Professional Documents
Culture Documents
YN1M302135 - ZAE - 400 KV GT
YN1M302135 - ZAE - 400 KV GT
Description
Reviewed by PAN 400kV Generator Transformer Bay Relay Setting
Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
Contents
Note: ....................................................................................................................................................... 2
Revision Note .......................................................................................................................................... 2
Equipment Details: .................................................................................................................................. 2
Protection Details: ................................................................................................................................... 3
1. High Impedance Overhang Differential Protection (87OH) / REB650 ................................................ 3
2. Non – Directional Over-current and Earth Fault Protection (51 / 51N) / REF615 ............................... 4
Non – Directional Over– Current Protection:......................................................................................... 4
Non – Directional Earth – Fault Protection: ........................................................................................... 5
3. Breaker Failure Protection (50BF) / REC670 .................................................................................... 6
Note:
1. Instrument transformers ratios shall be verified at site, before setting the analog channels during
Commissioning.
2. The O/C & E/F settings given here are only provisional. Based on the customer practice and/or the
operating time delay adopted in downstream / upstream relays, the settings should be corrected at site
to ensure proper coordination.
3. Setting is applicable to GT 1 (Bay 402) and GT 2 (Bay 406)
Revision Note
Equipment Details:
Description
Reviewed by PAN 400kV Generator Transformer Bay Relay Setting
Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
Protection Details:
Maximum through fault current I fHV at Rated Current at Tap 17 / percentage Impedance at Tap
=
Tap 17 of GT 17
= 1225.36 / 0.1588 A
= 7716.37 A
Description
Reviewed by PAN 400kV Generator Transformer Bay Relay Setting
Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
The description of parameters for high impedance differential function is shown below.
2. Non – Directional Over-current and Earth Fault Protection (51 / 51N) / REF615
The directional over – current protection setting is at set at 120 % of maximum load current. As per the
inputs provided, the maximum load current is 1072.19 A, therefore the pick-up is set for 1286.63 A.
Description
Reviewed by PAN 400kV Generator Transformer Bay Relay Setting
Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
The description of the parameters in the relay for directional over-current protection is as given below
The directional earth fault protection is set to at 20% of rated load current.
IEC Normal characteristics may to be adopted for the protection with reset being instantaneous.
1
TMS and pickup is set are only provisional in nature. TMS of 0.3 is selected assuming a trip time of 1.
seconds for a fault of 10 kA. Actual TMS and pick-up to be adopted shall be co-ordinated downstream and
upstream relays
Description
Reviewed by PAN 400kV Generator Transformer Bay Relay Setting
Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
The description of the parameters in the relay for directional earth-fault protection (51N) as given below.
A snap shot showing the sequence of operation for breaker failure protection is provided below. Please
refer to REC670 application manual for detailed explanation
2
TMS and pickup is set are only provisional in nature. TMS of 0.51 is selected assuming a trip time of 1.1
seconds for a fault of 5340 A. Actual TMS and pick-up to be adopted shall be co-ordinated downstream
and upstream relays
Description
Reviewed by PAN 400kV Generator Transformer Bay Relay Setting
Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0
The description of the parameters in the relay for the breaker failure protection is as given below.
Description
Reviewed by PAN 400kV Generator Transformer Bay Relay Setting
Calculation
Prepared by Order Ref Rev
PRAVEEN.A.N
3100044120 0