TR-7578-C Wiring Diagram

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Aux.

Supply 28
90-270 VAC/DC Aux. Supply
29
NC 30 PECON - WTI/SCANNER RS-485 73 MODBUS RTU
31 TR-7578-C OUTPUT 72 PROTOCOL
32 71 (Also ref. Annexure-4)
33
34
35
36 REMOTE 26
-
Aux.
37 OUTPUT 25 Supply
+
38
SUPPLY

4-20 mA Remote Indicator


39 RTD-1 RTD-2 RTD-3 RTD-4 RTD-5 RTD-6 RTD-7 RTD-8 (RWTI-400 or Equivalent)
40
41
42
Contactor

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
for Fan

Alarm

Use
Fault
Coil
Trip

2.5 mm2 Teflon covered


copper wires
for extension
To transformer for temperature monitoring
3 RTDs for top of the windings
3 RTDs for bottom of the windings
1 for core and
Note : Fault relay is normally in energized state. 1 2 3
It de-energizes on Fault condition. 1 for Ambient or spare

White Red

Note : 1) Numbers in are terminal nos. on TR-7578-C.


Pt-100
Terminal nos. 27 and 43 to 70 do not exist
2) Remote output can be programmed for either
any one of the channels or to correspond
to the maximum temperature being monitored RTD-1 CONNECTIONS
TO TR-7578-C

4 Alarm / Hooter AL-03 1 Annunciator / RTCC


3 Remote Indicator RWTI-400 1 Optional on RTCC ANNEXURE - 3
Embended in
2 RTD Pt-100 S-02 8
Trafo. windings
CONNECTION DIAGRAM
FOR
1 WTI/Scanner TR-7578-C 1 Marshalling Box
WTI-SCANNER TR-7578-C
Sr.No. Item Type No. Qty. Location.

You might also like