Professional Documents
Culture Documents
Siemens 3Wl Air Circuit Breakers: Now Available Retro Fit Kits To Replace Most Old ACB's With Siemens 3WL ACB's
Siemens 3Wl Air Circuit Breakers: Now Available Retro Fit Kits To Replace Most Old ACB's With Siemens 3WL ACB's
The SENTRON 3WL circuit breaker takes into account the increased demands made
on air circuit breakers in terms of operator control and monitoring of networks.
With it’s great flexibility it can be used as an incoming-feeder, distribution, tie,
and outgoing-feeder circuit breakers in electrical installations or for switching and
protecting motors, capacitors, generators,transformers, busbars and cables.
Highlights
Now Available
Retro Fit Kits to Replace most old
ACB’s with Siemens 3WL ACB’s
Air Circuit Breakers
3WL air circuit breakers
Communication
The use of modern communication-capable circuit breakers
opens up completely new possibilities in terms of start-up,
parameterization, diagnostics, maintenance and operation.
This allows many different ways of reducing costs and
improving productivity in industrial plants, buildings and
infrastructure projects to be achieved.
Figure 1: 3WL air circuit breaker, withdrawable Figure 2: 3WL air circuit breaker, fixed mounting
Degree of protection
With cover IP55 IP55
Without cover IP41 IP41
(with door sealing frame)
Dimensions 3-/4-pole
W
B D
T W mm 320/410 460/590 704/914 460/590
Fixed H mm 434 434 434 434
H
NSE0_01111a
Rating Plug
Size I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S N S H H C C
N S N S H H C C
3-pole 4-pole
Short-circuit breaking capacity
Rated operational voltage U e
up to 415 V AC
I cu kA 55 66 66 80 100 100 150 130
I cs kA 55 66 66 80 100 100 150 130
I cm kA 121 145 145 176 220 220 330 286
Rated operational voltage U e
up to 500 V AC
I cu kA 55 66 66 80 100 100 150 130
I cs kA 55 66 66 80 100 100 150 130
I cm kA 121 145 145 176 220 220 330 286
Rated operational voltage U e
up to 690 V AC
I cu kA 42 50 50 75 85 85 150 130
I cs kA 42 50 50 75 85 85 150 130
I cm kA 88 105 105 165 187 187 330 286
Rated operational voltage U e
up to 1000 V/1150 V AC
I cu kA -- -- -- -- 50 50 70 4) 70 4)
I cs kA -- -- -- -- 50 50 70 4) 70 4)
4)
I cm kA -- -- -- -- 105 105 154 154 4)
Rated short-time withstand current I cw
of the circuit breakers3)
0.5 s kA 55 66 66 80 100 100 100 100
1s kA 42 50 55 66 80 100 100 100
2s kA 29,5 35 39 46 65 1) /702) 80 80 80
3s kA 24 29 32 37 50 1) /652) 65 65 65
Short-circuit breaking capacity I cc
of the non-automatic air circuit breakers
Up to 500 V AC kA 55 66 66 80 100 100 100 100
U p to 6 9 0 V A C kA 42 50 50 75 85 85 100 100
Up to 1,000 V /1150 V AC kA -- -- -- -- 50 4) 50 4) 70 4) 70 4)
Size II
DC
Type 3WL12
Switching capacity class DC
Short-circuit breaking capacity
Up to 220 V DC I cc kA 35
Up to 300 V DC I cc kA 30
Up to 600 V DC I cc kA 25
Up to 1000 V DC I cc kA 20
Rated short-time withstand current I cw
0.5 s kA --
1s kA 35 5) /306) /257) /208)
2s kA --
3s kA --
1)
Size II with I n max 2500 A.
N
Circuit breaker with ECO switching capacity N 2)
Size II with I n max = 3200 A and I n max = 4000 A.
3)
At a rated voltage of 690 V the I cw value of the circuit breaker cannot be
S
Circuit breaker with standard switching capacity S greater than the I cu or I cs value at 690 V.
4)
Rated operational voltage U e = 1150 V.
H
Circuit breaker with high switching capacity H 5)
At U e = 220 V DC.
6)
At U e = 300 V DC.
7)
C
Circuit breakers with very high switching capacity C At U e = 600 V DC.
8)
At U e = 1000 V DC.
DC
Non-automatic air circuit breakers with DC switching
capacity
The Siemens 3WL ACB fitted in a Showing the upper set of extension
Nilsen NAB cradle bars connected to the ACB
ION
INSTALLAT
C TI O NS
INSTRU _______
__________
L1 AIR
SIEMENS 3W
EAKER
CIRCUIT BR
RETROFIT KIT
-FOR-
/D16 AIR
NILSEN NAB1 KER
EA
CIRCUIT BR
Ramelec (QLD) Pty Ltd Ramelec (VIC) Pty Ltd Ramelec Electronics Pty Ltd
2/5 Breene Place 8 Enterprise Court 13-15 Shepley Avenue
Morningside QLD 4170 Mulgrave VIC 3171 Panorama SA 5041
Tel: 07 3899 1322 Tel: 03 9808 9800 Tel: 1300 309 150
Fax: 07 3899 1422 Fax: 03 9808 9855 Fax: 1300 309 152
CONTACT US
TEL: 1300 309 303 FAX: 1300 309 308
Enquiries sales@ramelec.com.au
Visit us www.ramelec.com.au