16122-Power Cable Rated 15kV Copper Tape Shielded
16122-Power Cable Rated 15kV Copper Tape Shielded
1.1 REFERENCE
1.2 GENERAL
This specification covers the requirements for single-conductor copper-tape shielded fire-
retardant cross linked polyethylene (XLPE) insulated power cable.
1.3 SUBMITTALS
A. Technical Brochures
B. Methodology for Testing of cable.
C. Calibration Certificates of testing equipment.
1.4 STANDARD
Unless otherwise specified herein, the cables shall be designed, manufactured and tested
to meet or exceed the requirements of the latest revision of the following industry
standards publications.
A. ANSI/ICEA S-97-682-2007, “standard for utility shielded power cables rated 5kV
through 46kV”.
C. AEIC CS8-07, “Specifications for Extruded Dielectric, Shielded Power cables rated
5kV through 46kV.”
E. ASTM B-5, standard specification for high conductivity tough pitch copper refinery
shapes.
A. Conductor shall be soft drawn, annealed uncoated copper as per ASTM B-3 and
compressed Class B concentric lay standard as per ASTM B-8.
B. There shall be no water in the stranded conductors when each end of the shipping
length is inspected for water conduit.
E. The conductor shield shall be easily removable from the conductor and the outer
surface of the extruded shield shall be firmly bonded to the overlaying insulation.
G. Insulation
H. Limitations:
I. Curing shall be of the dry process thru the use of nitrogen gas done “in-line” thru the
manufacturing process.
A. Place all wiring, in raceway of type or types indicated. Provide all required and
indicated accessories for proper installation of all wiring.
1.7 TESTS
END OF SECTION