding in dead loco. Also
check it for every stop during journey.
18. Remember that in the dead locomotive, the loco brakes takes about 60 seconds to
release after releasing of auto brake from the leading loco. Hence after every auto
brake application and release wait for adequate time (minimum 1 minute) for release
of loco brakes in dead locomotive before resuming traction.
19. Escorts accompanied dead locomotive should never put BL key in position ‘D’ and
also strictly avoid to energise the dead locomotive.
20. After reaching the destination, before detaching the working loco and dead loco,
a) Unlock the application plunger (left plunger No.23) of parking brake solenoid
valve No. 30.
ETTC/BZA Page 96
Course Material for LP Refresher Course 206. Modifications to Locos
b) Press the release button of parking brake solenoid valve No. 30(right plunger
No.22). This will charge parking brake cylinders by 5 kg/cm2 from auxiliary
reservoir.
c) Apply parking brakes on dead locomotive by application plunger of parking brake
solenoid valve No. 30(left plunger No.23). Now parking brake gauge shows ‘0’.
ETTC/BZA Page 97
Course Material for LP Refresher Course 206. Modifications to Locos
In 3-phase Locos, some of locos 31393 onwards provided with KNORR CCB-2 brake system,
with minor modifications in equipment and working system with existing knorr-brake system.
Mode Switch:
ETTC/BZA Page 98
Course Material for LP Refresher Course 206. Modifications to Locos
One rotating switch called mode switch is provided in each cab below direct brake valve. This
spring loaded switch can be operated by pressing downward. This switch has following 4
positions.
1. HLPR: While using loco as banker, this switch should be kept at Help position on this
mode in addition to ZBAN at ON.
2. TRL (TRAIL): In non working cab (SU/MU), this switch should be kept on TRL
position.
3. LEAD: In working cab (SU / MU), this switch should be kept on LEAD position then
only BP will charge.
4. TEST: In this position BP leakage / brake continuity tests to be conducted. When this
switch is kept on TEST position , Loco brakes also get applied.
LCD DISPLAY :
It will show messages like
1. “Okay to Run” : Auto handle to RUN from FS position, BP will charge to 5 kg/cm2
and BC will reduce to zero.
2. “Safety Penalty – Keep Handle in FS” :To recover this penalty brake, move Auto/A9
handle to FS and then back to run.
3. “Train-line Emergency – Keep Handle in EMER” : To recover Emergency penalty,
Auto/A9 handle should be moved to Emergency and then back to FS and then to
RUN.
4. Operator Emergency- Keep Handle in EMER- To recover Emergency penalty,
Auto/A9 handle should be moved to Emergency and then back to FS and then to
RUN.
PTDC SWITCH :
It is having 3 positions ( STABLED POSITIONS) Used when train clearing in PTDC mode,
when brake electrons failed.
1. Apply,
2. Neutral,
3. Release.
ETTC/BZA Page 99
Course Material for LP Refresher Course 206. Modifications to Locos
AUTO/A9 OPERATION:
To charge the BP, energize the Loco as normal 3 phase loco, Keep Auto/A9 handle in FS, wait
to see the massage on LCD display of Controller as “Okay to Run”. Move the Auto handle to
RUN from FS position, BP will charge to 5 kg/cm2 and BC will reduce to zero.
To overcharge the BP to 5.50 Kg/cm2, Keep Auto/A9 handle in REL (Release) position
for 3 seconds. Once BP starts overcharging, leave Auto/A9 handle. BP will charge to 5.50 +/-
0.1 Kg/cm2.
Quick release of proportional brake in loco either can be performed by lifting Bail-ring
provided on Direct Brake/SA9 handle or by pressing PVEF Foot Switch.
Go to another cab:
Apply SA-9, Change the position of Mode selection switch from TRAIL to LEAD,
Switch ON Loco Electronics &Un-lock the A9 Handle, Bring A9 Handle from FULL Service
position to RUN position after LCD display OK-TO RUN, Résumé traction after conducting
loco brake power test.
To recover vigilance penalty, bring throttle handle (TE/BE) to ‘0’, wait for 32 seconds.
After that, move Auto/A9 handle to EMER and press BPVR on locopilot's desk. To charge
“BP” move Auto/A9 handle to RUN. BP will charge to 5.0 Kg/cm2. Acknowledge the fault by
pressing BPFA. Resume normal operation.
PARKING BRAKES :
1. Parking brakes can apply in three ways by BPPB, solenoid valve left spindle (red
colour) and by moving BL key D to OFF.
2. Parking brakes can release in three ways by BPPB, solenoid valve right spindle (red
colour) and by manual releasing.
This feature has been provided in case of brake electrons failure (CCB System), by keeping
brake system in this mode, locomotive / train can move at a restricted speed of Max. 10 Kmph
to clear the block section.
reduces to zero. (Note: If loco Brake remains applied, press 20TP (Test point) of
20CP on Pneumatic Panel to Release BC to Zero.
9. Ensure parking brake released condition, (apply parking brake by application spindle,
it will latch automatically and Release Parking Brake by Pulling Manual Release Pins
of Parking Brake Cylinders).
10. After moving, stop the train at a distance of 500m, ensure no brake binding.
11. At stopping, ensure there is no brake binding.
12. At destination, before detaching dead loco, apply parking brakes and put wooden
wedges.
13.
TROUBLE SHOOTING FOR BP NOT CHARGING IN LOCO:
1. Ensure MR pressure 8 to 10 kg/cm2.
2. Ensure both side angle COCs in closed position.
3. Ensure both side additional BP COCs open.
4. Ensure lead cab A-9 in run position, rear cab A-9 in FS and locked by pin.
5. Ensure both side RS COCs closed position.
6. Ensure MODE switch in leading cab LEAD position, in trailing cab in TRAIL
position.
7. Ensure Z-BAN switches in off position in both cabs.
8. Ensure both side PTDC handles in neutral position.
9. Initially To charge the BP, energize the Loco as normal 3 phase loco, Keep Auto/A9
handle in FS, wait to see the massage on LCD display of Controller as “Okay to
Run”.Move the Auto handle to RUN from FS position, BP would charge to 5 kg/cm2
and BC would reduce to zero.
10. Ensure there is VCD action.
11. If message will appear as “Safety Penalty – Keep Handle in FS” and BP not charging
more than 3 kg/cm2, To recover this penalty brake, move Auto/A9 handle to FS and
then back to RUN (Follow massage on LCD of Brake Controller), BP would charge to
5.0 Kg/cm2.
12. If message will appear as “Train-line Emergency – Keep Handle in EMER. To recover
Emergency penalty, Auto/A9 handle should be moved to EMER & then back to FS
and then to RUN (Follow crew message on Display of Brake Controller). BP would
charge to 5.0 Kg/cm2.
13. If message will appear as “Operator Emergency – Keep Handle in EMER. To recover
Emergency penalty, Auto/A9 handle should be moved to EMER & then back to FS
and then to RUN (Follow crew message on Display of Brake Controller). BP would
charge to 5.0 Kg/cm2.
14. If still BP is not charging switch of CE and switch on CE and try.
15. Still BP is not changing contact TLC.
16. Note : At the time of connection of Load with Locomotive, crew message will
appear as “Train-line Emergency – Keep Handle in EMER”. To recover Emergency
penalty, Auto/A9 handle should be moved to EMER & then back to FS and then to
RUN (Follow crew message on Display of Brake Controller). BP would charge to 5.0
Kg/cm2.
To avoid this message, keep mode switch in TEST position before opening the BP angle
cocks. On opening of BP angle cocks BP pressure drops to ‘0’,then change the Mode switch to
Lead position. BP pressure would charge.
MU trailing
Loco - Close Close Close Close Trail Trail
Working
MU Trailing
Close Close Close Close Trail Trail
Loco -Dead
Double
Open Close Close Close Trail Trail
head
Banker HLP
Open Close Close Close Trail
Loco R
Dead Loco Close Open Close Close Trail Trail
Open Open Close
PTDC Mode Open Close Open Open Trail Trail
207.TRACTION DISTRIBUTION
25KV,50 HZ 1 phase supply for electric traction is derived from grid system of state Govt.
through traction substations located along the route of electrified sections normally at a distance
of 35 to 50 kms.
The supply authority supplies power at 220/132/110/66 KV extra high voltage at each
TSS, which is owned , installed, operated and maintained by Railways and feeders are
controlled by TPC.
To ensure continuity of power supply under all conditions the high voltage fed to the
TSS is invariably arranged either from two sources of power supply or by a double circuit
transmission line so that even if one source fails, the other remains in service. Suitable
protective equipment is installed at TSS.
At each TSS two single phase transformers are installed one of which is 8in service and
other is 100% standby.
Feeding post: It supplies power to OHE and is provided with four interrupters.
Sectioning and paralleling post: These posts are situated approximately midway between
Feeding posts marking and demarking point of two zones fed from two different phases from
adjacent TSS. At this post a neutral section is provided.
Sub Sectioning and paralleling post: One or more SSPs can be provided between each FP and
adjacent SP depending upon the distance between them.
Auto tensioning device is provided to supply spark less current and to maintain tension in
contact wire due to temperature variations.
Regulated OHE: If both ends of OHE is provided with ATD, it is called regulated OHE. This
type of OHE is provided block sections and main lines on station sections. In these sections
trains can run with MPS.
Semi regulated OHE: One end of OHE is provided with ATD, it is called Semi- regulated
OHE. This type of OHE is provided in loop lines and yard lines. In this trains can run with
restricted speed.
Un regulated OHE: Both ends of OHE is not provided with ATD’S, it is called unregulated
OHE. This type of OHE is provided in sidings or dead ends. In this train or loco run with
cautious speed.
The following are the various caution boards available on OHE mast / area.
1. Neutral section warning boards
2. Panto lowering / raising boards
3. 25KV public safety warning boards
4. Power block working limit boards
5. Caution unwired turnouts boards
6. Electric engines stop boards
7. MRL (Maximum rail level marking)
8. Mast number / kilometer number
9. Telephone tap direction
10. Distance between mast and center of the track(Implantation)
11. 25KV danger board
12. P/C (Power / Coasting) boards
207.8 Cantilever-Parts:
Quick trouble a) Close BLDJ press BP2DJ observe C118 closing or not if
shooting for C118 closing problem in EFDJ/MTDJ check VCB unit
ICDJ (DJ not pressure gauge should be 5.Kg/cm2 ,Keep HQOA
1
closing) ‘0’,HQOP1,HQOP2 HOBA OFF position and tap DJ and try.
b)If C118 not closing check Q118/Q45/Q44/C118 as per
procedure.
Check CCBA ,CCPT , Addl CCBA ,ensure C105,C106,C107
ICDJ due to
fully opened, ensureQ44/Q46 in de energised condition,
2 Q118 not
operate GR manually, operate Q118 Manually If un success
energised
wedge Q118 and try.
Press BP2DJ and try if unsuccessful check CCDJ ,ensure
ICDJ due to Q45
3 LSGR glowing ,Operate GR manually Change ZPT position,
not energised
Operate Q45 manually and try from rear cab.
Ensure Q118,Q45 are energised and clean the I/Ls of
ICDJ due to Q44 Q118,Q45, ensure LSGR glowing/GR drum on ‘’0” if
4
not energised unsuccessful , Operate Q44 manually if DJ not Holding
wedge Q44.
Check the flexibility of C118, check wire nos 740,B315 near
ICDJ due to C118, clean I/Ls of Q45,Q44 &QCVAR and try from rear cab
5 C118 not if unsuccessful conduct LT test in LT test DJ closing but not
energised closing in HT then take advise from TLC and loop wire nos
726 &731 near HOM.
a)Check the HT-2 compartment for any smell ,smoke ,fire and
QLM alone
6. oil splashes, if any abnormality do not rest target and ask for
acted.
relief engine , If no abnormality reset once.
QLM acted
Check the concerned circuits if any abnormality, isolate the
7 along with other
same and reset the target once.
relays.
Check traction power Ckt 1 RSI-1,SL1, TM1, TM2,
QRSI-1 TM3,L1,L2,L3,J1 for any abnormality.
8
energised. If repeatedly acts isolate TM one by one and try, if
unsuccessful isolate truck 1.
Check traction power Ckt-2 RSI-2,SL2,TM4, TM5,
9 QRSI-2 TM6,L4,L5,L6,J2 for any abnormality.
energised. If repeatedly acts isolate TM one by one and try, if
unsuccessful isolate truck 2.
QOP-1 acted Check traction power Ckt-1 ,RSI-1,SL1,TM1, TM2,
10 target TM3,L1,L2,L3,J1 if any abnormality isolate the concern
(able to reset) equipment and clear the section.
a)Check traction power Ckt-1 RSI-1,SL1,TM1, TM2,
TM3,L1,L2,L3,J1 if any abnormality isolate the concern
equipment if no abnormality is noticed ,if there is No
QOP-1 acted
BANDING FAILURE, place HQOP-1,HOBA in off position
11 target (cannot
if necessary and clear the section.
be reset)
b)If there is banding failure isolate concern TM +ve and –ve
sides, clear the block section with speed not exceeding
15Kmph.
DJ closes but
Check whether QOA/QLA targets dropped.tap the safety
trips
relays and QPDJ ensure RS pressure above 6.5kg/cm2 if
17 immediately
unsuccessful keep HQOA “0”,HQOP1 ,HQOP2 ,HOBA in
(Operation A
“Off” position and try.
begining)
DJ closes, UA
meter deviates Check ARNO and QCVAR for any smell & smoke if no
LSCHBA not abnormality keep HQCVAR on “0” and close DJ . Release
extinguish BLRDJ after 4 seconds.
18.
before releasing
BLRDJ DJ trips
(Operation A
ending)
DJ closes
LSCHBA also
extinguish while
Problem with DJ N/O I/L on MTDJ branch after taking
releasing
19 permission from TLC loop 733- 739 wires near C118
BLRDJ DJ trips
contactor.
(In VCB locos)
(Operation A
ending-Part2)
After releasing Check for any smell ,smoke, fire from MVSL1&2,MPH if no
BLRDJ DJ trips abnormality place HVSL-1 & HVSL-2 on “3” HQCVAR
20 after 5.6sec &HPH on “0’ close DJ and clear the block section by
(Operation B observing TFP oil level.
part 1)
Problem with Q30 relay /less OHE ,Wedge Q45 work onwards
After releasing
with precautions.
BLRDJ,DJ
Note: Do not wedge Q45 if loco having Operation A ending
21 tripsimmediately
problem, for ARNO locos
(Operation B
part II)
After closing
Check for any smell, smoke ,fire from
BLVMT DJ
MVRH,MVMT1,MVMT2 if no abnormality place
22 trips within
HVRH,HVMT1,HVMT2 on 3 and clear the block section.
30sec
(Operation O)
Check for any smell ,smoke ,fire from MVSI-1,MVSI-2 if no
After taking 1st
abnormality place HVSI-1, HVSI-2 On 3 if unsuccessful clear
23 notch DJ trips .
the block section with manual operation of GR with SR
(Operation 1)
30Kmph.
a)If C107,C105,C106 contactors closed place
HVRH,HVMT1,HVMT2 on 3 if unsuccessful Wedge Q118
After taking 6th
clear the section.
notch DJ trips
24 b)If all contactors not closing check CCA&Q100.
in 5.6 seconds.
c)If any one contactor not closes wedge the contactor and
(Operation 2)
place concern switch in 3 position.
1 st notch auto Press, PSA, ZQWC and start, Check for brake binding, Slipped
regression with pinion, Locked axle, Ammeters A3/A4 not deviating isolate
29.
LSP glowing . TM3/TM4,if volt meters U2/U5 not deviating isolate
TM2/TM5 and try.
MPH not
working/
Place
HPH on ‘0’ and
clear section
with 920/500A
current. Place HPH on ‘0’ and clear section with 920/500A current.
30 MVRH not Place HVRH on ‘0’, ensure C-107 is open ,and clear the
working section with 920/500A current.
Place
HVRH on ‘0’
and clear section
with 920/500A
current.
MVSI-1 or
Isolate the RSI-1 block by keeping HVSI-1, HVSL-1 &
MVSL-1or
31 HVMT-1 in ‘0’ position, if load and and road permits work
MVMT-1 Not
further . If not inform to TLC and ask for banker loco.
working
MVSI-2 or
MVSL-2or Isolate the RSI-2 block by keeping HVSI-2, HVSL-2 &
32 MVMT-2 Not HVMT-2 in ‘0’ position, if load and and road permits work
working further . If not inform to TLC and ask for banker loco.
TLTE with LSB If LSB glowing ensure position of J-1, J-2 operate MPJ ,check
61 glowing(MPFD CTF 123, and C145, for correct position ensure LSC145
S) extinguished . Switch OFF battery for three minutes and try.
TLTE without Try with EEC ,Ensure SMGR in 6clock position, paco switch
LSB lifted condition,, ensure SMGR pressure 2.5 to 3.5 kg/cm2,
62
glowing(MPFD RGEB1COC open position ,change HPAR ,try from rear cab
S) ,if unsuccessful clear with manual operation of GR.
Ensure HVSI-1,HVSI-2,HVMT-1,HVMT-2 in ‘1’ ,try by
TLTE with GR
changing on ‘3’ Ensure EP1,EP-2 cocs in open condition, EP
63 progression(MP
drain coc closed position ,ensure MR above 8kg.cm2 if un
FDS)
successful try from rear cab.
a)In a defective loco LSGRPT or LS group lamp will glows, but
Find out the
LSOL is extinguished Condition.
defective loco
64 b)In a healthy loco LSOL will glows, but LSGRPT or LS group
and healthy loco
is extinguish condition.
in MU
Trouble shoot as a single loco ,during trouble shooting keep ZLS
IN MU DJ trips
65 on ‘0’ in trailing loco ,if unsuccessful clear the block section
in leading loco
with trailing loco.
Put BLSN ‘DOWN’ clear section if load permits, after clearing
the section check defective loco trouble shoot as single loco
In MU DJ trips during trouble shooting keep ZLS on ‘0’ in leading loco. Rear
66
in trailing loco loco DJ can be closed by pressing BP2DJ in rear loco provided
BLSN normal and BLDJ closed in leading.
Train Brakes not Ensure BP 5kg/cm2 in loco Pull QRV, isolate DV and pull
releasing in QRV,close BC1,BC2 cocs if unsuccessful Puncture the flexible
67
conventional hose pipe and try, If BC piston is inside slack SAB , disconnect
bogies brake pull rod cotter pin and secure it.
Train Brakes not
Pull QRV, close BP,FP cocs and drain out AR then isolate DV
releasing in
68 and pull QRV If unsuccessful close BC1, BC2 cocs if still
BMBC
unsuccessful remove the truss bar pin and secure it.
bogies(Coaches)
Train Brakes not Pull QRV, isolate DV and pull QRV, ensure piston stroke
releasing in indicator is inside or APM actuating plunger is lifted condition
69
BMBC still unsuccessful close the COC between APM and both BCs
bogies(Goods) .Finally shake the brake rigging assembly slightly.
Indentify the coach if indicator shows red colour it indicates
Train Brakes not brake binding. If it is releases indicator will turns in to green
70 releasing in colour. Pull the QRV of DV and try, close the BC1 & BC2 cocks
LHB coaches and try ,if unsuccessful remove Flexible hose pipes (two) of the
trolley and try.
1. Manual isolation of bogie can be done using switch no 154 without switching of CE.
However, to bring back isolated bogie in to service, CE off &CE on duly normalizing
the switch no 154 position.
The modified procedure of bogie isolation:
o If the loco is running: Bring the throttle to ‘0’ position, Open the VCB.
▪ Ensure Node No. 550, Keep switch No. 154 in required position, Required
▪ bogie will be isolated after 10 seconds.
If the loco is stand still: Bring the throttle to ‘0’ position, Ensure Node
▪ No.590, Keep switch No. 154 in required position, required bogie will
be isolated after 10 seconds.
2. To change the position off switch: 160, ensure Throttle on 0, loco/train is Dead stopped
and Reverser on 0.
3. To change the position off switch: 152, before operating this switch, TE/BE handle
should keep in ‘0’ position.
4. For resetting of MCBs in HB-1& HB-2, trip VCB, reset MCB and close VCB.
5. For resetting of MCBs in SB-1& SB-2 (Except 127.92 for Speedo Meter, 310.1/1 &
310.1/2 for head lights, 310.7/1 for marker lights.) switch off CE reset MCB and switch
on CE.
6. For MCBs 127.92 for Speedo Meter, 310.1/1 & 310.1/2 for head lights, 310.7/1 for
marker lights, trip VCB reset MCB and close VCB.
7. In case of angle transmitter going defective, immediately switch over to failure mode
using switch 152 in running condition, there is no need to stop.
8. In case of Harmonic filter isolation, speed restricted to 40kmph, in case of light load,
isolate bogie -1 by 154, to bring harmonic filter in to service CE off and CE on required.
If harmonic filter came in to service can work with normal speed.
9. While on run, if bogie meter suddenly not respond, LP should trip VCB and reclose
VCB.
10. While on run, if reduction in traction effort with LSP without any proper reason, isolate
bogie-2, work up to convent place, switch off CE and switch on CE ,to bring isolated
bogie in to service.
11. While on run, if bogie isolated without any message, at convent place, switch off CE and
switch on CE, to bring isolated bogie in to service.
12. While on run, after two or three attempts of reclosing of VCB while attending any fault,
bogie may get isolated, at convent place, switch off CE and switch on CE, to bring
isolated bogie in to service.
13. While working with MU, if leading loco fails ,with TRAILING MODE operation we
can clear section with leading loco only.( by keeping 154 switch of leading loco in I+II
position , VCB of rear loco can be closed from front loco itself to clear section but
leading loco CHBA will not work)
14. In IGBT locos, TM can isolate individually by the system, in case of Short circuit in
TM, Single phasing in TM etc instead of truck Isolation.
15. In IGBT locos, Due to space consistent the message for isolation of TM will be display
in F04 & F05 subsystem fault messages.
16. In IGBT locos, for traction converters (SRs) Electromagnetic Contactors are provided in
Place of electro pneumatic contactors. Position in Pneumatic panel.
17. In IGBT locos, SRs are cooled by water coolant Instead of oil, Water level Sensors are
provided in some locos, if water level decrease below Sensor level concern SR will
isolate with message numbers as F0206P1/ F0306P1.
18. In IGBT locos, ensure 3 way coc in proper position if provided for SR.
19. In some of the IGBT locos, water coolant pump provided in side SR.
20. In TPWS loco, ensure Battery control switch should in OFF position , TPWS Isolation
switch should be in ON position in on TPWS unit , Pneumatic isolation cocs in closed
condition in both Cabs, provided under the locopilot brake controller (A-9) on the FITL
interface unit (one window is provided for opening and closing of this coc ).
21. In Doppler Radar provided locos, if any sudden dropping of TE/BE, on bridges
experienced, isolate concern Doppler Radar breaker.
22. In case of any transformer pump not working, work with 70% of maximum TE/BE.
23. Automatic switching of corridor lights after 10Min of loco shut down to avoid battery
discharge , if corridor light are required ,BL key to be kept in “C” mode.
24. In case of “OHE failure” for short time, in loco un manned condition leads to battery
discharge through continuous working of MCPA.
25. Any fault message should not be acknowledge without read and note down.
26. MCB 127.7 in SB2, to be checked first during brake electrons failure.
27. Timely action to P2 message, avoid failure of loco with P1 message.
28. Continuous using of sanders leads to MR pressure dropping.
29. Pressure drop in MR, May due to VCD activation, ensure no VCD action.
30. Pressure drop in MR, May due to AIR DRIER defective, isolate AIR DRIER and try.
31. Pressure drop In MR, may due to ULs or ADVs air leaking, in such case:
➢ Close VEUL and ADV coc near battery box-2 if provided.
➢ Disconnect cable no 26 near C3W valve in pneumatic panel.
➢ In case KNORR ccb-2, close VEUL coc in pneumatic panel.
32. Pressure drop In MR, ensure there is no leakage in AFI indicator glass.
33. Ensure “ZBAN” switch is in normal position while changing CAB. Whenever BP drops
with fault message ”F1004 P1”, check the ZBAN switch also.
34. Check “ZTEL” if TE is not getting more than 300KN( WAG-9)
35. For switching of CE, Keep A-9 to emergency, to avoid MR dropping.
36. For resetting of VCD, keep A-9 to full service, to avoid MR dropping.
37. In case of speed not increasing, more than 1kmph/creeping, isolate bogie-1 or bogie -2
as per DDS message. (In IGBT locos the system can isolate defective TM).
38. In case of speed not increasing, more than 10kmph, tap 269.6/1& 269.6/2 pressure
switches near pneumatic panel.
39. In case of speed not increasing, more than 15 kmph, ensure 160 switch in proper
position.
40. If loco brakes not releasing, close and open 94 coc and try, in knorr-ccb2 brake locos
press and release test switches 16 and 20 in pneumatic panel.
41. In case of VCB not close, try to trouble shoot by isolating bogie one by one.
42. In case of voltage out of limit message, check PT fuse or by isolating one bogie as per
DDS message.
43. For changing of PT fuse, lower panto and change the PT fuse.
44. In case BL key giving trouble, try by pulling key up slightly.
45. BPCS switch should not be pressed for more than 5Sec. It shall give switch struck up
message and became non functional.
46. VCUs modified locos, in case of messages like F1301P1, F1302P1,
47. F1401P1, F1402P1, cab will not isolate, with precautions can work from Same cab.
48. Isolate SR-1 and SR-2, by 127.1/1 or 127.1/2, in case of faults like F0104P1, F0107P1,
and F0107P2.
49. If regenerative brake fail on run, press PVEF and apply A-9 .FOR application of brakes
and to avoid wheel skidding.
50. In cooling mode if VCB trip, check OCR and TFP OIL flashes.
51. If OCR acts second time CE OFF automatically.
52. OCR is provided with Mechanical Locking Type.
53. In case fault message with F020101 P1, F0301P2, if need CE off, switch on CE after 5
minutes only.
54. For resetting VCD, keep throttle-0, press BPVR after 160 sec for WAG-9/WAP-7,
120sec for WAP-5, 120sec for KNORR locos, 32sec for KNORR CCB-2 locos.
55. If any repeated tripping of MCB in HB-1 or HB-2, like both OCB breaker trip, try by
isolating concern auxiliary converter.
56. Before moving the loco (Dead/Working) ensure loco brakes and parking brakes are fully
released.
57. If CE not getting on, CE can on by pressing 126 and 218 contactors knobs in SB1 panel.
58. If MCPA not getting on, MCPA can start by pressing 48.2 contactor knob in SB2 panel.
59. If PANTO not gets raised, PANTO can raise by pressing 130.1 contactor in SB2 panel.
60. If VCB not getting close, VCB can close by pressing 136.4 contactor in SB1 panel.
61. If HEAD LIGHT not working, ensure 310.1/1 or 310.1/2, not in tripped condition.
62. If HEAD LIGHT not getting on , H/L can on by pressing 338.1 or 338.2 contactors knob
in SB1or SB2 panel respectively.
63. If CE not getting OFF, open 112.1 breaker.
64. If any trouble un able to rectified, before asking relief loco, try from rear cab, try by
changing panto, try by isolating one bogie, try by switching off CE and switch on CE if
not success then ask for relief engine.
HQ INSTRUCTIONS
C. 4.41. Loco Pilot and Assistant Loco Pilot to look back (HQRS INSTRUCTION
NO.8/2015 OF 31.03.2015)
The Loco Pilot and the Assistant Loco Pilot shall look back frequently during the journey
to see whether the train is following in a safe and proper manner.
S.R.4.41.1. At night, the Loco Pilot and the Assistant Loco Pilot shall frequently look
back on the run and verify that the side lights are burning in terms of G.R. 4.15. If the side
lights are not visible, the Loco Pilot shall call the attention of the Guard by giving two short
sharp whistles. If the train is complete and if only the side lights are not burning or not
provided, the Guard shall acknowledge by showing a green hand signal.
The Loco Pilots/Assistant Loco Pilots have to pay special attention after passing
permanent way gangs on line or a manned level crossing gate to see whether any danger
signal is being exhibited by them, warning the Loco Pilot /Assistant Loco Pilot of a danger
of an accident.
How to prevent:
➢ In case of TLTE due to Q52 permanently energized, LP has to wedge Q52 in de-
energized condition and work further. MP should not be kept in ‘+’ position for longer
period, to avoid quick progression of GR.
➢ For operating GR manually, crew has to keep MP on ‘N’ position and follow the other
conditions for operating manual operation of GR as given below.
Manual operation of GR
Whenever GR cannot be operated electrically with MP or EEC, it should be operated
manually by ZSMGR handle.
I. Hq.Instructions:19/2015 dtd:25.05.2015.
In case of HBB-2 processor failed(F.1401 P2).To avoid midsection failure
Isolate VCD,Release Parking brake manually,keep BLCP in MAN mode for CPs working.
1. If noticed during stoppage in section the concerned bogie shall be isolated by 154 and
clear the section provided load and road permits, otherwise relief loco shall be asked.
2. If crack/ break is noticed in station, the loco has to be failed and moved to shed as
LELA.
R. HQ INSTRUCTION NO.2/2016 OF 01.03.2016: Check RS Before Starting Train.
S. HQ INSTRUCTION NO.3/2016 OF 03.03.2016:
In AAL SIV locos in case of SIV tripping through fan fault MPCB(MOTOR
PROTECTION CIRCUIT BREAKER) can be reset once. If it trips again, crew shall
contact TLC.
T. HQ INSTRUCTION NO.4/2016 OF 16.03.2016:
VCD acknowledgement from ALP side is deactivated both in conventional and 3
phase locos.
U. HQ INSTRUCTION NO.5/2016 OF 04.04.2016:
BPFA has to be repeatedly pressed till BPFA lamp gets extinguished.
V. HQ INSTRUCTION NO.6/2016 OF 07.04.2016:
During short stoppage ALP shall check axle box temperature of loco by touching
axle box by hand. If the temperature of any axle box is abnormal, they should
inform to TLC.
W. HQ INSTRUCTION NO.09/2016 OF 03.10.2016:
Instructions while working with MU.
1. Try to clear section by coasting or with trailing loco, if load and road permits and
trouble shoot after clearing section.
2. If unable to clear section keep MP on O, then apply brake suitably and ask for relief
loco.
X. HQ INSTRUCTION NO.10/2016 OF 06.10.2016:
Loco pilot shall personally ensure that the coupling and hose pipe connections
between the engine and the train are properly connected up.