II Y SERIES R410A Data G2

CITY MULTI™
OUTDOOR UNITS
Y SERIES

Y SERIES
1. SPECIFICATIONS Y-2
2. CAPACITY TABLES Y-21
2.1 Correction by temperature Y-21
2.2 Correction by total indoor Y-26
2.3 Correction by refrigerant piping length Y-32
2.4 Correction at frosting and defrosting Y-36
2.5 Temp. range of running Y-36
3. SOUND LEVELS Y-37
4. EXTERNAL DIMENSIONS Y-42
5. ELECTRICAL WIRING DIAGRAMS Y-57
6. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS Y-62

Header
Joint
Indoor unit

Outdoor unit

Indoor unit

Indoor unit

Heat pump: PUHY-P-Y(S)GM-A(-BS) Cooling-only: PUY-P-YGM-A(-BS)


200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP 50HP
Y Heat pump ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Y Cooling-only ● ● ● ●

OUTDOOR UNIT R410A Y - 1


1. SPECIFICATIONS R410A Data G2

Model PUY-P200YGM-A(-BS) PUY-P250YGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 22.4 28.0
(Nominal) ✻1 kcal / h 19,300 24,100
✻1 Btu / h 76,400 95,500
✻2 kcal / h 20,000 25,000
Power input kW 6.14 7.72
Current input A 10.3 / 9.8 / 9.4 13.0 / 12.3 / 11.9
COP (kW / kW) 3.65 3.63
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 - -
(Nominal ) ✻3
kcal / h - -
✻3 Btu / h - -
Power input kW - -
Current input A - -
COP (kW / kW) - -
Temp. range of Indoor temp. D.B. -
heating Outdoor temp. W.B. -

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 13 P20 ~ P250 / 1 ~ 16
Noise level (measured in anechoic room) dB <A> 56 / 56 57 / 57
Diameter of Liquid (High press.) mm (in.) ø9.52 (ø3/8”) Flare ø9.52 (ø3/8”) Flare
refrigerant pipe (ø12.7 (ø1/2”) Flare, total length >=90m)
Gas (Low press.) mm (in.) ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed

External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 990 x 840 1,840 x 990 x 840
in. 72-1/2” x 39” x 33-1/8” 72-1/2” x 39” x 33-1/8”
Net weight kg (lb) 218 (481) 233 (514)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type Inverter scroll hermetic comp. Inverter scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 4.7 6.7
Case heater kW 0.045 x 1 (240V) 0.045 x 1 (240V)
Lubricant MEL56 MEL32
FAN Air flow rate m3 / min 200 200
L/s 3,333 3,333
cfm 7,063 7,063
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 1 Propeller fan x 1
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 0.38
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 7.0 kg (16 lb) R410A x 9.5 kg (21 lb)
Control LEV and HIC circuit
Drawing External YGM-W656-818 1/2
Wiring YGM-W274-627
Refrigerant circle YGM-rcd-200-350ygmc
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM- W656-818 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60 Pa) High static pressure motor : PAC-KBU04MT-F (60 Pa)
Joint : CMY-Y102S-G Joint : CMY-Y102S/L-G
Header : CMY-Y104/108/1010-G Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.

Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p200_250ygm_c

OUTDOOR UNIT R410A Y - 2


1. SPECIFICATIONS R410A Data G2

Model PUY-P300YGM-A(-BS) PUY-P350YGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 33.5 40.0
(Nominal) ✻1 kcal / h 28,800 34,400
✻1 Btu / h 114,300 136,500
✻2 kcal / h 30,000 35,000
Power input kW 9.57 11.39
Current input A 16.1 / 15.3 / 14.7 19.2 / 18.2 / 17.6
COP (kW / kW) 3.50 3.51
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 - -
(Nominal ) ✻3
kcal / h - -
✻3 Btu / h - -
Power input kW - -
Current input A - -
COP (kW / kW) - -
Temp. range of Indoor temp. D.B. -
heating Outdoor temp. W.B. -

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 19 P20 ~ P250 / 1 ~ 20
Noise level (measured in anechoic room) dB <A> 59 / 59 60 / 60
Diameter of Liquid (High press.) mm (in.) ø9.52 (ø3/8”) Flare ø12.7 (ø1/2”) Flare
refrigerant pipe (ø12.7 (ø1/2”) Flare, total length >=40m)
Gas (Low press.) mm (in.) ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed

External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 990 x 840 1,840 x 990 x 840
in. 72-1/2” x 39” x 33-1/8” 72-1/2” x 39” x 33-1/8”
Net weight kg (lb) 233 (514) 233 (514)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type Inverter scroll hermetic comp. Inverter scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 8.0 9.6
Case heater kW 0.045 x 1 (240V) 0.045 x 1 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 200 200
L/s 3,333 3,333
cfm 7,063 7,063
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 1 Propeller fan x 1
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 0.38
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 9.5 kg (21 lb) R410A x 9.5 kg (21 lb)
Control LEV and HIC circuit
Drawing External YGM-W656-818 1/2
Wiring YGMW274-627
Refrigerant circle YGM-rcd-200-350ygmc
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM- W656-818 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60 Pa)
Joint : CMY-Y102S/L-G
Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.

Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p300_350ygm_c

OUTDOOR UNIT R410A Y - 3


1. SPECIFICATIONS R410A Data G2

Model PUHY-P200YGM-A(-BS) PUHY-P250YGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 22.4 28.0
(Nominal) ✻1 kcal / h 19,300 24,100
✻1 Btu / h 76,400 95,500
✻2 kcal / h 20,000 25,000
Power input kW 6.14 7.72
Current input A 10.3 / 9.8 / 9.4 13.0 / 12.3 / 11.9
COP (kW / kW) 3.65 3.63
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 25.0 31.5
(Nominal ) ✻3
kcal / h 21,500 27,100
✻3 Btu / h 85,300 107,500
Power input kW 5.98 7.62
Current input A 10.0 / 9.5 / 9.2 12.8 / 12.2 / 11.7
COP (kW / kW) 4.18 4.13
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 13 P20 ~ P250 / 1 ~ 16
Noise level (measured in anechoic room) dB <A> 56 / 56 57 / 57
Diameter of Liquid (High press.) mm (in.) ø9.52 (ø3/8”) Flare ø9.52 (ø3/8”) Flare
refrigerant pipe (ø12.7 (ø1/2”) Flare, total length >=90m)
Gas (Low press.) mm (in.) ø19.05 (ø3/4”) Brazed ø22.2 (ø7/8”) Brazed

External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 990 x 840 1,840 x 990 x 840
in. 72-1/2” x 39” x 33-1/8” 72-1/2” x 39” x 33-1/8”
Net weight kg (lb) 218 (481) 233 (514)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type Inverter scroll hermetic comp. Inverter scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 4.7 6.7
Case heater kW 0.045 x 1 (240V) 0.045 x 1 (240V)
Lubricant MEL56 MEL32
FAN Air flow rate m3 / min 200 200
L/s 3,333 3,333
cfm 7,063 7,063
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 1 Propeller fan x 1
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 0.38
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 7.0 kg (16 lb) R410A x 9.5 kg (21 lb)
Control LEV and HIC circuit
Drawing External YGM-W656-818 1/2
Wiring YGM-W274-627
Refrigerant circle YGM-rcd-200-350ygmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-W656-818 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60 Pa) High static pressure motor : PAC-KBU04MT-F (60 Pa)
Joint : CMY-Y102S-G Joint : CMY-Y102S/L-G
Header : CMY-Y104/108/1010-G Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.

Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p200_250ygm

OUTDOOR UNIT R410A Y - 4


1. SPECIFICATIONS R410A Data G2

Model PUHY-P300YGM-A(-BS) PUHY-P350YGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 33.5 40.0
(Nominal) ✻1 kcal / h 28,800 34,400
✻1 Btu / h 114,300 136,500
✻2 kcal / h 30,000 35,000
Power input kW 9.57 11.39
Current input A 16.1 / 15.3 / 14.7 19.2 / 18.2 / 17.6
COP (kW / kW) 3.50 3.51
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 37.5 45.0
(Nominal ) ✻3
kcal / h 32,300 38,700
✻3 Btu / h 128,000 153,500
Power input kW 9.10 11.02
Current input A 15.3 / 14.5 / 14.0 18.6 / 17.6 / 17.0
COP (kW / kW) 4.12 4.08
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 19 P20 ~ P250 / 1 ~ 20
Noise level (measured in anechoic room) dB <A> 59 / 59 60 / 60
Diameter of Liquid (High press.) mm (in.) ø9.52 (ø3/8”) Flare ø12.7 (ø1/2”) Flare
refrigerant pipe (ø12.7 (ø1/2”) Flare, total length >=40m)
Gas (Low press.) mm (in.) ø22.2 (ø7/8”) Brazed ø28.58 (ø1-1/8”) Brazed

External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 990 x 840 1,840 x 990 x 840
in. 72-1/2” x 39” x 33-1/8” 72-1/2” x 39” x 33-1/8”
Net weight kg (lb) 233 (514) 233 (514)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type Inverter scroll hermetic comp. Inverter scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 8.0 9.6
Case heater kW 0.045 x 1 (240V) 0.045 x 1 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 200 200
L/s 3,333 3,333
cfm 7,063 7,063
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 1 Propeller fan x 1
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 0.38
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 9.5 kg (21 lb) R410A x 9.5 kg (21 lb)
Control LEV and HIC circuit
Drawing External YGM-W656-818 1/2
Wiring YGM-W274-627
Refrigerant circle YGM-rcd-200-350ygmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-W656-818 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60 Pa)
Joint : CMY-Y102S/L-G
Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.

Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p300_350ygm

OUTDOOR UNIT R410A Y - 5


1. SPECIFICATIONS R410A Data G2

Model PUHY-P400YGM-A(-BS) PUHY-P450YGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 45.0 50.0
(Nominal) ✻1 kcal / h 38,700 43,000
✻1 Btu / h 153,500 170,600
✻2 kcal / h 40,000 45,000
Power input kW 13.42 13.61
Current input A 22.6 / 21.5 / 20.7 22.9 / 21.8 / 21.0
COP (kW / kW) 3.35 3.67
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 50.0 56.0
(Nominal ) ✻3
kcal / h 43,000 48,200
✻3 Btu / h 170,600 191,100
Power input kW 12.43 13.86
Current input A 20.9 / 19.9 / 19.2 23.3 / 22.2 / 21.4
COP (kW / kW) 4.02 4.04
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 22 P20 ~ P250 / 1 ~ 24
Noise level (measured in anechoic room) dB <A> 61 / 61 60 / 61
Diameter of Liquid (High press.) mm (in.) ø12.7 (ø1/2”) Flare ø15.88 (ø5/8”) Flare
refrigerant pipe
Gas (Low press.) mm (in.) ø28.58 (ø1-1/8”) Brazed ø28.58 (ø1-1/8”) Brazed

External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,290 x 840 1,840 x 1,990 x 840
in. 72-1/2” x 50-13/16” x 33-1/8” 72-1/2” x 78-3/8” x 33-1/8”
Net weight kg (lb) 275 (607) 455 (1,004)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type Inverter scroll hermetic comp. Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter Inverter + Direct
Motor output kW 9.7 6.8 + 5.3
Case heater kW 0.045 x 1 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 240 400
L/s 4,000 6,667
cfm 8,476 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 1 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.64 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 13.0 kg (29 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Drawing External YGM-W656-819 1/2 YGM-W656-820 1/2
Wiring YGM-W274-627 YGM-W274-629
Refrigerant circle YGM-rcd-400ygmhp YGM-rcd-450-650ygmhp
Standard Document Installation Manual Installation Manual
attachment Accessory Details refer to External Drw YGM-W656-819 1/2 Details refer to External Drw YGM-W656-820 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60 Pa) High static pressure motor : PAC-KBU04MT-F (60 Pa)
Joint : CMY-Y102S/L-G Joint : CMY-Y102S/L-G,CMY-Y202-G
Header : CMY-Y104/108/1010-G Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.

Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p400_450ygm

OUTDOOR UNIT R410A Y - 6


1. SPECIFICATIONS R410A Data G2

Model PUHY-P500YGM-A(-BS) PUHY-P550YGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 56.0 63.0
(Nominal) ✻1 kcal / h 48,200 54,200
✻1 Btu / h 191,100 215,000
✻2 kcal / h 50,000 55,000
Power input kW 15.59 17.08
Current input A 26.3 / 25.0 / 24.0 28.8 / 27.3 / 26.4
COP (kW / kW) 3.59 3.69
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 63.0 67.0
(Nominal ) ✻3
kcal / h 54,200 57,600
✻3 Btu / h 215,000 228,600
Power input kW 15.89 16.37
Current input A 26.8 / 25.4 / 24.5 27.6 / 26.2 / 25.3
COP (kW / kW) 3.96 4.09
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. -20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 24 P20 ~ P250 / 1 ~ 24
Noise level (measured in anechoic room) dB <A> 60 / 61 61 / 62
Diameter of Liquid (High press.) mm (in.) ø15.88 (ø5/8”) Flare ø15.88 (ø5/8”) Flare
refrigerant pipe
Gas (Low press.) mm (in.) ø28.58 (ø1-1/8”) Brazed ø28.58 (ø1-1/8”) Brazed

External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2” x 78-3/8” x 33-1/8” 72-1/2” x 78-3/8” x 33-1/8”
Net weight kg (lb) 455 (1,004) 455 (1,004)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type Inverter scroll hermetic comp. + Scroll hermetic comp. Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct
Motor output kW 8.2 + 5.3 9.3 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Drawing External YGM-W656-820 1/2
Wiring YGM-W274-629
Refrigerant circle YGM-rcd-450-650ygmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-W656-820 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60 Pa)
Joint : CMY-Y102S/L-G,CMY-Y202-G
Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.

Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p500_550ygm

OUTDOOR UNIT R410A Y - 7


1. SPECIFICATIONS R410A Data G2

Model PUHY-P600YGM-A(-BS) PUHY-P650YGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 67.4 73.0
(Nominal) ✻1 kcal / h 58,000 62,800
✻1 Btu / h 230,000 249,100
✻2 kcal / h 60,000 65,000
Power input kW 17.59 19.65
Current input A 29.6 / 28.2 / 27.1 33.1 / 31.5 / 30.3
COP (kW / kW) 3.83 3.72
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 75.0 81.5
(Nominal ) ✻3
kcal / h 64,500 70,100
✻3 Btu / h 255,900 278,100
Power input kW 17.73 19.82
Current input A 29.9 / 28.4 / 27.4 33.4 / 31.7 / 30.6
COP (kW / kW) 4.23 4.11
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. -20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 32 P20 ~ P250 / 1 ~ 32
Noise level (measured in anechoic room) dB <A> 61 / 62 62 / 62.5
Diameter of Liquid (High press.) mm (in.) ø15.88 (ø5/8”) Flare ø15.88 (ø5/8”) Flare
refrigerant pipe
Gas (Low press.) mm (in.) ø28.58 (ø1-1/8”) Brazed ø28.58 (ø1-1/8”) Brazed

External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2” x 78-3/8” x 33-1/8” 72-1/2” x 78-3/8” x 33-1/8”
Net weight kg (lb) 455 (1,004) 455 (1,004)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type Inverter scroll hermetic comp. + Scroll hermetic comp. Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct
Motor output kW 10.1 + 5.3 10.9 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Drawing External YGM-W656-820 1/2
Wiring YGM-W274-629
Refrigerant circle YGM-rcd-450-650ygmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-W656-820 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60 Pa)
Joint : CMY-Y102S/L-G,CMY-Y202-G
Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.

Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p600_650ygm

OUTDOOR UNIT R410A Y - 8


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P700YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 78.4
(Nominal) kcal / h
✻1 67,400
✻1 Btu / h 267,500
✻2 kcal / h 70,000
Power input kW 21.70
Current input A 36.6 / 34.8 / 33.5
COP (kW / kW) 3.61
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 88.0
(Nominal ) ✻3
kcal / h 75,700
✻3 Btu / h 300,300
Power input kW 21.83
Current input A 36.8 / 35.0 / 33.7
COP (kW / kW) 4.03
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 34
Noise level (measured in anechoic room) dB <A> 62 / 62
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4”) Brazed + Flare
refrigerant pipe Gas (Low press.) mm (in.) ø34.93 (ø1-3/8”) Brazed
The Set model is a combination of Compressor and Heat exchanger unit as follows.
Model (Comp. unit and Heat exchanger unit ) PUHY-P700YGM-A(-BS) PUHN-P01YGM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,690 x 840 1,840 x 990 x 840
in. 72-1/2” x 66-9/16” x 33-1/8” 72-1/2” x 39” x 33-1/8”
Net weight kg (lb) 430 (948) 155 (342)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. x 2 -
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION -
Starting method Inverter -
Motor output kW 8.6 + 8.6 -
Case heater kW 0.045 x 2 (240V) -
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 240 240
L/s 4,000 4,000
cfm 8,476 8,476
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 1 Propeller fan x 1
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.64 0.64
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure -
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi) -
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection -
Compressor Over-heat protection -
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 27.0 kg (60 lb) -
Control LEV and HIC circuit
Pipe between Comp. Liquid mm (in.) ø12.7 (ø1/2") Flare ø12.7 (ø1/2") Brazed
and Heat exch. unit Gas mm (in.) ø28.58 (ø1-1/8") Brazed ø28.58 (ø1-1/8") Brazed
Drawing External YGM- W656-825A, 824A, 823A 1/2
Wiring YGM- W274-621,775
Refrigerant circle YGM- rcd-700-800ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-824A 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60 Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G
Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.

Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p700ygm

OUTDOOR UNIT R410A Y - 9


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P750YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 84.0
(Nominal) kcal / h
✻1 72,200
✻1 Btu / h 286,600
✻2 kcal / h 75,000
Power input kW 24.90
Current input A 42.0 / 39.9 / 38.4
COP (kW / kW) 3.37
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 94.5
(Nominal ) ✻3
kcal / h 81,300
✻3 Btu / h 322,400
Power input kW 25.37
Current input A 42.8 / 40.6 / 39.2
COP (kW / kW) 3.72
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 34
Noise level (measured in anechoic room) dB <A> 63 / 63
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4”) Brazed + Flare
refrigerant pipe Gas (Low press.) mm (in.) ø34.93 (ø1-3/8”) Brazed
The Set model is a combination of Compressor and Heat exchanger unit as follows.
Model (Comp. unit and Heat exchanger unit ) PUHY-P750YGM-A(-BS) PUHN-P01YGM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,690 x 840 1,840 x 990 x 840
in. 72-1/2” x 66-9/16” x 33-1/8” 72-1/2” x 39” x 33-1/8”
Net weight kg (lb) 430 (948) 155 (342)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. x 2 -
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION -
Starting method Inverter -
Motor output kW 9.4 + 9.4 -
Case heater kW 0.045 x 2 (240V) -
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 240 240
L/s 4,000 4,000
cfm 8,476 8,476
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 1 Propeller fan x 1
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.64 0.64
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure -
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi) -
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection -
Compressor Over-heat protection -
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 27.0 kg (60 lb) -
Control LEV and HIC circuit
Pipe between Comp. Liquid mm (in.) ø12.7 (ø1/2") Flare ø12.7 (ø1/2") Brazed
and Heat exch. unit Gas mm (in.) ø28.58 (ø1-1/8") Brazed ø28.58 (ø1-1/8") Brazed
Drawing External YGM- W656-825A, 824A, 823A 1/2
Wiring YGM- W274-621, 775
Refrigerant circle YGM- rcd-700-800ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-824A 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60 Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G
Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.

Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p750ygm

OUTDOOR UNIT R410A Y - 10


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P800YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 90.0
(Nominal) kcal / h
✻1 77,400
✻1 Btu / h 307,100
✻2 kcal / h 80,000
Power input kW 26.75
Current input A 45.1 / 42.9 / 41.3
COP (kW / kW) 3.36
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 100.0
(Nominal ) ✻3
kcal / h 86,000
✻3 Btu / h 341,200
Power input kW 26.90
Current input A 45.4 / 43.1 / 41.5
COP (kW / kW) 3.72
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 34
Noise level (measured in anechoic room) dB <A> 64 / 64
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4”) Brazed + Flare
refrigerant pipe Gas (Low press.) mm (in.) ø34.93 (ø1-3/8”) Brazed
The Set model is a combination of Compressor and Heat exchanger unit as follows.
Model (Comp. unit and Heat exchanger unit ) PUHY-P800YGM-A(-BS) PUHN-P01YGM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,690 x 840 1,840 x 990 x 840
in. 72-1/2” x 66-9/16” x 33-1/8” 72-1/2” x 39” x 33-1/8”
Net weight kg (lb) 430 (948) 155 (342)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. x 2 -
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION -
Starting method Inverter -
Motor output kW 10.1 + 10.1 -
Case heater kW 0.045 x 2 (240V) -
Lubricant MEL32 -
FAN Air flow rate m3 / min 240 240
L/s 4,000 4,000
cfm 8,476 8,476
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 1 Propeller fan x 1
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.64 0.64
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure -
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi) -
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection -
Compressor Over-heat protection -
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 27.0 kg (60 lb) -
Control LEV and HIC circuit
Pipe between Comp. Liquid mm (in.) ø12.7 (ø1/2") Flare ø12.7 (ø1/2") Brazed
and Heat exch. unit Gas mm (in.) ø28.58 (ø1-1/8") Brazed ø28.58 (ø1-1/8") Brazed
Drawing External YGM- W656-825A, 824A, 823A 1/2
Wiring YGM- W274-621, 775
Refrigerant circle YGM- rcd-700-800ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-824A 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60 Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G
Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.

Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p800ygm

OUTDOOR UNIT R410A Y - 11


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P850YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 96.0
(Nominal) kcal / h
✻1 82,600
✻1 Btu / h 327,600
✻2 kcal / h 85,000
Power input kW 25.28
Current input A 42.6 / 40.5 / 39.0
COP (kW / kW) 3.80
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 108.0
(Nominal ) ✻3
kcal / h 92,900
✻3 Btu / h 368,500
Power input kW 27.47
Current input A 46.3 / 44.0 / 42.4
COP (kW / kW) 3.93
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 42
Noise level (measured in anechoic room) dB <A> 63 / 64
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4") Brazed
refrigerant pipe Gas (Low press.) mm (in.) ø41.28 (ø1-5/8") Brazed
The Set model is a combination of Main unit and Sub unit as follows.
Model (Main unit and Sub unit ) PUHY-P450YMM-A(-BS) PUHY-P400YSM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2" x 78-3/8" x 33-1/8" 72-1/2" x 78-3/8" x 33-1/8"
Net weight kg (lb) 458 (1,010) 460 (1,015)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct Inverter + Direct
Motor output kW 9.4 + 5.3 / 8.5 + 5.3 8.5 + 5.3 / 8.5 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Pipe between Main Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Pipe between Sub Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Oil balance pipe mm (in.) ø9.52 (ø3/8") Flare ø9.52 (ø3/8") Flare
Drawing External YGM- W656-885, 884, 886 1/2
Wiring YGM- W274-638A
Refrigerant circle YGM- rcd-850-1250ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-886/885/884, 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G ; Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p850ygm

OUTDOOR UNIT R410A Y - 12


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P900YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 101.0
(Nominal) kcal / h
✻1 86,900
✻1 Btu / h 344,600
✻2 kcal / h 90,000
Power input kW 26.71
Current input A 45.0 / 42.8 / 41.2
COP (kW / kW) 3.78
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 113.0
(Nominal ) ✻3
kcal / h 97,200
✻3 Btu / h 385,600
Power input kW 29.10
Current input A 49.1 / 46.6 / 44.9
COP (kW / kW) 3.88
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 42
Noise level (measured in anechoic room) dB <A> 63 / 64
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4") Brazed
refrigerant pipe Gas (Low press.) mm (in.) ø41.28 (ø1-5/8") Brazed
The Set model is a combination of Main unit and Sub unit as follows.
Model (Main unit and Sub unit ) PUHY-P500YMM-A(-BS) PUHY-P400YSM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2" x 78-3/8" x 33-1/8" 72-1/2" x 78-3/8" x 33-1/8"
Net weight kg (lb) 458 (1,010) 460 (1,015)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct Inverter + Direct
Motor output kW 10.3 + 5.3 / 9.6 + 5.3 8.5 + 5.3 / 8.5 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Pipe between Main Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Pipe between Sub Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Oil balance pipe mm (in.) ø9.52 (ø3/8") Flare ø9.52 (ø3/8") Flare
Drawing External YGM- W656-885, 884, 886 1/2
Wiring YGM- W274-638A
Refrigerant circle YGM- rcd-850-1250ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-886/885/884, 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G ; Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p900ygm

OUTDOOR UNIT R410A Y - 13


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P950YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 108.0
(Nominal) kcal / h
✻1 92,900
✻1 Btu / h 368,500
✻2 kcal / h 95,000
Power input kW 29.23
Current input A 49.3 / 46.8 / 45.1
COP (kW / kW) 3.69
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 119.5
(Nominal ) ✻3
kcal / h 102,800
✻3 Btu / h 407,700
Power input kW 30.42
Current input A 51.3 / 48.7 / 47.0
COP (kW / kW) 3.93
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 42
Noise level (measured in anechoic room) dB <A> 63 / 64
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4") Brazed
refrigerant pipe Gas (Low press.) mm (in.) ø41.28 (ø1-5/8") Brazed
The Set model is a combination of Main unit and Sub unit as follows.
Model (Main unit and Sub unit ) PUHY-P550YMM-A(-BS) PUHY-P400YSM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2" x 78-3/8" x 33-1/8" 72-1/2" x 78-3/8" x 33-1/8"
Net weight kg (lb) 458 (1,010) 460 (1,015)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct Inverter + Direct
Motor output kW 11.2 + 5.3 / 10.9 + 5.3 8.5 + 5.3 / 8.5 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Pipe between Main Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Pipe between Sub Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Oil balance pipe mm (in.) ø9.52 (ø3/8") Flare ø9.52 (ø3/8") Flare
Drawing External YGM- W656-885, 884, 886 1/2
Wiring YGM- W274-638A
Refrigerant circle YGM- rcd-850-1250ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-886/885/884, 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G ; Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p950ygm

OUTDOOR UNIT R410A Y - 14


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P1000YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 113.0
(Nominal) kcal / h
✻1 97,200
✻1 Btu / h 385,600
✻2 kcal / h 100,000
Power input kW 31.11
Current input A 52.5 / 49.8 / 48.0
COP (kW / kW) 3.63
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 127.0
(Nominal ) ✻3
kcal / h 109,200
✻3 Btu / h 433,300
Power input kW 32.68
Current input A 55.1 / 52.4 / 50.5
COP (kW / kW) 3.89
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 42
Noise level (measured in anechoic room) dB <A> 63 / 64
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4") Brazed
refrigerant pipe Gas (Low press.) mm (in.) ø41.28 (ø1-5/8") Brazed
The Set model is a combination of Main unit and Sub unit as follows.
Model (Main unit and Sub unit ) PUHY-P600YMM-A(-BS) PUHY-P400YSM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2" x 78-3/8" x 33-1/8" 72-1/2" x 78-3/8" x 33-1/8"
Net weight kg (lb) 458 (1,010) 460 (1,015)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct Inverter + Direct
Motor output kW 11.6 + 5.3 / 11.6 + 5.3 8.5 + 5.3 / 8.5 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Pipe between Main Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Pipe between Sub Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Oil balance pipe mm (in.) ø9.52 (ø3/8") Flare ø9.52 (ø3/8") Flare
Drawing External YGM- W656-885, 884, 886 1/2
Wiring YGM- W274-638A
Refrigerant circle YGM- rcd-850-1250ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-886/885/884, 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G ; Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p1000ygm

OUTDOOR UNIT R410A Y - 15


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P1050YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 118.0
(Nominal) kcal / h
✻1 101,500
✻1 Btu / h 402,600
✻2 kcal / h 105,000
Power input kW 33.48
Current input A 56.5 / 53.6 / 51.7
COP (kW / kW) 3.52
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 132.0
(Nominal ) ✻3
kcal / h 113,500
✻3 Btu / h 450,400
Power input kW 34.24
Current input A 57.8 / 54.9 / 52.9
COP (kW / kW) 3.86
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 42
Noise level (measured in anechoic room) dB <A> 63.5 / 64.5
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4") Brazed
refrigerant pipe Gas (Low press.) mm (in.) ø41.28 (ø1-5/8") Brazed
The Set model is a combination of Main unit and Sub unit as follows.
Model (Main unit and Sub unit ) PUHY-P650YMM-A(-BS) PUHY-P400YSM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2" x 78-3/8" x 33-1/8" 72-1/2" x 78-3/8" x 33-1/8"
Net weight kg (lb) 458 (1,010) 460 (1,015)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct Inverter + Direct
Motor output kW 11.6 + 5.3 / 11.6 + 5.3 8.5 + 5.3 / 8.5 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Pipe between Main Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Pipe between Sub Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Oil balance pipe mm (in.) ø9.52 (ø3/8") Flare ø9.52 (ø3/8") Flare
Drawing External YGM- W656-885, 884, 886 1/2
Wiring YGM- W274-638A
Refrigerant circle YGM- rcd-850-1250ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-886/885/884, 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G ; Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p1050ygm

OUTDOOR UNIT R410A Y - 16


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P1100YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 124.0
(Nominal) kcal / h
✻1 106,600
✻1 Btu / h 423,100
✻2 kcal / h 110,000
Power input kW 36.39
Current input A 61.4 / 58.3 / 56.2
COP (kW / kW) 3.41
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 140.0
(Nominal ) ✻3
kcal / h 120,400
✻3 Btu / h 477,700
Power input kW 36.93
Current input A 62.3 / 59.2 / 57.0
COP (kW / kW) 3.79
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 42
Noise level (measured in anechoic room) dB <A> 64 / 65
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4") Brazed
refrigerant pipe Gas (Low press.) mm (in.) ø41.28 (ø1-5/8") Brazed
The Set model is a combination of Main unit and Sub unit as follows.
Model (Main unit and Sub unit ) PUHY-P450YMM-A(-BS) PUHY-P650YSM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2" x 78-3/8" x 33-1/8" 72-1/2" x 78-3/8" x 33-1/8"
Net weight kg (lb) 458 (1,010) 460 (1,015)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct Inverter + Direct
Motor output kW 9.4 + 5.3 / 8.5 + 5.3 11.6 + 5.3 / 11.6 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Pipe between Main Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Pipe between Sub Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Oil balance pipe mm (in.) ø9.52 (ø3/8") Flare ø9.52 (ø3/8") Flare
Drawing External YGM- W656-885, 884, 886 1/2
Wiring YGM- W274-638A
Refrigerant circle YGM- rcd-850-1250ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-886/885/884, 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G ; Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p1100ygm

OUTDOOR UNIT R410A Y - 17


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P1150YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 130.0
(Nominal) kcal / h
✻1 111,800
✻1 Btu / h 443,600
✻2 kcal / h 115,000
Power input kW 39.96
Current input A 67.4 / 64.0 / 61.7
COP (kW / kW) 3.25
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 145.0
(Nominal ) ✻3
kcal / h 124,700
✻3 Btu / h 494,700
Power input kW 38.46
Current input A 64.9 / 61.6 / 59.4
COP (kW / kW) 3.77
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 42
Noise level (measured in anechoic room) dB <A> 64 / 65
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4") Brazed
refrigerant pipe Gas (Low press.) mm (in.) ø41.28 (ø1-5/8") Brazed
The Set model is a combination of Main unit and Sub unit as follows.
Model (Main unit and Sub unit ) PUHY-P500YMM-A(-BS) PUHY-P650YSM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2" x 78-3/8" x 33-1/8" 72-1/2" x 78-3/8" x 33-1/8"
Net weight kg (lb) 458 (1,010) 460 (1,015)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct Inverter + Direct
Motor output kW 10.3 + 5.3 / 9.6 + 5.3 11.6 + 5.3 / 11.6 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Pipe between Main Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Pipe between Sub Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Oil balance pipe mm (in.) ø9.52 (ø3/8") Flare ø9.52 (ø3/8") Flare
Drawing External YGM- W656-885, 884, 886 1/2
Wiring YGM- W274-638A
Refrigerant circle YGM- rcd-850-1250ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-886/885/884, 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G ; Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p1150ygm

OUTDOOR UNIT R410A Y - 18


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P1200YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 136.0
(Nominal) kcal / h
✻1 117,000
✻1 Btu / h 464,000
✻2 kcal / h 120,000
Power input kW 44.40
Current input A 74.9 / 71.2 / 68.6
COP (kW / kW) 3.06
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 150.0
(Nominal ) ✻3
kcal / h 129,000
✻3 Btu / h 511,800
Power input kW 39.73
Current input A 67.0 / 63.7 / 61.4
COP (kW / kW) 3.78
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 42
Noise level (measured in anechoic room) dB <A> 64 / 65
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4") Brazed
refrigerant pipe Gas (Low press.) mm (in.) ø41.28 (ø1-5/8") Brazed
The Set model is a combination of Main unit and Sub unit as follows.
Model (Main unit and Sub unit ) PUHY-P550YMM-A(-BS) PUHY-P650YSM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2" x 78-3/8" x 33-1/8" 72-1/2" x 78-3/8" x 33-1/8"
Net weight kg (lb) 458 (1,010) 460 (1,015)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct Inverter + Direct
Motor output kW 11.2 + 5.3 / 10.9 + 5.3 11.6 + 5.3 / 11.6 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Pipe between Main Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Pipe between Sub Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Oil balance pipe mm (in.) ø9.52 (ø3/8") Flare ø9.52 (ø3/8") Flare
Drawing External YGM- W656-885, 884, 886 1/2
Wiring YGM- W274-638A
Refrigerant circle YGM- rcd-850-1250ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-886/885/884, 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G ; Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p1200ygm

OUTDOOR UNIT R410A Y - 19


1. SPECIFICATIONS R410A Data G2

Model (Set name) PUHY-P1250YSGM-A(-BS)


Power source 3-phase 4-wire 380-400-415V 50 / 60Hz
Cooling capacity kW ✻1 140.0
(Nominal) kcal / h
✻1 120,400
✻1 Btu / h 477,700
✻2 kcal / h 125,000
Power input kW 47.56
Current input A 80.2 / 76.2 / 73.5
COP (kW / kW) 2.94
Temp. range of Indoor W.B. 15 ~ 24˚C (59 ~ 75˚F)
cooling Outdoor D.B. - 5 ~ 43˚C (23 ~ 109˚F)
0 ~ 43˚C (32 ~ 109˚F) (When the Outdoor is at a position lower than the Indoors)
Heating capacity kW ✻3 156.5
(Nominal ) ✻3
kcal / h 134,600
✻3 Btu / h 534,000
Power input kW 42.63
Current input A 71.9 / 68.3 / 65.8
COP (kW / kW) 3.67
Temp. range of Indoor temp. D.B. 15 ~ 27˚C (59 ~ 81˚F)
heating Outdoor temp. W.B. - 20 ~ 15.5˚C (- 4 ~ 60˚F)

Indoor unit Total capacity 50 ~ 130% of outdoor unit capacity


connectable Model / Quantity P20 ~ P250 / 1 ~ 42
Noise level (measured in anechoic room) dB <A> 65 / 65.5
Diameter of Liquid (High press.) mm (in.) ø19.05 (ø3/4") Brazed
refrigerant pipe Gas (Low press.) mm (in.) ø41.28 (ø1-5/8") Brazed
The Set model is a combination of Main unit and Sub unit as follows.
Model (Main unit and Sub unit ) PUHY-P600YMM-A(-BS) PUHY-P650YSM-A(-BS)
External finish Pre-coated galvanized sheets (+ powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,840 x 1,990 x 840 1,840 x 1,990 x 840
in. 72-1/2" x 78-3/8" x 33-1/8" 72-1/2" x 78-3/8" x 33-1/8"
Net weight kg (lb) 458 (1,010) 460 (1,015)
Heat exchanger Salt-resistant cross fin & copper tube Salt-resistant cross fin & copper tube
Compressor Type x Quantity Inverter scroll hermetic comp. + Scroll hermetic comp.
Manufacturer AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter + Direct Inverter + Direct
Motor output kW 11.6 + 5.3 / 11.6 + 5.3 11.6 + 5.3 / 11.6 + 5.3
Case heater kW 0.045 x 2 (240V) 0.045 x 2 (240V)
Lubricant MEL32 MEL32
FAN Air flow rate m3 / min 400 400
L/s 6,667 6,667
cfm 14,126 14,126
External static press. 0 Pa (0 mmH2O) 0 Pa (0 mmH2O)
Type x Quantity Propeller fan x 2 Propeller fan x 2
Control, Driving mechanism Inverter-control, Direct-driven by motor Inverter-control, Direct-driven by motor
Motor output kW 0.38 x 2 0.38 x 2
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, pipe-in-pipe structure
Protection High pressure protection High pressure sensor, High pressure switch 4.15 MPa (601 psi)
Inverter circuit (COMP. / FAN) Over-current protection, Over-heat protection
Compressor Over-heat protection
Fan motor Thermal switch
Defrosting method Auto-defrost mode (Reversed refrigerant circle)
Refrigerant Type x Original charge R410A x 22.0 kg (49 lb) R410A x 22.0 kg (49 lb)
Control LEV and HIC circuit
Pipe between Main Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Pipe between Sub Liquid mm (in.) ø15.88 (ø5/8") Flare
-
unit and distributor Gas mm (in.) ø28.58 (ø1-1/8") Brazed
Oil balance pipe mm (in.) ø9.52 (ø3/8") Flare ø9.52 (ø3/8") Flare
Drawing External YGM- W656-885, 884, 886 1/2
Wiring YGM- W274-638A
Refrigerant circle YGM- rcd-850-1250ysgmhp
Standard Document Installation Manual
attachment Accessory Details refer to External Drw YGM-656-886/885/884, 1/2
Optional parts High static pressure motor : PAC-KBU04MT-F (60Pa)
Joint : CMY-Y102S/L-G,CMY-Y202/302-G ; Header : CMY-Y104/108/1010-G
Remark Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
Note : ✻1 Nominal cooling conditions ✻2 Nominal cooling conditions ✻3 Nominal heating conditions Unit converter
Indoor : 27˚CDB/19˚CWB (81˚FDB/66˚FWB) 27˚CDB/19.5˚CWB (81˚FDB/67˚FWB) 20˚CDB (68˚FDB) kcal/h = kW x 860
Outdoor : 35˚CDB (95˚FDB) 35˚CDB (95˚FDB) 7˚CDB/6˚CWB (45˚FDB/43˚FWB) Btu/h = kW x 3,412
Pipe length : 7.5 m (24-9/16 ft) 5 m (16-3/8 ft) 7.5 m (24-9/16 ft) cfm = m3/min x 35.31
Level difference : 0 m (0 ft) 0 m (0 ft) 0 m (0 ft) lb = kg / 0.4536
* Nominal conditions ✻1, ✻3 are subject to JIS B8615-1. *Above specification data is
* Due to continuing improvement, above specifications may be subject to change without notice. subject to rounding variation.
Ref. : Spec_y_p1250ygm

OUTDOOR UNIT R410A Y - 20


2. CAPACITY TABLES R410A Data G2

2-1. Correction by temperature


TM
CITY MULTI could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity
value and the ratio below, the capacity can be observed at various temperature.

PUHY- P200YGM P250YGM 1.4 Indoor Temperature


Nominal kW 22.4 28.0
Cooling kcal/h 19,300 24,100 1.3 24˚CWB
75˚FWB
Capacity Btu/h

Ratio of cooling capacity


76,400 95,500
1.2 22˚CWB
Input kW 6.14 7.72 72˚FWB

20˚CWB
1.1 68˚FWB

18˚CWB
64˚FWB
1.0
16˚CWB
61˚FWB
0.9
15˚CWB
59˚FWB

1.2 24˚CWB
75˚FWB

22˚CWB
1.1 72˚FWB

20˚CWB
1.0 68˚FWB
Ratio of power input

18˚CWB
64˚FWB
0.9
16˚CWB
61˚FWB
0.8
15˚CWB
59˚FWB

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 ˚CDB
23 32 41 50 59 68 77 86 95 104 113 ˚FDB
Ratio of cooling capacity and power input Outdoor temperature

PUHY- P200YGM P250YGM 1.3


Nominal kW 25.0 31.5
Heating kcal/h 21,500 27,100 1.2
Capacity Btu/h 15˚CDB
Ratio of heating capacity

85,300 107,500 59˚FDB


1.1
Input kW 5.98 7.62
20˚CDB
1.0 68˚FDB

0.9 25˚CDB
77˚FDB

0.8
27˚CDB
81˚FDB

0.7

0.6
Indoor Temperature

1.0
Ratio of power input

15˚CDB
59˚FDB
0.9
20˚CDB
0.8 68˚FDB

0.7 25˚CDB
77˚FDB

0.6 27˚CDB
81˚FDB

0.5

0.4
-20 -15 -10 -5 0 5 10 15 ˚CWB
-4 5 14 23 32 41 50 59 ˚FWB
Ratio of heating capacity and power input Outdoor temperature
Ref:cbt_p200-250

OUTDOOR UNIT R410A Y - 21


2. CAPACITY TABLES R410A Data G2

2-1. Correction by temperature


TM
CITY MULTI could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity
value and the ratio below, the capacity can be observed at various temperature.

PUHY- P300YGM P350YGM 1.4 Indoor Temperature


Nominal kW 33.5 40.0
Cooling kcal/h 28,800 34,400 1.3 24˚CWB
75˚FWB
Capacity Btu/h

Ratio of cooling capacity


114,300 136,500
1.2 22˚CWB
Input kW 9.57 11.39 72˚FWB

20˚CWB
PUHY- P400YGM 1.1 68˚FWB

18˚CWB
Nominal kW 45.0 64˚FWB
1.0
Cooling kcal/h 38,700 16˚CWB
Capacity Btu/h 153,500 61˚FWB
0.9
Input kW 13.42 15˚CWB
59˚FWB

1.2 24˚CWB
75˚FWB

22˚CWB
1.1 72˚FWB

20˚CWB
1.0 68˚FWB
Ratio of power input

18˚CWB
64˚FWB
0.9
16˚CWB
61˚FWB
0.8
15˚CWB
59˚FWB

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 ˚CDB
23 32 41 50 59 68 77 86 95 104 113 ˚FDB
Ratio of cooling capacity and power input Outdoor temperature

PUHY- P300YGM P350YGM 1.3


Nominal kW 37.5 45.0
Heating kcal/h 32,300 38,700 1.2
Capacity Btu/h 15˚CDB
Ratio of heating capacity

128,000 153,500 59˚FDB


1.1
Input kW 9.10 11.02
20˚CDB
PUHY- P400YGM 1.0 68˚FDB

Nominal kW 50.0
0.9 25˚CDB
Heating kcal/h 43,000 77˚FDB
Capacity Btu/h 170,600
0.8
Input kW 12.43 27˚CDB
81˚FDB

0.7

0.6
Indoor Temperature

1.0
Ratio of power input

15˚CDB
59˚FDB
0.9
20˚CDB
0.8 68˚FDB

0.7 25˚CDB
77˚FDB

0.6 27˚CDB
81˚FDB

0.5

0.4
-20 -15 -10 -5 0 5 10 15 ˚CWB
-4 5 14 23 32 41 50 59 ˚FWB
Ratio of heating capacity and power input Outdoor temperature
Ref:cbt_p300-400

OUTDOOR UNIT R410A Y - 22


2. CAPACITY TABLES R410A Data G2

2-1. Correction by temperature


TM
CITY MULTI could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity
value and the ratio below, the capacity can be observed at various temperature.

PUHY- P450YGM P500YGM 1.4 Indoor Temperature


Nominal kW 50.0 56.0
Cooling kcal/h 43,000 48,200 1.3 24˚CWB
75˚FWB
Capacity Btu/h

Ratio of cooling capacity


170,600 191,100
1.2 22˚CWB
Input kW 13.61 15.59 72˚FWB

20˚CWB
PUHY- P550YGM P600YGM 1.1 68˚FWB

18˚CWB
Nominal kW 63.0 67.4 64˚FWB
1.0
Cooling kcal/h 54,200 58,000 16˚CWB
Capacity Btu/h 215,000 230,000 61˚FWB
0.9
Input kW 17.08 17.59 15˚CWB
59˚FWB

PUHY- P650YGM
Nominal kW 73.0
Cooling kcal/h 62,800 1.2 24˚CWB
Capacity Btu/h 249,100
75˚FWB

22˚CWB
Input kW 19.65 1.1 72˚FWB

20˚CWB
1.0 68˚FWB
Ratio of power input

18˚CWB
64˚FWB
0.9
16˚CWB
61˚FWB
0.8
15˚CWB
59˚FWB

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 ˚CDB
23 32 41 50 59 68 77 86 95 104 113 ˚FDB
Ratio of cooling capacity and power input Outdoor temperature

PUHY- P450YGM P500YGM 1.3


Nominal kW 56.0 63.0
Heating kcal/h 48,200 54,200 1.2
Capacity Btu/h 15˚CDB
Ratio of heating capacity

191,100 215,000 59˚FDB


1.1
Input kW 13.86 15.89
20˚CDB
PUHY- P550YGM P600YGM 1.0 68˚FDB

Nominal kW 67.0 75.0


0.9 25˚CDB
Heating kcal/h 57,600 64,500 77˚FDB
Capacity Btu/h 228,600 255,900
0.8
Input kW 16.37 17.73 27˚CDB
81˚FDB

0.7
PUHY- P650YGM
Nominal kW 81.5
0.6
Heating kcal/h 70,100 Indoor Temperature
Capacity Btu/h 278,100
Input kW 19.82

1.0
Ratio of power input

15˚CDB
59˚FDB
0.9
20˚CDB
0.8 68˚FDB

0.7 25˚CDB
77˚FDB

0.6 27˚CDB
81˚FDB

0.5

0.4
-20 -15 -10 -5 0 5 10 15 ˚CWB
-4 5 14 23 32 41 50 59 ˚FWB
Ratio of heating capacity and power input Outdoor temperature
Ref:cbt_p450-650

OUTDOOR UNIT R410A Y - 23


2. CAPACITY TABLES R410A Data G2

2-1. Correction by temperature


TM
CITY MULTI could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity
value and the ratio below, the capacity can be observed at various temperature.

PUHY- P700YSGM P750YSGM 1.4 Indoor Temperature


Nominal kW 78.4 84.0
Cooling kcal/h 67,400 72,200 1.3 24˚CWB
75˚FWB
Capacity Btu/h

Ratio of cooling capacity


267,500 286,600
1.2 22˚CWB
Input kW 21.70 24.90 72˚FWB

20˚CWB
PUHY- P800YSGM 1.1 68˚FWB

18˚CWB
Nominal kW 90.0 64˚FWB
1.0
Cooling kcal/h 77,400 16˚CWB
Capacity Btu/h 307,100 61˚FWB
0.9
Input kW 26.75 15˚CWB
59˚FWB

1.2 24˚CWB
75˚FWB

22˚CWB
1.1 72˚FWB

20˚CWB
1.0 68˚FWB
Ratio of power input

18˚CWB
64˚FWB
0.9
16˚CWB
61˚FWB
0.8
15˚CWB
59˚FWB

0.7

0.6

0.5

0.4
-5 0 5 10 15 20 25 30 35 40 45 ˚CDB
23 32 41 50 59 68 77 86 95 104 113 ˚FDB
Ratio of cooling capacity and power input Outdoor temperature

PUHY- P700YSGM P750YSGM 1.3


Nominal kW 88.0 94.5
Heating kcal/h 75,700 81,300 1.2
Capacity Btu/h 15˚CDB
Ratio of heating capacity

300,300 322,400 59˚FDB


1.1
Input kW 21.83 25.37
20˚CDB
PUHY- P800YSGM 1.0 68˚FDB

Nominal kW 100.0
0.9 25˚CDB
Heating kcal/h 86,000 77˚FDB
Capacity Btu/h 341,200
0.8
Input kW 26.9 27˚CDB
81˚FDB

0.7

0.6
Indoor Temperature

1.0
Ratio of power input

15˚CDB
59˚FDB
0.9
20˚CDB
0.8 68˚FDB

0.7 25˚CDB
77˚FDB

0.6 27˚CDB
81˚FDB

0.5

0.4
-20 -15 -10 -5 0 5 10 15 ˚CWB
-4 5 14 23 32 41 50 59 ˚FWB
Ratio of heating capacity and power input Outdoor temperature
Ref:cbt_p700-800

OUTDOOR UNIT R410A Y - 24


2. CAPACITY TABLES R410A Data G2

2-1. Correction by temperature


TM
CITY MULTI could have varied capacity at different designing temperature. Using the nominal cooling/heating capacity
value and the ratio below, the capacity can be observed at various temperature.

PUHY- P850YSGM P900YSGM 1.4 Indoor Temperature


Nominal kW 96.0 101.0
Cooling kcal/h 82,600 86,900 1.3 24˚CWB
75˚FWB
Capacity Btu/h

Ratio of cooling capacity


327,600 344,600
1.2 22˚CWB
Input kW 25.28 26.71 72˚FWB

20˚CWB
PUHY- P950YSGM P1000YSGM 1.1 68˚FWB

18˚CWB
Nominal kW 108.0 113.0 64˚FWB
1.0
Cooling kcal/h 92,900 97,200 16˚CWB
Capacity Btu/h 368,500 385,600 61˚FWB
0.9
Input kW 29.23 31.11 15˚CWB
59˚FWB

PUHY- P1050YSGM P1100YSGM


Nominal kW 118.0 124.0
Cooling kcal/h 101,500 106,600 1.2 24˚CWB
Capacity Btu/h 402,600 423,100
75˚FWB

22˚CWB
Input kW 33.48 36.39 1.1 72˚FWB

20˚CWB
PUHY- P1150YSGM P1200YSGM 1.0 68˚FWB
Ratio of power input

Nominal kW 130.0 136.0 18˚CWB


64˚FWB
Cooling kcal/h 111,800 117,000 0.9
Capacity Btu/h 16˚CWB
443,600 464,000 61˚FWB
0.8
Input kW 39.96 44.40 15˚CWB
59˚FWB

PUHY- P1250YSGM 0.7

Nominal kW 140.0
0.6
Cooling kcal/h 120,400
Capacity Btu/h 477,700
0.5
Input kW 47.56

0.4
-5 0 5 10 15 20 25 30 35 40 45 ˚CDB
23 32 41 50 59 68 77 86 95 104 113 ˚FDB
Ratio of cooling capacity and power input Outdoor temperature

PUHY- P850YSGM P900YSGM 1.3


Nominal kW 108.0 113.0
Heating kcal/h 92,900 97,200 1.2
Capacity Btu/h 15˚CDB
Ratio of heating capacity

368,500 385,600 59˚FDB


1.1
Input kW 27.47 29.10
20˚CDB
PUHY- P950YSGM P1000YSGM 1.0 68˚FDB

Nominal kW 119.5 127.0


0.9 25˚CDB
Heating kcal/h 102,800 109,200 77˚FDB
Capacity Btu/h 407,700 433,300
0.8
Input kW 30.42 32.68 27˚CDB
81˚FDB

0.7
PUHY- P1050YSGM P1100YSGM
Nominal kW 132.0 140.0
0.6
Heating kcal/h 113,500 120,400 Indoor Temperature
Capacity Btu/h 450,400 477,700
Input kW 34.24 36.93

PUHY- P1150YSGM P1200YSGM 1.0


Ratio of power input

15˚CDB
Nominal kW 145.0 150.0 59˚FDB
Heating kcal/h 124,700 129,000 0.9
Capacity Btu/h 494,700 511,800 20˚CDB
0.8 68˚FDB
Input kW 38.46 39.73

0.7 25˚CDB
PUHY- P1250YSGM 77˚FDB

Nominal kW 156.5
0.6
Heating kcal/h 134,600 27˚CDB
81˚FDB
Capacity Btu/h 534,000
0.5
Input kW 42.63

0.4
-20 -15 -10 -5 0 5 10 15 ˚CWB
-4 5 14 23 32 41 50 59 ˚FWB
Ratio of heating capacity and power input Outdoor temperature
Ref:cbt_p850-1250

OUTDOOR UNIT R410A Y - 25


2. CAPACITY TABLES R410A Data G2

2-2. Correction by total indoor


TM
CITY MULTI system has different capacity and input at different total capacity of indoor unit connected. Using following
tables, the maximum capacity can be observed so as to ensure the system having enough capacity.

PUHY,PUY-P200,250YGM

50.0

40.0
Capacity(kW)

30.0

20.0

10.0
Input(kW)

5.0

P200 P250
Cooling Cooling
Heating Heating
0.0
100 150 200 250 300 350 400 450 500
Total capacity of indoor units

Ref: cbti-puhy200-250ygm
PUHY,PUY-P300,350YGM

50.0

40.0
Capacity(kW)

30.0

20.0

10.0
Input(kW)

5.0

P300 P350
Cooling Cooling
Heating Heating
0.0
100 150 200 250 300 350 400 450 500
Total capacity of indoor units

Ref: cbti-puhy300-350ygm

OUTDOOR UNIT R410A Y - 26


2. CAPACITY TABLES R410A Data G2

2-2. Correction by total indoor


TM
CITY MULTI system has different capacity and input at different total capacity of indoor unit connected. Using following
tables, the maximum capacity can be observed so as to ensure the system having enough capacity.

PUHY-P400,450YGM

80.0

70.0
Capacity(kW)

60.0

50.0

40.0

30.0
Input(kW)

15.0

10.0 P400 P450


Cooling Cooling
Heating Heating
5.0
200 250 300 350 400 450 500 550 600 650 700 750 800
Total capacity of indoor units

Ref: cbti-puhy400-450ygm
PUHY-P500,550YGM

80.0

70.0
Capacity(kW)

60.0

50.0

40.0

30.0
Input(kW)

15.0

10.0 P500 P550


Cooling Cooling
Heating Heating
5.0
200 250 300 350 400 450 500 550 600 650 700 750 800
Total capacity of indoor units

Ref: cbti-puhy500-550ygm

OUTDOOR UNIT R410A Y - 27


2. CAPACITY TABLES R410A Data G2

2-2. Correction by total indoor


TM
CITY MULTI system has different capacity and input at different total capacity of indoor unit connected. Using following
tables, the maximum capacity can be observed so as to ensure the system having enough capacity.

PUHY-P600,650YGM

100.0

80.0
Capacity(kW)

60.0

40.0

25.0

20.0
Input(kW)

15.0

10.0 P600 P650


Cooling Cooling
Heating Heating
5.0
300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
Total capacity of indoor units

Ref: cbti-puhy600-650ygm
PUHY-P700,750YSGM

100.0

80.0
Capacity(kW)

60.0

40.0

25.0

20.0
Input(kW)

15.0

10.0 P700 P750


Cooling Cooling
Heating Heating
5.0
300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
Total capacity of indoor units

Ref: cbti-puhy700-750ysgm

OUTDOOR UNIT R410A Y - 28


2. CAPACITY TABLES R410A Data G2

2-2. Correction by total indoor


TM
CITY MULTI system has different capacity and input at different total capacity of indoor unit connected. Using following
tables, the maximum capacity can be observed so as to ensure the system having enough capacity.

PUHY-P800,850YSGM

140.0

120.0
Capacity(kW)

100.0

80.0

60.0

25.0
Input(kW)

20.0

15.0 P800 P850


Cooling Cooling
Heating Heating
10.0
400 500 600 700 800 900 1000 1100 1200 1300
Total capacity of indoor units

Ref: cbti-puhy800-850ysgm
PUHY-P900,950YSGM

140.0

120.0
Capacity(kW)

100.0

80.0

60.0

25.0
Input(kW)

20.0

15.0 P900 P950


Cooling Cooling
Heating Heating
10.0
400 500 600 700 800 900 1000 1100 1200 1300
Total capacity of indoor units

Ref: cbti-puhy900-950ysgm

OUTDOOR UNIT R410A Y - 29


2. CAPACITY TABLES R410A Data G2

2-2. Correction by total indoor


TM
CITY MULTI system has different capacity and input at different total capacity of indoor unit connected. Using following
tables, the maximum capacity can be observed so as to ensure the system having enough capacity.

PUHY-P1000,1050YSGM

140.0

120.0
Capacity(kW)

100.0

80.0

60.0

30.0
Input(kW)

20.0

10.0 P1000 P1050


Cooling Cooling
Heating Heating
0.0
500 600 700 800 900 1000 1100 1200 1300 1400 1500
Total capacity of indoor units

Ref: cbti-puhy1000-1050ysgm
PUHY-P1100,1150YSGM

160.0

140.0
Capacity(kW)

120.0

100.0

80.0

40.0
Input(kW)

30.0

20.0 P1100 P1150


Cooling Cooling
Heating Heating
10.0
500 600 700 800 900 1000 1100 1200 1300 1400 1500
Total capacity of indoor units

Ref: cbti-puhy1100-1150ysgm

OUTDOOR UNIT R410A Y - 30


2. CAPACITY TABLES R410A Data G2

2-2. Correction by total indoor


TM
CITY MULTI system has different capacity and input at different total capacity of indoor unit connected. Using following
tables, the maximum capacity can be observed so as to ensure the system having enough capacity.

PUHY-P1200,1250YSGM

160.0

140.0
Capacity(kW)

120.0

100.0

80.0

40.0
Input(kW)

30.0

20.0 P1200 P1250


Cooling Cooling
Heating Heating
10.0
600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700
Total capacity of indoor units

Ref: cbti-puhy1200-1250ysgm

OUTDOOR UNIT R410A Y - 31


2. CAPACITY TABLES R410A Data G2

2-3. Correction by refrigerant piping length


TM
CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cool-
ing/heating capacity could happen correspondently. Using following correction factor according to the equivalent length of
the piping shown at 2.3a and 2.3b, the capacity can be observed. 2.3c shows how to obtain the equivalent length of piping.

2-3a. Cooling capacity correction


PUHY, PUY-P200YGM PUHY-P400YGM
1 1
Cooling capacity correction factor

Cooling capacity correction factor


Tota
0.95 Tot 0.95 l capa
al ca city
pac of in
ity door
0.9 of i 0.9 unit
ndo
or u
nit
0.85 0.85 200

0.8 100 0.8 300


400
0.75 150 0.75 520
200
0.7 260 0.7

0.65 0.65
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p200ygmc-y Ref.: crpl-p400ygmc-y

PUHY, PUY-P250YGM PUHY-P450YGM


1 1
Cooling capacity correction factor

Cooling capacity correction factor


0.95 Tota 0.95 Tota
l l capa
capa city
city of in
0.9 of in 0.9 doo
doo r un
r un it
it
0.85 0.85
225
125
0.8 0.8 338
188
450
0.75 250 0.75 585
325
0.7 0.7

0.65 0.65
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p250ygmc-y Ref.: crpl-p450ygmc-y

PUHY, PUY-P300YGM PUHY-P500YGM


1 1
Cooling capacity correction factor

Cooling capacity correction factor

0.95 Tota 0.95 Tota


l l cap
cap acit
acit y of
y of indo
0.9 indo 0.9 or u
or u nit
nit
0.85 0.85
250
0.8 150 0.8
375
225
0.75 0.75 500
300
390 650
0.7 0.7

0.65 0.65
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p300ygmc-y Ref.: crpl-p500ygmc-y

PUHY, PUY-P350YGM PUHY-P550YGM


1 1
Cooling capacity correction factor

Cooling capacity correction factor

0.95 Tota 0.95 Tota


l capa l capa
city city
of in of in
0.9 door 0.9 doo
unit r un
it
0.85 0.85
175
275
0.8 0.8
263
413
0.75 350 0.75
455 550
715
0.7 0.7

0.65 0.65
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p350ygmc-y Ref.: crpl-p550ygmc-y

OUTDOOR UNIT R410A Y - 32


2. CAPACITY TABLES R410A Data G2

2-3. Correction by refrigerant piping length


TM
CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cool-
ing/heating capacity could happen correspondently. Using following correction factor according to the equivalent length of
the piping shown at 2.3a and 2.3b, the capacity can be observed. 2.3c shows how to obtain the equivalent length of piping.

2-3a. Cooling capacity correction


PUHY-P600YGM PUHY-P800YSGM
1 1
Cooling capacity correction factor

Cooling capacity correction factor


0.95 Tota 0.95 Tota
l cap l cap
acit acit
y of y of
0.9 indo 0.9 indo
or u or u
nit nit
0.85 0.85

0.8 300 0.8 400

0.75 450 0.75 600


600 800
780 1040
0.7 0.7

0.65 0.65
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p600ygmc-y Ref.: crpl-p800ysgmc-y

PUHY-P650YGM PUHY-P850YSGM
1 1
Tota
Cooling capacity correction factor

Cooling capacity correction factor


0.95 0.95 l capa
Tota city
l cap of in
acit door
0.9 y of 0.9 unit
indo
or u
nit
0.85 0.85 425

0.8 0.8 637


325
850
0.75 488 0.75 1105
650
0.7 0.7
845
0.65 0.65
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p650ygmc-y Ref.: crpl-p850ysgmc-y

PUHY-P700YSGM PUHY-P900YSGM
1 1
Tota
Cooling capacity correction factor

Cooling capacity correction factor

0.95 Tota 0.95 l capa


l capa city
city of in
of in door
0.9 door 0.9 unit
unit
0.85 0.85 450
350
0.8 0.8 675
525 900
0.75 700 0.75 1170
910
0.7 0.7

0.65 0.65
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p700ysgmc-y Ref.: crpl-p900ysgmc-y

PUHY-P750YSGM PUHY-P950YSGM
1 1
Tota
Cooling capacity correction factor

Cooling capacity correction factor

0.95 Tota 0.95 l capa


l cap city
acit of in
y of door
0.9 indo 0.9 unit
or u
nit
0.85 0.85 475

0.8 375 0.8 712


950
563
0.75 0.75 1235
750
975
0.7 0.7

0.65 0.65
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p750ysgmc-y Ref.: crpl-p950ysgmc-y

OUTDOOR UNIT R410A Y - 33


2. CAPACITY TABLES R410A Data G2

2-3. Correction by refrigerant piping length


TM
CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cool-
ing/heating capacity could happen correspondently. Using following correction factor according to the equivalent length of
the piping shown at 2.3a and 2.3b, the capacity can be observed. 2.3c shows how to obtain the equivalent length of piping.

2-3a. Cooling capacity correction


PUHY-P1000YSGM PUHY-P1200YSGM
1 1
Cooling capacity correction factor

Cooling capacity correction factor


0.95 Total 0.95 Tota
c apac l
ity of cap
indo acit
or un y of
0.9 it 0.9 indo
or u
nit
0.85 500 0.85
600
0.8 750 0.8
1000 900
1300
0.75 0.75 1200
1560
0.7 0.7

0.65 0.65
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p1000ysgmc-y Ref.: crpl-p1200ysgmc-y

PUHY-P1050YSGM PUHY-P1250YSGM
1 1
Cooling capacity correction factor

Cooling capacity correction factor


0.95 Total 0.95
capa Tota
city o l cap
f ind acit
0.9 oor u 0.9 y of
nit indo
or u
nit
0.85 525 0.85
625
0.8 787 0.8
1050 937
0.75 1365 0.75 1250
1625
0.7 0.7

0.65 0.65
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p1050ysgmc-y Ref.: crpl-p1250ysgmc-y

PUHY-P1100YSGM
1
Cooling capacity correction factor

0.95 Tota
l capa
city
of in
0.9 door
unit
0.85
550
0.8
825
0.75 1100
1430
0.7

0.65
0 20 40 60 80 100 120 140 160
Piping equivalent length (m)
Ref.: crpl-p1100ysgmc-y

PUHY-P1150YSGM
1
Cooling capacity correction factor

0.95 Tota
l capa
city
of in
0.9 door
unit
0.85
575
0.8
862
0.75 1150
1495
0.7

0.65
0 20 40 60 80 100 120 140 160
Piping equivalent length (m)
Ref.: crpl-p1150ysgmc-y

OUTDOOR UNIT R410A Y - 34


2. CAPACITY TABLES R410A Data G2

2-3. Correction by refrigerant piping length


TM
CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cool-
ing/heating capacity could happen correspondently. Using following correction factor according to the equivalent length of
the piping shown at 2.3a and 2.3b, the capacity can be observed. 2.3c shows how to obtain the equivalent length of piping.

2-3b. Heating capacity correction


PUHY,PUY-P200,250YGM PUHY-P700,750,800YSGM
1.00 1.00
Heating capacity correction factor

Heating capacity correction factor


0.95 0.95

0.90 0.90
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p200_250ygmh Ref.: crpl-p700_800ysgmh

PUHY-P300,350,400YGM PUHY-P850,900,950,1000YSGM
1.00 1.00
Heating capacity correction factor

Heating capacity correction factor

0.95 0.95

0.90 0.90
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p300_400ygmh Ref.: crpl-p850_1000ysgmh

PUHY-P450,500,550,600,650YGM PUHY-P1050,1100,1150,1200,1250YSGM
1.00 1.00
Heating capacity correction factor

Heating capacity correction factor

0.95 0.95

0.90 0.90
0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 120 140 160
Piping equivalent length (m) Piping equivalent length (m)
Ref.: crpl-p450_650ygmh Ref.: crpl-p1050_1250ysgmh

2-3c. How to obtain the equivalent length of piping


1 PU(H)Y, PURY-P200YGM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 x number of bent on the piping) m
2 PU(H)Y, PURY-P250,300YGM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bent on the piping) m
3 PU(H)Y, PURY-P350YGM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.47 x number of bent on the piping) m
4 PUHY, PURY-P400,450,500,550,600,650YGM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bent on the piping) m
5 PUHY-P700,750,800YSGM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 x number of bent on the piping) m
6 PUHY-P850,900,950,1000,1050,1100,1150,1200,1250YSGM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.95 x number of bent on the piping) m

OUTDOOR UNIT R410A Y - 35


2. CAPACITY TABLES R410A Data G2

2-4. Correction at frosting and defrosting


Due to frosting at the outdoor heat exchanger and the automatical defrosting operation, the heating capacity of the outdoor
unit should be considered by multiplying the correction factor which shown in the table below.

Table of correction factor at frosting and defrosting


Outdoor inlet air temp. ˚C 6 4 2 1 0 -2 -4 -6 -8 -10 -20
Outdoor inlet air temp. ˚F 43 39 36 34 32 28 25 21 18 14 -4
PUHY,PUY,PURY-P200,250YGM 1.0 0.95 0.84 0.83 0.83 0.87 0.90 0.95 0.95 0.95 0.95
PUHY,PUY,PURY-P300YGM 1.0 0.93 0.82 0.80 0.82 0.86 0.90 0.90 0.95 0.95 0.95
PUHY,PUY,PURY-P350YGM 1.0 0.93 0.85 0.83 0.84 0.86 0.90 0.90 0.95 0.95 0.95
PUHY,PURY-P400YGM 1.0 0.95 0.90 0.87 0.88 0.89 0.90 0.95 0.95 0.95 0.95
PUHY,PURY-P450,500YGM 1.0 0.98 0.89 0.86 0.89 0.90 0.92 0.95 0.95 0.95 0.95
PUHY,PURY-P550,600,650YGM 1.0 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY,PURY-P700,750,800YSGM 1.0 0.98 0.89 0.879 0.89 0.90 0.92 0.95 0.95 0.95 0.95
PUHY-P850,900,950,1000YSGM
1.0 0.94 0.87 0.86 0.87 0.88 0.90 0.90 0.93 0.93 0.93
PUHY-P1050,1100,1150,1200,1250YSGM

2-5. Temp. range of running


• Cooling

˚FWB ˚CWB
86 30

77 25
Indoor temperature

68 20

59 15

50 10

41 5
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 ˚CDB
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122 ˚FDB
Outdoor temperature

* The operation temperature of outdoor unit is limited into 0~43˚CDB (32~109˚FDB) when the
outdoor unit is at a position lower than the indoor units.

• Heating

˚FDB ˚CDB
86 30

77 25
Indoor temperature

68 20

59 15

50 10

41 5
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 ˚CWB
-4 5 14 23 32 41 50 59 68 77 86 95 104 113 122 ˚FWB
Outdoor temperature
Ref.: tr-ygm-y

OUTDOOR UNIT R410A Y - 36


3. SOUND LEVELS R410A Data G2

Measurement condition Sound level of PUHY, PUY-P300YGM-A(-BS) Ref. : P300YGM-WYNB0-3618

PUY-P200,250,300,350YGM 90
85 Standard Night mode
PUHY-P200,250,300,350,400YGM
80
75

Octave band sound level (dB)


70
NC-70
65
1m
60
NC-60
55
50
NC-50
45
40
NC-40
35
Measurement 30
location 25 NC-30
1m
20 Approximate minimum
15 audible limit on NC-20
continuous noise NC-10
10
Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 65 61 58 55 51.5 51 51 45.5 59


60Hz 65 61 58 55 51.5 51 51 45.5 59
Night mode 50/60Hz 64 55 48.5 46.5 42.5 43 41.5 40 51
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY, PUY-P200YGM-A(-BS) Ref. : P200YGM-WYNB0-3616 Sound level of PUHY, PUY-P350YGM-A(-BS) Ref. : P350YGM-WYNB0-3619
90 90
85 Standard Night mode 85 Standard Night mode

80 80
75 75
Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70
65 65
60 60
NC-60 NC-60
55 55
50 50
NC-50 NC-50
45 45
40 40
NC-40 NC-40
35 35
30 30
25 NC-30 25 NC-30

20 Approximate minimum
20 Approximate minimum
15 audible limit on NC-20 15 audible limit on NC-20
continuous noise NC-10 continuous noise NC-10
10 10
Overall 63 125 250 500 1K 2K 4K 8K Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz) Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 62 58 56 52.5 49.5 50 41.5 38 56 Standard 50Hz 63 64 57.5 55 50.5 50.5 54 50 60
60Hz 62 58 56 52.5 49.5 50 41.5 38 56 60Hz 63 64 57.5 55 50.5 50.5 54 50 60
Night mode 50/60Hz 61 54.5 50 46 41.5 39.5 37 38 49 Night mode 50/60Hz 64 55 48.5 46.5 44.5 45 43.5 42 52
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from * When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe. Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY, PUY-P250YGM-A(-BS) Ref. : P250YGM-WYNB0-3617 Sound level of PUHY-P400YGM-A(-BS) Ref. : P400YGM-WYNB0-3620
90 90
85 Standard Night mode 85 Standard Night mode

80 80
75 75
Octave band sound level (dB)
Octave band sound level (dB)

70 70
NC-70 NC-70
65 65
60 60
NC-60 NC-60
55 55
50 50
NC-50 NC-50
45 45
40 40
NC-40 NC-40
35 35
30 30
25 NC-30 25 NC-30

20 Approximate minimum
20 Approximate minimum
15 audible limit on NC-20 15 audible limit on NC-20
continuous noise NC-10 continuous noise NC-10
10 10
Overall 63 125 250 500 1K 2K 4K 8K Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz) Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 62.5 58.5 55.5 53 49.5 49 49 43 57 Standard 50Hz 67.5 68.5 60.5 58.5 54.5 50.5 48.5 43 61
60Hz 62.5 58.5 55.5 53 49.5 49 49 43 57 60Hz 67.5 68.5 60.5 58.5 54.5 50.5 48.5 43 61
Night mode 50/60Hz 60 56.5 50 45.5 41 38.5 38 39 49 Night mode 50/60Hz 64.5 57.5 54.5 49 48 41.5 39 41 53
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from * When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe. Night Mode automatically in the case that the operation condition is severe.

OUTDOOR UNIT R410A Y - 37


3. SOUND LEVELS R410A Data G2

Measurement condition Sound level of PUHY-P550YGM-A(-BS) Ref. : P550YGM-WYNB0-3623

PUHY-P450,500,550,600,650YGM 90
85 Standard 50Hz
Standard 60Hz
80 Night mode
75

Octave band sound level (dB)


70
NC-70
65
1m
60
NC-60
55
50
NC-50
45
40
NC-40
35
Measurement
30

1m
location
25 NC-30

20 Approximate minimum
15 audible limit on NC-20
continuous noise NC-10
10
Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 67 61 62 59 54 52.5 49.5 44 61


60Hz 66.5 65.5 61.5 60 55 51.5 51.5 46 62
Night mode 50/60Hz 58.5 54.5 51.5 53.5 44.5 45.5 41 35.5 54
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY-P450YGM-A(-BS) Ref. : P450YGM-WYNB0-3621 Sound level of PUHY-P600YGM-A(-BS) Ref. : P600YGM-WYNB0-3624
90 90
85 Standard 50Hz 85 Standard 50Hz
Standard 60Hz Standard 60Hz
80 Night mode 80 Night mode
75 75
Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70
65 65
60 60
NC-60 NC-60
55 55
50 50
NC-50 NC-50
45 45
40 40
NC-40 NC-40
35 35
30 30
25 NC-30 25 NC-30

20 Approximate minimum
20 Approximate minimum
15 audible limit on NC-20 15 audible limit on NC-20
continuous noise NC-10 continuous noise NC-10
10 10
Overall 63 125 250 500 1K 2K 4K 8K Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz) Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 66.5 62.5 60.5 58 53.5 50.5 46 41.5 60 Standard 50Hz 69 66.5 62 58 53.5 51.5 51 46 61
60Hz 70.5 64.5 61 59.5 54.5 51 47 41 61 60Hz 65 66.5 63 59 54 52.5 51.5 46.5 62
Night mode 50/60Hz 61.5 60 51.5 51 46.5 41 36.5 39.5 53 Night mode 50/60Hz 59.5 55.5 51 52 48 44.5 42.5 37.5 54
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from * When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe. Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY-P500YGM-A(-BS) Ref. : P500YGM-WYNB0-3622 Sound level of PUHY-P650YGM-A(-BS) Ref. : P650YGM-WYNB0-3625
90 90
85 Standard 50Hz 85 Standard 50Hz
Standard 60Hz Standard 60Hz
80 Night mode 80 Night mode
75 75
Octave band sound level (dB)
Octave band sound level (dB)

70 70
NC-70 NC-70
65 65
60 60
NC-60 NC-60
55 55
50 50
NC-50 NC-50
45 45
40 40
NC-40 NC-40
35 35
30 30
25 NC-30 25 NC-30

20 Approximate minimum
20 Approximate minimum
15 audible limit on NC-20 15 audible limit on NC-20
continuous noise NC-10 continuous noise NC-10
10 10
Overall 63 125 250 500 1K 2K 4K 8K Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz) Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 67 61.5 60.5 58 53.5 50.5 48 43 60 Standard 50Hz 69.5 63 61.5 59.5 54.5 52.5 54 47 62
60Hz 68 65 60.5 59 54 51.5 49 43.5 61 60Hz 65 67 62 59.5 55 53 54.5 49 62.5
Night mode 50/60Hz 60 52.5 52 52.5 45.5 43 39 38.5 53 Night mode 50/60Hz 60.5 55.5 54.5 53 44.5 42 43.5 38.5 54
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from * When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe. Night Mode automatically in the case that the operation condition is severe.

OUTDOOR UNIT R410A Y - 38


3. SOUND LEVELS R410A Data G2

Measurement condition Sound level of PUHY-P800YSGM-A(-BS) Ref. : P800YGM-WYNB0-3631

PUHY-P700,750,800YSGM 90
85 Standard Night mode

80
75

Octave band sound level (dB)


1m 70
NC-70
65
60
Measurement NC-60
55
location
50
NC-50
45
40
NC-40
35

1m
30
25 NC-30

20 Approximate minimum
15 audible limit on NC-20
continuous noise NC-10
10
Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 62.5 65.5 64.5 61 58 55 53.5 50 64


60Hz 62.5 65.5 64.5 61 58 55 53.5 50 64
Night mode 50/60Hz 58 58.5 56 51.5 49 47 48 45 56
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY-P700YSGM-A(-BS) Ref. : P700YGM-WYNB0-3629


90
85 Standard Night mode

80
75
Octave band sound level (dB)

70
NC-70
65
60
NC-60
55
50
NC-50
45
40
NC-40
35
30
25 NC-30

20 Approximate minimum
15 audible limit on NC-20
continuous noise NC-10
10
Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 65.5 63 64 60 55 52 50.5 47 62


60Hz 65.5 63 64 60 55 52 50.5 47 62
Night mode 50/60Hz 58 55.5 57 53 44.5 41.5 41.5 42 54
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY-P750YSGM-A(-BS) Ref. : P750YGM-WYNB0-3630


90
85 Standard Night mode

80
75
Octave band sound level (dB)

70
NC-70
65
60
NC-60
55
50
NC-50
45
40
NC-40
35
30
25 NC-30

20 Approximate minimum
15 audible limit on NC-20
continuous noise NC-10
10
Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 65 63.5 64.5 61 56.5 53 51 47 63


60Hz 65 63.5 64.5 61 56.5 53 51 47 63
Night mode 50/60Hz 58 57 58 54 45.5 43 43 43.5 55
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

OUTDOOR UNIT R410A Y - 39


3. SOUND LEVELS R410A Data G2

Measurement condition Sound level of PUHY-P950YSGM-A(-BS) Ref. : P950YSGM-WYNB0-3716

PUHY-P850,900,950,1000,1050,1100,1150,1200,1250YSGM 90
85 Standard 50Hz
Standard 60Hz
80 Night mode
75

Octave band sound level (dB)


70
NC-70
65
60
Main unit Sub unit 1m NC-60
55
50
NC-50
45
40
NC-40
35
Measurement 30
location
NC-30

1m
25
20 Approximate minimum
15 audible limit on NC-20
continuous noise NC-10
10
Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 69.5 64.5 64 61 56.5 54 51 45.5 63


60Hz 72 67.5 64 62.5 57.5 54 52.5 47 64
Night mode 50/60Hz 64 62 55.5 56 49 47.5 43 41.5 57
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY-P850YSGM-A(-BS) Ref. : P850YSGM-WYNB0-3714 Sound level of PUHY-P1000YSGM-A(-BS) Ref. : P1000YSGM-WYNB0-3717
90 90
85 Standard 50Hz 85 Standard 50Hz
Standard 60Hz Standard 60Hz
80 Night mode 80 Night mode
75 75
Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70
65 65
60 60
NC-60 NC-60
55 55
50 50
NC-50 NC-50
45 45
40 40
NC-40 NC-40
35 35
30 30
25 NC-30 25 NC-30

20 Approximate minimum
20 Approximate minimum
15 audible limit on NC-20 15 audible limit on NC-20
continuous noise NC-10 continuous noise NC-10
10 10
Overall 63 125 250 500 1K 2K 4K 8K Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz) Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 70 66 64 61.5 56.5 53.5 49 44.5 63 Standard 50Hz 70.5 67.5 64 60.5 56 54 52 47 63
60Hz 73.5 67.5 64 62..5 57.5 54 50 44 64 60Hz 71.5 68.5 65 62 57 54.5 52.5 47.5 64
Night mode 50/60Hz 65 64 55 54.5 49.5 44 39.5 42.5 56 Night mode 50/60Hz 64.5 62.5 56 55 51 47 44 42 57
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from * When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe. Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY-P900YSGM-A(-BS) Ref. : P900YSGM-WYNB0-3715 Sound level of PUHY-P1050YSGM-A(-BS) Ref. : P1050YSGM-WYNB0-3718
90 90
85 Standard 50Hz 85 Standard 50Hz
Standard 60Hz Standard 60Hz
80 Night mode 80 Night mode
75 75
Octave band sound level (dB)

Octave band sound level (dB)

70 70
NC-70 NC-70
65 65
60 60
NC-60 NC-60
55 55
50 50
NC-50 NC-50
45 45
40 40
NC-40 NC-40
35 35
30 30
25 NC-30 25 NC-30

20 Approximate minimum
20 Approximate minimum
15 audible limit on NC-20 15 audible limit on NC-20
continuous noise NC-10 continuous noise NC-10
10 10
Overall 63 125 250 500 1K 2K 4K 8K Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz) Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 70 65 63.5 61 57 54 50.5 45.5 63 Standard 50Hz 71 65.5 63.5 61.5 56.5 54 54 48 63.5
60Hz 72.5 68 64 62.5 57.5 54.5 51.5 45.5 64 60Hz 71.5 68.5 64.5 62 57.5 55 55 49.5 64.5
Night mode 50/60Hz 64 61 55 55 49 46 41 42 56 Night mode 50/60Hz 64.5 62.5 57 56 49 45 45 42.5 57
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from * When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe. Night Mode automatically in the case that the operation condition is severe.

OUTDOOR UNIT R410A Y - 40


3. SOUND LEVELS R410A Data G2

Sound level of PUHY-P1100YSGM-A(-BS) Ref. : P1100YSGM-WYNB0-3719 Sound level of PUHY-P1250YSGM-A(-BS) Ref. : P1250YSGM-WYNB0-3722
90 90
85 Standard 50Hz 85 Standard 50Hz
Standard 60Hz Standard 60Hz
80 Night mode 80 Night mode
75 75
Octave band sound level (dB)

Octave band sound level (dB)


70 70
NC-70 NC-70
65 65
60 60
NC-60 NC-60
55 55
50 50
NC-50 NC-50
45 45
40 40
NC-40 NC-40
35 35
30 30
25 NC-30 25 NC-30

20 Approximate minimum
20 Approximate minimum
15 audible limit on NC-20 15 audible limit on NC-20
continuous noise NC-10 continuous noise NC-10
10 10
Overall 63 125 250 500 1K 2K 4K 8K Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz) Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A) 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 71.5 65.5 64 62 57 54.5 54.5 48.5 64 Standard 50Hz 73 69 65.5 62.5 57.5 55.5 56 50 65
60Hz 72 69 64.5 62.5 58 55.5 56 50 65 60Hz 68 70 66 63 58 56 56.5 51.5 65.5
Night mode 50/60Hz 64.5 62 57 56 49 45 45 42 57 Night mode 50/60Hz 64 60 57.5 56.5 51 48 47 42 58
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from * When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe. Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY-P1150YSGM-A(-BS) Ref. : P1150YSGM-WYNB0-3720


90
85 Standard 50Hz
Standard 60Hz
80 Night mode
75
Octave band sound level (dB)

70
NC-70
65
60
NC-60
55
50
NC-50
45
40
NC-40
35
30
25 NC-30

20 Approximate minimum
15 audible limit on NC-20
continuous noise NC-10
10
Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 71.5 65.5 64 62 57 54.5 54.5 48.5 64


60Hz 70 69.5 64.5 62.5 58 55.5 56 51 65
Night mode 50/60Hz 63 59 56.5 56.5 48 47.5 46 41 57
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

Sound level of PUHY-P1200YSGM-A(-BS) Ref. : P1200YSGM-WYNB0-3721


90
85 Standard 50Hz
Standard 60Hz
80 Night mode
75
Octave band sound level (dB)

70
NC-70
65
60
NC-60
55
50
NC-50
45
40
NC-40
35
30
25 NC-30

20 Approximate minimum
15 audible limit on NC-20
continuous noise NC-10
10
Overall 63 125 250 500 1K 2K 4K 8K
Octave band central frequency (Hz)
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz dB(A)

Standard 50Hz 70.5 64.5 64.5 61.5 57 55 54.5 48 64


60Hz 69 69.5 65 62.5 58 55 56 51 65
Night mode 50/60Hz 63 59 56.5 56.5 48 47.5 46 41 57
* When Night Mode is set, the A/C system's capacity is limited. The system could return to normal operation from
Night Mode automatically in the case that the operation condition is severe.

OUTDOOR UNIT R410A Y - 41


494

16
ø27 Knockout hole
Y <Bottom hole for
control wiring>
Conn. pipe(Gas)
200: ø19.05 <Brazed>

840
877
250: ø22.2 <Brazed> Y
300: ø22.2 <Brazed>
350: ø28.58 <Brazed>

553
845(mounting pitch)

20

80
A
166
70

57
16
4. EXTERNAL DIMENSIONS

65 160 ø62 Knockout hole 2X2-14X20 0val hole


768 80 45 900(mounting pitch) 45
<Hole for power supply> (Mounting hole)
Conn. pipe(Liquid) Changeable to ø27,ø33 by using 990
Knockout hole attached conduit mounting plate <Accessory>
200: ø9.52 <Flare> <Bottom piping hole>
250: ø9.52 <Flare> Top view
Air outlet
300: ø9.52 <Flare> Cross section X – X
350: ø12.7 <Flare>
PUHY,PUY-P200,250,300,350YGM-A(-BS)

265

Model A
200 132
250 136

ø53
300 136
350 146

OUTDOOR UNIT
Air
12 5 inlet
Air
inlet
1840

<Accessories> Cross section Y –Y Knockout hole


• Refrigerant (Gas) conn. pipe......1 pc.
1575

(P200type:Packaged in the accessory kit) Service panel


ø27 Knockout hole
(P250,P300,P350type:Already installed on the unit) <Left side hole for
135 Refrig. service
• Packing for conn. pipe................1 pc. control wiring>
(P200type:Not attached) 80 40 valve (Liquid) 67 160
<Flare>
(P250,P300,P350type:Attached near the ball valve) X X
• Conduit mounting plate
44

ø33, ø27..............................1 pc.Each


• Tapping screw M4......................2 pcs.
280
235

Note1.Use the opening at the bottom of the unit


150

134 100

when running the power supply line from

10 90
11 78

the front or from the side of the unit. 100 83 Knockout hole
Note2.Please refer to the next page for information 37 117 117 37 Knockout hole <Front piping
<Left piping hole> Refrig. service 67 207 hole> 207 67
regarding necessary spacing around the valve(Gas)
unit and foundation work. Left side view <Flange> Front view
Unit : mm
Drw. : YGM-W656-818 1/2

R410A Y - 42
R410A Data G2
1.Space required around unit
✻ In case of single installation ✻ In case of collective installation and continuous installation
[Basic rules for spacing the unit] 1Space required for collective installation and continuous installation:
1Since the service from the back of unit is required, When installing several units, provide the space between each block considering passage for air and people.
provide the back space 450 mm or above as the front. 2Open in two directions.
3In case of wall height <H> exceeds total height of unit, add <h> dimension
(h= wall height <H> - total height of unit) to ❈ marked dimension.

450
4If there is a wall at both the front and the rear of the unit, install up to four units consecutively in
the side direction and provide a space of 1000 mm or more as inlet space/passage space for each four units.

450
Wall height <H> B
Front Wall height <H> Wall height <H>
<Top view>

450
[When inlet air enters from right
B B A A A A A
and left sides of unit]
A A ❈

450
1Wall heights <H> of the front and the back sides
shall be within total height of unit.
4. EXTERNAL DIMENSIONS

2When wall height <H'> exceeds total height of unit, 450 450 450 450
add <h> dimension to 450 of the following figure. 1000 Wall height <H> 450 450
h= wall height <H'> - total height of unit. ❈ B ❈
450 450
Wall height <H> Wall height <H>

450
h
450
450

H
H'
A A

450
H
B A A A A B

900
900

B
Spacing PUHY,PUY-P200,250,300,350YGM-A(-BS)

No restrictions on wall height

OUTDOOR UNIT
<Side view>
<left and right>

450
B

1000 1000 1000


Wall height <H>
No restrictions on wall height A Front
B Must be open
A A A
(Unit : mm)

2.Foundation work 450 450

1When building the foundation, give full attention to the floor strength,
drain water disposal <drain water flows out of the unit, during operation>,
piping and wiring routes.
2Be sure that the corners are firmly seated. If the corners are not firmly
seated, the installation feet may be bent.
Corner
3When down piping and down wiring are performed, be sure that foundation and
base work does not block the base through holes.
M10 Anchor Bolt
<Local supply>
Unit : mm
Drw. : YGM-W656-818 2/2

R410A Y - 43
R410A Data G2
644

16
ø27 Knockout hole
Y <Bottom hole for
control wiring>

840
877
PUHY-P400YGM-A(-BS)

Knockout hole Y
<Bottom piping hole>

503
845(mounting pitch)

20

80
166

145
16

57
70
65 160 2X2-14X20 Oval hole
4. EXTERNAL DIMENSIONS

1068 80 ø62 Knockout hole 45 1200(mounting pitch) 45


<Hole for power supply> (Mounting hole)
1290
to ø46,ø53 by using
Conn. pipe(Gas) Cross section X – X Changeable
attached conduit mounting plate <Accessory>
ø28.58<Brazed> Top view
Conn. pipe(Liquid) Air outlet
ø12.7<Flare>
265

ø53

OUTDOOR UNIT
Air
12 5 inlet

Air
1840

Cross section Y – Y inlet Knockout hole


1575

ø27 Knockout hole


<Accessories> <Left side hole for Service panel
• Refrigerant (Gas) conn. pipe......1 pc. 135 control wiring>
(Already installed on the unit) Refrig. service
80 40
• Packing for conn. pipe................1 pc. valve (Liquid) 67 160
(Attached near the ball valve) <Flare> X X
• Conduit mounting plate
44

ø53, ø46.............................1 pc.Each


• Tapping screw M4.....................2 pcs.
280
235

Note1.Use the opening at the bottom of the unit


150

89
134 100

when running the power supply line from


11 78

10
the front or from the side of the unit. 100 83 Knockout hole
Knockout hole
Note2.Please refer to the next page for information 37 115 115 37 <Left piping hole> 68 355 <Front piping 355 68
regarding necessary spacing around the Refrig. service hole>
valve(Gas)
unit and foundation work. <Flange>
Left side view Front view
Unit : mm
Drw. : YGM-W656-819 1/2

R410A Y - 44
R410A Data G2
1.Space required around unit
✻ In case of single installation ✻ In case of collective installation and continuous installation
[Basic rules for spacing the unit] 1Space required for collective installation and continuous installation:
1Since the service from the back of unit is required, When installing several units, provide the space between each block considering passage for air and people.
provide the back space 450 mm or above as the front. 2Open in two directions.
3In case of wall height <H> exceeds total height of unit, add <h> dimension
(h=wall height <H> -total height of unit) to ❈ marked dimension.

450
4If there is a wall at both the front and the rear of the unit, install up to four units consecutively in
the side direction and provide a space of 1000 mm or more as inlet space/passage space for each four units.

450
Front Wall height <H>
B
<Top view>
Wall height <H> Wall height <H>

450

[When inlet air enters from right B B A A A A A
and left sides of unit] A A

450

1Wall heights <H> of the front and the back sides
Spacing PUHY-P400YGM-A(-BS)
4. EXTERNAL DIMENSIONS

shall be within total height of unit.


450 450 450 450 450 450
2When wall height <H> exceeds total height of unit, 1000 Wall height<H>
add <h> dimension to 450 of the following figure. ❈ B ❈
h=wall height <H'> -total height of unit.
450 450 Wall height <H> Wall height <H>

450
h
450
450

H
H'
A

450
H
A A
A

900
B B A A B
900

No restrictions on wall height <Side view>

450

OUTDOOR UNIT
<left and right>
B
1000 Wall height <H> 1000 1000

No restrictions on wall height A Front


B Must be open
A A A
(Unit : mm)

450 450
2.Foundation work
1When building the foundation, give full attention to the floor strength,
drain water disposal <drain water flows out of the unit, during operation>,
piping and wiring routes.
2Be sure that the corners are firmly seated. If the corners are not firmly
seated, the installation feet may be bent.
Corner
3When down piping and down wiring are performed, be sure that foundation and
base work does not block the base through holes. M10 Anchor Bolt
<Local supply>
Unit : mm
Drw. : YGM-W656-819 2/2

R410A Y - 45
R410A Data G2
494 1000

16
Y Y

840
877

Y Y
Knockout hole ø27 Knockout hole
<Bottom hole for

553
<Bottom piping hole>
control wiring>
845(mounting pitch)

20

80
162

145
16

57
ø62 Knockout hole

70
65 160 3X2-14X20 Oval hole 45 950(mounting pitch) 950(mounting pitch) 45
<Hole for power supply>
768 80
4. EXTERNAL DIMENSIONS

Changeable to ø46,ø53 by using (Mounting hole) 1990


Conn. pipe(Gas) attached conduit mounting plate <Accessory>
ø28.58<Brazed> Conn. pipe(Liquid)
ø15.88<Flare> Cross section X – X Top view
Air outlet
PUHY-P450,500,550,600,650YGM-A(-BS)

265

ø53

OUTDOOR UNIT
12 5 Air
inlet

Cross section Y – Y Air


1840

inlet Knockout hole


1575

<Accessories> ø27 Knockout hole Service panel


• Refrigerant (Gas) conn. pipe....1 pc. <Left side hole for
135 control wiring>
(Already installed on the unit) Refrig. service
• Packing for conn. pipe......1 pc. 80 40
valve (Liquid) 67 160
(Attached near the ball valve) <Flare>
• Conduit mounting plate X X
ø53, ø46......1 pc.Each
44

• Tapping screw M4...2 pcs.

280
235

Note1.Use the opening at the bottom of the unit


150

89
134 100
when running the power supply line from
the front or from the side of the unit.
11 78

100 83

10
Note2.Please refer to the next page for information Knockout hole Knockout hole
37 115 115 37 <Left piping hole> 68 205 <Front piping hole> 205 68
regarding necessary spacing around the Refrig. service
unit and foundation work. valve(Gas)
Left side view <Flange>
Front view
Unit : mm
Drw. : YGM-W656-820 1/2

R410A Y - 46
R410A Data G2
1.Space required around unit
✻ In case of single installation ✻ In case of collective installation and continuous installation
[Basic rules for spacing the unit] 1Space required for collective installation and continuous installation:
1Since the service from the back of unit is required, When installing several units, provide the space between each block considering passage for air and people.
provide the back space 450 mm or above as the front. 2Open in two directions.
3In case of wall height <H> exceeds total height of unit,add <h> dimension
(h=wall height <H> -total height of unit) to ❈ marked dimension.

450
4If there is a wall at both the front and the rear of the unit, install up to three units consecutively in
the side direction and provide a space of 1000 mm or more as inlet space/passage space for each three units.

450
Front B
Wall height <H> Wall height <H> Wall height <H>
<Top view>

[When inlet air enters from right


450
and left sides of unit] A A A A A
1Wall heights <H> of the front and the back sides B B
shall be within total height of unit.
4. EXTERNAL DIMENSIONS

A A ❈

450
2When wall height <H> exceeds total height of unit,
add <h> dimension to 450 of the following figure.
h=wall height <H> -total height of unit. 450 450 450 450
1000 Wall height <H> 450 450
450 450 B
❈ ❈
Wall height <H> Wall height <H>

450
h
450

450
A

H
H'

450
A

H
Spacing PUHY-P450,500,550,600,650YGM-A(-BS)

A A A A

900
900

B B B

OUTDOOR UNIT
No restrictions on wall height <Side view>
<left and right>

450 B

1000 Wall height <H> 1000 1000

A Front
B Must be open

(Unit : mm)
2.Foundation work
1When building the foundation, give full attention to the floor strength,
drain water disposal <drain water flows out of the unit, during operation>,
piping and wiring routes.
2Be sure that the corners are firmly seated.If the corners are not firmly
seated, the installation feet may be bent. Corner
3When down piping and down wiring are performed, be sure that foundation and
base work does not block the base through holes.
M10 Anchor Bolt
<Local supply>
Unit : mm
Drw. : YGM-W656-820 2/2

R410A Y - 47
R410A Data G2
544 650

16
Y Y

Knockout hole Y Y

840
877
<Bottom piping hole> 75 162 171 162
Refrig.service valve
(to indoor unit:Gas)

553
845(mounting pitch)
ø27 Knockout hole
<Bottom hole for
control wiring>

72 115
16

ø62 Knockout hole

107
161
95
3 X 2 – 14 X 20 Oval hole 45 800(mounting pitch) 800(mounting pitch) 45

115
124
159
<Hole for power supply>
Changeable to ø53 by using 323 Refrig.service valve 1690
(Mounting hole)
attached conduit mounting plate 625 (to indoor unit:Liquid)
PUHY-P700,750,800YGM-A(-BS)

<Accessory>
4. EXTERNAL DIMENSIONS

Cross section X – X Top view

60
ø53
Air outlet
5
Cross section Y – Y
265

<Accessories>
• Refrigerant conn. pipe with flange (to indoor unit:Gas)....1 pc.
(Already installed on the unit)
• Refrigerant conn. pipe with flange
(to heat exchanger unit:Gas)............................................1 pc. Service panel
(Already installed on the unit)
• Packing for conn. pipe with flange (to indoor unit:Gas)....1 pc.

OUTDOOR UNIT
(Attached near ball valve)
Air
• Packing for conn. pipe with flange inlet
(to heat exchanger unit:Gas)............................................1 pc.
(Attached near ball valve) Air Knockout hole
1840

• Refrigerant conn.pipe with flare nut inlet


(to indoor unit:Liquid)........................................................1 pc. Service panel
1575

(Includes one piece each for bottom piping and front piping ø27 Knockout hole Refrig. service valve
as accessories) <Left side hole for (to heat exchanger unit:Gas)
135
X X
• Crossover connection of refrigerant piping control wiring> 75 162 171 162 Conn. pipe(Gas)
(to heat exchanger unit:Gas)............................................1 pc. 80 40 Conn. pipe (to indoor unit:Gas)
• Crossover connection of refrigerant piping Knockout hole (to heat exchanger unit:Gas) ø34.93<Braze>
(to heat exchanger unit:Liquid).........................................1 pc. <Left side piping ø28.58<Brazed> Conn. pipe(Liquid)
11

• Conduit mounting plate hole for heat exchanger unit> (to indoor unit:Liquid)
ø19.05<Braze+Flare>
4

ø53....................................................1 pc.

280
252

• Wire clamping plate ...........................1 pc.


226
A

134 100
78

• Tapping screw M4..............................4 pcs.

10 90
Refrig. service valve 117 83 254 88
11

Note1.Use the opening at the bottom of the unit 37 175 175 37 (to heat exchanger unit:Liquid) 355 253
when running the power supply line from ø12.7<Flare> 253 355 Knockout hole
the front or from the side of the unit. <Front piping hole>
Note2.Please refer to page 74 for information Direction of the pipe end A
regarding necessary spacing around the Left side view in the case of the bottom 192 Front view
unit and foundation work. in the case of the front 161
Note3.This unit is used in combination with
a heat exchanger unit. (Refer to Drawing
No.W656825 Outline Drawing of Outdoor
Unit set)
Unit : mm
Drw. : YGM-W656-824A 1/2

R410A Y - 48
R410A Data G2
16
Note1.Use the opening at the bottom of the unit
when running the power supply line from
the side of the unit.
Note2.Please refer to page 74 for information
regarding necessary space around the
unit and foundation work.

877

840
ø27hole+rubber bush
PUHN-P01YGM-A(-BS)

<Hole for control wiring>


(Bottom of control box)

845(mounting pitch)

82
120 60 ø27hole+rubber bush

16
<Hole for power supply> 2x2-14x20 Oval hole
(Bottom of control box) 45 900(mounting pitch) 45
4. EXTERNAL DIMENSIONS

(Mounting hole) 990


Cross section X-X
Top view
Air outlet Air outlet

265

OUTDOOR UNIT
Air Air Air Air
inlet inlet inlet inlet
1840

1575

Knockout hole
Refrig. service valve X X <Right side piping hole>
(Gas pipe to compressor unit) 40 80
ø28.58<Braze> 70 45
50

Refrig. service valve


250

(Liquid pipe to compressor unit)


165
134 115

ø12.7<Braze>

10 90
11 78

80
37 117 Air 117 37 67 207 157 Air
inlet 207 67 inlet
Knockout hole
<Front side piping hole>
Left side view Right side view
Front view
Unit : mm
Drw. : YGM-W656-823A 1/2

R410A Y - 49
R410A Data G2
877 2690
840 990 10 1690
Air outlet Heat exchanger unit Compressor unit

265
4. EXTERNAL DIMENSIONS

PUHY-P700,750,800YSGM-A(-BS)

Air Air
inlet inlet
1840

1575

OUTDOOR UNIT
Crossover connection of refigerant piping Conn.pipe
(to heat exchanger unit:Gas) (to indoor unit:Gas) Conn.pipe
(Included with the compressor unit) ø34.93<Brazed> (to indoor unit:Liquid)
ø28.58<Brazed> ø19.05<Brazed+Flare>
Left side view Front view (Included one peace each for bottom piping
Crossover connection of refigerant piping and front piping with the compressor unit)
(to heat exchanger unit:Liquid)
(Included with the compressor unit)
ø12.7<Brazed>
Unit : mm
Drw. : YGM-W656-825A 1/1

R410A Y - 50
R410A Data G2
1.Space required around unit
✻ In case of single installation ✻ In case of collective installation and continuous installation
[Basic rules for spacing the unit] 1Space required for collective installation and continuous installation:
1There must be a minimum of 100 mm of back space. When installing several units, provide the space between each block considering passage for air flow and people.
However,provide 450 mm or more of back space as front 2Open in two directions around units.
space for easier access when servicing the unit. 3In case of wall height<H> exceeds total height of unit,add <h>dimension
(h= wall height<H> - total height of unit)to ❈ marked dimension.
Compressor unit 4If there is a wall at both of the front and the rear of the unit,install up to 2 sets(heat exchanger unit and

100
Heat exchanger unit compressor unit:2 units each) consecutively in the side direction and provide a space of 1000 mm
or more for air inlet space/passage space for each 2 sets.

Wall height<H> B Wall height<H>


Wall height<H>

450
250

Front
<Top view>
[When inlet air enters from right B B A A A A A
and left sides of unit] A A
4. EXTERNAL DIMENSIONS

1Wall heights<H> of the front and the back sides


shall be within total height of unit. ❈

450
2When wall height<H'> exceeds total height of unit, 1000 Wall height<H>
add <h>dimension to 450 of the following figure. 450 450 450 450 450 250
h= wall height<H'> - total height of unit. ❈ ❈
B
Heat exchanger unit Compressor unit

100
Spacing PUHY-P700,750,800YSGM-A(-BS)

Wall height<H> Wall height<H>

250
250

450
No restrictions on wall height

OUTDOOR UNIT
<left and right> B A A B A A B

900
900

450 100

h
B

250

H
H'
1000 Wall height<H> 1000 1000

H
A
A Front
B Must be open

<Side view> (Unit:mm)

2.Foundation work
1When building the foundation,give full attention to the floor strength,
drain water disposal <drain water flows out of the unit,during operation>,
piping and wiring routes. Corner
2Be sure that the corners are firmly seated.If the corners are not firmly
seated,the installation feet may be bent. M10 Anchor Bolt
3When down piping and down wiring are performed,be sure that foundation and <Local supply>
base work does not block the base through holes.
Unit : mm
Drw. : YGM-W656-824A 2/2

R410A Y - 51
R410A Data G2
494 1000

16
Refrig. service valve
<Liquid> Y Y

Refrig. service valve


<Gas>

840
877
Y Y
Knockout hole ø27 Knockout hole
<Bottom piping hole> <Bottom hole for control wiring>

553
845 (mounting pitch)

20

80
145
65 160
16

57
76
70
45 950 (mounting pitch) 950 (mounting pitch) 45
ø62 Knockout hole 1990
Conn. pipe 768
4. EXTERNAL DIMENSIONS

80 <Hole for power supply>


<To sub unit : Gas> Changeable to ø46, ø53 by using attached 3X2-14X20 Oval hole
ø28.58<Brazed> Cross section X-X conduit mounting plate <Accessory> (Mounting hole)
Top view
Air outlet
PUHY-P450,500,550,600,650YMM-A(-BS)

265

53

OUTDOOR UNIT
12 5 Air
inlet

Cross section Y-Y Air


1840

inlet Knockout hole


1575

Service panel
ø27 Knockout hole
<Accessories> 135 <Left side hole for control wiring>
• Refrigerant (Gas) conn. pipe ········1pc. 80 40 X
Knockout hole X
(Already installed on the unit) 67 160
• Packing for conn. pipe ················· 1pc. <Front piping hole>
(Attached near the ball valve)
• Conduit mounting plate

280
ø53, ø46 ······························ 1pc.Each

235
217
194
163

89
134 100
• Tapping screw M4 ···················· 2pcs.
Note1. Use the opening at the bottom of the unit
11 78

Refrig.service valve 100 Service valve

10
when running the power supply line from <Gas>
Conn. pipe <Liquid> <Oil balance>
37 115 115 37 68 205 ø15.88 <Flare> 205 68
the front or from the side of the unit. ø9.52 <Flare>
Knockout hole
Note2. Please refer to (2/2) for information 285 48
Left side view <Left piping hole> Front view
regarding necessary spacing around the
unit and foundation work. Refrig.service valve
Note3. This unit is used in combination with <Liquid>
a sub unit. (Refer to Drawing No.W656886
Outline Drawing of Outdoor Unit set)
Unit : mm
Drw. : YGM-W656-885 1/2

R410A Y - 52
R410A Data G2
1.Space required around unit

✻ In case of single installation ✻ In case of collective installation and continuous installation


[Basic rules for spacing the unit] 1Space required for collective installation and continuous installation:
1 Since the service from the back of unit is required, When installing several units, provide the space between each block considering passage for air and people.
2Open in two directions.
provide the back space 450 mm or above as the front. 3In case of wall height <H> exceeds total height of unit, add <h> dimension
Main unit Sub unit (h= wall height <H> - total height of unit) to ❈ marked dimension. B
4If there is a wall at both the front and the rear of the unit, install up to 1 set
(main unit and sub unit : 1 unit each) consecutively in the side direction and

} 450
provide a space of 1000 mm or more as inlet space/passage space for each 1 set.

} 450
Front Wall height<H> A A A A A
❈ Wall height<H>
<Top view>

} 450
[When inlet air enters from right
Wall height<H>
and left sides of unit]
4. EXTERNAL DIMENSIONS

1 Wall heights<H> of the front and the back sides B B


shall be within total height of unit.
2 When wall height<H'> exceeds total height of unit, A A
add <h>dimension to 450 of the following figure. } 450 } 450 }450 }450
h= wall height<H'> - total height of unit. ❈✻

} 450
}1000 Wall height<H>
Main unit Sub unit
} 450 B } 450
❈ ❈

} 450
Wall height<H> Wall height<H>
} 450

} 450
A

} 450
Spacing PUHY-P450,500,550,600,650YMM-A(-BS)

OUTDOOR UNIT
No restrictions on wall height
<left and right>
} 450 } 450 B A A B A A

} 900
} 900

h
B

H'
H
A
Wall height<H>
} 450

} 1000 } 1000 } 1000 A Front

<Side view> B Must be open

2.Foundation work (Unit : mm)

1 When building the foundation, give full attention to the floor strength,
drain water disposal <drain water flows out of the unit, during operation>, Corner
piping and wiring routes.
2 Be sure that the corners are firmly seated. If the corners are not firmly M10 Anchor Bolt
seated, the installation feet may be bent. <Local supply>
3 When down piping and down wiring are performed, be sure that foundation and
base work does not block the base through holes.
Unit : mm
Drw. : YGM-W656-885 2/2

R410A Y - 53
R410A Data G2
494 1000

16
Refrig. service valve Y Y
<Liquid>
Refrig. service valve
<Gas>

840
877
Y Y
Knockout hole 27 Knockout hole

553
<Bottom piping hole> <Bottom hole for control wiring>
845 (mounting pitch)

20

80
16

70

57
92
76
PUHY-P400,650YSM-A(-BS)

65 160 45 950 (mounting pitch) 950 (mounting pitch) 45


768 80
ø62 Knockout hole 1990
<Hole for power supply>
Changeable to ø46, ø53 by using attached 3X2-14X20 Oval hole
(Mounting hole)
4. EXTERNAL DIMENSIONS

conduit mounting plate <Accessory>


Cross section X-X Top view
Air outlet
265

53
Knockout hole

Service panel
12 5 Air

OUTDOOR UNIT
inlet Conn.pipe <Gas>
Cross section Y-Y ø41.28<Brazed>
Air
1840

inlet
1575

ø27 Knockout hole


<Accessories> X X
<Left side hole for
• Gas distributor ··················· 1pc. 135 control wiring> Conn.pipe
(Already installed on the unit) 80 40 <To main unit:Gas>
• Liquid distributor ················ 1pc. ø28.58<Brazed> 67 160
• Packing for conn. pipe ········ 1pc.

45
(Attached near the gas distributor)
• Conduit mounting plate

280
ø53, ø46 ······················ 1pc.Each 245
235
217
163

89
134 100
• Tapping screw M4 ············ 2pcs.
• Conn. pipe (Gas) ·············· 2pcs. 100 62 205 68
11 78

37 115 115 37 Knockout hole Service valve <Oil balance>

10
Note1. Use the opening at the bottom of the unit <Left piping hole> 68 205 ø9.52 <Flare>
when running the power supply line from
Knockout hole 285 48 Conn.pipe <Liquid>
the front or from the side of the unit.
<Front piping hole> ø15.88 <Flare>
Note2. Please refer to (2/2) for information
Left side view Front view
regarding necessary spacing around the
unit and foundation work.
Note3. This unit is used in combination with
a main unit. (Refer to Drawing No.W656886
Outline Drawing of Outdoor Unit set)
Unit : mm
Drw. : YGM-W656-884 1/2

R410A Y - 54
R410A Data G2
1.Space required around unit

✻ In case of single installation ✻ In case of collective installation and continuous installation


[Basic rules for spacing the unit] 1Space required for collective installation and continuous installation:
1 Since the service from the back of unit is required, When installing several units, provide the space between each block considering passage for air and people.
2Open in two directions.
provide the back space 450 mm or above as the front. 3In case of wall height <H> exceeds total height of unit, add <h> dimension
Main unit Sub unit (h= wall height <H> - total height of unit) to ❈ marked dimension. B
4If there is a wall at both the front and the rear of the unit, install up to 1 set
(main unit and sub unit : 1 unit each) consecutively in the side direction and

} 450
provide a space of 1000 mm or more as inlet space/passage space for each 1 set.

} 450
Front Wall height<H> A A A A A
❈ Wall height<H>
<Top view>

} 450
[When inlet air enters from right
Wall height<H>
and left sides of unit]
4. EXTERNAL DIMENSIONS

1 Wall heights<H> of the front and the back sides B B


shall be within total height of unit.
A A
Spacing PUHY-P400,650YSM-A(-BS)

2 When wall height<H'> exceeds total height of unit,


add <h>dimension to 450 of the following figure. }450 } 450 }450 } 450
h= wall height<H'> - total height of unit. ❈

} 450
} 1000 Wall height<H>
Main unit Sub unit
} 450 B } 450
❈ ❈

} 450
Wall height<H> Wall height<H>
} 450

} 450
A

} 450

OUTDOOR UNIT
No restrictions on wall height
<left and right>
} 450 } 450 B A A B A A

} 900
} 900

h
B

H'
H
A
Wall height<H>
} 450

} 1000 } 1000 } 1000 A Front

<Side view> B Must be open

2.Foundation work (Unit : mm)

1 When building the foundation, give full attention to the floor strength,
drain water disposal <drain water flows out of the unit, during operation>, Corner
piping and wiring routes.
2 Be sure that the corners are firmly seated. If the corners are not firmly M10 Anchor Bolt
seated, the installation feet may be bent. <Local supply>
3 When down piping and down wiring are performed, be sure that foundation and
base work does not block the base through holes.
Unit : mm
Drw. : YGM-W656-884 2/2

R410A Y - 55
R410A Data G2
877 1990 10 1990
840
Main unit Sub unit
Air outlet

Air
inlet
4. EXTERNAL DIMENSIONS

Air
inlet

Distributor (Gas)

OUTDOOR UNIT
g
d
e
Distributor (Liquid)
c

b a

Left side view Front view Indoor units


PUHY-P850,900,950,1000,1050,1100,1150,1200,1250YSGM-A(-BS)

Note1. Pipe size is as show in the table on the left.

PUHY-P850YSGM-A PUHY-P900YSGM-A PUHY-P950YSGM-A PUHY-P1000YSGM-A PUHY-P1050YSGM-A PUHY-P1100YSGM-A PUHY-P1150YSGM-A PUHY-P1200YSGM-A PUHY-P1250YSGM-A


Main unit PUHY-P450YMM-A PUHY-P500YMM-A PUHY-P550YMM-A PUHY-P600YMM-A PUHY-P650YMM-A PUHY-P450YMM-A PUHY-P500YMM-A PUHY-P550YMM-A PUHY-P600YMM-A
Sub unit PUHY-P400YSM-A PUHY-P650YSM-A
Indoor units~ Liquid a ø19.05
Distributor Gas b ø41.28
Distributor~ Liquid c ø15.88
Main unit Gas d ø28.58
Distributor~ Liquid e ø15.88
Sub unit Gas f ø28.58
Oil balance pipe g ø9.52
Unit : mm
Drw. : YGM-W656-886 1/1

R410A Y - 56
R410A Data G2
< Symbol explanation >
Symbol Name
ACCT1 AC Current Sensor
DCCT1 ✻3 DC Current Sensor
DCL1 DC reactor (Power factor improvement)
52C1 Magnetic contactor (Inverter main circuit)

Z20 TH8 TH7 TH6 TH5 TH11


MF1 Fan motor (Radiator panel)
63LS 63HS
LEV1
1 2 3 1 2 3 CH11 Crank case heater (Compressor)
Inverter controller box
21S4a ✻5 4-way valve
R22 R23
21S4b

white
white

red
red

black
black
21S4c ✻4
21 8 7 6 5 4 3 2 1 21 3 2 1 3 2 1 21 3 2 1 123456
CNTYP1 CN02 CN01 CNL CNH CNTYP4 CNTYP5 CNLVB
red black red SV1 Solenoid valve
CN52C Compressor ON/OFF
✻1
3 or STEP DEMAND (Discharge-suction bypass)
52 1 yellow CN3D 2 NIGHT MODE
C1 2 X52 1 )
3 detection SV5b
circuit CN3S 3 Solenoid valve
2 SNOW
red
1
X11 SV5c ✻4 (Heat exchanger capacity control)
CN3N 3 AUTO CHANGEOVER
blue 2 HEAT/COOL ✻2
1 Electronic expansion valve (SC coil)
1 detection
LEV1
2 CN38 circuit Trouble
63H1 5
3 green 4 Compressor ON/OFF
3 TH11 Discharge pipe temp. detect
CN51 2
1 Control circuit board 1
SV1 2 CN35 X09
(MAIN BOARD) 12V TH5 Pipe temp.detect (Hex outlet)
3 red

1 CN36 LD1
TH6 OA temp.detect
2
3 TH7 liquid outlet temp.detect
4 X08
SV 5 at Sub-cool coil
5b 6 X07 OFF ON OFF ON OFF ON OFF ON OFF ON
Thermistor

SV 7 1 1 1 1 1
5c 8 X06 CN04 TH8 bypass outlet temp.detect
21S 9
1 1 FAN control board 1 1 U at Sub-cool coil
4c 2 2 6
3 3 5 2 2 V
CNRS3A 4 4
(FAN BOARD) CNINV 4 MF
✻4 5 5 CNRS2 3 3 3 W THHS1 Radiator panel temp. detect
6 6 LED1 operation 2
7 7 1
10 10 10 10 10 LED2 error Fan motor
SW5 SW4 SW3 SW2 SW1
63H1 High pressure switch
✻5 T01 1 4 (Heat exchanger)
✻1 1 (Transformer) ON
X03 1 OFF
63HS High pressure sensor
21S 1 CN33 2 CNAC3 2 2 CNTR
4a 2 black 3 SW2
X02 1 3 123 CNVDC
21S 3 0 63LS Low pressure sensor
4b 4 SWU2 SWU1
5 SWU3
6 1 L1,L2 Choke coil (Transmission)
Unit address setting 2
3
5. ELECTRICAL WIRING DIAGRAMS

1 CN32 CNRS3B 4 Z20 Function device


2 5
X01 Refer to the service handbook 6
3 7
CH11
about the switch operations.
detection
Earth terminal
circuit
1 1 FILTER 1
2 2 2
3 3 BOARD 3
F02 F01 CNVCC1 4 4 4 < Difference of appliance >
250VAC 250VAC 5 5 5
6.3A T 6.3A T 6 6 6
CNS2 CNS1 7 7 CNOUT CNIN 7
blue blue 8 8 green blue 8 Model name Appliance
CN21 1 2 3 123 45 CN20 1 2 3 1 2 CNFG
blue blue CNL2 CNL1
CENTRAL PUHY-P200YGM-A “✻3” and “✻4” do not
12 12 12

OUTDOOR UNIT
exist.
CONTROL
PUHY,PUY-P200,250,300,350YGM / PUHY-P400YGM

TB7 L2 L1
shield S
TRANSMISSION PUHY-P250,P300,P350YGM-A “✻4” do not exist.
M2
LINE M1

TB3
PUHY-P400YGM-A All exists
M2
INDOOR/ M1 U “✻2”,“✻3”,“✻4” and
V MC1 PUY-P200YGM-A
OUTDOOR shield “✻5” do not exist.
W
TRANSMISSION
PUY-P250,P300,P350YGM-A “✻2”,“✻4” and “✻5”
LINE Motor do not exist.
ACCT1 ACCT-W
4 (Compressor)
3 CNCT2 12345678 1234567
ACCT-U 2 blue
1 CNVCC1 CNRS1 ✻1: Function according to switch operation.
red white black
TB1 ACNF1 DS1 ✻3 Power circuit board 1
(Terminal Block) (Noise Filter) (Diode stack) R11 R12 IPM1 CNFG 1
(SW4-7,CN3D 1-2P,and CN3D 1-3P)
U V W CNDC1 F02 (INV BOARD) blue
red red red P CNDC2 700VDC 2
Power source L1 L1 red black
L1 ~ + 2A T
C11 + R13 4 1 1 SW4-7:OFF
white DCL1 C14 3 2 2
L2 L2 white 3 3 CNDC2 LED1 operation
L2 ~ 2
3N~ 52C1 C12 + R14 N 1 4 4 black (Compressor ON/OFF and NIGHT MODE)
L3 L3 black black black black LED2 error
L3 ~ - 1 1
380/400/415V blue blue ZNR14 C15 DCCT1 1 6 1 4
N N ON ON
N 1234 CNDR1 CNDR2 CN3D Compressor CN3D NIGHT
E OFF OFF
50/60Hz 9 9 SW1 SW2 1-3P ON/OFF 1-2P MODE
1 1 CNFAN
PE Gate amp board 1 X01 red
3 OPEN ON OPEN OFF
Breakers for wiring (G/A BOARD) CN15V1 CN15V2 2
1
Breakers for current leakage F01 MF3 SHORT OFF SHORT ON
250VAC
14 14 2A T CNTH
PU(H)Y-P200,P250,P300YGM-A 30A CNCT
green
CNAC2 1 2 3 4 1 2
PU(H)Y-P350YGM-A 40A 12345 SW4-7:ON (STEP DEMAND)
THHS1 CN3D 1-2P
PUHY-P400YGM-A 60A
CN3D 1-3P OPEN SHORT

OPEN 100% 75%


SHORT 0% 50%

✻2:Auto changeover (CN3N 1-2P,1-3P)


CN3N 1-2P OPEN SHORT
CN3N 1-3P
OPEN Auto changeover:OFF - -

SHORT Auto changeover:ON COOL HEAT

NOTE:The broken lines indicate field wiring.


Drw. : YGM-W274-627

R410A Y - 57
R410A Data G2
< Symbol explanation >
Symbol Name
ACCT1 AC Current Sensor
Z20 TH8 TH7 TH6 TH5 TH12 TH11 DCCT1 DC Current Sensor
63LS 63HS
LEV1
1 2 3 1 2 3 DCL1 DC reactor (Power factor improvement)
Inverter controller box
52C1 Magnetic contactor (Inverter main circuit)
R22 R23
52C2 Magnetic contactor (No.2 Compressor)

white
white

red
red

black
black
51C2 Overload relay (No.2 Compressor)
2 1 8 7 6 5 4 3 2 1 4 3 2 1 2 1 3 2 1 3 2 1 2 1 3 2 1 123456 ✻1
3 Compressor ON/OFF
CNTYP1 CN02 CN13 CN01 CNL CNH CNTYP4 CNTYP5 CNLVB CN3D 2 or STEP DEMAND 52F Magnetic contactor (Fan motor)
red NIGHT MODE
red black 1 )
CN52C
52 1 yellow CN3S 3 MF3 Fan motor (Radiator panel)
C1 2 X52 2 SNOW
red 1
1 3 detection
circuit CH11,12
2 CN3N 3 AUTO CHANGEOVER Crank case heater (Compressor)
63H1 blue 21 HEAT/COOL ✻2
3
21S4a,b,c 4-way valve
1 RELAY-BOARD1 51C2
1 detection 1
2 circuit
SV1,3 Solenoid valve
63H2 2 CN38 CN51C2 2 95 96
3 3 green 3
(Discharge-suction bypass)
5 Trouble
4 Compressor ON/OFF X1 1 A2 A1
1 3 52
SV1 2 CN52C2 2 52C2 C2 SV5b,c Solenoid valve
2 CN35 X09 CN51 1 blue 3
3 red (Heat exchanger capacity control)
12V X2 4 13 14
5
1 CN36 LEV1 Electronic expansion valve (SC coil)
2 1 A2 A1
3 Control circuit board 52F
X3 CN52F 2
4 X08 yellow 3 TH11,12 Discharge pipe temp. detect
SV 5
(MAIN BOARD) CNOUT2
5b 6 X07 CH12
1 1 1
SV 7
LD1 2 2 TH5 Pipe temp.detect (Hex outlet)
5c 8 X06 CNCH 2
9 CNOUT1 3 3 blue 3
21S yellow 4
4c 4 543 2 1
5 CNRT2 TH6 OA temp.detect
X05 6
1 OFF ON OFF ON OFF ON OFF ON OFF ON CN05
SV3
2 CN34 1 1 1 1 1 52F TH7 liquid outlet temp.detect
3 red 5 1 1 U
4 CNRT1 4 2 2 V Fan motor
red 3 MF2 at Sub-cool coil
5
2 3 3 W (Heat exchanger)
6
Thermistor

1
4 TH8 bypass outlet temp.detect
X03
21S 1 CN33
4a 2 10 10 10 10 10 at Sub-cool coil
X02 1 1 FAN control board 1 1 U
21S 3 SW5 SW4 SW3 SW2 SW1 2 6
2 5 V Fan motor
4b 4 3 3 4
2 2 THHS1 Radiator panel temp. detect
5 ✻1 CNRS3A 4 4
(FAN BOARD) CNINV
3 3 3 W
MF1
(Heat exchanger)
6 5 5 CNRS2 2
2 6 6 LED1 operation
7 7 1 63H1,2 High pressure switch
1 LED2 error CN04
1 CN32 0 SWU2 SWU1 1 4
T01
2 X01 SWU3 (Transformer) 63HS High pressure sensor
1 ON
3 1
CNAC3 2 2 CNTR
OFF
CH11 Unit address setting black 3 3
SW2
123 CNVDC 63LS Low pressure sensor
PUHY-P450,500,550,600,650YGM-A(-BS)

Refer to the service handbook


about the switch operations. 1
L1,L2 Choke coil (Transmission)
2
5. ELECTRICAL WIRING DIAGRAMS

3
CNRS3B 4 Z20 Function device
detection 5
circuit 6
7

1 1 FILTER 1
Earth terminal
F02 F01 2 2 2
250VAC 250VAC 3 3 3
6.3A T 6.3A T
BOARD
CNVCC1 4 4 4
CNS2 CNS1 5 5 5
blue blue 6 6 6
CN21 1 2 3 1 2 3 7 7 CNOUT CNIN 7
123 45 CN20 1 2 blue ✻1: Function according to switch operation.
blue 8 8 green 8

CENTRAL CNFG
blue CNL2 CNL1 (SW4-7,CN3D 1-2P,and CN3D 1-3P)
CONTROL 1 2 1 2 1 2
TB7
shield S SW4-7:OFF (Compressor ON/OFF

OUTDOOR UNIT
TRANSMISSION M2 L2 L1
LINE M1 and NIGHT MODE)
TB3
M2
INDOOR/ M1 U CN3D Compressor CN3D NIGHT
VMC1
Motor
OUTDOOR shield W (Compressor) 1-3P ON/OFF 1-2P MODE
TRANSMISSION
OPEN ON OPEN OFF
LINE ACCT1 ACCT-W
4 SHORT OFF SHORT ON
3 CNCT2 12345678 1234567
2 blue
ACCT-U 1 CNVCC1 CNRS1
red white black
TB1 ACNF1 DS1 Power circuit board 1
(Terminal Block) (Noise Filter) (Diode stack) R11 R12 IPM1 CNFG 1
U V W CNDC1 F02 (INV BOARD) blue 2
SW4-7:ON (STEP DEMAND)
L1 L1 red red red red P CNDC2 black 700VDC
Power source L1 ~ + 2A T
C11 + R13 4 1 1
white DCL1 C14 3 2 2
L2 L2 white L2 2 CNDC2 LED1 operation
~ 3 3 CN3D 1-2P
3N~ C12
+ R14 1 4 4 black
black black 52C1 black N LED2 error
L3 L3 black L3 OPEN SHORT
~ - 1 1 CN3D 1-3P
380/400/415V blue blue ZNR14 C15 DCCT1 1 6 1 4
N N N 1234 CNDR1 CNDR2 ON ON
E OPEN 100% 75%

red
50/60Hz OFF OFF

white

black
9 9 SW1 SW2
1 1 CNFAN SHORT 0% 50%
PE Gate amp board 1 X01 red
3
F12 F11 (G/A BOARD) 2
Breakers for wiring AC660V AC660V CN15V1 CN15V2
1
Breakers for current leakage 50A F 50A F MF3
F01
250VAC ✻2:Auto changeover (CN3N 1-2P,1-3P)
14 14 2A T CNTH
PUHY-P450,500YGM-A 60A CNCT green
CNAC2 1 2 3 4 1 2
12 345
CN3N 1-2P OPEN SHORT
PUHY-P550,P600,P650YGM-A 75A 51C2 CN3N 1-3P
THHS1
OPEN Auto changeover:OFF - -

SHORT Auto changeover:ON COOL HEAT

52C2 NOTE:The broken lines indicate field wiring.

V
W U
MC2
Motor
(Compressor)
Drw. : YGM-W274-629

R410A Y - 58
R410A Data G2
Z20 TH12 TH10 TH8 TH7 TH6 TH5 TH11 < Symbol explanation >
63LS 63HS
LEV1 CH12
1 2 3 1 2 3
Inverter controller box Symbol Name
2 1

R22 R23 ACCT1, 2 AC Current Sensor

red
white
black
red
white
black
12 34 5 DCCT1, 2 DC Current Sensor
21 4 3 2 1 21 8 7 6 5 4 3 2 1 21 3 2 1 3 2 1 21 3 2 1 123456 123 45 CNRT1 yellow
CNTYP1 CN13 CN09 CN02 CN01 CNL CNH CNTYP4 CNTYP5 CNLVB CN01 X1 DCL1, 2 DC reactor (Power factor improvement)
red green black red
CN52C 3 ✻1 black black
CN3D 2 Compressor ON/OFF CNAC1 CNAC2 52C1, 2 Magnetic contactor (Inverter main circuit)
52 1 yellow or STEP DEMAND
C1 2 X52 1 NIGHT MODE 3
) 3
1 3 detection 2 2
circuit 3 1 MF1, 2 Fan motor (Radiator panel)
2 CN3S 2 1
red 1 SNOW
63H1 3 X11
3 AUTO CHANGEOVER X10 X10
CH11,12 Crank case heater (Compressor)
CN3N 2
✻2 RELAY - BOARD
1 blue 1 HEAT/COOL
yellow
1 detection CNIN 1 2 3 4 5 6 21S4a, b, c 4-way valve
2 circuit CNX10 3 2 1
2 CN38 5 Trouble
63H2 3 4 Compressor ON/OFF
3 green
3 SV1, 3
CN51 2
Solenoid valve
1 Control circuit board 1
SV1 2 CN35 (Discharge-suction bypass)
X09 12V
3 red (MAIN BOARD) 1
2 SV5b, c
LD1
3 Solenoid valve
1 CN36 CNOUT1 4
2 5 (Heat exchanger capacity control)
3 6
4 X08
SV 5 LEV1 Electronic expansion valve (SC coil)
5b 6 OFF ON OFF ON OFF ON OFF ON OFF ON
X07
SV 7 1 1 1 1 1
5c 8 X06 TH11,12 Discharge pipe temp. detect
21S 9
4c 1
2
X05 3
1 TH5 Pipe temp.detect (Hex outlet)
SV3 2 CN34 CNRS3A 4
5
3 red 6
4 10 10 10 10 10 7 TH6 OA temp.detect
5 SW5 SW4 SW3 SW2 SW1
6 CN04
X03
✻1 FAN control board 6
1 1 U TH7 liquid outlet temp.detect
21S 1 CN33 2 5 2 2 V
4a 2 X02 1
(FAN BOARD) CNINV 4
W MF at Sub-cool coil
3 3 3 3
21S 0 LED1 operation 2
SWU2 SWU1
Thermistor

4b 4 1
5 SWU3 LED2 error
TH8 bypass outlet temp.detect
6
1 4 1 Fan motor
T01 2 at Sub-cool coil
Unit address setting (Transformer) ON 3 (Heat exchanger)
1 1
1 CN32 CNAC3 2 CNRS2 4
2 2 CNTR OFF 5
X01 Refer to the service handbook black 3 SW2 6 TH10 Comp. shell temp. detect
3 3 1 2 3 CNVDC 7
CH11
about the switch operations.
PUHY-P700,750,800YGM-A(-BS)

detection THHS1, 2 Radiator panel temp. detect


circuit
1 1 FILTER 1
2 2 2
3 3 3 63H1, 2 High pressure switch
F02 F01 4 BOARD 4
250VAC 250VAC CNVCC1 4
5 5 5
6.3A T 6.3A T 6 6 CNOUT CNIN 6
CNS2 CNS1 7 7 7 63HS High pressure sensor
blue blue 8 8 green blue 8
CN21 12 3 123 45 CN20 1 2 3 1 2
CENTRAL blue CNFG 63LS
blue CNL2 CNL1 Low pressure sensor
1 2 1 2 1 2
CONTROLL L1, L2 Choke coil (Transmission)
TB7 L2 L1
TRANSMISSION shield
S
M2 Z20 Function device
LINE M1

TB3 Earth terminal


INDOOR/ M2 U
5. ELECTRICAL WIRING DIAGRAMS

M1 V
shield MC1
OUTDOOR W

TRANSMISSION ✻1: Function according to switch operation.


Motor
LINE ACCT1
ACCT-W
4
3 CNCT2
(Compressor) (SW4-7,CN3D 1-2P, and CN3D 1-3P)
1234567 1234567
2 blue
ACCT-U 1 CNVCC1 CNRS2
red white black Power circuit board 1 SW4-7:OFF (Compressor ON/OFF
TB1 ACNF1 DS1
(Terminal Block) (Noise Filter) (Diode stack) R11 R12 IPM1 CNFG 1
P U V W CNDC1 F02 (INV BOARD) blue 2
L1 L1 red red red red CNDC2 black 700VDC and NIGHT MODE)
Power source L1 ~ + 2A T
DCL1 + 4 1 1
white C11 R13 C14 2

OUTDOOR UNIT
L2 L2 white 3 2 CNDC2
3N~ L2 ~ 2 3 3 LED1 operation
52C1 C12 + R14 N 1 4 4 black CN3D Compressor CN3D NIGHT
L3 L3 black black black black LED2 error
L3 ~ - 1 1
380/400/415V ZNR14 C15 DCCT1 1 6 1 4
N N blue blue ON ON 1-3P ON/OFF 1-2P MODE
N 1 2 3 4 CNDR1 CNDR2
E OFF OFF
50/60Hz 9 9 SW1 SW2 OPEN ON OPEN OFF
Gate amp board 1 1 1 CNFAN
PE (G/A BOARD) X01 red
Breakers for wiring 3 SHORT OFF SHORT ON
CN15V1 CN15V2 2
Breakers for current leakage 1 MF1
F01
250VAC
14 14 2A T CNTH SW4-7:ON (STEP DEMAND)
PUHY-P700,750,800YGM-A 75A CNCT green CNRS1
1234 12 1234567
CNAC2 12345
CN3D 1-2P
THHS1 OPEN SHORT
CN3D 1-3P
OPEN 100% 75%
SHORT 0% 50%

✻2:Auto changeover (CN3N 1-2P,1-3P)


U
V MC2 CN3N 1-2P OPEN SHORT
W
CN3N 1-3P
Motor OPEN Auto changeover:OFF - -
ACCT2
4 (Compressor)
3 CNCT2 12345678 1234567
ACCT-W 2 blue
ACCT-U 1 CNVCC1 CNRS2 SHORT Auto changeover:ON COOL HEAT
red white black
ACNF2 DS2 Power circuit board 2
(Noise Filter) (Diode stack) R21 R22 IPM2 CNFG 1
P U V W CNDC1 F02 (INV BOARD) blue 2 NOTE:The broken lines indicate field wiring.
red red red CNDC2 black 700VDC
L1 ~ + 2A T
DCL2 + 4 1 1
white C21 R23 C24 3 2 2
L2 ~ 2 3 3 CNDC2 LED1 operation
C22 + R24 N 1 4 4 black
black black 52C2 black CN52C
L3 ~ - LED2 error
DCCT2 1 1 X02 yellow
blue ZNR24 C25 1 6 1 4 3 52
N 1 2 3 4 CNDR1 ON ON 2 C2
CNDR2
E OFF OFF 1
9 9 SW1 SW2
Gate amp board 2 1 1 CNFAN
X01 red
(G/A BOARD) 3
CN15V1 2
CN15V2 1
MF2
F01
250VAC
14 14 2A T CNTH
CNCT green CNRS1
1 2 3 4 1 2 1234567
CNAC2 1 2 3 45

THHS2
Drw. : YGM-W274-621

R410A Y - 59
R410A Data G2
<SYMBOL EXPLANATION>
Symbol Name
DCL DC reactor
(Power factor improvement)
T01 for Control circuit board
Transformer
T02 for FAN control board
TH5b Thermistor Pipe temp.detect
52F Magnetic contactor
(FAN inverter main circuit)
Inverter controller box Earth terminal

TB1 NF DS
(Terminal Block) (Noise Filter) R1 (Diode stack) CNVDC
L1 L1 red ~ + ZNR4 red (3P) FAN control board 1
PUHN-P01YGM-A(-BS)

Power source L1 L1 red 3 2


L2 L2 white white C5 DCL C1 + R2 CNINV 3
3N~ L2 L2 ~ 2 4 MF
52F C2 + R3 (6P)
L3 black black black 5
380/400/415V L3 L3 L3 ~ - 1 6 Fan motor
N N blue blue LED1 Operation
50/60Hz N N (Heat exchanger)
LED2 error
BREAKER(16A) CNTR 1 4 CNRS2
(3P) ON (7P)
OFF
1 2 3 SW2 1234567
PE

T02
T01
5. ELECTRICAL WIRING DIAGRAMS

52F

CNP
blue 1 2 3 1 2 3 1 2 3 1234567
CND CNT CN3T CN7V
red AC250V 6.3A X01 red CN21
F901 1

OUTDOOR UNIT
1 2
2
3 CN29
4 black
TH5b
5 1
2

Control circuit board CN30


green
1
2
TB3 3
(Terminal Block) CN2M
blue 0 12 0 1 0 1
M1 EF 9 9
Indoor/outdoor 1 1 5 1 4 1 6
7 8
2 3
7 8
2 3

B CD
345

M2 2 67
5 6
4
5 6
4
89A
Transmission Line
S SW4 SW7 SW2 SW14 SW12 SW11
(2nd digit (1st digit
Switch (for mode selection) address setting) address setting)

The broken lines indicate field wiring.


Drw. : YGM-W274-775

R410A Y - 60
R410A Data G2
< Symbol explanation >
Symbol Name
ACCT AC Current Sensor
DCCT DC Current Sensor
DCL DC reactor (Power factor improvement)
52C1 Magnetic contactor (Inverter main circuit)
52C2 Magnetic contactor (No.2 Compressor)
✻4
51C2 Overload relay (No.2 Compressor)
Z20 TH2 TH8 TH7TH6 TH5 TH12 TH11 63LS 63HS
LEV1 52F Magnetic contactor (Fan motor)
123 123
Inverter controller box
MF3 Fan motor (Radiator panel)
R22 R23 CH11,12 Crank case heater (Compressor)

red
white
black
red
white
black
21S4a,b,c 4-way valve
21 321 87654321 4321 21 321 321 21 321 123456
3 Compressor ON/OFF ✻1
CN52C CNTYP1 CN03 CN02 CN13 CN01 CNL CNH CNTYP4 CNTYP5 CNLVB CN3D 2 or STEP DEMAND SV1,3 Solenoid valve (Discharge-suction bypass)
1 NIGHT MODE )
yellow red red black red
52 1 CN3S 32 SV5b,c Solenoid valve (Heat exchanger capacity control)
C1 2 X52
red 1 SNOW
1 3 detection
circuit SV5d Solenoid valve
2 CN3N 32 AUTO CHANGEOVER
63H1 3 blue 1 HEAT/COOL ✻2
LEV1 Electronic expansion valve(SC coil)
1 RELAY-BOARD white 51C2 black
1 CN38 detection 1
2 circuit 2 TH11,12 Discharge pipe temp. detect
63H2 2 green CN51C2 3 95 96
3 3 CN51
5 Trouble X1 brown TH2 Gas pipe temp.detect (Hex outlet)
CN35 4 CN52C2 1 A2 52 A1
1 3 Compressor ON/OFF
SV1 2 2 red 52C2 C2 purple
3 red X09 Control circuit board 1
blue 23 TH5 Pipe temp.detect (Hex outlet)
4
(MAIN BOARD) 12V X2 5 orange 13 14
1 CN36 TH6 OA temp.detect
2 LD1 LD2 CN52F 1 gray A2 A1
3 X3 yellow 2
52F
4 X08 3 yellow TH7 liquid outlet temp.detect at Sub-cool coil
Thermistor

SV 5 CNOUT2
5b 6 X07 1 CH12
7 1 CNCH 1 TH8 bypass outlet temp.detect at Sub-cool coil
SV OFF ON OFF ON OFF ON OFF ON OFF ON 2 2
5c 8 X06 1 1 1 1 1 3
9 CNOUT1 3 blue 23
21S 4 4 54 32 1 THHS1 Radiator panel temp. detect
4c yellow 5 CNRT2
1 CN34 X05 6
SV3 2
CN05 63H1,2 High pressure switch
red X04 CNRT1 5 red 52F red 1 1 U
SV 3
4 4
✻4 5d 10 10 10 10 10 red 3 white white 2 2 V Fan motor
5 MF2 63HS High pressure sensor
6 SW5 SW4 SW3 SW2 SW1 2 black black 3 3 W (Heat exchanger)
1
4
X03 ✻3 ✻1 Maintenance 63LS Low pressure sensor
21S 1 CN33
4a 2 X02 setting 1 1 U
3 1 1 FAN control board 6
21S Function setting 2 2 5 2 2
L1,L2 Choke coil (Transmission)
4b 4 3 3 V Fan motor
5 4 4 CNRS2 (FAN BOARD) CNINV 4
CNRS3A 5 5 3 3 3 W MF1 (Heat exchanger)
6 6 6 2 Z20 Function device
2 LED1 operation 1
1 7 7 CN04
1 CN32 0 T01 LED2 error
SWU2 SWU1 Earth terminal
5. ELECTRICAL WIRING DIAGRAMS

2 SWU3 (Transformer) 1 4
3 X01 CNAC3 1 1 CNTR ON Function
2 2 OFF setting
Address setting black 3 SW2 <Difference of appliance>
CH11 3 12 3
CNVDC
Refer to the service handbook
about the switch operations. 1
Appliance (include"-BS") Difference(not existed)
2
3
CNRS3B 4 PUHY-P450/500/550/600/650YGM-A ✻4
detection 5
circuit 6
7
F02 1 1 1
PUHY-P450/500/550/600/650YMM-A –
250VAC F01 2 2 FILTER 2
3 3 BOARD 3
6.3A T 250VAC CNS2 CNS1 4 4 4 PUHY-P400/650YSM-A –
blue blue CNVCC1 5 5 5
6.3A T 6 6

OUTDOOR UNIT
7
CN21 7
CNOUT CNIN 67
12 3 123 45 123 12
CN20 8 8green blue 8
blue [1: Function according to switch operation.
CNFG CNL2 CNL1
blue

red
12 12 12 (SW4-7,CN3D 1-2P,and CN3D 1-3P)

blue
TB7

white
CENTRAL CONTROL M1
M2 L2 L1 SW4-7:OFF (Compressor ON/OFF and
TRANSMISSION LINE S
shield TB3
NIGHT MODE)
INDOOR/OUTDOOR M1 U CN3D Compressor CN3D NIGHT
M2
Motor
V MC1
TRANSMISSION LINE W (Compressor) 1-3P ON/OFF 1-2P MODE
shield
OPEN ON OPEN OFF
ACCT ACCT
4 SHORT OFF SHORT ON
-W 3 CNCT2 12345678 1234567
2
ACCT-U 1 blue CNVCC1 CNRS1
TB1 ACNF red white black F02 SW4-7:ON (8STEPS DEMAND)
DS IPM 700VDC Power circuit board
(Terminal Block) (Noise Filter) (Diode stack) R1 R2 CNFG 1
P CNDC1 2A T (INV BOARD) blue 2
L1 L1 red L1 red red red CNDC2 U V W black OS(KU) side CN3D
Power source ~ + 4 1 1 CNDC2 LED1 operation 8 STEPS
L2 L2 white DCL C1 + R3 C4 3 2 2
L2 white ~ 2 3 3 black LED2 error DEMAND 1-2P OPEN SHORT
3N~ N 1 4 4
L3 L3 black L3 black black 52C1 C2 + R4 black 1
~ - 1 1 ON
6 ON 1 4 1-3P
380/400/415V N N blue ZNR4 C5 DCCT 1-2P 1-3P OPEN SHORT OPEN SHORT
N blue 1 2 3 4 OFF OFF
CNDR1 CNDR2 SW1 SW2
E

white
OPEN 100% 50% 88% 75%

red
50/60Hz 9 9 CNFAN
1 1
PUHY-P450,500,550,600,650YMM-A(-BS), PUHY-P400,650YSM-A(-BS)

black
white
Function setting OC OPEN
Gate amp board X01 red 3
SHORT 50% 0% 38% 25%
PE F12 F11 (G/A BOARD) CN15V2 2 side
AC660V CN15V1 1
AC660V MF3 CN3D
50A F 50A F F01 OPEN 88% 38% 75% 63%
14 14 250VAC CNTH SHORT
2A T CNCT green SHORT 75% 25% 63% 50%
1 2 3 4 1 2
51C2 CNAC2 12345

THHS1 [2:Auto changeover (CN3N 1-2P,1-3P)


CN3N 1-2P
52C2 OPEN SHORT
CN3N 1-3P
L1 L2 L3
red
OPEN Auto changeover:OFF – –
Motor U
MC2 V
white SHORT Auto changeover:ON COOL HEAT
(Compressor) W black
[3:Set up of a function(SW5-7,5-8)
SW5-7 SW5-8
PUHY-P✻✻✻YGM-A OFF OFF
PUHY-P✻✻✻YMM-A ON OFF
PUHY-P✻✻✻YSM-A ON ON
NOTE:The broken lines indicate field wiring.
Drw. : YGM-W274-638A

R410A Y - 61
R410A Data G2
6. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS R410A Data G2

PUY-P200,250,300,350YGM-A(-BS) Drw. : YGM-rcd-200-350ygmc

BV1

BV2
CJ2
ST1

ST2
63LS

ACC

ST6
ST7

TH7

Drier
SV1

ST4

ST8
CP1

LEV1

CP2
63HS

ST3

COMP
O/S
21S4a

TH11
63H

CJ1

SCC
21S4b

TH8
HEX B

TH5
SV5b
TH6
HEX F

OUTDOOR UNIT R410A Y - 62


6. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS R410A Data G2

PUHY-P200,250,300,350YGM-A(-BS) Drw. : YGM-rcd-200-350ygmhp

BV1

BV2
CJ2
ST1

ST2
63LS

ACC

ST6
ST7

TH7

Drier
SV1

ST4

ST8
CP1

LEV1

CP2
63HS

ST3

COMP
O/S
21S4a

TH11
63H

CJ1

SCC
21S4b

TH8
HEX B

TH5
SV5b
TH6
HEX F

OUTDOOR UNIT R410A Y - 63


CJ2

ST1

21S4a BV1
21S4c
PUHY-P400YGM-A(-BS)

63HS 63LS
21S4b
63H
HEX F1
CJ1

CP1
HEX B O/S
SV1
ST6

TH11

TH6 ACC

OUTDOOR UNIT
HEX F2 COMP

ST11 ST10
SV5c

TH8
SV5b
TH5 ST2

ST8 BV2
TH7
SCC
6. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS

LEV1
CP3 ST9 Drier
Drw. : YGM-rcd-400ygmhp

R410A Y - 64
R410A Data G2
BV1

ST1

21S4b 21S4c 21S4a

HEX1b HEX2b CJ1


(F) (B)
63HS SV3

ST5
TH6
CV1 CV2
PUHY-P450,500,550,600,650YGM-A(-BS)

O/S CP1 O/S

ST6 SV1 CJ2

CP2 ST7 63LS

OUTDOOR UNIT
TH11 TH12

63H1 63H2

COMP COMP ACC


1 Oil 2
Tank CJ3
HEX1a SV5c HEX2a
ST13 ST12 ST11 ST10
(F) (B)

SV5b
TH5 BV2
6. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS

SCC TH7 ST2


LEV1 ST8

TH8 CP3 ST9 Drier


Drw. : YGM-rcd-450-650ygmhp

R410A Y - 65
R410A Data G2
Heat exchanger unit Compressor unit

CV3 BV1
BV4
ST17 ST1

21S4c 21S4b 21S4a

CJ1
63HS SV3
HEX2b HEX1b ST5
PUHY-P700,750,800YSGM-A(-BS)

HEX2a HEX1a
CV1 CV2

O/S CP1 O/S


TH6
ST6 SV1
CJ2
CP2 ST7 63LS

OUTDOOR UNIT
TH11 TH12
SV5b
63H1 63H2
TH5
Comp1 Comp2
Oil Acc
TH5b TH10 CJ3
Tank
ST13 ST12 ST11 ST10
CJ4
SV5c
BV5 CV4 BV2
ST18
SCC TH7 ST2
(HIC circuit) LEV1 ST8
TH8
CP3 ST9 Drier
6. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS

Drw. : YGM-rcd-700-800ysgmhp

R410A Y - 66
R410A Data G2
<PUHY-P-YSM-A(-BS)>
ST1 BV1

21S4b 21S4c 21S4a

Gas
distributor
HEX1b HEX2b CJ1
(F) (B) TH2
63HS SV3

ST5
TH6
CV1 CV2

O/S CP1 O/S

ST6 SV1
CJ2

CP2 ST7 63LS

TH11 TH12

63H1 63H2
<Indoor unit>
Comp1 Comp2
Oil Acc
CJ3
tank
HEX1a SV5c HEX2a
ST13 ST12 ST11 ST10
(F) (B)
Stop-valve
SV5b
TH5

SCC TH7 ST2 BV2 SV5d


(HIC cycle) LEV1 ST8

TH8 CP3 ST9 Drier

<PUHY-P-YMM-A(-BS)>
ST1 BV1

OUTDOOR UNIT
21S4b 21S4c 21S4a

HEX1b HEX2b CJ1


(F) (B) TH2
63HS SV3

ST5 Oil balance pipe


TH6
CV1 CV2

O/S CP1 O/S


PUHY-P850,900,950,1000,1050,1100,1150,1200,1250YSGM-A(-BS)

ST6 SV1
CJ2

CP2 ST7 63LS

TH11 TH12
6. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS

63H1 63H2

Comp1 Comp2
Oil Acc
CJ3
tank
HEX1a SV5c HEX2a ST13 ST12 ST11 ST10
(F) (B)
Stop-valve Liquid
SV5b distributor
TH5

SCC TH7 ST2 BV2 SV5d


(HIC cycle) LEV1 ST8

TH8 CP3 ST9 Drier


Drw. : YGM-rcd-850-1250ysgmhp

R410A Y - 67
R410A Data G2
R410A Data G2

OUTDOOR UNIT R410A Y - 68