1. Lightings
Minimum load for normal light is 100W and for LED light is 35W. If
it is more than 35W for LED it will be as per actual load.
Type Load(W)
Ceiling Light 100W
Ex.Fan & Fan 100W
LED Light 35W
Spot Light 50W
Emergency Light 20W
Bell 20W
Chandler 500W
Type Load(W)
13A Single Socket 200W
13A Double Socket 400W
15A Socket (Commercial & Industrial) 1000W
15A Socket(Residential) 500W
3. COOKER UNIT
C.B Phase conductor Earth conductor Circuit
Capacity(A) size(mm²) size(mm²) Max.Load(W)
32 6 6 3000
7. PUMPS+MOTORS
𝐏(𝐊𝐖)
I= = 1.74(KW)
√𝟑∗𝐕∗𝐂𝐎𝐒∅
BREAKER & CABLE SELECTION
MCCB/ACB
CABLE(mm²) ECC(mm²)
(A)
SINGLE PHASE
20 1X2CX 6mm² Cu/XLPE/SWA/PVC 1CX 6mm² Cu ECC Y/G
32 1X2CX 10mm² Cu/XLPE/SWA/PVC 1CX 10mm² Cu ECC Y/G
40 1X2CX 16mm² Cu/XLPE/SWA/PVC 1CX 16mm² Cu ECC Y/G
THREE PHASE
32 1X4CX 10mm² Cu/XLPE/SWA/PVC 1CX10mm² Cu ECC Y/G
40 1X4CX 16mm² Cu/XLPE/SWA/PVC 1CX16mm² Cu ECC Y/G
63 1X4CX 25mm² Cu/XLPE/SWA/PVC 1CX16mm² Cu ECC Y/G
80 1X4CX 35mm² Cu/XLPE/SWA/PVC 1CX16mm² Cu ECC Y/G
100 1X4CX 35mm² Cu/XLPE/SWA/PVC 1CX25mm² Cu ECC Y/G
125 1X4CX 50mm² Cu/XLPE/SWA/PVC 1CX25mm² Cu ECC Y/G
160 1X4CX 70mm² Cu/XLPE/SWA/PVC 1CX35mm² Cu ECC Y/G
200 1X4CX 95mm² Cu/XLPE/SWA/PVC 1CX50mm² Cu ECC Y/G
225 1X4CX 120mm² Cu/XLPE/SWA/PVC 1CX70mm² Cu ECC Y/G
250 1X4CX 150mm² Cu/XLPE/SWA/PVC 1CX70mm² Cu ECC Y/G
300 1X4CX 185mm² Cu/XLPE/SWA/PVC 1CX95mm² Cu ECC Y/G
350 1X4CX 240mm² Cu/XLPE/SWA/PVC 1CX120mm² Cu ECC Y/G
400 1X4CX 300mm² Cu/XLPE/SWA/PVC 1CX150mm² Cu ECC Y/G
600 4X1CX 630mm² Cu/XLPE/SWA/PVC 1CX240mm² Cu ECC Y/G
800 4X1CX 630mm² Cu/XLPE/SWA/PVC 1CX300mm² Cu ECC Y/G
1000 4X1CX 630mm² Cu/XLPE/SWA/PVC 1CX300mm² Cu ECC Y/G
1600 7X1CX 630mm² Cu/XLPE/SWA/PVC 1CX300mm² Cu ECC Y/G
2500 11X1CX 630mm² Cu/XLPE/SWA/PVC 1CX300mm² Cu ECC Y/G
Earth Leakage Protection System(ELCB):
Rating
Cable Size(mm²)
(KVA)
2000 14x1C x 630 mm² Cu PVC/PVC or XLPE/PVC
1500 11x1C x 630 mm² Cu PVC/PVC or XLPE/PVC
1000 7x 1C x 630 mm² Cu PVC/PVC or XLPE/PVC
500 4x 1C x 630 mm² Cu PVC/PVC or XLPE/PVC
250 1x 4C x 300 mm² Cu PVC/SWA/PVC or XLPE/SWA/PVC
200 1x 4C x 185 mm² Cu PVC/SWA/PVC or XLPE/SWA/PVC
100 1x 4C x 70 mm² Cu PVC/SWA/PVC or XLPE/SWA/PVC
The Accepted KA rating Level for the various KVA rating of the
substation:
Double Transformer:
Requirements Details
Minimum dimension Room Size 8m x 5m
Distance between Two Transformer 1.8m
Minimum dimension Door Size 2.4m x2.4m (open outside)
Requirements Details
Minimum dimension 3m x 2.7m separate
Room Size
Door Type Non-louver aluminium panel
door
11. KWH METER
Three types:
1- Single phase (up to 12KW)
2- Three phase (For 40A,63A,80A,100A,125A)
3- CT Meter (More than 125 A) ,Not allowed in DBs because
the maximum DB(3Ø)=125A according to SEWA.
P=Real Power
𝐐𝐜 = 𝐏(𝐭𝐚𝐧∅𝟏 − 𝐭𝐚𝐧∅𝟐 )
Q= Reactive Power
Assume: COS ∅1 = 0. 8 COS ∅2 = 0. 95 ( √𝟑 𝐕 𝐈 𝐬𝐢𝐧∅ )
𝐕𝐝 %
𝐕𝐝 = ∗ 𝟒𝟏𝟓
𝟏𝟎𝟎
16. EARTING SYSYTEM
1-Locally Earthed system (TT): Earth resistance ˂ 1Ω.
Earth Electrode:
Requirements details
TT Type Each 30m from LV Room
depth 3m
Housing 30cm x 30cm x 30cm
Above 500 A 2 Electrode
Show the figure below to know the differences in connection: