Professional Documents
Culture Documents
M&E Estimate
M&E Estimate
Rate Amount
Item Description Unit Qty
(RM) (RM)
A Related Works
F Sanitary Services
F.1 Semi-Detached Factory Lots 4 6,150.00 24,600.00
F.2 Terrace Factory Lots 6 9,250.00 55,500.00
Summary Page 1 of 20
TO SUPPLY, INSTALL, TESTING AND COMMISSIONING THE FOLLOWING:
ME1
ITEM DESCRIPTION UNIT QTY RATE AMOUNT
(RM) (RM)
ALL ITEMS ARE PROVISIONAL QUANTITIES AND
SUBJECT TO FINAL MEASUREMENT
A RELATED WORKS
1.1 Testing & Commissioning of all services to the Lump Sum 5,000.00 5,000.00
satisfaction of Client, Supervising Engineers, Council's, &
SESB's representatives.
1.2 Operation & Maintenance Manuals c/w as-built drawings, Lump Sum 5,000.00 5,000.00
test results, catalogs, spare part list etc.-3 sets in hard
cover. (for all M&E services)
1.3 Preparation & Submission of Shop drawings (for all M&E Lump Sum 5,000.00 5,000.00
services) - 3 sets
1.4 Cleaning up of debris resulting from the contract works. Lump Sum 5,000.00 5,000.00
1.5 Hacking, excavation, back filling, make good the walls/ Lump Sum 10,000.00 10,000.00
floors/ roads etc. caused by this works.
1.60 Warranty & Maintenance for defects liability period (12 Lump Sum 10,000.00 10,000.00
months), minimum once every 2 months. (For all M&E
services)
1.70 To liaise with relevant authorities for consultation, Lump Sum 5,000.00 5,000.00
obtaining & apply for necessary documentation, meters,
approval & licenses with JBA, SESB & Council for all
services but not limited to the below:
1.2 1 no. 75 mm dia. Vertical G.I Class 'C' pipe min. 2100mm
high above ground c/w support and protection painted in
orange color for electrical riser as shown in the drawings. mtr 3 50.00 150.00
2.2 Main cable from tap off unit to SLCP using 2x1c-16mm
mtr 10
sq. PVC/SWA/PVC/Al run underground.
LOT 1
Sub-mains Cabling
1.3 Multicore underground amoured copper cable c/w cable gland,
termination kits, trenching, clean sand bedding, brick protection,
backfilling, compacting and all necessary accessories as
indicated in drawings:
Wiring
1.5 Light point using 2 x 1c - 1.5 mm sq. PVC Cu. + 1.5 mm sq.
EPVC Cu. run in SIRIM approved type high impact heavy duty
(4421) concealed uPVC conduit / G.I conduit painted in orange
color when run exposed or above ceiling c/w 10A flush mounted
type switches as per drawings for:
1.6 Emergency light point using 2 x 1c - 1.5 mm sq. PVC Cu. + 1.5
mm sq. EPVC Cu. run in SIRIM approved type high impact heavy
duty (4421) concealed uPVC conduit / G.I conduit when run
exposed or above ceiling as per drawings for:
(a) DB-L1G (Lot 1) pts 2 130.00 260.00
1.8 Ceiling Fan point c/w fan hook using 2 x 1c - 1.5 mm sq. PVC
Cu. + 1.5 mm sq. EPVC Cu. run in SIRIM approved type high
impact heavy duty (4421) concealed uPVC conduit / G.I conduit
painted in orange color when run exposed or above ceiling c/w
10A flush mounted type switches as per drawings for:
1.9 Exhaust Fan point (wall type) using 2 x 1c - 1.5 mm sq. PVC Cu.
+ 1.5 mm sq. EPVC Cu. run in SIRIM approved type high impact
heavy duty (4421) concealed uPVC conduit / G.I conduit painted
in orange color when run exposed or above ceiling c/w 10A flush
mounted type switches as per drawings for:
1.10 Ceiling Exhaust Fan point using 2 x 1c - 1.5 mm sq. PVC Cu. +
1.5 mm sq. EPVC Cu. run in SIRIM approved type high impact
heavy duty (4421) concealed uPVC conduit / G.I conduit painted
in orange color when run exposed or above ceiling c/w 10A flush
mounted type switches as per drawings for:
1.11 Socket point using 2 x 1c - 2.5 mm sq. PVC Cu. + 2.5 mm sq.
EPVC Cu. run in SIRIM approved type high impact heavy duty
(4421) concealed uPVC conduit / G.I conduit when run exposed
or above ceiling c/w flush mounted 13A S.S.O (Mounted at
high level) as per drawings for:
(a) DB-L1G (Lot 1) pts 3 180.00 540.00
1.12 Socket using 2 x 1c - 2.5 mm sq. PVC Cu. + 2.5 mm sq. EPVC
Cu. run in SIRIM approved type high impact heavy duty (4421)
concealed uPVC conduit / G.I conduit painted in orange color
when run exposed or above ceiling c/w flush mounted 13A
S.S.O as per drawings for:
1.13 Socket point using 2 x 1c - 2.5 mm sq. PVC Cu. + 2.5 mm sq.
EPVC Cu. run in SIRIM approved type high impact heavy duty
(4421) concealed uPVC conduit / G.I conduit when run exposed
or above ceiling c/w flush mounted 13A S.S.O (Weatherproof
type) to IP55 as per drawings for:
1.14 Socket point using 2 x 1c - 2.5 mm sq. PVC Cu. + 2.5 mm sq.
EPVC Cu. run in SIRIM approved type high impact heavy duty
(4421) concealed uPVC conduit / G.I conduit when run exposed
or above ceiling c/w flush mounted 13A S.S.O, Waterproof
type to IP55 (Undersink) as per drawings for:
(a) DB-L1G (Lot 1) pts 2 280.00 560.00
1.16 40A SPN Cooker Unit c/w 13A Switch Socket Outlet using 2 x 1c
- 4 mm sq. PVC Cu. + 4 mm sq. EPVC Cu. run in SIRIM
approved type high impact heavy duty (4421) concealed uPVC
conduit / G.I conduit painted in orange color when run exposed
or above ceiling c/w flush mounted 13A S.S.O as per drawings
for:
1.17 20A Isolator for Water Booster Pump using 2 x 1c - 2.5 mm sq.
PVC/SWA/PVC,Cu. run in SIRIM approved type high impact
heavy duty (4421) concealed uPVC conduit / G.I conduit painted
in orange color when run exposed or above ceiling or run
underground c/w Weatherproof Type 13A S.S.O (IP66) with
plug cover as per drawings for:
B/F: 41,340.00
Total carried forward to Collection Page For M&E Works - Lot 1 (ME2) 43,340.00
1.1 2-Way 100mm dia. G.I. pipe duct laid underground extend
beyond drain / below ground level c/w all necessary
accessories as shown in drawings.
(i) From JRC7 No. 1 to JRC7 No. 2 mtr 15 180.00 2,700.00
1.2 1-Way 100mm dia. G.I. pipe duct laid underground extend
beyond drain / below ground level c/w all necessary
accessories as shown in drawings.
(i) From JRC7 No. 2 to TP1 mtr 20 120.00 2,400.00
1.3 1-Way 50mm dia. uPVC pipe duct laid underground c/w all
necessary accessories as shown in drawings.
(i) From TP1 to TP2 (Lot 1) mtr 10 50.00 500.00
1.4 50mm dia. vertical G.I Class 'C' Pipe min. 2100mm high
above ground c/w support for telephone riser protection
painted in anti-corrosive paint and green color as per
telekom standard and requirement & as per drawings.
(i) From TP2 to FTB1 (Lot 1) mtr 5 50.00 250.00
3.3 2 core single mode fibre optic indoor drop cable run in
concealed high impact heavy duty (4421) EPVC conduit/
m.s trunking/ G.I. conduit when run exposed or above
ceiling c/w Field Assembly Connector (FASC) and all other
necessary accessories required.
(i) From FTB1 to FWS1 (Lot 1) pt 1 600.00 600.00
3.4 Telekom approved type fibre wall socket outlet c/w all other
necessary accessories required.
(i) Lot 1 set 1 150.00 150.00
3.5 Internet & Data point using Cat6 cable run in concealed
high impact heavy duty (4421) EPVC conduit/ m.s trunking/
G.I. conduit when run exposed or above ceiling c/w RJ45
outlets sockets as per drawing
Total carried forward to Collection Page For M&E Works - Lot 1 (ME2) 26,950.00
Rate Amount
Item Description Unit Qty
(RM) (RM)
All Items Are Provisional Quantities and Subject to
Final Measurement
a) Semi-Detached Factory
3.0 Cold Water Piping using PPR (PN16) pipe & fittings to
DIN8077 & BS6920 1990 Part 1,2 & 3, run underground,
high level under apron & conceal brickwalls c/w valves,
gate valves, non-return valves, elbows, tees, reducers,
etc and all other necessary works as per drawings and
specifications.
3.1 Internal cold water pipe from water meter to water Lot(s) 1 1,500.00 1,500.00
storage tank and from water storage tank at 1st floor
to all outlets as shown in the drawings.
Rate Amount
Item Description Unit Qty
(RM) (RM)
All Items Are Provisional Quantities and Subject to
Final Measurement
3.0 Cold Water Piping using PPR (PN16) pipe & fittings to
DIN8077 & BS6920 1990 Part 1,2 & 3, run underground,
high level under apron & conceal brickwalls c/w valves,
gate valves, non-return valves, elbows, tees, reducers,
etc and all other necessary works as per drawings and
specifications.
3.1 Internal cold water pipe from water meter to water Lot(s) 1 3,000.00 3,000.00
storage tanks and from water storage tanks to all
outlets as shown in the drawings.
Rate Amount
Item Description Unit Qty
(RM) (RM)
All Items Are Provisional Quantities and Subject to
Final Measurement
3.0 Cold Water Piping using PPR (PN16) pipe & fittings to
DIN8077 & BS6920 1990 Part 1,2 & 3, run underground,
high level under apron & conceal brickwalls c/w valves,
gate valves, non-return valves, elbows, tees, reducers,
etc and all other necessary works as per drawings and
specifications.
3.1 Internal cold water pipe from water meter to water Lot(s) 1 2,300.00 2,300.00
storage tanks and from water storage tanks to all
outlets as shown in the drawings.
Rate Amount
Item Description Unit Qty
(RM) (RM)
All Items Are Provisional Quantities and Subject to
Final Measurement
3.0 Cold Water Piping using PPR (PN16) pipe & fittings to
DIN8077 & BS6920 1990 Part 1,2 & 3, run underground,
high level under apron & conceal brickwalls c/w valves,
gate valves, non-return valves, elbows, tees, reducers,
etc and all other necessary works as per drawings and
specifications.
3.1 Internal cold water pipe from water meter to water Lot(s) 1 2,100.00 2,100.00
storage tank and from water storage tank at 2nd
floor to all outlets as shown in the drawings.
Rate Amount
Item Description Unit Qty
(RM) (RM)
All Items Are Provisional Quantities and Subject to
Final Measurement
B SANITARY SERVICE
a) Semi-Detached Factory
2.0 Down pipe c/w weather proof apron, vent cowl and etc Set 1 800.00 800.00
b) Terrace Factory
Sanitary Page 22 of 20
TO SUPPLY, INSTALL, TESTING AND COMMISSIONING THE FOLLOWING:
Rate Amount
Item Description Unit Qty
(RM) (RM)
All Items Are Provisional Quantities and Subject to
Final Measurement
B SANITARY SERVICE
1.0 Supply and installation of Sanitary piping using UPVC, S,
W & soil pipe to BS4660 (Brown) for below ground and
BS4515 (White) for above ground to nearest manhole
C/W gully traps, floor traps, elbows, sockets, vents,
reducers, inspection chambers, etc and all other Lot 1 5,000.00 5,000.00
necessary works such as hacking and making good of
walls / floors and accessories for the completion of the
system
2.0 Down pipe c/w weather proof apron, vent cowl and etc Set 1 1,000.00 1,000.00
Sanitary Page 23 of 20
TO SUPPLY, INSTALL, TESTING AND COMMISSIONING THE FOLLOWING:
Rate Amount
Item Description Unit Qty
(RM) (RM)
All Items Are Provisional Quantities and Subject to
Final Measurement
a) Semi-Detached Factory
1.1 9kg ABC type fire extinguisher c/w bomba certifcate and Nos 2 200.00 400.00
mounting brackets
2.1 Supply and installation of Conventional Fire Alarm Panel Set 1 4,900.00 4,900.00
c/w 72 hours battery backup, mimic panel, zone cards
and master alarm bell.
2.2 Supply and installaion bomba approved type 150mm Nos 3 200.00 600.00
diameter alarm bell c/w fault isolator, accessories and
etc.
2.3 Supply and installaion bomba approved type manual 200.00 400.00
break glass c/w fault isolator, accessories and etc.
Nos 2
2.4 Wiring GI conduit for item 2.2, and 2.3 above. Lot 1 2,500.00 2,500.00
Rate Amount
Item Description Unit Qty
(RM) (RM)
All Items Are Provisional Quantities and Subject to
Final Measurement
b) Terrace Factory
1.1 9kg ABC type fire extinguisher c/w bomba certifcate and Nos 2 200.00 400.00
mounting brackets
2.1 Supply and installation of Conventional Fire Alarm Panel Set 1 4,900.00 4,900.00
c/w 72 hours battery backup, mimic panel, zone cards
and master alarm bell.
2.2 Supply and installaion bomba approved type 150mm Nos 3 200.00 600.00
diameter alarm bell c/w fault isolator, accessories and
etc.
2.3 Supply and installaion bomba approved type manual 200.00 400.00
break glass c/w fault isolator, accessories and etc.
Nos 2
2.4 Wiring GI conduit for item 2.2, and 2.3 above. Lot 1 2,500.00 2,500.00