Design-Build Service for Accessibility Upgrade at the 68th St-Hunter College Station
REVISION 1
DATE 09/12/2022
NOTES OR COMMENTS :
REVIEWER'S REMARKS:
1. Installation of dry fire standpipe
and fittings shall be in accordance
to Part 3 (Execution) of the
specifications.
CONTRACTOR SUBMITTAL
GANNETT FLEMING
Review is for general compliance with contract documents. Sole
responsibility for correctness of dimensions, details, quantities,
and safety during fabrication and erection shall remain with the
Contractor.
Accepted Other
Accepted as noted
Resubmit as noted
Rejected
A-36164
Forte Construction
926 Lincoln Ave,
Holbrook, New York 11741
9/8/2022
2 0 1 3 E D I T I O N
3"-64"
DUCTILE IRON PIPE DESIGN
NSF ®
FOR FIRE PROTECTION, WATER & WASTEWATER
Certified to
ANSI/NSF 61
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P2
Table of Contents
Ductile Iron Pipe 3
Laying Conditions 5
Design Method and Examples
of Selection Method 6
Pressure Class 10
Thickness Class 11
Earth Load Plus Truck Load 12
Internal Pressure 22
Maximum Depth of Cover 23
Products for Water, Waste Water,
and Fire Protection 25
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P3
From the standpoint of mechanical properties, Ductile Iron more nearly resembles steel than gray
iron. Ductile Iron has a modulus of elasticity of approximately 24 million psi.
Long-term experience and exhaustive research have clearly established the excellent corrosion
resistance of gray cast iron, and in normal environments, it serves indefinitely without special
corrosion protection. The fact is well known that in more than 570 utilities in North America,
cast iron pipe has served continuously for over a century. The development and use of Ductile
Iron pipe made it possible to evaluate its service characteristics as compared to gray iron pipe
and it has been confirmed that its corrosion resistance is equal to or greater than the excellent
resistance of gray iron pipe. It has also been learned through both laboratory testing and field
experience that Ductile Iron is far less susceptible to structural failure resulting from corrosion
attack than is gray iron.
Ductile Iron Pipe Research Association (DIPRA) published a proven environmental evaluation
system which allows engineers and utilities to determine areas of required external protection
for cast gray iron pipe. Knowledge of the comparative corrosion resistance of Ductile Iron pipe
makes it proper to apply the same environmental evaluation procedures to this material.
Since years of experience had established that corrosion protection of iron pipe cannot be provided,
or even significantly enhanced, by merely increasing pipe wall thickness, DIPRA discovered that
loose polyethylene encasement provided excellent protection against soil corrosion as well as stray
direct current. This material provides the same complete protection for Ductile Iron as for gray iron
pipe. DIPRA has recommended polyethylene encasement for thousands of miles of gray and Ductile
Iron pipe in severely corrosive soil areas. Polyethylene encasement has been proven to be an
extremely effective and economical corrosion protection system.
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P4
Corrosion resistance data, extensive field service experience and accurate soil evaluation,
together with proven corrosion prevention using polyethylene encasement, have demonstrated
the correctness of the revision of ANSI/AWWA C150/A21.50. Designers may now approach any
known set of field conditions with confidence in the knowledge that properly designed and
installed Ductile Iron pipe will not fail because of corrosion.
The 1991 Revisions of ANSI/AWWA C150/A21.50 and ANSI/AWWA C151/A21.51 include tables with
the nominal thickness for each of the standard pressure classes. These standard pressure classes
are defined as the rated water working pressure, in psi, of the pipe. The nominal thicknesses shown
for these standard pressure classes are adequate for the rated working pressure plus a surge
allowance of 100 psi. Other tables in these two standards show the dimensions and weights for
special classes of pipe. These “Special Classes” are the thickness classes of the “50” series (i.e.
Thickness Class 50, Thickness Class 52, etc.) which have been a part of these standards for a
number of years.
U.S. Pipe qualifies for Federal Procurement under Public Law No. 94-580, Section 6002, known as
the Resource Recovery Act of 1976, since, due to modern technology, recycled iron and steel scrap
is used to a large degree in our Ductile Iron pipe production.
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P5
Laying Conditions
Table 1. Design Values for Standard Laying Conditions
1
LAYING CONDITIONS DESCRIPTION E BEDDING KB KX
ANGLE
Type 1*
Type 2
Type 3
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P6
Calculations are made for the thicknesses required to resist the bending stress and the deflection
caused by trench load. The larger of the two is selected as the thickness required to resist
trench load. Calculations are then made for the thickness required to resist the hoop stress of
internal pressure.
The larger of these is selected as the net design thickness. To this net thickness is added a
service allowance to obtain the minimum manufacturing thickness, and a casting tolerance to
obtain the total calculated thickness.
The standard thickness and the pressure class for specifying and ordering are selected from a
table of standard pressure classes. (Table 2, page 10.)
The reverse procedure is used to determine the rated working pressure and maximum depth of
cover for pipe of a given class.
Trench Load, Pv. Trench load is expressed as vertical pressure in pounds per square inch and is
equal to the sum of earth load Pe and truck load Pt.
Earth Load, Pe . Earth load is computed as the weight of the unit prism of soil with a height equal
to the distance from the top of the pipe to the ground surface. The unit weight of backfill soil is
taken to be 120 lb/cu ft.
Truck Load, Pt . The truck loads are those specified in ANSI/AWWA C150/A21.50 and are for a
single AASHTO H-20 truck on unpaved road or flexible pavement, 16,000-lb. wheel load, and
1.5 impact factor.
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P7
Example No. 1
Select the thickness for 24" Ductile Iron pipe laid on a flat bottom trench with backfill lightly
consolidated and laying condition Type 2 under 10 feet of cover for a working pressure of 300 psi.
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P8
Interpolating:
27 - 24 = 3
28 - 24 = 4
.34" - .30" = .04"
(3/4) x .04" = .03"
.03" + .30" = .33" Total Calculated Thickness
See Table 2, use Class 350.
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P9
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P 10
Pressure Class
Table 2. Nominal Thickness for Standard Pressure Classes of Ductile-Iron Pipe
PRESSURE CLASS*
NOMINAL THICKNESS Inches
OUTSIDE CASTING
SIZE DIAMETER 150 200 250 300 350 TOLERANCES
Inches Inches Inches
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P 12
3 2.5 0.18 350 0.17 350 0.17 350 0.16 350 0.15 350
3 3 0.18 350 0.17 350 0.16 350 0.15 350 0.15 350
3 4 0.17 350 0.16 350 0.16 350 0.15 350 0.15 350
3 5 0.17 350 0.16 350 0.16 350 0.15 350 0.15 350
3 6 0.17 350 0.16 350 0.16 350 0.15 350 0.15 350
3 7 0.17 350 0.16 350 0.16 350 0.15 350 0.15 350
3 8 0.17 350 0.16 350 0.16 350 0.15 350 0.15 350
3 9 0.17 350 0.16 350 0.16 350 0.15 350 0.15 350
3 10 0.18 350 0.16 350 0.16 350 0.15 350 0.15 350
3 12 0.18 350 0.16 350 0.16 350 0.15 350 0.15 350
3 14 0.18 350 0.17 350 0.17 350 0.16 350 0.15 350
3 16 0.19 350 0.17 350 0.17 350 0.16 350 0.15 350
3 20 0.19 350 0.18 350 0.18 350 0.16 350 0.15 350
3 24 0.20 350 0.19 350 0.19 350 0.17 350 0.15 350
3 28 0.21 350 0.19 350 0.19 350 0.18 350 0.15 350
3 32 0.21 350 0.20 350 0.20 350 0.18 350 0.16 350
NOTE: To convert inches (in.) to millimeters (mm), multiply by 25.4; to convert feet (ft.) to meters (m), multiply by 0.3048.
*Pipe may be available for depths of cover greater than those shown in the table.
6 4 0.20 350 0.18 350 0.17 350 0.16 350 0.15 350
†Total calculated thickness includes service allowance and casting tolerance added to net thickness.
6 5 0.19 350 0.18 350 0.17 350 0.16 350 0.15 350
6 6 0.19 350 0.18 350 0.17 350 0.16 350 0.15 350
Table continued on next page.
6 7 0.20 350 0.18 350 0.17 350 0.16 350 0.15 350
6 8 0.20 350 0.18 350 0.17 350 0.16 350 0.15 350
6 9 0.20 350 0.19 350 0.18 350 0.16 350 0.15 350
6 10 0.21 350 0.19 350 0.18 350 0.16 350 0.15 350
6 12 0.21 350 0.20 350 0.18 350 0.17 350 0.16 350
6 14 0.22 350 0.20 350 0.19 350 0.17 350 0.16 350
6 16 0.23 350 0.21 350 0.20 350 0.17 350 0.16 350
6 20 0.24 350 0.22 350 0.21 350 0.18 350 0.16 350
6 24 0.25 350 0.24 350 0.22 350 0.19 350 0.17 350
6 28 — — 0.25 350 0.23 350 0.21 350 0.17 350
6 32 — — — — 0.24 350 0.22 350 0.17 350
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P 13
4 2.5 0.19 350 0.18 350 0.17 350 0.16 350 0.15 350
4 3 0.19 350 0.18 350 0.17 350 0.16 350 0.15 350
4 4 0.18 350 0.17 350 0.16 350 0.15 350 0.15 350
4 5 0.18 350 0.17 350 0.16 350 0.15 350 0.15 350
4 6 0.18 350 0.17 350 0.16 350 0.15 350 0.15 350
4 7 0.18 350 0.17 350 0.16 350 0.15 350 0.15 350
4 8 0.18 350 0.17 350 0.16 350 0.15 350 0.15 350
4 9 0.18 350 0.17 350 0.16 350 0.15 350 0.15 350
4 10 0.18 350 0.17 350 0.16 350 0.16 350 0.15 350
4 12 0.19 350 0.18 350 0.17 350 0.16 350 0.15 350
4 14 0.19 350 0.18 350 0.17 350 0.16 350 0.15 350
4 16 0.20 350 0.19 350 0.18 350 0.16 350 0.15 350
4 20 0.21 350 0.20 350 0.19 350 0.17 350 0.15 350
4 24 0.21 350 0.21 350 0.20 350 0.18 350 0.16 350
4 28 0.22 350 0.21 350 0.20 350 0.19 350 0.16 350
4 32 0.23 350 0.22 350 0.21 350 0.19 350 0.16 350
6 2.5 0.22 350 0.20 350 0.19 350 0.17 350 0.16 350
6 3 0.21 350 0.19 350 0.18 350 0.17 350 0.15 350
6 4 0.20 350 0.18 350 0.17 350 0.16 350 0.15 350
6 5 0.19 350 0.18 350 0.17 350 0.16 350 0.15 350
6 6 0.19 350 0.18 350 0.17 350 0.16 350 0.15 350
6 7 0.20 350 0.18 350 0.17 350 0.16 350 0.15 350
6 8 0.20 350 0.18 350 0.17 350 0.16 350 0.15 350
6 9 0.20 350 0.19 350 0.18 350 0.16 350 0.15 350
6 10 0.21 350 0.19 350 0.18 350 0.16 350 0.15 350
6 12 0.21 350 0.20 350 0.18 350 0.17 350 0.16 350
6 14 0.22 350 0.20 350 0.19 350 0.17 350 0.16 350
6 16 0.23 350 0.21 350 0.20 350 0.17 350 0.16 350
6 20 0.24 350 0.22 350 0.21 350 0.18 350 0.16 350
6 24 0.25 350 0.24 350 0.22 350 0.19 350 0.17 350
6 28 — — 0.25 350 0.23 350 0.21 350 0.17 350
6 32 — — — — 0.24 350 0.22 350 0.17 350
NOTE: To convert inches (in.) to millimeters (mm), multiply by 25.4; to convert feet (ft.) to meters (m), multiply by 0.3048.
*Pipe may be available for depths of cover greater than those shown in the table.
†Total calculated thickness includes service allowance and casting tolerance added to net thickness. Table continued on next page.
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P 22
Internal Pressure
Table 5. Thickness for Internal Pressure
RATED WATER WORKING PRESSURE psi
150 200 250 300 350
TOTAL USE TOTAL USE TOTAL USE TOTAL USE TOTAL USE
PIPE CALCULATED PRESSURE CALCULATED PRESSURE CALCULATED PRESSURE CALCULATED PRESSURE CALCULATED PRESSURE
SIZE THICKNESS* CLASS THICKNESS CLASS THICKNESS CLASS THICKNESS CLASS THICKNESS CLASS
Inches Inches Inches Inches Inches Inches
3 0.15 350 0.16 350 0.16 350 0.17 350 0.17 350
4 0.16 350 0.16 350 0.17 350 0.18 350 0.18 350
6 0.17 350 0.18 350 0.19 350 0.20 350 0.20 350
8 0.18 350 0.19 350 0.21 350 0.22 350 0.23 350
10 0.21 350 0.22 350 0.23 350 0.25 350 0.26 350
12 0.22 350 0.23 350 0.25 350 0.27 350 0.28 350
14 0.24 250 0.26 250 0.28 250 0.30 300 0.31 350
16 0.25 250 0.27 250 0.30 250 0.32 300 0.34 350
18 0.27 250 0.29 250 0.31 250 0.34 300 0.36 350
20 0.28 250 0.03 250 0.33 250 0.36 300 0.38 350
24 0.30 200 0.33 200 0.37 250 0.40 300 0.43 350
30 0.34 150 0.38 200 0.42 250 0.45 300 0.49 350
36 0.38 150 0.42 200 0.47 250 0.51 300 0.56 350
42 0.41 150 0.47 200 0.52 250 0.57 300 0.63 350
48 0.46 150 0.52 200 0.58 250 0.64 300 0.70 350
54 0.51 150 0.58 200 0.65 250 0.72 300 0.79 350
60 0.54 150 0.61 200 0.68 250 0.76 300 0.83 350
64 0.56 150 0.64 200 0.72 250 0.80 300 0.87 350
NOTE: To convert inches (in.) to millimeters (mm), multiply by 25.4; to convert pounds per square inch (psi) to kilopascals (kPa), multiply by 6.895.
The thicknesses shown are adequate for the rated working pressure plus a surge allowance of 100 psi (689 kPa). Calculations are based on a minimum yield
strength in tension of 42,000 psi (290 MPa) and a 2.0 safety factor times the sum of working pressure and 100 psi (689 kPa) surge allowance.
*Total calculated thickness includes service allowance and casting tolerance added to net thickness.
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P 24
42 150 0.41 ** — 9 13 20
42 200 0.47 ** 8 12 15 22
42 250 0.52 ** 10 14 17 25
42 300 0.57 ** 12 16 20 27
42 350 0.63 ** 15 19 23 32
48 150 0.46 ** — 9 13 20
48 200 0.52 ** 8 11 15 22
48 250 0.58 ** 10 13 17 24
48 300 0.64 ** 12 15 19 27
48 350 0.70 ** 15 18 22 30
54 150 0.51 ** — 9 13 20
54 200 0.58 ** 8 11 14 22
54 250 0.65 ** 10 13 16 24
54 300 0.72 ** 13 15 19 27
54 350 0.79 ** 15 18 22 30
60 150 0.54 ** 5§ 9 13 20
60 200 0.61 ** 8 11 14 22
60 250 0.68 ** 10 13 16 24
60 300 0.76 ** 13 15 19 26
60 350 0.83 ** 15 18 22 30
64 150 0.56 ** 5§ 9 13 20
64 200 0.64 ** 8 11 14 21
64 250 0.72 ** 10 13 16 24
64 300 0.80 ** 12 15 19 26
64 350 0.87 ** 15 17 21 29
NOTE: To convert inches (in.) into millimeters (mm), multiply by 25.4; to convert feet (ft.) to meters (m), multiply by 0.3048; and to convert
pounds per square inch (psi) into kilopascals (kPa), multiply by 6.895.
Calculations are based on a 2.0 safety factor times the sum of working pressure and 100 psi (689 kPa) surge allowance. Ductile Iron pipe
for working pressures higher than 350 psi (2413 kPa) is available.
*Ductile Iron pipe is adequate for the rated working pressure indicated for each nominal size plus a surge allowance of 100 psi (689 kPa).
†An allowance for a single H-20 truck with 1.5 impact factor is included for all depths of cover.
‡Calculated maximum depth of cover exceeds 100 ft. (30.5 m).
§Minimum allowable depth of cover is 3 ft. (0.9 m).
**For pipe 14" (350 mm) and larger, consideration should be given to the use of laying conditions other than Type 1.
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
866.DIP.PIPE
DUCTILE IRON PIPE DESIGN
NSF ®
Certified to
ANSI/NSF 61
2013 EDITION P 25
Restrained Joints
TR FLEX® Pipe 4"-64" Ductile Iron
FIELD LOK 350® Gaskets 4"-24"
FIELD LOK® Gasket 30", 36"
TR FLEX GRIPPER® Rings 4"-36" Ductile Iron
TR TELE FLEX® Assemblies 4"-24" Ductile Iron
FIELD-FLANGE 350® Fittings 4"-24" Ductile Iron
M-Series Hydrants
AWWA Dry Barrel hydrants - 4-1/2" or 5-1/4"
METROPOLITAN®/M-94 Valve Opening
METROFLOW™/M-03
Valves
AWWA Resilient Seated Gate Valves - 3"-36"
METROSEAL® R/S Gate Valves
Double Disc Gate Valves 16"-60", AWWA C500
Miscellaneous Products
PROTECTO 401™ Lined Ductile Iron Pipe for 4"-64" Ductile Iron
Domestic Sewage and Industrial Wastes
FLANGE-TYTE® Gaskets 4"-64"
Polymeric Coatings and Linings For all pipe sizes
Saddle Outlets Various Ductile Iron
Welded Outlets Various Ductile Iron
Polyethylene Encasement 4"-64"
Tapping Sleeves and Valves All sizes
Tapping Machines 3"-16"
U.S. PIPE AND FOUNDRY CO. DUCTILE IRON PIPE DESIGN BRO-001 REVISED 10.13
NSF ®
Certified to
ANSI/NSF 61
www.wheatland.com
Wheatland ASTM A 53
Schedule 40 and Schedule 80 Pipe
Wheatland Steel Pipe is made by specialists who understand that it’s the small details
Specifications and descriptions are accurate as known at time of publication and subject to change
without notice.
700 South Dock Street
Wheatland, PA 16146
800.257.8182
www.wheatland.com
ASTM A 53 Grades A and B: Black and Galvanized Pipe is manufactured for ordinary use in steam, water,gas, and
air lines. UL Listed and FM Approved, sizes 1” through 6” nominal, for use in Fire Sprinkler Pipe Applications.
Mechanical Properties
Grade A: Yield 30,000 [205 Mpa] psi minimum Tensile: 48,000 psi [330 Mpa] minimum
Grade B: Yield 35,000 [240 Mpa] psi minimum Tensile: 60,000 psi [415 Mpa] minimum
Sch40&80_ASTM_A53_2012
Ductile Iron AWWA (Cast) Fittings
23.05
2.0 CERTIFICATION/LISTINGS
Product designed and manufactured under the Victaulic Quality Management System, as certified by LPCB in
accordance with ISO-9001:2008.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
1
victaulic.com
NOTES
• Coatings are applied per manufacturer’s recommended mils.
• The standard black asphalt coating used on Victaulic cement lined AWWA size fittings is NSF 61 Listed.
• Cast surfaces will be provided with surface equivalent to SSPC-SP6 prior to coating unless specified otherwise.
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com
4.0 DIMENSIONS
Elbows
No. 100-C 90º Long Radius Elbow
No. 10-C 90º Elbow
No. 11-C 45º Elbow
No. 12-C 22½º Elbow
No. 13-C 11¼º Elbow
C to E
E to E
C to E
C to E
C to E
C C to E
to E
No. 100-C No. 10-C No. 11-C No. 12-C No. 13-C
No. 100-C No. 10-C No. 11-C No. 12-C No. 13-C
Size 90° Long Radius Elbow 90° Elbow 45° Elbow 22½° Elbow 11¼° Elbow
Actual Approx. Approx. Approx. Approx. Approx.
Outside Weight Weight Weight Weight Weight
Nominal Diameter C to E (Each) C to E (Each) C to E (Each) C to E (Each) C to E (Each)
inches inches inches lb inches lb inches lb inches lb inches lb
DN mm mm kg mm kg mm kg mm kg mm kg
3 3.960 7.75 19.3 5.50 8.6 3.00 5.8 3.00 12.5 3.00 9.0
80 100.6 197 8.8 140 3.9 76 2.6 76 5.7 76 4.1
4 4.800 9.00 28.0 6.50 12.0 4.00 8.4 4.00 11.5 4.00 11.5
100 121.9 229 12.7 165 5.4 102 3.8 102 5.2 102 5.2
6 6.900 11.50 55.0 8.00 22.0 5.00 15.0 5.00 25.0 5.00 21.5
150 175.3 292 25.0 203 10.0 127 6.8 127 11.3 127 9.8
8 9.050 14.00 83.0 9.00 38.0 5.50 28.8 5.50 39.5 5.50 39.0
200 229.9 356 37.7 229 17.2 140 13.1 140 17.9 140 17.7
10 11.100 16.50 160.0 11.00 76.0 6.50 43.3 6.50 67.0 6.50 77.0
250 281.9 419 72.6 279 34.5 165 19.6 165 30.4 165 34.9
12 13.200 19.00 210.0 12.00 92.0 7.50 72.0 7.50 108.0 7.50 120.0
300 335.3 483 95.3 305 41.7 191 32.7 191 49.0 191 54.4
14 15.300 21.50 261.0 14.00 174.0 7.50 104.0 7.50 92.0 7.50 101.0
350 388.6 546 118.4 356 78.9 191 47.2 191 41.7 191 45.8
16 17.400 24.00 337.0 15.00 239.0 8.00 142.0 8.00 112.0 8.00 121.0
400 442.0 610 152.9 381 108.4 203 64.4 203 50.8 203 54.9
18 19.500 26.50 451.0 16.50 328.0 8.50 186.0 8.50 145.0 8.50 146.0
450 495.3 673 204.6 419 148.8 216 84.4 216 65.8 216 66.2
20 21.600 29.00 588.0 18.00 413.0 9.50 246.0 9.50 200.0 9.50 202.0
500 548.6 737 266.7 457 187.3 241 111.6 241 90.7 241 91.6
24 25.800 34.00 909.0 22.00 668.0 11.00 414.0 11.00 282.0 11.00 284.0
600 655.3 864 412.3 559 303.0 279 187.8 279 127.9 279 128.8
30 32.000 41.50 2136.0 25.00 1002.0 15.00 720.0 15.00 681.0 15.00 699.0
750 762.0 1054 968.9 635 454.4 381 326.6 381 308.9 381 317.1
36 38.300 49.00 3120.0 28.00 1608.0 18.00 1152.0 18.00 975.0 18.00 1124.0
900 914.4 1245 1415.2 711 729.4 457 522.6 457 442.3 457 509.8
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com
4.1 DIMENSIONS
Tee, True Wye, Cross, Lateral, and Cap
No. 20-C Tee
No. 33-C True Wye
No. 35-C Cross
No. 30-C 45º Lateral
No. 60-C Cap
C to E
C to E C to LE
C to
LE
C T
LE
to
to
C to C to
C
E SE
SE
No. 20-C No. 33-C No. 35-C No. 30-C No. 60-C
No. 20-C No. 33-C No. 35-C No. 30-C No. 60-C
Size Tee True Wye Cross 45° Lateral Cap 1
Actual Approx. Approx. Approx. Approx. Approx.
Outside Weight Weight Weight Weight T Weight
Nominal Diameter C to E (Each) C to LE C to SE (Each) C to E (Each) C to LE C to SE (Each) Thickness (Each)
inches inches inches lb inches inches lb inches lb inches inches lb inches lb
DN mm mm kg mm mm kg mm kg mm mm kg mm kg
3 3.960 5.50 14.2 5.50 3.00 25.00 5.50 24.0 10.00 3.00 28.0 1.22 3.0
80 100.6 140 6.4 140 76 635 140 10.9 254 76 12.7 31 1.4
4 4.800 6.50 19.0 6.50 3.00 55.0 6.50 40.0 12.00 3.00 38.4 1.16 5.0
100 121.9 165 8.6 165 76 25.0 165 18.1 305 76 12.7 29 2.3
6 6.900 8.00 34.0 8.00 3.50 90.0 8.00 71.0 14.50 3.50 67.0 1.16 9.0
150 175.3 203 15.4 203 89 40.8 203 32.2 368 89 30.4 29 4.1
8 9.050 9.00 59.0 9.00 4.50 140.0 9.00 106.0 17.50 4.50 120.0 1.34 16.0
200 229.9 229 26.8 229 114 63.5 229 48.1 445 114 54.4 34 7.3
10 11.100 11.00 111.0 11.00 5.00 220.0 11.00 225.0 20.50 5.00 215.0 1.53 37.2
250 281.9 279 50.4 279 127 99.8 279 102.1 521 127 97.5 39 16.9
12 13.200 12.00 136.0 12.00 5.50 315.0 12.00 310.0 24.50 5.50 346.0 1.53 52.0
300 335.3 305 61.7 305 140 142.9 305 140.6 622 140 157.0 39 23.6
14 15.300 14.00 262.0 14.00 6.00 14.00 307.0 27.00 6.00 492.0 2.75 2 55.0
*
350 388.6 356 118.8 356 152 356 139.3 686 152 223.2 70 25.0
16 17.400 15.00 304.0 15.00 6.50 15.00 426.0 30.00 6.50 696.0 2.75 2 68.0
*
400 442.0 381 137.9 381 165 381 193.2 762 165 315.7 70 30.9
18 19.500 16.50 408.0 16.50 7.00 16.50 567.0 32.00 7.00 870.0 2.75 2 90.0
*
450 495.3 419 185.1 419 178 419 254.9 813 178 394.6 70 40.8
20 21.600 18.00 552.0 18.00 8.00 18.00 717.0 35.00 8.00 1103.0 2.75 2 110.0
*
500 548.6 457 250.4 457 203 457 325.2 889 203 500.3 70 50.0
24 25.800 22.00 980.0 22.00 9.00 22.00 1177.0 40.50 9.00 1746.0 2.75 2 165.0
*
600 655.3 559 444.5 559 229 559 533.9 1029 229 792.0 70 74.8
30 32.000 25.00 1552.0 25.00 10.00 25.00 1366.0 49.00 10.00 3280.0 4.00 2 300.0
*
750 762.0 635 704.0 635 254 635 619.6 1245 254 1487.8 102 136.1
36 38.300 28.00 2050.0 28.00 15.00 28.00 1885.0 56.00 15.25 5020.0 4.00 2 536.0
*
900 914.4 711 929.9 711 381 711 855.0 1422 387 2277.1 102 243.1
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 4
victaulic.com
4.2 DIMENSIONS
Bullhead Tee
No. 21-C
C to
EOR
C to
EOB
No. 21-C
Size Dimensions
Approximate
Nominal C to EOR C to EOB Weight Each
inches inches inches lb
DN mm mm kg
4 4 6 47.0
x x * *
100 100 150 21.3
6 6 8 8.00 800 79.0
x x
150 150 200 203 203 35.8
8 8 10 11.00 11.00 164.0
x x
200 200 250 279 279 74.4
10 10 12 226.0
x x * *
250 250 300 102.5
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 5
victaulic.com
4.3 DIMENSIONS
Reducing Fittings
No. 25-C Reducing Tee
No. 35-CR Reducing Cross
No. 30-CR 45º Reducing Lateral
C to E J
C to
LE
LE
J
to
to
C to
C
E SE
H H
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 6
victaulic.com
C to E J
C to
LE
LE
J
to
to
C to
C
E SE
H H
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 7
victaulic.com
C to E J
C to
LE
LE
J
to
to
C to
C
E SE
H H
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 8
victaulic.com
4.4 DIMENSIONS
Reducers and Reducing Elbows
No. 50-C Concentric Reducer
No. 51-C Eccentric Reducer
No. 10-CR 90º Reducing Elbow C to E
No. 100-CR 90º Long Radius Reducing Elbow
C to E
E to E E to E
No. 50-C No. 51-C No. 10-CR No. 10-CR 90° Long Radius
Size Concentric Reducer Eccentric Reducer 90° Reducing Elbow Reducing Elbow
Approx. Approx. Approx. Approx.
Weight Weight Weight Weight
Nominal E to E (Each) E to E (Each) C to E (Each) C to E (Each)
inches inches lb inches lb inches lb inches lb
DN mm kg mm kg mm kg mm kg
4 3 7.00 10.0 7.00 12.0 6.50 17.0 9.00 20.0
x
100 80 178 4.5 178 5.4 165 7.7 229 8.1
6 3 9.00 15.0 9.00 20.0 8.00 28.5 11.50 36.0
x
150 80 229 6.8 229 9.1 203 12.9 292 16.3
4 9.00 16.5 9.00 25.0 8.00 29.6 11.50 40.0
100 229 7.5 229 11.3 203 13.4 292 18.1
8 3 11.00 33.0 11.00
x * — — — —
200 80 279 15.0 279
4 11.00 28.0 11.00 35.0 9.00 46.5 14.00 60.0
100 279 12.7 279 15.9 229 21.1 356 27.2
6 11.00 34.0 11.00 44.0 9.00 48.5 14.00 71.0
150 279 15.4 279 20.0 229 22.0 356 32.2
10 4 12.00 42.0 12.00 54.0 11.00 68.0 16.50 90.0
x
250 100 305 19.1 305 24.5 279 30.8 419 40.8
6 12.00 46.0 12.00 60.0 11.00 77.0 16.50 106.0
150 305 20.9 305 27.2 279 34.9 419 48.1
8 12.00 50.0 12.00 70.0 11.00 88.0 16.50 121.0
200 305 22.7 305 31.8 279 39.9 419 54.9
12 4 14.00 60.0 14.00 82.0 12.00
x * * *
300 100 356 27.2 356 37.2 305
6 14.00 70.0 14.00 84.0 12.00 110.0 19.00 143.0
150 356 31.8 356 38.1 305 49.9 483 64.9
8 14.00 74.0 14.00 91.0 12.00 126.0 19.00 163.0
200 356 33.6 356 41.3 305 57.2 483 73.9
10 14.00 84.0 14.00 110.0 12.00 150.0 19.00 188.0
250 356 38.1 356 49.9 305 68.0 483 85.3
14 6 16.00 89.0 16.00 104.0 14.00
x * * *
350 150 406 40.4 406 47.2 356
8 16.00 102.0 16.00 121.0 14.00 135.0 21.50 183.0
200 406 46.3 406 54.9 356 61.2 546 83.0
10 16.00 112.0 16.00 135.0 14.00 170.0 21.50 213.0
250 406 50.8 406 61.2 356 77.1 546 96.6
12 16.00 126.0 16.00 150.0 14.00 195.0 21.50 240.0
300 406 57.4 406 68.0 356 88.5 546 108.9
16 6 18.00 11.0 18.00 140.0
x — — * *
400 150 457 49.9 457 63.5
8 18.00 122.0 18.00 160.0 15.00 24.00 228.0
*
200 457 55.3 457 72.6 381 610 103.4
10 18.00 135.0 18.00 168.0 15.00 195.0 24.00 263.0
250 457 61.2 457 76.2 381 88.5 610 119.3
12 18.00 146.0 18.00 190.0 15.00 240.0 24.00 295.0
300 457 66.2 457 86.2 381 108.9 610 133.8
14 18.00 173.0 18.00 210.0 15.00 280.0 24.00 290.0
350 457 78.5 457 95.3 381 127.0 610 131.5
* Contact Victaulic for details.
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 9
victaulic.com
E to E E to E
No. 50-C No. 51-C No. 10-CR No. 10-CR 90° Long Radius
Size Concentric Reducer Eccentric Reducer 90° Reducing Elbow Reducing Elbow
Approx. Approx. Approx. Approx.
Weight Weight Weight Weight
Nominal E to E (Each) E to E (Each) C to E (Each) C to E (Each)
inches inches lb inches lb inches lb inches lb
DN mm kg mm kg mm kg mm kg
18 8 19.00 148.0 19.00 180.0 16.50
x * — —
450 200 483 67.1 483 81.6 419
10 19.00 158.0 19.00 215.0 16.50 26.50
* *
250 483 71.1 483 97.5 419 673
12 19.00 173.0 19.00 215.0 16.50 305.0 26.50 336.0
300 483 78.5 483 97.5 419 138.3 673 152.4
14 19.00 200.0 19.00 230.0 16.50 345.0 26.50 355.0
350 483 90.7 483 104.3 419 156.5 673 161.0
16 19.00 220.0 19.00 275.0 16.50 360.0 26.50 386.0
400 483 100.0 483 124.7 419 163.3 673 175.1
20 8 20.00 173.0 20.00
x * — — — —
500 200 508 78.5 508
10 20.00 182.0 20.00 215.0 18.00 29.00
* *
250 508 82.6 508 97.5 457 737
12 20.00 201.0 20.00 250.0 18.00 365.0 29.00
*
300 508 91.2 508 113.4 457 165.6 737
14 20.00 230.0 20.00 270.0 18.00 405.0 29.00
*
350 508 104.3 508 122.5 457 183.7 737
16 20.00 251.0 20.00 300.0 18.00 440.0 29.00 466.0
400 508 113.9 508 136.1 457 199.6 737 211.4
18 20.00 275.0 20.00 320.0 18.00 485.0 29.00 507.0
450 508 124.7 508 145.2 457 220.0 737 230.0
24 8 24.00 257.0 24.00 300.0
x * * * *
600 200 610 116.6 610 136.1
10 24.00 274.0 24.00 300.0
* * * *
250 610 124.3 610 136.1
12 24.00 293.0 24.00 395.0 22.00 590.0 34.00
*
300 610 132.9 610 179.2 559 267.6 864
14 24.00 331.0 24.00 425.0 22.00 630.0 34.00
*
300 610 150.1 610 192.8 559 285.8 864
16 24.00 358.0 24.00 455.0 22.00 690.0 34.00 658.0
400 610 162.4 610 206.4 559 313.0 864 298.5
18 24.00 386.0 24.00 465.0 22.00 735.0 34.00
*
450 610 175.1 610 210.9 559 333.4 864
20 24.00 418.0 24.00 525.0 22.00 815.0 34.00 759.0
500 610 189.6 610 238.1 559 369.7 864 344.3
* Contact Victaulic for details.
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 10
victaulic.com
E to E E to E
No. 50-C No. 51-C No. 10-CR No. 10-CR 90° Long Radius
Size Concentric Reducer Eccentric Reducer 90° Reducing Elbow Reducing Elbow
Approx. Approx. Approx. Approx.
Weight Weight Weight Weight
Nominal E to E (Each) E to E (Each) C to E (Each) C to E (Each)
inches inches lb inches lb inches lb inches lb
DN mm kg mm kg mm kg mm kg
30 8
x * * * * * * — —
750 200
10
* * * * * * — —
250
12 30.00 30.00
* * * * — —
300 762 762
14 30.00 30.00 25.50
* * * — —
350 762 762 635
16 30.00 30.00 25.50 41.50
* * * *
400 762 762 635 1054
18 30.00 30.00 25.50 41.50
* * * *
450 762 762 635 1054
20 30.00 30.00 25.50 41.50
* * * *
500 762 762 635 1054
24 30.00 30.00 25.50 1170.0 41.50
* * *
600 762 762 635 530.7 1054
36 8
x * * * * * * — —
900 200
10
* * * * * * — —
250
12
* * * * * * — —
300
14 36.00 36.00
* * * * — —
350 914 914
16 36.00 36.00
* * * * — —
400 914 914
18 36.00 36.00
* * * * — —
450 914 914
20 36.00 1280.0 36.00 49.00
* * * *
500 914 580.6 914 1245
24 36.00 1370.0 36.00 49.00
* * * *
600 914 621.4 914 1245
30 36.00 1450.0 36.00 49.00
* * * *
750 914 657.7 914 1245
* Contact Victaulic for details.
NOTE
• Non-standard reducing cross sizes are available. Contact Victaulic for details.
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 11
victaulic.com
4.5 DIMENSIONS
Base Fittings
No. 10-CB Base Elbow
No. 20-CB Base Tee
No. 25-CB Reducing Base Tee
No. 100-CB Long Radius Base Elbow
C to E
C to E
C to C to E
E
C C
C to C to to to
E E E E
R R R R W
U U U U
T S T S T S T S S
No. 10-CB No. 20-CB No. 25-CB No. 100-CB Round Base
+ 9 0° reducing elbows are available with a base. Contact Victaulic for details.
NOTES
• Bolt hole template shown for round base is the same as for the flange of the supporting pipe size, except using only four holes in all cases so placed as to
straddle center lines.
• The bases of these fittings are intended for support in compression and are not to be used for anchors or supports in tension or sheer.
• Grooved end base 90° elbows (#X-90 CDI) and base tees (#X-CDI) are available with dimensions to ANSI B16.1.
• Side base fittings are available. Contact Victaulic for details.
• For Center to End dimensions, refer to corresponding fitting without the base.
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 12
victaulic.com
4.6 DIMENSIONS
Tee, True Wye, Cross, Lateral, and Cap
No. 10-CF 90º Flare
No. 100-CF 90º Long Radius Flare
No. 43-CF Straight Flare
No. 10-CS 90º Side Outlet
No. 20-CS Tee Side Outlet
C to E
C to E
C to E C to E
C
C to E
to F to
F E
No. 10-CF No. 100-CF No. 43-CF No. 10-CS No. 20-CS
No. 10-CF No. 100-CF No. 43-CF No. 10-CS No. 20-CS
Size 90° Flare 90° Long Radius Flare Straight Flare 90° Side Outlet 3 Tee Side Outlet 3
Actual Approx. Approx. Approx. Approx. Approx.
Outside Weight Weight Weight Weight Weight
Nominal Diameter C to E C to F (Each) C to E C to F (Each) E to E (Each) C to E (Each) C to E (Each)
inches inches inches inches lb inches inches lb inches lb inches lb inches lb
DN mm mm mm kg mm mm kg mm kg mm kg mm kg
3 3.960 5.50 9.00 18.0 7.75 11.25 23.00 8.00 13.0 5.50 13.0 5.50 28.0
80 100.6 140 229 8.2 197 286 10.4 203 5.9 140 5.9 140 12.7
4 4.800 6.50 9.50 35.0 9.00 12.50 42.0 8.00 17.0 6.50 30.0 6.50 42.0
100 121.9 165 241 15.9 229 318 19.1 203 7.7 165 13.6 165 19.1
6 6.900 8.00 11.50 70.0 11.50 15.00 68.0 8.00 23.0 8.00 58.0 8.00 85.0
150 175.3 203 292 31.8 292 381 30.9 203 10.4 203 26.3 203 38.6
8 9.050 9.00 13.50 120.0 14.00 18.50 118.0 10.00 43.0 9.00 90.0 9.00 114.0
200 229.9 229 343 54.4 356 470 53.5 254 19.5 229 40.8 229 51.7
10 11.100 11.00 16.50 157.0 16.50 22.50 188.0 10.00 58.0 11.00 124.0 11.00 219.0
250 281.9 279 419 71.2 419 572 85.3 254 26.3 279 56.3 279 99.3
12 13.200 12.00 18.50 190.0 19.00 25.50 275.0 12.00 100.0 12.00 170.0 12.00 295.0
300 335.3 305 470 86.2 483 648 124.7 305 45.4 305 77.1 305 133.8
14 15.300 14.00 21.50 235.0 21.50 29.00 325.0 12.00 90.0 14.00
* * *
350 388.6 356 546 106.6 546 737 147.4 305 40.8 356
16 17.400 15.00 23.00 300.0 24.00 32.00 435.0 16.00 145.0 15.00
* * *
400 442.0 381 584 136.1 610 813 197.3 406 65.8 381
18 19.500 16.50 25.00 391.0 26.50 35.00 571.0 16.00 205.0 16.50
* * *
450 495.3 419 635 177.4 673 889 259.0 406 93.0 419
20 21.600 18.00 27.00 496.0 29.00 38.00 731.0 18.00 221.0 18.00
* * *
500 548.6 457 686 255.0 737 965 331.6 457 100.3 457
24 25.800 22.00 32.50 808.0 34.00 44.50 1642.0 18.00 293.0 22.00
* * *
600 655.3 559 826 366.5 864 1130 744.8 457 132.9 559
30 32.000 24.00 567.0
* * * * * * * * * *
750 762.0 610 257.2
36 38.300 24.00 736.0
* * * * * * * * * *
900 914.4 610 333.0
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 13
victaulic.com
5.0 PERFORMANCE
Contact Victaulic for details.
6.0 NOTIFICATIONS
WARNING
• Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic piping products.
• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any Victaulic piping products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury and property damage.
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 14
victaulic.com
R R R R
H L
X Y Z
E Y Y K
S S Z Y X
G M E G M K
F N F N
T T T T F G H NM K
T S R R S T
90° ELBOW – STRAIGHT SIZE TEE – STRAIGHT SIZES ECCENTRIC REDUCER
S E K
G M
F H L N
G M
T R R T
F H N K
90° ELBOW BASE TEE CONCENTRIC REDUCER
H L
R R G M
E S S K E J P K
F N
G F T T N M
R V V R
Y Y
E H L K
E G M K G M
F T T N F N
R R
H L
R R E K
G E K M G M
S S
F N
F T N
T
90° BASE ELBOW – STRAIGHT & REDUCING 45° LATERAL – STRAIGHT & REDUCING
23.05 1680 Rev J Updated 06/2017 © 2017 Victaulic Company. All rights reserved.
victaulic.com 15
Victaulic® Grooved Coupling
Style 31 23.02
Patented
2.0 CERTIFICATION/LISTINGS
Coupling design, materials and testing conform to the requirements of AWWA C606 standard for Grooved and
Shouldered Joints.
NOTES
• Refer to Victaulic publication 10.01 for details
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
23.02 1656 Rev K Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
1
victaulic.com
23.02 1656 Rev K Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com
4.0 DIMENSIONS
Style 31
Y Z
Y Z
Y Z
X X
X
23.02 1656 Rev K Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com
5.0 PERFORMANCE
Style 31
Pipe End
Size Separation4 Deflect FR. CL4
Actual Maximum Maximum
Outside Joint Working Permis.
Nominal Diameter Allowable Per Pipe Pressure5 End Load5
inches inches inches Cplg. In./Ft. psi lb
DN mm mm Degree mm kPa N
3 3.960 0 - 0.09 0.28 500 6200
1° - 21´
DN80 100.6 0 - 2.4 23 3450 27590
4 4.800 0 - 0.09 0.21 500 9000
1° - 8´
DN100 121.9 0 - 2.4 17 3450 40050
6 6.900 0 - 0.09 0.14 400 14950
0° - 47´
DN150 175.3 0 - 2.4 12 2750 66528
8 9.050 0 - 0.09 0.11 400 25600
0° - 36´
DN200 229.9 0 - 2.4 9 2750 113920
10 11.100 0 - 0.16 0.15 350 33850
0° - 48´
DN250 281.9 0 - 4.0 13 2410 150632
12 13.200 0 - 0.16 0.13 350 47.900
0° - 41´
DN300 335.3 0 - 4.0 11 2410 21150
14 15.300 0 - 0.16 0.11 250 45950
0° - 35´
DN350 388.6 0 - 4.0 9 1725 204470
16 17.400 0 - 0.25 0.16 250 59400
0° - 49´
DN400 442.0 0 - 6.4 13 1725 264330
18 19.500 0 - 0.25 0.14 250 74650
0° - 44´
DN450 495.3 0 - 6.4 12 1725 332190
20 21.600 0 - 0.25 0.12 150 54900
0° - 40´
DN500 548.6 0 - 6.4 10 1035 244305
24 25.800 0 - 0.25 0.11 150 78.400
0° - 33´
DN600 655.3 0 - 6.4 9 1035 34880
30 32.000 0 - 0.47 0.17 150 120570
0° - 51´
DN750 812.8 0 - 11.9 14 1035 536530
36 38.300 0 - 0.47 0.15 150 172815
0° - 47´
DN900 972.8 0 - 11.9 13 1035 769030
4 Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for pipe prepared to flexible cut
grooved specifications. Pipe cut grooved to rigid cut grooved specifications does not permit expansion and contraction.
5 Working Pressure and End Load are total, from all internal and external loads, based on AWWA class 53 or higher ductile iron pipe radius cut grooved in
accordance with Victaulic published radius cut groove dimensions.
NOTE
• WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 ½ times the figures shown.
23.02 1656 Rev K Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
victaulic.com 4
victaulic.com
6.0 NOTIFICATIONS
WARNING
• Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic piping products.
• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any Victaulic piping products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury and property damage.
23.02 1656 Rev K Updated 09/2019 © 2019 Victaulic Company. All rights reserved.
victaulic.com 5
MALLEABLE IRON FITTINGS
PF-11.13
MALLEABLE IRON FITTINGS
Class 150 (Standard)
Note: See following page for pressure-temperature ratings. Galvanized weights may vary. Please contact your Anvil Representative if you need verification.
All Elbows & Tees 3/8" (10 DN) and Larger are 100% Gas Tested at a Minimum of 100 PSI. (6.9 bar)
PF-11.13
NYCT Contract A-36164
Design-Build Service for Accessibility Upgrade at the 68th St-Hunter College Station
REVISION : 0
DATE : 8/11/22
NOTES OR COMMENTS :
REVIEWER'S REMARKS:
1. Installation of dry fire standpipe
and fittings shall be in accordance
to Part 3 (Execution) of the
specifications.
2. Pipe 3” and above shall be Class
53 AWWA ductile iron pipe
Schedule 80 galvanized steel.
3. Pipes under 3” shall be Schedule
80 galvanized steel. Galvanized
CONTRACTOR SUBMITTAL pipe shall be hot-dip
GANNETT FLEMING galvanized in accordance with
ASTM A153 or zinc electroplated in
Review is for general compliance with contract documents. Sole
responsibility for correctness of dimensions, details, quantities, accordance
and safety during fabrication and erection shall remain with the with ASTM B633. Resubmit with
Contractor.
appropriate schedule of piping.
Accepted Other 4. Dry Standpipe piping is used to
Accepted as noted
Resubmit as noted connect to fire hose valves.
Rejected Sprinkler piping is not in scope of
By Fakhri Ahmad Date 08/17/22 project.
FCJV – JOINT VENTURE
This certifies that we have reviewed this Submittal and to the best of our
knowledge the contents are in compliance with the Contract Documents
( A-36164 )
Design-Build Services for Accessibility Upgrades at the 68th Street- Hunter College Station
A-36164
Forte Construction
926 Lincoln Ave,
Holbrook, New York 11741
Schedule 40 galvanized steel with victaulic grooved fittings. Threaded fittings will be used as
needed to connect to threaded Angle Hose Valve
BRIAN GOTTLIEB
8/3/2022
Fire Sprinkler Pipe
A53 Schedule 40
Submittal Data Sheet
SUBMITTAL INFORMATION
LOCATIONS: COMMENTS:
WFS-052820
Available Sizes
• 1 ¼ – 8"/DN32 – DN200
Maximum Working Pressure
• Pressure ratings for Victaulic FireLock™ Fittings conform to the ratings of Victaulic FireLock EZ™ Style 009N
couplings (refer to publication 10.64 for more information).
Application
• FireLock™ fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for
Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference.
• Connects pipe, provides change in direction and adapts sizes or components
Pipe Materials
• Carbon steel
2.0 CERTIFICATION/LISTINGS
EN 10311
Regulation (EU)
No. 305/2011
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
10.03 01539 Rev O Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
1
victaulic.com
4.0 DIMENSIONS
C to E C
to E
C to E
T
C C
to
to E E
10.03 01539 Rev O Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com
5.0 PERFORMANCE
Flow Data
10.03 01539 Rev O Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com
6.0 NOTIFICATIONS
General Notes
NOTE: When assembling FireLock EZ™ couplings onto end caps, take additional care to make certain the end cap is
fully seated against the gasket end stop. For FireLock EZ™ Style 009N/009H couplings, use FireLock™ No. 006 end
caps containing the “EZ” marking on the inside face or No. 60 end caps containing the “QV EZ” marking on the
inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H/009N couplings.
10.03 01539 Rev O Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 4
Victaulic® FireLock™ Installation-Ready™ Rigid Couplings
Style 009N and Style 109 10.64
Patented Patented
Available Sizes
• Style 009N: 1 ¼ – 12"/DN32 – DN300
• Style 109: 1 ¼ – 4"/DN32 – DN100
Pipe Material
• Schedule 10, Schedule 40 or specialty carbon steel pipe listed in Section 5. For use with alternative materials and
wall thicknesses please contact Victaulic
• For exceptions reference section 6.0 Notifications
Maximum Working Pressure
• Accommodates pressures ranging from full vacuum (29.9 in Hg/760 mm Hg) to 365 psi/2517 kPa
Function
• Joins carbon steel pipe with grooved ends conforming to publication 25.01
• Provides a rigid pipe joint designed to restrict axial or angular movement
2.0 CERTIFICATION/LISTINGS
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
1
victaulic.com
Coupling Linkage: High Strength Steel with comparable physical properties to that of the Track Bolt (ASTM A449).
Linkage is zinc electroplated per ASTM B633 Fe/Zn 5, Type III Finish.
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com
4.0 DIMENSIONS
Style 009N Two-Bolt Installation-Ready Coupling
Y Z Y Z
X X
4" FSP must be
ductile iron
Style 009N Pre-Assembled Style 009N Joint Assembled
NOTES
• When assembling Style 009N or Style 109 couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end
stop. For Style 009N or Style 109 couplings, use FireLock No. 006 end caps containing the “EZ” marking on the inside face or No. 60 end caps containing the
“QV EZ” marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009N or Style 109 couplings. IMPORTANT: Gaskets intended
for the Style 009 or Style 009V couplings cannot be used with the Style 009N or Style 109 coupling. There is no interchanging of gaskets or housings between
coupling styles.
• Use Of FlushSeal Gaskets For Dry Pipe Systems Style 009N or Style 109 couplings are supplied with Grade “E” Type A gaskets. These gaskets include an
integral pipe stop, that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems. It should be noted that standard Victaulic
FlushSeal gaskets cannot be used with the Style 009N or Style 109 couplings.
• The Allowable Pipe End Separation dimension shown is for system layout purposes only. Style 009N or Style 109 Installation-Ready rigid couplings are
considered rigid connections and will not accommodate expansion/contraction or angular movement of the piping system. Contact Victaulic for torsional
resistance information.
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com
4.1 DIMENSIONS
Style 109 One-Bolt Installation-Ready Coupling
YB Z
Z YL
YL YB
X X
4 orking Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in
W
accordance with Victaulic specifications. See the Listings/Approvals section of this publication for ratings on other pipe.
5 The allowable pipe separation dimension shown is for system layout purposes only. Style 109 couplings are considered rigid connections and will not
accommodate expansion or contraction of the piping system.
NOTES
• When assembling Style 009N or Style 109 couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end
stop. For Style 009N or Style 109 couplings, use FireLock No. 006 end caps containing the “EZ” marking on the inside face or No. 60 end caps containing the
“QV EZ” marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009N or Style 109 couplings. IMPORTANT: Gaskets intended
for the Style 009 or Style 009V couplings cannot be used with the Style 009N or Style 109 coupling. There is no interchanging of gaskets or housings between
coupling styles.
• Use Of FlushSeal Gaskets For Dry Pipe Systems Style 009N or Style 109 couplings are supplied with Grade “E” Type A gaskets. These gaskets include an
integral pipe stop, that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems. It should be noted that standard Victaulic
FlushSeal gaskets cannot be used with the Style 009N or Style 109 couplings.
• The Allowable Pipe End Separation dimension shown is for system layout purposes only. Style 009N or Style 109 Installation-Ready rigid couplings are
considered rigid connections and will not accommodate expansion/contraction or angular movement of the piping system. Contact Victaulic for torsional
resistance information.
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 4
victaulic.com
5.0 PERFORMANCE
Style 009N Two-Bolt Installation-Ready Coupling Listings/Approvals6
The information provided below is based on the latest listing and approval data at the time of publication.
Listings/Approvals are subject to change and/or additions by the approval agencies. Contact Victaulic for performance
on other pipe and the latest listings and approvals.
Size cULus FM VdS LPCB
Actual Outside
Nominal Diameter Sch. 10 Sch. 40 Sch. 10 Sch. 40
psi psi psi psi psi psi
inches inches kPa kPa kPa kPa kPa kPa
DN mm bar bar bar bar bar bar
365 365 363 363 363 363
1 1/4 1.660
2517 2517 2503 2503 2500 2500
DN32 42.4
25 25 25 25 25 25
365 365 363 363 363 363
1 1/2 1.900
2517 2517 2503 2503 2500 2500
DN40 48.3
25 25 25 25 25 25
365 365 363 363 363 363
2 2.375
2517 2517 2503 2503 2500 2500
DN50 60.3
25 25 25 25 25 25
365 365 363 363 – 363
2.875
2 1/2 2517 2517 2503 2503 – 2500
73.0
25 25 25 25 – 25
365⁷ – 363⁸ – 363 363
3.000
DN65 2517⁷ – 2503⁸ – 2500 2500
76.1
25⁷ – 25⁸ – 25 25
365 365 363 363 363 363
3 3.500
2517 2517 2503 2503 2500 2500
DN80 88.9
25 25 25 25 25 25
– – 363 363 – –
4.250
– – 2503 2503 – –
108.0
– – 25 25 – –
365 365 363 363 363 363
4 4.500
2517 2517 2503 2503 2500 2500
DN100 114.3
25 25 25 25 25 25
– – 363⁸ – – –
5.250
– – 2503⁸ – – –
133.0
– – 25⁸ – – –
290⁹ – 363⁸ – 232 363
5.500
DN125 2000⁹ – 2503⁸ – 1600 2500
139.7
20⁹ – 25⁸ – 16 25
290 365 363 363 232 363
5.563
5 2000 2517 2503 2503 1600 2500
141.3
20 25 25 25 16 25
– – 363⁸ – – –
6.250
– – 2503⁸ – – –
159
– – 25⁸ – – –
290¹⁰ – 363⁸ – – 363
6.500
2000¹⁰ – 2503⁸ – – 2500
165.1
20¹⁰ – 25⁸ – – 25
6 Listed/Approved for continuous use in wet and dry systems. Listed/Approved for dry systems -40° F/C and above. Please see the Victaulic Installation
Manual I-009N for details concerning when supplemental lubrication is required.
7 cULus listed for DIN 2458 (EN 10220) 2.6 mm pipe wall.
8 FM approved for BS 1387 (EN 10255) Medium 3.6 mm pipe wall.
9 cULus listed for EN 10220 4.0 mm pipe wall.
10 cULus listed for EN 10255 4.5 mm pipe wall.
11 With optional stainless steel fasteners, cULus Listed to 175psi/1207 kPa/12 bar and FM Approved to the FM ratings shown in the above table. The stainless
steel fasteners have a marking designation of "316" on the end face of the bolt.
12 FM approved for 0.188" pipe wall.
13 cULus listed for 0.188" pipe wall.
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 5
victaulic.com
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 6
victaulic.com
5.1 PERFORMANCE
Style 109 One-Bolt Installation-Ready Coupling Listings/Approvals15
The information provided below is based on the latest listing and approval data at the time of publication. Listings/
Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on
other pipe and the latest listings and approvals.
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 7
victaulic.com
5.2 PERFORMANCE
Specialty Pipe
Style 009N Two-Bolt Installation-Ready Coupling Listings/Approvals
NOTES
• EF = EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • MT = Mega-Thread steel pipe manufactured by Wheatland Tube Co.
• EL = EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • MLT = MLT steel pipe manufactured by Wheatland Tube Co
• ET40 = Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • TF = Tex-Flow steel pipe manufactured by Tex-Tube Co.
• EZF = EZ-Flow steel pipe manufactured by Northwest Pipe Co. • WG5, WG5E, WF5 = WGalweld 5, WGalweld 5E, WFlow 5 steel pipe
• EZT = EZ-Thread steel pipe manufactured by Youngstown Tube Co. manufactured by Wuppermann Stahl GmbH.
• FF = Fire-Flo steel pipe manufactured by Youngstown Tube Co. • WG7, WG7E, WL7 = WGalweld 7, Wgalweld 7E, WLight 7 steel pipe
manufactured by Wuppermann Stahl GmbH
• GL = GL steel pipe manufactured by Wheatland Tube Co.
• WLS = WLS steel pipe manufactured by Wheatland Tube Co.
• MF = Mega-Flow steel pipe manufactured by Wheatland Tube Co.
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 8
victaulic.com
5.3 PERFORMANCE
Specialty Pipe
Style 109 One-Bolt Installation-Ready Coupling Listings/Approvals
Size Pressure Rating
cULus FM
inches psi psi
kPa kPa
Pipe Type DN bar bar
300
1 ¼ – 2 ½
N/A 2068
DN32 – 73.0 mm
20
300
1 ½ – 2 ½
EF 2068 N/A
DN40 – 73.0 mm
20
300 300
3–4
2068 2068
DN80 – DN100
20 20
300
1 ¼ – 2
N/A 2068
DN32 – DN50
20
Easy-Flow
300
3–4
N/A 2068
DN80 – DN100
20
300
1 ¼ – 2
EL N/A 2068
DN32 – DN50
20
300 300
1 ¼ – 2
ET40 2068 2068
DN32 – DN50
20 20
300
1 ¼ – 2
N/A 2068
DN32 – DN50
20
EZT
300
1 ½ – 2
2068 N/A
DN40 – DN50
20
300 300
1 ½ – 4
FF 2068 2068
DN40 – DN100
20 20
300
1 ¼ – 2
GL N/A 2068
DN32 – DN50
300 300
1 ¼ – 4
MF 2068 2068
DN32 – DN100
20 20
300 300
1 ¼ – 2
MT 2068 2068
DN32 – DN50
20 20
300 300
1 ¼ – 2
MLT 2068 2068
DN32 – DN50
20 20
NOTES
• EF = EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • GL = GL steel pipe manufactured by Wheatland Tube Co.
• Easy-Flow = Easy-Flow steel pipe manufactured by Borusan Mannesmann • MF = Mega-Flow steel pipe manufactured by Wheatland Tube Co.
Boru. • MT = Mega-Thread steel pipe manufactured by Wheatland Tube Co.
• EL = EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • MLT = MLT steel pipe manufactured by Wheatland Tube Co.
• ET40 = Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • TF = Tex-Flow steel pipe manufactured by Tex-Tube Co.
• EZT = EZ-Thread steel pipe manufactured by Youngstown Tube Co. • WG7, WG7E = WGalweld 7 and WGalweld 7E steel pipe manufactured by
• FF = Fire-Flo steel pipe manufactured by Youngstown Tube Co. Wuppermann Stahl GmbH.
• WLS = WLS steel pipe manufactured by Wheatland Tube Co.
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 9
victaulic.com
NOTES
• EF = EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • GL = GL steel pipe manufactured by Wheatland Tube Co.
• Easy-Flow = Easy-Flow steel pipe manufactured by Borusan Mannesmann • MF = Mega-Flow steel pipe manufactured by Wheatland Tube Co.
Boru. • MT = Mega-Thread steel pipe manufactured by Wheatland Tube Co.
• EL = EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • MLT = MLT steel pipe manufactured by Wheatland Tube Co.
• ET40 = Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • TF = Tex-Flow steel pipe manufactured by Tex-Tube Co.
• EZT = EZ-Thread steel pipe manufactured by Youngstown Tube Co. • WG7, WG7E = WGalweld 7 and WGalweld 7E steel pipe manufactured by
• FF = Fire-Flo steel pipe manufactured by Youngstown Tube Co. Wuppermann Stahl GmbH.
• WLS = WLS steel pipe manufactured by Wheatland Tube Co.
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 10
victaulic.com
6.0 NOTIFICATIONS
WARNING
• Read and understand all instructions before attempting to install any Victaulic
products.
• Always verify that the piping system has been completely depressurized and
drained immediately prior to installation, removal, adjustment, or maintenance of
any Victaulic products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury
and property damage.
• These products shall be used only in fire protection systems that are designed and installed in accordance with current, applicable
National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with applicable
building and fire codes. These standards and codes contain important information regarding protection of systems from freezing
temperatures, corrosion, mechanical damage, etc.
• The installer shall understand the use of this product and why it was specified for the particular application.
• The installer shall understand common industry safety standards and potential consequences of improper product installation.
• It is the system designer's responsibility to verify suitability of materials for use with the intended fluid media within the piping system
and external environment.
• The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level,
and flow rate on materials to confirm system life will be acceptable for the intended service.
Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause
system failure, resulting in death or serious personal injury and property damage.
NOTICE
• Victaulic does not recommend the use of any furnace butt-welded pipe with sizes 2"/DN50 and smaller Victaulic
gasketed joint products. This includes, but is not limited to, ASTM A53 Type F pipe.
10.64 07072 Rev R Updated 10/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 11
MALLEABLE IRON FITTINGS
Class 150 (Standard)
Note: See following page for pressure-temperature ratings. Galvanized weights may vary. Please contact your Anvil Representative if you need verification.
All Elbows & Tees 3/8" (10 DN) and Larger are 100% Gas Tested at a Minimum of 100 PSI. (6.9 bar)
PF-11.13
MALLEABLE IRON FITTINGS
General Assembly of Threaded Fittings
1) Inspect both male and female components prior to assembly.
• Threads should be free from mechanical damage, dirt, chips and excess cutting oil.
• Clean or replace components as necessary.
2) Application of thread sealant
• Use a thread sealant that is fast drying, sets-up to a semi hard condition and is vibration resistant. Alternately, an anaerobic
sealant may be utilized.
• Thoroughly mix the thread sealant prior to application.
• Apply a thick even coat to the male threads only. Best application is achieved with a brush stiff enough to force sealant down
to the root of the threads.
3) Joint Makeup
• For sizes up to and including 2" pipe, wrench tight makeup is considered three full turns past handtight. Handtight engagement
for 1⁄2" through 2" thread varies from 41⁄2 turns to 5 turns.
• For 2 1⁄2" through 4" sizes, wrench tight makeup is considered two full turns past handtight. Handtight engagement for 2 1⁄2"
through 4" thread varies from 51⁄2 turns to 63⁄4 turns.
PF-11.13