YN1M302135 - ZAC - 400 KV Bus Coupler
YN1M302135 - ZAC - 400 KV Bus Coupler
Description
Reviewed by PAN
400kV Bus Coupler Bay Relay Setting Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
Contents
Note: ....................................................................................................................................................... 2
Revision Note .......................................................................................................................................... 2
Equipment Details: .................................................................................................................................. 2
Protection Details: ................................................................................................................................... 2
1. Non – Directional Over-current and Earth Fault Protection (51 / 51N) / REF615 ............................... 3
Non – Directional Over– Current Protection:......................................................................................... 3
Non – Directional Earth – Fault Protection: ........................................................................................... 4
2. Breaker Failure Protection (50BF) / REC670 .................................................................................... 5
Note:
1. Instrument transformers ratios shall be verified at site, before setting the analog channels during
Commissioning.
2. The O/C & E/F settings given here are only provisional. Based on the customer practice and/or the
operating time delay adopted in downstream / upstream relays, the settings should be corrected at site
to ensure proper coordination.
Revision Note
Equipment Details:
Protection Details:
Description
Reviewed by PAN
400kV Bus Coupler Bay Relay Setting Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
1. Non – Directional Over-current and Earth Fault Protection (51 / 51N) / REF615
The directional over – current protection setting is at set at 120 % of maximum rated CT current, therefore
the pick-up is set for 2400 A.
The description of the parameters in the relay for directional over-current protection is as given below
1
TMS and pickup is set are only provisional in nature. TMS of 0.21 is selected assuming a trip time of 1
second for a fault of 10 kA. Actual TMS and pick-up to be adopted shall be co-ordinated downstream and
upstream relays
Description
Reviewed by PAN
400kV Bus Coupler Bay Relay Setting Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
IEC Normal characteristics may to be adopted for the protection with reset being instantaneous.
The description of the parameters in the relay for directional earth-fault protection (51N) as given below.
2
TMS and pickup is set are only provisional in nature. TMS of 0.38 is selected assuming a trip time of 1
seconds for a fault of 5340 A. Actual TMS and pick-up to be adopted shall be co-ordinated downstream
and upstream relays
Description
Reviewed by PAN
400kV Bus Coupler Bay Relay Setting Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
A snap shot showing the sequence of operation for breaker failure protection is provided below. Please
refer to REC670 application manual for detailed explanation
The description of the parameters in the relay for the breaker failure protection is as given below.
Description
Reviewed by PAN
400kV Bus Coupler Bay Relay Setting Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
Description
Reviewed by PAN
400kV Bus Coupler Bay Relay Setting Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0