DSEGenset®

DSE7310/20 MKII SPECIFICATIONS

DC SUPPLY

AUTO START & AUTO MAINS FAILURE CONTROL MODULES


CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
5 V for upto 1 minute

CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing
supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT


510 mA at 12 V, 240 mA at 24 V

MAXIMUM STANDBY CURRENT


330 mA at 12 V, 160 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

GENERATOR & MAINS (UTILITY)


VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
KEY FEATURES • Unbalanced load protection • Start & stop capability via SMS
• Configurable power-up mode • Independent earth fault protection messaging FREQUENCY RANGE
• MPU fail delay • Breaker control via fascia buttons • 3 configurable maintenance alarms 3.5 Hz to 75 Hz
• Enhanced graphical user interface • Fuel and start outputs configurable • Compatible with a wide range of MAGNETIC PICKUP
• Drag & drop advanced PLC editor when using CAN CAN engines, including tier 4 VOLTAGE RANGE
• MSC ID within PLC GenComm • 6 configurable DC outputs engine support +/- 0.5 V to 70 V
override • 2 configurable volt-free relay • Uses DSE Configuration Suite PC FREQUENCY RANGE
• 4-Line back-lit LCD text display outputs Software for simplified 10,000 Hz (max)
• Multiple Display Languages • 6 configurable analogue/digital configuration
INPUTS
• Five key menu navigation inputs • Licence-free PC software DIGITAL INPUTS A TO H
• LCD alarm indication • Support for 0 V to 10 V & 4 mA to • IP65 rating (with supplied gasket) Negative switching
• Heated display option available 20 mA sensors offers increased resistance to water ANALOGUE INPUTS A & F
• Customisable power-up text and • 8 configurable digital inputs ingress Configurable as:
images • Configurable 5 stage dummy load • Modules can be integrated into Negative switching digital input
0 V to 10 V sensor
• DSENet expansion compatibility and load shedding outputs building management systems 4 mA to 20 mA sensor
• Data logging facility • CAN, MPU and alternator (BMS) using MODBUS RTU Resistive sensor
• Internal PLC editor frequency speed sensing in one
ANALOGUE INPUTS B, C, D & E
• Protections disable feature variant KEY BENEFITS Configurable as:
• Fully configurable via PC using • Real time clock • Automatically transfers between Negative switching digital input
USB, RS232 & RS485 • Manual and automatic fuel pump mains (utility) and generator Resistive sensor

communication control (DSE7320 MKll only) for OUTPUTS


• Front panel configuration with • Engine pre-heat and post-heat convenience. OUTPUT A & B (FUEL & START)
15 A DC at supply voltage
PIN protection functions • Hours counter provides accurate
• Power save mode • Engine run-time scheduler information for monitoring and OUTPUTS C & D
• 3 phase generator sensing and • Engine idle control for starting & maintenance periods 8 A AC at ­­­250 V AC (Volt-free)
protection stopping • User-friendly set-up and button AUXILIARY OUTPUTS E, F, G, H, I & J
• 3 phase mains (utility) sensing and • Fuel usage monitor and low fuel layout for ease of use 2 A DC at supply voltage
protection (DSE7320 MKII only) level alarms • Multiple parameters are monitored
DIMENSIONS
• Automatic load transfer control • Simultaneous use of RS232 and & displayed simultaneously for full OVERALL
(DSE7320 MKII only) RS485 communication ports visibility 245 mm x 184 mm x 51 mm
• Generator current and power • True dual mutual standby using • The module can be configured to 9.6” x 7.2” x 2.0”

monitoring (kW, kvar, kVA, pf) RS232 or RS485 for accurate suit a wide range of applications for PANEL CUT-OUT
• Mains current and power engine hours balancing. user flexibility 220 mm x 160 mm
8.7” x 6.3”
monitoring (kW, kvar, kVA, pf) • MODBUS RTU support with • PLC editor allows user configurable
(DSE7320 MKII only) configurable MODBUS pages. functions to meet user specific MAXIMUM PANEL THICKNESS
• kW and kvar overload and reverse • Advanced SMS messaging application requirements. 8 mm
0.3”
power alarms (additional external modem
• Over current protection required) STORAGE TEMPERATURE RANGE
-40°C to +85°C
-40 °F to +185 °F

OPERATING TEMPERATURE RANGE


-30°C to +70°C
-22 °F to +158 °F
RELATED MATERIALS
TITLE PART NO. HEATED DISPLAY VARIANT
-40 °C to +70 °C
DSE7310 MKII & DSE7320 MKII Installation Instructions 053-181 -40 °F to +158 °F
DSE7310 MKII & DSE7320 MKII Operator Manual 057-253
DSE7310 MKII & DSE7320 MKII Configuration Suite PC Manual 057-243

DEEP SEA ELECTRONICS LTD DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 TELEPHONE +1 (815) 316 8706
EMAIL sales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com EMAIL usasales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457 055-203/12/20 (2) US
DSEGenset®

DSE7310/20 MKII ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY

AUTO START & AUTO MAINS FAILURE CONTROL MODULES BS EN 61000-6-2


EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
The DSE7310 MKII is an Auto Start The DSE7320 MKII will also monitor The extensive list of features includes EMC Generic Emission Standard for
Control Module and the DSE7320 the mains (utility) supply. The modules enhanced event and performance the Industrial Environment
MKII is an Auto Mains (Utility) Failure include USB, RS232 and RS485 monitoring, remote communications ELECTRICAL SAFETY
Control Module suitable for a wide ports as well as dedicated DSENet® & PLC functionality. Dual mutual BS EN 60950
variety of single, diesel or gas, terminals for system expansion. standby is now available on both the Safety of Information Technology Equipment,
including Electrical Business Equipment
gen-set applications. DSE7310 MKII & DSE7320 MKII using
Both modules are compatible with RS232 or RS485 communications. TEMPERATURE
BS EN 60068-2-1
Monitoring an extensive number of electronic (CAN) and non-electronic This provides for a simpler and more Ab/Ae Cold Test -30 ºC
engine parameters, the modules will (magnetic pick-up/alternator sensing) convenient installation with more BS EN 60068-2-2
display warnings, shutdown and engines and offer an extensive advanced features such as true Bb/Be Dry Heat +70 ºC
engine status information on the number of flexible inputs, outputs engine hours balancing. VIBRATION
back-lit LCD screen, illuminated LEDs, and extensive engine protections so BS EN 60068-2-6
remote PC and via SMS text alerts the system can be easily adapted to The modules can be easily configured Ten sweeps in each of three major axes
5 Hz to 8 Hz at +/-7.5 mm,
(with external modem). meet the most demanding industry using the DSE Configuration Suite PC 8 Hz to 500 Hz at 2 gn
requirements. software. Selected front panel editing
is also available. HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 ºC
at 95% RH 48 Hours
BS EN 60068-2-78
Cab Damp Heat Static 40 ºC
at 93% RH 48 Hours

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF GEN-SET APPLICATIONS


MODEM MODBUS PC
DSE2130
DSE2157
DSE2548 8 6 6
DSE2510/20
232 485

DSENET® RS232 AND USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER


EXPANSION RS485 PORT INPUTS INPUT STOP SUPPLY 8-35V

DEUTZ
DSE7310/20 MKII ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA

MAINS (UTILITY) N/C VOLT FREE GENERATOR/ N/O VOLT FREE GENERATOR CHARGE FUEL & CRANK ELECTRONIC
SENSING OUTPUT LOAD CURRENT OUTPUT SENSING ALTERNATOR OUTPUTS ENGINES &
DSE7320 MKII ONLY (Flexible with CAN) MAGNETIC PICK-UP

VOLTS VOLTS D+
W/ L +

1ph 1 1ph 1 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E/N N

ISO 9001
Registered
Quality
Managem
ent 015