Electrical Data
Insulation System Class H
Stator Winding Double Layer Concentric
Winding Pitch Two Thirds
Winding Leads 4
Winding Number 05 / 705
Number of Poles 4
IP Rating IP23
RFI Suppression EN 61000-6-2 & EN 61000-6-4, refer to factory for others
Waveform Distortion NO LOAD < 2% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
Short Circuit Ratio 1/Xd
Steady State X/R Ratio 3.6
50 Hz
Telephone Interference THF<2%
Voltage Series 230 230
Power Factor 0.8 1.0
kVA Base Rating (Class H) 25 27
Saturated Values in Per Unit at Base Ratings and Voltages
Xd Dir. Axis Synchronous 1.174 1.268
X'd Dir. Axis Transient 0.165 0.178
X''d Dir. Axis Subtransient 0.127 0.137
Xq Quad. Axis Reactance 1.001 1.081
X''q Quad. Axis Subtransient 0.154 0.166
XL Stator Leakage Reactance 0.743 0.802
X2 Negative Sequence Reactance 0.212 0.229
X0 Zero Sequence Reactance 0.071 0.077
Unsaturated Values in Per Unit at Base Ratings and Voltages
Xd Dir. Axis Synchronous 1.544 1.667
X'd Dir. Axis Transient 0.190 0.205
X''d Dir. Axis Subtransient 0.149 0.160
Xq Quad. Axis Reactance 1.031 1.114
X''q Quad. Axis Subtransient 0.185 0.200
XL Stator Leakage Reactance 0.840 0.907
X2 Negative Sequence Reactance 0.254 0.275
X0 Zero Sequence Reactance 0.083 0.090
Time Constants (Seconds)
T’d TRANSIENT TIME CONST. 0.037
T’’d SUB-TRANSTIME CONST. 0.002
T’do O.C. FIELD TIME CONST. 0.259
Ta ARMATURE TIME CONST. 0.014
Page 2 A055R778_RevD_29.08.2017