Professional Documents
Culture Documents
S Civ Fire DSS - 00
S Civ Fire DSS - 00
Fire Fighting
Distribution and Switching Substations
2 APPLICATION FIELD
This specification refers to the fire protection system which must be supplied, installed and tested
inside the areas and rooms present inside the electrical substations.
For further details, please refer to the descriptions in the following paragraphs.
3 REFERENCE DOCUMENTS
The list of the reference documents is indicated in the following paragraphs.
In case of discrepancy between these Specifications and any of the applicable Codes and
Standards, the following order of precedence shall apply:
1) ADDC/AADC specifications
2) Regulation and Law
3) applicable reference standards
4) other documents.
The Supplier shall note that compliance of the manufacturer with the provision of these
specifications does not relieve him from his responsibility to supply the equipment and accessories
of proper design, electrically and mechanically suited to meet the operating guarantees at the
specified service conditions.
The prescription included in the Regulations and Law shall prevail on all other international
standards mentioned in paragraph 3.2.
4 SERVICE CONDITIONS
The service conditions are specified in S-GEN-SER, in case something is not or not properly
specified regarding the service conditions, the Reference Standards prescriptions shall be
considered.
6.1 GENERAL
The design, installation and tests shall be accomplished in accordance with the latest edition of the
American NFPA-Codes or European standard as herein specified.
All equipment / materials to be supplied for the fire fighting and fire alarm systems shall be
approved by one of the following authorities:
• Factory Mutual, FM
• Underwriter's Laboratory, UL
For design based on NFPA, only FM/UL approved equipment shall be supplied.
However Civil Defence & Municipality approval for all equipment for fire protection systems
proposed, supplied and installed by the contractors is mandatory.
Each major component of protective firefighting equipment shall be marked in Arabic and English
in accordance with NFPA recommendations.
Each and every valve in every system shall be identified with a metal tag, bearing a white
enamelled number on a red field, secured to the valve wheel or body. All details of this requirement
shall be subject to prior approval.
The firefighting installations must, in any case, be ready for operation before commissioning the
station.
Only companies experienced and approved in the design and erection of fire protection
installations will be accepted as (Sub-Contractors) and all works for design, installation,
supervision, testing and commissioning shall be performed directly through these Companies.
Further sub-contracting of any work will not be accepted.
The design of buildings, civil constructions as well as all fire protection installations shall also
confirm to local regulations, latest edition and amendments, and are subject to acceptance by the
local authority having jurisdiction.
6.2 FIRE ZONES
Each building shall be sub-divided into various fire zones. The fire barrier (membrane) either in
vertical or horizontal, such as a wall, door or floor assembly shall be designed and constructed
with a fire resistance rating of minimum 2 hours to limit the spread of fire and also to restrict the
movement of Smoke.
The following areas shall always form an independent fire zone:
• Each emergency exit
• Each plant MV and LV switchgear room
• Each control, relay, telecommunication and computer room
• Each transformer bays
• Each cable floor, cable shaft and cable tunnel
• Each battery rooms
• Each storage rooms
All electrical cables or pipes running through openings of fire-resistant walls and ceilings must be
properly sealed with an approved sealing system, consisting of fire and water resistant materials
providing a fire resistance for a minimum of 90 minutes.
Client: ADDC/ AADC
STANDARD TECHNICAL SPECIFICATIONS FOR ELECTRICITY DISTRIBUTION WORKS
Title: SPECIFICATION FOR FIRE FIGHTING FOR DISTRIBUTION SUBSTATIONS
DOCUMENT NO: S-CIV-FIRE-DSS_00.DOCX Rev: 0-2022 Sheet: 11 of: 23
Air-conditioning and ventilation ducts penetrating fire walls or ceilings shall be provided with
motorized fire dampers, equipped with magnetic release via fire Alarm/HVAC panel as detected
by the fire detection and fire alarm system, limit switches for central indications and motorized re-
opening system.
Fire zones shall have adequately designed fixed Smoke evacuation / extraction systems.
Outdoor cable trenches shall have fire barriers by means of approved sealing systems in distances
not exceeding 40 m and subject to Municipality & Civil Defence approval.
6.2.1 In-Accessible Cable Trenches
The risk of fire spreading in cable trenches can be greatly reduced by sectionalising the trenches
in small and suitable fire sections of not more than 40 m of the trench length by means of fire
resistant sectionalising walls and cable penetration seals.
The fire resistant sectionalising walls, except the openings left for cable penetrations, shall be made
of concrete, bricks, mortar, high-density mineral fibre panels or of any other proper materials,
tested and approved to international fire test criteria, providing a fire resistance for a minimum of
90 minutes.
The remaining space between the penetrating control and power cables and the openings in the
fire-resistant sectionalising walls shall be sealed with an approved sealing system, providing a fire
resistance for a minimum of 90 minutes.
6.3 EMERGENCY EXITS
Passages and ways leading to exits and emergency exits shall be clearly marked by suitable
photoluminescent type symbols and signs both in English and Arabic. Lighted emergency exit
signs which meet NFPA requirements shall be of the maintained (always ON with battery back-
up) type. In basement the exit route shall be marked on ground using photoluminescent paint and
supported with photoluminescent type symbols and signs both in English and Arabic. Distances
and locations should
be foreseen as per NFPA and local fire code requirements. All building and room doors for
electrical installations must be equipped with escape facilities.
6.4 FIRE EXTINGUISHERS
The fire extinguishers shall be designed, installed and tested in accordance with NFPA No. 10,
latest edition. The year of manufacture must be clearly mentioned on every extinguisher.
Portable fire extinguishers shall be maintained in a fully charged and operable condition and shall
be kept in their designated places at all times when they are not being used.
Fire extinguishers shall be conspicuously located where they will be readily accessible and
immediately available in the event of fire. Preferably, they shall be located along normal paths of
travel, including exits from areas.
Before installing any fire-extinguishing equipment, read and understand the installation and use
instructions, including the limitations, cautions, and warnings contained on the equipment and in
the owner’s manual.
Portable extinguishers shall be installed in an accessible spot, free from blocking by storage and
equipment, and near room exits that provide an escape route. So that the top of the extinguisher is
10 EXCEPTIONS
Possible exceptions to the present prescriptions, concerning the adoption of technical and/or
manufacturing aspects different from the ones prescribed in the present specification, can be
evaluated by ADDC/AADC.
In such a case, ADDC/AADC will take into account the opportunity to require additional tests
with regard to the technical/manufacturing proposed solutions.
Such exceptions can be approved by ADDC/AADC.