Professional Documents
Culture Documents
Hotel Distributionمشروع توزيع الكهرباء لفندق كامل
Hotel Distributionمشروع توزيع الكهرباء لفندق كامل
Faculty of Engineering
Elec. Power Department
(Hotel building)
Prepared by:
- Abd allah Salah Eldin Mohammed
- Abd elrahman Mohammed Abd elate
- Ahmed Nasr Fathi
- Ali Ahmed abd Eltawab
- Emry Elsayed Abdo
- Hamade Saber Mahmoued
- Mokhtar Said Ibrahim Ahmed
- Omar Mohammed Salama
Acknowledgment
Preface
Over view about our project
* Design an electrical feeding for a hotel which consists of:
12 th floor plan
Typical floor plan
Pool deck level
Mezzanine floor plan
Ground floor plan
Basement floor plan
V
BRIEF CONTENTS
Preface
APPENDIX
REFFERENCES
Chapter 1
Indoor Lighting
1.1. Introduction:
1
Chapter 1 Lighting
1.2. Illumination
From Physics we can derive models, called "illumination ", of how
light reflects from surfaces and produces what we perceive as color. In
general, light leaves some light source, illumination is the result of the
light on surfaces in which it falls thus the illumination makes the surface
look more or less bright with a certain color and this brightness and color
which the eye sees and interprets as something useful or pleasant or other
wise.
(i.e. A lamp or the sun is reflected from many surfaces and then finally
reflected to our eyes, or through an image plane of a camera).
2
Chapter 1 Lighting
1.3.3. Brightness:
The human eye does not see luminance; it sees luminance. Therefore, the
amount of light delivered into the space and the reflectance of the
surfaces in the space affects your ability to see.
3
Chapter 1 Lighting
4
Chapter 1 Lighting
Then, the appropriate type and quantity of lamps and light fixtures may
be selected based on the following:
• fixture efficiency
• lamp lumen output
• the reflectance of surrounding surfaces the effects of light losses
from lamp lumen depreciation and dirt accumulation
• room size and shape
• availability of natural light (daylight)
5
Chapter 1 Lighting
• glare
• uniformity of luminance
• color rendition
1.4.1 Glare:
• Lumen:
• Luminous Intensity:
It is the luminous flux emitted by the source per unit solid angle,
measured in the direction in which the intensity is required. It is denoted
by I and is measured in candela (cd) or lumens / steradian.
• Luminous Flux:
It is defined as the total quantity of light energy emitted per second from
a luminous body. It is denoted by symbol and measured in lumens.
It is defined as the luminous flux falling per meter square on the surface
which is every where perpendicular to the rays of light from a source of
one candle power and one meter away from it.
6
Chapter 1 Lighting
Where
7
Chapter 1 Lighting
• Utilization Factor:
• Maintenance Factor:
8
Chapter 1 Lighting
• Depreciation Factor:
This is merely the reverse of the maintenance factor and defined as the
ratio of initial meter-candles to the ultimate maintained meter-candles on
the working plane. Its value is more than unity.
• Ceiling ratio:
For indirect lighting, the average luminance of all surfaces forming the
ceiling cavity should be not more than 500 cd/m2 however small areas of
luminance up to 1500 cd/m2 will generally be acceptable, provided sharp
changes from low to high luminance are avoided.
• Walls:
9
Chapter 1 Lighting
surface of the sphere each square mm of the surface will receive the same
amount of light if the sphere be replaced by one of the larger radius, the
same total amount of light is spread over a larger area proportional to the
square of the radius.
E2 = I / (R2^2)
E = I*(dw/da)
AND dw = da COS ө/ r^2
11
Chapter 1 Lighting
This expresses both the inverse square and cosine laws of illumination
from a point source.
12
Chapter 1 Lighting
13
Chapter 1 Lighting
Ball room
14
Chapter 1 Lighting
Looby
15
Chapter 1 Lighting
Storage
Service bar
16
Chapter 1 Lighting
Retail
General cashier
17
Chapter 1 Lighting
Bank
Coorridoor
18
Chapter 1 Lighting
Night club
Manager office
19
Chapter 1 Lighting
Work station
20
Chapter 1 Lighting
Toilet
Security disc
21
Chapter 1 Lighting
Receiving office
Human resources
22
Chapter 1 Lighting
Pump room
23
Chapter 1 Lighting
Telephone
24
Chapter 1 Lighting
Meeting
25
Chapter 1 Lighting
Electric room
26
Chapter 2 Sockets
Chapter 2
Sockets
2.1 Introduction
There are many types of sockets which used in distribution system but in
our project we show the sockets which be used in commercial building
and the floor boxes used in the administrative building.
Is used for light load only ( each socket is 180VA ). Its ratings are 2A,
3A, 5A and 10A. Rating (3A) and (5A) can be used for bedrooms,
entrance and balcony which needs low electrical power appliances such
as T.V, Radio and small electrical fans.
27
Chapter 2 Sockets
28
Chapter 3 Cables
Chapter 3
Cables
3.1. Introduction:
This chapter explaining the design of feeders for lighting circuits and socket
branch circuits by determine the current that can carry the diameters of
cables "feeder" and connections between it and also between distribution
boards.
29
Chapter 3 Cables
3.3.1. Conductor:
In plain soft annealed copper, cables are supplied either with class 2 of
compacted circular or circular stranded conductors or aluminum conductors
Copper is about 1.7 times more conductive than aluminum, so smaller
diameters will result with copper although the conductor will be heaver.
Conductors are sized to adequately carry the required current at the rated
temperature of operation (temperature is influenced by the heat transfer
properties of the materials and conditions in which they are installed.). The
cable manufacturer can assist in sizing.
30
Chapter 3 Cables
with a dielectric constant of about 10. All are compatible with, and firmly
bond to, the insulation.
Modern ethylene copolymers allow for compounding of exceptionally
smooth materials on continuous compounding machines and transport in
completely enclosed handling systems in pellet form.
3.4. Insulation
1-Conductors
2-Insulation
3-screening
4-armoring
32
Chapter 3 Cables
33
Chapter 3 Cables
One very important aspect of the insulation shield is its degree of “strip-
ability”. The insulation shield must be easily removable in order to be
terminated and spliced. In most cables, the insulation shield is co-extruded
with the insulation and cross linked to its surface. Most insulation shields are
based on ethylene vinyl acetate (EVA) copolymers that have a high enough
polarity that even though cross-linked to the insulation, do not mix with and
bond permanently to it. Note: EVA can generate acetic acid, noticeable by a
strong vinegar odor, if overheated during cure. Acid scavengers are added to
neutralize small amounts of acid if generated. Computer programs are used
to predict and control the surface temperature of the cable during
manufacture.
The insulation shield, like the conductor shield, is required in medium- and
high- voltage cables rated 2kV and above. The insulation shield provides for
a smooth, radial electric field within the insulation. Industry specifications
require a resistively of below 500 ohmmeters to adequately carry current to
the metallic shield. Most commercial materials are below 100 ohm-meters.
One very important aspect of the insulation shield is its degree of “strip-
ability”. The insulation shield must be easily removable in order to be
terminated and spliced. In most cables, the insulation shield is co-extruded
with the insulation and crosslinked to its surface. Most insulation shields are
based on ethylene vinyl acetate (EVA) copolymers that have a high enough
polarity that even though cross-linked to the insulation, do not mix with and
bond permanently to it. Note: EVA can generate acetic acid, noticeable by a
strong vinegar odor, if overheated during cure.
34
Chapter 3 Cables
An extruded black PVC (class ST2) outer sheath is provided to all cables.
Jackets are available in a number of different compounds for specific
requirements. Jacket types include polyvinyl chloride (PVC), polyethylene
(LLDPE, MDPE, and HDPE), Polypropylene (PP), Neoprene, Hyperion®,
and thermoplastic chlorinated polyethylene (CPE). For certain applications,
a lead sheath and interlocking or corrugated armors are available for
multiconductor cables. Jackets may offer properties, such as sunlight, flame,
and chemical and abuse resistance. Jacket selection depends on where and
how a cable will be used and the exposure conditions, both during
installation and while in service.
35
Chapter 3 Cables
1. Conductor
2. Conductors
3. Insulation
4. Insulation Screen (Nonmetallic)
5. Insulation Screen (Metallic)
6. Outer Sheaths
1. Conductor
2. Conductor Screen
3. Insulation
36
Chapter 3 Cables
By covering the route of the laid cables with durable and resistant materials,
the cables will be protected from tools if there should be excavations. Due to
the increasingly extensive networks and excavations, it is important to keep
complete and accurate marking of the cable route. If this method cannot be
used, then all dimension figures of the markers should be indicated on the
site drawing.
Cable jointing must be carried out by a skilled staff with maximum care,
using the appropriate material.
37
Chapter 3 Cables
Where more than one circuit or cable run together in conduit, trucking, or on
the surface the mutual heating between them reduces their current carrying
capacities. For most arrangements of cables in general use factors are issued
with the rating tables where by the maximum current carrying capacity of
cables in groups can be calculated. Because they have to deal With the
subject in a general way, these factors must be derived on the assumption
that all the cables in a group are of the same size and are equally loaded.
This situation does not often arise in practice, but it is usually assumed that
the application of such factors to a practical group of mixed sized of cables
38
Chapter 3 Cables
would be on the safe side. In fact, this is not true. The application of usual
group factors across the board to a group of cables of different sizes can
result in the smaller cables being overheated and the larger cables being
under utilized. Extensive work on this matter has resulted in the issue of
several new ERA reports which provide ratings for cables in groups of
mixed sizes carrying different loads. It is obvious that, because the ratings
for cables in such groups are specific to the cable and load content of each
group, rating under these circumstances and, dependent on the size of group
and the loading of the other cables, its permissible load may be even greater
than that for the cable in isolation. The method of conductor size selection
given in the ERA reports provides for the adjustment of individual sizes
(subject to other constraints such as voltage drop) so that the most
economical mix of sizes can be selected. A point worth making here is that,
a wiring cable which is continuously loaded to even 10% more than its
maximum permissible value has its expectation of life reduced by about
50%.
Where a large number of simultaneously loaded cables must be
accommodated it can be preferable to split them into several small groups so
as to avoid the economic penalties of the low ratings required for large
groups.
39
Chapter 3 Cables
40
Chapter 3 Cables
For socket:-
Basement
41
Chapter 4 Protection
System
Chapter 4
Protection System
4.1. Introduction
65
Chapter 4 Protection
System
66
Chapter 4 Protection
System
any pole trips, a "common trip" breaker must be used. These may either
contain two or three tripping mechanisms within one case, or for small
breakers, may externally tie the poles together via their operating handles.
67
Chapter 4 Protection
System
68
Chapter 4 Protection
System
4.7. Characteristics
The circuit breaker has special functioning characteristics. It is normally
either close or open for long periods of time, is asked to change state on
occasion and rarely sees short circuit current.
4.7.1. Reliability:
It needs to change state efficiently after long periods of inactivity.
The circuit breaker control must ensure correct closing action, whatever
the closing current value, and ensure breaking (opening) at the required
moment by releasing, by mechanical action or via a relay, the energy
stored in the accumulators.
This energy has to face opposing forces when closing or breaking
circuits under load or not, and even stronger forces with short circuit
currents.
This means an excess of energy, when operated without load, has to be
damped with a proper damping system.
69
Chapter 4 Protection
System
4.8 . Types
Acoording to isolating material
70
Chapter 5 Mechanical
Loads
Chapter 5
5.1. Dryer description
71
Chapter 5 Mechanical
Loads
Chillers are, for the most part, a device designed to cool another product
or application through the use of a fluid medium.
72
Chapter 5 Mechanical
Loads
This mist refrigerant then enters the heat exchanger and the whole
process is repeated.
5.3. Elevators
The concept of an elevator is simple it is just a compartment attached
to a lifting system. By tying apiece of rope to a box and this is a basic
elevator.
Modern passenger and freight elevators are a lot more elaborate than
this. They need advanced mechanical systems to handle the substantial
weight of the elevator car and its cargo. Additionally, they need control
mechanisms so passengers can operate the elevator, and they need safety
devices to keep everything running smoothly.
There are two major elevator designs in common use today: hydraulic
elevators and roped elevators.
73
Chapter 5 Mechanical
Loads
The pump forces fluid from the tank into a pipe leading to the
cylinder. When the valve is opened, the pressurized fluid will take the
path of least resistance and return to the fluid reservoir. But when the
74
Chapter 5 Mechanical
Loads
valve is closed, the pressurized fluid has nowhere to go except into the
cylinder. As the fluid collects in the cylinder, it pushes the piston up,
lifting the elevator car.
When the car approaches the correct floor, the control system sends a
signal to the electric motor to gradually shut off the pump. With the pump
off, there is no more fluid flowing into the cylinder, but the fluid that is
already in the cylinder cannot escape (it can't flow backward through the
pump, and the valve is still closed). The piston rests on the fluid, and the
car stays where it is.
To lower the car, the elevator control system sends a signal to the
valve. The valve is operated electrically by a basic solenoid switch. When
the solenoid opens the valve, the fluid that has collected in the cylinder
can flow out into the fluid reservoir. The weight of the car and the cargo
pushes down on the piston, which drives the fluid into the reservoir. The
car gradually descends. To stop the car at a lower floor, the control
system closes the valve again.
75
Chapter 5 Mechanical
Loads
The problem is that the entire cylinder structure must be buried below
the bottom elevator stop. This means you have to dig deeper as you build
higher. This is an expensive project with buildings over a few stories tall.
To install a hydraulic elevator in a 10-store building, for example, you
would need to dig at least nine stories deep.
The roped elevator design gets around both of these problems, the
most popular design is the roped elevator, in the roped elevator the car is
raised and lowered by traction steel ropes rather than pushed from below.
The ropes are attached to the elevator car, and looped around a sheave
(3). A sheave is just a pulley with a grooves around the circumference.
76
Chapter 5 Mechanical
Loads
The sheave grips the hoist ropes, so when you rotate the sheave, the
ropes move too.
The sheave is connected to an electric motor (2). When the motor turns
one way, the sheave raises the elevator; when the motor turns the other
way, the sheave lowers the elevator. In gearless elevators, the motor
rotates the sheaves directly. In geared elevators, the motor turns a gear
train that rotates the sheave. Typically, the sheave, the motor and the
control system (1) are all housed in a machine room above the elevator
shaft.
The ropes that lift the car are also connected to a counterweight (4),
which hangs on the other side of the sheave. The counterweight weighs
about the same as the car filled to 40-percent capacity. In other words,
77
Chapter 5 Mechanical
Loads
when the car is 40 percent full (an average amount), the counterweight
and the car are perfectly balanced.
Both the elevator car and the counterweight ride on guide rails (5)
along the sides of the elevator shaft. The rails keep the car and
counterweight from swaying back and forth, and they also work with the
safety system to stop the car in an emergency.
The first line of defense is the rope system itself. Each elevator rope is
made from several lengths of steel material wound around one another.
With this sturdy structure, one rope can support the weight of the elevator
car and the counterweight on its own. But elevators are built with
78
Chapter 5 Mechanical
Loads
multiple ropes (between four and eight, typically). In the unlikely event
that one of the ropes snaps, the rest will hold the elevator up.
if all of the ropes were to break, or the sheave system were to release
them, it is unlikely that an elevator car would fall to the bottom of the
shaft. Roped elevator cars have built-in braking systems, or safeties, that
grab onto the rail when the car moves too fast. .
Safeties are activated by a governor when the elevator moves too quickly.
Most governor systems are built around a sheave positioned at the top of
the elevator shaft. The governor rope is looped around the governor
sheave and another weighted sheave at the bottom of the shaft. The rope
is also connected to the elevator car, so it moves when the car goes up or
down. As the car speeds up, so does the governor. The diagram below
shows one representative governor design.
79
Chapter 5 Mechanical
Loads
The governor ropes are connected to the elevator car via a movable
actuator arm attached to a lever linkage. When the governor ropes can
move freely, the arm stays in the same position relative to the elevator car
(it is held in place by tension springs). But when the governor sheave
locks itself, the governor ropes jerk the actuator arm up. This moves the
lever linkage, which operates the brakes, or safeties.
80
Chapter 5 Mechanical
Loads
Elevators also have electromagnetic brakes that engage when the car
comes to a stop. The electromagnets actually keep the brakes in the open
position, instead of closing them. With this design, the brakes will
automatically clamp shut if the elevator loses power.
81
Chapter 5 Mechanical
Loads
Elevators also have automatic braking systems near the top and the
bottom of the elevator shaft. If the elevator car moves to far in either
direction, the brake brings it to a stop.
If all else fails, and the elevator does fall down the shaft, there is one
final safety measure that will probably save the passengers. The bottom
of the shaft has a heavy-duty shock absorber system -- typically a piston
mounted in an oil-filled cylinder. The shock absorber works like a giant
cushion to soften the elevator car's landing.
5.5. Doors
The automatic doors at grocery stores and office buildings are mainly
there for convenience and as an aid for handicapped people. The
automatic doors in an elevator, on the other hand, are absolutely essential.
They are there to keep people from falling down an open shaft.
Elevators use two different sets of doors: doors on the cars and doors
opening into the elevator shaft. The doors on the cars are operated by an
electric motor, which is hooked up to the elevator computer.
82
Chapter 5 Mechanical
Loads
The electric motor turns a wheel, which is attached to a long metal arm.
The metal arm is linked to another arm, which is attached to the door. The
door can slide back and forth on a metal rail.
When the motor turns the wheel, it rotates the first metal arm, which
pulls the second metal arm and the attached door to the left. The door is
made of two panels that close in on each other when the door opens and
extend out when the door closes. The computer turns the motor to open
the doors when the car arrives at a floor and close the doors before the car
starts moving again. Many elevators have a motion sensor system that
keeps the doors from closing if somebody is between them.
The car doors have a clutch mechanism that unlocks the outer doors at
each floor and pulls them open. In this way, the outer doors will only
open if there is a car at that floor (or if they are forced open). This keeps
the outer doors from opening up into an empty elevator shaft.
The Egyptian Model VF range is designed for low and medium rise
buildings. It has speeds of up to 1.6 m/s and duties of up to 13 persons
accommodating different building arrangements and usage.
83
Chapter 5 Mechanical
Loads
Comfort air conditioning makes deep plan buildings feasible. Without air
conditioning, buildings must be built narrower or with light wells so that
inner spaces receive sufficient outdoor air via natural ventilation. Air
conditioning also allows buildings to be taller since wind speed increases
significantly with altitude making natural ventilation impractical for very
tall buildings. Comfort applications for various building types are quite
different and may be categorized as
85
Chapter 5 Mechanical
Loads
In both comfort and process applications the objective may be to not only
control temperature, but also humidity, air quality, air motion, and air
movement from space to space
87
Chapter 6 Emergency
Chapter 6
Emergency Systems
6.1. Introduction
88
Chapter 6 Emergency
6.2.2 Objectives:
89
Chapter 6 Emergency
6.3.2. Maintained:
The lamps are energized during normal main supply. In the event of
the mains failure, the same lamps remains illuminated by automatically
switched to integral battery source.
6.3.3. Sustained:
Where at least two or more lamps are energized during normal main
supply and in the event of main power failure, one of the lamps remains
illuminated by automatically getting switched to integral battery source.
90
Chapter 6 Emergency
6.5.1. Method 1:
6.5.1.1. Construction:
91
Chapter 6 Emergency
92
Chapter 6 Emergency
6.5.2. Method 2
6.5.2.1. Automatic Transfer Switches:
93
Chapter 6 Emergency
. Power transfer switch rated with 3 poles, 800
Amps with pole covers and arc barriers removed
This equipment has been wired and tested at the factory. Installing the
switch includes the following procedures:
94
Chapter 6 Emergency
95
Chapter 6 Emergency
96
Chapter 6 Emergency
97
Chapter 6 Emergency
98
Chapter 6 Emergency
99
Chapter 6 Emergency
The main differences between the gasoline generator engine and the
diesel generator engine are:
The diesel generator engine has no spark plug, that it intakes air and
compresses it, and that it then injects the fuel directly into the combustion
chamber (direct injection). It is the heat of the compressed air that lights
the fuel in a diesel engine.
100
Chapter 6 Emergency
compresses it and then injects fuel into the compressed air. The heat of
the compressed air lights the fuel spontaneously.
Gasoline engines generally use either carburetion, in which the air and
fuel is mixed long before the air enters the cylinder, or port fuel injection,
in which the fuel is injected just prior to the intake stroke (outside the
cylinder). Diesel engines use direct fuel injection -- the diesel fuel is
injected directly into the cylinder.
Diesel generator
101
Chapter 6 Emergency
over the engine by the fan is pushed through the radiator. This action
provides surface cooling for the engine together with cooling of the
engine coolant in the radiator. Radiator and fan cooling is independent of
potentially interruptible utility supplied cooling water. In addition,
coolant can be treated rust inhibitors, anti-freeze.
102
Chapter 6 Emergency
103
Chapter 6 Emergency
104
Chapter 6 Emergency
105
Chapter 6 Emergency
This is a figure shows how does the generator link between the board
panels and its link with the emergency loads.
106
Chapter 6 Emergency
Some of the emergency loads the power should not be cut off from it
for 1 second like surgery rooms and childbirth room and computers these
sensitive places the power can't be cut off from it so this need to use the
Uninterruptible power supply which is a battery that is fed from the main
source supply during normal operation when this main supply fails this
(UPS) begin these emergency loads until the standby generator start
feeding all the emergency loads.
107
Chapter 6 Emergency
6.16.1 Switching:
The utility and generator breakers are metal enclosed free standing,
manually operated, air power circuit breakers. The breakers have
instantaneous, short time, and long time trip settings with manual control
and position indication on the door of the breaker compartment. The
480V transfer switch is metal enclosed, break before make, dead bus
transfer, automatic on loss of voltage, solenoid operated, and
mechanically held complete with microprocessor controls and indication,
four pole switch. Transfer time and time delay settings are adjustable.
The transfer switch will supply start and stop signals to the back-up diesel
generator upon loss of and restoration of utility power. These controls are
timed and must be coordinated with the diesel generator manufacturer for
start-up, loading, and cool down times. Remote indication, control, alarm
108
Chapter 6 Emergency
The UPS is a static solid state system with a battery for back-up power.
The rectifiers convert ac to do power for supply to the redundant inverters
and for charging the battery. The inverters receive power from either the
rectifier or battery, and convert it from do to ac. The inverters also
include power conditioning equipment and circuits to remove harmonics
developed in the system.
Because the input power is converted from ac to do to ac, power
system disturbances are also removed from the UPS output. This makes
UPS s ideal for use with sensitive electronic equipment and computers.
The rectifiers and inverters are constructed with power diodes or silicon
control rectifiers along with controls and filtering circuitry. The UPS also
contains thermal magnetic molded case circuit breakers and two bump
less static switches. The switches will transfer the output of the UPS from
one redundant inverter to the other upon failure of the lead inverter . The
transfer between the inverters is accomplished with absolutely no loss of
109
Chapter 6 Emergency
Utility breaker closed, diesel generator not running but in auto mode,
diesel generator breaker closed, transfer switch connected to utility,
inverter A connected through UPS static switch to UPS bus and UPS
switchboard connected to the UPS.
110
Chapter 6 Emergency
• Initial energization:
Verify UPS incoming breaker open. Verify utility feed closed through
to input of UPS and measure voltage and phasing. Verify rectifier/battery
charger output A breaker open. Verify rectifier/battery charger output B
breaker open. Verify battery breaker A open and measure battery voltage
and polarity. Verify battery breaker B open and measure battery voltage
and polarity. Verify inverter A and inverter B incoming breakers open.
Close UPS incoming breaker A and measure rectifier/battery charger A
111
Chapter 6 Emergency
output voltage, check dc output meter. Press battery "pre charge" button,
if available, and close rectifier/battery charger A output breaker and close
battery breaker A. Measure battery charger voltage. Allow unit to run
until battery fully charged or for a minimum of 24 hours. Record time.
Measure rectifier/battery charger A output current and read meter every 4
hours. Open UPS incoming breaker A. Operate UPS from battery until
minimum voltage recorded (1 to 4 hours). Open battery breaker A. Close
UPS incoming breaker B and measure rectifier/battery charger B output
voltage, check do output meter. Press battery "pre charge" button, if
available, and close rectifier/battery charger B output breaker and close
battery breaker B. Measure battery charger voltage. Allow unit to run
until battery fully charged or for a minimum of 24 hours. Record time.
Measure rectifier/battery charger B output current and read meter every 4
hours.
112
Chapter 7 Earthing
Chapter 7
Earthing
7.1. Introduction:
Many electrical operated devices (e.g. washing machines, heaters and some
lighting fittings) have exposed metal parts that could become live if a fault
occurred. Anyone touching it could then receive a shock or even be killed
depending on the current flowing through them to earth. To prevent this, an
earthing conductor should be provided to all socket outlets, lighting circuits
and any fixed appliances to which exposed metal parts are then connected.in
the small town project we take earthing to power sockets
For safety of equipment and personnel against lightning and voltage surges
113
Chapter 7 Earthing
7.2.1. Requirements:
Some elements of an earthling system may be provided to fulfill a specific
purpose, but are nevertheless part of one single earthing system. Standards
require all earthing measures within an installation to be bonded together,
forming one system.
7.2.2. Step voltage:
The difference in surface potential experienced by a person bridging a
Distance of one meter with the feet without contacting any other grounded
object.
7.2.3. Touch voltage:
The difference in potential between a grounded structure or station And the
surface potential at the point where a person is standing while at the same
Time having a hand in contact with the grounded structure or object.
7.2.4. Transferred touch voltage:
A special case of touch voltage where a voltage is conducted toward or away
room a grounded structure or station to a remote point. A transferred touch
voltage (potential) can be contacted between the hands or hands and feet.
7.2.5. Mesh voltage:
is the worst possible value of a touch voltage to be found within a mesh of a
ground grid, if standing at or near the center of the mesh.
Fault circuit impedance X/R ratio: Ratio of reactance to resistance of the
electrical impedance of a faulted (short) circuit from the source of fault
current to the location of the fault on the circuit.
114
Chapter 7 Earthing
Fig[1]Step touch voltage created at earth surface by current flowing into ground
from grounded object
115
Chapter 7 Earthing
Table 1 Ground resistivity for various kinds of the soil and concrete
116
Chapter 7 Earthing
Ground Symbol
117
Chapter 7 Earthing
118
Chapter 7 Earthing
If the earthing resistance is of low value the fault currents are high and the
system conditions approach to solid earthing. On the other hand if the
earthing resistance is of higher value then the system conditions approach
that of the insulated neutral system with corresponding risk of transient over-
voltages occurring.
It is usual practice to employ earth resistance of low values having
ohmic values such that when earth fault occurs on one phase of the system at
the power source, a current equal to full load current of the largest generator
or transformer feeding system, flows in the associated earth connections.
The earthing of a system neutral point through a low value resistance
allows the use of discriminating protective gear and at the same time limits
the earth fault current to a value that will cause no serious disturbance to the
system and minimize the extent of damage at the fault location.
The disadvantages of resistance earthing are:
1. Since the system neutral is displaced during earth faults, the
equipment has to be selected for higher voltages.
120
Chapter 7 Earthing
121
Chapter 7 Earthing
• When two different types of metal such as copper and iron are held in
contact with each other, a galvanizing action takes place between
them resulting in the corrosion of the anode metal. This is a problem
commonly encountered when placing grounding electrodes of
copper wire or copper plate. It can be solved by completely covering
the electrode with SAN-EARTH to prevent corrosion.
122
Chapter 7 Earthing
123
Chapter 7 Earthing
124
Chapter 7 Earthing
125
Chapter 7 Earthing
Table 1 Ground resistivity for various kinds of the soil and concrete
126
Chapter 7 Earthing
Generally, as explained earlier, soil is found in layers and the resistivity will
carry from layer to layer. By changing the spacing of the electrodes, it is
possible to develop a profile of the soil resistivity at various depths
127
Chapter 7 Earthing
128
Chapter 7 Earthing
table2
• Temperature: the resistivity of the soil is also influenced by
temperature. Table [3] shows the variation of the resistivity of sandy
loam, containing 15.2% moisture e, with temperature changes from
20° to -15°C. In this temperature range the resistivity is seen to vary
from 7200 to 330,000 ohm-centimeters.
Table [3]
Because soil resistivity directly relates to moisture content and temperature,
it is reasonable to assume that the resistance of any grounding system will
vary throughout the different seasons of the year. Since both temperature
and moisture content become more stable at greater distances below the
129
Chapter 7 Earthing
Table [4]
130
Chapter 7 Earthing
The method of earthing can normally be found out by tracing the wiring
from the meter/consumer unit. It is usually fairly obvious. IMPORTANT! -
It is no longer permitted to use a water or gas pipe for the main or only
earthing connection. There may, however be earth bonding wires connected
onto the water and gas pipes for 'equipotential bonding' .If there is no
131
Chapter 7 Earthing
Conductors
Furse offer three types of conductor: Flat tape Solid circular and
stranded cable.
A range of conductor materials are available. Above ground, copper,
aluminum and steel may be used. Below ground, copper is the most common
choice due to its high resistance to corrosion.
132
Chapter 7 Earthing
133
Chapter 7 Earthing
Fittings
134
Chapter 7 Earthing
Fittings
BS 7430, BS 6651
135
Chapter 7 Earthing
136
Chapter 7 Earthing
Fittings
137
Chapter 7 Earthing
The equation for earth resistance for various systems of electrodes is quite
complicated, and in some cases may be expressed only as an approximation.
R = r * L/ A
Where:
R= Uniform earth resistance (Ω).
A = X-section area of the electrode (m2).
ρ = Resistivity of soil (Ω.m).
L= Length of the electrode (m).
For Single driven rod:
R = (r /2*pi*L)*[ln(3*L/d)]
Where:
L=length of the electrode (m).
d= diameter of the electrode (m).
For Multiple driven rods:
R [of N rods in parallel]/R [of one rod] = [1+K * X] /N
Where;
N= number of parallel rods
K= Screen Coefficient
X = L * D/ ln (3*L/d)
Where: D= Distance between parallel rods (m).
7.19.2. Factor Affecting Earth Resistance:
* Effect of rod size: It's an important factor that affects 7.18.2.2.
the resistance of the soil which usually decreases as the depth
increases.
138
Chapter 7 Earthing
This table shows the variation of screen coefficient due to number of rods
Z N K
2 4 2.707
3 8 4.25
4 12 5.4
5 16 6
6 20 6.46
7 24 6.83
8 28 7.15
9 32 7.41
10 36 7.61
Where;
Z= Number of rods inside of a hollow square.
WE defined the sutible earth resistance to be( 5 Ohm ) ,Which is the total
resistance of the small town
139
Chapter 7 Earthing
ρ 3* L
RE = Rrod = Ln
2 *π * L d
• L=3m
• D=3Cm
100 3*3
RE = Rrod = Ln
• 2 * π * 3 0.025 =31.23 Ohm
140
Chapter 7 Earthing
141
Chapter 8 Fire
alarm
Chapter 8
Fire Alarm system
8.1. Introduction:
Fire alarm systems are normally required by building codes. In the
case of new buildings, this is usually accomplished through the adoption
of building regulations. In existing buildings, fire alarm systems may be
required by municipal or provincial fire code provisions or by special
provincial acts or municipal bylaws directed at specific classes of
buildings.
Fire alarm systems are often associated only with pull boxes and
alarm bells. However, they are usually much more complex. They may
include numerous components such as fire detectors, annunciated panels,
loudspeakers, telephones, control panels and pull boxes. In addition to the
alarm function, fire alarm and detection systems can also actuate other
fire safety measures in a building.
Firing alarm system implies, sounds and alarm in the event of fire
there can be one or several alarms through out a building and there can be
142
Chapter 8 Fire
alarm
several points which activate the warning. The alarm points can be
operated manually or automatically; in the latter they may be sensitive to
heat, smoke or ionization. There are clearly many combinations possible
and we shall try to give some systematic account of the way the way they
are built up.
8.2 Functions
The primary function of a fire alarm is to alert the occupants of a
building to the presence of a fire. It may also perform other functions. For
instance, the system can be designed to simultaneously alert the fire
department by means of a direct or relayed signal where a rapid response
by the fire department is essential. This is particularly important in certain
industrial occupancies containing large quantities of highly combustible
or explosive materials where a fire can develop rapidly, and in high
buildings, hospitals and nursing homes where evacuation assistance may
be required. In other cases, because of the nature of the building
occupancy, the alarm system may be designed to alert initially only the
building staff before the general alarm is activated.
143
Chapter 8 Fire
alarm
8.3 Components
A typical fire alarm system consists of a control unit, manually
activated signaling boxes (pull boxes), fire detectors and audible alarm
devices. There may also be visual signal devices to warn the hearing-
impaired, annunciators to indicate the origin of the alarm signal, and
emergency telephones and other equipment for communication between
the central control panel and other parts of the building.
The control unit powers the fire alarm system. It transmits signals
from pull boxes (Figure 2) and fire detectors to the alarm signal devices,
either audible or visual, installed at strategic locations in the building.
Audible signal devices include bells, speakers, and sirens, a strobe light
being a common visual signal device.
144
Chapter 8 Fire
alarm
The two basic types of fire detectors are smoke detectors and heat
detectors. A smoke detector transmits a signal to the control unit when
the concentration of airborne combustion products reaches a
predetermined level. A heat detector transmits a similar signal when the
temperature reaches a predetermined level or when there is an abnormal
rate of temperature rise.
There are two principal types of smoke detectors: photoelectric and
ionization. Photoelectric detectors react to visible particles of smoke.
Ionization smoke detectors, on the other hand. Are sensitive to the
presence of ions, which are electrically charged particles produced by the
chemical reactions that take place during combustion.
Both ionization and photoelectric detectors are effective. Which one
is better in a given situation depends on the nature of the fire. Hot gases
with few smoke particles are more readily detected by ionization smoke
detectors, while photoelectric detectors are more sensitive to cooler
smoke with large smoke particles.
These smoke detectors should not be confused with the self-
contained devices commonly used in apartment suites and houses that are
145
Chapter 8 Fire
alarm
146
Chapter 8 Fire
alarm
A typical annunciator panel with indicators for each zone of the building
The fire zone can also be determined if the alarm system incorporates
a "coded" audible signal in which a different signal is used for each zone.
The advantage of this method is that staff can immediately identify the
fire zone and go directly there to investigate. Ho time is wasted going to
the annunciator panel. In large buildings with many zones, a coded
audible signal system may be unworkable. In other buildings, however,
both an annunciator and coded alarm signal can be used.
147
Chapter 8 Fire
alarm
148
Chapter 8 Fire
alarm
8.5. Design
A fire alarm system should be designed to provide early detection and
warning of a fire. The designer must consider the size, complexity and
use of the building, and the degree of detection and warning desired.
While the design of fire alarm systems is normally regulated by building
codes, the level of protection specified is usually a minimum and the
designer should consider providing higher levels of protection where
circumstances indicate the need.
149
Chapter 8 Fire
alarm
150
Chapter 8 Fire
alarm
areas where the main risk is smoldering fires and, in areas where optical
detectors are deemed unsuitable due to the risk of false alarms.
• Operating Principles
Carbon-based materials in the smoldering stage of a fire can produce
significant levels of carbon monoxide.
Carbon Monoxide detectors contain an electrochemical cell that senses
carbon monoxide and will therefore give an early Warning of fire.
Supplement to Standard Detection Devices Carbon monoxide
detectors do not detect smoke or any other combustion products and are
not universal replacements for smoke detectors.
• Resistance to False Alarms
Carbon monoxide detectors are less susceptible than smoke detectors
to false alarms from sources such as toast, steam, cooking, plumbing
work and hair spray.
• Application
Typical applications include hotel bedrooms, halls of residence,
Sheltered accommodation and hospital wards
• Limitations
Carbon monoxide detectors are set to a higher sensitivity than the
maximum allowed by the domestic carbon monoxide alarm standard.
They will respond to carbon monoxide from faulty gas appliances or
vehicle exhausts. CO detectors give a poor response to life
151
Chapter 8 Fire
alarm
152
Chapter 8 Fire
alarm
• Failsafe Operation
In the event of a mains failure, back-up batteries housed in the Zone
master cabinet will continue to power the system.
• Automatic & Manual Release
Automatic or manual control may be selected, giving the user complete
discretion over the use of the extinguishing.
153
Chapter 8 Fire
alarm
154
Chapter 8 Fire
alarm
Control master 300b range of advanced fire panels utilize the latest in
analogue addressable fire alarm technology to provide a flexible and
expandable detection system which is ideal for medium to large
commercial and industrial premises. Networked Control master systems
may be linked to a PC graphic
Control master provides the most sophisticated monitoring of a work
environment, and the most comprehensive protection against serious fire
damage and life threatening hazards, which can develop from an outbreak
of fire. Benefits of the range of Panels include:
• Monitored detection
Intelligent detectors monitor smoke and temperature variance
Throughout a site for smoke build-up and significant heat increase
• Location reports
Control master provides precise location reports of any situation
Requiring immediate investigation (reducing search time around
The premises)
155
Chapter 8 Fire
alarm
• Alarm activation
Alarms are raised at appropriate locations for staged site evacuations,
to ensure the safe exit of all personnel. Necessary safety measures are
also set in motion (voice alarm system announcements, lift control, gas
valves shut down, fire doors closed and any other appropriate measures).
• Fully expandable
The Control master system expands easily to fully networked
applications in large and complex sites, with cost effective installation
and minimum disruption.
• Flexible control
Control master can be linked directly to the emergency services
during periods when the building is unoccupied, ensuring rapid response
to a fire condition.
• Solid construction
The Control master electronics are enclosed in a high quality steel
enclosure with preformed knockouts to aid in installation. The control
panel housing can be either surface or flush mounted.
• False alarm management
To minimize false alarms the sensitivity of individual loop detectors can
be adjusted to suit the environment. Time delays can also be programmed
into the panel, which cause a warning signal to be indicated at the panel,
allowing time for investigation.
156
Chapter 8 Fire
alarm
157
Chapter 8 Fire
alarm
158
Chapter 8 Fire
alarm
159
Chapter 8 Fire
alarm
8.6.2.4. Dorgard:
Speech master
161
Chapter 8 Fire
alarm
• Alerting staff
Prior to a general Alert/Evac message being broadcast warn staff so they
are prepared to assist with the evacuation.
• Service and maintenance
A correctly designed and installed voice alarm system provides the
peace of mind that the facility exists for emergency warnings to be
conveyed clearly, calmly and concisely. Also ongoing service and
maintenance of all (including other manufacturers) voice alarm systems.
162
Chapter 8 Fire
alarm
163
Chapter 8 Fire
alarm
164
Chapter 8 Fire
alarm
• Repeatable service
The service is repeatable, allowing the room to be tested at any time,
for example, if any changes are to be made to the protected area. It is a
requirement of BS ISO 14520 that a test is performed annually if it can
not be verified that no changes have been made to the room since the
previous test.
• Does not interfere with extinguishing system
It is versatile. Neither the type of the gaseous fire fighting agent, nor
the original provider of the extinguishing system inhibits the vital service.
• Essential part of Halon system decommission
New clean agents have less tolerance for leakage than Halon systems.
Halon protected rooms could lose over50% of agent concentration before
the fire could re-ignite. The new agents are more critical and can
normally only lose about 20% before re-ignition. Therefore, what was an
adequately sealed protected area for the use of Halon, would not be
adequately sealed for the use of a new agent.
165
Chapter 8 Fire
alarm
The door fan unit is fitted into a doorway of the protected area by
means of the expandable door panels designed to fit most door frame
sizes, and measures the size of holes in the enclosure and the pressures
that may exit across them.
The fan speed is adjusted to obtain a steady pressure between the test
area and the volume surrounding the test (equivalent to the column
weight exerted by the extinguishing agent following a discharge). This
pressure is then maintained whilst readings are taken from pressure
gauges.
The measured rate of air input needed to maintain this pressure level is
equivalent to the amount leaking from the test area. A second
measurement is taken by doing the first test in reverse i.e. by depressuring
the test area. The two readings are averaged to reduce error.
The computer then converts the flow and pressure readings into an
Equivalent Leakage Area, or the total area of all the cracks, gaps and
holes in the test area. The data generated is then processed using
specifically designed computer software, in compliance with the National
Fire Protection Association (NFPA) and the British Standard ISO
14520 which predicts the period of time that the concentration will be
held in the test area at any given height.This retention time can be further
calculated for different heights.
The computer software has also been designed to be conservative
with its predictions. The software produces the worst case scenario in
which 50% of the cracks, gaps in the test area are at a low level where
heavier gas/air mixture will seep out and 50% are at a high level where
lighter air will enter to displace it. This approach makes the results
extremely reliable and means that any system which passes the room
166
Chapter 8 Fire
alarm
integrity test would have been virtually certain to pass a full discharge
test.
Within an hour of the completed tests the computer produces a
printout with full details of the input and test results, with a detailed
report following in the post shortly afterwards. Failure is indicated if it
takes less than ten minutes for the agent/air interface to drop below the
minimum specified protected height.
However, if the test area does fail to satisfy the requirements, a
detailed survey carried out making a note of the leakage areas to allow
remedial sealing works to be carried out.
167
Chapter 9 Trans.
& Gene.
Chapter 9
Transformer and Generator
Transformer
10.1. Construction Overview
A transformer is a static machine. Although it is not an energy
conversion device, it is indispensable in many energy conversion
systems. It is a simple device, having two or more electric circuits
coupled by a common magnetic circuit. Analysis of transformers involves
many principles that are basic to the understanding of electric machines.
Transformers are so widely used as electrical apparatus that they are
treated along with other electric machines in most books on electric
machines.
A transformer essentially consists of two or more windings coupled
by a mutual magnetic field. Ferromagnetic cores are used to provide tight
magnetic coupling and high flux densities. Such transformers are known
as iron core transformers. They are invariably used in high-power
168
Chapter 9 Trans.
& Gene.
applications. Air core transformers have poor magnetic coupling and are
sometimes used in low-power electronic circuits.
Two types of core constructions are normally used, as shown in the
following figure. In the core type (Fig. a), the windings are wound around
two legs of a magnetic core of rectangular shape. In the shell type (Fig.
b), the windings are wound around the center leg of a three-legged
magnetic core. To reduce core losses, the magnetic core is formed of a
stack of thin laminations. Silicon-steel laminations of 0.014 inch
thickness are commonly used for transformers operating at frequencies
below a few hundred cycles. L-shaped laminations are used for core-type
construction and E-shaped laminations are used for shell-type
construction. To avoid a continuous air gap (which would require a large
exciting current), laminations are stacked alternately.
169
Chapter 9 Trans.
& Gene.
secondary winding. The winding with the higher number of turns will
have a high voltage and is called the high-voltage (HV) or high-tension
(ITT) winding. The winding with the lower number of turns is called the
low-voltage (LV) or low-tension (LT) winding. To achieve tighter
magnetic coupling between the windings, they may be formed of coils
placed one on top of another (Fig. a) or side by side (Fig. b) in a
“pancake” coil formation where primary and secondary coils are
interleaved. Where the coils are placed one on top of another, the low-
voltage winding is placed nearer the core and the high-voltage winding
on top.
Transformers have widespread use. Their primary function is to
change voltage level. Electrical power is generated in a power house at
about 30,000 volts. However, in domestic houses, electric power is used at
110 or 220 volts. Electric power is transmitted from a power plant to a load
center at 200,000 to 500,000 volts. Transformers are used to step up and
step down voltage at various stages of power transmission, as shown in the
following figure.
170
Chapter 9 Trans.
& Gene.
Transformers are also used to measure voltages and currents; these are
known as instrument transformers.
171
Chapter 9 Trans.
& Gene.
172
Chapter 9 Trans.
& Gene.
Generator
10.4. Construction Overview
A synchronous machine rotates at a constant speed in the steady
state. Unlike induction machines, the rotating air gap field and the rotor in
the synchronous machine rotate at the same speed, called the synchronous
speed. Synchronous machines are used primarily as generators of
electrical power. In this case they are called synchronous generators or
alternators. They are usually large machines generating electrical power
at hydro, nuclear, or thermal power stations. Synchronous generators with
173
Chapter 9 Trans.
& Gene.
174
Chapter 9 Trans.
& Gene.
drawn from the ac source to aid magnetization by the rotor field current
and the machine will operate at a lagging power factor.
If the rotor field current is increased, leading reactive current will
be drawn from the ac source to oppose magnetization by the rotor field
current and the machine will operate at a leading power factor. Thus, by
changing the field current, the power factor of the synchronous motor can
be controlled.
If the motor is not loaded but is simply floating on the ac supply
system, it will thus behave as a variable inductor or capacitor as its rotor
field current is changed. A synchronous machine with no load is called a
synchronous condenser. It may be used in power transmission systems to
regulate line voltage. In industry, synchronous motors are sometimes
used with other induction motors and operated in an overexcited mode so
that they draw leading current to compensate the lagging current drawn
by the induction motors, thereby improving the overall plant power
factor.
175
Chapter 9 Trans.
& Gene.
176
Chapter 9 Trans.
& Gene.
177
Chapter 10 Out
door
lighting
Chapter 10
Out Door Lighting
179
REFFERENCES
Software Programs
Products Catalogues
Scientific References