Professional Documents
Culture Documents
90.18737 WF GDC O&m Manual
90.18737 WF GDC O&m Manual
WEIGH FEEDER
FOR
WEIGH FEEDER
TABLE OF CONTENTS
SR. NO. DESCRIPTION NO OF PAGES
04 MOTOR SPECIFICATION 01
09 LOADCELL SPECIFICATION 03
10 DATA SHEET 02
11 ELECTRICAL DRAWING 81
12 MECHANICAL GAD 02
WEIGH FEEDER
FOR
WEIGH FEEDER
User Manual
2 General ............................................................................................. 4
2 .1 Conventions ....................................................................................... 4
1 SAFETY INSTRUCTIONS
For Safety instructions, please refer Section 1.2 of Appliance Description document.
2 GENERAL
This manual is dedicated to "Users". User is defined as a person using the feeder for
production including:
• Monitoring values
• Correcting errors
• Trouble shooting
2 .1 CONVENTIONS
>ButName< means a button with name ButName
"ScrName" means a screen with name ScrName
[PrmName] means a parameter with Name PrmName
xx.yy means parameter number
xx.yy [PrmName] means indication of parameter name with its corresponding
parameter number
3 HMI PANEL
The HMI panel is serially connected to GDC. The HMI panel offers a touch-sensitive colored
display. HMI content is structured like:
Access to
"Online "Command" "Menu"
Menu" "User
"Maintenance" "Commissioning"
Menu"
User X X X
level
Service X X X X
Admin X X X X X
3 .1 ONLINE MENU
The "Online Menu" is the basic display at the HMI and serves as a data display and as a
branch to the "Command Screen" and "Menus"
Tapping on Belt Load and Motor Speed parameter changes their unit. Belt Load is available
in % and Kg/m and Belt Speed is available in rpm and cm/s
3 .2 ERROR SCREEN
In case of error or warning, this is displayed in the >error< of the "Online Menu".
Pressing >Error< the "Error Screen" is displayed.
In the "Error Screen" errors are displayed in red and warnings in yellow
In the base line of the "Error Screen" two buttons are offered:
• >Back< to "Online Menu"
• >Reset< to acknowledge errors and warnings. If error/warning still exists, it is redisplayed after
acknowledging.
3 .3 COMMAND SCREEN
Access to "Command Screen" is available via >Command< in the "Online Menu".
In "Command Screen", on top of the header the present operating mode (refer to Table 1 & 2)
and present system status .
Depending on the source of Run/Halt Command, there are three operating modes.
Table 1
Depending on the feeder operation, Local and Remote modes are further divided into four
operating modes
Table 2
• Modes can be changed through commands and these commands can come from HMI or
Digital Input or Fieldbus.
• If command source is “Internal”, then HMI commands can be used to change the modes and
if command source is “External”, then Digital Input or Fieldbus Command can be used to
change the modes.
• For more details see Section 2.7 of Parameter Manual or System Control Settings in
Commissioning Manual.
• If 38.07 Field Switch Operation is “Yes” then Digital Input “Field Selector Switch” controls the
Field Mode Selection.
If 38.07 Field Switch Operation is “No” then Digital Input “Field Selector Switch” doesn’t affect
the Field Mode Selection and Field Active/Field Release Command on HMI can be used for Field
Mode Selection.
• If 38.05 Field Permission control is “External” then Digital Input “Field Permission” controls the
Field Permission.
If 38.05 Field Permission control is “Internal” then Digital Input “Field Permission” doesn’t
affect the Field Permission. Field Permission Command on HMI can be used to Enable/Disable
Field Permission.
Important points:
• Change in Operating mode in WF Running condition, stops the feeder.
• Field mode cannot be activated in WF Running condition.
• Gravimetric-Volumetric mode cannot be changed in WF Running condition.
3 .5 MENUS
Parameters can be accessed through menus. There are 3 different types of menus and it can
be accessed using different levels.
Access to
"User Menu" "Maintenance" "Commissioning"
User level X
Service X X
Admin X X X
Login Success and Login Failure events are logged in Event Log.
Procedure
Select User type and enter the Password.
Press >Login< button. On Login Success, >Menu< button gets enabled and Menu access will be
given as per User Type.
Software versions, GDC name and GDC IP Address are displayed on Login screen as seen in the
Picture.
3 .5.2 Maintenance
In "Maintenance" all data and actions are available which are performed for service purposes
like diagnostics, adjustments and calibration
The totalizer 2 is a long time running totalizer representing the mass fed over the feeding
system. This totalizer can be cleared in this menu by >Reset<. To leave this menu >Cancel<
or any other key in the base line can be used
3 .5.3 Commissioning
In "Commissioning" all parameters and actions are available which need to be adjusted
before commissioning the feeder
If not all parameters of a group can be displayed on one screen, this is indicated on base line
by the present page number and with >Next< next page can be accessed.
In the base line of parameters, menu can be left by >Back<and returned to "Commissioning"
4 INDEX HISTORY
Index Author Edition Modifications
1.0 ppol-in First issue
1.1 ppol-in Second issue Maintenance menu changed
1.2 ppol-in Third issue Minor changes
1.3 ppol-in Fourth issue Batch Mode, Aeration, Master-slave
Parameter Manual
1 Parameters ............................................................................................................................. 3
1 .1 Parameter groups ................................................................................................................... 3
1 PARAMETERS
1 .1 PARAMETER GROUPS
All parameters are arranged in groups relating to main themes like configuration, System Control, …
1.9 USB Operations Action to USB: save, restore, copy, .. firmware and
configuration
name
The max. feed rate limits the defining of setpoints.
41.11
(Alternative designation: max. flowrate)
Maximum
feedrate [t/h]
41.21 The distance between the measuring point and weigh feeder
outlet (material drop point) is given as charging distance with
Discharge
band scales. This parameter is required for feeding at the
distance [m]
drop point.
41.23 Length of the area where material mass is measured Only
applicable for belt weigh feeders. See section LM below
Measuring
under characteristics. (Alternative designation: effective
section [m]
weigh length)
41.12 This load value serves as a reference for the relative display
of load‐relevant data such as load WIa1[%], (), etc
Nominal load
[Kg/m]
41.35 Time that the conveyor needs for one rotation at max. speed
(31.33) of the feeder drive.
Nom. rotation
time [Sec]
Max. Speed
[rpm]
31.52 This value limits the amount of correction values of the zero
point that can be transferred via the interface.
Max. zero
correction [%]
c) 2 synchron sensors
40.53 SIO Baud Setting the baud rate at serial interface 9600-
Rate 115200 bps
[d]
The calibration factor MF1 represents the increase of the
46.25 MF1
weigh characteristic after calibration.
Calibration
factor
46.35 MF2 The calibration factor MF2 represents the increase of the
Calibration weigh characteristic after calibration.
factor
32.03 Range 1 to
PID Parameters
Derivative Gain 10
Tv [Sec]
32.04 Range 1 to
PID Parameters
10
Derivative
Damping Time
Td [Sec]
32.05
Set point value for Prefeed System
Load Setpoint
[%]
32.06 Applicable
Prefeeder set point is relative value of main Drive Set
When 32.18
Proportionate point.
Proportion of this much percentage of main drive set point set to “WF
Value [%]
is sent to Prefeeder Drive as set point. Drive SP”
32.20 Minimum When Load value is less than Min Initial Load then
Initial Load Prefeeder runs at Initial Load Setpoint for time defined by
[%] Initial Load Delay. After this time period, the setpoint
value is generated by PI
32.24 Max If prefeed load is greater than Max Prefeed load then It doesn’t
Prefeed Load Prefeeder motor stops affect the
[%] Prefeeder
On Output
36.02 Inverter This enables to select type of inverter interfaced with the
Type 1 controller. Example ACS550
Also select the Inverter Address
36.03 Inverter This enables to select type of inverter interfaced with the
Type 2 controller. Example ACS550
Also select the Inverter Address
36.04 Number Select type and select number of AIO cards interfaced with Select Old
of AIO the controller. Example 0,1,2 875 or New
type of card
Please read note Below
36.05 Number Select type and select number of DIO cards interfaced with Select Old
of DIO the controller. Example 0,1,2,3 889 or New
type of card
Please read note Below
Frequency drives ACS550, VACON20, ACS850, PF40, SK520 are currently supported.
OLD DIO will not work when Master Slave Configuration is enabled
Inverter port baud rate should be set to 19200.
FLSmidth Private Limited page 14/36
PARAMETER MANUAL Ver 1.3
40.40 System This option enables to configure the system to work with
Type iDD or as a standalone unit.
Standalone GDC : This option enables user to operate
GDC controller as a standalone unit. Here the loadcell
signal is directly given to the GDC controller.
Copy Resources This menu enables user to copy resources from USB to
from USB Internal memory.
Restore This menu enables user to restore backup files from the
Configuration USB.
from USB
Enter Correct Hour, Minute & Second and Press Set Time
Set time
to change the Controller Time.
Valid Range of Values (24 Hour Format)
a. Hour : 0 – 23
b. Minute : 0 – 59
c. Second : 0 – 59
37.32 Change the type between Warning and Error for SF Belt
Slip fault
SF ZSS Type
E.g.
37.14 Output can be scaled to 0.10 to 2.00
AIO1 Output 1 If set to 1 then
Output is
scaled to 0‐
100 % and If
37.14 Output can be scaled to 0.10 to 2.00
set to 2 then
AIO1 Output 2 Output is
scaled to 0‐
200 %.
37.15 Output can be scaled to 0.10 to 2.00 Note:
AIO2 Output 1
Analog output
scale can’t be
set to 0. If set
37.16 Output can be scaled to 0.10 to 2.00 it to 0 then it
is changed to
AIO2 Output 2
1.
PI Settings
32.11 Integral
Gain Tn [s]
PI Settings
32.12
Derivative Gain
[s]
PI Settings
32.13
Derivative
Dumping Time
Td [s]
Time [s]
0 0 DRW rotor
feeder
1 0 XRW rotor
feeder
0 1 DBW/FBW
belt feeder
B2..B7 Not used
B8..B9 B8 B9 synchronization
0 0 time based
1 0 Synchron
sensor
0 1 2 synchron
Sensors
1 1 Disable
B10..B11 Not used
B12..B13 B12 B13 speed source
0 0 fix frequency
Limited 1 0 tachometer
0 1 Incremental
sensor
(right)
1 1 incremental
sensor
(left)/Inverter
B14..B31 Not used
example:
3101h=
XRW + synchron sensor +
incremental sensor (left)
40.51 SIO Interface 0 to 5
Value Selection
0 Off
1 Modbus
2 Profibus
3 DeviceNet
4 Ethernet IP
5 Modbus TCP/IP
40.52 SIO Address 1 to 127
40.53 SIO Baud Rate 9600 to 115200
40.19 Prefeed 0 to 2
0 = Off 1 = On – Auto Control 2 = On – IO Control
40.21 prehopper 0 to 1
0 = no 1 = yes
40.25 Feeder Variant 0 to 3
0 = None 1 = Screw Feeder 2 = Weigh Belt Feeder
3 = Reserve
3 -75
4 -100
5 -150
6 -175
46.24 Loadcell1 dead load point [Digit]
46.25 Loadcell1 calibration factor
46.26 Loadcell1 correction calibration [%]
46.32 Loadcell2 input range [mV] 0 to 7
Value Selection
0 41.48
1 20.74
2 10.37
3 5.19
4 +/- 5.19
5 +/- 10.37
6 +/- 20.74
7 +/- 41.48
46.33 Loadcell2 compensation of dead load [%] 0 to 6
Value Selection
0 0
1 -25
2 -50
3 -75
4 -100
5 -150
6 -175
46.34 Loadcell2 dead load point [Digit]
46.35 Loadcell2 calibration factor
46.21 Limit1 [%] 0.0 to 100.0
46.22 Limit2 [%] 0.0 to 100.0
46.23 Limit3 [%] 0.0 to 100.0
46.24 Nominal Capacity [t] 0 to 9999
46.25 Underload Limit [%] 0 to 200
46.26 Overload Limit [%] 0 to 200
32.01 Proportional Gain Kp 0.0 to 25.99
32.02 Integral Gain Tn [s] 0.0 to 99.99
32.03 Derivative Gain Tv [s] 0.0 to 99.99
32.04 Derivative Damping Time Td [s] 0.0 to 99.99
32.05 Set point Value [%] 0.0 to 199.99
32.17 Proportionate Value [%] 0.0 to 200.00
32.18 Prefeed Type 0 to 2
32.19 Permissible Deviation 0 to 99.99
32.20 Minimum Initial Load [%] 0 to 999.99
32.21 Initial Load Delay [s] 0 to 999
32.22 Initial Load Setpoint [%] 0 to 999.99
32.23 Max PF Motor Speed [rpm] 0 to 9999.99
32.24 Max Prefeed Load [%] 0 to 999.99
36.01 Number of Inverters 0 to 2
36.02 Inverter 1 Type 0 to 5
Value Selection
0 SK520
1 VACON20
2 ACS550
3 NA
4 PF40
5 ACS550
36.03 Inverter 2 Type 0 to 5
Value Selection
0 SK520
1 VACON20
2 ACS550
3 NA
4 PF40
5 ACS550
36.04 Number of AIO (Max 2) 0 to 2
36.05 Number of DIO (Max 3) 0 to 3
36.06 Number of Field AIO 0 to 3
36.07 Number of Field DIO 0 to 3
36.08 Fieldbus Swap 0 to 3
0 = Disable 1 = Word Swap
2 = Byte Swap 3 = Word_Byte Swap
36.09 Fieldbus Monitoring 0 to 1
0 = Disabled 1 = Enabled
38.01 Remote Local Selection 0 to 1
0 = Internal 1 = External
38.02 Control Source in Remote 0 to 1
0 = Hardwire 1 = Hostlink
38.03 Gravimetric Volumetric Selection 0 to 2
0 = Internal 1 = External 2 = Auto
38.04 Start Stop Type in Remote 0 to 1
0 = Level 1 = Rising Edge
38.05 Fieldbus Permission 0 to 1
0 = Internal 1 = External
38.06 Separate Start Stop in Remote 0 to 1
0 = No 1 = Yes
38.07 Field Switch Selection 0 to 1
0 = No 1 = Yes
38.08 Control Source in Field 0 to 2
0 = Hardwire 1 = PHT 2 = Drive
System Type 11 or 12
11 – Standalone GDC 12 – GDC with iDD
MAC Address
Date and Time(24 Hr Format)
37.01 AIO1 Input 1 Definition 0 to 3
Value Input
0 Off
1 PLC Setpoint
2 Proportionate Capacity
3 Field Set point
37.02 AIO1 Input 2 Definition 0 to 3
37.03 AIO2 Input 1 Definition 0 to 3
FLSmidth Private Limited page 30/36
PARAMETER MANUAL Ver 1.3
5 1 Sec
37.28 Pulse Resolution 100Kg/250Kg/500Kg 0 to 2
37.29 Deviation Limit [%] 0 to 100.00
37.30 Underload Limit [%] 0 to 100.00
37.31 Overload Limit [%] 0 to 100.00
37.32 SF ZSS Type 0 to 1
32.06 Proportional Gain Kp 0.0 to 25.99
32.07 Integral Gain Tn [s] 0.0 to 99.99
32.08 PI Selection 0 to 1
0 = Disable 1 = Enable
32.10 Proportional Gain Kp 0.0 to 25.99
32.11 Integral Gain Tn [s] 0.0 to 99.99
32.12 Derivative Gain Tv [s] 0.0 to 99.99
32.13 Derivative Damping Time Td [s] 0.0 to 99.99
32.14 Feedrate calculation Filter 0 to 20
32.15 Belt Load Display Filter 0 to 20
35.01 Number of Aeration 0 to 6
35.02 Aeration Scheme 0 to 2
0 = Off 1 = Concurrent 2 = Sequential
35.03 Aeration Timer Settings 0 to 1
0 = Same 1 = Different
35.04 Common On Time 0 to 999
35.05 Common Off Time 0 to 999
35.09 Aeration 0 On Time 0 to 999
35.10 Aeration 1 On Time 0 to 999
35.11 Aeration 2 On Time 0 to 999
35.12 Aeration 3 On Time 0 to 999
35.13 Aeration 4 On Time 0 to 999
35.14 Aeration 5 On Time 0 to 999
35.09 Aeration 0 Off Time 0 to 999
35.10 Aeration 1 Off Time 0 to 999
35.11 Aeration 2 Off Time 0 to 999
35.12 Aeration 3 Off Time 0 to 999
35.13 Aeration 4 Off Time 0 to 999
35.14 Aeration 5 Off Time 0 to 999
32.16 Feedrate Display Filter 0 to 20
36.10 Proportionate Feedrate [%] 0.0 to 100.0
36.11 Gravimetric Set point [tph] 0.0 to 9999.99
36.12 Volumetric Set point [tph] 0.0 to 9999.99
Free Bytes in Internal Storage Memory [Bytes]
37.50 AIO1 Output1 Scaling 0.1 to 2.0
37.51 AIO1 Output2 Scaling 0.1 to 2.0
37.52 AIO2 Output1 Scaling 0.1 to 2.0
37.53 AIO2 Output2 Scaling 0.1 to 2.0
39.02 Correction Time [s] 0 to 999
39.03 CM Timeout 0 to 20
IO Mapping for Inputs and Outputs 0 to 49
Mapping for E00 – E49 and A00 – A49
Input and Output lists are given below
GDC CPU Software version BWFX.X
Parameter List Version vX.X
Inputs Codes
0 Belt Slip
1 Belt Track
2 Material Detection
3 Synchronous Sensor
4 Remote Start [Stop]
5 Fault Reset
6 Drive Interlock
7 Field Selector Switch
8 Emergency LCB
9 Start Feeder LCB
10 Stop Feeder LCB
11 Start Release
12 Field Permission
13 Volumetric [Gravimetric]
14 Control Supply On
15 Isolation Switch On
16 Field Supply On
17 [Emergency]
18 Vibration Interlock
19 Remote [Local]
20 Prefeed Start
21 Prefeed Stop
22 Aeration
26 Spil Conveyor Off
27 Maintenance Switch
28 Motor Thermal Switch
29 Vibrator Switch
30 Prefeed Slip
31 Prefeed Belt Track
32 Set point Increase
33 Set point Decrease
34 Start Prefeeder LCB
35 Stop Prefeeder LCB
36 Prefeeder Set point Increase
37 Prefeeder Setpoint Decrease
38 Remote Stop
39 Vibrator Stop
40 Pull Chord Switch
41 PF Motor Interlock
42 CM Abort
43 CM Start
44 CM Accept
45 BIN PF On
46 BIN PF Loc/Rem
47 Shutoff Gate
48 SF Belt Slip
Output Codes
0 Feeder On
1 General Fault
2 Remote [Local]
3 Pulse
4 Panel Healthy
5 Feeder On Lamp
6 Feeder On Lamp LCB
7 Field mode [Local]
8 Volumetric [ Gravimetric]
9 Drive Fault
10 Vibrator On Signal
11 Vibrator On Status
12 Belt Track Fault
13 Prefeeder On
14 Prefeeder Fault
15 Deviation Fault
16 Loadcell Fault
17 Tacho fault
18 Belt Slip Fault
19 Emergency Off
21 CM Aborted
22 Bin Gate Open/Close
23 Vibrator On Lamp LCB
24 Prefeeder On Lamp LCB
25 Feeder Trip
26 Vibrator Motor Fault
27 Material Low
28 Zeroing On
29 Pull Chord Healthy
30 Maintenance Off
31 PF Motor Fault
32 Bin High
33 Bin Low
34 CM On
35 Sk Exceeded
36 BIN PF Start/Stop
37 LC1 Underload
38 SF Belt Slip Fault
39 LC1 Overload
41 Aeration 1
42 Aeration 2
43 Aeration 3
44 Aeration 4
45 Aeration 5
46 Aeration 6
47 Aeration Header
48 High
49 Low
2 INDEX HISTORY
Index Author Edition Modifications
Commissioning Guide
Software : WF
1 General
This document describes the installation and commissioning of GDC for Weigh Feeder.
Operations
Connection Details
System Calibration
Conventions
3 Connectors on GDC
No Connector Connector Name and Connector Connector Type Connector
Location Function Details Colour
1 Power Supply Card X1 – 24 V DC Power X1.1 ( 24P) 3 Way screw Black
Supply Terminal
X1.2 (24N)
X1.3 (E)
X2.3 (SH)
X6.3 (SH)
11 AIO Card X11 – Analog Input 2 X11.1 (10V) 3 Way Screw Green
Terminal
X11.2 (I/P+)
X11.3 (I/P-)
12 AIO Card X12 – Analog Input 1 X12.1 (10V) 3 Way Screw Green
Terminal
X12.2 (I/P+)
X12.3 (I/P-)
16 Loadcell Card X16 – Tacho 1/Encoder X16.1 (+12 V) 6 Way Screw Green
Terminal
X16.2 (A+)
X16.3 (A-)
X16.4 (B+)
X16.5 (B-)
X16.6 (GND)
X18.3 (GND)
X19.3 (GND)
X20.3 (SH)
Note:
Electrical Connection information in above table may change subject to change in hardware.
Always refer engineering wiring diagram or Appliance Description for wiring assistance.
5 Parameter Settings
Parameters need to be set as per specific job. For more information on Parameters,
check Parameter manual. Parameters editing in Commissioning menu is possible with
Admin Login only.
Follow these steps to bring up your new GDC controller to perform as per job
1. Go to 1.8 [System Type] menu and select the appropriate option as per Job
requirement
2. Go to 1.2 [Configuration menu].
Select 40.11 [Feeding System Type] in Configuration menu. For e.g. Belt Feeder or
Belt Weigher
Select 40.14 [Speed source] for e.g. Tachometer, Encoder
Select 40.51 [Fieldbus Type] as per job requirement and set other parameters
appropriately
3. Calculate and Set parameters in 1.1 [Weigh Feeder] menu. Parameter Calculations
are explained in Weigh Feeder Calculation section.
4. Go to 1.3 [Measuring Function] and Select Loadcell parameters as per requirement.
5. If prefeed is included then Go to 1.5 [Prefeed] and set Prefeed parameters For e.g.
PI Settings, Proportionate Setpoint Value.
6. Go to 1.6 [Interface] and select No of Inverters, Type of Inverters, No of Analog and
Digital cards
7. Go to 1.7 [System Control] and set the parameters as per requirement. These
parameters are explained in System Control Settings section.
8. Go to 1.10 [Date & Time] and check and set correct system date and time.
9. Go to 1.11 [IO Configurations] and select Analog IOs as per job requirement.
IO Logic can be inverted in [IO Inversion] menu.
IO monitoring timers and other IOs (ZSS, Pulse) can be set in this menu.
10. Go to 2.8 [Feeder PI Settings] in Maintenance menu and set PI Parameters and
Feedrate Filters.
11. Go to 3.2 [LAN Settings] and set the device name. Device name should be 8
characters long. This name will be appeared in all the log files that copied from GDC.
12. Calibrate the Analog IOs, Loadcell, and perform Dynamic Zeroing
13. Check Digital IOs status in Diagnostics as per job requirement. Now system should
be in healthy condition and so it’s ready to Run.
• 38.04 [Start-Stop Type in Remote] is used to set Type of Start-Stop input in Remote
Mode.
Level Type means Start input is high then feeder will start and
Rising Edge Type means when Start input goes low to high then only feeder will start.
• If 38.05 [Field Permission] is “External” then Digital Input “Field Permission” control the
Field Permission.
If 38.05 [Field Permission] is “Internal” then Digital Input “Field Permission” doesn’t
affect the Field Permission. >Field Permission< Command can be used to Enable/Disable
Field Permission.
• 38.06 [Separate Start-Stop in Remote] is used to set separate inputs for Start-Stop in
Remote mode.
• If 38.07 [Field Switch Operation] is “Yes” then Digital Input “Field Selector Switch”
controls the Field Mode Selection.
If 38.07 [Field Switch Operation] is “No” then Digital Input “Field Selector Switch” doesn’t
affect the Field Mode Selection and >Field Active/Release< Command on HMI can be
used for Field Mode Selection.
• 38.08 [Control Source in Field] is used to set control of Field Operations in Field mode.
“Hardwire” means via Digital Inputs,
“PHT” means via Handheld Terminal and
“Drive” means via Inverter
Nominal Rotation Time @ 1000 RPM (Nominal RPM) = 30.5 Sec (Parameter 41.35)
(*note = the above numerical values are used for example purpose)
8 Digital IO List
8.1 Inputs
Code Meaning 1 [0] Source Destination
0 Belt Slip Feeder GDC
1 Belt Track Feeder GDC
2 Material Detection Feeder GDC
3 Synchronous Sensor Feeder GDC
4 Remote Start [Stop] PCS GDC
5 Fault Reset PCS GDC
6 Drive Interlock Panel GDC
7 Field Selector Switch LCB GDC
8 Emergency LCB LCB GDC
9 Start Feeder LCB LCB GDC
10 Stop Feeder LCB LCB GDC
11 Start Release PCS GDC
12 Field Permission PCS GDC
13 Volumetric PCS GDC
[Gravimetric]
14 Control Supply On Panel GDC
15 Isolation Switch On Panel GDC
16 Field Supply On Panel GDC
17 [Emergency] Panel GDC
18 Vibration Interlock Panel GDC
19 Remote [Local] PCS GDC
20 Prefeed Start PCS GDC
21 Prefeed Stop PCS GDC
22 Aeration LCB GDC
26 Spil Conveyor Off PCS GDC
27 Maintenance Switch Feeder GDC
28 Motor Thermal Switch Feeder GDC
29 Vibrator Switch LCB GDC
30 Prefeed Slip Feeder GDC
31 Prefeed Belt Track Feeder GDC
32 Set point Increase LCB GDC
33 Set point Decrease LCB GDC
34 Start Prefeeder LCB LCB GDC
35 Stop Prefeeder LCB LCB GDC
36 Prefeeder Set point LCB GDC
Increase
37 Prefeeder Setpoint LCB GDC
Decrease
38 Remote Stop PCS GDC
39 Vibrator Stop LCB GDC
40 Pull Chord Switch Feeder GDC
8.2 Outputs
Code Meaning 1 [0] Source Destination
0 Feeder On GDC PCS
1 General Fault GDC PCS
2 Remote [Local] GDC PCS
3 Pulse GDC PCS
4 Panel Healthy GDC PCS
5 Feeder On Lamp GDC Panel
6 Feeder On Lamp LCB GDC LCB
7 Field mode [Local] GDC PCS
8 Volumetric [ GDC PCS
Gravimetric]
9 Drive Fault GDC PCS
10 Vibrator On Signal GDC Panel
11 Vibrator On Status GDC PCS
12 Belt Track Fault GDC PCS
13 Prefeeder On GDC PCS
14 Prefeeder Fault GDC PCS
15 Deviation Fault GDC PCS
16 Loadcell Fault GDC PCS
17 Tacho fault GDC PCS
18 Belt Slip Fault GDC PCS
19 Emergency Off GDC PCS
21 CM Aborted GDC PCS
22 Bin Gate Open/Close GDC PCS
23 Vibrator On Lamp LCB GDC LCB
24 Prefeeder On Lamp GDC LCB
LCB
25 Feeder Trip GDC PCS
26 Vibrator Motor Fault GDC PCS
27 Material Low GDC PCS
28 Zeroing On GDC PCS
29 Pull Chord Healthy GDC PCS
30 Maintenance Off GDC PCS
31 PF Motor Fault GDC PCS
9 Analog IO List
9.1 Inputs
9.2 Outputs
Analog Inputs are available in 4-20 mA and 0-10 V through selection using Jumper
settings on AIO Cards.
10 Fieldbus Mapping
10.1 General
Fieldbus card can be used to interface many fieldbus options to GDC controller. GDC
supports Modbus RTU, Profibus DP, Modbus TCP, and Ethernet IP.
Data Format – 8, E, 1
Input Registers
Register Type Name Unit
No
11 Accept CM H active
12
13
14
15 Start CM H active
5 0 0 Abort CM H active
1 8
10
11
12
13
14
15
Output Register
Register Type Name Unit
No
8 0 0
10
13
1 – Word Swapped
Input Registers
Register Type Name Unit
No
11 Accept CM H active
12
13
14
15 Start CM H active
2 16 Abort CM H active
17
19
20
21
22
23
3 24
25
26
27
28
29
30
31
Output Register
Register Type Name Unit
No
9 Float Totalizer 1 t
20 Float Totalizer 2 t
10
15
1 – Word Swapped
Example:
• If Digital Input 0-11 Status (Parameter Code 1) and Digital Output 12-23 Status (Parameter
Code 2) needs to be read,
then Byte 0 of Input Register 14 should be set to code 1 and Byte 1 of Input Register 14
should be should be set to code 2. Input Register 14 holds Parameter Codes for Optional Read
Value 1 and 2.
• Hence Digital Input 0-11 Status can be read at Optional read value 1 i.e. Output Register 12
and Digital Output 0-11 Status can be read at Optional Read Value 2 i.e. Output register 13.
CM Status Codes
0 – Abort Reset,
1 – Hopper below Limit 1, 2 – User Aborted, 3 – Prefeeder On, 4 – Feeder Stopped, 5 – CM Started,
10 – CM Timeout
• Adjust counts to set 20 mA on multi-meter by pressing +/-. Increase the step size by
using 1X, 2X, 5X, 100X, 500X. Then press >Save as Span<.
13 Loadcell Calibration
Conditions
Procedure
1. To fully calibrate the Weigh Feeder, Perform Loadcell Calibration and Record Dynamic
Zero.
Conditions
Procedure
Conditions
Procedure
Zero Correction can be used to correct calibration error due to zero drifting. Zero
drifting is result od mechanical error and losses.
Procedure
1. Enter Totalizer quantity
2. Enter weighed quantity
3. Press >Calculate< to calculate correction factor
4. Press >Accept< to apply correction
5. Zero correction value can be entered directly
6. 31.54 Sum of Zero correction indicated total correction
7. 31.52 Max. Zero Correction limits the amount of correction.
Procedure
To reset the value of span correction factor, enter 0 manually and accept it.
The curve correction menu is used to store F and W values in tph for respective
setpoints.These values are used to linearize the beltload.
Procedure
5. Control measurement will be performed for time entered in 36.02 Correction Time.
Wait until the process status is updated to "CM completed".
6. Press >Accept Correction< to store F and W values for the current SP.
Note:
Check and set parameter 31.51, 31.52 and Correction Parameters
appropriately before performing control measurement. Refer parameter
manual for Parameters help.
Zero correction value is sent over fieldbus and Accept remote correction
command bit is set to apply zero correction.
S2 – All OFF
S2 – All ON
Upto 5 slaves are supported. Master sends bin level data to all the slaves.
17 Index history
Troubleshooting Manual
18 USB drive is not inserted • Check if Insert USB Pen drive Warning
USB MOUNT FAILED! • Check whether inserted Pen Drive is
not faulty
19 Start Release input is absent • Check Digital Input “Start Release” Error
INTEGRATION OFF!
Status in Diagnostics
20 Belt tracking Switch defective • Readjust belt tracking Error
• Check function of the switch, possibly
BELT TRACK FAULT! replace
• Check Digital Input “Belt Track”
Status in Diagnostics
21 FIELDBUS H/W ERROR! Send Fieldbus card for repairs Error
22 Emergency signal is present • Check Digital Input “Emergency” Error
Status in Diagnostics
EMERGENCY STOP!
• Check and rectify Emergency
Condition
feedrate
Minimum speed of drive is too high
38 LOADCELL 1 FAULT Any type of Loadcell fault occurs Check Loadcell Diagnostics for more Error
details
39 LOADCELL 2 FAULT Any type of Loadcell fault occurs Check Loadcell Diagnostics for more Error
details
40 INVALID DYNAMIC ZERO • Difference between Static zero and • Perform Loadcell Calibration Warning
dynamic zero is not in acceptable • Record dynamic zero
limits
Possible Causes:
• Zero calibration is shifted
• Dynamic zero is not performed
after Loadcell Zero calibration
41 BATCH COMPLETED • Batch operation completed • Warning
42 FILE OPEN ERROR GDC is not able to open new file in • Check SD Card Warning
memory
43 THERMAL FAULT Motor thermal switch input is absent • Check Digital Input “Motor Thermal Error
Switch” Status in Diagnostics
44 PULL CHORD HEALTHY Pull chord input is absent • Check Digital Input “Pull Chord Error
Status” Status in Diagnostics
45 PF MOTOR FAULT Motor is not powered or • Check Digital Input “PF Motor Error
Motor MPCB is tripped Interlock” Status in Diagnostics
• Check Drive MPCB and Motor
Overcurrent conditions
46 BIN UNDERLOAD Loadcell counts below minimum load • Check Loadcell Calibration Warning
value • Check Loadcell connections
• Check Loadcell supply voltage
• Check feeder mechanics whether
sufficient load is being applied on
Loadcell or not
• Check position of Weighing idler, Tie
Rod tension, Lever Functionality
• Check if Loadcell is defective
47 BIN OVERLOAD Loadcell counts above maximum load • Check Loadcell Calibration Warning
value • Check Loadcell connections
• Check Loadcell supply voltage
• Check feeder mechanics whether
excess load is being applied on
Loadcell or not
• Check position of Weighing idler, Tie
Rod tension, Lever Functionality
• Check if Loadcell is defective
• Check actual mV vs mV reported on
HMI in Loadcell Diagnostics.
• Check 46.32 Input Range
48 SHUTOFF GATE ERROR! If Shutoff gate is not opened • Check Digital Input “Shutoff Gate” Warning
status in Diagnostics
• Check Shutoff gate mechanical
49 SF BELT SLIP FAULT! Drive drum slips because belt tension is • Check the 37.17 [ZSS Timer Value], As per
too low or load on the belt is too large Possibly this time needs to be setting
Faulty Belt Switch increased 37.32
• Check the conveyor belt position
• Check Digital Input “SF Belt Slip”
Status in Diagnostics
• Check installation of slip sensor and
signal disk
• Check slip sensor for function, replace
if necessary
50 MASTER COM ERROR Master communication is not working • Check if the RS485 card is properly Warning
properly inserted
• Check communication cable wiring
51 SLAVE COM ERROR Slave communication is not working • Check if the PSU card is properly Warning
inserted
• Check communication cable wiring
• In Order to analyze the feeding and for long-term monitoring of the feeding system, data is stored in memory inside the
feeding controller. GDC Stores two years of data.
• The event log contains different events such as start, stop, and error message for the various units. An entry is only
made in the event of a status change, e.g. start.
• Data will be logged with the interval of 2 seconds in MS Excel Compatible format.
• These logs can be copied to USB Pen Drive using Copy Datalog User Menu. GDC creates different folders inside pen
drives before copying data.
User Password
00000
Service Password
MMDDX
• Calculation for X
Admin Password
Calculation of X
1. SUM = 1 + 1 + 1 + 2 = 5 (<=10)
WEIGH FEEDER
Weigh Feeder
Operations and Maintenance manual
Version 1.0
WEIGH FEEDER
Copyright
© All copyright and other property in this document and its contents are confidential and proprietary to FLSmidth Pfister. No
part of these materials should be reproduced, published, transmitted or distributed in any form or by any means, electronic,
mechanical, photocopying, recording or otherwise, or stored in any information storage or retrieval system of any nature nor
should the materials be disclosed to third parties without the prior express written authorization of FLSmidth Pfister.
WEIGH FEEDER
Content
2 Technical Details......................................................................................................................... 12
2.1 Technical Description .......................................................................................................... 13
WEIGH FEEDER
4.3 Disassembly......................................................................................................................... 23
WEIGH FEEDER
WEIGH FEEDER
WEIGH FEEDER
This belt weigh feeder is constructed in accordance with the state of the art
and the recognized technical safety regulations. However, a precondition is
that it is essential to follow the safety instructions.
During transportation, lift the belt weigh feeder using the marked points
on the belt frame.
In order to ensure safe operation of the belt weigh feeder, all the drives
must be fitted with repair switches that can be locked in position.
The belt weigh feeder and its surroundings must be cleaned once a day.
Parts may only be replaced by parts that are at least equal in quality,
i.e. with the same or higher strength, temperature resistance, resistance
to chemicals, nominal pressure and test pressure.
WEIGH FEEDER
After the repair work has been completed, the belt weigh feeder may
only be put into operation as outlined in the commissioning instructions.
When changing the belt, steady the belt weigh feeder with the belt
replacement brackets to ensure that it does not tilt.
Use of the Weigh feeder for purposes other than the intended purpose is
prohibited.
WEIGH FEEDER
1.1 Introduction
The TLD XXXX/3.1X Belt Weigh Feeder is used for continuous gravimetric
feeding of bulk material in powder or grain form at a specified rate. The
Weigh Feeder output ranges from approx. 0.5 - 500 t/hr. Control ranges are
possible to 1:10.
WEIGH FEEDER
2 Technical Details
WEIGH FEEDER
Mounting Frame
Weighing Electronics
WEIGH FEEDER
The belt weigh feeder consists of a belt frame (1) in which the idlers (8) are
inserted. The conveyor belt (29) is pulled by the spherically turned drive
pulley (5). Together with its continuous shaft, it is mounted in flanged
bearings that are fastened to the belt frame. The conveyor belt is tensioned
and guided by the spherically turned tail pulley (6) so that it runs centrally
over the idlers and pulleys. The Self Alignment & Tensioning Arrangement
(11) compensates fluctuations in the belt pull caused by changing material
loading conditions. In the measuring section, which is formed by the three
measuring rollers (9), the belt load is taken up by the central roller and
guided over the weighing section to the measuring device (17). At the
weigher, there are material strippers fitted at the drive, tail pulley and inner
and outer conveyor belt sides.
The drive unit comprises of motor and reduction gear box both mounted on
a Main frame
2.1.3 Pulley
The pulley used is the standard steel drum pulley, which consists of a
continuous rim and two end discs fitted with compression hubs. The pulley
is covered with rubber to increase the co-efficient of friction between the
belt and the pulley.
WEIGH FEEDER
2.1.4 Idlers
Idler configuration used is to support the belts. Idler rolls consist of ERW
tube enclosed at each end and fitted with stationary shaft, anti-friction
bearings and seals.
A Tensioning and Guiding device is used to guide the conveyor belt and to
maintain the requisite tension.
WEIGH FEEDER
WEIGH FEEDER
3.1 Packing
The type of packing depends on the transportation route and type and
storage possibilities on the customer's premises. The belt weigh feeder is
usually supplied without packing.
The symbols applied to the belt weigh feeder and the packing must be
observed.
For transportation, the Weighing Rocker must be locked with the Locking
Screw (17). To protect the Load Cell (18), push it down by tightening the
Nut (14). In this way, all pressure is removed from the load cell and the
tension rod (4) has a play of approx. 2 mm at the load cell.
Do not alter the length of the tension rod at the screw (8).
WEIGH FEEDER
The Testing Device is secured with the screw and nut (15) to prevent the
lever (5) moving out of place. For transportation, the locking screw (15)
must be screwed in with the lever positioned upwards (as on delivery). The
testing device is ready for operation when the locking screw has been
removed. It is not necessary to secure the motorised testing device
(optional extra) before transportation.
When delivered from the factory, the belt weigh feeder is already prepared
for transport. If the belt weigh feeder is transported later, it must first be
secured and prepared as outlined under section 3.2.
The weight of the belt weigh feeder can be read off the name plate.
WEIGH FEEDER
WEIGH FEEDER
4 Mounting Instructions
WEIGH FEEDER
Assembly of the Weigh Feeder is carried out on site using the corresponding
installation drawing. Ensure that all relevant accident prevention regulations
are observed throughout the assembly work.
The belt weigh feeder must be set up centrally over the width of the belt
and underneath the material infeed chute.
The belt weigh feeder can be leveled with the support plates supplied on
delivery.
WEIGH FEEDER
1. Place shims of the same thickness under the spirit level at the left
and right at the same distance from the pulley end because the
pulleys are convex in shape.
2. Align the pulleys horizontally if necessary. To this end, adjust the
shims under the belt weigh feeder support. 0.
Remove the transport lugs and keep them in a safe place in case the belt
weigh feeder needs to be transported subsequently.
The belt weigh feeder is fully wired internally. The leads run to the control
box inside protective cable conduits.
4.3 Disassembly
WEIGH FEEDER
WEIGH FEEDER
WEIGH FEEDER
WEIGH FEEDER
Check the height adjustment of the measuring roller (9.1) and the
measuring section limiting rollers (9.2). With an unloaded belt, the
measuring roller (9.1) is 0.3 mm higher than the two adjacent limiting
rollers (9.2). These again are 2 mm higher than all other idlers/rollers
(factory setting). The height of each measuring roller may be adjusted with
a self-locking set screw positioned in the roller carrier. To adjust height,
release the belt tension and lift the concerning roller.
WEIGH FEEDER
During transportation the testing device is secured with the locking screw.
To activate the Testing device remove the locking screw (15). Sometimes
the belt weigh feeders are additionally secured by using the transport lug
which is to be removed during installation.
The test weight (20) is not applied to the weighing rocker (16) when the
lever (5) is swiveled up and the locking screw (8) is engaged in the hole in
the retainer plate.
Ensure that the test weight and application prism are clean and
the weighing rocker is not blocked by foreign particle deposits.
WEIGH FEEDER
It is essential to carry out the test run of the weigh feeder for calibration
and to ensure the proper installation of equipment.
In this process the Weigh Feeder is operated without loading any material
for the purpose of calibration and to measure the Zero curve. During this
run the Rod gate at the material infeed chute is closed and the silo is
empty.
To test run the weigh feeder without material follow the below
mentioned instructions:
WEIGH FEEDER
To ensure smooth and safe motion of the belt, follow the below
mentioned instructions:
1. If the belt slips to one side during running, increase the pulley axle
base on this side by means of the forcing spindles at the tail
pulley, or reduce it on the other side, depending on the height of
the belt tension.
2. The belt must be regulated often during the first operating hours.
0.
WEIGH FEEDER
10 - Tensioning Arrangement
Indicator Plate
The Tensioning / Guiding Device runs along the return side of the conveyor
belt and compensates for the changes in length caused by temperature
fluctuations or changing material extraction forces. During running the belt
tension should be checked and adjusted as necessary.
1. Adjust the axle distance to the forcing spindles on the tail pulley.
2. Ensure that the mounting distance of both the spindle is same.
3. When the belt tension is correct, the indicator marking on the
tensioning / guiding device in correct position. 0.
WEIGH FEEDER
Due to various pulling forces across the width of the belt, the belt can move
gradually to the side. Carry out basic adjustment as described in section
5.4.1.1. The Tensioning / Guiding Device compensate for the belt
movements during operation caused by changing conditions in the material
infeed chute or silo.
If the belt has drifted to the side, the Tensioning Roller (8) will be set askew
by the Guiding Rollers (5) on both sides and will counteract the drift.
The distance between the guiding rollers and the belt edge should
be approx. 3 mm on both sides.
WEIGH FEEDER
The zero curve compensates for fluctuations due to the tare effect.
5.4.1.5 Calibration
To test run the weigh feeder with material follow the below
mentioned instructions:
1. Set the material height limiter at the outlet of the infeed chute to
the material height H specified in the data sheet. Fill the silo with
the material and then open the (Rod) gate over the infeed chute.
2. Set the control to automatic operating mode.
3. Ensure that further transportation of the material after the belt
Weigh Feeder is guaranteed.
WEIGH FEEDER
1. The zero point of the belt weigh feeder is set when the machine is
warm.
2. The maximum material temperature is not exceeded.
3. There is no interruption to the material supply from the silo. 0.
An overall error is calculated from errors of the belt weigh feeder and errors
in the comparative weighing process, including the increments of both
displays.
5.4.4 Shutdown
WEIGH FEEDER
WEIGH FEEDER
6.2 Lubrication
Lubrication Points:
WEIGH FEEDER
Figure 11.
WEIGH FEEDER
WEIGH FEEDER
NOTE:- Grease filling is also change when the oil or shaft sealing ring are replaced.
(Qty - Oil in Litres & Grease ig.
WEIGH FEEDER
Replace the Roller Bearing grease and Sealing Rings whenever the Helical
Bevel Gear Unit is changed. The lubrication interval and the lubricant
quantity and specification are as mentioned in the above table.
Replace the Roller Bearing grease and Sealing Rings whenever the Helical
Gear Unit is changed. The lubrication interval and the lubricant quantity and
specification are as mentioned in the above table. Recommended lubricant
for gear unit:
The ball bearings and shaft sealing rings have lifetime lubrication. The ball
bearings and shaft sealing rings must be replaced every 10,000 operating
hours. The grease filling must be renewed when they are replaced.
WEIGH FEEDER
The bearings of the drive and tail pulleys must be re-lubricated every
10,000 operating hours.
All drive motors are supplied in assembled and ready to use condition. All
bearings of the drive motors are filled with pre-requisite amount of grease.
During periodic maintenance, the bearings should be thoroughly cleaned
and Lithium based grease should be filled up to 2/3rd of the capacity.
WEIGH FEEDER
6.3 Maintenance
Maintenance Points:
WEIGH FEEDER
Figure 12.
WEIGH FEEDER
WEIGH FEEDER
The belt weigh feeder is a measuring instrument. Soiling and dust deposits
can cause incorrect dosing results. For this reason, dirt of this kind must be
removed daily, or, even better, prevented from collecting.
Very high temperatures can build up in the motor and gear. The heat is
dissipated from their surface. Dust deposits reduce the amount of heat
given off, and can lead to overheating. Please observe the manufacturer's
operating instructions.
The bearings in the motor gear and drive / tail pulleys can get very hot if
they are overloaded, the lubrication fails or they are soiled. For this reason,
check them daily for unusual and loud noises during operation and lubricate
the bearings if necessary. If the area of the bearings gets hot, switch the
unit off immediately.
Dust deposits and foreign particles on the weighing device go into the
dosing as measuring errors. To maintain the proportioning accuracy, the
weighing device must be inspected and adjusted once a month and
recalibrated if necessary.
Dust deposits on the weighing device affect measurements. For this reason,
it is important to brush or vacuum off dust carefully, in particular from the
weighing rocker, holder and load cell. To clean the measuring device, open
Cover (2). (Refer Figure 5 )
Protect the weighing device from dirt. Replace the lid and tank
after maintenance work.
WEIGH FEEDER
Check that the weighing device runs smoothly at the screw (17) and the
overload limit screw (12).
Check that the weighing rocker with holder (3) runs smoothly in relation to
the belt frame (1). (Refer Figure 5 )
During dosage operation, the test weight (20) and the lever (7)
must not touch the weighing rocker.
To check the zero point, stop the supply of material to the belt weigh feeder
and empty the weigher and infeed chute completely.
1. Apply the test weight to the weighing rocker. To do so, swivel the
lever (5) down by pulling out the locking screw (8).
2. Select the calibration menu.
3. Compare the displayed calibration weight with the value stated on
the test weight or data sheet. Both values must agree.
4. Compare calibration value in kg/m with the displayed loading. In
the case of a deviation of the two values >0.2% recalibrate
according to adjusting instructions (electrical documentation).
5. In the calibration menu compare the change of the input voltage
on applying the test weight with the value in the data sheet. 0.
1. Power Shunt
− If there are foreign particles between belt frame and
weighing rocker, etc Power shunts are caused by
WEIGH FEEDER
2. The gap between the overload limit and housing of the measuring
device is soiled. Clean the gap.
3. Load cell up against its overload protection: readjust the overload
protection of the load cell.
4. Load cell is defective: Replace/Repair Load cell. 0.
Check the conveyor belt for wear. If it is heavily worn (rubber belt is
damaged; belt carrier is visible), the belt must be replaced as described in
the repair instructions.
WEIGH FEEDER
Check that the drive pulley stripper and the tail pulley stripper function
correctly. The strippers operate without contact. If necessary, correct the
distance between the stripper and pulley. This distance should be about 1
mm.
Perform a visual inspection of the seals for leaks every 3,000 operating
hours, and at least every 6 months.
Change the shaft sealing rings every 10,000 operating hours, depending on
the oil temperature, at least every 3 years.
WEIGH FEEDER
Change the shaft sealing rings every 10,000 operating hours. Inspect and,
if necessary, replace the ball bearings.
WEIGH FEEDER
7 Repair Instructions
WEIGH FEEDER
WEIGH FEEDER
The idlers and pulleys should also be cleaned and checked to ensure they
run smoothly whenever necessary. The belt is changed on the side opposite
the drive or terminal box.
WEIGH FEEDER
WEIGH FEEDER
WEIGH FEEDER
1. Release the Nuts (3) on the pulling head and turn back. (Refer
Figure 17)
2. Pull in the Tail pulley (5) with Hexagonal Nut; if necessary, hold
spindle still with the lock nuts. (Refer Figure 17)
3. Push the tail pulley in equally on both sides. (Refer Figure 17)
4. Pull back the threaded rod (4) hold the threaded rod with locked
nuts. (Refer Figure 17)
5. Unscrew the threaded rod (4) from the belt frame part (2) and pull
the threaded rod back until it no longer protrudes over the tail
pulley. (Refer Figure 17)
WEIGH FEEDER
6. Dismount the belt frame part (2) on the belt change side (1).
(Refer Figure 17)
7. Engage the supplied belt replacement bracket(s) in the belt frame
in the locking plate (15). (Refer Figure 17)
8. Push on the new belt onto the bracket(s) and raise them slightly
at the end. (Refer Figure 17)
9. Cut through the old conveyor belt.
10. Remove the support or suspension device of the conveyor
weigher on the belt changing side. 0.
To repair the measuring and testing device perform the below mentioned
actions sequentially:
WEIGH FEEDER
WEIGH FEEDER
Free the weighing rocker (16.1) so that it moves easily. Blocked or stiff
weighing rocker can result in dosing errors.
WEIGH FEEDER
The rollers on the measuring section have higher rotational accuracy than
the other idlers/rollers and must not be replaced with the others. The
measuring rollers are a different color from the other idlers/rollers so that
they are easy to distinguish.
WEIGH FEEDER
1. Release tension on the conveyor belt and raise the relevant roller.
2. Adjust the set screw as required. Insert the roller. Check height
adjustment.
3. Tension the belt, check the belt course adjustment and automatic
belt guidance. Refer 5.4.1. 0.
7.4 Drive
WEIGH FEEDER
WEIGH FEEDER
WEIGH FEEDER
1. Screw out Nut (2) to release the pressure of the pressure springs
(3).
2. Remove the holder with rubber stripper blade (4) from the U-bolts
(1).
3. Pull out the rubber stripper blade (4) with its holder.
4. Replace the rubber stripper blade.
5. Fit the new rubber stripper blade by following the instructions in
reverse order.
6. Adjust the pressure of the stripper for the operating conditions by
tensioning the pressure springs.
WEIGH FEEDER
Index of Figures
TACHOMETER PROBE
1) an oscillator
2) a trigger circuit
3) an output stage
Immediately an exitation voltage is applied, oscillation begins which causes the emmission, Of a radio
frequency electromagnetic sensing particular current to be drawn.
The coil is wound on a ferrite core which concentrates the sensing field in the axial direction through the
active face of the tachometer probe.
When a metel object enters the radiated field, it absorbs energy from the field.a load is placed upon the
oscillator and the output amplitude is reduced.
This alters the amount of current being drawn. The trigger circuit recognises this and changes the state of
the switching device in the output stage. If the metal object is removed, the oscillation will begin again, and
the device will return to its orginal state.
Length :- 22 mm
General
Feed rate (Q) 60 t/h Moisture 6.00 %
Material CHINA CLAY Matl. Temp. AMBIENT ° C
Bulk density 1.3 t/m3 Matl. Characteristics SLIGHTLY SLUGGISH
95 % < 75,
Grain size mm Ambient Temp. 40 ° C
MAX 90
Weigh feeder
Mes. Section 3.5 dm Matl. X sextion (A) 0.12 m2
Pulley dia 235 mm Height of layer (h) 230 mm
Pulley crs. 3000 mm Nom.load (GM) 52.07 kg
Belt width 1000 mm Belt Speed (VB) 0.1120 m/sec
Bed LG. Top (X) 210.82 mm Output rpm (nTR) 9.11 rpm
Drive - Motor
Drive Side R.H. SIDE Rated Speed (RPM) 1450 Rated Freq. (Hz) 50
Motor Make SIEMENS IE2 Max. Speed (RPM) 1556 Max. Freq.(Hz) 53.6
3 PHASE AC TEFC SQUIRREL
Motor Type Min. Speed (RPM) 127 Min. Freq.(Hz) 4.4
CAGE INDUCTION MOTOR
Insulation Class F Base Speed (RPM) 1400 Base Frequency (Hz.) 48.3
Protection IP 55 Rated Torque (kgf m) 1.03
Rated Current (A) 3 Rated Power ( kW) 1.50
Connection Scheme Star Limiting Req. Torque Value (VVFD) NA
Belting
Make FPIL STD Endless length 6848 mm
Rating 315/3, EP, 3/1.5, M24 Grade M24
Belt width 1000 mm Total thickness 7.5 mm
Loadcell
Make SCAIME
Type AVX75XC3CH 75 Kg x 2 150 kg
Rated load(FN) 150 kg ≅ 100 %
Tare load (FT) 15 kg ≅ 10 %
Mes. Load(FM) 52.07 kg ≅ 34.72 %
FM max =
1.25 x FM 65.09 kg ≅ 43.39 %
Condition FT + FM max. ≤ FN
Lever
Lever ratio (I) = 2.5 Dim. c = mm
Test load(actual load)(GP) 23.60 kg Dim. d = mm
Selected Test Weight 23.60 kg
Test Weight Calibration Percentage 100.00 % Dim. e = mm
General
Feed rate (Q) 60 t/h Moisture 1.00 %
Material RED OCHRE Matl. Temp. AMBIENT ° C
Bulk density 2.0 t/m3 Matl. Characteristics SLIGHTLY SLUGGISH
Grain size 95 % < 75, MAX 90 mm Ambient Temp. 35 ° C
Weigh feeder
Mes. Section 3.5 dm Matl. X sextion (A) 0.12 m2
Pulley dia 215 mm Height of layer (h) 230 mm
Pulley crs. 3400 mm Nom.load (GM) 80.88 kg
Belt width 1000 mm Belt Speed (VB) 0.0721 m/sec
Bed LG. Top (X) 210.82 mm Output rpm (nTR) 6.41 rpm
Drive - Motor
Drive Side R.H. SIDE Rated Speed (RPM) 1450 Rated Freq. (Hz) 50
Motor Make SIEMENS Max. Speed (RPM) 1611 Max. Freq.(Hz) 55.6
3 PHASE AC TEFC SQUIRREL
Motor Type Min. Speed (RPM) 132 Min. Freq.(Hz) 4.5
CAGE INDUCTION MOTOR
Insulation Class F Base Speed (RPM) 1450 Base Frequency (Hz.) 50.0
Protection IP 55 Rated Torque (kgf m) 1.5
Rated Current (A) 4.4 Rated Power ( kW) 2.20
Connection Scheme Delta Limiting Req. Torque Value (VVFD) NA
Belting
Make FPIL STD Endless length 7575 mm
Rating 400/3, EP, 3/1.5, M24 Grade M24
Belt width 1000 mm Total thickness 7.5 mm
Loadcell
Make SCAIME
Type AVX75XC3CH 75 Kg x 2 150 kg
Rated load(FN) 150 kg ≅ 100 %
Tare load (FT) 15 kg ≅ 10 %
Mes. Load(FM) 80.88 kg ≅ 53.92 %
FM max =
1.25 x FM 101.10 kg ≅ 67.40 %
Condition FT + FM max. ≤ FN
Lever
Lever ratio (I) = 1.0 Dim. c = mm
Test load(actual load)(GP) 23.60 kg Dim. d = mm
Selected Test Weight 23.60 kg
Test Weight Calibration Percentage 100.00 % Dim. e = mm
ELECTRICAL DRAWING
ELECTRICAL DRAWING - R0
DETAIL ELECTRICAL DRAWINGS - R0
TERMINATION DETAILS - R0
TABLE OF CONTENTS
SR. NO. PAGE DESCRIPTION DRAWING NO. PAGE. NO.
90.18737-WF-011
PROJECT : SHEET : 1
90.18737 - ----
CONSULTANT : START DATE DRAWN BY OF : 3
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TABLE OF CONTENTS
SR. NO. PAGE DESCRIPTION DRAWING NO. PAGE. NO.
90.18737-WF-011
PROJECT : SHEET : 2
90.18737 - ----
CONSULTANT : START DATE DRAWN BY OF : 3
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TABLE OF CONTENTS
SR. NO. PAGE DESCRIPTION DRAWING NO. PAGE. NO.
90.18737-WF-011
PROJECT : SHEET : 3
90.18737 - ----
CONSULTANT : START DATE DRAWN BY OF : 3
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
3. * FLSMIDTHPFISTER SCOPE
VM HOPPER
LCS
TACHO
M T WF ZSS
*WCS 02
*WC 08
*WC 06
S1 S2 *WCS 01.2
*WCS 01.1
*WC 01 *WC 02
WC 07
WCS 11
WCS 04
WCS 03
WP 02
WC 05
WCS 07
ELECTRICS ENCLOSURE WITH
GDC ELECTRONICS
WC 03
WP 04
WP 01
WC 04
WCS 05
WCS 06
WCS 08
DOWNSTREAM INTERLOCK
MATERIAL STARVATION
α ACTUAL FEEDRATE
REMOTE MODE SEL
50 Hz ±5% 50 Hz
LOCAL MODE SEL.
FEEDER HEALTHY
COMMUNICATION
VOL. MODE SEL.
TPH DEVIATION
GENERAL FAULT
α SET POINT
FAULT RESET
START/STOP
PROFIBUS
(MCC SUPPLY (UPS
BSS O/P
ZSS O/P
WF TRIP
WF ON
CUSTOMER) CUSTOMER)
PLC/DCS PANEL
(CUSTOMER)
90.18737-WF-011
PROJECT : SHEET : 1
90.18737 - 011-EE01-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1;3;5
Q1
3
32 Amps
2;4;6
1;3;5
F1
3 1;3;5
1;3
F2 TX1 Fa
ELECTRIC ENCLOSURE
U4 X1
L1 L2 L3 2
INVERTER
U V W
X2 1;3 U3
1;3 Fc 110V AC
Fb
2
1 Amp. 2 24VDC @2 Amps.
2 1 Amp.
U V W
K1
2;4 2;4
L2 1 1 1
110V AC
U1
U1 V1 W1 GDC
LAMP & GDC
ILLUMINATION
24V DC
3+PE
3+PE
M
M
FIELD
3~
3~
M1 M2
WF MOTOR VIB MOTOR
1.5 KW 0.27 KW
4 POLE 4 POLE MAX DISTANCE BETWEEN PANEL & MOTOR IS 150 MTRS
1500 RPM 1500 RPM
3.3A 0.52 A
90.18737-WF-011
PROJECT : SHEET : 2
90.18737 - 011-EE02-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
NOTE:-
LOUVERS + 1) MAX. FLOOR OPENING FOR CABLE :- 430 mm x 350 mm
FILTERS
2) DESIGN FEATURES :
NAME PLATE - FRONT SIDE WITH SWIVEL DOOR.
HMI
- REAR SIDE FIXED ON BOLTS.
DISPLAY
- PROTECTION SYSTEM IP54 WITH DOORS CLOSED.
INVERTER DISPLAY - INLINE INSTALLATION.
- UNDRILLED GLAND PLATE TO BE PROVIDED
PANEL LABEL
1800
DOOR LOCK POWER WF UPS
3) SHEET THICKNESS :
2000
ON ON ON
200
(STRUCTURE FINISH) AS PER SHADE NO. RAL 7035
2 N0S BASE - AS PER IS:5 - DARK BLACK
EARTHING
600 BOLT 460 6) PANEL DIMENSION : 600 mm X 500 mm X 2000 mm.
(M10)
500 PACKED SIZE:- 680 mm x 590 mm x 2110 mm.
MAINTENANCE
500
30
MAINTENANCE
SPACE REQD.
MAX. FRONT70
1000 (MIN)
EARTHING
DO NOT DRILL
CAUTION
90.18737-WF-011
PROJECT : SHEET : 3
90.18737 - 011-EE05-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
85
3) GLAND PLATE :- DRILLED GLAND HOLES WITH
BLANKING PLUGS.
S4 90 4) SHEET THICKNESS :
TPH
- 1.5 mm DOOR
D1 L2
VIB VIB - 1.38mm REST
DOOR ON OFF
- GLAND PLATE - 3.0 mm THK.
LOCK 5) WEIGHT :
- APPROX. 10 KGS.
295
300
S5
330(CTC)
L2
6) SURFACE PROTECTION :
FIELD NON-FIELD
- OUTSIDE & INSIDE
EPOXY POWDER COAT-
65 (STRUCTURE FINISH)
S3 S2 S1 P1
7) PROTECTION/CLASS : IP55
8) PACKED SIZE:
55
- 260mm x 340 mm x 440 mm.
400 210
.
CL OF CABLE
EARTHING
ENTRY QTY.- 1 NO.
BOLTS M6
2 NOS.
CONTROLS/INDICATIONS
90.18737-WF-011
PROJECT : SHEET : 4
90.18737 - 011-EE09-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
247
225
200
ø22.5 HOLE FOR BACKGROUND / OUTER SURF.
Ø22.5 HOLE FOR COLOUR - RAL 7035
CABLE GLAND (3 Nos.)
30 35 30
CONDUIT GLAND (6 Nos.)
21.25
43.75
55
168.00
45
45
TERMINALS
45
168
45
200
160
45
45
45
ø6.5 EARTHING BOLT
45
(2 nos)
15
55
44
21.25
15
FRONT VIEW
83.14 INNER VIEW 83.14
M5, SCREW (4 nos)
LABEL DETAIL
120 120
M6 SCREW (4 nos) (ON COVER)
FOR COVER FITTING
FOR JB MTG.
VIEW-(LEFT SIDE) VIEW-(RIGHT SIDE)
QTY : 1 NO.
NOTE:
1. OVERALL DIMENSIONS :
200.0 W x 200.0 HT. x 120.0 D
2. WEIGHT : 2.05 KGS.
3. MATERIAL SPECIFICATION :
130
- CRCA SHEET 1.5 mm THK.
4. SURFACE:- POWDER COAT RAL 7035
5. PROTECTION CLASS : IP 65
20
8. JB MAKE : PYROTECH
WARNING LABELS FOR JB
EARTHING
DO NOT DRILL
CAUTION
90.18737-WF-011
(JB1)
PROJECT : SHEET : 5
90.18737 - 011-EE10-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
268.96
240.56
U1
U1.1 U1.2 U1.3 U1.4 U1.5 U1.6 U1.7 U1.8
T+ T+ X14
10V1 +V
T- X6 T- X2
(OPTIONAL)
I/P+ A+
PROFIBUS
SH SH
I/P-
X12 X8 A- X8
AI1 X16
RS-485 (HMI) INVERTER B+ DI
DI
RS-485 B-
GND
10V2
X5 I/P+X11 ENCODER
128.4
132.5
RUN
I/P- AI2 LOADCELL
USB HOST
83
HEALTHY COMM
ERROR HEALTHY
+ X10
(OPTIONAL) X4 - AO1
POWER
Ethernet X7 X7
DO X15 DO
24 P
X3
24 N X1 + X9
E
– AO2
USB Device 24 V DC
LOADCELL
90.18737-WF-011
PROJECT : SHEET : 6
90.18737 - 011-EE26-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
VOLTAGE COLOR
GREY (+VE)
24V DC
BLACK (-VE)
2. EQPT DETAILS
90.18737-WF-011
PROJECT : SHEET : 1
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
MCC
(CUSTOMER)
POWER SUPPLY
415 V AC ±10%
50HZ ±5%
3ø SUPPLY
S1 L3
R Y B E X6 P L N
P1.4 / LAMP
X6 N
N1.4 / 11.2
X6 P
TX1 P1.3 / 10.1 1
WP01 S2
415I/P X6 N
3x4 mm² N1.3 / 10.1 DOORLIMIT
220V O/P@1 Amps 2 SWITCH
X6 P
L2 L1 P1.2 / 10.13
110V O/P@1 Amps
P X6 N POWER SUPPLY
X13 1 2 3 E N1.2 / 10.13
S 2N 2L 110V AC
0V 1L X6 P
P1.1 / 7.1
110VAC
X6 N
N1.1 / 7.1
LP1
4 2
1
Fc 4 2
1 Amps. 3 1
2 Fb
1 Amp. 3 1
1 3 5
Q1
32Amps
2 4 6
L3.1 / 17.5
L2.1 / 17.5
L1.1 / 17.5
L3 / 16.2
L2 / 16.2
415V/50Hz
L1 / 16.2
E / 3.11
90.18737-WF-011
PROJECT : SHEET : 2
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
UPS
(CUSTOMER)
UPS
110V AC
50HZ
1ø SUPPLY
L N E
WP04
2x2.5 mm²
X13 10 11 E
1 3
Fa
2 4
2 Amp.
LP3
UPS ON
2
X5 P
24P1.4 / 11.12
1
X5 N
24N1.4 / 11.12
X5 P
24P1.3 / 7.13
X5 N
24N1.3 / 7.13
N L
U3 X5 P
110V AC 24P1.2 / 5.8
24VDC @2.5Amps. E X5 N
POWER SUPPLY
24N1.2 / 5.8
V- V+
24V DC
24P1.1 / 5.5
24N1.1 / 5.5
WCSA-1
2x0.50 mm²
E / 2.13
90.18737-WF-011
PROJECT : SHEET : 3
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
/6 HMI
/7
U1.1
/8
CPU (T+) X6.1 6
(T+) HMI:E E / 17.5
/9
SUPPLY
/10
HMI:24N 24N1.2 / 3.11
COM2
/11 X6.2 8
(T-) (T-)
/12
/13
HMI:24P 24P1.2 / 3.11
/14 X6.3 9
(SH) (SH)
/15
/16.12
U1.2
FREE
U1.3
POWER SUPPLY (24P)
X1.1 24P1.1 / 3.11
X1.3
(E)
INVERTER MODBUS
COMMUNICATION
U1.5
DIGITAL IO CARD 1
U1.6
LOADCELL & TACHO CARD
CONNECTOR MOUNTED
ON CONTROLLER WCS 08
U1.7 2x0.75
X14:3+ X4
X4 3
PROFIBUS
FIELD BUS CARD
PROFIBUS DP INTERFACE
X14:8- X4 8
X14:5 PLC/DCS
(CUSTOMER)
U1.8
DIGITAL IO CARD 2
90.18737-WF-011
ARCHITECTURE
PROJECT : SHEET : 5
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
/5
U1.5
SETPOINT
ANALOG CARD
AI1 AI2 AO1
AO2
FREE
4-20mA 4-20mA O/P
4-20mA O/P
ANALOG INPUT
+10V
+10V
AI1+ AI1- AI2+ AI2- AO1+ AO1-
PE AO2+ AO2-
X12 1 2 3 X11 1 2 3 X10 1+ 2-+
PE X9 1+ 2-
-X22 4 5 6 7
WCS11
3x0.75
GREEN
BLACK
GRAY
X9 1 2 3
X22 1 2 3
X41 4 5 6 7
X9 4 5 6
WCSF
1
3x0.35 mm²
BLACK
RED
2
P1
3
LOCAL SETPOINT LCS
WCS07
2x0.75
WCSD
2x0.35
+7 -8
20
11.1 / 110P2
4-20mA I/P 19
4-20mA O/P 11.1 / 110N2
α SET POINT D1
α ACTUAL FEEDRATE
10.4 / 110N2.1
PLC/DCS
(CUSTOMER) FEEDRATE INDICATOR
90.18737-WF-011
PROJECT : SHEET : 6
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
/5 DIGITAL INPUT CARD 1
=A1-U3-U2.7-X8:15
U1.5
10
3
DB-15(F)
24P1.3 / 3.11
24VDC
24N1.3 / 3.11
E1.1 / 11.13
U2
E0 E1 E2 E3 E4 E5
P1:1
/8.1
3
E0 E1 E2 E3 E4 E5
/9.1
/10.1
E0 E1
E2 E3 E4
BELT TRACK E5
BELT SLIP FLAP TPYE SW. REMOTE START/STOP
24P
E2
E5
24P
24P
24P
24P
24P
E0
E1
E3
E4
U7
RL1 P C O RL2 P C O RL3 P C O
U5
RELAY BOARD RL1 P C O RL2 P C O RL3 P C O
110V AC
RL1 4CH/1CO RL2 RL3
RELAY BOARD
110V AC
RL1 4CH/1CO RL2 RL3
RL1 COM 1 RL2 COM 2 RL3 COM 3
110V AC
RL1 COM 1 2 3
2.8 / N1.1
2.8 / P1.1
X10 1 2 3 4 5
WC05
12x1.5
LCS
X14 1 2 3 4 5 6 7
X12 1 2 3 4 5 6
110P 110N
11.1 11.1
WC07
6x1.5
JB1 WC04
6x1.5
X15 16 17 18 19 20 21 22 23 24
90.18737-WF-011
PROJECT : SHEET : 7
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1 U1.5
GDC
DIGITAL INPUT CARD 1
=A1-U3-U2.7-X8:8
/5
11
2
6
DB-15(F)
U2
E6 E7 E8 E9 E10 E11
/7.2
E6 E7 E8 E9 E10 E11
E6 E7 E8 E9 E10 E11
E10
E11
24P
24P
24P
24P
24P
24P
E6
E7
E8
E9
13 13
F1 F2
/16.3 14 /17.8 14
90.18737-WF-011
PROJECT : SHEET : 8
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
DIGITAL OUTPUT CARD 1
=A1-U3-U2.7-X7:3
/5
U1.5
6
DB-15(M)
U2
A0 A1 A2 A3 A4 A5
/7.2
A0 A1 A2 A3 A4 A5
A000 A002
A001 A003 A004 A005
WF ON TRIP
GENERAL FAULT UNDERLOAD REMOTE (LOCAL) EMG STOP
NO:0
NO:1
NO:2
NO:3
NO:4
NO:5
NC:0
NC:1
NC:2
NC:3
NC:4
NC:5
C:0
C:1
C:2
C:3
C:4
C:5
21 13
F1 K1
/10.12 14
22/16.3
X21 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
WC03
34x1.5
WF VIB ON
WF ON GENERAL FAULT TPH DEVIATION MATERIAL STARVATION REMOTE MODE SEL EMG STOP FEEDBACK
TRIP
PLC/DCS
(CUSTOMER)
90.18737-WF-011
PROJECT : SHEET : 9
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
DIGITAL OUTPUT CARD 1
=A1-U3-U2.7-X7:11
/5
U1.5
15
10
9
DB-15(M)
U2
A6 A7 A8 A9 A10 A11
/7.2
A6 A7 A8 A9 A10 A11
NO:10
NO:11
NC:10
NC:11
NO:6
NO:7
NO:8
NO:9
NC:6
NC:7
NC:8
NC:9
C:10
C:11
C:6
C:7
C:8
C:9
2.8 / P1.3
A1
110V AC K1
A2 P1.2 / 2.8 110V AC
N1.2 / 2.8
13A
2.8 / N1.3
K1
/10.12 14A
VIB START/STOP
X21 17 18 19 20 21 22 23 24
X10 6 7
WC03
34x1.5
WC 05
12x1.5
LP2 LCS
X14 8 9 INT/DEINT MODE SEL. TOTALISER PULSE O/P VOL. MODE SEL. GRAV MODE SEL.
1
2 1 1
L1 L2
2 2
1 2 /17.7
WF ON 110N2.1 / 6.12 3 4 /17.7
PLC/DCS 5 6 /17.7
(CUSTOMER) 13 14 /9.14
EE DOOR WF ON/FAULT VIB ON/OFF
13A 14A /10.4
90.18737-WF-011
PROJECT : SHEET : 10
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
/5 DIGITAL INPUT CARD 2
=A1-U3-U2.7-X8:15
U1.8
10
3
DB-15(F)
P1:1
/12.1
3
E0 E1 E2 E3 E4 E5
/13.2
/14.2
E1
E0 E2
E3 E4 E5
24P
24P
24P
24P
24P
24P
E0
E1
E2
E3
E4
E5
U6 P C O P C O P C O P C O P C O P C O
RL1 RL2 RL3 RL4 RL5 RL6
RELAY BOARD
110VAC
RL1 RL2 RL3 8CH/1CO RL4 RL5 RL6
WC05
12x1.5
X14 10 11 12 13 14 15 16
3 3 1 1 3
110N2 / 6.12 S1 S2 S3 S4 S5
LOC/REM START STOP EMG OFF VIB ON/OFF
110P2 / 6.12 4 4 2 2 4
90.18737-WF-011
PROJECT : SHEET : 11
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1 U1.8
GDC
DIGITAL INPUT CARD 2
=A1-U3-U2.7-X8:8
/5
11
2
6
DB-15(F)
U8
E6 E7 E8 E9 E10 E11
/11.1
E6 E7 E8 E9 E10 E11
E6 E7 E8 E9 E10 E11
E10
E11
24P
24P
24P
24P
24P
24P
E6
E7
E8
E9
90.18737-WF-011
PROJECT : SHEET : 12
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
DIGITAL OUTPUT CARD 2
=A1-U3-U2.7-X7:3
/5
U1.8
6
DB-15(M)
U8
A0 A1 A2 A3 A4 A5
/11.1
A0 A1 A2 A3 A4 A5
A000
A001 A002 A003 A004 A005
NO:0
NO:1
NO:2
NO:3
NO:4
NO:5
NC:0
NC:1
NC:2
NC:3
NC:4
NC:5
C:0
C:1
C:2
C:3
C:4
C:5
X21 25 26 27 28 29 30 31 32 33 34
WC03
34x1.5
FEEDER HEALTHY READY TO START BSS O/P LOCAL MODE SEL ZSS O/P
PLC/DCS
(CUSTOMER)
90.18737-WF-011
PROJECT : SHEET : 13
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
DIGITAL OUTPUT CARD 2
=A1-U3-U2.7-X7:11
/5
U1.8
15
10
9
DB-15(M)
U8
A6 A7 A8 A9 A10 A11
/11.1
A6 A7 A8 A9 A10 A11
NO:10
NO:11
NC:10
NC:11
NO:6
NO:7
NO:8
NO:9
NC:6
NC:7
NC:8
NC:9
C:10
C:11
C:6
C:7
C:8
C:9
90.18737-WF-011
PROJECT : SHEET : 14
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TACHO I/P
SUPPLY +
SUPPLY +
SIGNAL +
SUPPLY -
SIGNAL -
GROUND
SENSE +
SENSE -
FREE
FREE
X15 1 5 4 2 6 8 9 3 7 X16 1 2
X11 5 2 7 3 4 6 1 X11 8 9 10
WCS03
6x0.75 mm²
WCS04
2x0.75
JB1
X15 5 2 11 1 3 12 4 8 7 10 9 6 13 14 15
SH
WCS02
/15.3
2x0.35
WCS01-1 WCS01-2
4x0.35 4x0.35
A C
A C TH
LC1
LC2
LOADCELL
B D
TACHO
B D
FIELD
90.18737-WF-011
PROJECT : SHEET : 15
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
415 V/50Hz
U1.2
1 3 5
13 21 INVERTER MODBUS
COMMUNICATION
F1 14 22
2.4-4 Amps (T-)
/8.3 /9.13 (T+)
X2.1 X2.2 SH
I>> I>> I>>
2 4 6
+24V GND DCOM DI1 DI2 DI3 DI4 DI5 DI6 SRC B A AGND SCR
-U4
1.5KW U1 V1 W1 PE X1.10 X1.11 X1.12 X1.13 X1.14 X1.15 X1.16 X1.17 X1.18 X3.28 X3.29 X3.30 X3.31 X3.32
ON
S1
ON
ACS550-01-04A1-4
ON
U2 V2 W2 PE X1.4 X1.5 X1.6 X1.7 X1.9 X1.8 X1.9 X1.19 X1.20 X1.21 X1.22 X1.23 X1.24 X1.25 X1.26 X1.27
+10V AI2 AGND AO1 AGND AO2 AGND RO1C RO1A RO1B RO2C RO2A RO2B RO3C RO3A RO3B
/11.10/
L2 U V W
150uH / 15 AMPS
U1 V1 W1
X13 4 5 6 E
WP02
4x4 mm² NOTE:
TERMINAL
MAX CABLE DISTANCE BETWEEN VFD PANEL & RESPECTIVE
1 2 3 E
BOX MOTOR CAN BE 150 MTRS
M1 M
3~
M1
WF MOTOR
1.5 KW,4 POLE
1500 RPM,3.3A
90.18737-WF-011
PROJECT : SHEET : 16
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
5.8 / E
2.13 / L3.1
2.13 / L1.1
1 3 5 13
F2
14
0.4-0.6 Amps
/8.5
1 3 5
K1
/10.12
2 4 6
X13 7 8 9 E
WP03
3x1.5
M2
X17 1 2 3 E
M2
M2 M
VIB MOTOR
0.27 KW 3~
4 POLE
1500 RPM
0.52 A
VIB MOTOR
90.18737-WF-011
PROJECT : SHEET : 17
90.18737 - 011-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 16
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CABLE OVERVIEW
TOTAL USED CROSS-SECTION NO OF
CABLE NAME SOURCE (FROM) TARGET (TO) CABLE TYPE VOLTAGE CONDUCTORS CONDUCTORS (SQ MM) RUNS REMARKS SCOPE OF CABLE PAGE NO.
=A1-WC01 =A1-JB1-X15 =A1-FIELD (YY) UNARMOURED 110V AC 2 2 1.5 1 BELTSWAY SW (LEFT) FPIL =A1/7.3
=A1-WC02 =A1-JB1-X15 =A1-FIELD (YY) UNARMOURED 110V AC 2 2 1.5 1 BELT SWAY SW (RIGHT) FPIL =A1/7.4
=A1-WC03 =A1-X21 =A1-PLC/DCS (YWY) ARMOURED 220 VAC 34 34 1.5 1 DIGITAL INPUT TO PLC CUSTOMER =A1/9.2
=A1-WC04 =A1-X12 =A1-PLC/DCS (YWY) ARMOURED 110V AC 6 6 1.5 1 DIGITAL INPUT TO WF GDC CUSTOMER =A1/7.8
=A1-WC05 =A1-LCS-X14 =A1-X10 (YWY) ARMOURED 110V AC 12 12 1.5 1 CONTROLS CUSTOMER =A1/7.1
=A1-WC06 =A1-JB1-X15 =A1-FIELD (YY) UNARMOURED 110V AC 2 2 1.5 1 ZERO SPEED SW FPIL =A1/7.1
=A1-WC07 =A1-JB1-X15 =A1-LCS-X14 (YWY) ARMOURED 110V AC 6 5 1.5 1 ZSS, BSS,FLAP TYPE FPIL =A1/7.1
=A1-WC08 =A1-JB1-X15 =A1-FIELD (YY) UNARMOURED 110V AC 2 2 1.5 1 FLAP TYPE SW. FPIL =A1/7.6
=A1-WCS01-1 =A1-JB1-X15 =A1-FIELD-LC1 (YY) UNARMOURED 12V 4 4 0.35 1 LOADCELL-1 FPIL =A1/15.3
=A1-WCS01-2 =A1-JB1-X15 =A1-FIELD-LC2 (YY) UNARMOURED 12V 4 4 0.35 1 LOADCELL-2 FPIL =A1/15.7
=A1-WCS02 =A1-JB1-X15 =A1-FIELD-TH (YY) UNARMOURED 12V DC 2 2 0.35 1 TACHO FPIL =A1/15.10
=A1-WCS03 =A1-JB1-X15 =A1-X11 (YWY) ARMOURED 12V DC 6 6 0.75 1 LOADCELL CUSTOMER =A1/15.3
=A1-WCS04 =A1-JB1-X15 =A1-X11 (YWY) ARMOURED 12V DC 2 2 0.75 1 TACHO CUSTOMER =A1/15.10
=A1-WCS05 =A1-X9 =A1-PLC/DCS (YWY) ARMOURED 4-20mA 2 2 0.75 1 4-20mA O/P α ACTUAL FEEDRATE CUSTOMER =A1/6.8
=A1-WCS06 =A1-X9 =A1-PLC/DCS (YWY) ARMOURED 4-20mA 2 2 0.75 1 4-20mA I/P α SET POINT CUSTOMER =A1/6.2
=A1-WCS07 =A1-LCS-X41 =A1-X22 (YWY) ARMOURED 4-20mA 2 2 0.75 1 FEEDRATE INDICATOR CUSTOMER =A1/6.13
=A1-WCS08 =A1-X4-X4 =A1-PLC/DCS (YWY) ARMOURED ----- 2 2 0.75 1 PROFIBUS COMMUNICATION CUSTOMER =A1/5.7
=A1-WCS11 =A1-LCS-X41 =A1-X22 (YWY) ARMOURED 0-10V 3 3 0.75 1 LOCAL SETPOINT CUSTOMER =A1/6.5
=A1-WP01 =A1-X13 =A1-MCC (YWY) ARMOURED 415V AC 3 3 4 1 MCC SUPPLY CUSTOMER =A1/2.1
(YWY) - ARMOURED COPPER CABLE (YY) - UNARMOURED COPPER CABLE (*) - POTENTIAL FREE (AYWY) - ARMOURED ALUMINIUM CABLE (AYY) - UNARMOURED ALUMINIUM CABLE
90.18737-WF-011
PROJECT : SHEET : 1
90.18737 - 011-EE04-R0
CONSULTANT : START DATE DRAWN BY OF : 2
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CABLE OVERVIEW
TOTAL USED CROSS-SECTION NO OF
CABLE NAME SOURCE (FROM) TARGET (TO) CABLE TYPE VOLTAGE CONDUCTORS CONDUCTORS (SQ MM) RUNS REMARKS SCOPE OF CABLE PAGE NO.
=A1-WP03 =A1-M2-X17 =A1-X13 (YWY) ARMOURED 415V AC 3 3 1.5 1 VIB MOTOR CUSTOMER =A1/17.7
=A1-WP04 =A1-X13 =A1-UPS (YWY) ARMOURED 110V AC 2 2 2.5 1 UPS CUSTOMER =A1/3.1
(YWY) - ARMOURED COPPER CABLE (YY) - UNARMOURED COPPER CABLE (*) - POTENTIAL FREE (AYWY) - ARMOURED ALUMINIUM CABLE (AYY) - UNARMOURED ALUMINIUM CABLE
90.18737-WF-011
PROJECT : SHEET : 2
90.18737 - 011-EE04-R0
CONSULTANT : START DATE DRAWN BY OF : 2
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WCS08
Strip
Cable name
Cable name
=A1+-X4-X4
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
90.18737-WF-011
PROJECT : SHEET : 1
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WCS05
-WCS06
Strip
Cable name
Cable name
=A1+-X9
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
1 /6.2
= 6 /6.9
90.18737-WF-011
PROJECT : SHEET : 2
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WC05
Strip
Cable name
Cable name
=A1+-X10
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
-U7-RL1 COM
-LP2 1
90.18737-WF-011
PROJECT : SHEET : 3
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WCS04
-WCS03
Strip
Cable name
Cable name
=A1+-X11
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 10 /15.11
90.18737-WF-011
PROJECT : SHEET : 4
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WC04
Strip
Cable name
Cable name
=A1+-X12
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
90.18737-WF-011
PROJECT : SHEET : 5
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WP04
-WP03
-WP02
-WP01
Strip
Cable name
Cable name
=A1+-X13
(YWY) ARMOURED
(YWY) ARMOURED
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
POWER SUPPLY 415 V AC ±10% 50HZ ±5% 3ø SUPPLY 1 -MCC R 1 -Q1 1 /2.1
90.18737-WF-011
PROJECT : SHEET : 6
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WC07
-WC05
Strip
Cable name
Cable name
=A1+-LCS-X14
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
220P 2 /7.2
= 4 /7.2
-LCS-S1 4 10 /11.1
-LCS-D1 20
-LCS-D1 19 11 /11.1
90.18737-WF-011
PROJECT : SHEET : 7
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WC08
-WC02
-WC01
-WC06
-WCS02
-WCS01-2
-WCS01-1
-WCS03
-WCS02
-WCS04
-WC07
Strip
Cable name
Cable name
=A1+-JB1-X15
(YY) UNARMOURED
(YY) UNARMOURED
(YY) UNARMOURED
(YY) UNARMOURED
(YY) UNARMOURED
(YY) UNARMOURED
(YY) UNARMOURED
(YWY) ARMOURED
(YY) UNARMOURED
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 1 -FIELD-LC2 A 7 /15.7
= 4 -FIELD-LC2 B 8 /15.7
= 2 -FIELD-LC2 C 9 /15.9
= 3 -FIELD-LC2 D 10 /15.8
= 15 /15.11
= 17 -LCS-X14 3 /7.2
= -FIELD 20 /7.4
= -FIELD 21 /7.4
= -FIELD 2 23 /7.6
90.18737-WF-011
PROJECT : SHEET : 8
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WC03
Strip
Cable name
Cable name
=A1+-X21
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
90.18737-WF-011
PROJECT : SHEET : 9
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WCS11
-WCS07
Strip
Cable name
Cable name
=A1+-X22
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 3 /6.14
= 7 /6.6
90.18737-WF-011
PROJECT : SHEET : 10
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-LCS-WCSF
-WCS07
-LCS-WCSD
-WCS11
Strip
Cable name
Cable name
=A1+-LCS-X41
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 3 /6.14
= 7 /6.6
90.18737-WF-011
PROJECT : SHEET : 11
90.18737 - 011-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
BILL OF MATERIALS
LEGEND QTY. DESIGNATION GENERAL SPECIFICATIONS PART NO. ERP PART NO. MANUFACTURER PAGE NO.
=A1-F1 1 MOTOR PROTECTION CIRCUIT BREAKER 2.4-4 AMPS 3VU13 40-1MJ00 805001010000 SIEMENS =A1/16.2
=A1-F2 1 MOTOR PROTECTION CIRCUIT BREAKER 0.4-0.6 AMPS 3VU13 40-1ME00 80500F0E0000 SIEMENS =A1/17.7
=A1-Fb 1 MINIATURE CIRCUIT BREAKER 1.0 AMP-2P 5SL62017RC 8030010E0100 SIEMENS =A1/2.12
=A1-Fc 1 MINIATURE CIRCUIT BREAKER 1.0 AMP-2P 5SL62017RC 8030010E0100 SIEMENS =A1/2.7
=A1-HMI 1 7" TOUCH SCREEN DISPLAY 24V DC HMI WITH CABLE 80Z003002200 FPIL =A1/5.6
=A1-LCS-D1 1 DIGITAL PANEL METER 85 TO 270V AC - 4 (DIGIT) (TPH) PIC101N C05096040700 SELECTRON =A1/6.12
=A1-LCS-L1 1 LED LAMP 110V AC - RED 3SB52 85-6HC02 80200G130000 SIEMENS =A1/10.3
=A1-LCS-L2 1 LED LAMP 110V AC - RED 3SB52 85-6HC02 80200G130000 SIEMENS =A1/10.4
=A1-LCS-S1 1 MODULAR SELECTOR ACTUATORS 2 POSITION SELECTOR SW. (BLACK) 3SB50 00-2AB01 50G0060A0100 SIEMENS =A1/11.2
=A1-LCS-S2 1 MODULAR PUSH BUTTON ACTUATORS PUSH BUTTON (GREEN) WITH NO CONTACT BLOCK 3SB50 00-0AE01+3SB54 00-0B 50G005070100 SIEMENS =A1/11.4
=A1-LCS-S3 1 MODULAR PUSH BUTTON ACTUATORS PUSH BUTTON (RED)WITH NO CONTACT BLOCK 3SB50 00-0AC01+3SB54 00-0B 50G005080100 SIEMENS =A1/11.7
=A1-LCS-S4 1 MUSHROOM ACTUATORS EMERGENCY STOP (RED) 3SB52 03-0UC01 50G002090100 SIEMENS =A1/11.9
=A1-LCS-S5 1 MODULAR SELECTOR ACTUATORS 2 POSITION SELECTOR SW. (BLACK) 3SB50 00-2AB01 50G0060A0100 SIEMENS =A1/11.11
90.18737-WF-011
PROJECT : SHEET : 1
90.18737 - 011-EE03-R0
CONSULTANT : START DATE DRAWN BY OF : 2
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 41
1 2 3 4 5 6 7 8 9 10 11 12 13 14
BILL OF MATERIALS
LEGEND QTY. DESIGNATION GENERAL SPECIFICATIONS PART NO. ERP PART NO. MANUFACTURER PAGE NO.
=A1-LP1 1 LED LAMP 110V AC - RED 3SB52 85-6HC02 80200G130000 SIEMENS =A1/2.5
=A1-LP2 1 LED LAMP 110V AC - AMBER 3SB52 85-6HL02 80200I140000 SIEMENS =A1/10.2
=A1-LP3 1 LED LAMP 110V AC - RED 3SB52 85-6HC02 80200G130000 SIEMENS =A1/3.2
=A1-S1 1 SURFACE MOULED ON / OFF SW. 5 AMPS ------- 50G0090C0200 ANCHOR =A1/2.11
=A1-S2 1 DOOR LIMIT SWITCH 400V AC, 6A 3SE5250-0BC05 80A026460000 SIEMENS =A1/2.13
=A1-TX1 1 TRANSFORMER I/P 415V AC, O/P 220V AC @ 1 AMP, 110V AC @ 1 AMP------- 80F00K0D0200 OM INDUSTRIES =A1/2.4
=A1-U1 1 GRAVIMETRIC DOSING CONTROLLER 24V DC GDC (LCT-BASIC) 5000I00D0L00 FPIL =A1/5
=A1-U2 1 SMALL RELAY BOARD 12 I/O & 12 O/P RL I/O 5000P00H0P00 FPIL =A1/7.2
=A1-U3 1 POWER SUPPLY Input: AC 100-240V, Output 24VDC 2.5A S8VK - C06024 C030K1500100 OMRON =A1/3.7
=A1-U5 1 RELAY BOARD 4 CHANNEL - 1 CHANGE OVER 110V AC - 4CH/1CO 80900D0E0B00 FPIL =A1/7.8
=A1-U6 1 RELAY BOARD 8 CHANNEL - 1 CHANGE OVER 110V AC - 8CH/1CO 809005070100 FPIL =A1/11.2
=A1-U7 1 RELAY BOARD 4 CHANNEL - 1 CHANGE OVER 110V AC - 4CH/1CO 80900D0E0B00 FPIL =A1/7.1
=A1-U8 1 SMALL RELAY BOARD 12 I/O & 12 O/P RL I/O 5000P00H0P00 FPIL =A1/11.1
=A1-X4 1 PROFIBUS CONNECTOR LED TYPE - EASYCONN - PB 0° 972-0DP30 E0J050060400 VIPA =A1/5.6
90.18737-WF-011
PROJECT : SHEET : 2
90.18737 - 011-EE03-R0
CONSULTANT : START DATE DRAWN BY OF : 2
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 1/11/2019 VIM-IN TOTAL : 41
FLSMIDTH PVT. LTD.
(PFISTER INDIA BUSSINESS UNIT)
i-THINK TECHNO CAMPUS, 'A' WING,1ST FLOOR,
OFFICE NO. 2, OFF POKHRAN ROAD 2, BEHIND TCS,
THANE, MAHARASHTRA
CITY : MUMBAI ZIP CODE : 400 601 COUNTRY : INDIA
PHONE : 022 6117 2555 FAX : 022 6117 2917 E-MAIL : transweigh.sales@flsmidthpfister.com
ELECTRICAL DRAWING - R0
DETAIL ELECTRICAL DRAWINGS - R0
TERMINATION DETAILS - R0
TABLE OF CONTENTS
SR. NO. PAGE DESCRIPTION DRAWING NO. PAGE. NO.
90.18737-WF-012
PROJECT : SHEET : 1
90.18737 - ----
CONSULTANT : START DATE DRAWN BY OF : 3
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TABLE OF CONTENTS
SR. NO. PAGE DESCRIPTION DRAWING NO. PAGE. NO.
90.18737-WF-012
PROJECT : SHEET : 2
90.18737 - ----
CONSULTANT : START DATE DRAWN BY OF : 3
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TABLE OF CONTENTS
SR. NO. PAGE DESCRIPTION DRAWING NO. PAGE. NO.
90.18737-WF-012
PROJECT : SHEET : 3
90.18737 - ----
CONSULTANT : START DATE DRAWN BY OF : 3
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
3. * FLSMIDTHPFISTER SCOPE
HOPPER
LCS
TACHO
M T WF ZSS
*WCS 02
*WC 06
S1 S2 *WCS 01.2
*WCS 01.1
*WC 01 *WC 02
WC 07
WCS 11
WCS 04
WCS 03
WP 02
WC 05
WCS 07
ELECTRICS ENCLOSURE WITH
GDC ELECTRONICS
WC 03
WP 04
WP 01
WC 04
WCS 05
WCS 06
WCS 08
DOWNSTREAM INTERLOCK
MATERIAL STARVATION
α ACTUAL FEEDRATE
REMOTE MODE SEL
50 Hz ±5% 50 Hz
LOCAL MODE SEL.
FEEDER HEALTHY
COMMUNICATION
VOL. MODE SEL.
TPH DEVIATION
GENERAL FAULT
PROFIBUS
(MCC SUPPLY (UPS
BSS O/P
ZSS O/P
WF TRIP
WF ON
CUSTOMER) CUSTOMER)
PLC/DCS PANEL
(CUSTOMER)
90.18737-WF-012
PROJECT : SHEET : 1
90.18737 - 012-EE01-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
1;3;5
Q1
3
32 Amps
2;4;6
1;3;5
F1
3
1;3
TX1 Fa
ELECTRIC ENCLOSURE
U4 X1
L1 L2 L3 2
INVERTER
U V W
X2 1;3 U3
1;3 Fc 110V AC
Fb
2
1 Amp. 2 24VDC @2 Amps.
2 1 Amp.
U V W
2;4 2;4
L2 1 1 1
110V AC
U1
U1 V1 W1 GDC
LAMP & GDC
ILLUMINATION
24V DC
3+PE
M
FIELD
3~
M1
WF MOTOR
2.2 KW
4 POLE MAX DISTANCE BETWEEN PANEL & MOTOR IS 150 MTRS
1500 RPM
4.4 A
90.18737-WF-012
PROJECT : SHEET : 2
90.18737 - 012-EE02-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
NOTE:-
LOUVERS +
FILTERS 1) MAX. FLOOR OPENING FOR CABLE :- 430 mm x 350 mm
2) DESIGN FEATURES :
NAME PLATE
- FRONT SIDE WITH SWIVEL DOOR.
HMI - REAR SIDE FIXED ON BOLTS.
DISPLAY
- PROTECTION SYSTEM IP54 WITH DOORS CLOSED.
INVERTER DISPLAY
- INLINE INSTALLATION.
- UNDRILLED GLAND PLATE TO BE PROVIDED
PANEL LABEL
1800
DOOR LOCK POWER WF UPS
3) SHEET THICKNESS :
2000
ON ON ON
500
30
MAINTENANCE
SPACE REQD.
MAX. FRONT70
1000 (MIN)
EARTHING
DO NOT DRILL
CAUTION
90.18737-WF-012
PROJECT : SHEET : 3
90.18737 - 012-EE05-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
85
3) GLAND PLATE :- DRILLED GLAND HOLES WITH
BLANKING PLUGS.
S4 90 4) SHEET THICKNESS :
TPH
- 1.5 mm DOOR
D1 L1
- 1.38mm REST
DOOR - GLAND PLATE - 3.0 mm THK.
LOCK 5) WEIGHT :
- APPROX. 10 KGS.
295
300
330(CTC)
6) SURFACE PROTECTION :
FIELD NON-FIELD
- OUTSIDE & INSIDE
EPOXY POWDER COAT-
65 (STRUCTURE FINISH)
S3 S2 S1 P1
7) PROTECTION/CLASS : IP55
8) PACKED SIZE:
55
- 260mm x 340 mm x 440 mm.
400 210
.
CL OF CABLE
EARTHING
ENTRY QTY.- 1 NO.
BOLTS M6
2 NOS.
CONTROLS/INDICATIONS
CAUTION
90.18737-WF-012
PROJECT : SHEET : 4
90.18737 - 012-EE09-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
247
225
200
ø22.5 HOLE FOR BACKGROUND / OUTER SURF.
Ø22.5 HOLE FOR COLOUR - RAL 7035
CABLE GLAND (3 Nos.)
30 35 30
CONDUIT GLAND (5 Nos.)
21.25
43.75
55
168.00
45
45
TERMINALS
45
168
45
200
160
45
45
45
ø6.5 EARTHING BOLT
45
(2 nos)
15
55
44
21.25
15
FRONT VIEW
83.14 INNER VIEW 83.14
M5, SCREW (4 nos)
LABEL DETAIL
120 120
M6 SCREW (4 nos) (ON COVER)
FOR COVER FITTING
FOR JB MTG.
VIEW-(LEFT SIDE) VIEW-(RIGHT SIDE)
QTY : 1 NO.
NOTE:
1. OVERALL DIMENSIONS :
200.0 W x 200.0 HT. x 120.0 D
2. WEIGHT : 2.05 KGS.
3. MATERIAL SPECIFICATION :
130
- CRCA SHEET 1.5 mm THK.
4. SURFACE:- POWDER COAT RAL 7035
5. PROTECTION CLASS : IP 65
20
EARTHING
DO NOT DRILL
CAUTION
90.18737-WF-012
(JB1)
PROJECT : SHEET : 5
90.18737 - 012-EE10-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
268.96
240.56
U1
U1.1 U1.2 U1.3 U1.4 U1.5 U1.6 U1.7 U1.8
T+ T+ X14
10V1 +V
T- X6 T- X2
(OPTIONAL)
I/P+ A+
PROFIBUS
SH SH
I/P-
X12 X8 A- X8
AI1 X16
RS-485 (HMI) INVERTER B+ DI
DI
RS-485 B-
GND
10V2
X5 I/P+X11 TACHO
128.4
132.5
RUN
I/P- AI2 LOADCELL
USB HOST
83
HEALTHY COMM
ERROR HEALTHY
+ X10
(OPTIONAL) X4 - AO1
POWER
Ethernet X7 X7
DO X15 DO
24 P
X3
24 N X1 + X9
E
– AO2
USB Device 24 V DC
LOADCELL
90.18737-WF-012
PROJECT : SHEET : 6
90.18737 - 012-EE26-R0
CONSULTANT : START DATE DRAWN BY OF : 6
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
VOLTAGE COLOR
GREY (+VE)
24V DC
BLACK (-VE)
2. EQPT DETAILS
90.18737-WF-012
PROJECT : SHEET : 1
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
MCC
(CUSTOMER)
POWER SUPPLY
415 V AC ±10%
50HZ ±5%
3ø SUPPLY
S1 L3
R Y B E X6 P L N
P1.4 / LAMP
X6 N
N1.4 / 11.2
X6 P
TX1 P1.3 / 10.1 1
WP01 S2
415I/P X6 N
3x4 mm² N1.3 / 10.1 DOORLIMIT
220V O/P@1 Amps 2 SWITCH
X6 P
L2 L1 P1.2 /
110V O/P@1 Amps
P X6 N POWER SUPPLY
X13 1 2 3 E N1.2 /
S 2N 2L 110V AC
0V 1L X6 P
P1.1 / 7.1
110VAC
X6 N
N1.1 / 7.1
LP1
4 2
1
Fc 4 2
1 Amps. 3 1
2 Fb
1 Amp. 3 1
1 3 5
Q1
32Amps
2 4 6
L3 / 16.2
L2 / 16.2
415V/50Hz
L1 / 16.2
E / 3.11
90.18737-WF-012
PROJECT : SHEET : 2
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
UPS
(CUSTOMER)
UPS
110V AC
50HZ
1ø SUPPLY
L N E
WP04
2x2.5 mm²
X13 7 8 E
1 3
Fa
2 4
2 Amp.
LP3
UPS ON
2
X5 P
24P1.4 / 11.12
1
X5 N
24N1.4 / 11.12
X5 P
24P1.3 / 7.13
X5 N
24N1.3 / 7.13
N L
U3 X5 P
110V AC 24P1.2 / 5.8
24VDC @2.5Amps. E X5 N
POWER SUPPLY
24N1.2 / 5.8
V- V+
24V DC
24P1.1 / 5.5
24N1.1 / 5.5
WCSA-1
2x0.50 mm²
E / 2.13
90.18737-WF-012
PROJECT : SHEET : 3
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
/6 HMI
/7
U1.1
/8
CPU (T+) X6.1 6
(T+) HMI:E E/
/9
SUPPLY
/10
HMI:24N 24N1.2 / 3.11
COM2
/11 X6.2 8
(T-) (T-)
/12
/13
HMI:24P 24P1.2 / 3.11
/14 X6.3 9
(SH) (SH)
/15
/16.12
U1.2
FREE
U1.3
POWER SUPPLY (24P)
X1.1 24P1.1 / 3.11
X1.3
(E)
INVERTER MODBUS
COMMUNICATION
U1.5
DIGITAL IO CARD 1
U1.6
LOADCELL & TACHO CARD
CONNECTOR MOUNTED
ON CONTROLLER WCS 08
U1.7 2x0.75
X14:3+ X4
X4 3
PROFIBUS
FIELD BUS CARD
PROFIBUS DP INTERFACE
X14:8- X4 8
X14:5 PLC/DCS
(CUSTOMER)
U1.8
DIGITAL IO CARD 2
90.18737-WF-012
ARCHITECTURE
PROJECT : SHEET : 5
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
/5
U1.5
SETPOINT
ANALOG CARD
AI1 AI2 AO1
AO2
FREE
4-20mA 4-20mA O/P
4-20mA O/P
ANALOG INPUT
+10V
+10V
AI1+ AI1- AI2+ AI2- AO1+ AO1-
PE AO2+ AO2-
X12 1 2 3 X11 1 2 3 X10 1+ 2-+
PE X9 1+ 2-
-X22 4 5 6 7
WCS11
3x0.75
GREEN
BLACK
GRAY
X9 1 2 3
X22 1 2 3
X41 4 5 6 7
X9 4 5 6
WCSF
1
3x0.35 mm²
BLACK
RED
2
P1
3
LOCAL SETPOINT LCS
WCS07
2x0.75
WCSD
2x0.35
+7 -8
20
11.1 / 110P2
4-20mA I/P 19
4-20mA O/P 11.1 / 110N2
α SET POINT D1
α ACTUAL FEEDRATE
10.4 / 110N2.1
PLC/DCS
(CUSTOMER) FEEDRATE INDICATOR
90.18737-WF-012
PROJECT : SHEET : 6
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
/5 DIGITAL INPUT CARD 1
=A2-U3-U2.7-X8:15
U1.5
10
3
DB-15(F)
24P1.3 / 3.11
24VDC
24N1.3 / 3.11
E1.1 / 11.13
U2
E0 E1 E2 E3 E4 E5
P1:1
/8.1
3
E0 E1 E2 E3 E4 E5
/9.1
/10.1
E0 E1
E2 E3 E4
BELT TRACK E5
BELT SLIP FLAP TPYE SW. REMOTE START/STOP
24P
E2
E5
24P
24P
24P
24P
24P
E0
E1
E3
E4
U7
RL1 P C O RL2 P C O RL3 P C O
U5
RELAY BOARD RL1 P C O RL2 P C O RL3 P C O
110V AC
RL1 4CH/1CO RL2 RL3
RELAY BOARD
110V AC
RL1 4CH/1CO RL2 RL3
RL1 COM 1 RL2 COM 2 RL3 COM 3
110V AC
RL1 COM 1 2 3
2.8 / N1.1
2.8 / P1.1
X10 1 2 3 4
WC05
12x1.5
LCS
X14 1 2 3 4 5 6
X12 1 2 3 4 5 6
110P 110N
11.1 11.1
WC07
6x1.5
JB1 WC04
6x1.5
X15 16 17 18 19 20 21 22
90.18737-WF-012
PROJECT : SHEET : 7
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1 U1.5
GDC
DIGITAL INPUT CARD 1
=A2-U3-U2.7-X8:8
/5
11
2
6
DB-15(F)
U2
E6 E7 E8 E9 E10 E11
/7.2
E6 E7 E8 E9 E10 E11
E6 E7 E8 E9 E10 E11
E10
E11
24P
24P
24P
24P
24P
24P
E6
E7
E8
E9
13
F1
/16.3 14
WF INTERLOCK
90.18737-WF-012
PROJECT : SHEET : 8
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
DIGITAL OUTPUT CARD 1
=A2-U3-U2.7-X7:3
/5
U1.5
6
DB-15(M)
U2
A0 A1 A2 A3 A4 A5
/7.2
A0 A1 A2 A3 A4 A5
A000 A002
A001 A003 A004 A005
WF ON TRIP
GENERAL FAULT UNDERLOAD REMOTE (LOCAL) EMG STOP
NO:0
NO:1
NO:2
NO:3
NO:4
NO:5
NC:0
NC:1
NC:2
NC:3
NC:4
NC:5
C:0
C:1
C:2
C:3
C:4
C:5
21
F1
22/16.3
X21 1 2 3 4 5 6 7 8 9 10 11 12 13 14
WC03
34x1.5
WF
WF ON GENERAL FAULT TPH DEVIATION MATERIAL STARVATION REMOTE MODE SEL EMG STOP FEEDBACK
TRIP
PLC/DCS
(CUSTOMER)
90.18737-WF-012
PROJECT : SHEET : 9
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
DIGITAL OUTPUT CARD 1
=A2-U3-U2.7-X7:11
/5
U1.5
15
10
9
DB-15(M)
U2
A6 A7 A8 A9 A10 A11
/7.2
A6 A7 A8 A9 A10 A11
NO:10
NO:11
NC:10
NC:11
NO:6
NO:7
NO:8
NO:9
NC:6
NC:7
NC:8
NC:9
C:10
C:11
C:6
C:7
C:8
C:9
2.8 / P1.3
110V AC
2.8 / N1.3
X21 15 16 17 18 19 20 21 22
X10 5
WC03
34x1.5
WC 05
12x1.5
LP2 LCS
X14 7 INT/DEINT MODE SEL. TOTALISER PULSE O/P VOL. MODE SEL. GRAV MODE SEL.
1
2 1
L1
2
90.18737-WF-012
PROJECT : SHEET : 10
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
/5 DIGITAL INPUT CARD 2
=A2-U3-U2.7-X8:15
U1.8
10
3
DB-15(F)
P1:1
/12.1
3
E0 E1 E2 E3 E4 E5
/13.2
/14.2
E1
E0 E2
E3 E4 E5
24P
24P
24P
24P
24P
24P
E0
E1
E2
E3
E4
E5
U6 P C O P C O P C O P C O P C O P C O
RL1 RL2 RL3 RL4 RL5 RL6
RELAY BOARD
110VAC
RL1 RL2 RL3 8CH/1CO RL4 RL5 RL6
WC05
12x1.5
X14 8 9 10 11 12 13
3 3 1 1
110N2 / 6.12 S1 S2 S3 S4
LOC/REM START STOP EMG OFF
110P2 / 6.12 4 4 2 2
90.18737-WF-012
PROJECT : SHEET : 11
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1 U1.8
GDC
DIGITAL INPUT CARD 2
=A2-U3-U2.7-X8:8
/5
11
2
6
DB-15(F)
U8
E6 E7 E8 E9 E10 E11
/11.1
E6 E7 E8 E9 E10 E11
E6 E7 E8 E9 E10 E11
E10
E11
24P
24P
24P
24P
24P
24P
E6
E7
E8
E9
90.18737-WF-012
PROJECT : SHEET : 12
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
DIGITAL OUTPUT CARD 2
=A2-U3-U2.7-X7:3
/5
U1.8
6
DB-15(M)
U8
A0 A1 A2 A3 A4 A5
/11.1
A0 A1 A2 A3 A4 A5
A000
A001 A002 A003 A004 A005
NO:0
NO:1
NO:2
NO:3
NO:4
NO:5
NC:0
NC:1
NC:2
NC:3
NC:4
NC:5
C:0
C:1
C:2
C:3
C:4
C:5
X21 23 24 25 26 27 28 29 30 31 32
WC03
34x1.5
FEEDER HEALTHY READY TO START BSS O/P LOCAL MODE SEL ZSS O/P
PLC/DCS
(CUSTOMER)
90.18737-WF-012
PROJECT : SHEET : 13
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
U1
GDC
DIGITAL OUTPUT CARD 2
=A2-U3-U2.7-X7:11
/5
U1.8
15
10
9
DB-15(M)
U8
A6 A7 A8 A9 A10 A11
/11.1
A6 A7 A8 A9 A10 A11
NO:10
NO:11
NC:10
NC:11
NO:6
NO:7
NO:8
NO:9
NC:6
NC:7
NC:8
NC:9
C:10
C:11
C:6
C:7
C:8
C:9
90.18737-WF-012
PROJECT : SHEET : 14
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TACHO I/P
SUPPLY +
SUPPLY +
SIGNAL +
SUPPLY -
SIGNAL -
GROUND
SENSE +
SENSE -
FREE
FREE
X15 1 5 4 2 6 8 9 3 7 X16 1 2
X11 5 2 7 3 4 6 1 X11 8 9 10
WCS03
6x0.75 mm²
WCS04
2x0.75
JB1
X15 5 2 11 1 3 12 4 8 7 10 9 6 13 14 15
SH
WCS02
/15.3
2x0.35
WCS01-1 WCS01-2
4x0.35 4x0.35
A C
A C TH
LC1
LC2
LOADCELL
B D
TACHO
B D
FIELD
90.18737-WF-012
PROJECT : SHEET : 15
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
415 V/50Hz
U1.2
1 3 5
13 21 INVERTER MODBUS
COMMUNICATION
F1 14 22
4-6 Amps (T-)
/8.3 /9.13 (T+)
X2.1 X2.2 SH
I>> I>> I>>
2 4 6
+24V GND DCOM DI1 DI2 DI3 DI4 DI5 DI6 SRC B A AGND SCR
-U4
2.2 KW U1 V1 W1 PE X1.10 X1.11 X1.12 X1.13 X1.14 X1.15 X1.16 X1.17 X1.18 X3.28 X3.29 X3.30 X3.31 X3.32
ON
S1
ON
ACS550-01-05A4-4
ON
U2 V2 W2 PE X1.4 X1.5 X1.6 X1.7 X1.9 X1.8 X1.9 X1.19 X1.20 X1.21 X1.22 X1.23 X1.24 X1.25 X1.26 X1.27
+10V AI2 AGND AO1 AGND AO2 AGND RO1C RO1A RO1B RO2C RO2A RO2B RO3C RO3A RO3B
/11.10/
L2 U V W
150uH / 15 AMPS
U1 V1 W1
X13 4 5 6 E
WP02
4x4 mm² NOTE:
TERMINAL
MAX CABLE DISTANCE BETWEEN VFD PANEL & RESPECTIVE
1 2 3 E
BOX MOTOR CAN BE 150 MTRS
M1 M
3~
M1
WF MOTOR
2.2 KW,4 POLE
1500 RPM,4.4 A
90.18737-WF-012
PROJECT : SHEET : 16
90.18737 - 012-EE16-R0
CONSULTANT : START DATE DRAWN BY OF : 15
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/14/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CABLE OVERVIEW
TOTAL USED CROSS-SECTION NO OF
CABLE NAME SOURCE (FROM) TARGET (TO) CABLE TYPE VOLTAGE CONDUCTORS CONDUCTORS (SQ MM) RUNS REMARKS SCOPE OF CABLE PAGE NO.
=A2-WC01 =A2-JB1-X15 =A2-FIELD (YY) UNARMOURED 110V AC 2 2 1.5 1 BELTSWAY SW (LEFT) FPIL =A2/7.3
=A2-WC02 =A2-JB1-X15 =A2-FIELD (YY) UNARMOURED 110V AC 2 2 1.5 1 BELT SWAY SW (RIGHT) FPIL =A2/7.4
=A2-WC03 =A2-X21 =A2-PLC/DCS (YWY) ARMOURED 220 VAC 34 32 1.5 1 DIGITAL INPUT TO PLC CUSTOMER =A2/9.2
=A2-WC04 =A2-X12 =A2-PLC/DCS (YWY) ARMOURED 110V AC 6 6 1.5 1 DIGITAL INPUT TO WF GDC CUSTOMER =A2/7.8
=A2-WC05 =A2-LCS-X14 =A2-X10 (YWY) ARMOURED 110V AC 12 9 1.5 1 CONTROLS CUSTOMER =A2/7.1
=A2-WC06 =A2-JB1-X15 =A2-FIELD (YY) UNARMOURED 110V AC 2 2 1.5 1 ZERO SPEED SW FPIL =A2/7.1
=A2-WC07 =A2-JB1-X15 =A2-LCS-X14 (YWY) ARMOURED 110V AC 6 4 1.5 1 ZSS, BSS,FLAP TYPE FPIL =A2/7.1
=A2-WCS01-1 =A2-JB1-X15 =A2-FIELD-LC1 (YY) UNARMOURED 12V 4 4 0.35 1 LOADCELL-1 FPIL =A2/15.3
=A2-WCS01-2 =A2-JB1-X15 =A2-FIELD-LC2 (YY) UNARMOURED 12V 4 4 0.35 1 LOADCELL-2 FPIL =A2/15.7
=A2-WCS02 =A2-JB1-X15 =A2-FIELD-TH (YY) UNARMOURED 12V DC 2 2 0.35 1 TACHO FPIL =A2/15.10
=A2-WCS03 =A2-JB1-X15 =A2-X11 (YWY) ARMOURED 12V DC 6 6 0.75 1 LOADCELL CUSTOMER =A2/15.3
=A2-WCS04 =A2-JB1-X15 =A2-X11 (YWY) ARMOURED 12V DC 2 2 0.75 1 TACHO CUSTOMER =A2/15.10
=A2-WCS05 =A2-X9 =A2-PLC/DCS (YWY) ARMOURED 4-20mA 2 2 0.75 1 4-20mA O/P α ACTUAL FEEDRATE CUSTOMER =A2/6.8
=A2-WCS06 =A2-X9 =A2-PLC/DCS (YWY) ARMOURED 4-20mA 2 2 0.75 1 4-20mA I/P α SET POINT CUSTOMER =A2/6.2
=A2-WCS07 =A2-LCS-X41 =A2-X22 (YWY) ARMOURED 4-20mA 2 2 0.75 1 FEEDRATE INDICATOR CUSTOMER =A2/6.13
=A2-WCS08 =A2-X4-X4 =A2-PLC/DCS (YWY) ARMOURED ----- 2 2 0.75 1 PROFIBUS COMMUNICATION CUSTOMER =A2/5.7
=A2-WCS11 =A2-LCS-X41 =A2-X22 (YWY) ARMOURED 0-10V 3 3 0.75 1 LOCAL SETPOINT CUSTOMER =A2/6.5
=A2-WP01 =A2-X13 =A2-MCC (YWY) ARMOURED 415V AC 3 3 4 1 MCC SUPPLY CUSTOMER =A2/2.1
(YWY) - ARMOURED COPPER CABLE (YY) - UNARMOURED COPPER CABLE (*) - POTENTIAL FREE (AYWY) - ARMOURED ALUMINIUM CABLE (AYY) - UNARMOURED ALUMINIUM CABLE
90.18737-WF-012
PROJECT : SHEET : 1
90.18737 - 012-EE04-R0
CONSULTANT : START DATE DRAWN BY OF : 2
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CABLE OVERVIEW
TOTAL USED CROSS-SECTION NO OF
CABLE NAME SOURCE (FROM) TARGET (TO) CABLE TYPE VOLTAGE CONDUCTORS CONDUCTORS (SQ MM) RUNS REMARKS SCOPE OF CABLE PAGE NO.
=A2-WP04 =A2-X13 =A2-UPS (YWY) ARMOURED 110V AC 2 2 2.5 1 UPS CUSTOMER =A2/3.1
(YWY) - ARMOURED COPPER CABLE (YY) - UNARMOURED COPPER CABLE (*) - POTENTIAL FREE (AYWY) - ARMOURED ALUMINIUM CABLE (AYY) - UNARMOURED ALUMINIUM CABLE
90.18737-WF-012
PROJECT : SHEET : 2
90.18737 - 012-EE04-R0
CONSULTANT : START DATE DRAWN BY OF : 2
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WCS08
Strip
Cable name
Cable name
=A2+-X4-X4
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
90.18737-WF-012
PROJECT : SHEET : 1
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WCS05
-WCS06
Strip
Cable name
Cable name
=A2+-X9
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
1 /6.2
= 6 /6.9
90.18737-WF-012
PROJECT : SHEET : 2
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WC05
Strip
Cable name
Cable name
=A2+-X10
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
-U7-RL1 COM
-LP2 1
90.18737-WF-012
PROJECT : SHEET : 3
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WCS04
-WCS03
Strip
Cable name
Cable name
=A2+-X11
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 10 /15.11
90.18737-WF-012
PROJECT : SHEET : 4
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WC04
Strip
Cable name
Cable name
=A2+-X12
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
90.18737-WF-012
PROJECT : SHEET : 5
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WP04
-WP02
-WP01
Strip
Cable name
Cable name
=A2+-X13
(YWY) ARMOURED
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
POWER SUPPLY 415 V AC ±10% 50HZ ±5% 3ø SUPPLY 1 -MCC R 1 -Q1 1 /2.1
90.18737-WF-012
PROJECT : SHEET : 6
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/25/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WC07
-WC05
Strip
Cable name
Cable name
=A2+-LCS-X14
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
220P 2 /7.2
= 4 /7.2
-LCS-S1 4 8 /11.1
-LCS-D1 20
-LCS-D1 19 9 /11.1
90.18737-WF-012
PROJECT : SHEET : 7
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WC02
-WC01
-WC06
-WCS02
-WCS01-2
-WCS01-1
-WCS03
-WCS02
-WCS04
-WC07
Strip
Cable name
Cable name
=A2+-JB1-X15
(YY) UNARMOURED
(YY) UNARMOURED
(YY) UNARMOURED
(YY) UNARMOURED
(YY) UNARMOURED
(YY) UNARMOURED
(YWY) ARMOURED
(YY) UNARMOURED
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 1 -FIELD-LC2 A 7 /15.7
= 4 -FIELD-LC2 B 8 /15.7
= 2 -FIELD-LC2 C 9 /15.9
= 3 -FIELD-LC2 D 10 /15.8
= 15 /15.11
= 17 -LCS-X14 3 /7.2
= -FIELD 20 /7.4
= -FIELD 21 /7.4
90.18737-WF-012
PROJECT : SHEET : 8
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WC03
Strip
Cable name
Cable name
=A2+-X21
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
90.18737-WF-012
PROJECT : SHEET : 9
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-WCS11
-WCS07
Strip
Cable name
Cable name
=A2+-X22
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 3 /6.14
= 7 /6.6
90.18737-WF-012
PROJECT : SHEET : 10
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
TERMINAL DIAGRAM
-LCS-WCSF
-WCS07
-LCS-WCSD
-WCS11
Strip
Cable name
Cable name
=A2+-LCS-X41
(YWY) ARMOURED
(YWY) ARMOURED
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 3 /6.14
= 7 /6.6
90.18737-WF-012
PROJECT : SHEET : 11
90.18737 - 012-EE17-R0
CONSULTANT : START DATE DRAWN BY OF : 11
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 8/17/2018 HAP-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
BILL OF MATERIALS
LEGEND QTY. DESIGNATION GENERAL SPECIFICATIONS PART NO. ERP PART NO. MANUFACTURER PAGE NO.
=A2-F1 1 MOTOR PROTECTION CIRCUIT BREAKER 4-6 AMPS 3VU13 40-1MK00 805005050000 SIEMENS =A2/16.2
=A2-Fb 1 MINIATURE CIRCUIT BREAKER 1.0 AMP-2P 5SL62017RC 8030010E0100 SIEMENS =A2/2.12
=A2-Fc 1 MINIATURE CIRCUIT BREAKER 1.0 AMP-2P 5SL62017RC 8030010E0100 SIEMENS =A2/2.7
=A2-HMI 1 7" TOUCH SCREEN DISPLAY 24V DC HMI WITH CABLE 80Z003002200 FPIL =A2/5.6
=A2-LCS-D1 1 DIGITAL PANEL METER 85 TO 270V AC - 4 (DIGIT) (TPH) PIC101N C05096040700 SELECTRON =A2/6.12
=A2-LCS-L1 1 LED LAMP 110V AC - RED 3SB52 85-6HC02 80200G130000 SIEMENS =A2/10.3
=A2-LCS-S1 1 MODULAR SELECTOR ACTUATORS 2 POSITION SELECTOR SW. (BLACK) 3SB50 00-2AB01 50G0060A0100 SIEMENS =A2/11.2
=A2-LCS-S2 1 MODULAR PUSH BUTTON ACTUATORS PUSH BUTTON (GREEN) WITH NO CONTACT BLOCK 3SB50 00-0AE01+3SB54 00-0B 50G005070100 SIEMENS =A2/11.4
=A2-LCS-S3 1 MODULAR PUSH BUTTON ACTUATORS PUSH BUTTON (RED)WITH NO CONTACT BLOCK 3SB50 00-0AC01+3SB54 00-0B 50G005080100 SIEMENS =A2/11.7
=A2-LCS-S4 1 MUSHROOM ACTUATORS EMERGENCY STOP (RED) 3SB52 03-0UC01 50G002090100 SIEMENS =A2/11.9
=A2-LP1 1 LED LAMP 110V AC - RED 3SB52 85-6HC02 80200G130000 SIEMENS =A2/2.5
=A2-LP2 1 LED LAMP 110V AC - AMBER 3SB52 85-6HL02 80200I140000 SIEMENS =A2/10.2
=A2-LP3 1 LED LAMP 110V AC - RED 3SB52 85-6HC02 80200G130000 SIEMENS =A2/3.2
=A2-S1 1 SURFACE MOULED ON / OFF SW. 5 AMPS ------- 50G0090C0200 ANCHOR =A2/2.11
90.18737-WF-012
PROJECT : SHEET : 1
90.18737 - 012-EE03-R0
CONSULTANT : START DATE DRAWN BY OF : 2
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 1/11/2019 VIM-IN TOTAL : 40
1 2 3 4 5 6 7 8 9 10 11 12 13 14
BILL OF MATERIALS
LEGEND QTY. DESIGNATION GENERAL SPECIFICATIONS PART NO. ERP PART NO. MANUFACTURER PAGE NO.
=A2-S2 1 DOOR LIMIT SWITCH 400V AC, 6A 3SE5250-0BC05 80A026460000 SIEMENS =A2/2.13
=A2-TX1 1 TRANSFORMER I/P 415V AC, O/P 220V AC @ 1 AMP, 110V AC @ 1 AMP------- 80F00K0D0200 OM INDUSTRIES =A2/2.4
=A2-U1 1 GRAVIMETRIC DOSING CONTROLLER 24V DC GDC (LCT-BASIC) 5000I00D0L00 FPIL =A2/5
=A2-U2 1 SMALL RELAY BOARD 12 I/O & 12 O/P RL I/O 5000P00H0P00 FPIL =A2/7.2
=A2-U3 1 POWER SUPPLY Input: AC 100-240V, Output 24VDC 2.5A S8VK - C06024 C030K1500100 OMRON =A2/3.7
=A2-U5 1 RELAY BOARD 4 CHANNEL - 1 CHANGE OVER 110V AC - 4CH/1CO 80900D0E0B00 FPIL =A2/7.8
=A2-U6 1 RELAY BOARD 8 CHANNEL - 1 CHANGE OVER 110V AC - 8CH/1CO 809005070100 FPIL =A2/11.2
=A2-U7 1 RELAY BOARD 4 CHANNEL - 1 CHANGE OVER 110V AC - 4CH/1CO 80900D0E0B00 FPIL =A2/7.1
=A2-U8 1 SMALL RELAY BOARD 12 I/O & 12 O/P RL I/O 5000P00H0P00 FPIL =A2/11.1
=A2-X4 1 PROFIBUS CONNECTOR LED TYPE - EASYCONN - PB 0° 972-0DP30 E0J050060400 VIPA =A2/5.6
90.18737-WF-012
PROJECT : SHEET : 2
90.18737 - 012-EE03-R0
CONSULTANT : START DATE DRAWN BY OF : 2
P.O. NO. : K/8001062PO180700145 DTD.17-07-2018 1/11/2019 VIM-IN TOTAL : 40
MECHANICAL GAD
MECHANICAL GAD